Date post: | 22-Jan-2016 |
Category: |
Documents |
Upload: | bansal-robin |
View: | 223 times |
Download: | 0 times |
Modeling of Wind Farms in the Load Flow Analysis
Project report
Submitted in partial fulfillment of the
Requirements for the award of the degree
of
Bachelor of Technology
In
Electrical Engineering
by
1. Rahul Syal (20108011)
2. Vivek Sisaudia (20108017)
3. Vikalp Dhiman (20102005)
4. Pranjal Mishra (20108090)
5. Prashant Srivastava(20102076)
Guided
by
Dr. Asheesh Kumar Singh
DEPARTMENT OF ELECTRICAL ENGINEERING
MOTILAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY-ALLAHABAD
1
MOTILAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY
ALLAHABAD
DEPARTMENT OF ELECTRICAL ENGINEERING
CERTIFICATE
We hereby certify that the work which is being presented in this project report
Modeling of Wind Farms in the Load Flow Analysis in partial fulfillment of the requirements
for the award of the Degree of Bachelor of Technology in Electrical Engineering and submitted
in the Department of Electrical Engineering of Motilal Nehru National Institute of Technology
Allahabad is an authentic record of our own work carried out during a period from July 2013 to
May 2014 under the guidance of Dr. Asheesh K.Singh.The matter presented in this project
report has not been submitted by us for the award of any other degree of this or any other
institution.
Submitted by:
1. Rahul Syal (20108011)
2. Vivek Sisaudia (20108017)
3. Vikalp Dhiman (20102005)
4. Pranjal Mishra (20108090)
5. Prashant Srivastava
(20102076)
Project Guide :
Dr. Asheesh K.Singh
2
Associate Professor
Electrical Engineering
Department
Acknowledgement
We would like to articulate our deep gratitude to our project guide Dr. Asheesh K.
Singh, Associate Professor, Electrical Engineering Department who has always been source
of motivation and firm support for carrying out the project. We express our gratitude to Dr.
Asheesh K. Singh, Associate Professor,Electrical Engineering Department for his invaluable
suggestion and constant encouragement all through the thesis work. We would also like to
convey our sincerest gratitude and indebtedness to all other faculty members and staff of
Department of Electrical Engineering, MNNIT, Allahabad who bestowed their great effort
and guidance at appropriate times without which it would have been very difficult on our
project work. An assemblage of this nature could never have been attempted with our
reference to and inspiration from the works of others whose details are mentioned in
references section. We acknowledge our indebtedness to all of them. Further, we would like
to express our feeling towards our parents and God who directly or indirectly encouraged and
motivated us during this dissertation.
3
Abstract
The purpose of this project is to Modeling of Wind Farms in the Load Flow Analysis. Two
methods are proposed, for the simulation of wind farms with asynchronous generators in the
load flow analysis. Both methods are based on the steady-state model of the induction
machine. The first involves improving the conventional PQ bus, and the second involves
modeling the generators in steady-state in the bus where the wind farm is located. The two
sets of results are then compared.
When the conventional PQ bus model is used, the real and reactive powers have constant
values, although some authors propose methods for modifying these values in order to
represent loads depending either on the voltage or on the frequency. When the PX bus model
is used, the real power is known and the reactive power is calculated as a function of the
magnetizing reactance of the generators.
Both methods suppose prior knowledge of the WT features. The turbine’s power curve is
generally supplied by the manufacturer. When the induction generator parameters are not
known, they must be estimated. One of the problems that wind energy will create in electrical
power systems is the dependence of the injected power on the wind speed. The wind speed
cannot he predicted, but the probability of a particular wind speed occurring can be estimated.
This can be done if the probability distribution is known by assuming it to be a Wei-bull
distribution.
4
Certificate of Non plagiarism
Declaration:
I have read the information pertaining to plagiarism contained in the materials for this unit
and am aware that there is further information available in the form of the Student Plagiarism
and Academic Misconduct: Coursework Policy, the document Avoiding Plagiarism and
Academic Misconduct the relevant sections on plagiarism provided in the Referencing Guide
To the best of my knowledge and belief, this assessment task is my own work, all sources have
been properly acknowledged, and the assessment task contains no plagiarism.
I have not previously submitted this work or any version of it for assessment in any other unit
or award offered by any other institution, without first ensuring that an explicit provision has
been made and that I have obtained written permission from my Unit Coordinator/Supervisor
for doing so (documentation supporting this provision MUST be attached)
I acknowledge that this assessment submission may be transferred and stored in a database
for the purposes of data-matching to help detect plagiarism.
Student’s Signature: ________________________________________________________
Student’s Signature: ________________________________________________________
Student’s Signature: ________________________________________________________
Student’s Signature: ________________________________________________________
Student’s Signature: ________________________________________________________
Date of signing: _______________________________________________________
5
Table of Content
Title 1
Certificate 2
Acknowledgement 3
Abstract 4
Certificate of Non plagiarism 5
Table of content 6
Chapter 1: WIND ENERGY- AN OVERVIEW 8
1.1 Wind energy in India 8
1.2 Economy of wind energy in India 9
1.3 Wind farms in India 10
Chapter 2: FUNDAMENTALS OF WIND TURBINES. 12
2.1 Power contained in the wind 12
2.2 Power Speed Characteristics 13
2.3 WEI-BULL Distribution 15
Chapter 3: WIND TURBINE CONTROL SYSTEMS 17
3.1 Pitch Angle Control 17
3.2 Stall Control 18
3.3 Power Electronic Control 18
3.4 Yaw Control 19
3.5 Control Strategy 20
6
Chapter 4: GRID CONNECTED AND ASYNCHRONOUS GENERATOR (DFIG)
FOR WIND TURBINES
4.1 Model of Wind Turbine 25
4.2 Generator Model 26
4.3 Requirement of the load flow analysis 28
4.4Loadflow models considered (with flow charts) 31
4.5 AC load flows and their drawbacks 36
4.6 Genetic Algorithm Approach for Solving AC DC Optimal Power
Flow
42
4.7 AC/DC load flow
43
Chapter 5: MODELS OF ASYNCHRONOUS WIND TURBINES
5.1 INTRODUCTION 46
5.2 VARIOUS TYPES OF WTGUs
50
Chapter 6: SIMULATION AND RESULT
6.1 MODELING OF THE POWER IN THE WIND POWER SYSTEM
6.2 SIMULATION 61
6.3 RESULT 63
DISCUSSION
CONCLUSION
REFERENCES
7
CHAPTER 1
WIND ENERGY- AN OVERVIEW
INTRODUCTION
The conventional energy sources are limited and pollute the environment. So more attention
and Interest have been paid to the utilization of renewable energy source such as Wind
Energy, Fuel-cell, Solar Energy etc., Wind Energy is the fastest growing and most
promising renewable Energy source among them as it is economically viable.
1.1 WIND ENERGY IN INDIA
In 2008, India was the country that brought online the third largest amount of wind energy,
after the US and China, and it now ranks fifth in total installed capacity with 9,645 MW
of wind power installed at the end of 2008. A strong domestic manufacturing base has
underpinned the growth of the Indian wind energy market. The Indian wind turbine
manufacturer Suzlon is now a recognized player on the global market and many international
companies are established in India. India has a great untapped potential for wind energy. A
strong domestic manufacturing base has underpinned the growth of the Indian wind energy
market. India has a great untapped potential for wind energy. According to official estimates,
the Country's total wind energy resource amounts to 48 GW of installed capacity, but some
experts think that this figure is on the conservative side, and that technological
improvements could significantly increase this potential. The positive development of wind
energy in India has mainly been driven by progressive state level legislation, including policy
measures such as renewable portfolio standards and feed -in-tariffs. At the moment, there is
no coherent national renewable energy policy to drive the development of wind energy.
This is urgently needed to realize the country’s full potential and reap the benefits for both the
environment and the economy. The Government of India is currently considering the
8
introduction of a national renewable energy policy, so this report comes as a timely
reminder of how important a role wind energy could play in securing India’s energy
security, curbing its CO2 emissions, providing new employment and boosting economic
development. This also realizes how important a role wind energy could play in
securing India's energy security, curbing its CO2 emissions, providing new employment
and boosting economic development. As can be seen by the Indian Wind Energy
Outlook, the wind industry, both domestic and international, stands ready to do its part in
achieving an energy revolution in India.
1.2 ECONOMY OF WIND ENERGY IN INDIA
In the early 1980s, the Indian government established the Ministry of Non-Conventional
Energy Sources (MNES) to encourage diversification of the country's energy supply, and
satisfy the increasing energy demand of a rapidly growing economy. In 2006, this ministry
was renamed the Ministry of New and Renewable Energy (MNRE). Renewable energy is
growing rapidly in India. With an installed capacity of 13.2 GW, renewable energy sources
(excluding large hydro) currently account for 9% of India's overall power generation capacity.
By 2012, the Government of India is planning to add an extra 14 GW of renewable resources in
its 10th Five Year Plan. The Government of India had set itself a target of adding 3.5 GW of
renewable energy sources to the generation mix. In reality, however, nearly double that figure
was achieved. In this period, more than 5.4 GW of wind energy was added to the
generation mix, as well as 1.3 GW from other Resources.
