GENERATING SET TECHNICAL GUIDE GSW95V-275V Open set
MODELCODE
TECH
NIC
AL F
EATU
RES
PRIME POWER PRP kVA (kW)
Manual / Automatic control panel mounted on the genset, protected by a locking door, complete with digital control unit AC3000 for monitoring,
control and protection of the generating set.
Output
kWm
ElectronicIP23
ElectronicIP23
ALTERNATOR STAMFORDEngine governor (standard)
Protections with alarm
Protections with shutdown
• Engine protections: low fuel level, low oil pressure, high engine temperature. • Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery voltage, battery charger failure. • Circuit breaker protection: III poles. • Differential protection.
• Engine protections: low fuel level, low oil pressure, high engine temperature, low coolant level.• Genset protection: under/over voltage, overload, under/over battery voltage, battery charger failure.
• Plinth row for connection from ACP to LTS panel.• Power cables connection to terminals board (external).
IP23Insulation ClassMechanical degree of protection TypeVoltage regulation Type
MANUAL / AUTOMATIC CONTROL PANEL (ACP)
Displacement c.c.Cylinders and disposition n° disp.
TypeAspiration
Fuel consumption (100% load)
Type
L/hFuel consumption (75% load) L/h
Engine power PRP
Weight (dry)
Cooling system TypeSpeed r.p.m
DIESEL ENGINE
Fuel capacity Litres
Dimensions (LxWxH) mmAutonomy (100% load PRP) h
50
VOLVO
24013.3
2200 x 1000 x 1700
1200kg
Cos φ500.8 0.8
EMERGENCY POWER LTP kVA (kW)400/231 400/231Voltage Volt
Power factorFrequency 50
STAMFORD alternator.
MODEL|GSW95-275 Volvo
VOLVO Diesel engine.
Water cooling system with radiator.
Industrial muffler.
Complete with engine and battery liquids.
TECH
NIC
AL C
HAR
ACTE
RIST
ICS
NO
T IM
PEG
NAT
IVE
RESE
RVAT
ION
OF
MO
DIF
ICAT
ION
S FO
R IN
NO
VATI
ON
OF
THE
PR
OD
UCT
GSW450V GSW510V GSW560V GSW590V
400/231 400/231 400/231 400/231
MAN
UAL
/ A
UTO
MAT
IC C
ON
TRO
L PA
NEL
(AC
P)
Digital instrumentation
through AC3000control unit(CAN BUS).
Commands and others
GSW415VGSW310V GSW330V• Genereting set voltage (3 phases). • Mains voltage.• Generating set frequency. • Generating set current (3 phases). • Battery voltage.• Power (kVA - kW - kVAr).• Power factor Cos φ. • Hours-counter.• Engine speed r.p.m.• Fuel level (%).• Oil pressure. • Engine temperature.
Electronic
• Selector switch with six positions: Automatic test - Automatic starting - Engine locked - Mains contactor forced - Manual starting - Genset contactor forced. • Push-buttons: start/stop, up/down selection, reset.• Emergency stop button. • DC system disconnection key. • Acoustic alarm. • Automatic battery charger.
GSW95V SG281TWA
83 (66) 91 (73)
TAD530GEWater 1500
Hz
47604 L
Turbo - Intercooler
741816
Mechanical UCI224G
H
GSW110VSG331TWA
97 (78) 108 (86)
24011.4
2200 x 1000 x 1700
1250TAD531GE
Water 150047604 L
Turbo - Intercooler
86 2119
Mechanical UCI274D
H
GSW145VSG371TWA
127 (102)142 (114)
0.82408.8
2200 x 1000 x 1700
1370TAD532GE
Water 15004760
4 LTurbo - Intercooler
1142725
Electronic UCI274E
HIP23
Electronic
GSW170VSG401TWA
153 (122)170 (136)400/231
500.8240 7.5
2600 x 1000 x 1700
1820TAD731GE
Water 15007150
6 LTurbo - Intercooler
133 3229
Mechanical UCI274F
H
GSW195VSG451TWA
182 (146)200 (160)
500.840010.2
2650 x 1200 x 1800
1980TAD732GE
Turbo - Intercooler
160 3934
2650 x 1200 x 1800
Electronic UCI274G
H
Water 15007150
6 L
2200TAD733GE
71506 L
GSW220VSG501TWA
203 (162) 220(176)
500.84009.3
2650 x 1200 x 1844
Electronic UCI274H
H
Turbo - Intercooler
177 4338
Water 1500
500.84008.16
GSW275VSG571TWA
249 (199)275 (220)
2326TAD734GE
Water 1500 7150
6 LTurbo - Intercooler
213 49 39
Electronic UCD274K
HIP23
ElectronicElectronic ElectronicIP23IP23
REF. GDS 11.01
Rev.00 Pag. 1 of 2
GENERATING SET TECHNICAL GUIDE GSW310V-590V Open set
GENSET SUPPLEMENTS (ONLY AVAILABLE WHEN ORDERED)
CONTROL PANEL SUPPLEMENTS (ONLY AVAILABLE WHEN ORDERED)
CO
NTR
OL
PAN
EL S
UPP
LEM
ENTS
AFP: AUTOMATIC FUEL TRANSFER PUMP.
