MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS. Ta-Te Lin, Yi-Chung Chang Department of Agricultural Machinery Engineering, National Taiwan University, Taipei, Taiwan, R.O.C. INTRODUCTION MODEL DEVELOPMENT SIMULATION AND ANALYSES CONCLUSIONS. INTRODUCTION. - PowerPoint PPT Presentation
Popular Tags:
35
MODELING AND ANALYSES OF EVAPORATIVE MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS COOLING EFFICIENCY FOR MIST-FOG SYSTEMS Ta-Te Lin, Yi-Chung Chang Department of Agricultural Machinery Engineering, National Taiwan University, Taipei, Taiwan, R.O.C.
Transcript
Page 1: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

MODELING AND ANALYSES OF EVAPORATIVE MODELING AND ANALYSES OF EVAPORATIVE

COOLING EFFICIENCY FOR MIST-FOG SYSTEMSCOOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Ta-Te Lin, Yi-Chung Chang

Department of Agricultural Machinery Engineering,

National Taiwan University,

Taipei, Taiwan, R.O.C.

Page 2: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

INTRODUCTION

MODEL DEVELOPMENT

SIMULATION AND ANALYSES

CONCLUSIONS

Page 3: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

INTRODUCTIONINTRODUCTION

EVAPORATIVE COOLING AND ITS APPLICATIONS FACTORS AFFECTING EVAPORATIVE COOLING OBJECTIVES

Page 4: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

EVAPORATIVE COOLING AND ITS APPLICATIONSEVAPORATIVE COOLING AND ITS APPLICATIONS

Page 5: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

FACTORS AFFECTING EVAPORATIVE COOLINGFACTORS AFFECTING EVAPORATIVE COOLING

RELATIVE HUMIDITY AMBIENT TEMPERATURE DROPLET SIZE VENTILATION RATE DROPLET TRAVEL DISTANCE

Page 6: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

OBJECTIVESOBJECTIVES

To develop a theoretical model for the calculation of evaporative cooling efficiency base on mass transfer and particle dynamic theories.

To validate the model with existing laboratory data.

To analyze the influences of selected parameters, such as temperature and relative humidity, on the evaporative cooling efficiency of mist-fog systems.

Page 7: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

MODEL DEVELOPMENTMODEL DEVELOPMENT

MASS TRANSFER OF DROPLETS PARTICLE DYNAMICS CALCULATION OF PSYCHROMETRIC PARAMETERS

Page 8: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

MASS TRANSFER OF DROPLETSMASS TRANSFER OF DROPLETS

dm

dtk A PMg s v

dD

dt

M

M

D

D

P

PN Np v

m

v

p

a

l fsc re

2 2 0 6 1 3 1 2

. / /

The Goering Model:

The Basic Mass Transfer Equation:

Page 9: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Diffusivity

MASS TRANSFER OF DROPLETSMASS TRANSFER OF DROPLETS

D Tv k 5 28 10 6 188. .

Pressure Difference P P Pswb v

Partial Pressure of Air

Pressure Difference

P P Pf atm v

aatmP

gRT

Page 10: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

PARTICLE DYNAMICSPARTICLE DYNAMICS

Particle Motion:

a

d X

dt

D

mx 2

2

sin

a

d Y

dt

W D

my 2

2

cos

D D Vdm

dtf e

Drag Force Calculation:

DC AV

fd a p r 2

2

CN

Ndre

re 24

0 5.

CN

Ndre

re 26 38

0 49 0 5 2000 845

.. .

.

Page 11: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Effect of Wind Direction and Droplet Moving Angle:

Effect of Spray Nozzle Gauge Pressure:

PARTICLE DYNAMICSPARTICLE DYNAMICS

arcsin

cos cosV V

Va

r

2

arcsinV

Vx

V V Vx y 2 2 0 5.

V V V V Vr a a cos cos sin sin 2 2

VP

on

l

2

Page 12: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

PARTICLE DYNAMICSPARTICLE DYNAMICS

D

F

W

y

y

x

x

Va

VVr

£]

£^

Diagram of Particle Dynamics

Page 13: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

CALCULATION OF PSYCHROMETRIC PARAMETERSCALCULATION OF PSYCHROMETRIC PARAMETERS

P eswb

Wet Bulb Saturation Pressure:

Dry Bulb Vapor Pressure:

P P Pv swb atm ( ) / ( . / ) 1 015577

A BT CT DT ET

FT GTwb wb wb wb

wb wb

2 3 4

2

1006 9254

0 62195

.