The Indian Ministry of New and Renewable Energy (MNRE) estimates that there is a potential
of around 90,000 MW for the country, including 48,561 MW of wind power, 14,294
MW of small hydro power and 26,367 MW of biomass In addition, the potential for
solar energy is estimated for most parts of the country at around 20 MW per square
kilometer of open, shadow free area covered with 657 GW of installed capacity.
1.3 WIND POTENTIAL
9
The total potential for wind power in India was first estimated by the Centre for Wind Energy
Technology (C-WET) at around 45 GW, and was recently increased to 48.5 GW. This figure was
also adopted by the government as the official estimate. The C-WET study was based on a
comprehensive wind mapping exercise initiated by MNRE, which established a country-wide
network of 105O wind monitoring and wind mapping stations in 25 Indian States. This effort
made it possible to assess the national wind potential and identify suitable areas for
harnessing wind power for commercial use, and 216 suitable sites have been identified.
However, the wind measurements were carried out at lower hub heights and did not take into
account technological innovation and improvements and repowering of old turbines to replace
them with bigger ones at heights of 55-65 meters, to replace them with Bigger ones. At heights
of 55-65 meters, the Indian Wind Turbine Manufacturers Isolation (IWTMA) estimates that the
12 potential for wind development in India is around 65-70 GW. The World Institute for
Sustainable Energy, India (WISE) considers that with larger turbines, greater land
availability and expanded resource exploration, the potential could be as big as 100 GW.
Wind power in India has been concentrated in a few regions, especially the Southern state of
Tamil Nadu, which maintains its position as the state with the most wind power, with 4.1 GW
installed at the end of 2008, representing 44% of India’s total wind capacity.
1.4 WIND FARMS IN INDIA
1. Muppandal–Perungudi (Tamil Nadu) With an aggregate wind power capacity of 450
MW, the Muppandal–Perungudi region near Kanyakumari in Tamil Nadu has the
distinction of having one of the largest clusters of wind turbines. About Rs 2500 crores has
been invested in wind power in this region.
2. KavdyaDonger, Supa (Maharashtra)
A wind farm project has been developed at Kavdya Donger at Supa, off the Pune–Ahmednagar
highway, about 100 km from Pune. This wind farm has 57 machines of 1-MW capacity each.
Annual utilization capacity of up to 22% has been reported from this site. The farm is
10
connected through V-SAT to project developers as well as promoters for online performance
monitoring.
3. Satara district (Maharashtra) Encouraging policy for private investment in wind power
projects has resulted in significant wind power development in Maharashtra, particularly in
the Satara district. Wind power capacity of about 340 MW has been established at
Vankusawade, Thosegarh, and Chalkewadi in Satara district, with an investment of about
Rs.1500 crores.
11
CHAPTER 2:
FUNDAMENTALS OF WIND TURBINES
2.1 Power in the wind.
Wind energy is not a constant source of energy. It varies continuously and gives energy in
sudden bursts. About 50% of the entire energy is given out in just 15% of the operating time.
Wind strengths vary and thus cannot guarantee continuous power. It is best used in the
context of a system that has significant reserve capacity such as hydro, or reserve load,
such as a desalination plant, to mitigate the economic effects of resource variability. The total
capacity of wind power on this earth that can be harnessed is about 72 TW. There are now
many thousands of wind turbines operating in various parts of the world, with utility
companies having a total capacity of 59,322 MW. The power generation by wind energy was
about 94.1GW in 2007 which makes up nearly 1% of the total power generated in the world.
Globally, the long-term technical potential of wind energy is believed to be 5 times
current global energy consumption or 40 times current electricity demand. This would require
covering 12.7% of all land area with wind turbines. This land would have to be covered with 6
large wind turbines per square kilometer. The power extracted from the wind can be
calculated by the given formula:
P=0.5× ρ×A×V 3×CP (1)
P= extracted power from the wind,
ρ = air density, (approximately 1.225 kg/m3at 20₀C at sea level)
V= wind velocity (m/s) (velocity can be controlled between 3 to 30 m/s)
12
CP =the power coefficient which is a function of both tip speed ratio, and blade pitch angle,
Power coefficient (CP ) is defined as the ratio of the output power produced to the power
available in the wind.
Betz Limit:
No wind turbine could convert more than 59.3% of the kinetic energy of the wind into
Mechanical energy turning a rotor. This is known as the Betz Limit, and is the
theoretical Maximum coefficient of power for any wind turbine. The maximum value of CP
according to Betz limit is 59.3%. For good turbines it is in the range of 35-45%.
2.2. Types of Wind energy Conversion Devices.
A wind turbine is a rotating machine which converts the kinetic energy in wind into mechanical
energy. If the mechanical energy is then converted to electricity, the machine is called a wind
generator, wind turbine, wind power unit (WPU), wind energy converter (WEC), or aero
generator. Wind turbines can be separated into two types based by the axis in which the
turbine rotates. Turbines that rotate around a horizontal axis are more common. Vertical-axis
turbines are less frequently used.
1. Horizontal axis wind turbine
a) “Dutch-type” grain grinding windmills.
b) Multi-blade water-pumping windmills.
c) High speed propeller type windmills
2. Vertical axis wind turbine
a) The Savonius rotor.
b) The Darrieus rotor.
2.3 Power speed characteristics:
The wind turbine power curves shown in figure illustrate how the mechanical power that can
be extracted from the wind depends on the rotor speed. For each wind speed there is an
optimum turbine speed at which the extracted wind power at the shaft reaches its maximum.
Such families of Wind turbine power curves can be represented by a single dimensionless
13
characteristic curve namely the CP - curve, as in the figure, where the power coefficient is
plotted against the TSR. For a given turbine, the power coefficient depends not only on the TSR
but also on the blade pitch angle. Figure shows the typical variation of the power coefficient
with respect to the TSR 𝛌 with the blade pitch control. The mechanical power transmitted to
the shaft is—
P=0.5× ρ×A×V 3×CP(2)
Where is the function of TSR 𝛌 and the pitch angle α. For a wind turbine with radius R, it can
be expressed
λ=ω×RV
(3)
The maximum value of the shaft mechanical power for any wind speed can be expressed as
P=0.5×CP×π×(R5
λ3)×ω3
(4)
Thus the maximum mechanical power that can be extracted from the wind is proportional to
the cube of the rotor speed.
14
2.4 Wei-bull Distribution-
Wind speed keeps changing hence to define constant power there is a need of probability speed distribution. It is done by Wei-bull or Rayleigh Distribution.
Fig- Probability density function variation with wind speed
Due to the non-linear variation of power with steady wind speed, the mean power obtained over time in a variable wind with a mean velocity Um is not the same as the power obtained in a steady wind of the same speed.
Fig- Power output variation in steady and variable wind
15
Fig- Steady wind power curve and wind speed probability density.
The final mean power at a mean wind speed Um is the steady power W(u) multiplied by the
probability density distribution P(u) and summed (i.e. integrated) over all the range of wind
speeds. Thus, the mean power Pm at a mean speed U is given by:
Pm=∫0
∞
P (u ) .W (u) .du
CHAPTER 3
Wind Turbine Control Systems
16
Wind turbines require certain control systems. Horizontal-axis turbines have to be oriented to
face the wind. In high winds, it is desirable to reduce the drive train loads and protect the
generator and the power electronic equipment for overloading, by limiting the turbine power
to the rated value up to the furling speed. At gust speeds, the machine has to be stalled. At
low and moderate wind speeds, the aim should be to capture power as efficiently as possible.
Along with many operating characteristics, the technical data sheet of a turbine mentions its
output at a particular wind speed. This is the minimum wind speed at which the turbine
produces its designated output power. For most turbines, this speed is normally between 9
and 16 m/s. The choice of the rated wind speed depends on the factors related to the wind
characteristics of a given site. The generator rating is best chosen so as to best utilize the
mechanical output of the turbine at the rated wind speed. Wind turbines can have four
different types of control mechanisms, as discussed below:
3.1 Pitch Angle Control:
The system changes the pitch angle of the blades according to the variation of wind speed. As
discussed earlier, with pitch control, it is possible to achieve a high efficiency by continuously
aligning the blade in the direction of the relative wind. On a pitch controlled machine, as the
wind speed exceeds its rated speed, the blades are gradually turned about the longitudinal
axis and out of the wind to increase the pitch angle. This reduces the aerodynamic efficiency of
the rotor, and the rotor output power decreases. When the wind speed exceeds the safe limit
for the system, the pitch angle is so changed that the power output reduces to zero and the
machine shifts to the stall mode. After the gust passes, the pitch angle is reset to the normal
position and the turbine is restarted. At normal wind speeds, the blade pitch angle should
ideally settle to a value at which the output power equals the rated power. The input variable
to the pitch controller is the error signal arising from the difference between the output
electrical power and the reference power. The pitch controller operates the blade actuator to
alter the pitch angle. During operation below the rated speed, the control system endeavors to
the pitch the blade at an angle that maximizes the rotor efficiency. The generator must be able
to absorb the mechanical power output and deliver to the load. Hence, the generator output
power needs to be simultaneously adjusted.
