www.midnitesolar.com Ph. 360-403-7207 Fax 360-691-6862. MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and AC coupled. Ryan, Technical Support Manager [email protected] 360-403-7207 XT151. www.midnitesolar.com Ph. 360-403-7207 Fax 360-691-6862. Off Grid. - PowerPoint PPT Presentation
26
MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and AC coupled. www.midnitesolar.com Ph. 360-403-7207 Fax 360-691-6862
Transcript
Page 1: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

MidNite Solar’s Pre wired solutions

for Off Grid, Battery based Grid tie and

AC coupled.www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 2: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Ryan, Technical Support [email protected] XT151

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 3: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

What type of system do I

need?

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

• Off Grid. • Battery Based Grid Tie.• AC Coupled.

All of MidNite Solar’s Pre Wired systems are fully customizable for

your needs

Page 4: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Off Grid

• Stand alone system• Will not sell back to the

utility• Various inverters available

for Off Grid (Some will do both)

• 120 or 120/240?

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 5: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Grid Tie With Battery Backup• Sells to the grid• Runs critical loads

during grid failure• Do you need 120vac

or 120/240vac• Some models support

generator input as well

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 6: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

AC Coupled

• Adds battery backup to a purely grid tie system.

• Adds some complexity to the system.

• Best suited for existing grid tie systems as an add on.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 7: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

• Growing market segment• Can be confusing!• Can be complicated!• Numerous ways to go• MidNite has taken most of

the mystique out of the equation

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

AC Coupled

Page 8: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

What is AC Coupled ?

AC Coupling is a controlled back feed to a battery based inverter A back feed is hooking up AC to the output of an inverter AC coupling is a synchronized back feed. The grid tie inverter shifts frequency to match the battery based inverter before connecting. This makes it ok to do.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 9: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

What is AC Coupled ?

Not all battery based sinewave inverters are capable of back feed.

Your choices in North America are:

SMA Sunny IslandOutback FX, VFX and

RadianMagnum PAE seriesSchneider XW series

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 10: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

• Magnum and OutBack inverters sense circuits that control charging are on the AC inputs not the output, therefore cannot control the charging

• These inverters charge wide open and cannot taper off.

• A relay is required to disconnect the GT

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

What is AC Coupled ?

Page 11: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

• SMA and Schneider use frequency shift to knock the GT inverter offline to stop the charging.

• The Sunny Island will control a Sunny Boy to do tapered charging.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

What is AC Coupled ?

Page 12: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Generators and AC Coupled

• Radian and the Schneider have 2 AC inputs so a generator can be added.

• Provisions must be added to disconnect the GT inverter when the generator runs or the GT will try to sell to the Inverter.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 13: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Sizing Of The Off Grid Inverter

• Outback, Magnum and Schneider have a 1:1 ratio limit.

• SMA has a 2:1 ratio

• The customer may not need all of the grid tie solar as part of the ac coupled.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 14: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Outback FX series

• 120 vac per single unit.• Either Grid tie or Off Grid

not both. Both AC couple.• Grid tie models (G series)

does not play well with generators.

• Smaller scale and expandable.

• 12,24 and 48VDC models available

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 15: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Quad Off Grid Outback Prewired

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 16: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Outback Radian

• Grid tie or Offgrid Supports both AC coupled as well

• 120/240 in a single unit• Has 2 AC inputs (2nd for

generator)• 8,000 watts per unit,

Stackable• 48VDC model• Requires relays for AC coupled

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 17: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Outback Radian

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 18: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Outback Radian

Page 19: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Magnum Energy

• 120vac and 120/240vac models (Only the 120/240 PAE should be used for AC coupled) *various wattage inverters available

• Stackable Vented only Off Grid only (AC coupled)

• 12, 24 and 48VDC models

Page 20: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Magnum Energy

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 21: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Magnum Energy

Page 22: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Magnum Energy

Page 23: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Xantrex XW

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

• Grid tie or Off grid. Supports both 120/240 in a single unit

• Has 2 AC inputs (2nd for generator)

• 4.5KW or 6KW units, Stackable

• 24 or 48VDC models

Page 24: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

SMA Sunny Island

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

• Grid tie or Offgrid. Supports both

• 120VAC• Single input but we offer an

automatic transfer switch for generator backup.

• 4.5KW or 6KW units, Stackable

• 48VDC

Page 25: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

SMA Sunny Island

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862

Page 26: MidNite Solar’s Pre wired solutions for Off Grid, Battery based Grid tie and  AC  coupled.

Ryan StankevitzMidNite Solar360-403-7207 XT [email protected]

www.midnitesolar.comPh. 360-403-7207 Fax 360-691-6862