.

P P

hT Tswb atm

fgwb

Latent Heat of Water:

h Tfg 2502535 259 2385 76424 27316. . ( . )

Page 14: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

SIMULATION AND ANALYSESSIMULATION AND ANALYSES

SIMULATION PROCEDURES VALIDATION OF THE MODEL PARTICLE SIZE AND MOVING DISTANCE EFFECT OF TEMPERATURE AND RELATIVE

HUMIDITY

Page 15: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

SIMULATION AND ANALYSESSIMULATION AND ANALYSES

SIMULATION PROCEDURES VALIDATION OF THE MODEL PARTICLE SIZE AND MOVING DISTANCE EFFECT OF TEMPERATURE AND RELATIVE

HUMIDITY

Page 16: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

SIMULATION AND ANALYSESSIMULATION AND ANALYSES

SIMULATION PROCEDURES VALIDATION OF THE MODEL PARTICLE SIZE AND MOVING DISTANCE EFFECT OF TEMPERATURE AND RELATIVE

HUMIDITY

Page 17: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

SIMULATION AND ANALYSESSIMULATION AND ANALYSES

SIMULATION PROCEDURES VALIDATION OF THE MODEL PARTICLE SIZE AND MOVING DISTANCE EFFECT OF TEMPERATURE AND RELATIVE

HUMIDITY

Page 18: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

SIMULATION AND ANALYSESSIMULATION AND ANALYSES

SIMULATION PROCEDURES VALIDATION OF THE MODEL PARTICLE SIZE AND MOVING DISTANCE EFFECT OF TEMPERATURE AND RELATIVE

HUMIDITY

Page 19: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

0. 000. 050. 100. 150. 200. 250. 300. 350. 400. 450. 500. 550. 60

1 3 5 7 9 11

13

15

17

19

21

23

25

Test Number

Eva

pora

tion

Eff

icie

ncy

( )

MeasuredPredicted

Comparisons between predicted and measured evaporation efficiencies.

Page 20: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Comparisons between predicted and measured final chamber temperature.

20

22

24

26

28

30

32

34

1 3 5 7 9 11

13

15

17

19

21

23

25

Test Number

Fina

l Cha

mbe

r Tem

pera

ture

(C

)

MeasuredPredicted

Page 21: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Droplet evaporation percentage at various moving distances under different temperatures and relative humidities. Initial droplet size is 45 microns

0

10

20

30

40

50

60

70

80

90

100

0.0 0.1 0.2 0.3 0.4 0.5Moving Distance (m)

Dro

plet

Eva

pora

tion

Per

cent

age

(%)

20℃, 80%RH30℃, 80%RH20℃, 50%RH30℃, 50%RH20℃, 30%RH30℃, 30%RH

Page 22: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Effect of droplet diameter and psychrometric parameters on the moving distance.

0.01

0.10

1.00

10.00

100.00

0 50 100 150 200

Droplet Diameter (microns)

Mov

ing

Dis

tanc

e (m

)

20 ℃, 80%

30 ℃, 80%

20 ℃, 50%

30 ℃, 50%

20 ℃, 30%

30 ℃, 30%

Page 23: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Droplet evaporation rate under different relative humidities. Dry bulb temperature is 30 and the initial droplet d℃iameter is 65 microns.

0

5

10

15

20

25

30

35

40

45

50

0 5 10 15 20 25 30 35 40

Time (s)

Eva

pora

tion

Rat

e (1

0-12 k

g/s)

RH 50%

RH 60%

RH 70%

RH 80%

RH 90%

Page 24: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Droplet evaporation rate under different relative humidities. Dry bulb temperature is 30 and the initial droplet d℃iameter is 65 microns.

0

20

40

60

80

100

120

140

160

0 5 10 15 20 25 30 35 40 Time (s)

Tot

al

Eva

pora

tion

(10

-12 k

g)

RH 50%

RH 60%

RH 70%

RH 80%

RH 90%

Page 25: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Evaporation rate of droplet with different initial diameter. Dry bulb temperature is 25 and the relative humidity i℃s 90%.