17
3.2 Stall Control:
(a) Passive stall control:
This stall control to limit the power output at high winds is applied to constant-pitch
turbines driving induction generators connected to the network. The rotor speed is fixed by
the network, allowing only 1-4% variation. As the wind speed increases, the angle of attack
also increases for a blade running at a near constant speed. Beyond a particular angle of
attack, the lift force decreases, causing the rotor efficiency to drop. This lift force can be
further reduced to restrict the power output at high winds by properly shaping the rotor blade
profile to create turbulence on the rotor blade side not facing the wind.
(b) Active stall control:
In this method of control, at high wind speeds, the blade is rotated by a few degrees
in the direction opposite to that in a pitch controlled machine. This increases the angle of
attack, which can be controlled to keep the output power at its rated value at all high wind
speeds below the furling speed.
A passive controlled machine shows a drop in power at high winds. The action of active stall
control is sometimes called deep stall. Owing to economic reasons, active pitch control is
generally used only with high capacity machines.
3.3 Power Electronic Control:
In a system incorporating a power electronic interface between the generator and load (or the
grid), the electrical power delivered by the generated to the load can be dynamically
controlled. The instantaneous difference between mechanical power and electrical power
changes the rotor speed following the equation
J .dωdt
=Pm−Peω
(6)
18
Where J is the polar moment of inertia of the rotor, ω is the angular speed of the
rotor, is the mechanical power produced by the turbine, and is the electrical power delivered
to the load. Integrating, we the above equation, we get:
0 .5×J×(ω22−ω12 )=∫
t1
t2
(Pm−Pe) .dt
(7)
3.4 Yaw Control:
Turbine is continuously oriented along the direction of the wind flow. This is achieved with a
tail-vane in small turbines, using motorized control systems activated either by fan-tail, in case
of wind farms, by a centralized instrument for the detection of the wind direction. It is also
possible to achieve yaw control without any additional mechanism, simply by mounting
the turbine downwind so that the thrust force automatically pushes the turbine in the
direction of the wind.
Speed of the rotor can also be controlled using the yaw control mechanism. The rotor is made
to face away from the wind direction at high wind speeds, thereby reducing the mechanical
power. Yawing often produces loud noise, and it is restriction of the yawing rate in large
machines to reduce noise is required.
3.5 Control Strategy:
Different speed control strategies are required for the five different ranges of wind speed.
a) Power is not generated by the machine below a cut-in speed. Rotation of the machine
may start in this speed range if there is sufficient starting torque. But no power is
generated and rotor rotates freely.
b) Maximum power is extracted from the wind at normal wind speeds. This is
achieved at a particular TSR value. Hence, for tracking maximum power point,
rotational speed is changed continuously proportional to the wind speed.
19
c) At high wind speeds, rotor speed is limited to a maximum value which depends on the
design of the mechanical components. Here Cp is lower than the maximum value.
Power output is not proportional to the cube of the wind speed.
d) At even higher wind speeds, output power is kept constant at the maximum value
allowed by the electrical components.
CHAPTER 4
20
GRID CONNECTED AND ASYNCHRONOUS GENERATOR FOR WIND
TURBINES
In terms of the generators for wind-power application, there are different concepts in use
today. The major distinction among them is made between fixed speed and variable speed
wind turbine generator concepts. In the early stage of wind power development, fixed-speed
wind turbines and induction generators were often used in wind farms. But the limitations of
such generators, e.g. low efficiency and poor power quality, adversely influence their further
application. With large-scale exploration and integration of wind sources, variable speed wind
turbine generators, such as doubly fed induction generators (DFIGs) and permanent magnetic
synchronous generators (PMSGs) are emerging as the preferred technology. In contrast to
their fixed-speed counterparts, the variable speed generators allow operating wind turbines at
the optimum tip-speed ratio and hence at the optimum power efficient for a wide wind speed
range. As the penetration of wind power increases, integrating large wind farms to power grids
and the relevant influences on the host grids needs to be carefully investigated. So, accurate
and reliable model of variable speed wind turbine generators are urgently needed for power
system simulation analysis. The paper is dedicated to analyzing the complete model of a
variable speed wind turbine with permanent magnet synchronous generator and developing
control schemes for the wind turbine generator. The modeled system consists of a PMSG
model, a pitch-angled controlled wind turbine model and a drive train model.
4.1 Aerodynamic Model
The wind turbine extracts power from wind and then converters it into mechanical power. The
amount of aerodynamic torque is related to the wind speed. The drive train of PMSG consists
of five parts, namely, rotor, low speed shaft, gearbox, high-speed shaft and generator. In the
analysis, other parts of wind turbines, e.g. tower and flap bending modes can be reasonably
neglected. When the interest of study varies the complexity of the drive train differs. For
example, when the problems such as torsional fatigue are studied, dynamics from both sides
of gearbox have to be considered. So, two-lumped mass or more sophisticated models are
required. But when the study focuses on the interaction between wind farms and AC grids the
21
drive train can be treated as one-lumped mass model for the sake of time efficiency and
acceptable precision. So, the drive train takes the form of the latter one in the paper and is
displayed in figure in which the parameters have been referred to the generator side.
4.2 Generator Model
Doubly fed electric machines are electric motors or electric generators that have windings on
both stationary and rotating parts, where both windings transfer significant power between
shaft and electrical system. Usually the stator winding is directly connected to the three-phase
grid and the three-phase rotor winding is fed from the grid through a rotating or static
frequency converter.
Although the multiphase slip ring assembly reduces reliability and requires regular
maintenance, it allows easy control of the rotor (moving) winding set so both multiphase
winding sets actively participate in the energy conversion process with the electronic
controller controlling half (or less) of the power capacity of the electric machine for full control
of the machine.
This is especially important when operating at synchronous speed, because then the rotor
current will be DC current. Without slip rings the production of DC current in the rotor winding
is only possible when the frequency converter is at least partly located in the rotor and
rotating with it. This kind of rotor converter naturally requires its own winding system
22
(preferably using high frequency in the 10 kHz range for compact size) for power transfer out
of or into the rotor. Furthermore, there are thermal and mechanical constraints (for example
centrifugal forces) of the power electronic assembly in the rotor. However, high speed
alternators have had electronics incorporated on the rotor for many years. Furthermore, high
frequency wireless power transfer is used in many applications because of improvements in
efficiency and cost over low frequency alternatives.
4.3 Requirement of the load flow analysis (both AC and AC/DC) for the power system
DC power flow is a simplification, and linearization of a full AC power flow. DC power flow
looks only at active power flows, neglecting voltage support, reactive power management and
transmission losses. Thanks to its simplicity and linearity it is very often used for contingency
analysis [5] and techno economic studies of power systems for assessing the influence of
commercial energy exchanges on active power flows in the transmission network. The method
as such is well-known and its fundamentals have been discussed extensively.
The classic power flow problem consists of active and reactive power flow and can be
formulated using four variables per node – voltage angle, voltage magnitude, active and
reactive power injections. Active power losses are not known in advance as they depend on
the active power injection pattern and voltage profile. Other variables are also
interdependent, making the problem non-linear. This is why it is often linearized and the
solution is obtained using successively linearized steps iteratively. The losses are re-estimated
at each iteration based on all other variables. Modern power system analysis tools use as a
basis the Newton-Raphson algorithm. Assumptions of DC power flow:
Voltage angle differences are small
Flat voltage profile
Line resistance is negligible
23
4.4 Load flow models considered
Newton Raphson Method
In numerical analysis, Newton's method (also known as the Newton–Raphson method),
named after Isaac Newton and Joseph Raphson, is a method for finding successively
better approximations to the roots (or zeroes) of a real-valued function. Limitations of
Newton Raphson Method are:
i. Finding the f’(x) i.e. the first derivative of f(x) can be difficult in cases where f(x) is
complicated.
ii. Infinite oscillation resulting in slow convergence near local maxima or minima. If the
initial guess is far from desired root, then the method may converge to some other
root
Gauss-Seidel Method
In an n -bus power system, let the number of P-Q buses be np and the number of P-V
(generator) buses be ng such that n = np + ng + 1. Both voltage magnitudes and angles of the P-
Q buses and voltage angles of the P-V buses are unknown making a total number of
2np + ng quantities to be determined. Amongst the known quantities are 2np numbers of real
and reactive powers of the P-Q buses, 2ng numbers of real powers and voltage magnitudes of
24
the P-V buses and voltage magnitude and angle of the slack bus . Therefore there are sufficient
numbers of known quantities to obtain a solution of the load flow problem.
Flow chart for Gauss Siedel Method
Fast Decoupled Method
In the operations of a power system, it is important for personnel to have a high level of
contingent information. The reason is that personnel need to know what power-flow changes
will occur due to generator outages. The contingent information can also be used to anticipate
future power disruptions in the power network. In this case fast decoupled load flow method
is used as a common method to retrieve contingent information conveniently.
