+ All Categories
Home > Documents > Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model...

Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model...

Date post: 11-Mar-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
20
HAWS ® P/N 0510000457 Rev.3 11/16 Model 8780 Page 1 of 20 1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: [email protected] Website: www.hawsco.com No. 0510000457(3) Model 8780 Tempering Skid General Area Classification & Class I Division 2 INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
Transcript
Page 1: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 1 of 20

1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: [email protected] Website: www.hawsco.com

No. 0510000457(3)

Model 8780

Tempering Skid General Area Classification & Class I Division 2

INSTALLATION, OPERATION &

MAINTENANCE INSTRUCTIONS

Page 2: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 2 of 20

IMPORTANT Read this installation manual completely to ensure proper installation, then file it with the owner or

maintenance department. Compliance and conformity to drain requirements and other local codes and

ordinances is the responsibility of the installer.

Separate parts from packaging and make sure all parts are accounted for before discarding any

packaging material. If any parts are missing, do not begin installation until you obtain the missing parts.

Flush the water supply lines before beginning installation and after installation is complete. Test the unit

for leaks and adequate water flow. Main water supply to the emergency fixture should be “ON” at all

times. Provisions shall be made to prevent the unauthorized shutoff. Please refer to the enclosed

instructions for flushing the unit prior to use.

The ANSI Z358.1 standard requires an uninterrupted supply of flushing fluid. Haws plumbed emergency

fixtures requires a minimum of 45-90 PSI flowing pressure. Flushing fluid should be tepid per ANSI

Z358.1.

The inspection and testing results of this equipment should be recorded weekly to verify proper

operation. This equipment should be inspected annually to ensure compliance with ANSI Z358.1.

Installation and maintenance of this system must be completed by a qualified plumber and electrician in

accordance to the information contained in this installation manual and in compliance with all national

and local codes. When making electrical connections be sure to follow all lockout-tag out safety

procedures.

It is recommended that all water supply and electrical connections be made at temperatures above

freezing (32ºF (0ºC)). Failure to do so may result in major product and or property damage.

For technical support, contact Haws' authorized service provider, Zevado™ | (888) 508-8065 | www.zevado.com

Page 3: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 3 of 20

DESCRIPTION OF PRODUCT

Haws Corporation Performance Series model 8780 tempered water system is situated upon a fiber

reinforced skid. The bright yellow, fiber-reinforced membrane is waterproof, chemically resistant, and

protected with UV inhibitors for a long lasting finish. This system includes a standard 480 voltage, 3 phase

power circuit and has additional 5 voltage options available. The entire electrical system is designed for a

wet/wash down area and can be NEMA or Class 1 Division 2 rated.

Hot water, generated via 4kW or 6kW immersion heater (determined by tank size), is stored in a chosen

tank size of 119, 120, 200 or 330 gallons. Hot and cold water are mixed with an engineered blending

system to provide warm water for one or two, in the case of a 330 gallon tank, combination shower/eyewash

unit(s) running at a maximum of 30 GPM. The blending system is a safe, prepackaged, fully engineered

and tested system for mixing large volumes of hot and cold water specifically designed for emergency

showers and eyewashes. The system provides multiple levels of protection to prevent scalding, including a

high temperature shutoff valve. Also included is a pressure relief cold-water bypass that protects against

constricted flow. There are no electrical components in the blending system. Dry contacts are provided for

remote alarm hookup.

SHIPPING, HANDLING AND STORAGE

Performance Series Model Description Dimensions

W x L x H Weight Dimensions W x L x H (Crated)

Weight (Crated)

8780.21.3X

Tempering Skid 60” x 60” x 102”

970 lbs.

69” x 69” x 106”

1200 lbs. 8780.22.3X 970 lbs. 1200 lbs. 8780.23.3X 1700 lbs. 2150 lbs. 8780.25.3X 1020 lbs. 1350 lbs.

Recommended Equipment, Materials and Supplies to be provided by Installer:

• Concrete slab rated to support a minimum of 6,000 pound load requirement.

• (4) 3/4” minimum diameter by 1-1/2" minimum length anchor bolts with washers.

