Product Data Sheet 00813-0100-4360 Pressure-173 Model 1151 Model 1151 Alphaline ® Pressure Transmitters . Model 1151 PROVEN ROSEMOUNT ® VALUE AND PERFORMANCE Versatile application: Ranges from 0–0.5 inH 2 0 to 6,000 psig (1.24 kPa to 41370 kPa) Easy maintainance and upgradeability with solid-state, plug-in circuit boards; adjustable damping; and local span and zero adjustments Compact, rugged, construction for easy installation and long-lasting performance Smart, analog, or low-power electronics to fit almost every application Over 30 years of proven Rosemount quality and technology
Transcript
Page 1: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Product Data Sheet 00813-0100-4360

Model 1151 Alphaline® Pressure Transmitters.

Model 1151

Pressure-173

Mod

el11

51

PROVEN ROSEMOUNT®

VALUE AND PERFORMANCE• Versatile application: Ranges from 0–0.5

inH20 to 6,000 psig (1.24 kPa to 41370 kPa)

• Easy maintainance and upgradeability withsolid-state, plug-in circuit boards; adjustabledamping; and local span and zeroadjustments

• Compact, rugged, construction for easyinstallation and long-lasting performance

• Smart, analog, or low-power electronics to fitalmost every application

• Over 30 years of proven Rosemount qualityand technology

Page 2: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

INTRODUCTIONThis product data sheet highlights Rosemount® Model 1151 differential, absolute, gage, and high-line pressure transmitter features and options. For information about the draft range, liquid level transmitters, transmitters with remote seals, and additional information on smart transmitters, refer to their respective data sheets referenced on the back page of this data sheet.

INDUSTRY-LEADING PERFORMANCEAND FEATURESThe Model 1151 Alphaline® series of pressure transmitters brings true precision to the measurement of flow, level, gage and absolute pressures, vacuum, and specific gravity. Direct electronic sensing with the completely sealed δ-cell (delta-cell) capacitance sensing element allows significant improvement and stability in pressure measurements. Welded stress isolation clamping in the sensor housing prevents introduction of errors caused by stresses and torques on the process flanges and minimizes effects of line pressure and overpressure.

Installation, calibration, and commissioning are simplified by compact design, integral junction box, and local span and zero adjustments.

The housing features an explosion-proof, weather-proof construction with separate compartments for the electronics and wiring connections. For most models, 316L SST, Hastelloy® C, Monel®, gold-plated Monel, or tantalum materials are available for corrosive service. Modular construction and plug-in printed circuit boards aid in trouble-shooting and reduce parts stocking

APPLICATIONSModel 1151 Pressure Transmitters are available in a variety of configurations for differential, flow, gage, absolute, vacuum, liquid level, and specific gravity measurement applications. The transmitter model number, determined from the ordering information tables, specifies available features such as pressure ranges, outputs, and materials of construction that are basic to each transmitter. Additional options, such as accessories, certifications, and special manufacturing procedures are also available.

OPERATIONDuring operation, the isolating diaphragms and fill fluid on the high and low sides transmit the process pressure to the oil fill fluid. The fluid in turn transmits the process pressure to a sensing dia-phragm in the center of the d-cell sensor. The sensing diaphragm functions as a stretched spring element that deflects in response to differential pressure across it (in GP transmitters, atmospheric pressure is transmitted in a like manner to the low side of the sensing diaphragm). In AP transmitters, a reference pressure is maintained on the low side. The displacement of the sensing diaphragm, a maximum movement of 0.004 in. (0.10 mm), is proportional to the pressure. Capacitor plates on both sides detect the position of the sensing diaphragm. The differential capacitance between the sensing diaphragm and the capacitor plates is converted electronically to an appropriate current, voltage, or digital HART® (Highway Addressable Remote Transducer) output signal.

Capacitor Plates

Lead Wires

Sensing Diaphragm

Rigid Insulation

Oil Fill

IsolatingDiaphragm Welded Seals

1151

–01

42A

FIGURE 1. Cross Section of the Rosemount d-Cell™ Sensor.

© 1998, Rosemount Inc.May be protected by one or more of the following U.S. Patent Nos. 3, 854,039;3,975,719; 4,339,750; 5,237,285; Re. 30,603. May Depend on Model. OtherU.S. and Foreign Patents Issued and Pending.

re-174

Page 3: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

PRODUCT OFFERING

e-175

Mod

el11

51

MODELS 1151DP, GP, AND APDIFFERENTIAL, GAGE, AND ABSOLUTEPRESSURE TRANSMITTERS• Superior performance: 0.1% accuracy,

15:1 rangeability

• Differential pressures from 30 inH2O to 1,000 psi (7.5 to 6895 kPa)

• Gage pressures from 30 inH2O to 6,000 psig (7.5 to 41369 kPa)

• Absolute pressures from 150 inH2O to 1,000 psia (37.4 to 6895 kPa)

• Smart, analog, or low-power electronics

• Compact, rugged construction resistant to vibration

• Modular construction, adjustable damping, and local span and zero adjustments

MODEL 1151HP DIFFERENTIALPRESSURE TRANSMITTER FOR HIGHLINE PRESSURES• Superior performance: 0.1% accuracy,

15:1 rangeability

• Differential pressures from 30 inH2O to 1,000 psi (7.5 to 6895 kPa)

• Provides accurate differential pressure measurements to 4,500 psi (31026 kPa)

• Silicone and inert fill fluid

• Modular construction, adjustable damping, and local span and zero adjustments

MODEL 1151LT FLANGE-MOUNTEDLIQUID LEVEL TRANSMITTER• Liquid level measurement with 0.25% accuracy

• Pressures from 0–25 to 0–2,770 inH2O (0–6.2 to 0–690 kPa)

• Flush, 2-, 4-, and 6-inch extended diaphragms

• Many optional fill fluids to meet application requirements

• Up to 600% elevation or 500% suppression

• Adjustable damping

• Stainless steel, Hastelloy C-C276, and Tantalum wetted materials

Pressur

1151

-41

A11

51-4

1B11

51-4

1C

Page 4: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

OPTIONS

The following sections describe a variety of available options for the Model 1151 Transmitter. These options permit greater application flexibility.

Mounting BracketsB1 Bracket for 2-in. Pipe Mounting• Bracket for mounting transmitter on 2-in. pipe.

• Constructed of carbon steel with carbon steel U-bolt.

• Coated with polyurethane paint.B4 Bracket for 2-in. Pipe with 316 SST Bolts• Same bracket as Option Code B1 with 316 SST bolts.

B7 304 SST Bracket and 316 SST Boltsfor 2-in. Pipe Mounting

• Same bracket as Option Code B1 with all SST materials.

B2 Bracket for Panel Mounting• Bracket for mounting transmitter on panel or wall.

• Constructed of carbon steel with carbon steel bolts.

• Coated with polyurethane paint.

B5 Bracket for Panel with 316 SST Bolts• Same bracket as Option Code B2 with

316 SST bolts.

re-176

B3 Flat Bracket for 2-in. Pipe Mounting• Bracket for vertical mounting of transmitter on

2-in. pipe.

• Constructed of carbon steel with carbon steel U-bolt.

• Coated with polyurethane paint.B6 Flat Bracket for 2-in. Pipe with 316 SST Bolts• Same bracket as Option Code B3 with 316 SST

bolts.

B9 304 SST Flat Bracket and 316 SST Boltsfor 2-in. Pipe Mounting

• Same bracket as Option Code B3 with all 316 SST materials.

Bolts and Nuts for Flanges and AdaptersOptions permit bolts and nuts for flanges and adapters in the specified material.

L3 ANSI/ASTM A - 193-B7L4 Austenitic 316 SSTL5 ANSI/ASTM A193-B7M

1151

-11

51B

04B

Drain/VentPlug

FlangeBolts

FlangeAdapterBolts

FlangeAdapter

ProcessFlange

FIGURE 2. Model 1151 Flange Configuration.

Page 5: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

e-177

Mod

el11

51

3051

-305

1B

19A

1151

-115

1D,A

06A

3051

-305

1A19

A11

51-0

244A

115

1-1

151E

06A

3051

-30

51H

19B

1151

-11

51F

06B

Pressur

5.625(143)

3.75(95)

1.65(42)

3.87(98)

2.81(71)

NOTEDimensions are in inches (millimeters).

FIGURE 3. Mounting Bracket Option Codes B1, B4, and B7.

4.97(127)

2.62(67)

2.625(67)

5.625(143)

2.625(67)

2.625(67)

3.87(98)

NOTEDimensions are in inches (millimeters).

1.40(36)

Mounting Holes0.375 (10) Diameter

3.75(95)

FIGURE 4. Panel Mounting Bracket Option Codes B2 and B5.

4.5(114)

2.81 (71)Typical

1.40 (46)

2.81 (71)Typical

2.81 (71)Typical

1.65(42)

8.0(203)

FIGURE 5. Flat Mounting Bracket Option Codes B3, B6, and B9.

1.62(41)

2.81(71)

2.125(54)

NOTEDimensions are in inches (millimeters).

Page 6: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

MetersAnalog

Meters have 2-in. (50.8 mm) scale.

Plug-in mounting configuration.

Indication accuracy ±2%.

Operating temperature limit: –40 to 150 °F(–40 to 65 °C).

Meters are enclosed in a housing certified by Factory Mutual as explosion proof for Class I, Division 1, Groups B, C, and D; Class II, Division 1, Groups E, F, and G and Class III, Division 1.

For optional CSA explosion-proof approval, see certification Option Code E6.

M1 Linear Analog Meter, 0–100% ScaleM2 Square Root Analog Meter,

0–100% Flow ScaleM3 Special Scaling Analog Meter

(Specify Range)M6 Square Root Analog Meter, 0–10 √ Scale

NOTESMeter Options are not available with Output Codes L or M,or Option Codes V2 or V3.

