Electropneumatic Positioner Type 3730-2 Mounting and Operating Instructions EB 8384-2 EN Firmware version 1.3x Edition April 2005 Fig. 1 · Type 3730-2
Transcript
Page 1: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Electropneumatic PositionerType 3730-2

Mounting andOperating Instructions

EB 8384-2 ENFirmware version 1.3xEdition April 2005

Fig. 1 · Type 3730-2

Page 2: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Contents Page

1 Design and principle of operation . . . . . . . . . . . . . . . . . . . 81.1 Additional equipment . . . . . . . . . . . . . . . . . . . . . . . . . 91.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2 Attachment to the control valve – Mounting parts and accessories . . . 132.1 Direct attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . 162.1.1 Type 3277-5 Actuator. . . . . . . . . . . . . . . . . . . . . . . . . 162.1.2 Type 3277 Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . 182.2 Attachment according to IEC 60534-6 . . . . . . . . . . . . . . . . . 202.3 Attachment to Type 3510 Micro-flow Valve. . . . . . . . . . . . . . . 222.4 Attachment to rotary actuators . . . . . . . . . . . . . . . . . . . . . 242.5 Reversing amplifier for double-acting actuators . . . . . . . . . . . . . 262.6 Attaching an external position sensor . . . . . . . . . . . . . . . . . 282.6.1 Mounting the position sensor with direct attachment. . . . . . . . . . . 282.6.2 Mounting the position sensor with attachment according to IEC 60534-6 302.6.3 Mounting the position sensor to Type 3510 Micro-flow Valve . . . . . . 312.6.4 Mounting the position sensor to rotary actuators . . . . . . . . . . . . 32

3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343.1 Pneumatic connections . . . . . . . . . . . . . . . . . . . . . . . . 343.1.1 Signal pressure gauges . . . . . . . . . . . . . . . . . . . . . . . . 343.1.2 Supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343.2 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . 353.2.1 Switching amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . 37

4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384.1 Operator controls and display . . . . . . . . . . . . . . . . . . . . . 384.2 Enabling and selecting parameters . . . . . . . . . . . . . . . . . . 404.3 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 414.3.1 Automatic and manual operating modes . . . . . . . . . . . . . . . . 414.3.2 SAFE – Fail-safe position . . . . . . . . . . . . . . . . . . . . . . . 42

5 Start-up and settings . . . . . . . . . . . . . . . . . . . . . . . . . 425.1 Determining the fail-safe position . . . . . . . . . . . . . . . . . . . 425.2 Setting the volume restriction Q . . . . . . . . . . . . . . . . . . . . . 435.3 Limiting the signal pressure . . . . . . . . . . . . . . . . . . . . . . 435.4 Checking the operating range of the positioner . . . . . . . . . . . . . 435.5 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455.5.1 Initialization modes . . . . . . . . . . . . . . . . . . . . . . . . . . 465.6 Fault/failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 535.7 Zero calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

2 EB 8384-2 EN

Contents

Page 3: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

5.8 Reset to default values . . . . . . . . . . . . . . . . . . . . . . . . 545.9 Start-up via local interface (SSP) . . . . . . . . . . . . . . . . . . . . 55

6 Status and diagnostic alarms . . . . . . . . . . . . . . . . . . . . . 556.1 Standard EXPERT diagnostics . . . . . . . . . . . . . . . . . . . . . 556.2 Extended EXPERT+ diagnostics . . . . . . . . . . . . . . . . . . . . . 566.3 Classification of the status alarms and condensed status. . . . . . . . . 56

7 Adjusting the limit switch . . . . . . . . . . . . . . . . . . . . . . . 59

8 Quick start-up guide . . . . . . . . . . . . . . . . . . . . . . . . . 618.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 618.2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 628.3 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 638.3.1 Simplest method (MAX) . . . . . . . . . . . . . . . . . . . . . . . . 638.3.2 Precise method (NOM) . . . . . . . . . . . . . . . . . . . . . . . . 638.3.3 Manual method (MAN) . . . . . . . . . . . . . . . . . . . . . . . . 63