• A forklift capable of lifting 5,000 lbs. should be utilized to transport the unit from truck to site. The

unit should be lifted from the rear or equipment end and low to the ground.

• Electrical Supply Materials (if applicable).

• Plumping Supply Materials (if applicable).

• Freeze protection equipment for the water supply leading up to the enclosure (if applicable).

Storage

The unit should be stored in a clean, dry place until ready for installation unless otherwise specified.

WARNING: DO NOT connect power before plumbing and supply and drain lines. Connections should be performed by a certified electrician and plumber only.

Page 4: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 4 of 20

INSTALLATION PROCEDURE

a. Remove unit from crate.

b. The unit should be secured on a level site, using the supplied brackets and suitable anchoring

devices. Suggested anchoring devices are 3/4” minimum diameter by 3/4" minimum length anchor

bolts with washers.

c. If the skid is to be placed over a drain, the drain should be able to handle a flow of 35 GPM,

otherwise, the slab should allow the water to drain out the sides and away from the booth.

WARNING: Failure to allow water to drain may result in premature failure of booth and void of product warranty.

d. The expansion tank should be pre-charged with

compressed air to a pressure equal to the water supply

pressure. An air fitting is accessible on the top of the

expansion tank, under the plastic cap.

e. The connection provided for the water supply is a 1-1/2” NPT union and 1-1/4” NPT union tempered

water outlet. Supply lines are expected to be capable of supplying 30 GPM of potable water at a

dynamic pressure of 45-90 psi. The water supply line should run for a few minutes to eliminate any

debris before it enters the equipment.

f. Electrical supply connection must be made to the disconnect switch

junction box.

CAUTION: Do not apply power to the unit until all water connections are made and the tank and piping are full of water. Applying power prematurely will damage the equipment.

Page 5: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 5 of 20

g. Once all water and power connections are made, open an emergency shower or eyewash valve to eliminate any air that may be in the lines, and allow water in the system to flow. Inspect

plumbing for leaks and repair as necessary. During transit, some plumbing may have become

loose, allowing water to leak from the threads. Once the plumbing has been checked, the shower

should run for several minutes to evacuate any debris that might have entered the system. Turn

shower off once water is clear of debris.

h. At this point the power can be turned on. The tank water must be allowed to heat up before the

blending system will function properly. Heating can take up to several hours, depending on supply

water temperature, size of immersion heater and tank.

CAUTION: Before turning on the power, close all electrical boxes.

NOTE: The emergency shower or eyewash should be utilized for testing of the blending system. Refer to

the Maintenance, Testing, and Repair section of the Blending System Manual document for proper

adjustment and operation.

i. Activate shower again to fill the system with as much tempered water as possible. As the warm

water reaches the shower, it can be shut off.

WARNING: System is not freeze protected without an energized electrical connection. It is recommended that installation be completed when ambient temperature is above freezing.

Page 6: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 6 of 20

CHECK LIST FOR START-UP Complete OK

Inspector Initials

Pre-connection Check Check all components for any connections or connectors that may have loosened

during shipping.

System Flush (All Electrical Power off for System Flush) Verify that a minimum of 45 psi and maximum 90 psi is supplied to the inlet of the hot

water tank.

Drain is able to handle a flow of 35 GPM (if applicable).

System water supply is connected and all water supply valves opened.

Water is clear and free of any contamination, particles or discoloration.

Connections System is charged with water and all air is evacuated from the system.

Connect remote monitoring via plant control system (if applicable).

Applying Power to the System Verify that the proper voltage is present.

Verify that equipment ground is properly connected.

Apply power to the system.

The tank heater set point is preset in the program. It may take 4 to 6 hours for the

tank to reach the operating temperature. Once the tank has reached operating

temperature for a minimum of 1 hour, press the “↑” arrow and record these values in

the chart provided in the Tank Monitor section of the program narrative included in

this manual.

Shower and Eye/Facewash (if applicable) Flow water through an eyewash or shower.

Blending Valve When shower is activated read the center temperature gauge directly above the

blending valve to ensure to the readout is 85ºF (29ºC) ± 2º.

Programmable Logic Controller Display Set the current time and date in the controller (see instructions on page 7).