Meter Options M2, M6, M8, and M9 are not available withOutput Code J.

Meter Options M4, M7, and M9 are not available withOutput Code G.

re-178

LCD4-digit display.

Indication accuracy ±0.25% of calibrated span±1 digit.

Display resolution at ±0.5% of calibrated span±1 digit.

Operating temperature limit: –4 to 158 °F(–20 to 70 °C).Plug-in mounting configuration.

Meters are enclosed in a housing certified by Factory Mutual as explosion proof for Class I, Division 1, Groups B, C, and D; Class II, Division 1, Groups E, F, and G and Class III, Division 1.

For Optional CSA explosion-proof approval, see certification Option Code E6.

M4 Linear LCD Meter, 0 to 100%M7 Special Scale LCD Meter (Specify Range,

Mode, and Engineering Units)M8 Square Root LCD Meter, 0 to 100%M9 Square Root LCD Meter, 0–10 √ Scale

751-

015

3A,

1151

-253

4A

01A

,11

51I0

5A

7.5 Max. (191)Optional Meter

0.75 (19)Clearance forCover Removal(Typical)

9.0 Max.(229)

OPTION CODE M4LINEAR SCALE

OPTION CODE M1LINEAR SCALE

NOTEDImensions are in inches (millimeters).

FIGURE 6. Meter Options.

Page 7: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

115

1-11

51D

17A

Process ConnectionsD1 Side Drain/Vent-Top

Drain/vent valve mounted in side of flange.

Top position used to vent gas buildup in liquid process applications with transmitter mounted vertically.

Plug of same material as requested flange inserted in end of flange opposite adapter.

D2 Side Drai n/Vent-B ottomDrain/vent valve mounted in side of flange.

Bottom position used to drain liquid buildup in gas process applications with transmitter mounted vertically.

Plug of same material as requested flange inserted in end of flange opposite adapter.

D3 1/4–18 NPT Process ConnectionOption provides 1/4–18 NPT process connection on flanges rather than standard 1/2–14 NPT.

Flange adapters are deleted to provide desired connection.

D6 316 SST Low Side Flange(Model s 1151GP and 1151AP Only)

½–14 NPTConnection

on Adapters(¼–18 NPT

Connectionwit h Adapters

Removed)

Standard Drain/VentReplaced with Plug

Alternate SideDrain/Vent Top Posit ion

(Opti on Code D1)

Alt ernate Side Drain/Vent BottomPosi t ion (Opti on Code D1)

FIGURE 7. Model 1151 Process Connections.

1151

-115

1B04

A

K1 1/4–18 NPT Kynar™ Process Flange InsertK2 1/2–14 NPT Kynar Process Flang e Insert

Options provide Kynar plastic process flange insert that prevents process from coming in contact with the metal of the flange. One process insert for Models 1151AP, GP and LT; two inserts for Model 1151DP.

Process connections are from the side.

Available with carbon steel and stainless steel process flanges only.Pressure Maximum: 200 psi at 200 °F with Kynar impulse piping; 300 psi at 200 °F with metal impulse piping.

S1 Ass embled with One Remote Diaphragm SealS2 Ass embled with Two Remote Diaphragm

SealsOptions provide for the assembly of one or two remote diaphragm seals.

For Models 1151AP and 1151LT applications consult factory.For seal choices, see Rosemount Product Data Sheet 00813-0100-4016.

KynarInsert ¼–18 or ½–14 NPT

Process Connection

FIGURE 8. Flange Insert.

Pressure-179

Page 8: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

1151

-115

1B17

B11

51-1

151B

17B

S4 Assembled with Model 1195 Integral OrificeDesigned for highly accurate, small-bore flow measurement of any clean gas, liquid, or vapor. See Product Data Sheet 00813-0100-4686.Reduce the costs associated with traditional orifice plate installations.

Several configurations are available factory assembled to Rosemount differential pressure transmitters.(1)

Wide orifice bore/flow range capability.

Wide choice of process connections, including threaded, socket weld, and ANSI flanges.

Static pressure maximum limit is 3,000 psig.

Wetted materials are available that comply with NACE MR 01-75(90).

Available only with Ranges 2, 3, 4, and 5.

For integral orifice selection, see Product Data Sheet 00813-0100-4686.

OPTIONAL3-VALVE MANIFOLD

MODEL 1195 INTEGRALORIFICE ASSEMBLY

FIGURE 9. Model 1151 with Manifold and Model1195 Integral Orifice.

re-180

115

1-11

51A

21A

Wetted O-rings

Standard: Viton ® (2)

W2 Buna NW3 Ethylene-PropyleneW4 Aflas ®

W5 Copper O-ring for Vacuum Service(Nonwetted - Model 1151LT only)

W6 Spring-Loaded Teflon ®

Contains a Hastelloy spring that is in contact with the process fluid. Consult factory if Hastelloy is unacceptable.

ProceduresStandard Configuration

Unless otherwise specified, transmitter will be shipped as follows:

Engineering Units: inH2O4 mA: 020 mA: Upper Range LimitOutput: LinearSoftware Tag: BlankCustomer may specify the above items at no charge. Software tag (8 characters) is left blank unless specified.

WettedO-rings

FIGURE 10. Flange Exploded View.

Wetted O-rings

Standard: Viton ® (2)

W2 Buna NW3 Ethylene-PropyleneW4 Aflas ®

W5 Copper O-ring for Vacuum Service(Nonwetted - Model 1151LT only)

W6 Spring-Loaded Teflon ®

Contains a Hastelloy spring that is in contact with the process fluid. Consult factory if Hastelloy is unacceptable.

ProceduresStandard Configuration

Unless otherwise specified, transmitter will be shipped as follows:

Engineering Units: inH2O4 mA: 020 mA: Upper Range LimitOutput: LinearSoftware Tag: BlankCustomer may specify the above items at no charge. Software tag (8 characters) is left blank unless specified.

WettedO-rings

FIGURE 1. Flange Exploded View.

(1) Applicable only to orifice assemblies without piping.(2) For enhanced sealing performance below 0 °F, consult factory.

Page 9: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

C9 Custom Configuration (Option Code C9)If Option Code C9 is ordered, the customer may specify the following data in addition to the standard configuration parameters. Refer to Configuration Data Sheet 00806-0100-4593.

Descriptor: 16 charactersMessage: 32 charactersDate: Day, Month, YearDamping: SecondsBurst Mode: Select Output ChoiceFlange Material: Model Code InformationO-Ring Material: Model Code InformationIsolator Material: Model Code InformationSensor Fluid: Model Code InformationDrain/Vent: Model Code InformationIntegral Meter: Installed or NoneRemote Seal: Specified InformationFailure Mode: High or LowTransmitter Security: Off or On

P1 Hydrostatic TestingEach transmitter is hydrostatic tested according to Table 1.

Test medium is water.

This option provided for transmitters with remote diaphragm seal on application only.

Rosemount Procedure 1746 outlines the testing procedure.

TABLE 1. Hydrostatic Test Pressure.

Model Test Pressure

1151DP 3,000 psi

1151HP 6,750 psi

1151AP 2,000 psi

1151GP

Ranges 3–8 2,000 psi

Range 9 4,500 psi

Range 0 7,500 psi

1151LT

Class 150 Flange 450 psi

Class 300 Flange 1,100 psi

1151DR 1,500 psi

P2 Cleaning for Special ServiceThis option minimizes contaminants to the process system by cleaning wetted surfaces with a suitable detergent.

Rosemount Procedure 97412 outlines the cleaning procedure.

P3 Cleaning for <1 PPM Chlorine/FluorineP4 Calibration at Line Pressure

This option allows transmitters to be calibrated at an elevated line pressure rather than atmospheric pressure.Customer must specify line pressure at which transmitter is to be calibrated.

Customer is provided with calibration data at line pressure and equivalent data at atmospheric pressure.

Available with Models 1151DP and 1151HP only. (Not available with Remote Seals.)

Elevated line pressure and differential span desired for calibration must not exceed the rated pressure for that model of transmitter.

Minimum differential span that can be calibrated at elevated line pressure is 30 inH2O; maximum is 300 psi.

Rosemount Procedure 3787 outlines the calibration procedure.

P5 Calibration at TemperatureThis option allows transmitters to be calibrated at temperatures other than room temperature in the range of 0 to 200 °F (–18 to 93 °C).

Customer must specify temperature at which transmitter is to be calibrated and calibration range.

Calibration temperature will be printed on instrument tag specified by customer, or on a tag wired to the transmitter if no tag is specified.

Rosemount Procedure 27823B outlines the calibration procedure.

Pressure-181

Page 10: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

P7 Enhanced Temperature Performancefor Analog ElectronicsTransmitter is specifically compensated as a complete assembly and will exhibit 1/2 of the standard temperature coefficient over the ambient temperature range of 20 to 140 °F (–7 to 60 °C). Outside this range, the unit will meet the standard temperature effect specification published for that model.

Not available on Range 10, limited to 1,500 psi on Range 9.

The transmitter is compensated as an assembly; therefore, units in which the sensor module or electronics are changed after the P7 procedure has been performed will meet the standard published temperature specification for that particular model.

Available on DP, GP, and HP models, Ranges3–8, with SST diaphragms and Output Codes E, G, L, and M.

P8 0.1% Accuracy for Analog ElectronicsAvailable on Model 1151DP (Ranges 3–8), GP (Ranges 3–8), HP, and LT transmitters with 316 SST diaphragms and Output Codes E, G, L, and M.

re-182

OutputsV1 Reverse Output

This option permits reversing of pressure input so that electrical output will increase as pressure input decreases.

