+ All Categories
Home > Documents > Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to...

Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to...

Date post: 31-Mar-2018
Category:
Upload: doankhue
View: 223 times
Download: 2 times
Share this document with a friend
10
For more information about this book and other Solar PV products visit www.MikeHolt.com/solar Mike Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for SOLAR PV SYSTEMS Extracted From Mike Holt’s Illustrated Guide to Understanding NEC ® Requirements for Solar Photovoltaic Systems 11.29.11 Mike Holt Enterprises, Inc. 1.888.NEC.CODE www.MikeHolt.com [email protected] NEC ® , NFPA 70 ® , NFPA 70E ® and National Electrical Code ® are registered trademarks of the National Fire Protection Association. COPYRIGHT © 2011 Charles Michael Holt
Transcript
Page 1: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

For more information about this book and other Solar PV products visit www.MikeHolt.com/solar

Mike Holt’s Illustrated Guide to

Directory, Identification, Label, Marking, Plaque, and Sign Requirements for

SOLAR PV SYSTEMSExtracted From

Mike Holt’s Illustrated Guide to Understanding NEC ® Requirements for Solar Photovoltaic Systems

11.29.11

Mike Holt Enterprises, Inc.1.888.NEC.CODE • www.MikeHolt.com • [email protected]

NEC®, NFPA 70®, NFPA 70E® and National Electrical Code® are registered trademarks of the National Fire Protection Association.

COPYRIGHT © 2011 Charles Michael Holt

Page 2: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

ARTICLE

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 1

Solar Photovoltaic (PV) Systems690

690.4 Installation.

(B) Identification and Grouping. PV system conductors, both dc and ac, can be installed in the same raceways, outlet and junction boxes, or similar fittings with each other, but must be kept entirely indepen-dent of non-PV system wiring conductors. Figure 690–22

Part I. General

690.1 Scope.

Article 690 applies to photovoltaic (PV) electrical energy systems, array circuit(s), inverter(s), and charge controller(s) for PV systems, which may be interactive with other electrical power sources (elec-tric utility) or stand-alone with or without energy storage (batteries). Figures 690–1 and 690–2

IntroductIon to ArtIcle 690—SolAr PhotovoltAIc (Pv) SyStemSYou’ve seen, or maybe own, photocell-powered devices such as night lights, car coolers, and toys. These generally consist of a small solar panel and a small light or motor. Typically, these run on less than 10V dc and draw only a fraction of an ampere. These kinds of devices are very different from a system that can power a house or interconnect with a utility to offset a building’s energy consumption.

Consider the sheer size and weight of solar modules for providing electrical power to a building. You’re looking at mechanical and site selec-tion issues that may require specialized expertise. The value of these modules also means there are security issues to consider, which may require more than just installing locks. There are also civil and architectural issues to address.

In summary, these installations are complicated and require expertise in several non-electrical areas, which the NEC doesn’t address.

Article 690 focuses on reducing the electrical hazards that may arise from installing and operating a solar photovoltaic system, to the point where it can be considered safe for property and people. This article consists of eight Parts, but the general requirements of Chapters 1 through 4 apply to these installations, except as specifically modified by Article 690.

Figure 690–1

Figure 690–2

Page 3: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 2

Directory, Identification, Label, Marking, Plaque, and Sign Requirements for Solar PV Systems

Ex: Identification of different systems isn’t required where conductor identification is evident by spacing or arrangement.

(F) Circuit Routing. PV source and output conductors must be routed along building structural members (beams, rafters, trusses, and columns) where the location of those structural members can be determined by observation. The location of PV source and output con-ductors imbedded in built-up, laminate, or membrane roofing mate-rials in areas not covered by PV modules and associated equipment must be clearly marked.

(H) Multiple Inverters. Where multiple utility-interactive inverters are located remote from each other, a directory is required at each dc PV system disconnecting means, at each ac disconnecting means, and at the main service disconnecting means showing the location of all ac and dc PV system disconnecting means in the building/structure.

Ex: A directory isn’t required where all PV system disconnecting means are grouped at the service disconnecting means.