Page 7: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 7 of 20

Setting Current Time and Date on the Controller

• Press the “SHIFT” and “OK” buttons to enter the menu.

• Press “4” to enter setup.

• Press “1” to set date or “2” to set time.

• After date or time is set, press the “SHIFT” and “↑” key to return to setup menu.

• The Time and Date can be verified by pressing the “→” or “↓” keys while in the normal operating

screen.

NOTE: If the blending valve temperature reading is incorrect, adjust the

blending valve by turning the socket head screw counterclockwise

located on the bottom of the center section of the valve body.

Page 8: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 8 of 20

LOGIC DIAGRAM AND NARRATIVE

The program allows for monitoring the tank temperature. When no faults are present the tank temperature,

tank heater status, and flow status are displayed. There are several alarm points that are continuously

monitored. These alarms are shown on the Display as long as the fault is active. Alarm conditions may

also be monitored by connecting another control system via interposing relays and terminals provided. See

electrical schematic for details. A fault history is also provided to assist in monitoring the system

performance. Additionally, the tank heater performance can be monitored to assist in determining when

maintenance is required.

Accessing the different functions is accomplished by depressing the appropriate key(s) on the display. The

table below lists the key functions:

Key Function ← Display Fault History ↑ Display Tank Heater Monitor → Display Current Time ↓ Display Current Date 0 Reset High Tank Temp Alarm

0 & 2 Local Alarm Light Function (Off)* 1 Reset High Booth Temp Alarm*

1 & 2 Start Summer Mode* 1 & 3 Local Alarm Light Function (On)* 3 & 4 Return from Summer to Normal Mode*

*Not used on some models

Page 9: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 9 of 20

The following table lists the inputs and outputs used in the system.

NOTE: For model specific program, please contact Haws Corporation at 1-888-640-4297.

Input Function Output Function I-00 Flow Switch Q-00 Tank Heater Contactor I-01 Horn Silence Button * Q-01 Space Heater Contactor * I-02 Level Switch Q-02 Alarm Light * I-03 Booth Thermostat * Q-03 Horn *

AI-02 Tank Temperature Thermocouple Q-04 Customer Contact (Trouble) AI-03 Booth Temperature Thermocouple * Q-05 Customer Contact (Flow)

*Not used on some models

The program consists of a series of charts (sub-routines) that are grouped according to function. Each

chart will be discussed in the following sections.

Tank Control When the tank temperature is below 163°F (72°C) and 144ºF (62ºC) for the 200 gallon tank, the tank heater

contactor will close and the heater elements will be energized. When the temperature rises above 166°F

(74°C) and 146ºF (63º) for the 200 gallon tank, the contactor will open and the element will become de-

energized. A low level condition or an over temperature condition (that has not been addressed) will prohibit

the contactor from closing even if the temperature is below the set point. If the tank thermocouple falls to

a point below 32°F (0°C) a potential thermocouple failure is present and the tank heater contactor will not

close.

The customer trouble alarm contacts are monitored in this section of the program. The following conditions

will de-energize output Q-04 (customer contact trouble) when a potential fault is present:

Low Tank Temperature under 155°F (68°C)

High Tank Temperature over 168°F (76°C)

High Tank Temperature over 175°F (79°C) REQUIRES MANUAL RESET

Low Tank Level

NOTE: The high temperature alarm for the tank is designed to give a warning by displaying a fault message

and changing the state of the customer contacts before the temperature rises to a point that requires a

manual reset of the heating equipment. Should the alarm not be addressed before reaching the high set

point then the system will require additional attention and a manual reset.

Page 10: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 10 of 20

Messages

The display messages are controlled in this chart. When no faults are present, the display will present the

following conditions:

Tank Heater On (when active)

Tank Temperature

When a single fault condition is present, the display will indicate which fault condition is present. If more

than one fault condition exists, the display will cycle through each fault at 4 second intervals. Each message

will automatically clear when the condition is no longer active or when the corrective action has been taken.

This chart also records a message to the “Fault History” chart which will assign the time and date when the

fault occurred. Timer counter (TC-05 in conjunction with TC-06) will keep track of the 4 second timing

intervals and advance the message display to the next active fault (if present).