9 Retrofitting an inductive limit switch . . . . . . . . . . . . . . . . . . 64

10 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

11 Servicing explosion-protected devices . . . . . . . . . . . . . . . . . 65

12 Code list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

13 Setting with TROVIS-VIEW software – Parameter list . . . . . . . . . . 8013.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8013.2 Starting TROVIS-VIEW and performing basic settings . . . . . . . . . . 8013.3 Setting the parameters. . . . . . . . . . . . . . . . . . . . . . . . . 8413.4 Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

14 Dimensions in mm . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Test certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

EB 8384-2 EN 3

Contents

Page 4: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

4 EB 8384-2 EN

Safety instructions

General safety instructions

The positioner may only be assembled, started up or operated by trainedand experienced personnel familiar with the product.According to these mounting and operating instructions, trained personnel isreferred to as individuals who are able to judge the work they are assignedto and recognize possible dangers due to their specialized training, theirknowledge and experience as well as their knowledge of the relevantstandards.

Explosion-protected versions of this positioner may only be operated bypersonnel who have undergone special training or instructions or who areauthorized to work on explosion-protected devices in hazardous areas.Refer to section 11 on Servicing explosion-protected versions.

Any hazards that could be caused by the process medium, the operatingpressure, the signal pressure or by moving parts of the control valve are tobe prevented by means of the appropriate measures.

If inadmissible motions or forces are produced in the actuator as a result ofthe supply pressure level, it must be restricted by means of a suitable supplypressure reducing station.

Proper shipping and appropriate storage are assumed.

Note! The device with a CE marking fulfils the requirements of the Directives94/9/EC (ATEX) and 89/336/EEC (EMC).The declaration of conformity can be viewed and downloaded on theInternet at http://www.samson.de.

Page 5: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 5

Versions

Article code Type 3730-2 X X X X X 0 0 X 0 X 0 0 X 0 X X

Explosion protectionWithout

II 2 G EEx ia IIC T6/II 2 D IP 65 T 80 °Cacc. to ATEXCSA/FM intrinsically safe/non incendive

II 3 G EEx na II T6acc. to ATEX

01

38

Additional equipment

Inductivelimit switch

WithoutWith Type SJ 2-SN

01 0

Sol. valve SIL 4 Without24 V DC

04

Analogposition transmitter

WithoutWith

01

ExternalPosition sensor

WithoutWith 0

01

Diagnostics ExpertExpert + (extended)

12

Housing material AluminumStainless steel 1.4581 0

01

Positioner forspecialapplications

Without

Free of substances thatimpair painted surfaces

Exhaust air with pneum.connection ¼ NPT

0

1

2

Special versions Without

IECEx 1

0

0

0

1

0

2

Page 6: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

6 EB 8384-2 EN

Firmware modification

Modifications of positioner firmware in comparison to previous versions

Previous New

1.01 1.10

Via the serial interface and the serial interface adapter, the positioner can beconfigured and operated using TROVIS-VIEW software.

The following additional status indications were implemented:Code 76 - No emergency modeCode 77 - Program loading errorDisplays number of zero calibrations performed since the last initialization.

For initialization of "AIR TO CLOSE" actuators, the direction of action (Code7) is automatically set to increasing/decreasing.

Code 3, the activation period of the enabled configuration function was ex-tended to 120 s.

1.10 1.20

Electronics changed, no new functions added.

1.20 1.30

New EXPERT+ diagnostics functions (Code 48) addedPositioner in EXPERT+ version with extended diagnostics features.

A running initialization can be canceled by pressing the pushbutton.

Page 7: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 7

Firmware modification

Page 8: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

1 Design and principle ofoperation

The electropneumatic positioner is mountedto pneumatic control valves and is used toassign the valve position (controlledvariable x) to the control signal (referencevariable w). The DC control signal receivedfrom a control unit is compared to the travelor rotational angle of the control valve andissues a signal pressure (output variable y).

The positioner is designed depending on thecorresponding accessories for directattachment to Type 3277 Actuators or forattachment to actuators according toIEC 60534-6 (NAMUR).

Additionally, a coupling wheel included inthe accessories is required to transfer the ro-tary motion for rotary actuators according toVDI/VDE 3845.Springless rotary actuators require an ac-cessory reversing amplifier to permit thepowered operation in either direction.