690.5 Ground-Fault Protection. PV systems must have ground-fault protection to reduce fire hazards. Figure 690–27

(C) Labels and Markings. A warning label must be on the utility-interactive inverter stating the following: Figure 690–28

WarnInG eleCtrIC SHOCK HaZarD—IF a GrOUnD FaUlt IS InDICateD, nOrMallY GrOUnDeD

COnDUCtOrS MaY Be UnGrOUnDeD anD enerGIZeD

PV system conductors must be identified by separate color coding, marking tape, tagging, or other approved means and grouped as follows:

(1) PV Source Circuits. Identified at points of termination, connec-tion, and splices.

(2) PV Output and Inverter Circuits. Identified at points of termina-tion, connection, and splices.

(3) Multiple Systems. Conductors of each system must be identified at termination, connection, and splice points. Figure 690–23

Figure 690–22

Figure 690–23

Figure 690–27

Page 4: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 3

Directory, Identification, Label, Marking, Plaque, and Sign Requirements for Solar PV Systems

(4) A permanent plaque identifying the locations of the service and inverter ac disconnect(s) must be placed at service and inverter ac disconnect(s) locations.

690.15 PV equipment Disconnect. PV equipment must have a disconnecting means that opens all ungrounded circuit con-ductors from all sources of power. Where equipment is energized from more than one source, such as an inverter supplied by dc cur-rent input from the array and ac current output to the utility source, a disconnecting means is required for each and both dc and ac dis-connects must be grouped together and each permanently marked to identify their purpose. Figure 690–73

CaUtIOn: The label must resist the environment for 25 to 40 years of system use and be suitable for the environment and be installed so as not to void equipment listing [110.3(B)]. When plastic is used, it should not be placed in direct sun-light, unless specifically manufactured as sunlight resistant; a metallic engraved sign would be best.

PArt II. cIrcuIt requIrementS690.10 Stand-alone Systems.

(C) Single 120V Supply. The battery based inverter output is per-mitted to supply a 120V single-phase, 3-wire, 120/240V distribution panel marked with the following words or equivalent:

WarnInG — SInGle 120-VOlt SUPPlY DO nOt COnneCt MUltIWIre BranCH CIrCUItS

PArt III. dISconnectIng meAnS690.14 PV System Disconnecting Means.

(C) Requirements for Disconnecting Means. The PV system discon-nect must open all ungrounded conductors.

(2) Marking. Each PV system disconnect must be permanently marked to identify it as the PV system disconnect. Figure 690–71

(D) Inverter Disconnects. Where utility-interactive inverters are not readily accessible, dc and ac circuit disconnecting means is requires as follows:

Figure 690–28 Figure 690–71

Figure 690–73

Page 5: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 4

Directory, Identification, Label, Marking, Plaque, and Sign Requirements for Solar PV Systems

690.17 Disconnect requirement. Disconnects must be a manually operable switch or circuit breaker meeting all of the following:

(4)For dc disconnects where line and load terminals will be energized when the switch is in the open position, a warning sign must be placed on or adjacent to the disconnect such as: Figure 690–78

WarnInG—eleCtrIC SHOCK HaZarD DO nOt tOUCH terMInalS—terMInalS On BOtH tHe lIne anD lOaD

SIDeS MaY Be enerGIZeD In tHe OPen POSItIOn

PArt Iv. WIrIng methodS690.31 Wiring Methods.

(E) Circuits Inside Buildings/Structures.

(3) Marking/Labeling. Wiring methods and enclosures containing PV dc conductors must be marked “Photovoltaic Power Source” by labels or other approved permanent marking means. Figure 690–87

(4) Marking /Labeling Methods. The marking required by 690.31(E)(3) must be visible after installation and appear on every section of the wiring system separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels/marking must not be more than 10 ft and labels must be suitable for the environment. Figure 690–88

690.35 Ungrounded Systems. PV power systems are per-mitted to be ungrounded if they comply with the following:

690.16 Disconnecting Means for Fuses

(B) PV Output Circuit. A disconnecting means must be provided for PV output circuits. Where the disconnecting means is more than 6 ft from the fuse, a directory indicating the location of the fuse discon-nect must be at the fuse location. Figure 690–75

Nonload-break fuse pullouts or holders must be marked “Do not open under load. Figure 690–76

Figure 690–75

Figure 690–76

Figure 690–78

Page 6: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 5

Directory, Identification, Label, Marking, Plaque, and Sign Requirements for Solar PV Systems

(1) Rated maximum power-point current (Imp x number of combined paralleled source circuits).