This option applies only to Models 1151GP and 1151LT. When this option is selected, the process flange, adapter, drain/vent valve, appropriate O-rings, and bolting are installed on low side of transmitter. Not available for Ranges 9 and 0.

Not available with Model 1151AP. Reverse output on Models 1151DP, 1151HP, and 1151DR can be obtained by connecting high-pressure input to low side of transmitter and vice versa.

This option should not be ordered with smart transmitters (Output Code S). The Model 1151 Smart transmitter can be configured for reverse output through a HART-Compatible Interface.

V2 1 V Test ResistorA 1 V precision resistor is mounted across the test terminals to provide 4–20 mV output or a 10–50 mV output if 10–50 mA output is used.

This option cannot be used with any meter options or Option Codes I5 or I6.

V3 5 V Test ResistorA 5 V precision resistor is mounted across test terminals to provide 20–100 mV output or a50–250 mV output if 10–50 mA output is used.

This option cannot be used with any meter options or Option Codes I5 or I6.

Z1 4-Wire, 0–20 mA OutputZ2 4-Wire, 0–16 mA OutputZ3 4-Wire, 0–10 mA Output

These options provide a zero-based current output.

These options cannot be used with any meter or certification options, Vx options, or Output Codes G, L, M, or S.

Page 11: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Pressure-183

Mod

el11

51

SPECIFICATIONS

Functional SpecificationsServiceLiquid, gas, and vapor applications.

RangesSee Table 3 for ranges. Minimum span equals the upper range limit (URL) divided by rangedown. Rangedown varies with the output code. See Table 2.

OutputsCode S, Smart4–20 mA dc, user selectable for linear or square root output. Digital process variable superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol.

Code E, Analog4–20 mA dc, linear with process pressure.

Code G, Analog10–50 mA dc, linear with process pressure.

Code J, Analog4–20 mA dc, square root of differential input pressure between 4 and 100% of input. Linear with differential input pressure between 0 and 4% of input.

Code L, Low Power0.8 to 3.2 V dc, linear with process pressure.

Code M, Low Power1 to 5 V dc, linear with process pressure.

Power SupplyExternal power supply required. Transmitter operates according to the following requirements:

Output Codes S, E, J 12 to 45 V dc with no load.Output Code G 30 to 85 V dc with no load.Output Code L 5 to 12 V dc.Output Code M 8 to 14 V dc.

Where:

Code Vmin Vmax Rmin Rmax RL at Supply Voltage (V S)

S(1)

(1) A minimum of 250 ohms is required for communication.

12 45 0 1650 RL = 43.5 (VS – 12)

E(2),J

(2) For CSA approvals Vmax = 42.4 V dc.

12 45 0 1650 RL = 50 (VS – 12)

G 30 85 0 1100 RL= 20 (VS – 30)

L 5 12 Low Power Minimum Load Impedance:100 kVM 8 14

Rmax

RL

Rmin

Vmin VS Vmax0

OperatingRegion

Current Consumption Under Normal OperatingConditions (Low Power Only)

Output Code L1.5 mA dc.

Output Code M2.0 mA dc.

Span and ZeroOutput Code SSpan and zero may be accessed with local adjustments or remotely through a HART-compatible Interface.Output Codes E, G, J, L, and MSpan and zero are continuously adjustable.

Zero Elevation and SuppressionOutput Codes S, E, and GZero elevation and suppression must be such that the lower range value is greater than or equal to the (–URL) and the upper range value is less than or equal to the (+URL). The calibrated span must be greater than or equal to the minimum span and less than or equal to the maximum span.

Output Code JZero is adjustable up to 10% of the calibrated flow span.

Output Code LZero is adjustable ±10% of URL and span is adjustable from 90 to 100% of URL.

Output Code MZero is adjustable ±50% of URL and span is adjustable from 50 to 100% of URL.

Page 12: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

TABLE 2. Rangeability.

Output CodeMinimum Span

(URL=Upper Range Limit)Maximum Span

S (DP and GP, SST, Range 3–8; HP SST, Range 4–7) URL/15 2 3 URL(1)

(1) Transmitter is capable of measuring from –URL to URL.

S (All Others) URL/6 2 3 URL(1)

E, G, J URL/6 URL

L URL/1.1 URL

M URL/2 URL

TABLE 3. Model 1151 Transmitter Range Availability by Model (URL = Upper Range Limit).

Range Code Model 1151 Ranges (URL) DP HP GP DP/GP/Seals AP LT

3 30 inH20 (7.46 kPa) • NA • NA NA NA

4 150 inH20 (31.08 kPa) • • • • • •

5 750 inH20 (186.4 kPa) • • • • • •

6 100 psi (689.5 kPa) • • • • • •

7 300 psi (2,068 kPa) • • • • • NA

8 1,000 psi (6,895 kPa) • NA • NA • NA

9 3,000 psi (20,684 kPa) NA NA • NA NA NA

0 6,000 psi (41,369 kPa) NA NA • NA NA NA

TABLE 4. Model 1151 Upper Range Limits (URL).

RangeCode

bar mbar kg/cm 2 psi kPainH 20

@20 °CmmH 2O@20 °C

inHg@0 °C

3 0.075 75 0.076 1.082 7.461 30 762 2.203

4 0.373 373 0.380 5.409 37.305 150 3810 11.013

5 1.865 1865 1.901 27.045 186.505 750 19050 55.065

6 6.90 6895 7.031 100 690 2773 70434 204

7 21 20685 21 300 2069 8319 211302 611

8 69 68950 70 1000 6895 27730 704340 2036

9 207 206850 211 3000 20685 83190 2113020 6108

0 413.686 413686 421.842 6000 41369 166378 4225992 12216.12

TABLE 5. Model 1151 Output Code Availability.

Code Model 1151 Output Options/Damping DP HP GP DP/GP/Seals AP LT

S 4–20 mA, Digital, Smart/Variable • • • • • •

E 4–20 mA, Linear, Analog/Variable • • • • • •

G 10–50 mA, Linear, Analog/Variable • • • • • •

J(1)

(1) Available with Ranges 3–5.

4–20 mA, Square Root, Analog/Variable • • NA NA NA NA

L 0.8 to 3.2 V, Linear, Low Power/Fixed • • • • • NA

M 1 to 5 V, Linear, Low Power/Fixed • • • • • NA

re-184

Page 13: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

Temperature LimitsElectronics Operating

Code S –40 to 185 °F (–40 to 85 °C).Code E –40 to 200 °F (–40 to 93 °C).Code G, L, M –20 to 200 °F (–29 to 93 °C).Code J –20 to 150 °F (–29 to 66 °C).

Sensing Element OperatingSilicone fill –40 to 220 °F (–40 to 104 °C).Inert fill 0 to 160 °F (–18 to 71 °C).

StorageCode S –60 to 185 °F (–51 to 85 °C).Codes E, G, L, M –60 to 250 °F (–51 to 121 °C).Code J –60 to 180 °F (–51 to 82 °C).

Static Pressure and Overpressure LimitsModel 1151DP0 psia to 2,000 psig (0 to 13.79 MPa) on either side without damage to transmitter. Operates within specifications from static line pressures of 0.5 psia (3.45 kPa) to 2,000 psig (13.79 MPa).

Model 1151HP0 psia to 4,500 psig (0 to 31.02 MPa) on either side without damage to transmitter. Operates within specifications from 0.5 psia (3.45 kPa) to 4,500 psig (31.02 MPa).

TABLE 6. Fill Fluid Specifications.

Fill FluidTemperature

Limits (1)

(1) Temperature limits are reduced in vacuum service. Contact yourlocal Rosemount representative for assistance.

SpecificGravity

Coeff. ofTherm. Exp.

cc/cc/°F(cc/cc/°C)

Viscosityat 25 °C

centistokes

D.C.® 200Silicone

–40 to 400 °F(–40 to 205 °C)

0.9340.00060

(0.00108)9.5

D.C. 704Silicone

60 to 400 °F(15 to 205 °C)

1.070.00053

(0.00095)44

Inert Fill–50 to 350 °F

(–45 to 177 °C)1.85

0.0004(0.000864)

6.5

Syltherm®

800, Silicone–50 to 400 °F

(–45 to 205 °C)0.934

0.00052(0.000936)

9.5

SylthermXLT, Silicone

–100 to 300 °F(–73 to 149 °C)

0.850.000666

(0.001199)1.6

GlycerinandWater(2)

(2) Glycerin and Water and Propylene Glycol and Water are notsuitable for vacuum service.

0 to 200 °F(–17 to 93 °C) 1.13

0.00019(0.00034) 12.5

PropyleneGlycolandWater(3)

(3) Not compatible with Buna-N or Ethylene-Propylene O-ringmaterial.

0 to 200 °F(–17 to 93 °C)

1.02

0.00019(0.00034)

2.85

NeobeeM-20(3)

0 to 400 °F(–17 to 205 °C)

0.9000.00056

(0.001008)9.8

Model 1151AP0 psia to 2,000 psia (0 to 13.79 MPa) without damage to transmitter. Operates within specifications from 0 psia to the upper range limit of the transmitter.

Model 1151GP0 psia to 2,000 psig (0 to 13.79 MPa) for ranges to 1,000 psig (6.90 MPa), 4,500 psig (31.02 MPa) for the 3,000 psig (20.68 MPa) range, and 7,500 psig (51.71 MPa) for the 6,000 psig (41.37 MPa) range, without damage to the transmitter. Operates within specifications from 0.5 psia (3.45 kPa) to the upper range limit of the transmitter.

Model 1151LT

Burst Pressure All Models10,000 psig (68.95 MPa) proof pressure on the flanges.Humidity Limits0 to 100% relative humidity.