25
Flow chart for Fast Decoupled Method
4.5 AC load flows and their drawbacks
The classic power flow problem consists of active and reactive power flow and can be
formulated using four variables per node – voltage angle, voltage magnitude, active and
reactive power injections. Active power losses are not known in advance as they depend on
the active power injection pattern and voltage profile. Other variables are also
interdependent, making the problem non-linear. This is why it is often linearized and the
solution is obtained using successively linearized steps iteratively. The losses are re-estimated
at each iteration based on all other variables. DC power flow is a commonly used tool for
contingency analysis. Recently, due to its simplicity and robustness, it also becomes
increasingly used for the real-time dispatch and techno economic analysis of power systems. It
is a simplification of a full power flow looking only at active power. Aspects such as voltage
support and reactive power management are possible to analyze. However, such
simplifications cannot always be justified and sometimes lead to unrealistic results. Especially
the implementation of power flow controlling devices is not trivial since standard DC power
flow fundamentally neglects their effects. Until recently, this was not an issue as the
26
application of power flow controlling devices in the European grid was limited. Therefore, it is
important to fundamentally re-validate the fast, but less accurate, DC power flow method.
4.6 AC/DC load flow
Sequential Power Flow
Simultaneous Power Flow
The advantage of sequential load flow algorithm is the easy integration of dc side equations
into ac load flow framework without making any changes to the existing framework. Figure
shows flow chart of sequential load flow algorithm-
It is worth mentioning that the dc network as well as the ac network power flows has to be
solved iteratively. Once the dc slack bus power injection is updated, the ac power flow solution
changes. So, apart from these internal iterations for dc and ac power flow solutions, an
external iteration loop is required to ensure the overall convergence of the algorithm. In the
initial dc slack bus power is estimated as the algebraic sum of all other converters, which can
increase the total number of iterations.
In Sequential Power Flow method, both ac and dc sides are considered together as a unified
ac-dc grid for solving the power flow. Since ac and dc equations are solved simultaneously, an
27
external iteration loop is not required here. However, in this algorithm, the slack station losses
are considered as a separate variable XS. Apart from ac and dc mismatch equations, an
additional mismatch equation is therefore included to account for slack converter losses.
With sequential algorithm, power flow convergence in two external iterations when a flat start
is considered. In the first external iteration, ac side requires five and dc side requires two
internal iterations for convergence.
28
CHAPTER 5
MODELS OF ASYNCHRONOUS WIND TURBINES
5.1 INTRODUCTION
Wind energy is one of the important renewable energy sources. As opposed to the currently
existing carbon-based energy sources such as coal, petroleum, and natural gas, wind energy
has the advantages that it is clean, unpolluted, inexhaustible, and free in term of its
natural existence . Current trend shows that wind energy is getting popular to replace
the traditional energy sources due to the expectable depletion of traditional energy
resource and the humankind’s effort in reduction of carbon dioxide emission but not
affecting the usable energy production for the continuous developments. Wind energy,
although with the advantages mentioned, is still developed at preliminary stage of power
generation. Generally, wind energy is converted into kinetic energy before the Conversion
to the usable electrical energy. Wind energy is converted to low speed rotational energy
via blades and through the gear box, the rotational energy is used to drive the generator for
electric power generation. Wind energy is an abundant resource with free cost but it is
important to study the way to maximize the power generation by wind energy. Several control
methods of wind energy conversion system has been proposed by researchers to maximize
the wind energy harvest. However, most of the proposed methods have rather low
efficiency to extract power. Besides, the extracted energy is the very unstable since the nature
of wind flow is spontaneous which this situation will lower the power extraction and
subsequently reduce the efficiency of power generation.
Wind Turbine with Variable Speed Generator The wind turbine model is used to generate
mechanical torque. The negative value of output torque means the wind turbine is providing
torque. Result shows the output torque is positive for wind speed smaller than 7 m/s,
which represent that the wind turbine is not providing power, but consuming power
from the load. Hence, the value of wind speed at 7 m/s could be possibly as the cut-in speed
of the wind turbine model and the result of output mechanical torque. For a range of wind
speed is shown in Figure, the effect of both varying generator speed and wind speed on
the output torque is investigated in simulation and the results are shown in Figure. It can be
29
noticed that higher wind speed can provide larger torque and hence larger power to the load.
For instance, at Ω 1.5 m/s, the turbine output torque by wind speed 12 m/s is about -0.38 W,
but the turbine output torque by wind speed 18 m/s is about -1.35 W. wind turbine at higher
output torque can provide larger output power, hence improving the power efficiency of
the power generation.
5.2 Various types of WTGUs:
1 Fixed speed WTGU: This type of WTGU has a squirrel cage induction generator which is
driven by a wind turbine either having a fixed turbine blade angle (stall regulated fixed
speed WTGU) or having a pitch controller to regulate the blade angle (pitch regulated fixed
speed WTGU). In both these types of WTGU, the induction generator is directly connected
to the grid. In the operating range the rotor speed varies within a very small range (around
5% of the nominal value) and hence, these are reckoned as fixed speed WTGU. Normally in
these WTGU a fixed shunt capacitor is used to provide reactive power compensation.
(a) Stall regulated fixed speed WTGU: The power output of this class of WTGU depends
on the turbine and generator characteristics, wind speed, rotor speed and the terminal
voltage. For a given turbine and generator characteristics, wind speed alone is the
independent variable while the rotor speed and terminal voltage are interdependent
and vary with wind speed as well as the network conditions. In some of the existing
models for this WTGU, either the turbine characteristics is neglected (constant
mechanical input) or the WTGU power output is considered to be independent of the
terminal voltage variation. The method suggested here facilitates the computation of
the power output of the WTGU without making these simplifying assumptions. In order
to take this interdependency of rotor speed and voltage into account, the power
output is calculated iteratively. For a given wind speed, the power output is computed
for an assumed terminal voltage. The calculation is repeated if the computed power
output results in a change in the terminal voltage. The power output calculation
requires finding the rotor speed common to both the turbine and the generator. This
rotor speed corresponds to the intersection of the turbine and the generator
30
characteristics. Since the two characteristics are non-linear, an iterative method has
been developed here for computing the rotor speed.
(b) Pitch regulated fixed speed WTGU: In this class of WTGU, the pitch angle controller
regulates the wind turbine blade angle (ν) according to the wind speed variations.
Hence, the power output of this class of WTGU depends on the characteristics of the
pitch controller in addition to the turbine and generator characteristics. Since the
interest here is in steady state behavior, rather than the actual control process the
effect of the control process is important. This control guarantees that the power
output of the WTGU for any wind speed will be equal to the designed value for that
speed (irrespective of the voltage). This designed power output Pe of the WTGU with
wind speed is provided by the manufacturer in the form of a power curve. Hence, for a
given wind speed Pe can be obtained from the power curve of the WTGU, but Qe
needs to be computed. With Pe known and an assumed voltage, the induction
generator Pe expression can be recast as a quadratic equation in slip (rotor speed). This
equation is solved to get the slip value. With the slip known, the reactive power output
Qe is calculated from the induction generator equivalent circuit. Any change in voltage
due to these output changes is computed and the above process is repeated till
convergence.
2. Semi variable speed WTGU: This class of WTGU consists of a pitch controlled wind turbine
and a wound rotor induction generator. The rotor circuit of the generator is connected to an
external variable resistance. Power electronic devices are used to vary the rotor resistance.
In these WTGU, the reactive power compensation is normally provided by a fixed shunt
capacitor. There are two controllers, a pitch controller and rotor resistance controller. These
two controllers are designed to operate in a coordinated manner. This design guarantees that
the active power output is equal to the maximum power at wind speeds below nominal and
equal to rated power above nominal wind speeds. For this class of WTGU also, the
manufacturer provides the designed real power output versus wind speed characteristics.
3. Variable speed WTGU: WTGU having double fed induction generator (DFIG): The DFIG
consists of a pitch controlled wind turbine and an induction generator whose stator winding is
directly connected to the grid but the rotor circuit is connected to the grid through a back to
31
back voltage source converter. The voltage source converter (connected to the rotor) applies
voltage across the rotor which is regulated by two rotor current controllers. WTGU having
generator (synchronous/induction) with front end converter (GFEC): The GFEC consists of a
pitch controlled wind turbine and a variable frequency synchronous or induction generator
connected to the grid through a power electronic converter (back to back voltage source
converter). In this case, the voltage source converter output applied to the stator is varied by
the control signals obtained from the current controllers.
PQ MODEL OF AN ASYNCHRONOUS WIND TURBINE
A way to model a wind farm as a PQ bus is to assume a generated real power and a given power factor,
with which the consumed reactive power is calculated. Some improvements can be achieved if the
steady-state model of the induction machine is taken into account. The model shown in Fig is assumed.
In this model, applying the conservation of complex power theorem (Boucherot’s theorem) allows the
following expression to be written for the reactive power consumed by the machine:
Fig. Reactive Power consumed variation with wind speed
The reactive power curve as a function of wind speed can be seen in Fig. Q=−Q0−Q1P−Q2P
2
(8)
Where above mentioned constants are experimentally obtained. If the wind speed is desired to be the
input datum for the problem, the real power can be obtained as a function of it:
P=0.5×ρ×A×V 3×CP (9)
All parameters have been mentioned already.
PQ MODEL OF AN ASYNCHRONOUS WIND TURBINE
32
The other method proposed here consists of modeling the machine as an RX bus, following the
next three steps-
(a) Calculate the power that each WT can extract from the wind for a given wind speed and a
given rotor speed, according to its power coefficient curve.
(b) Calculate the power that each WT can generate, according to the results of the load flow
analysis, and to the rotor speed given in step (a).
