Mike CundiffCommercial Regional Manager
Controls Integration and Training
Required Hardware
LonWorks BACnet
Operation: On/Off, Mode, Set Temperature, Fan Speed, and Air Flow Direction
Monitor: Status, Error Code, Error Unit Address, Filter Sign, and Malfunction Log
Prohibit: On/Off, Mode, Set Temperature, and Filter Sign
Emergency Stop
Note: All Points are for Indoor Units. There are no points for Outdoor Unit, BC Controller, or Central Controller
Programming Required
LonWorks
Mitsubishi: Make sure dipswitches are properly set on LMAP
BAS Contractor: Status, Error Code, Error Unit Address, Filter Sign, and Malfunction Log
Backup: Configuration of the LMAP is stored in permanent memory. Reconfiguration is done with dip switches. Configuration will not be lost unless cleared with dip switches.
Programming Required
BACnet
Mitsubishi: Initial BAC-HD150 setup using free, internet available software tool.
BAS Contractor: Status, Error Code, Error Unit Address, Filter Sign, and Malfunction Log
Backup: Configuration is kept in permanent memory. Reconfiguration is done with software and saved configuration file. Configuration will not be lost unless reconfigured with software tool.
Estimated Cost
Mitsubishi: Cost of BACnet or Lon gateway, etc.
BAS Contractor: Project Specific
Commissioning
Mitsubishi Controls: Installing contractor with factory authorized service personnel assistance.
BAS System: Project Commissioning Agent
Project Examples
Allied Health Bldg- LWTC Additional Schools:Tioga Library UW
• Tacoma, WA
• Siemens Integration
• Connected to UW campus
• 45 Zones
• Kirkland, WA
• Alerton Integration
• Controlled locally by campus facilities
• 280 Tons 85 Zones
• UW Savery Hall – JCI
• UW TransBldg – JCI
• UW Joy Bldg – Siemens
• Seattle Pacific U
• Carnation Elem – Alerton
• Tolt MS – CCI
• Cherry Valley Elem – Alerton
• Stillwater – Alerton
•Bremerton H.S.
• Bethel S.D.
• Sitka SD – Alerton
Software Updates and Backup
Software Updates: All updates will be made available for free on the www.mylinkdrive.com website with instructions and all relevant information. Updates will be able to be performed without needing special parts or software that are not available for free on our website.
Back-Ups: Backup configuration file can be saved by the staff in any place that is safe. Software to load the configuration file is available for free on the www.mylinkdrive.com website with instructions and all relevant information.
Mitsubishi Controls - Scheduling
Holiday Scheduling:
Up to 50 days per year, such as public holidays can be scheduled as days that are different than the weekly schedule up to 24 months into the future (including the current month).
5 seasonal weekly (Monday through Sunday) schedule settings are possible.
Non BMS - Programming
• Programming ability: On/Off, Mode, Fan Speed, Set Temp, Prohibits/Permits
• Daily / Weekly / Annual Schedule
• Weekly: 12 programs per day, one for each fan coil/group
• Annual schedule out 2 years
• 5 Patterns (Program Sequence)
Annual Schedule Web Browser Screen