+ All Categories
Home > Documents > Model 175/215/270 Steam Sterilizer - Skytron · 0520 1 0/0 Model 175/215/270 Steam Sterilizer...

Model 175/215/270 Steam Sterilizer - Skytron · 0520 1 0/0 Model 175/215/270 Steam Sterilizer...

Date post: 08-Aug-2018
Category:
Upload: trinhdiep
View: 221 times
Download: 0 times
Share this document with a friend
6
TEC-F-0520 REV1 04/30 Model 175/215/270 Steam Sterilizer powered by Pre-installation Planning Guide Skytron’s objective is to provide a program and guideline to assist individuals (hospital owners, architects, structural engineers) responsible for the Installation and operation of the sterilizer. Skytron can provide a set of drawings of the sterilizer and facility drawings showing the sterilizer set in its intended position if requested. Signed drawings are required for 270 recessed installations. Skytron is not responsible for local permits and codes.
Transcript

TEC-F-0520 REV1 04/30

Model 175/215/270 Steam Sterilizerpowered by

Pre-installation Planning GuideSkytron’s objective is to provide a program and guideline to assist individuals (hospital owners, architects, structural engineers) responsible for the Installation and operation of the sterilizer.Skytron can provide a set of drawings of the sterilizer and facility drawings showing the sterilizer set in its intended position if requested. Signed drawings are required for 270 recessed installations.

Skytron is not responsible for local permits and codes.

COMPETENCY AND INSTALLATION REQUIREMENTS

This product is a Class 2 medical device that is subject to FDA Part 820 requirements. Installation can only take place by qualified and trained individuals. An Installation Qualification Report is required as proof of system operational validation prior to clinical use.

Contact Skytron for installation needs.

The base language for this document is ENGLISH. Any translations must be from the base language document.

Printed copies are not controlled documents.

Although current at the time of publication, SKYTRON'S policy of continuous development makes this manual subject to change without notice. If current manuals are required, contact your local SKYTRON representative or contact SKYTRON directly at the distribution address listed above.

Distributed by:US - SKYTRON5085 Corporate Exchange Blvd. S.E.Grand Rapids, MI 49512 (616) 656-2900www.skytron.us

Page 1

Sterilizer Pre-installation Planning Guide • REV1

SKYTRON RESPONSIBILITIES

1. SKYTRON will provide the customer with a data sheet for 175/215 sterilizer models or an equipment drawing for (specific) 270 models showing basic locations and specifications for all utilities.2. SKYTRON/DISTRIBUTOR will provide the appropriate specialized technical staff to complete final system; configuration, power up, and testing.3. SKYTRON will provide specific seismic calculations, if applicable. Seismic installation should be approved by a structural engineer.4. SKYTRON will arrange the delivery date and delivery site details with the transportation company responsible for delivering the sterilizer.

NoticeFor Integrity 270 model sterilizer (only) SKYTRON requires a minimum of 60 days delivery time from receipt of signed drawings and Order Production-Install (OPI) document.

DISTRIBUTOR/REPRESENTATIVE RESPONSIBILITIES

1. Distributor/Representative will conduct a pre-installation visit(s) to the facility to inspect the site. Identify and document any poor physical accessibility for installation and future service. Measure all openings from the receiving point to the final sterilizer location. Verify utilities Power/Water/Drain/Steam and HVAC for recessed installations.2. Distributor/Representative will become aware of any safety requirements, union requirements, applicable local codes and other site specific conditions that may apply.3. Distributor/Representative will notify Skytron, as soon as possible, of the delivery date and site details, plus any special delivery/freight truck, shipping, and/or delivery requirements.4. Distributor/Representative will communicate any change orders or project delays to Skytron.5. Distributor/Representative will make the necessary accommodations to unload and move the sterilizer into the facility at its final destination. This requires appropriate equipment, i.e. pallet jack, fork lift, or designated lifting device.6. Distributor/Representative will complete the Installation Report and Start Up Checklist to comply with FDA’s Good Manufacturing Practice and Skytron’s Device History Record, sent to Skytron immediately after start-up is complete.

CUSTOMER RESPONSIBILITIES

1. Customer will designate a representative to coordinate and approve the installation. The customer representative will be responsible for final approval of the work within ten days of completion, at which time the representative will also approve the final SKYTRON invoice.2. Customer will verify the sterilizer installation is in accordance with all applicable local codes.3. Customer will provide SKYTRON with the appropriate room drawings to include Plan, Electrical, and Mechanical Drawings if applicable for the project.4. Customer will supply and install all conduit and electrical junction boxes and complete all electrical connections in accordance with the National Electrical Code (NEC) and all applicable local and state electrical codes.Electrical connections must be installed by a qualified electrician in accordance with ANSI/NFPA70 standards, using UL (Underwriters Laboratory) recognized materials.5. Customer will test feed water supply prior to initial startup. A water test kit and analysis from Skytron (P/N WQ-TEST) may be purchased, or test locally. If mineral content exceeds the limits below, external treatment may be necessary.