The positioner basically consists of a travelsensor system that functions proportional tothe resistance, an analog i/p module withdownstream booster as well as the electronicunit with a microcontroller.The positioner is fitted with three binary con-tacts as standard: A fault alarm output isused to indicate a fault to the control stationand two configurable software limit switchesto indicate the valve’s end positions.The position of the valve is transmitted aslinear travel motion or angle of rotation viapick-up lever and travel sensor (2) to an an-alog PD controller (3). Simultaneously, anA/D converter (4) transmits the position ofthe valve to the microcontroller (5). The PD

controller compares this actual position tothe 4 to 20 mA DC control signal (referencevariable) after it has been converted by theA/D converter (4).In case of a system deviation, the operationof the i/p converter (6) is changed so thatthe actuator (1) is filled or vented via thedownstream air capacity booster (7). Thiscauses the closure member of the controlvalve to move to the position determined bythe reference variable.The pneumatic air capacity booster (7) andthe pressure regulator (8) are provided withsupply air. An intermediate flow regulator(9) with fixed settings is used to purge thepositioner and also guarantees trouble-freeoperation of the pneumatic booster. The out-put signal pressure supplied by the boostercan be limited over the software.The volume restriction Q (10) is used to opti-mize the positioner by adapting it to the ac-tuator size.

Serial interface

The positioner is equipped with an interfaceto allow the SAMSON TROVIS-VIEW Con-figuration and Operator Interface softwareto transmit data and parameters over anadapter cable from the RS-232 interface ofa computer to the positioner. Refer to sec-tion 13.

To detect any valve faults at an early stage,the positioner can optionally be equippedwith EXPERT+ valve diagnostics. You can ac-cess the functions provided by EXPERT+

valve diagnostics over TROVIS-VIEW soft-ware and over the DTM file of the device.Refer to Data Sheet T 8388 EN for more de-tails on EXPERT+ valve diagnostics. Instruc-tions on how to operate the software can be

8 EB 8384-2 EN

Design and principle of operation

Page 9: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

found in the Operating InstructionsEB 8388 EN.

1.1 Additional equipment

As an option, the device can be additionallyequipped with a solenoid valve for forcedventing, an analog position transmitter, aninductive limit switch or an external positionsensor.

Version with solenoid valve

If the operating voltage for the solenoidvalve (12) fails, the supply pressure for thei/p module is vented to the atmosphere. Thepositioner can no longer operate and the

control valve moves to the fail-safe positiondetermined by the actuator, independent ofthe reference variable.

Positioner with position transmitter

The position transmitter (13) is a two-wiretransmitter and issues the travel sensor sig-nal as a 4 to 20 mA signal processed by themicrocontroller.Since this signal is issued independent of thepositioner’s input signal (min. current3.8 mA), the actual travel/angle of rotationis controlled in real-time. Additionally, theposition transmitter provides the possibilityof signaling a positioner fault over a signalcurrent of <2.4 mA or >21.6 mA.

EB 8384-2 EN 9

Design and principle of operation

Fig. 2 · Functional diagram

1 Control valve2 Travel sensor3 PD controller4 A/D converter5 Microcontroller6 i/p converter7 Air capacity booster8 Pressure regulator9 Flow regulator10 Volume restriction11* Inductive limit switch12* Solenoid valve13* Analog position transmitter14 Software limit switches

Alarm 1/215 Fault alarm output

Alarm 316 Display17* Solenoid valve control18* Galvanic isolation19 D/A converter20 Communication interface* Optional

w

x

Q

%S

mm

GG

PD

SerialInterface

162013

15

A2

A3

A1

112

4 195

312

6

7

8

10

1

14

14

w

xy

24V DC

9

17 18

Page 10: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Version with inductive limit switch

The rotary shaft of the positioner carries anadjustable tag which actuates the installedproximity switch.The optional inductive limit switch (11) leadsto A1 and the software limit switch, whichremains in operation, leads to A2.

Version with external position sensor

In this version, only the sensor is mounted tothe control valve. The positioner is locatedseparately from the valve.The connection of x and y signals to thevalve is established via cable and air hosing(only for non-hazardous areas and withoutinductive limit switch).