Fig- Curves for the generator and turbine
(c) Compare both powers and look for the value of the slip, for which the electrical and the
mechanical powers coincide, for the wind speed given.
33
CHAPTER 6SIMULATION AND RESULTS
Load Flow Analysis of 33 Bus System Using Wei bull Distribution using paper[1] & [2]
Input bus data:
Br. No. Rc. Nd. Sn Nd. Branch R (OHM) X (OHM) SENDING PL (KW) NODE QL (KVAR)1 1 2 0.0922 0.047 100 602 2 3 0.493 0.2511 90 403 3 4 0.366 0.1864 120 804 4 5 0.3811 0.1941 60 305 5 6 0.819 0.177 60 206 6 7 0.1872 0.6188 200 1007 7 8 0.7114 0.2351 200 1008 8 9 1.03 0.74 60 209 9 10 1.044 0.74 60 20
10 10 11 0.1966 0.065 45 3011 11 12 0.3744 0.1238 60 3512 12 13 1.468 1.155 60 3513 13 14 0.5416 0.7129 120 8014 14 15 0.591 0.526 60 1015 15 16 0.7463 0.545 60 2016 16 17 1.289 1.721 60 2017 17 18 0.732 0.574 90 4018 18 19 0.164 0.1565 90 4019 19 20 1.5042 1.3554 90 4020 20 21 0.4095 0.4784 90 4021 21 22 0.7089 0.9373 90 4022 22 23 0.4512 0.3083 90 5023 23 24 0.898 0.7091 420 20024 24 25 0.896 0.7011 420 20025 25 26 0.203 0.1034 60 2526 26 27 0.2842 0.1447 60 2527 27 28 1.059 0.9337 60 2028 28 29 0.8042 0.7006 120 7029 29 30 0.5075 0.2585 1200 60030 30 31 0.9744 0.963 1500 7031 31 32 0.3105 0.3619 210 10032 32 33 0.341 0.5302 60 40
34
Pe : Active Power in MW Qe : Reactive Power in MVAR|V| : Terminal Voltage in P.U.
CASE BUS NO. TYPE of WTGU Wind
Speed
Pe(MW) Qe(MVAR) |V| (pu)
1 33 Stall Regulated Fixed
Speed
- 0.000000 0.000000 0.850821
6 Semi Variable Speed - 0.000000 0.000000 0.886101
18 DFIG - 0.000000 0.000000 0.867649
25 GFEC - 0.000000 0.000000 0.933572
2 33 Stall Regulated Fixed
Speed
11 0.710965 0.138621 0.894289
6 Semi Variable Speed 8 0.367190 0.047734 0.928876
18 DFIG 9.5 0.599402 0.000000 0.931083
25 GFEC 9 0.560438 0.000000 0.962401
3 33 Stall Regulated Fixed
Speed
13 0.867095 0.240592 0.915962
6 Semi Variable Speed 10 0.565784 0.095813 0.947733
18 DFIG 11 0.908436 0.000000 0.971893
25 GFEC 10.5 0.851965 0.000000 0.971908
4 33 Stall Regulated Fixed
Speed
13 0.870471 0.191872 0.985108
6 Semi Variable Speed 10 0.565784 0.097548 0.983276
18 DFIG 11 0.908436 0.000000 0.991258
25 GFEC 10.5 0.851965 0.000000 0.984167
35
PERFORMING LOAD FLOW ANALYSIS ON DIFFERENT TYPES OF WTGUs using paper [1]
ACTUAL RESULT:
CASE BUS NO. TYPE of WTGU Wind
Speed
( Uw )
Pe(MW) Qe(MVAR) |V| (pu)
1 33 Stall Regulated Fixed Speed - 0.000000 0.000000 0.878486
6 Semi Variable Speed - 0.000000 0.000000 0.933139
18 DFIG - 0.000000 0.000000 0.895878
25 GFEC - 0.000000 0.000000 0.964824
2 33 Stall Regulated Fixed Speed 11 0.748595 0.157656 0.919991
6 Semi Variable Speed 8 0.394330 0.049261 0.958645
18 DFIG 9.5 0.619500 0.000000 0.958991
25 GFEC 9 0.586000 0.000000 0.982107
3 33 Stall Regulated Fixed Speed 13 0.890600 0.270924 0.958661
6 Semi Variable Speed 10 0.590918 0.109595 0.975278
18 DFIG 11 0.929250 0.000000 0.991195
25 GFEC 10.5 0.879000 0.000000 0.991210
4 33 Stall Regulated Fixed Speed 13 0.892213 0.200400 1.015036
6 Semi Variable Speed 10 0.590918 0.099890 1.012525
18 DFIG 11 0.929250 0.000000 1.051119
25 GFEC 10.5 0.879000 0.000000 1.013085
36
USING NEWTON RAPHSON METHOD:
CASE BUS NO. TYPE of WTGU Wind
Speed
( Uw )
Pe(MW) Qe(MVAR) |V| (pu)
1 33 Stall Regulated Fixed Speed - 0.0000 0.0000 0.8172
6 Semi Variable Speed - 0.0000 0.0000 0.8921
18 DFIG - 0.0000 0.0000 0.8422
25 GFEC - 0.0000 0.0000 0.9150
2 33 Stall Regulated Fixed Speed 11 0.5102 0.1235 0.8876
6 Semi Variable Speed 8 0.2634 0.0374 0.9162
18 DFIG 9.5 0.4728 0.0000 0.9167
25 GFEC 9 0.4113 0.0000 0.9349
3 33 Stall Regulated Fixed Speed 13 0.7010 0.1909 0.9089
6 Semi Variable Speed 10 0.5016 0.0981 0.9293
18 DFIG 11 0.7561 0.0000 0.9532
25 GFEC 10.5 0.6281 0.0000 0.9976
4 33 Stall Regulated Fixed Speed 13 0.7010 0.1823 0.9812
6 Semi Variable Speed 10 0.5016 0.0873 0.9801
18 DFIG 11 0.7561 0.0000 0.9968
25 GFEC 10.5 0.6281 0.0000 0.9902
37
USING GAUSS SEIDEL METHOD:
CASE BUS NO. TYPE of WTGU Wind
Speed
( Uw )
Pe(MW) Qe(MVAR) |V| (pu)
1 33 Stall Regulated Fixed
Speed
- 0.0000 0.0000 0.8165
6 Semi Variable Speed - 0.0000 0.0000 0.8903
18 DFIG - 0.0000 0.0000 0.8396
25 GFEC - 0.0000 0.0000 0.9076
2 33 Stall Regulated Fixed
Speed
11 0.5063 0.1210 0.8814
6 Semi Variable Speed 8 0.2610 0.0319 0.9033
18 DFIG 9.5 0.4713 0.0000 0.9102
25 GFEC 9 0.4099 0.0000 0.9322
3 33 Stall Regulated Fixed
Speed
13 0.6944 0.1889 0.9018
6 Semi Variable Speed 10 0.5001 0.0941 0.9246
18 DFIG 11 0.7548 0.0000 0.9513
25 GFEC 10.5 0.6219 0.0000 0.9941
4 33 Stall Regulated Fixed
Speed
13 0.6944 0.1799 0.9779
6 Semi Variable Speed 10 0.5001 0.0856 0.9734
18 DFIG 11 0.7548 0.0000 0.9912
25 GFEC 10.5 0.6219 0.0000 0.9837
38
USING FAST DECOUPLED METHOD:
CASE BUS NO. TYPE of WTGU Wind
Speed
( Uw )
Pe(MW) Qe(MVAR) |V|
(pu)
1 33 Stall Regulated Fixed Speed - 0.0000 0.0000 0.8159
6 Semi Variable Speed - 0.0000 0.0000 0.8896
18 DFIG - 0.0000 0.0000 0.8387
25 GFEC - 0.0000 0.0000 0.9065
2 33 Stall Regulated Fixed Speed 11 0.5061 0.1204 0.8805
6 Semi Variable Speed 8 0.2604 0.0311 0.9019
18 DFIG 9.5 0.4702 0.0000 0.9095
25 GFEC 9 0.4089 0.0000 0.9301
3 33 Stall Regulated Fixed Speed 13 0.6928 0.1881 0.9002
6 Semi Variable Speed 10 0.4990 0.0936 0.9227
18 DFIG 11 0.7541 0.0000 0.9498
25 GFEC 10.5 0.6207 0.0000 0.9926
4 33 Stall Regulated Fixed Speed 13 0.6928 0.1784 0.9763
6 Semi Variable Speed 10 0.4990 0.0840 0.9718
18 DFIG 11 0.7541 0.0000 0.9901
25 GFEC 10.5 0.6207 0.0000 0.9815
39
COMPARISION OF PERFORMANCE OF VARIABLE SPEED WIND TURBINE AT A
PARTICULAR SPEED AND USING WEIBULL DISTRIBUTION
AT A PARTICULAR SPEED:
CASE BUS NO. TYPE of WTGU Wind
Speed
( Uw )
Pe(MW) Qe(MVAR) |V|
(pu)
1 33 Stall Regulated Fixed Speed - 0.0000 0.0000 0.8172
6 Semi Variable Speed - 0.0000 0.0000 0.8921
18 DFIG - 0.0000 0.0000 0.8422
25 GFEC - 0.0000 0.0000 0.9150
2 33 Stall Regulated Fixed Speed 11 0.5102 0.1235 0.8876
6 Semi Variable Speed 8 0.2634 0.0374 0.9162
18 DFIG 9.5 0.4728 0.0000 0.9167
25 GFEC 9 0.4113 0.0000 0.9349
3 33 Stall Regulated Fixed Speed 13 0.7010 0.1909 0.9089
6 Semi Variable Speed 10 0.5016 0.0981 0.9293
18 DFIG 11 0.7561 0.0000 0.9532
25 GFEC 10.5 0.6281 0.0000 0.9976