Volumetric DisplacementLess than 0.01 in3 (0.16 cm3).

Failure Mode Alarm (Output Code S)If self-diagnosis detects a gross transmitter failure, the analog signal will be driven below 3.9 mA or above 21 mA to alert the user. High or low alarm signal is user selectable.

Transmitter Security (Output Code S)Activating the transmitter security function prevents changes to the transmitter configuration, including local zero and span adjustments. Security is activated by an internal switch.

TABLE 7. Flange Pressure Rating.

Standard Class/Rating Carbon SteelStainless

Steel

ANSI 150 285 psig(1)

(1) At 100 °F (38 °C); the rating decreases with increasingtemperature.

275 psig(1)

ANSI 300 740 psig(1) 720 psig(1)

ANSI 600 1,480 psig(1) 1,440 psig(1)

DIN PN 10–40 40 bar(2)

(2) At 248 °F (120 °C); the rating decreases with increasingtemperature.

40 bar(2)

DIN PN 10/16 16 bar(2) 16 bar(2)

DIN PN 25/40 40 bar(2) 40 bar(2)

Level4–20 mA

SaturationValue

4–20 mAAlarmValue

Low 3.9 mA 3.8 mA

High 20.8 mA 21.75 mA

Pressure-185

Page 14: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

Overpressure Alarm (Output Code S)If the sensor detects a negative overpressure value, the analog signal will be driven to 3.9 mA. If the sensor detects a positive overpressure value, the analog signal is driven to 20.8 mA.

DampingNumbers given are for silicone fill fluid at room temperature. The minimum time constant is 0.2 seconds (0.4 seconds for Range 3). Inert-filled sensor values would be slightly higher.

Output Code STime constant is adjustable in 0.1 second increments from minimum to 16.0 seconds.

Output Codes E and GTime constant continuously adjustable between minimum and 1.67 seconds.

Output Code JTime constant continuously adjustable between minimum and 1.0 second.

Output Codes L, MDamping is fixed at minimum time constant.

Model 1151LTTime constant continuously adjustable between 0.4 and 2.2 seconds with silicone oil fill, or 1.1 and 2.7 seconds with inert fill for flush models and electronics codes E or G.

Turn-on TimeMaximum of 2.0 seconds with minimum damping. Low power output is within 0.2% of steady state value within 200 ms after application of power.

Performance Specifications(Zero-based calibrated ranges, reference conditions, silicone oil fill,316 SST isolating diaphragms.)

AccuracyOutput Code S

Ranges 3 through 8, DP and GP transmitters;Ranges 4 through 7, HP transmitters

±0.1 of calibrated span for spans from 1:1 to 10:1 of URL. Between 10:1 and 15:1 of URL.

All other ranges and transmitters±0.25% of calibrated span.

Output Code S, square root mode

Output Codes E, G, L, and M±0.2% of calibrated span for Model 1151DP Ranges 3 through 5. All other ranges and transmitters, ±0.25% of calibrated span.

accuracy 0.02 URLspan--------------

0.1– % of calibrated span±=

0.2 0.05 URLspan-------------

×+ % of calibrated flow span±

re-186

Output Code J±0.25% of calibrated span.

StabilityOutput Code S±0.1% of URL for six months for DP and GP Ranges 3 through 8. (±0.25% for all other ranges and transmitters.)

Output Codes E and G±0.2% of URL for six months for Ranges 3 through 5. (±0.25 for all other ranges.)

Output Codes J, L, and M±0.25% of URL for six months.

Temperature EffectOutput Code S [–20 to 185 °F (–29 to 85 °C)]

For DP and GP transmitter Range 4 through 8;HP transmitter Range 4 through 7:

Zero Error = ±0.2% URL per 100 °F (56 °C)Total Error = ±(0.2% URL + 0.18% of calibrated span) per 100 °F; For Range 3, double the stated effects. For other ranges and transmitters follow analog temperature specifications (Output Code E).

Output Code E, G, L, and M[–20 to 200 °F (–29 to 93 °C)]

For Ranges 4 through 0Zero Error = ±0.5% URL per 100 °F.Total Error = ±(0.5% URL + 0.5% of calibrated span) per 100 °F; double the effect for Range 3.

Output Code JThe total output effect, whether at zero or full scale, including zero and span errors is ±1.5% of URL per 100 °F (56 °C). ±2.5% of URL per 100 °F (56 °C) for Range 3.

Static Pressure EffectDP Transmitters

Zero Error±0.25% of URL for 2,000 psi (13790 kPa) for Range 4 and 5 or ±0.5% for other ranges, correctable through rezeroing at line pressure.

Span ErrorCorrectable to ±0.25% of input reading per 1,000 psi (6895 kPa), or to ±0.5% for Range 3. For Output Code J, the span error is correctable to ±0.125% of output reading per 1,000 psi, or to ±0.25% for Range 3.

HP TransmittersZero Error±2.0% of URL for 4,500 psi (31027 kPa), correctable through rezeroing at line pressure.

Span ErrorCorrectable to ±0.25% of input reading per 1,000 psi (6895 kPa). For Output Code J, the span error is correctable to ±0.125% of output reading per 1,000 psi.

Page 15: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

Vibration Effect0.05% of URL per g to 200 Hz in any axis.

Power Supply EffectOutput Codes S, E, G, and JLess than 0.005% of output span per volt.

Output Codes L, MOutput shift of less than 0.05% of URL for a 1 V power supply shift.

Load EffectOutput Codes S, E, G, and JNo load effect other than the change in power supplied to the transmitter.

Output Codes L, MLess than 0.05% of URL effect for a change in load from 100 kV to infinite ohms.

Short Circuit Condition (Low Power Only)No damage to the transmitter will result when the output is shorted to common or to power supply positive (limit 12 V).

EMI/RFI EffectOutput shift of less than 0.1% of span when tested to SAMA PMC 33.1 from 20 to 1000 MHz and for field strengths up to 30 V/m. (Code J is 0.1% of flow span.)

Mounting Position EffectZero shift of up to 1 inH2O (0.25 kPa). Range 3 transmitters with Output Code J should be installed with the diaphragm in the vertical plane.

With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (0.25 kPa). With liquid level diaphragm in horizontal plane, zero shift of up to 5 inH2O (1.25 kPa) plus extension length on extended units. All zero shifts can be calibrated out. No effect on span.

Physical Specifications,Standard ConfigurationWetted Materials

Isolating Diaphragms316L SST, Hastelloy C-276, Monel, gold-plated Monel, or Tantalum. See ordering table for availability per model type.

Drain/Vent Valves316 SST, Hastelloy C, or Monel. See ordering table for availability per model type.

Process Flanges and AdaptersPlated carbon steel, 316 SST, Hastelloy C, or Monel. See ordering table for availability per model type.

Wetted O-ringsViton® (other materials also available). With gold-plated Monel diaphragms (diaphragm Code _6), special fluorocarbon O-rings are supplied.

Non-wetted MaterialsFill FluidSilicone oil or inert fill.

Bolts and Bolting Flange (GP and AP only)Plated carbon steel.

Electronics HousingLow-copper aluminum. NEMA 4X.

Cover O-ringsBuna-N.

PaintPolyurethane.

Process Connections1/4–18 NPT on 2.125-in. (54-mm) centers on flanges for Ranges 3, 4, and 5.1/4–18 NPT on 2.188-in. (56-mm) centers on flanges for Ranges 6 and 7.1/4–18 NPT on 2.250-in. (57-mm) centers on flanges for Range 8.1/2–14 NPT on adapters.

For Ranges 3, 4, and 5, flange adapters can be rotated to give centers of 2.0 in. (51 mm), 2.125 in. (54 mm), or 2.250 in. (57 mm).

Electrical Connections1/2–14 NPT conduit with screw terminals and integral test jacks compatible with miniature banana plugs (Pomona 2944, 3690, or equivalent). The HART Hand-Held Interface connections are fixed to the terminal block on smart transmitters.

Weight12 lb (5.4 kg) for AP, DP, GP, and HP transmitters, excluding options.

Meter Option: Add 2 lb (1 kg).Hazardous Locations CertificationsStainless steel certification tag is provided.

Factory Mutual (FM) ApprovalsFM Explosion Proof tag is standard. Appropriate tag will be substituted if optional certification is selected.

TABLE 8. Flange Weights with Model 1151LT Transmitter.

Flange (1)

(1) Stainless steel flange weights are listed.

Flush2-in

(50mm)Ext.

4-in.(100mm)

Ext.

6-in.(150mm)

Ext.

2-in., Class 1503-in., Class 1504-in., Class 1502-in., Class 3003-in., Class 3004-in., Class 3002-in., Class 6003-in., Class 600

18 (8.2)23 (10.4)29 (13.2)20 (9.1)

28 (12.7)38 (17.2)22 (10.0)31 (14.1)

N/A25 (11.3)32 (14.5)

N/A30 (13.6)41 (18.6)

N/A33 (15.0)

N/A26 (11.8)34 (15.4)

N/A31 (14.1)43 (19.5)

N/A34 (15.4)

N/A27 (12.3)36 (16.3)

N/A32 (14.5)45 (20.4)

N/A35 (15.9)

DN 50, PN10-40DN 80, PN 25/40DN 100, PN 10/16DN 100, PN 25/40

20 (9.1)25 (11.3)25 (11.3)29 (13.2)

N/A27 (12.3)28 (12.7)32 (14.5)

N/A28 (12.7)30 (13.6)34 (15.4)

N/A29 (13.2)32 (14.5)36 (16.3)

Pressure-187

Page 16: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

Default Explosion Proof: Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof: Class II, Division 1, Groups E, F, and G. Suitable for use in: Class III, Division 1. Indoor and outdoor use. NEMA 4X. Factory Sealed.