1.2 Technical data

10 EB 8384-2 EN

Design and principle of operation

Positioner

Nominal travel,adjustable

Direct attachment to Type 3277: 3.6 to 30 mm, attachment acc. to IEC 60534-6:3.6 to 200 mm or 24° to 100° opening angle for rotary actuators

Travel range Adjustable within the nominal travel/nominal angle, max. ratio 1 : 5

Reference variable w Signal range 4 to 20 mA, 2-wire unit, reverse polarity protection,min. span 4 mA, static destruction limit 100 mA

Minimum current 3.6 mA for display, 3.8 mA for operation

Load impedance Version without explosion protection: ≤ 6 V (corresponding to 300 Ω at 20 mA),Explosion-protected version: ≤ 7 V (corresponding to 350 Ω at 20 mA)

Supply air

Supply pressure from 1.4 to 6 bar (20 to 90 psi),Air quality acc. to ISO 8573-1 Edition 2001: Max. particle size and density: Class 4Oil content: Class 3, pressure dew point: Class 3 or at least 10 K beneath the lowestambient temperature to be expected

Signal pressure (output) 0 bar up to supply pressure, limitable to 1.4/2.4/3.7 ±0.2 bar via software

Characteristic,user-defined adjustableover operating software

Linear/equal percentage/reverse equal percentage/butterfly valve linear/butterfly valve eq. percentage/rotary plug valve linear/rotary plug valve eq. percent-age/segmented ball valve linear/segmented ball valve eq.percentageDeviation from terminal-based conformity ≤ 1 %

Hysteresis ≤ 0.3 %

Sensitivity ≤ 0.1 %

Page 11: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 11

Design and principle of operation

Transit time Separately adjustable up to 240 seconds for supply air and exhaust air

Direction of action Reversible

Air consumption, steadystate

Independent from supply pressure approx. 110 ln/h

Air deliveryActuator pressurizedActuator vented

At ∆p = 6 bar: ≥ 8.5 mn3/h, at ∆p = 1.4 bar: 3.0 mn

3/h KVmax (20 °C) = 0.09at ∆p = 6 bar: ≤ 14.0 mn

3/h, at ∆p = 1.4 bar: 4.5 mn3/h KVmax (20 °C) = 0.15

Permissible ambienttemperature

–20 to +80 °C, with metal cable gland –40 to +80 °CThe limits specified in the EC Type Examination Certificate additionally apply forexplosion-protected devices.

Influences Temperature: ≤ 0.15 %/10 K Supply air: NoneVibration: ≤ 0.25 % up to 2000 Hz and 4 g acc. to IEC 770

Electromagneticcompatability Complying with EN 61000-6-2, EN 61000-6-3 and NAMUR Recommendation NE 21

Explosion protection

II 2 G EEx ia IIC T6 / II 2 D IP 65 T 80 °C orII 3 G EEx nA II T6 / II 3 D IP 65 T 80 °C

IECEx ia IIC T6 / IP 54 and IP 65 T 80 °CFM/CSA intrinsically safe Class I, II, III, Division 1, Group A, B, C, D, E, F, G, T6FM/CSA non incendive Class I, Division 2, Group A, B, C, D, T6

Degree of protection IP 65

Communication (local) SAMSON SSP interface and serial interface adapter

Software requirements TROVIS-VIEW with database module 3730-2

Binary contacts 1 fault alarm contact,2 software limit switches with configurable limit values, reverse polarity protection

Signal statusNo response:

Response:

Without explosion protectionConductive (R = 348 Ω)Non-conducting

Ex.-protected version:≥ 2.1 mA≤ 1.2 mA

Operating voltage

Positioners with model no. ../9000 only for connection tosignal converter acc. to EN 60947-5-6.All other versions also for connection to binary input ofthe PLC acc. to EN 61131, Pmax = 400 mW

Only for connection tosignal converter acc. toEN 60 957-5-6

Page 12: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

12 EB 8384-2 EN

Design and principle of operation

Solenoid valve SIL 4 approval acc. to IEC 61508

Input

24 V DC reverse polarity protection, static destruction limit 40 V;

Current consumption I =U 5.6 V4020

−Ω

(corresponding to 4.5 mA at 24 V)

Signal Signal "0" no pick-up ≤ 15 V Signal "1" safe pick-up >19 V

Service life >2 x 105 switching cycles

Implementation insafety-relevant systems incompliance withIEC 61508

Probability of failure on demand of safety functions PFD < 2.8 x 10-7 for a confidencelevel of 95 %.The safe failure fraction (SFF) according to Table A1 in IEC 61508-2 is greater orequal to 0.99. The valves are therefore suitable for implementation in safety-relatedsystems with a hardware fault tolerance of 1 or 2 up to and including SIL 4.