4 33 Stall Regulated Fixed Speed 13 0.7010 0.1823 0.9812
6 Semi Variable Speed 10 0.5016 0.0873 0.9801
18 DFIG 11 0.7561 0.0000 0.9968
25 GFEC 10.5 0.6281 0.0000 0.9902
USING WEIBULL DISTRIBUTION:
40
CASE BUS NO. TYPE of WTGU Wind
Speed
( Uw )
Pe(MW) Qe(MVAR) |V| (pu)
1 33 Stall Regulated
Fixed Speed
- 0.000000 0.000000 0.850821
6 Semi Variable
Speed
- 0.000000 0.000000 0.886101
18 DFIG - 0.000000 0.000000 0.867649
25 GFEC - 0.000000 0.000000 0.933572
2 33 Stall Regulated
Fixed Speed
11 0.710965 0.138621 0.894289
6 Semi Variable
Speed
8 0.367190 0.047734 0.928876
18 DFIG 9.5 0.599402 0.000000 0.931083
25 GFEC 9 0.560438 0.000000 0.962401
3 33 Stall Regulated
Fixed Speed
13 0.867095 0.240592 0.915962
6 Semi Variable
Speed
10 0.565784 0.095813 0.947733
18 DFIG 11 0.908436 0.000000 0.971893
25 GFEC 10.5 0.851965 0.000000 0.971908
4 33 Stall Regulated
Fixed Speed
13 0.870471 0.191872 0.985108
6 Semi Variable
Speed
10 0.565784 0.097548 0.983276
18 DFIG 11 0.908436 0.000000 0.991258
25 GFEC 10.5 0.851965 0.000000 0.984167
41
Performing Load Flow Analysis on all types of WTGU Model on a
different Set of Bus using paper [1]
Pe : Active Power Generation
Qe : Reactive Power Generation
V : Terminal Voltage
Uw : Wind Speed
CASE BUS NO. TYPE of WTGU Wind
Speed
( Uw )
Pe(MW) Qe(MVAR) |V| (pu)
1 31 Stall Regulated Fixed Speed - 0.000000 0.000000 0.850821
9 Semi Variable Speed - 0.000000 0.000000 0.886101
14 DFIG - 0.000000 0.000000 0.867649
22 GFEC - 0.000000 0.000000 0.933572
2 31 Stall Regulated Fixed Speed 11 0.710965 0.138621 0.894289
9 Semi Variable Speed 8 0.367190 0.047734 0.928876
14 DFIG 9.5 0.599402 0.000000 0.931083
22 GFEC 9 0.560438 0.000000 0.962401
3 31 Stall Regulated Fixed Speed 13 0.867095 0.240592 0.915962
9 Semi Variable Speed 10 0.565784 0.095813 0.947733
14 DFIG 11 0.908436 0.000000 0.971893
22 GFEC 10.5 0.851965 0.000000 0.971908
4 31 Stall Regulated Fixed Speed 13 0.870471 0.191872 0.985108
9 Semi Variable Speed 10 0.565784 0.097548 0.983276
14 DFIG 11 0.908436 0.000000 0.991258
22 GFEC 10.5 0.851965 0.000000 0.984167
42
Comparison of Various Wind Turbine Models using paper [1]
Variable Speed Wind Turbines:
1. DFIG (Doubly Fed induction Generator)
Case No. Bus No. Wind Speed
(Uw) in m/s
Pe(MW) Qe(MW) |V| (pu)
1. 18 - 0.0000 0.0000 0.8422
14 - 0.0000 0.0000 0.8676
2. 18 9.5 0.4728 0.0000 0.9167
14 9.5 0.5994 0.0000 0.9310
3. 18 11 0.7561 0.0000 0.9532
14 11 0.9084 0.0000 0.9718
4. 18 11 0.7561 0.0000 0.9968
14 11 0.9084 0.0000 0.9912
2. GFEC (Generator with Front End Converter)
Case No. Bus No. Wind Speed
(Uw) in m/s
Pe(MW) Qe(MW) |V| (pu)
1. 25 - 0.0000 0.0000 0.9150
22 - 0.0000 0.0000 0.9335
2. 25 9 0.4113 0.0000 0.9349
22 9 0.5604 0.0000 0.9624
3. 25 10.5 0.6281 0.0000 0.9976
43
22 10.5 0.8519 0.0000 0.9719
4. 25 10.5 0.6281 0.0000 0.9902
22 10.5 0.8519 0.0000 0.9841
Fixed Speed Wind Turbines:
Stall Regulated Fixed Speed
Case No. Bus No. Wind Speed
(Uw) in m/s
Pe(MW) Qe(MW) |V| (pu)
1. 33 - 0.0000 0.0000 0.8172
31 - 0.0000 0.0000 0.8508
2. 33 11 0.5102 0.1235 0.8876
31 11 0.7109 0.1386 0.8942
3. 33 13 0.7010 0.1909 0.9089
31 13 0.8670 0.2405 0.9159
4. 33 13 0.7010 0.1823 0.9812
31 13 0.8704 0.1918 0.9851
Semi Variable Speed Wind Turbines:
Case No. Bus No. Wind Speed
(Uw) in m/s
Pe(MW) Qe(MW) |V| (pu)
1. 6 - 0.0000 0.0000 0.8921
9 - 0.0000 0.0000 0.8861
2. 6 8 0.2634 0.0374 0.9162
44
9 8 0.3671 0.0477 0.9288
3. 6 10 0.5016 0.0981 0.9293
9 10 0.5657 0.0958 0.9477
4. 6 10 0.5016 0.0873 0.9801
9 10 0.5657 0.0942 0.9832
In above tables:
Pe: Active power in MW.
Qe: Reactive Power In MW.
|V|: Bus voltage in pu.
Note: In all the above tables four different cases have been tabulated. These cases are
1. WTGU operating below cut-in wind speed (which is equivalent to the system without
WTGU) and system loads corresponds to the base load.
2. WTGU operating at low wind speeds with all the variable speed WTGU operating with
specified Q and system loads corresponds to the base load.
3. WTGU operating at higher wind speeds than case 2 with GFEC and DGIG operating with
settable Q and system loads corresponds to the base load.
4. WTGU operating at wind speeds corresponding to case 3 with GFEC and DFIG operating
with settable Q and system load corresponds to 30 % of the base load.
The feeder voltage is 12.66 kV (base voltage). The base case total load is 4.715 MW and
2.3 MVAR.
AC/DC Combined Power Flow Solution using paper [3]
45
Data: Under nominal condition each of G1, G2, G3, G4, G5, and G6 generates 700 MW
whereas G3 left slack. The converters connected to DC buses DC1, DC2 and DC3 control the DC
power at 600 MW, 300 MW and 300 MW respectively. The converter connected to DC4 is slack
converter keeps the DC link constant at 320KV.The base power for the DC side is 600 MW
however the base MVA for the AC side is 100 MVA.
Note: Each generating source comprises of stall regulated wind turbines in wind farm, where
the generators are induction machine with following parameters:
Stator resistance Rs = 0.01352 ohms
Stator reactance Xs = 0.5380 ohms
Rotor resistance Rr = 0.01290 ohms
Rotor reactance Xr = 0.21289 ohms
Magnetizing reactance Xm = 3.42979 ohms
Area swept by the blades of wind turbine is 961 meter2.
Wind speed varies from 13 m/sec to 29 m/sec.
Case 1: All Converters are in PQ model with zero reactive power injection and with rated active
power.
46
Sequential Algorithm Simultaneous Algorithm
AC Bus Voltage(p.u.) Angle(rad) Pinj (p.u.) Voltage(p.u.) Angle(rad) Pinj (p.u.)
1 1.0219 0.2918 7.000 1.0219 0.2918 7.000
2 1.0018 0.1256 7.000 1.0018 0.1256 7.000
3 1.0219 -0.1079 7.000 1.0219 -0.1079 7.000
4 1.0018 -0.2785 7.051 1.0018 -0.2785 7.0509
5 0.9926 0.1828 0 0.9926 0.1828 0
6 0.9759 0.0086 0 0.9759 0.0086 0
7 0.9616 -0.1317 0 0.9616 -0.1317 0
8 0.9616 -0.3372 0 0.9616 -0.3372 0
9 0.9764 -0.5374 0 0.9764 -0.5374 0
10 0.9842 -0.3950 0 0.9842 -0.3950 0
11 1.0081 -0.2201 0 1.0081 -0.2201 0
12 0.9923 -0.3387 0 0.9923 -0.3387 0
13 0.9771 -0.5850 0 0.9771 -0.5850 0
14 1.0018 -0.2236 7.000 1.0018 -0.2236 7.000
15 1.0018 -0.4680 7.000 1.0018 -0.4680 7.000
DC Bus Voltage(p.u.) Angle(rad) Pinj (p.u.) Voltage(p.u.) Angle(rad) Pinj (p.u.)