(2) Rated maximum power-point voltage (Vmp x number of modules in each source circuit).

(3) Maximum system voltage (Voc).

Note: See 690.7(A) for maximum photovoltaic system voltage calculation.

(4) Short-Circuit Current (Isc x 1.25).

Note: See 690.8(A) for maximum circuit current calculation.

Author’s Comment: The values for maximum power-point cur-rent (Imp), maximum power-point voltage (Vmp), open circuit voltage (Voc), and short-circuit current (Isc) are indicated on the manufactures specifications sheet for the modules used for the system.

(5) Maximum rated output current of the charge controller (if installed)

Example: Determine the DC PV power source information needed for the PV power source label based on the following: array consists of twenty-three 200W modules, 11.05 Imp, 18.10 Vmp, 22.60 Voc (at 7°C), and 11.80 Isc. Figure 690–111

(1) Rated Maximum Power-Point Current (Imp)Imp = Module Rated Imp × Number of Strings in Parallel Imp = 11.05A × 1Imp = 11.05A

(2) Rated Maximum Power-Point Voltage (Vmp)Vmp = Module Vmp × Number of Modules per String Vmp = 18.10V × 23 = 416V

(3) Maximum System Voltage (Voc)PV Voc = Module Voc × Table 690.7 Correction Factor × # Modules per StringPV Voc = 22.60 Voc × 1.14 × 23 modulesPV Voc = 593V

(4) Short-Circuit Current (Isc)Isc = Module Isc × 1.25 × Number of Strings in ParallelIsc = (11.80A × 1.25) × 1 Isc = 14.75A

(F) Labeled. The PV power source must be labeled with the following warning at every junction box and termination point:

WarnInG—eleCtrIC SHOCK HaZarD tHe DC COnDUCtOrS OF tHIS PHOtOVOltaIC SYSteM are UnGrOUnDeD anD MaY Be enerGIZeD.

PArt vI. mArkIng690.53 Direct-Current PV Power Source. A permanent label must be applied by the installer at the PV dc disconnect indicating:

Figure 690–87

Figure 690–88

Page 7: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 6

Directory, Identification, Label, Marking, Plaque, and Sign Requirements for Solar PV Systems

Example: What’s the rated ac output current for a utility-inter-active inverter rated 5 kW at 120/240V supplied by twenty-three dc modules each rated 200W?

Inverter Rated ac Output Current = Inverter kW rating/Nominal ac VoltageInverter Rated ac Output Current = 5,000W/240VInverter Rated ac output current = 20.83A at 240V

Author’s Comment: Panelboards containing ac inverter circuit breakers must be field-marked to indicate the presence of multi-ple ac power sources [705.12(D)(4)].

690.56 Identification of Power Sources.

(A) Facilities with Stand-Alone Systems. Any building/struc-ture with a stand-alone PV system (not connected to a utility power) must have a permanent plaque placed on the exterior of the building/structure at a readily visible location that is acceptable to the author-ity having jurisdiction. The plaque must indicate the location of the stand-alone PV system disconnecting means and that the structure contains a stand-alone electrical power system.

(B) Facilities with Utility Power and PV System. Buildings/struc-tures containing both utility power and a PV system must have a per-manent plaque placed at the service and PV system ac disconnecting means identifying the location of the other system if not located at the same location. Figure 690–113

690.54 Interactive System. The point of connection of the PV system to ac power must be marked with the rated ac output current and nominal operating ac voltage. Figure 690–112

Figure 690–113

Figure 690–111

Figure 690–112

Page 8: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 7

ARTICLE

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 7

Interconnected Electric Power Production Sources705

Note: Primary sources of electricity include a utility supply and on-site electric power sources like photovoltaic or wind powered systems.

705.10 Directory. A permanent plaque or directory denoting all electric power sources on or in the premises must be installed at each service equipment location and all interconnected electric power production sources.