Analog positiontransmitter Two-wire transmitter

Supply voltage 12 to 30 V DC, reverse polarity protection, static destruction limit 40 V

Output signal 4 to 20 mA

Direction of action Reversible

Operating range 0 to 100 % of the travel range, optional also for fault indication over 2.4 or 21.6 mA

Characteristic Linear

Hysteresis and HF influence Same as positioner

Ripple content of outputsignal 0.6 % at 28 Hz acc. to IEC 381 T1

Other influences Same as positioner

Fault indication Can be issued with current signal < 2.4 mA or > 21.6 mA

Inductive limit switch Type SJ 2SN Proximity Switch

For connection to switching amplifier acc. to EN 60947-5-6. Can be used in combination with a software limit switch.

External position sensor

Nominal travel Adjustable same as positioner

Cable Max. 10 m with M12x1 connector, designed for continuous flexing, flame retardantacc. to VDE 0472, reistant to oils, lubricants as well as other corrosive media

Ambient conditionsPerm. temperature: –40 to +105 °C, the limits specified in the EC Type ExaminationCertificate additionally apply for explosion-protected devices.Vibration immunity: up to 10 g in the range between 10 and 2000 Hz

Degree of protection IP 67

MaterialsHousing: Die-cast aluminum GD AlSi12 acc. to DIN 1725 (3.2582), chromated andplastic coated, special version. CrNiMo (1.4581); External parts: Stainless steel1.4571 and 1.4301. Cable gland M20x1.5, black polyamide

Weight Approx. 1.0 kg

Page 13: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2 Attachment to the controlvalve – Mounting parts andaccessories

The positioner can be attached either di-rectly to a SAMSON Type 3277 Actuator oraccording to IEC 60534-6 (NAMUR) to con-trol valves with cast yokes or rod-type yokesas well as to rotary actuators according toVDI/VDE 3845.

For attachment to the various actuators, cor-responding mounting parts and accessoriesare required. These are listed with their or-der numbers in Tables 1 to 5.

On attaching the positioner, it is importantto observe the assignment between leverand pin position according to the travelslisted in the travel tables.

The tables show the maximum adjustmentrange at the positioner. The travel that canbe implemented at the valve is restricted bythe pin position used and additionally by theactuator spring compression required.The positioner is standard equipped with thelever M (pin position 35).

Note!If the standard mounted lever M (pin posi-tion 35) is replaced, the newly mounted le-ver must be moved once all the way as faras it will go in both directions to adapt it tothe internal measuring lever.

EB 8384-2 EN 13

Attachment to the control valve – Mounting parts and accessories

Travel table for direct attachment to Type 3277 Actuator

Type3277-5

and3277

Actuators

Actuator sizecm2

Rated travelmm

Adjustment range at positionerMin. Travel Max.

Requiredlever

Assignedpin position

120 7.5 5 17.6 M 25

120/240/350 15 7.5 35.4 M 35

700 30 10 50 M 50

Travel table for attachment according to IEC 60534-6 (NAMUR)

SAMSON valves Other valves/actuators Requiredlever

Assignedpin position

Type 3271Actuator

cm2 Rated travel mm Min. Travel Max.

60 and 120 withType 3510 Valve 7.5 3.6 17.6 S 17

120 7.5 5.0 17.6 M 25

120/240/350 15 7.5 35.4 M 35

700/1400/2800 15 and 30/30 10 50 M 50

1400/2800 60 14.0 70.8 L 70

1400/2800 60 20.0 100 L 100

2800 120 40.0 200 XL 200

Rotary actuators Opening angle 24° to 100° M 90°

Page 14: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

14 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Table 1 Direct attachment to Type 3277-5 Actuator, see Fig. 3 Order no.