0

2

4

6

8

10

12

14

0 10 20 30 40 50 60 70 80

Time (s)

Eva

pora

tion

Rat

e (1

0-12 k

g/s) 15 microns

45 microns

65 microns

105 microns

Page 26: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Evaporation rate of droplet with different initial diameter. Dry bulb temperature is 25 and the relative humidity i℃s 90%.

0

2

4

6

8

10

12

14

0 2 4 6 8 10 12 Moving Distance (m)

Eva

pora

tion

Rat

e (1

0-12 k

g/s) 15 microns

45 microns

65 microns

105 microns

Page 27: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Evaporation efficiency as affected by droplet diameter and psychrometric parameters. The nozzle height is 1.8m.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 20 40 60 80 100 120 140 160 180 200

Droplet Diameter (microns)

Eva

pora

tion

Eff

icie

ncy

()

20℃, 80%30℃, 80%20℃, 50%30℃, 50%20℃, 30%30℃, 30%

Page 28: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Evaporation efficiency as affected by droplet diameter and psychrometric parameters. The nozzle height is 3.0m.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 20 40 60 80 100 120 140 160 180 200

Droplet Diameter (microns)

Eva

pora

tion

Eff

icie

ncy

()

20℃,80%

30℃,80%

20℃,50%

30℃,50%

20℃,30%

30℃,30%

Page 29: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Droplet evaporation percentage at various moving distances under different temperatures and relative humidities. The nozzle height is 0.9m and the droplet diameter is 65 microns.

5

20

35

50

65

80

95 21

25

29

33

37

0102030405060708090

100

EvaporationEfficiency (%)

Relative Humidity (%)

Temperature(¢ J)

Page 30: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Droplet evaporation percentage at various moving distances under different temperatures and relative humidities. The nozzle height is 0.9m and the droplet diameter is 105 microns.

5

20 35 50 65 80 95

21

25

2933

37

0102030405060708090

100

蒸發效率Evaporation

Efficiency (%)

相對溼度Relative Humidity

(%)

溫度Temperature

(¢ J)

(B)

Page 31: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Droplet evaporation percentage at various moving distances under different temperatures and relative humidities. The nozzle height is 1.2m and the droplet diameter is 65 microns.

51

5

25

35

45

55

65

75

85

95 21

24

27

3033

3639

0

10

20

30

40

50

60

70

80

90

100

蒸發效率Evaporation

Efficiency (%)

相對溼度Relative Humidity

(%)

溫度Temperature

(¢ J)

(C)

Page 32: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

FITTING WITH SIMPLE FUNCTIONS

4037.53532.5

3027.525

22.5

Temperature 〔℃〕60

6570

7580

8590

Relative Humidity (%)

10

10

20

20

30

30

40

40

50

50

60

60

70

70

80

80

90

90

100

100

Eva

pora

tion

Eff

icie

ncy

(%)

Page 33: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

Droplediameter

(m)

NozzleHeight

(m)

Best fitted function R2 Commonfunction

R2

0.6 z=a+b(lnx)2+cy1.5 0.9908 0.9755

45 0.9 z=a+blnx+cy3 0.9892 0.9718

1.2 lnz=a+bx/lnx+c/lny 0.9973 0.9970

0.6 lnz=a+b(lnx)2+cy1.5 0.9913 0.9703

65 0.9 lnz=a+bx0.5lnx+cy5 0.9952 z=a+blnx+cy 0.9769

1.2 lnz=a+blnx+cy3 0.9853 0.9756

0.6 lnz=a+bx0.5+cy1.5 0.9930 0.9587

105 0.9 lnz=a+bx0.5+cy1.5 0.9930 0.9556

1.2 lnz=a+b(inx)2+cy1.5 0.9915 0.9630

FITTING WITH SIMPLE FUNCTIONS

Page 34: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

CONCLUSIONSCONCLUSIONS

A theoretical model to predict evaporative cooling efficiency for mist-fog systems was established based on mass transfer theory and particle dynamics.

The model was validated with experimental data from existing literature and the predicted evaporation efficiency agreed well with the measured values.

The effects of temperature, relative humidity and the size of spray droplet on the cooling efficiency of mist-fog systems were analyzed with the developed model. Useful information can be generated with model simulations as an aid in designing effective mist-fog systems.

Page 35: MODELING AND ANALYSES OF EVAPORATIVE COOLING EFFICIENCY FOR MIST-FOG SYSTEMS

THANK YOUTHANK YOU