Feed Water Quality Nominal Conditions

Sterilizer with facility supplied steam

Total hardness as CaCO²: 50 -120 mg/L, maximum 171 mg/L

Total Dissolved Solids: 100 -200 mg/L, maximum 500 mg/L

pH: 6.8 - 7.5, maximum 8.5

Sterilizer with Integrated Steam Generator

Total hardness as CaCO²: 0 - 17 mg/L, maximum 130 mg/L

Total Dissolved Solids: 50 -150 mg/L, maximum 250 mg/L

Total Silica: 0.1 - 1.0 mg/L, maximum 2.5 mg/L

pH: 6.8 - 7.5, maximum 8.5

Resistivity: ohm-cm 3,000 - 10,000, max 40,000Conductivity: 100 - 300 µS/cm, max 25 µS/cm

Page 2

Sterilizer Pre-installation Planning Guide • REV1

PLUMBING & UTILITY REQUIREMENTS

– Integrity™ 175 & 175SG

Recirculation Tank Overflow Drain – 1” NPT connection provided.Sanitary Floor Sink: 12” (305 mm) square x 8” (203 mm) deep with minimum 2” ID drain to accommodate peak water consumption of 2.9 gpm (11 Lpm) recommended.

Recirculation Tank Manual Drain – ⅜” ODT

Cold Water Supply – ½” NPT connection provided.Dynamic Pressure: 30 to 50 psi (0.21 - 0.34 MPa) Flow Rate: 6 gpm (22.7 Lpm)Temperature: 50° to 77° F (10 to 25 °C)Vacuum breaker, back flow preventer, and shutoff valve required.

Jacket Pressure Relief Valve – 1" NPT outlet.ASME Boiler and Pressure Vessel Code Section VIII, Div. 1, UG-135 piping practices recommended. Check local codes for special requirements.

System Electrical Power – 13’ 4” (4 m) Length Power Cord with 3 prong grounded plug provided. Dedicated Outlet: 120 VAC, 60 Hz, single phase, properly grounded and circuit protected outlet recommended.

– Integrity™ 175

Facility Steam – ½” NPT connection provided.Dynamic Pressure: 50 - 80 psi (0.34 - 0.55 MPa)Flow Rate: 65 lb/hour (30 kg/hr)Condensate Free 97% - 100% saturated vapor.

– Integrity™ 175SG

Steam Generator Pressure Relief Valve – 1" NPT outlet.ASME Boiler and Pressure Vessel Code Section VIII, Div. 1, UG-135 piping practices recommended. Check local codes for special requirements.

Steam Generator Manual Drain – ⅜” ODT

Steam Generator Electrical Power – 208 VAC, 60 Hz, 3 phase, 50 A 480 VAC, 60 Hz, 3 phase, 20 AREQUIRED: Appropriately sized wiring L1, L2, L3 and Ground as well as a three phase, circuit protected Main Disconnect Switch (with lockout in the OFF position) located near the sterilizer.

6. Customer will provide proper drainage in accordance with applicable local codes. Temperature of drain water will not exceed 140° F (60 °C) under normal operation.7. Customer will provide all required utilities in place and in working order for SKYTRON to complete sterilizer installation and testing.Make sure that house steam and water lines are properly and completely blown down to remove construction contaminants from the system prior to making the connection to the sterilizer. A failure to do this could result in unwarranted damage to the sterilizer generating additional labor and cost to repair.If customer provided systems are not in place and working during the installation, delays may occur and result in additional charges added to the final invoice. If return trips are necessary due to a lack of customer supplied equipment, additional daily charges may occur.8. Customer and/or Distributor will be responsible for supply and installation of drywall and trim required for recessed installations.During construction, precautions must be taken to protect the sterilizer from the workers/contractors and construction materials such as: paint, drywall compounds, dust, and any other debris.

9. Customer will become familiar with the warranty coverage requirements, rights, and responsibilities. The Skytron Integrity Series Sterilizer includes a comprehensive warranty guarantee. Part of the warranty terms requires customer participation and action.

OPERATING ENVIRONMENT

• Ambient temperature: 41°-104° F (5 - 40 °C)• Relative humidity: 30% - 85% RH• Atmospheric pressure: 11.6 psi - 15.4 psi (800 - 1060 mbar)• To maintain a safe operating environment, below the maximum of 104° F (40 °C) may require ventilation equipment.

Page 3

Sterilizer Pre-installation Planning Guide • REV1

– Integrity™ 270

Recirculation Tank Overflow Drain – 1½” NPT connection provided.Sanitary Floor Sink: 12” (305 mm) square x 8” (203 mm) deep with minimum 2” ID drain to accommodate peak water consumption of 10.6 gpm (40 Lpm) recommended.

Recirculation Tank Manual Drain – ⅜” ODT

Cold Water Supply – ¾” NPT connection provided.Dynamic Pressure: 30 to 50 psi (0.21 - 0.34 MPa) Flow Rate: 6 gpm (22.7 Lpm)Temperature: 50° to 77° F (10 to 25 °C)Vacuum breaker, back flow preventer, and shutoff valve required.