Mounting parts For actuators with 120 cm2 effective diaphragm area 1400-7452

Accessoriesfor theactuator

Switchover plate (old) for Actuator Type 3277-5xxxxxx.00 (old) 1400-6819

Switchover plate new for Actuator Type 3277-5xxxxxx.01 (new) 1400-6822

Connecting plate for additional attachment of a solenoid valve G 1/8Connecting plate (old) for Actuator Type 3277-5xxxxxx.00 (old) 1/8 NPT

1400-68201400-6821

Connecting plate new for Actuator Type 3277-5xxxxxx.01 (new) 1400-6823

Note: Only new switchover and connecting plates can be used with new actuators (Index 01).Old and new plates are not interchangeable.

Accessoriesfor thepositioner

Connecting plate (6) G ¼: 1400-7461 ¼ NPT: 1400-7462

or pressure gauge bracket (7) G ¼: 1400-7458 ¼ NPT: 1400-7459

Pressure gauge mounting kit (8) (output/supply) St. st./Bs:1400-6950

St. st./St. st.:1400-6951

Table 2 Direct attachment to Type 3277 Actuator, see Fig. 4

Accessories

Mounting parts for actuators with 240, 350 and 700 cm2, see Fig. 4 1400-7453

Required piping with screw fittings for "Actuator stemretracts" or when the top diaphragm chamber is filledwith air

cm2 Steel St. steel240 1400-6444 1400-6445350 1400-6446 1400-6447700 1400-6448 1400-6449

Connection block with seals and screw G ¼: 1400-8811 ¼ NPT: 1400-8812

Pressure gauge mounting kit (output and supply) St.st./Bs:1400-6950

St.st/St.st.:1400-6951

Page 15: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 15

Attachment to the control valve – Mounting parts and accessories

Table 4 Attachment to rotary actuators (VDI/VDE 3845 for all sizes of fixing level 2) see Figs. 7 and 8

Mountingparts

With follower clampand coupling wheel

VDI/VDE 3845 for all sizes of fixing level 2for Type 3278 Actuator with 160/320 cm2

for Camflex II

1400-74481400-76141400-9120

Accessories

Connecting plate G ¼: 1400-7461 ¼ NPT: 1400-7462

or pressure gauge bracket (7) G ¼: 1400-7458 ¼ NPT: 1400-7459

Pressure gauge mounting kit (output/supply) St.st./Bs: 1400-6950 St.st./St.st: 1400-6951

Table 5 General accessories

Accessories

Pneumatic reversing amplifier for double-actingactuators

G ¼¼ NPT

1079-11181079-1119

Cable gland M20 x 1.5 Nickel-plated brass 1890-4875

Adapter M 20 x 1.5 to ½ NPT, aluminum 0310-2149

Retrofit kit for inductive limit switch 1x SJ 2-SN 1400-7460

Cover plate with list of parametersand operating instructions

German/English (standard)English/SpanishEnglish/French

1190-07611190-31001190-3142

Table 3 Attachment to NAMUR ribs or control valves with rod-type yokes (rod diameter Ø 35 mm or smaller)according to IEC 60534-6, see Fig. 5

Travel in mm Lever For actuators Order no.

7.5 S Type 3271-5 Actuator with 60/120 cm2 on Type 3510Valve, see Fig. 6 1400-7457

5 to 50 Without (lever M onbasic model)

Actuators from other manufacturers and Type 3271 with120 to 700 cm2 1400-7454

14 to 100 L Actuators f. other manufacturers and Type 3271 w. 1400 cm2 1400-7455

40 to 200 XL Actuators from other manufacturers and Type 3271 with2800 cm2, 120 mm travel 1400-7456

30 or 60 L Type 3271 Actuator with 2800 cm2 and 30 or 60 mm travel 1400-7466

Mounting brackets for Emerson and Masoneilan linear actuatorsIn addition, a mounting kit acc. to IEC 60534-6 is required depending on the travel. See row above. 1400-6771

Accessories

Connecting plate G ¼: 1400-7461 ¼ NPT : 1400-7462

or pressure gauge bracket (7) G ¼: 1400-7458 ¼ NPT: 1400-7459

Pressure gauge mounting kit (output/supply) St.st./Bs: 1400-6950 St.st./St.st.: 1400-6951

Page 16: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.1 Direct attachment

2.1.1 Type 3277-5 Actuator

Refer to Table 1 on page 14 for the requiredmounting parts as well as the accessorieswith their order numbers.Note the travel table on page 13!