Fault History

The fault history chart keeps track of the time and date of the last occurrence of each fault. When the “left

arrow key” is depressed, the time and date of each fault will be listed on the display. There will be a 4

second delay before the first fault is displayed. Each fault will be listed for 4 seconds as long as the “left

arrow” key is depressed. The time and date of each fault are stored in registers R-004 through R-021. Once

the “left arrow” key is released the display will return to the normal condition display if no faults are present.

If there are faults in the system, the display will return to the fault display when the “left arrow” key is

released.

Tank Monitor

The tank monitor chart provides a means of monitoring the tank heater performance. This chart records

the actual amount of time that the tank heater contactor is on via registers R-050 through R-052. Counter

TC-14 cycles the chart through the last 3 on/off cycles of the tank heater contactor. TC-13 records the

actual on time of the contactor. When the unit is initially placed in service and has reached operating

temperature for several hours, the on/off cycles should be recorded in the table below. Pressing the “up

arrow” key will display the last three cycles. Each cycle will be displayed for 4 seconds as long as the key

is depressed.

CYCLE ON/OFF TIME

1 2 3

These values can be checked on a routine basis. If the amount of time that the tank heater is on has

increased, it may be an indication that the tank heater needs service or repair.

Page 11: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 11 of 20

Tank History

This tank history chart controls the display messages recorded by the tank monitor chart. TC-15 sets the

time that each message is displayed. TC-16 is used to increment from “Heater on time 1” through “Heater

on time 3”.

PREVENTATIVE MAINTENANCE

Weekly

• Verify the tank temperature readout on the display reads 165º F ± 2ºF (74ºC ± 1ºC).

• Verify area lights located inside and outside the booth are operational.

• Verify shower and eyewash flow per ANSI requirements.

• Verify temperature gauge on center pipe of blending valve reads 84ºF ± 2ºF (29ºC ± 1ºC).

Monthly

• Verify eyewash flows.

• Verify shower flow.

• Verify correct operation of mixing valve. See Maintenance section.

Quarterly

• Flush Y – strainers (if installed)

Page 12: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 12 of 20

Annually

• Check tank heater and tank for deposit buildup. Drain tank and clean/replace heater if

necessary.

• All valves should be periodically tested; at least once a year, more often if water is dirty.

• Drain tank and verify level switch operation.

Page 13: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 13 of 20

MAINTENANCE, TESTING, REPAIR

Blending Valve System

The blending valve system should require minimal amount of

maintenance. During scheduled testing, the temperature output

should be checked for proper adjustment. For a complete test, the

steps below should be followed.

1. Activate the shower to initiate flow.

2. Observe temperature on outlet. Temperature should be 84ºF ± 2°F (29ºC ± 1ºC). Let flow for

30 seconds to see if temperature remains stable.

3. Adjust mixing valve to a warmer setting until the temperature increases to roughly 88°F. This

step ensures that the hot shut-off valve and by-pass valve are working properly.

4. Adjust valve back to 70°F (21ºC) by adjusting the mixing valve in the cooler direction.

5. Slowly return temperature in the warmer direction until a constant 84ºF ± 2°F (29ºC ± 1ºC) is

maintained. Turn shower off.

NOTE: For more information, refer to the Blending Valve System O&M manual.

“Y” Strainers

“Y” strainers should be blown out at the same time as scheduled testing of showers or monthly.

For technical support, contact Haws' authorized service provider, Zevado™ | (888) 508-8065 | www.zevado.com

Page 14: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 14 of 20

TROUBLESHOOTING

TROUBLE REPAIR CHECKLIST Tank temperature too cold (set point 165°F (74ºC)

and 145ºF (63ºC) for 200 gallon tank):

a) Used recently? Full recovery for each tank and

heater size below:

• 119 gallon/4kW, 10 hours

• 120 gallon/4kW, 10 hours

• 200 gallon/4kW, 14 hours

• 330 gallon/6kW, 18 hours

b) Check controller setting (165°F/145ºF). Check

for heater on display if below 165°F/145ºF.

c) Check controller for alarms.

d) Check heater circuit fuses F1.

e) Check control voltage and power supply fuses

PFU & CFU.