I5 Intrinsic Safety and Non-incendive Approvals: FM certifications optional for specific Classes, Divisions, and Groups when connected in accordance with the FM entity approvals,see Table 9. Factory Sealed.

K5 Combination of Explosion Proof, Intrinsic Safety, and Non-incendive Approvals.

Canadian Standards Association (CSA) ApprovalsE6 Explosion proof for Class I, Division 1, Groups

C and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1 Hazardous Locations. Certified for Class I, Division 2, Groups A, B, C, and D; CSA enclosure type 4X. Factory Sealed.

I6 Intrinsic Safety Approvals CSA certifications optional for specific Classes, Divisions, and Groups when connected in accordance with the CSA barrier selection table, Table 10. Temperature Code T2D.

C6 Combination of I6 and E6, CSA Explosion Proof and Intrinsic Safety Approval. Factory Sealed.

K6 CSA/CENELEC Explosion-Proof and Intrinsic Safety Approval.

Standards Association of Australia (SAA)Flameproof CertificationE7 Flameproof

Ex d IIB + H2 T6.Class I, Zone 1.

Dust-Ignition proofDIP T6.Class II.

Special Conditions: For transmitters having NPT or PG cable entry threads, an appropriate flameproof thread adaptor shall be used to facilitate application of certified flameproof cable glands.

I7 Intrinsically SafeEx ia IIC T6 (Tamb = 40 °C).Ex ia IIC T5 (Tamb = 70 °C).Class I, Zone 0.Special Conditions: Observe electrical connection parameters when installing transmitter.

Standards Association of Australia (SAA)

N7 Type NEx n IIC T6 (Tamb = 40 °C).Ex n IIC T5 (Tamb = 70 °C).Class I, Zone 2.

re-188

Special Conditions: The equipment must be connected to a supply voltage which does not exceed the rated voltage. The enclosure end caps must be correctly fitted whilst the equipment is energized.

CESI/CENELEC Flameproof CertificationE8 90.C.016: EEx d IIC T6 (without meter).

90.C.017: EEx d IIB + H2 T6.

CESI/CENELEC Intrinsic Safety CertificationI8 EEx ia IIC T6 (Tamb = 40 °C); (Pmax = 0.75 W).

EEx ia IIC T5 (Tamb = 55 °C); (Pmax = 1.00 W).EEx ia IIC T4 (Tamb = 80 °C); (Pmax = 1.00 W).

Special Conditions: When transient protection terminal options (R1 or R9) are installed, the transmitter must be supplied from a galvanically isolated i.s. barrier.

BASEEFA/CENELEC Intrinsic Safety CertificationI1 Smart

EEx ia IIC T5 (Tamb = 40 °C).EEx ia IIC T4 (Tamb = 80 °C).AnalogEEx ia IIC T5.

Special Conditions: When transient protection terminal options (R1 or R9) are installed, the transmitter must be supplied from a galvanically isolated i.s. barrier.

BASEEFA Type N (Non-incendive) CertificationN1 Smart

Ex N II T5 (Tamb = -40 °C to 50 °C); Un = 45 V.Ex N II T4 (Tamb = -40 °C to 80 °C); Un = 45 V.

AnalogEx N II T5; Un = 45 V.

Special Conditions: The apparatus must be installed in accordance with BS 5345: Part 7: 1979 and be earthed by means of enclosure earth terminal.

Schweizerischer Elektrotechnischer Verein (SEV)Intrinsic Safety CertificationIC Smart

EEx ia IIC T5 (Tamb = 40 °C).EEx ia IIC T4 (Tamb = 80 °C).

AnalogEEx ia IIC T6 (Pmax = 0.35 W).EEx ia IIC T5 (Pmax = 0.65 W).EEx ia IIC T4 (Pmax = 0.95 W).

Page 17: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

TABLE 9. FM Entity Approvals.

1151 ParametersEquipment Associated

Parameters

FM Approved for Class I, II, III, Division 1 and 2 Groups

A B C–G

VMax = 40 VIMax = 165 mACl = 0 (Standard)Cl = 0.024 mF (Smart)Ci = 0.010 mF (Standard w/R Option)Ci = 0.034 mF (Smart w/R Option)Ll = 0 (Standard)Li = 20 mH (w/R Option)

VOC ≤ 40 VISC ≤ 165 mACA > 0CA > 0.024 mFCA > 0.010CA > 0.034LA > 0LA > 20 mH

• • •

VMax = 40 VIMax = 225 mACi = 0 (Standard)Ci = 0.024 mF (Smart)Ci = 0.010 mF (Standard w/R Option)Ci = 0.034 mF (Smart w/R Option)Ll = 0 (Standard)Li = 20 mH (w/R Option)

VOC ≤ 40 VISC ≤ 225 mACA > 0CA > 0.024 mFCA > 0.010CA > 0.034LA > 0LA > 20 mH

NA NA •

TABLE 10. CSA Barrier Selection.

Barrier Manufacturer/ModelCSA Approved for Class I, Division 1 and 2 Groups

A B C D

Any CSA Approved Barrier ≤30 V, ≥ 330 V or≤ 28 V, ≥300 V or ≤22 V, ≥ 180 V

• • • •

Foxboro Converters 2AS-I3I-CGB, 2AI-I3V-CGB, 2AI-12V-CGB, 2AS-I2I-CGB, 3A2-I2DCS-E/CGB-A, 3F4-I2DAI CS-E/CGB-A, 3AD-I3IA CS-E/CGB-A,3A2-I3D CS-E/CGB-A, and 3A4-I2DA CS-E/CGB-A

NA • • •

Any CSA Approved Barrier ≤ 30 V, ≥ 150 V NA NA • •

Mod

el11

51

MODEL 1151 SMART RETROFIT KIT

In keeping with the Rosemount Inc. design philosophy of upgrading products without sacrificing parts compatibility, the Model 1151 Pressure Transmitter, can be converted to microprocessor-based or “smart” operation. With its wide range of product offerings and low cost of ownership, the Model 1151 is a perfect candidate for smart retrofitting, and the Model 1151 Smart Retrofit Kit makes this possible.

Smart electronics can be installed quickly by removing the analog electronics boards and plugging

in a new, single-board smart electronics assembly. The electronics in the smart retrofit kit are identical to the electronics used in the Model 1151 Smart and feature the same advantages of the factory-produced smart transmitter.

Retrofitting ProcedureAny Model 1151 Differential, Gage, Absolute, or

Level Transmitter, Ranges 3–0, can be retrofitted with smart electronics. The retrofitting procedure takes just a few minutes. The five simple steps for converting a Model 1151 Analog Transmitter to smart operation are as follows:

Step 1 Remove the screws and unplug the analog electronics.

Step 2 Insert two spacers and reattach the header board.

Step 3 Plug in the smart electronics and secure with three screws.

Step 4 Attach eyelets to the terminal block to allow easy connection of the HART Communicator.

Step 5 Characterize the transmitter.For more information, see PDS 00813-0100-4594, Model 1151 Pressure Transmitter Smart Retrofit Kit, or consult your Rosemount Representative.

Pressure-189

Page 18: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

1151

-115

1A,B

05A

re-190

SmartElectronics

Terminal Eyelets

Transmitter Security andFailure Mode Alarm Switches

Zero and Span Buttons

BoardSpacers

d-Cell SensingModule

Blank Flangefor AP and GP

ProcessFlange

FIGURE 11. Typical Transmitter Exploded View, Shown with Smart Electronics.

1151

-115

1A27

A

Range

Flange Distance “A” Centerto Center

inches mm

3, 4, 5 2.125 54

6, 7 2.188 56

8 2.250 57

9 2.281 58

0 2.328 59

MeterHousing

Terminal Connectionsthis Side

¼–18 NPT onFlanges for Pressure

Connection withoutFlange Adapters

½–14 NPTon FlangeAdapters A

(See Table)

4.5 (114)Max.

7.5 (191) Max.with Optional Meter

0.75 (19)Clearance forCover Removal(Typical)

TransmitterCircuitrythis Side

1.625(41)

Blank FlangeUsed onAP and GPTransmitters

FlangeAdapter 4.5

(114)

3.375(86) Flanges Can

Be Rotated

3.69(94)

4.5 (114)Max. Permanent

Tag (Optional)

Nameplate

Wired-on Tag(Standard)

Drain/VentValve

¼–18 NPT forSide Drain/Vent

(Optional Topor Bottom)

FIGURE 12. Model 1151 Transmitter Dimensional Drawing.

NOTEDimensions are ininches (millimeters).

½–14 NPTConduit

Connection(2 Places)

9.0(229)Max.

Page 19: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

115

1-5

1LT

B05

A11

51-1

151B

30B

115

1-51

LTA

05A

305

1-3

051B

27B

Pressur

TABLE 11. Model 1151LT Dimensional Specifications.

ClassPipeSize

FlangeThickness

A

Bolt CircleDiameter

B

OutsideDiameter

C

No.of

Bolts

BoltHoleDiameter

Exten.Diam.

D (1)

O.D.Gask.Surf.