705.12 Point of Connection.

(D) Load Side. Where distribution equipment is capable of supplying multiple branch circuits or feeders or both, the interconnecting pro-visions for the utility-interactive inverter(s) must comply with (D)(1) through (D)(7).

(4) Marking. Panelboards containing ac inverter circuit breakers must be field-marked to indicate the presence of multiple ac power sources such as: Figure 705-15

(7) Inverter Output Connection. Where distribution equipment is capable of supplying multiple branch circuits or feeders, the ac inverter circuit breaker must be located at the opposite end from the input feeder supply conductors. Figure 705-18

PArt I. generAl705.1 Scope. Article 705 covers the installation of electric power production sources (photovoltaic, wind, micro-hydro generators, etc) operating in parallel with a primary source(s) of electricity. Figure 705-1

IntroductIon to ArtIcle 705—Interconnected electrIc PoWer ProductIon SourceSAnytime there’s more than one source of power production at the same building or structure, safety issues arise. In cases where a power production source such as a generator is used strictly for standby power, the NEC requires transfer switches and other safety considerations as covered in Articles 700, 701, or 702 depending on whether the standby power is legally required or optional. When interactive electri-cal power production sources such as wind powered generators, solar photovoltaic systems, or fuel cells are present, there usually isn’t a transfer switch. In fact, it can be expected that there will be more than one source of electrical supply connected simultaneously. This can raise many questions regarding how to maintain a satisfactory level of safety when more than one power source is present.

Article 705 answers these and other questions related to power sources that operate in parallel with a primary source. Typically, a primary source is the utility supply, but it can be an on-site source instead.

Figure 705–1

Page 9: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

Directory, Identification, Label, Marking, Plaque, and Sign Requirements for Solar PV Systems

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 888.NEC.CODE (632.2633) 8

Where distribution equipment is capable of supplying multiple branch circuits or feeders, a permanent warning label on panelboard is required to warn that the inverter output connection circuit breaker must not be relocated: Figure 705-19

WarnInG—InVerter OUtPUt COnneCtIOn DO nOt relOCate CIrCUIt BreaKer

Figure 705–15

Figure 705–18

Figure 705–19

Page 10: Mike Holt’s Illustrated Guide to Directory, Identification ... Holt’s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for ... or

I n t r o d u c i n g

Mike Holt's Illustrated Guide toUnderstanding NEC® Requirements for

SOLAR PHOTOVOLTAIC SYSTEMS

For a limited time you can get your copy for 25% o� list price – use discount code PVPDF11

2011 SOLAR PHOTOVOLTAIC SYSTEMS ORDER FORMNAME TITLE

This brand new book and DVD program is an insightful guide to the sweeping changes in the NEC as it relates to the installation of PV systems of any size. This program explores the safety aspects of installation and the maintenance of PV systems. If you are a PV installer, Electrician, Inspector or Engineer this book will be an eye opener to the complexity of solar photovoltaic systems and the importance in understanding those NEC Rules that govern their installation.

25% OFF

COMPANY

ADDRESS

CITY

PHONE

E-MAIL ADDRESS

CREDIT CARD # EXP. DATE

3 OR 4 DIGIT SECURITY CODE ON FRONT OF AMEX OR BACK FOR ALL OTHERS

STATE ZIP

VISA MASTERCARD DISCOVER AMEX MONEY ORDER CHECK

DVD Program (includes book & 2 DVDs)

$

$

$49.60

PRICE QTY TOTAL

$168.00

Book List Price $62

List Price $210

FOR VOLUME DISCOUNTS, PLEASE CALL OUR OFFICEMail form to: 3604 Parkway Blvd., Suite 3, Leesburg, Florida 34748

Visit: www.MikeHolt.com • Call: 888.NEC.CODE (632.2633) • Fax: 352.360.0983

SUB-TOTAL $SALES TAX FLORIDA RESIDENTS ONLY ADD 6% $

Shipping (5% of total price) - Minimum $7.50 $TOTAL $

“...as for me and my house, we will serve the Lord” [Joshua 24:15]

MIKE HOLT Enterprises, Inc.TM


Recommended