GEN
SET
SUPP
LEM
ENTS
RSS: REMOTE START & STOP PRE-ARRANGED FREE CONTACTS.
TECH
NIC
AL C
HAR
ACTE
RIS
TICS
NO
T IM
PEG
NAT
IVE
RES
ERVA
TIO
N O
F M
OD
IFIC
ATIO
NS
FOR
IN
NO
VATI
ON
OF
THE
PR
OD
UCT
Automatic control panel for automatic starting by Mains failure. Delivered loose from the genset, and complete
with digital control unit AC01 for monitoring, control and protection of the generating
set.
• Genereting set voltage (3 phases). • Mains voltage.• Generating set frequency. • Generating set current (3 phases). • Battery voltage.• Power (kVA - kW - kVAr).• Power factor Cos φ. • Hours-counter.• Engine speed r.p.m.• Fuel level (%).• Oil pressure. • Engine temperature.
GSW330V GSW415V GSW450VGSW310V
AUTO
MAT
IC C
ON
TRO
L PA
NEL
(AM
F)
Commands and others
Digital instrumentation
through AC-01 control unit (CAN BUS).
• Plinth row for connection from pre-wired panel (mounted on the genset) to AMF panel.• Power cables connected to terminals board (internal).
• Plinth row for connection from ACP to LTS panel. • Terminals board for power cables connection (Genset-Mains-Load).
PHS: COOLANT PREHEATING SYSTEM.
• Engine protections: low fuel level, low oil pressure, high engine temperature. • Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery voltage, battery charger failure.
• Engine protections: low fuel level, low oil pressure, high engine temperature, low coolant level.• Genset protection: under/over voltage, overload, under/over battery voltage, battery charger failure.
GSW560V
Protections with shutdown
Output
GSW590V
IV poles - 500A
LOAD TRANSFER SWITCH PANEL.
RES: RESIDENTIAL SILENCER.
FEC: FLEXIBLE EXHAUST COMPENSATOR.
Automatic control panel + LTS panel measures the Mains voltage and starts automatically the genset within few seconds in case of Mains failure. It transfers immediately the load again to the genset when the Mains voltage returns within the rated values.
Change over contactors
GSW450V GSW510V
IV poles - 1.000A
ACCE
SSO
RIE
S
Connections
Protections
RCG: REMOTE CONTROL BY GSM KIT (kit for genset management and control by remote PC; comunication available by means of RS232 directly to PC or through GSM modem). Available only for automatic versions with AC01 control unit.
GSW415V
Load transfer switch panel built in a metal cabinet and
supplied loose from the genset.
• Contactors mechanically and electrically interlocked. • Emergency stop button.
Change over contactors
Mains/Genset
GSW310V GSW330V
• Selector switch with six positions: Automatic test - Automatic starting - Engine locked - Mains contactor forced - Manual starting - Genset contactor forced. • Push-buttons: start/stop, up/down selection, reset.• Emergency stop button. • Remote starting availability. • Acoustic alarm. • Automatic battery charger.
AUTOMATIC CONTROL PANEL (AMF)
TIF: IV POLES CIRCUIT BREAKER INSTEAD OF III POLES.
ACCESSORIES
GSW510V GSW560V GSW590V
IV poles - 700A
IV poles - 1.000A
IV poles - 1.000A
GPA: ALTERNATOR IP23 PROTECTION.
IV poles - 500A
IV poles - 500A
IV poles - 700A
IV poles - 700A
Protections with alarm
IV poles - 1.000A
IV poles - 500A
IV poles - 700A
IV poles - 700A
IV poles - 700A
Rev.00 Pag. 2 of 2