1 0.9986 - -1.0000 0.9986 - -1.0000
2 0.9893 - 0.5000 0.9893 - 0.5000
3 0.9953 - -0.5000 0.9953 - -0.5000
4 1.0000 - 0.97706 1.0000 - 0.97706
Case 2: All the converters are in PV mode maintaining the PCC voltage to 1.0 p.u.
Sequential Algorithm Simultaneous Algorithm
47
AC Bus Voltage(p.u.) Angle(rad) Pinj (p.u.) Voltage(p.u.) Angle(rad) Pinj (p.u.)
1 1.0219 0.2743 7.000 1.0219 0.2743 7.000
2 1.0018 0.1062 7.000 1.0018 0.1062 7.000
3 1.0219 -0.1074 7.000 1.0219 -0.1074 7.000
4 1.0018 -0.2767 7.0291 1.0018 -0.2767 7.02958
5 1.0078 0.1623 0 1.0078 0.1623 0
6 0.9911 -0.0050 0 0.9911 -0.0050 0
7 0.9926 -0.1445 0 0.9926 -0.1445 0
8 0.9861 -0.3403 0 0.9861 -0.3403 0
9 0.9926 -0.5327 0 0.9926 -0.5327 0
10 0.9911 -0.3928 0 0.9911 -0.3928 0
11 1.0078 -0.2200 0 1.0078 -0.2200 0
12 0.9926 -0.3338 0 0.9926 -0.3338 0
13 0.9926 -0.5782 0 0.9926 -0.5782 0
14 1.0018 -0.2179 7.000 1.0018 -0.2179 7.000
15 1.0018 -0.4621 7.000 1.0018 -0.4621 7.000
DC Bus Voltage(p.u.) Angle(rad) Pinj (p.u.) Voltage(p.u.) Angle(rad) Pinj (p.u.)
1 0.9986 - -1.0000 0.9986 - -1.0000
2 0.9893 - 0.5000 0.9893 - 0.5000
3 0.9953 - -0.5000 0.9953 - -0.5000
4 1.0000 - 0.97706 1.0000 - 0.97706
Comparison of Genetic Algorithm and Newton Raphson Approach for
Solving AC DC Optimal Power Flow Problem
48
For IEEE-14 Bus System:
Bus Data:
Problem Statement: The problem here is to minimize the overall cost function. The overall
cost function fi(PGi) is given by:
49
Note: The problem was solved using two methods (Genetic Algorithm and Newton Raphson)
and there results were tabulated. A DC link is connected between bus 1 and bus 14.The
voltage values of all buses have been bounded between 0.95 and 1.05.
Also for Genetic Algorithm:
Number of Iterations: 100
Number of runs: 9
For Newton Raphson:
Number of Iterations: 25
Number of runs: 1
Result:
Actual Result:
50
Bus No. Voltage (pu) Generator Cost ($/MWh)
GAOPF Newton OPF GAOPF Newton
OPF
Best Worst Best Worst
1 0.98 1.02 0.99
2 0.99 1.00 0.98 68.47 120.01 90.94
3 1.01 0.97 0.97 60.34 180.20 90.46
4 0.96 0.96 0.96
5 0.97 0.99 0.96
6 0.99 0.99 1.02 102.6 85.51 89.87
7 1.02 0.98 0.97
8 0.99 1.01 1.02 118.6 120.91 88.40
9 0.98 0.98 0.95
10 0.97 0.95 0.96
11 1.01 1.01 0.99
12 0.98 0.95 1.00
13 1.03 0.99 0.99
14 0.97 1.02 0.95
Obtained Result:
51
Bus
No.
Voltage (pu) Generator Cost ($/MWh)
GAOPF Newton
OPF
GAOPF Newton
OPF
Best Worst Best Worst
1 0.976 1.013 0.987
2 0.989 0.998 0.974 68.453 119.157 90.652
3 1.005 0.967 0.968 60.332 179.861 90.381
4 0.958 0.958 0.952
5 0.967 0.989 0.952
6 0.989 0.989 1.011 102.514 85.480 89.613
7 1.013 0.976 0.968
8 0.989 1.005 1.011 118.538 120.864 88.228
9 0.976 0.976 0.941
10 0.967 0.944 0.952
11 1.005 1.005 0.987
12 0.976 0.944 0.997
13 1.023 0.989 0.987
14 0.967 1.013 0.941
Genetic Algorithm Approach for Solving AC DC Optimal Power Flow
Problem
For IEEE-30 Bus System:
52
Bus Data:
53
Given bus data
Problem Statement: The problem here is to minimize the overall cost function. The overall
cost function fi(PGi) is given by:
54
Note: The problem was solved using two methods (Genetic Algorithm and Newton Raphson)
and there results were tabulated. A DC link is connected between bus 1 and bus 28. The rating
of converter at bus 1 and 28 is 1.00 pu. The voltage values of all buses have been bounded
between 0.95 and 1.05.
Also for Genetic Algorithm:
Number of Iterations: 100
Number of runs: 14
For Newton Raphson:
Number of Iterations: 30
Number of runs: 1
Result:
55
Actual Result:
Bus
No.
Voltage (pu) Generator Cost
($/MWh)
GAOPF Newton
OPF
GAOPF Newton
OPF
Best Worst Best Wors
t
1 1.00 0.99 1.00 9.77 11.67 10.55
2 0.99 1.00 0.99 7.97 11.06 6.53
3 0.96 0.98 0.99
4 0.98 0.96 0.98
5 1.01 1.02 0.99 8.13 11.40 6.52
6 0.99 1.00 0.97
7 0.98 0.95 0.98
8 0.96 0.99 1.03 8.15 10.57 6.93
9 0.96 1.01 0.99
10 1.01 1.02 1.02
11 0.99 1.00 1.01 8.40 10.54 11.87
12 1.01 0.95 1.00
13 0.99 1.01 1.01 6.12 10.56 6.90
14 0.97 0.96 0.99
15 1.00 1.00 0.99
16 0.98 0.97 1.00
17 0.99 0.96 1.00
18 0.99 1.01 0.99
19 1.01 0.98 0.99
20 0.97 1.01 1.03
21 0.98 0.97 0.99
22 0.99 0.99 0.98
56
23 0.99 1.01 0.99
24 1.01 1.01 1.02
25 0.98 0.97 1.03
26 0.99 1.01 1.02
27 0.98 0.97 1.05
28 0.99 0.95 0.99
29 1.01 0.98 1.05
30 0.99 0.98 1.05
Obtained Result:
57
Bus
No.
Voltage (pu) Generator Cost
($/MWh)
GAOPF Newton
OPF
GAOPF Newton
OPF
Best Worst Best Worst
1 0.997 0.988 0.997 9.53 11.42 10.32
2 0.988 0.997 0.988 7.72 10.75 6.29
3 0.959 0.976 0.988
4 0.976 0.959 0.976
5 1.005 1.014 0.988 7.83 11.19 6.31
6 0.988 0.997 0.967
7 0.976 0.949 0.976
8 0.959 0.988 1.028 7.79 10.35 6.74
9 0.959 1.005 0.988
10 1.0005 1.014 1.014
11 0.988 0.997 1.005 8.22 10.39 11.69
12 1.005 0.949 0.997
13 0.988 1.005 1.005 5.89 10.34 6.78
14 0.967 0.959 0.988
15 0.997 0.997 0.988
16 0.976 0.967 0.997
17 0.988 0.959 0.997
18 0.988 1.005 0.988
19 1.005 0.976 0.988
20 0.967 1.005 1.028
21 0.976 0.967 0.988
22 0.988 0.988 0.976
23 0.988 1.005 0.988
24 1.005 1.005 1.014
25 0.976 0.967 1.028
26 0.988 1.005 1.014
27 0.976 0.967 1.046
28 0.988 0.949 0.988
29 1.005 0.976 1.046
30 0.988 0.976 1.046
58
Simulation of IEEE-14 and IEEE-30 Bus system using modified Newton
Raphson Method for AC/DC Circuits.