E

Lower Housing

XmtrSide

F

Proc.Side

G

ANSI150

2 (51)3 (76)

4 (102)

1.12 (28)1.31 (33)1.31 (33)

4.75 (121)6.0 (152)7.5 (191)

6.0 (152)7.5 (191)9.0 (229)

448

0.75 (19)0.75 (19)0.75 (19)

NA2.58 (66)3.5 (89)

3.75 (95)5.0 (127)6.81 (173)

2.9 (74)3.11 (79)

4.06 (103)

2.16 (55)3.11 (79)

4.06 (103)

ANSI300

2 (51)3 (76)

4 (102)

1.25 (32)1.50 (38)1.62 (41)

5.0 (127)6.62 (168)7.88 (200)

6.5 (165)8.25 (210)10.0 (254)

888

0.75 (19)0.88 (22)0.88 (22)

NA2.58 (66)3.5 (89)

3.75 (95)5.0 (127)6.81 (173)

2.9 (74)3.11 (79)

4.06 (103)

2.16 (55)3.11 (79)

4.06 (103)

ANSI600

2 (51)3 (76)

1.12 (28)1.37 (35)

5.0 (127)6.62 (168)

6.5 (165)6.62 (168)

88

0.75 (19)0.88 (22)

NA2.58 (66)

3.75 (95)5.0 (127)

2.9 (74)3.11 (79)

2.16 (55)3.11 (79)

DINPN10-40

DN 50 26 mm 125 mm 165 mm 4 18 mm NA 95 mm 74 mm 55 mm

DINPN 25/40

DN 80DN 100

30 mm30 mm

160 mm190 mm

200 mm235 mm

88

18 mm22 mm

65 mm89 mm

127 mm173 mm

79 mm103 mm

79 mm103 mm

DINPN 10/16

DN 100 26 mm 180 mm 220 mm 8 18 mm 89 mm 173 mm 103 mm 103 mm

(1) Tolerances are 0.040 (1.02), –0.020 (0.51).

C

B

DIAPHRAGM ASSEMBLYAND MOUNTING FLANGE

NOTEDimensions are in inches (millimeters).

MeterHousing

Terminal ConnectionsThis Side

Nameplate (Remove forSpan and Zero Adjust)

TransmitterCircuitryThis Side

½–14 NPT forConduit Connection(2 places)

0.75 (19) Clearance forCover Removal (typical)

½–14 NPTon FlangeAdapters

¼–18 NPT on Flangesfor Pressure Connectionwithout the Use of FlangeAdapters

Permanent Tag(optional)

11.38 (289)Max. Serrated Face

Gasket Surface

ED

AWired-on Tag(standard)

FlangeAdapter

2-, 4-, or 6-in.(51, 102, or 152)Extension

4.5 (114)Max.

4.5 (114)Max.

4.45 (113)Max.

7.5(190.5)

Max. withOptional

Meter

FIGURE 13. Dimensional Drawings.

FlushingConnection

1(25)

FG

E

OPTIONAL FLUSHINGCONNECTION RING(LOWER HOUSING)

Drain/Vent Valve

e-191

Page 20: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

ORDERING INFORMATIONTABLE 12. Model 1151 Differential, High Line, Gage and Absolute Pressure Transmitters. — = Not Applicable • = Applicable

Model Transmitter Type (select one) DP HP GP AP

1151DP1151HP1151GP1151AP

Differential Pressure TransmitterDifferential Pressure Transmitter for High Line PressuresGage Pressure TransmitterAbsolute Pressure Transmitter

•———

—•——

——•—

———•

Code Pressure Ranges (URL) (select one)—For Rangeability, see below DP HP GP AP

34567890

30 inH2O (7.46 kPa)150 inH2O (37.3 kPa)750 inH2O (186.4 kPa)100 psi (689.5 kPa)300 psi (2068 kPa)1,000 psi (6895 kPa)3,000 psi (20684 kPa)6,000 psi (41369 kPa)

••••••——

—••••———

••••••••

—•••••——

Code Transmitter Output (select one) DP HP GP AP

SEGJLM

4–20 mA/Digital, Smart/Variable Damping4–20 mA, Linear, Analog/Variable Damping10–50 mA, Linear, Analog/Variable Damping4–20 mA, Square Root, Analog/Variable Damping0.8 to 3.2 V, Linear, Low Power/Fixed Damping1 to 5 V, Linear, Low Power/Fixed Damping

••••••

••••••

•••—••

•••—••

CodeMATERIALS OF CONSTRUCTION (1)

Flanges/Adapters Drain/VentsDiaphragmsFill Fluid

(1) Bolts and conduit plugs are plated carbon steel.

DP HP GP(2)

(2) On GP and AP transmitters, the low-side flange is plated carbon steel.For a stainless-steel low-side flange, order process connection Option Code D6.

AP(2)

525354555612222324252633(3)

3435

(3) These selections meet NACE material recommendations per MR 01-75.

Nickel-plated Carbon Steel 316 SST 316L SST SiliconeNickel-plated Carbon Steel 316 SST Hastelloy C-276 SiliconeNickel-plated Carbon Steel 316 SST Monel SiliconeNickel-plated Carbon Steel 316 SST Tantalum SiliconeNickel-plated Carbon Steel 316 SST Gold-plated Monel SiliconeCadmium-plated Carbon Steel 316 SST 316L SST Silicone316 SST 316 SST 316L SST Silicone316 SST 316 SST Hastelloy C-276 Silicone316 SST 316 SST Monel Silicone316 SST 316 SST Tantalum Silicone316 SST 316 SST Gold-plated Monel SiliconeHastelloy C Hastelloy C-276 Hastelloy C-276 SiliconeHastelloy C Hastelloy C-276 Monel SiliconeHastelloy C Hastelloy C-276 Tantalum Silicone

••••••••••••••

•••——••••——•——

••••••••••••••

•••——••••——•——

RangeabilityOutput Code Min.SpanS (DP and GP, SST, Range 3–8;

HP, SST, Range 4–7)S (all others)E, G, JLM

URL/15

URL/6URL/6URL/1.1URL/2

(2)

re-192

Page 21: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

TABLE 12. (continued).

CodeMATERIALS OF CONSTRUCTION (1)

Flanges/Adapters Drain/VentsDiaphragmsFill Fluid DP HP GP(2) AP(2)

364344454673(3)

83(3)

5A5B5C5D1A2A2B2D3B(3)

3D4B4C4D7B(3)

8B(3)

Hastelloy C Hastelloy C-276 Gold-plated Monel SiliconeMonel Monel Hastelloy C-276 SiliconeMonel Monel Monel SiliconeMonel Monel Tantalum SiliconeMonel Monel Gold-plated Monel Silicone316 SST Hastelloy C-276 Hastelloy C-276 SiliconeNickel-plated Carbon Steel Hastelloy C-276 Hastelloy C-276 SiliconeNickel-plated Carbon Steel 316 SST 316L SST InertNickel-plated Carbon Steel 316 SST Hastelloy C-276 InertNickel-plated Carbon Steel 316 SST Monel InertNickel-plated Carbon Steel 316 SST Tantalum InertCadmium-plated Carbon Steel 316 SST 316L SST Inert316 SST 316 SST 316L SST Inert316 SST 316 SST Hastelloy C-276 Inert316 SST 316 SST Tantalum InertHastelloy C Hastelloy C-276 Hastelloy C-276 InertHastelloy C Hastelloy C-276 Tantalum InertMonel Monel Hastelloy C-276 InertMonel Monel Monel InertMonel Monel Tantalum Inert316 SST Hastelloy C-276 Hastelloy C-276 InertNickel-plated Carbon Steel Hastelloy C-276 Hastelloy C-276 Inert

••••••••••••••••••••••

—••——••———————————————

••••••••••••••••••••••

—••——••———————————————

Code Mounting Brackets (Optional – Select One) DP HP GP AP

B1B2B3B4B5B6B7B9

Bracket, 2-in. Pipe MountBracket, Panel MountBracket, Flat, 2-in. Pipe MountB1 Bracket w/Series 316 SST BoltsB2 Bracket w/Series 316 SST BoltsB3 Bracket w/Series 316 SST Bolts316 SST B1 Bracket with 316 SST Bolts316 SST B3 Bracket with 316 SST Bolts

••••••••

••••••••

••••••••

••••••••

Code Meters (optional - select one) DP HP GP AP

M1(4)

M2(5)

M3(4)

M4(4)

M6(5)

M7(6)

M8(7)

M9(7)

Analog Scale, Linear Meter, 0–100%Analog Scale, Square Root Meter, 0–100% FlowAnalog Scale, Linear Meter, Special ScaleLCD Meter, Linear Meter, 0–100%, User SelectableAnalog Scale, Square Root Meter, 1–10√LCD Meter, Linear Meter, Special ConfigurationLCD Meter Square Root Meter, 0–100% FlowLCD Meter, Square Root Meter, 0–10√

••••••••

••••••••

•—••—•——

•—••—•——

(1) Bolts and conduit plugs are plated carbon steel.

(2) On GP and AP transmitters, the low-side flange is plated carbon steel.For a stainless-steel low-side flange, order process connections Option Code D6.

(3) These selections meet NACE material recommendations per MR 01-75.

(4) Not available with Output Codes L or M, or Option Codes Zx, V2, or V3.

(5) Not available with Output Codes J, L, M, or Option Codes Zx, V2, or V3.

(6) Not available with Output Codes G, L, M, or Option Codes Zx, V2, or V3.

(7) Not available with Output Codes G, J, L, M, or Option Codes Zx, V2, or V3.

(2)

Pressure-193

Page 22: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

TABLE 12. (continued).