Jacket Pressure Relief Valve – 1" NPT outlet.ASME Boiler and Pressure Vessel Code Section VIII, Div. 1, UG-135 piping practices recommended. Check local codes for special requirements.

Facility Steam – 1” NPT connection provided.Dynamic Pressure: 50 - 80 psi (0.34 - 0.55 MPa) Flow Rate: 220 lb/hour (100 kg/hour)Condensate free 97% - 100% saturated vapor.

System Electrical Power – 13’ 4” (4 m) Length Power Cord with 3 prong grounded plug provided. Dedicated Outlet: 120 VAC, 60 Hz, single phase, properly grounded and circuit protected outlet recommended.

Vacuum Pump Electrical Power (Optional) – 208 VAC, 60 Hz, 3 phase, 15A 480 VAC, 60 Hz, 3 phase, 7AREQUIRED: Appropriately sized wiring L1, L2, L3 and Ground as well as a three phase, circuit protected Main Disconnect Switch (with lockout in the OFF position) located near the sterilizer.

– Integrity™ 215 &215SG

Recirculation Tank Overflow Drain – 1” NPT connection provided.Sanitary Floor Sink: 12” (305 mm) square x 8” (203 mm) deep with minimum 2” ID drain to accommodate peak water consumption of 4.2 gpm (16 Lpm) recommended.

Recirculation Tank Manual Drain – ⅜” ODT

Cold Water Supply – ½” NPT connection provided.Dynamic Pressure: 30 to 50 psi (0.21 - 0.34 MPa) Flow Rate: 6 gpm (22.7 Lpm)Temperature: 50° to 70° F (10 to 21 °C).Vacuum breaker, back flow preventer, and shutoff valve required.

Jacket Pressure Relief Valve – 1" NPT outlet.ASME Boiler and Pressure Vessel Code Section VIII, Div. 1, UG-135 piping practices recommended. Check local codes for special requirements.

System Electrical Power – 13’ 4” (4 m) Length Power Cord with 3 prong grounded plug provided. Dedicated Outlet: 120 VAC, 60 Hz, single phase, properly grounded and circuit protected outlet recommended.

– Integrity™ 215

Facility Steam – ½” NPT connection provided.Dynamic Pressure: 50 - 80 psi (0.34 - 0.55 MPa) Flow Rate: 100 lb/hour (50 kg/hour)Condensate free 97% - 100% saturated vapor.

– Integrity™ 215SG

Steam Generator Pressure Relief Valve – 1" NPT outlet.ASME Boiler and Pressure Vessel Code Section VIII, Div. 1, UG-135 piping practices recommended.Check local codes for special requirements.

Steam Generator Manual Drain – ⅜” ODT

Steam Generator Electrical Power – 208 VAC, 60 Hz, 3 phase, 75A 480 VAC, 60 Hz, 3 phase, 33AREQUIRED: Appropriately sized wiring L1, L2, L3 and Ground as well as a three phase, circuit protected Main Disconnect Switch (with lockout in the OFF position) located near the sterilizer.

5085 Corporate Exchange Blvd. S.E.Grand Rapids, MI 49512 • 1.616.656.2900 • FAX 1.616.656.2906

Page 4

STERILIZER WEIGHT AND SHIPPING CRATE (APPROXIMATE) MEASUREMENTS

Model Configuration Total WeightApproximate

Crate Dimensions Length x Width x Height

175Single Door Recessed 1254 lbs (569 kg)

58” x 42” x 88” (1473 x 1067 x 2235 mm)

Single Door Freestanding 1419 lbs (624 kg)

175SGSingle Door Recessed - Steam Generator 1375 lbs (644 kg)

Single Door Freestanding - Steam Generator 1540 lbs (699 kg)

215Single Door Recessed 1716 lbs (780 kg)

64” x 46” x 88” (1626 x 1168 x 2235 mm)

Single Door Freestanding 1881 lbs (653 kg)

215SGSingle Door Recessed - Steam Generator 1859 lbs (845 kg)

Single Door Freestanding - Steam Generator 2036 lbs (924 kg)

270

Single Door Recessed - Venturi 3342 lbs (1516 kg) Sterilizer

Mechanical Cart

Loading Carriage

Freestanding Enclosure (optional)

64” x 75” x 88” (1880 x 1626 x 2184 mm)

44” x 44” x 79” (1143 x 1118 x 2032 mm)

69” x 32” x 48” (1753 x 813 x 1219 mm)

84” x 52” x 21” (2134 x 1321 x 533 mm)

Single Door Freestanding - Venturi 3765 lbs (1708 kg)

Single Door Recessed - Vacuum Pump 3549 lbs (1610 kg)

Single Door Freestanding - Vacuum Pump 3964 lbs (1798 kg)

Dual Door Recessed - Venturi 3779 lbs (1714 kg)

Dual Door Recessed - Vacuum Pump 3986 lbs (1808 kg)

NoticeShipping crates and pallets are made of wood. Provisions for appropriate disposal is required.


Recommended