Actual Result: (obtained using genetic algorithm)
1. for IEEE-14 Bus System
Bus No. Voltage(p.u.) Generator Cost ($/MWh)
GAOPF GAOPF
Best Worst Best Worst
1 0.976 1.013
2 0.989 0.998 68.453 119.157
3 1.005 0.967 60.332 179.861
4 0.958 0.958
5 0.967 0.989
6 0.989 0.989 102.514 85.480
7 1.013 0.976
8 0.989 1.005 118.538 120.864
9 0.976 0.976
10 0.967 0.944
11 1.005 1.005
12 0.976 0.944
13 1.023 0.989
14 0.967 1.013
For IEEE-30 Bus System
59
60
Bus No. Voltage(p.u.) Generator Cost
($/MWh)
GAOPF GAOPF
Best Worst Best Worst
1 1.00 0.99 9.77 11.67
2 0.99 1.00 7.97 11.06
3 0.96 0.98
4 0.98 0.96
5 1.01 1.02 8.13 11.40
6 0.99 1.00
7 0.98 0.95
8 0.96 0.99 8.15 10.57
9 0.96 1.01
10 1.01 1.02
11 0.99 1.00 8.40 10.54
12 1.01 0.95
13 0.99 1.01 6.12 10.56
14 0.97 0.96
15 1.00 1.00
16 0.98 0.97
17 0.99 0.96
18 0.99 1.01
19 1.01 0.98
20 0.97 1.01
21 0.98 0.97
22 0.99 0.99
23 0.99 1.01
24 1.01 1.01
25 0.98 0.97
26 0.99 1.01
27 0.98 0.97
28 0.99 0.95
29 1.01 0.98
30 0.99 0.98
Obtained Result: (Using Modified Newton Raphson)
For IEEE-14 Bus System
Bus No. Voltage(p.u.) Generator Cost ($/MWh)
Advanced Newton Raphson
Method
Advanced Newton Raphson
Method
1 0.985
2 0.971 90.471
3 0.963 90.194
4 0.949
5 0.951
6 1.007 89.472
7 0.965
8 1.007 88.095
9 0.936
10 0.951
11 0.985
12 0.993
13 0.985
14 0.936
For IEEE-30 Bus System
61
Bus No. Voltage(p.u.) Generator Cost ($/MWh)
Advanced Newton
Raphson Method
Advanced Newton
Raphson Method
1 0.998 10.38
2 0.986 6.34
3 0.986
4 0.979
5 0.986 6.41
6 0.967
7 0.979
8 1.026 6.74
9 0.986
10 1.019
11 1.005 11.69
12 0.998
13 1.005 6.71
14 0.986
15 0.986
16 0.998
17 0.998
18 0.986
19 0.986
20 1.026
21 0.986
22 0.979
23 0.986
24 1.019
25 1.026
26 1.019
62
27 1.048
28 0.986
29 1.048
30 1.048
Discussion
63
1. With its abundant, inexhaustible potential, its increasingly competitive cost, and
environmental advantage, wind energy is one the best technologies available today to
provide a sustainable supply to the world development. In depth understanding and
investigation of wind power generators, wind farm integration, grid core and etc. is
very meaningful.
2. In terms of generators for wind power application, there are different concepts in use
today. The major distinction among them is made between fixed speed and variable
speed wind turbine generator concepts. In the early stage of the power development,
fixed speed wind turbines and induction generators were often used in wind farms. But
the limitations of such generators like low efficiency and poor power quality adversely
influences their further application. With large scale exploration and integration of
wind sources, variable speed wind turbines generators, such as doubly fed induction
generator (DFIG) and permanent magnet synchronous generators are emerging as
preferred technology. In contrast to their fixed speed counterparts, the variable speed
induction generators allow operating wind turbines at the optimum speed tip speed
ratio and hence at the optimum power efficient for a wide wind speed range.
3. As the penetration of wind power increases, integrating large wind farms to power
grids and the relevant influences on the host grids needs to be carefully investigated.
So, accurate and reliable model of the variable speed wind turbine generators and
urgently needed for power simulation analysis. Two models were propose namely PQ
and RX model. It was found that RX model was better as it obtained a single working
point for each wind speed,. However the conventional PQ model has its advantage of
being simpler and easy to implement.
4. One of the greatest problem facing wind farms is that the electrical power generated
depends on variable characteristics of the wind. To become competitive in liberalized
market, the reliability of wind energy must be guaranteed. Good local wind forecast
are therefore essential for accurate prediction of generation levels for each moment of
the day.
64
5. From above tables of individual wind turbines following can be deduced:
a) The power output of DFIG is greater than that of GFEC for a given wind speed.
b) GFEC has better voltage profile than that DFIG for wind speed up to cut off speed.
In fact DFIG has best voltage profile amongst all generator models.
c) Voltage profile of Variable Speed Wind Turbine is far better as compared to Semi
Variable and Fixed Speed Turbines.
d) At speed considerably below cut off speed the output of fixed speed Wind Turbine
is greatest.
e) Semi Variable Wind Turbines are used to employ benefits of both Fixed and
Variable speed Generators. Although their performance is inferior than that of
Fixed Speed at low wind speed and Variable Speed at higher wind speeds.
f) The major advantage of Variable Speed Wind Turbines is that reactive power
compensation can be employed.
Conclusion
1. This study brings out some interesting features about the WTGU performance and
their impact when used as DG sources. The real power output of all the types of
65
WTGU (considered here) at any given wind speed does not change perceptibly
even with significant changes in terminal voltage.
2. The Q demand of the fixed and semi-variable speed WTGU is sensitive to terminal
voltage variations. However, in the case of variable speed WTGU the terminal
voltage variation (normal range) has no impact on their Q demand.
3. From load flow analysis of different wind turbines models using different methods
it was concluded that Newton Raphson method was best for performing load flow
analysis as it is more accurate.
4. It was also found that load flow results obtained using Weibull distribution were
far accurate than those obtained at particular speed.
5. After plotting load flow results of different wind turbines on two sets of bus it was
found that choice for a given wind turbine really exists between DFIG and GFEC.
6. However DFIG has greater power output as compared to its counterpart it is the most
preferable choice. Also GFEC is more expensive because of power electronics associated
with it.
7. From the results one could conclude that result obtained by GAOPF best solution
has shown improvement as compared to Newton OPF solution. Also the overall
cost of generation obtained by GAOPF best solution is less.
8. But GAOPF required 100 iterations and 9 runs compared to 20 iterations and 1 run
required by Newton OPF method. Thus Newton OPF method is faster as compared
to GAOPF method.
9. From the results one could conclude that result obtained by GAOPF best solution
has shown improvement as compared to Newton OPF solution. Also the overall
cost of generation obtained by GAOPF best solution is less.
10. But GAOPF required 100 iterations and 14 runs compared to 30 iterations and 1
run required by Newton OPF method. Thus Newton OPF method is faster as
compared to GAOPF method.
References
66
[1] K.C. Divya, P.S. Nagendra Rao “Models for wind turbine generating systems and
their application in load flow studies”, Department of Electrical Engineering,
Indian Institute of Science, Bangalore 560012, India.
[2] Heras,Escriva,Ortega “Wind farm electrical power production model for load flow
analysis”.
[3] Nakul Narayanan K & Pinaki Mitra “A comparative study of sequential and
simultaneous AC/DC power flow algorithm”.
[4] Feijoo and Cidras “Modeling of wind farms in the load flow analysis”.
[5] A. Panosyan, B. R. Oswald “Modified Newton Raphson Load Flow Analysis for
Integrated AC/DC Power Systems” in Institute of Electric Power Systems,
University of Hannover, Germany.
[6] Warkad,Khedkar,Dhole “A Genetic algorithm approach for solving AC-DC optimal
power flow problem” in Department of Electrical Engineering, Visvesvaraya
National Institute of Technology, Nagpur, India.
[7] Slootweg,Haan,H.Polinder “General Model for Representing Variable SpeedWind
Turbines in Power System Dynamics Simulations” in IEEE Porto Power Tech,
Porto, Potugal.
[8] E. Simiu and R. H. Scanlan, “Wind Effects on Structures, an Introduction to Wind
Engineering”, 2nd Ed. New York: Wiley, 1986.
[9] R. Pena, J. C. Clare, and G. M. Asher, “Doubly fed induction generator using back-
to-back PWM converters and its application to variable- speed wind–energy
conversion,” Proc. Inst. Elect. Eng., vol. 143.
[10] S. Heier, “Grid Integration of Wind Energy Conversion Systems”. Chicester, U.K.:
Wiley, 1998.
[11] O. Wasynczuk, D. T. Man, and J. P. Sullivan, “Dynamic behavior of a class of wind
turbine generators during random wind fluctuations,” IEEE Trans. Power App.
Syst., vol. 100, pp. 2837–2845, June 1981.
[12] M. Fujimitsu, T. Komatsu, K. Koyanagi, K. Hu, and R. Yokoyama, “Modeling of
doubly-fed adjustable-speed machine for analytical studies on long-term
dynamics of power system” in Proc. PowerCon, Dec. 2000.
67
[13] Ming Yin, Student Member, IEEE, Gengyin Li, Member,” Modeling of the Wind
Turbine with a PermanentMagnet Synchronous Generator for Integration” in IEEE
Power Engineering Society General Meeting, Jun. 2006, Montreal, Canada.
[14] S. Hier, “Grid Integration of Wind Energy Conversion Systems”, John Wiley and
sons, 1998.
[15] Y. D. Song, B. Dhinakaran, and X. Y. Bao, “Variable speed control of wind
turbines using nonlinear and adaptive algorithms,” Journal of Wind Engineering
and Industrial Aerodynamics, vol. 85, pp. 293-308.
[16] S. K. Chung, “Phase-locked loop for grid-connected three-phase power conversion
systems”, IEE Proc. Electr. Power Appl., vol. 147.
[17] T. Sun, Z. Chen, and F. Blaabjerg, “Voltage recovery of grid-connected wind
turbines after a short-circuit fault,” in Proc. The 29th Annual Conf. Of IEEE Ind.
Electron. Soc., IECON’03, Roanoke, VA, USA.
68