Code Certifications (optional - select one) DP HP GP AP

I5(1)

K5C5(2)

C6(1)

K6E4E7E8I1(3)

I7(4)

I8(5)

N1(6)

N7IC(3)

Q4Q8(7)

Factory Mutual (FM) Non-incendive and Intrinsic Safety ApprovalFactory Mutual (FM) Explosion-Proof and Intrinsic Safety CombinationIndustry and Science Canada (ISC) Approval (Available in Canada Only)Combination of I6 and E6; CSA Explosion-Proof and Intrinsic Safety Approval

(Requires 42.4 V dc max. power supply)CSA/CENELEC Explosion-Proof and Intrinsic Safety ApprovalJapanese Industrial Standards (JIS) Flameproof CertificationStandards Association of Australia (SAA) Flameproof CertificationCESI/CENELEC Flameproof CertificationBASEEFA Intrinsic Safety CertificationStandards Association of Australia (SAA) Intrinsic Safety CertificationCESI/CENELEC Flameproof CertificationBASEEFA Type N CertificationStandards Association of Australia (SAA) Non-incendive Safety ApprovalSchweizerischer Elektrochnischer Verein (SEV) Intrinsic Safety CertificationCalibration Data SheetMaterial Traceability per EN 10204 3.1B

•••

•••••••••••••

•••

•••••••••••••

•••

•••••••••••••

•••

•••••••••••••

Code Housing DP HP GP AP

H1(8)

H2(8)

H3H4C1C2J1

SST Non-wetted Parts on Transmitter without MeterSST Non-wetted Parts on Transmitter with MeterSST Housing, Covers, Conduit Plug, Lock-nut, Without MeterSST Housing, Covers, Conduit Plug, Lock-nut, With MeterPG 13.5 Conduit Threads (Available in Germany Only)M20 Conduit Threads (Available in Germany Only)G½ Conduit Threads

•••••••

•••••••

•••••••

•••••••

Code Terminal Blocks DP HP GP AP

R1 Integral Transient Protection (Only available with Option Code S and E electronics) • • • •

Code Bolts for Flanges and Adapters (optional - select one) DP HP GP AP

L3L4L5

ASTM A193-B7 Flange and Adapter Bolts316 SST Flange and Adapter BoltsASTM A193-B7M Flange and Adapter Bolts

•••

•••

•••

•••

(1) Not available with Output Code G or Option Code Zx.

(2) Not available with Option Codes M1–M9.

(3) Not available with Output Codes G, J, L, M, or Option Code Zx.

(4) Not available with Output Code G or Option Code Zx.

(5) Not available with Output Codes G, J, L, M, S, or Option Code Zx.

(6) Not available with Output Codes G, L, M, or Option Code Zx.

(7) This option is available for the transmitter flange and adapters.

(8) Option includes SST housing, covers, conduit plug, locknut, L4 bolting, and D6 low side blank flange for GP and AP transmitters.Option Codes L4 and D6 parts are included with housing Option Codes H1 and H2.

NOTEFM explosion-proofapproval is standard.

re-194

Page 23: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

TABLE 12. (continued).

Code Process Connections (optional (1)) DP HP GP AP

D1

D2

D3

D4

D5

D6

D9

G1G2G3G4G5G6K1(2)

K2(2)

S1(3)

S2(3)

S4(4)

Side Drain/Vent, Top

Side Drain/Vent, Bottom

Process Adapters Deleted

Conformance to DIN 19213 and DIN 50049 3.1B Ranges 3, 4, 5(Available in Germany Only)Conformance to DIN 19213 and DIN 50049 3.1B Ranges 6, 7, 8, without¼ NPT Threads or Drain/Vent Valve Connections (Available in Germany Only)316 SST Low Side Blank Flange

JIS Process Connection–RC ¼ Flange with RC ½ Flange Adapter

DIN Spacing (Single Entry Port, No Side V/D Hole Flange)DIN Spacing (Single Entry Port, Two Side V/D Hole Flange)DIN Spacing (Dual Entry Port, No Side V/D Hole Flange)DIN Spacing (Dual Entry Port, One Top Side V/D Hole Flange)DIN Spacing (Dual Entry Port, One Bottom Side V/D Hole Flange)DIN Spacing (Dual Entry Port, Two Side V/D Hole Flange)Kynar insert, ¼–18 NPTKynar insert, ½–14 NPTAttachment of One Remote Seal - See PDS 00813-0100-4016Attachment of Two Remote Seals - See PDS 00813-0100-4016Attachment of Integral Orifice Assembly - See PDS 00813-0100-4686

••••••••••

•—•••••••••••••••

••••••••••

•—••••••••••————•

••••••••••

•••••••••••••••——

••••••••••

••••••••••••••———

(1) Allowable combinations are: D1, D3, D6; D2, D3, D6; and D6, S1.

(2) The maximum working pressure on this option is 300 psig. Available only with materials of construction Option Codes 1x or 2x.

(3) This option may only be used on Ranges 4–8.

(4) This option has a maximum static pressure rating of 3,000 psi, and is available for factoryassembly only without associated piping and is available only for Ranges 2, 3, 4, and 5.

{ 316 SSTHastelloy C-276Monel316 SSTHastelloy C-276Monel316 SSTHastelloy CMonel

{{

Carbon Steel316 SSTHastelloy CMonel

{

Pressure-195

Mod

el11

51

Page 24: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

TABLE 12. (continued).

Code Wetted O-ring Material DP HP GP AP

W2W3W4W6(1)

Buna-NEthylene-PropyleneAflasSpring-loaded Teflon

••••

•••—

••••

••••

Code Procedures DP HP GP AP

C9(2)

P1(3)

P2(4)

P3P4P5P7(5)

P8(6)

Software ConfigurationHydrostatic Testing, 150% Maximum Working PressureCleaning for Special ServiceCleaning for <1 PPM Chlorine/FluorineCalibrate at Line PressureCalibrate at Specific TemperatureImproved Temperature CoefficientCalibrate to 0.1% Accuracy

••••••••

••••••••

•••——•••

•••—••——

Code Outputs DP HP GP AP

V1(7)

V2(8)

V3(8)

Z1(9)

Z2(9)

Z3(9)

Reverse Output4–20 mV Test Signal20–100 mV Test Signal4-wire, 0–20 mA Output4-wire, 0–16 mA Output4-wire, 0–10 mA Output

—•••••

—•••••

••••••

—•••••

Typical Model Number: 1151DP 4 S 52 B3 M1

(1) Contains a Hastelloy spring that is wetted by the process; consult factory for Teflon O-ring without a spring.

(2) Available with Output Code S only.

(3) Hydrostatic testing for Range 0, 125% maximum working pressure.

(4) Fluorolube® grease on wetted O-rings.

(5) Not available on Range 10: limited to 1,500 psi on Range 9; not applicable with Output Code S.

(6) Available only with stainless steel isolators and for span of 10 inH2O and greater;not applicable with Output Code S; available only with Output Codes E, G, L, or M;not available on AP or DR transmitters.

(7) Reverse output option is not needed with smart electronics; configured via HART-based communicator.

(8) Not available with Output Codes L or M.

(9) Not available with Option Codes Mx, Vx, Ix, or Ex, or Output Codes G, L, M, or S.

re-196

Page 25: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

TABLE 13. Model 1151LT Flange-Mounted Liquid Level Transmitter.

Model Product Description

1151LT Alphaline Flange-Mounted Liquid Level Transmitter

Code Range

456

0–25 to 0–150 inH2O (0–635 to 0–3,810 mmH2O)0–125 to 0–750 inH2O (0–3,175 to 0–19,050 mmH2O)0–471 to 0–2,770 inH2O (0–11.96 to 0–70.36 mmH2O)

Code Output

SEG

1151 Smart 4–20 mA dc Electronics (see PDS 00813-0100-4593)4–20 mA dc, with Adjustable Damping10–50 mA dc, with Adjustable Damping

Code Size MaterialExtension Length

G0H0J0A0A2A4A6B0B2B4B6C0C2C4C6D0D2D4D6E0F0

2 in./DN 50316L SST Flush Mount Only2 in./DN 50Hastelloy C-276 Flush Mount Only2 in./DN 50Tantalum Flush Mount Only3 in./DN 80316L SST Flush Mount3 in./DN 80316L SST 2 in./50 mm3 in./DN 80316L SST 4 in./100 mm3 in./DN 80316L SST 6 in./150 mm4 in./DN 100316L SST Flush Mount4 in./DN 100316L SST 2 in./50 mm4 in./DN 100316L SST 4 in./100 mm4 in./DN 100316L SST 6 in./150 mm3 in./DN 80Hastelloy C-276 Flush Mount3 in./DN 80Hastelloy C-276 2 in./50 mm3 in./DN 80Hastelloy C-276 4 in./100 mm3 in./DN 80Hastelloy C-276 6 in./150 mm4 in./DN 100Hastelloy C-276 Flush Mount4 in./DN 100Hastelloy C-276 2 in./50 mm4 in./DN 100Hastelloy C-276 4 in./100 mm4 in./DN 100Hastelloy C-276 6 in./150 mm3 in./DN 80Tantalum Flush Mount Only4 in./DN 100Tantalum Flush Mount Only

Code

MOUNTING FLANGEApplicable with these High Pressure Side

Size Rating Material Diaphragm Sizes

MABNCDPEXFGYHJZLQRSVKTUW

2 in. Class 150 CS 2-in./DN 503 in. Class 150 CS 3-in./DN 804 in. Class 150 CS 4-in./DN 1002 in. Class 300 CS 2-in./DN 503 in. Class 300 CS 3-in./DN 804 in. Class 300 CS 4 in./DN 1002 in. Class 600 CS 2 in./DN 503 in. Class 600 CS 3 in./DN 802 in. Class 150 SST 2 in./DN 503 in. Class 150 SST 3 in./DN 804 in. Class 150 SST 4 in./DN 1002 in. Class 300 SST 2 in./DN 503 in. Class 300 SST 3 in./DN 804 in. Class 300 SST 4 in./DN 1002 in. Class 600 SST 2 in./DN 503 in. Class 600 SST 3 in./DN 80DN 50 PN 10-40 CS 2 in./DN 50DN 80 PN 40 CS 3 in./DN 80DN 100 PN 40 CS 4 in./DN 100DN 100 PN 10/16 CS 4 in./DN 100DN 50 PN 10-40 SST 2 in./DN 50DN 80 PN 40 SST 3 in./DN 80DN 100 PN 40 SST 4 in./DN 100DN 100 PN 10/16 SST 4 in./DN 100

Rangeability

Output CodeSE,G

Min. SpanURL/15URL/6

} When specifying these option codes, alower housing must be selected from theflushing connection options Table 14.