Tank temperature too hot: a) Check controller setting.

b) Check alarms on controller.

Uneven water flow to eyewash (if applicable): a) Eyewash must be level.

b) Clogged flow control. Clean or replace flow

control in eyewash head.

Insufficient water flow to eyewash or shower: a) Check water supply dynamic pressure (45-90

PSI).

b) Check and clean “Y” strainers.

c) Check ball valves. Must be open and unclogged.

d) Clogged flow control.

If there are any questions that cannot be answered here, please consult Haws Corporation at 1-888-640-4297.

For technical support, contact Haws' authorized service provider, Zevado™ | (888) 508-8065 | www.zevado.com

Page 15: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 15 of 20

SPARE PARTS

Please call Haws Corporation to order spare parts: 1-888-640-4297

FUSES PRIMARY (PFU) AND CONTROLLER (CFU)

VOLTAGE PFU CFU QTY P/N QTY P/N

208V, 1PH 2 0210000298

1 0210000297

208V, 3PH 2 0210000298 240V, 1PH 2 0210000298 240V, 3PH 2 0210000298 480V, 3PH 2 0210000070 600V, 3PH 2 0210000070

FUSES TANK HEATER (F1)

VOLTAGE 4KW TANK HEATER 6KW TANK HEATER

F1 F1 QTY P/N TYPE QTY P/N TYPE

208V, 1PH 2 0210000072 KTK-R-25 2 0210000292 JKS-40 208V, 3PH 3 0210000065 KTK-R-15 3 0210000072 KTK-R-25 240V, 1PH 2 0210000072 KTK-R-25 2 0210000293 JKS-35 240V, 3PH 3 0210000065 KTK-R-15 3 0210000164 KTK-R-20 480V, 3PH 3 0210000143 KTK-R-10 3 0210000143 KTK-R-10 600V, 3PH 3 0210000142 KTK-R-6 3 0210000143 KTK-R-10

CONTACTORS

TANK HEATER (CON1)

VOLTAGE CON1 QTY P/N SIZE

208V, 1PH 1 0210000196 24V, 40A 208V, 3PH 1 0210000335 24V, 21A 240V, 1PH 1 0210000196 24V, 40A 240V, 3PH 1 0210000335 24V, 21A 480V, 3PH 1 0210000335 24V, 21A 600V, 3PH 1 0210000335 24V, 21A

Page 16: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 16 of 20

POWER SUPPLY

POWER SUPPLY VOLTAGE P/N 208V, 1PH 0210000189 208V, 3PH 0210000189 240V, 1PH 0210000189 240V, 3PH 0210000189 480V, 3PH 0210000190 600V, 3PH 0210000190

Page 17: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 17 of 20

DRAWINGS NOTE: General drawing included. Please find specific drawings on website or contact Haws Corporation.

a. Installation Drawing (8780.21.31-GA)

Page 18: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 18 of 20

b. Electrical Schematic (8780.21.31-E)

Page 19: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 19 of 20

c. Piping and Instrumentation Diagram (8780.21.31-PID)

Page 20: Model 8780 - Haws Corporation · Haws Corporation Performance 0 tempered water Series model 878system is situated upon a fiber reinforced skid. The bright yellow, fiber-reinforced

HAWS® P/N 0510000457 Rev.3 11/16 Model 8780 Page 20 of 20

LIMITED WARRANTY HAWS warrants that this specific product is guaranteed against defective material or poor workmanship for a period of one year from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale. The emergency equipment manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose for which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries. NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR GIVEN BY HAWS.

SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS MODEL PLEASE CALL: TECHNICAL SUPPORT: 1-800-766-5612

FOR CUSTOMER SERVICE: 1-888-640-4297

For technical support, contact Haws' authorized service provider, Zevado™ | (888) 508-8065 | www.zevado.com

For more information on Haws products, see our website: www.hawsco.com

© 2016 Haws® Corporation – All Rights Reserved

HAWS® and other trademarks used in these materials are the exclusive property of Haws Corporation.


Recommended