ANSI

DIN

NOTEExtension diameters aresized to fit Schedule 80pipe. Consult factory forSchedule 40 pipe.

Pressure-197

Page 26: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Model 1151 Alphaline ® Pressure Transmitters

Model1151

Pressu

TABLE 13. (continued).

Code

SENSOR MODULE AND LOW-SIDE MATERIALS OF CONSTRUCTIONLow-Side Flange Drain/Vent Low-Side Isolator Low-Sideand Adapter Valves Diaphragm Fluid Fill

52125522232533351A5D2A2B2D3B3D

Nickel-plated CS 316 SST 316L SST SiliconeCadmium-plated CS 316 SST 316L SST SiliconeNi Plated CS 316 SST Tantalum Silicone316 SST 316 SST 316L SST Silicone316 SST 316 SST Hastelloy C-276 Silicone316 SST 316 SST Tantalum SiliconeHastelloy C Hastelloy C-276 Hastelloy C-276 SiliconeHastelloy C Hastelloy C-276 Tantalum SiliconeCadmium-plated CS 316 SST 316L SST InertNickel-plated CS 316 SST Tantalum Inert316 SST 316 SST 316L SST Inert316 SST 316 SST Hastelloy C-276 Inert316 SST 316 SST Tantalum InertHastelloy C Hastelloy C-276 Hastelloy C-276 InertHastelloy C Hastelloy C-276 Tantalum Inert

Code Process Fill—High Pressure Side Temperature Limits

ACDHGNPS

Syltherm XLT –100 to 300 °F (–73 to 135 °C)D. C. Silicone 704 60 to 400 °F (15 to 205 °C)D. C. Silicone 200 –40 to 400 °F (–40 to 205 °C)Inert –50 to 350 °F (–45 to 177 °C)Glycerin and Water 0 to 200 °F (–17 to 93 °C)Neobee M-20 0 to 400 °F (–17 to 205 °C)Propylene Glycol and Water 0 to 200 °F (–17 to 93 °C)Syltherm 800 –50 to 400 °F (–45 to 205 °C)

re-198

Page 27: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

Rosemount Inc.

Mod

el11

51

TABLE 13. (continued).

Code Options (see complete approvals descriptions)

S1(1)

M1(2)

M3(2)

M4(2)

M7(2)

E6I5(3)

K5I6(1)

C5(4)

C6(1)

K6E4E7E8I1(5)

I7(1)

I8(6)

N1(7)

N7IC(3)

W5Q4Q8(8)

V1V2V3Z1(9)

Z2(9)

Z3(9)

F_

One Remote Seal Selected from PDS 00813-0100-4016METERSLinear Meter, 0–100% ScaleSpecial Scale Meter, Specify RangeLCD Meter, 0–100%LCD Meter, Linear, Special ConfigurationHARZARDOUS LOCATIONS CERTIFICATIONSCanadian Standards Association (CSA) Explosion-Proof ApprovalFactory Mutual (FM) Non-incendive and Intrinsic Safety ApprovalFactory Mutual (FM) Explosion-Proof and Intrinsic Safety CombinationCanadian Standards Association (CSA) Intrinsic Safety ApprovalIndustry and Science Canada (ISC) Approval (Available in Canada Only)Combination of I6 and E6; CSA Explosion-Proof and Intrinsic Safety Approval(Requires 42.4 V dc max. power supply)CSA/CENELEC Explosion-Proof and Intrinsic Safety ApprovalJapanese Industrial Standards (JIS) Flameproof CertificationStandards Association of Australia (SAA) Flameproof CertificationCESI/CENELEC Flameproof CertificationBASEEFA Intrinsic Safety CertificationStandards Association of Australia (SAA) Intrinsic Safety CertificationCESI/CENELEC Flameproof CertificationBASEEFA Type N CertificationStandards Association of Australia (SAA) Non-incendive Safety ApprovalSchweizerischer Elektrochnischer Verein (SEV) Intrinsic Safety CertificationOTHER OPTIONSCopper O-ring for Vacuum Service (Nonwetted)Calibration Data SheetMaterial Traceability per EN 10204 3.1BReverse Output4–20 mV Test Signal20–100 mV Test Signal4-wire, 0–20 mA Output4-wire, 0–16 mA Output4-wire, 0–10 mA OutputSelect One Code from Flushing Connections Lower Housing Option Table 14.

Typical Model Number: 1151LT 4 S A0 A 52 D F1

(1) For welded capillary assemblies, order sensor module and low-side materials of construction Option Code 22(refer to PDS 00813-0100-4016 for more information).

(2) Not available with Option Codes Zx, V2, or V3.

(3) Not available with Output Code G or Option Code Zx.

(4) Not available with Option Codes M1–M9.

(5) Not available with Output Codes G, J, L, M, or Option Code Zx.

(6) Not available with Output Codes G, J, L, M, S, or Option Code Zx.

(7) Not available with Output Codes G, L, M, or Option Code Zx.

(8) Available for the diaphragm, upper housing, flange, adapter, extension, and lower housing.

(9) Not available with Option Codes Mx, Vx, Ix, or Ex, or Output Codes G, L, M, or S.

NOTEFM explosion-proofapproval is standard.

TABLE 14. Flushing Connections Lower Housing Options. • available – not available

CodeFlushing Connection RingMaterial (Lower Housing)

FlushingConnections

SizeDiaphragm Size

2-in. 3-in. 4-in.

F1F2F3(1)

F4(1)

FAFC(2)

F7F8F9F0

(1) Not available with high pressure side Option Codes A0, B0, and G0.

(2) Not available with high pressure side Option Code G0.

SSTSST

Hastelloy C-276Hastelloy C-276

SSTHastelloy C-276

SSTSST

Hastelloy C-276Hastelloy C-276

1212001212

¼-18 NPT¼-18 NPT¼-18 NPT¼-18 NPT

——

½-14 NPT½-14 NPT½-14 NPT½-14 NPT

•••••••

••••

——••••

••••

——••••

Pressure-199

Page 28: Model 1151 Model 1151 Alphaline Pressure Transmitters Model 1151 Alphaline® Pressure Transmitters Model 1151 Pressure-174 INTRODUCTION This product data sheet highlights Rosemount

-Rosemountore Pte Ltd.an Crescent

Model1151

Pressu

Rosemount Inc.8200 Market BoulevardChanhassen, MN 55317 USA

Fisher-Rosemount LimitedHeath Place Bognor Regis

FisherSingap1 Pand

STANDARD ACCESSORIESAll models are shipped with flange adapters, drain/vent valves, and one instruction manual per shipment.

TaggingThe Alphaline Pressure Transmitter will be tagged, at no charge, in accordance with customer requirements. All tags are stainless steel. The standard tag is wired to the transmitter. Tag character height is 0.125 in. (0.318 cm). A permanently attached tag is available upon request.

CalibrationTransmitters are factory calibrated to the customer’s specified range. If calibration is not specified, the transmitters are calibrated at maximum range. Calibration is performed at ambient temperature and pressure.

Optional Three-Valve ManifoldsPart No. 01151-0150-0001:3-valve manifold, carbon steel for DP (Ranges 3–5), HP (Ranges 4–5). (Anderson, Greenwood & Co., M4AVIC-TR-68).

Part No. 01151-0150-0002:3-valve manifold, 316 SST with carbon steel bolts for DP (Ranges 3–5), HP (Ranges 4–5). (Anderson, Greenwood & Co., M4AVIS-TR-68).

RETROFIT KIT ORDERING INFORMATIONSpecify the 01151-0935-0001 Smart Retrofit Kit. A complete kit includes the following items:

1 Model 1151 Smart Transmitter electronics1 Electronics cover and O-ring

2 Standoffs

2 Board spacers

2 Terminal eyelets

Tel 1-800-999-9307Telex 4310012Fax (612) 949-7001© 1997 Rosemount Inc. PR

INTED

INU.S. A.

http://www.rosemount.com

¢00813-0100-4360@¤00813-0100-4360 Rev. BB 11/98

West Sussex PO22 9SHEnglandTel 44 (1243) 863 121Fax 44 (1243) 867 5541

SingapTel (65)Fax (65Tlx RS

re-200

Other Model 1151 Literature00813-0100-4593Model 1151 Smart Pressure Transmitters

00813-0100-4294Model 1151DR Draft Range DifferentialPressure Transmitter

(Pressure-231)Filled Systems for Pressure Transmitters

00813-0100-4594Model 1151 Smart Retrofit Kit

Rosemount, the Rosemount logotype, and SMART FAMILY are registeredtrademarks of Rosemount Inc.HART is a registered trademark of the HART Communication Foundation.d-Cell, Rosemount System 3, and RMV9000 are trademarks of Rosemount Inc.Fluorolube is a registered trademark of Hooker Chemical Co.Hastelloy, Hastelloy C, and Hastelloy C-276 are registered trademarks of CabotCorp.Monel is a registered trademark of International Nickel Co.Viton is a registered trademark of E.I. du Pont de Nemours & Co.Neobee M-20 is a registered trademark of Stepan Chemical Co.Syltherm and D.C. are registered trademarks of Dow Corning Corp.Teflon is a registered trademark of E.I. du Pont de Nemours & Co.Aflas is a registered trademark of Asahi Glass Co., Ltd.Kynar is a trademark of Pennwalt Inc.