Actuator with 120 cm2

Depending on the type of positioner attach-ment, the signal pressure is routed either leftor right of the yoke through a bore to theactuator diaphragm. Depending on thefail-safe action of the actuator "Actuatorstem extends" or "Actuator stem retracts"(valve closes or opens if the supply air fails),the switchover plate (9) must first be at-tached to the actuator yoke. Align theswitchover plate with the correspondingsymbol for left or right attachment accordingto the marking (view looking onto theswitchover plate).

1. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gaugesonto the positioner, making sure bothseal rings (6.1) are seated properly.

2. Remove vent plug (4) on the back of thepositioner and close the signal pressureoutput "Output 38" on the connectingplate (6) or on the pressure gaugebracket (7) with the stopper (5) includedin the accessories.

3. Place follower clamp (3) on the actuatorstem, align and screw tight so that themounting screw is located in the grooveof the actuator stem.

4. Mount cover plate (10) with narrow sideof the cut-out opening (Fig. 3, on the

left) pointing towards the signal pressureconnection. Make sure that the bondedgasket (14) points towards the actuatoryoke.

5. 15 mm travel: Keep the follower pin (2)at lever M (1) on the back of thepositioner in the pin position 35 (deliv-ered state).7.5 mm travel: Remove the follower pin(2) from the pin position 35, reposition itin the bore for pin position 25 andscrew tight.

6. Insert formed seal (15) in the groove ofthe positioner casing.

7. Place positioner on the cover plate (10)in such a manner that the follower pin(2) rests on the top of the follower clamp(3). Adjust the lever (1) correspondinglyand open the positioner cover to holdthe positioner shaft in position at the capor the switch (Fig. 16).The lever (1) must rest on the followerclamp with spring force.Mount the positioner on the cover plate(10) using the two fixing screws. Duringthe installation make sure that the sealring (10.1) is inserted in the bore of theintermediate plate.

8. Mount cover (11) on the other side.Make sure that the vent plug pointsdownwards when the control valve is in-stalled to allow any condensed waterthat collects to drain off.

16 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 17: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 17

Attachment to the control valve – Mounting parts and accessories

Fig. 3 · Direct attachment - Signal pressure connection for Type 3277-5 Actuator with 120 cm2

9 11

Supply 9 Output 38

56

4

7

61010.1

3

2

1

15

6.1

1.11.2

14

8

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp4 Vent plug5 Stopper6 Connecting plate6.1 Seal rings7 Pressure gauge bracket8 Press. gauge mounting kit9 Switchover plate

for actuator10 Cover plate10.1Seal ring11 Cover14 Gasket15 Formed seal

Important!Always use the connecting plate (6)included in the accessories to connectsupply and output.Never screw threaded parts directlyinto the housing.

Symbols

Actuator stemextends

Attachment left Attachment right

Actuator stemretracts

Switchover plate (9)

Signal pressureinput for right

attachmentMarking

Cut-out of coverplate

Signal pressureinput for leftattachment

Page 18: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.1.2 Type 3277 Actuator

Refer to Table 2 on page 14 or the requiredmounting parts as well as the accessorieswith their order numbers.Note the travel table on page 13!

Actuators with 240 to 700 cm2

The positioner can be mounted either on theleft or on the right side of the yoke. The sig-nal pressure is routed to the actuator overthe connection block (12), for actuators withfail-safe action "Actuator stem extends" in-ternally through a bore in the valve yokeand for "Actuator stem retracts" through ex-ternal piping.

1. Place follower clamp (3) on the actuatorstem, align and screw tight so that themounting screw is located in the grooveof the actuator stem.

2. Mount cover plate (10) with narrow sideof the cut-out opening (Fig. 4, on theleft) pointing towards the signal pressureconnection. Make sure that the bondedgasket (14) points towards the actuatoryoke.

3. For actuators with 700 cm2, remove thefollower pin (2) at lever M (1) on theback of the positioner from pin position35, reposition it in the bore for pin posi-tion 50 and screw tight.For actuators 240 and 350 cm2 with15 mm travel, the follower pin (2) re-mains in pin position 35.

4. Insert formed seal (15) in the groove ofthe positioner casing.

5. Place positioner on the cover plate insuch a manner that the follower pin (2)

rests on the top of the follower clamp(3). Adjust the lever (1) correspondinglyand open the positioner cover to holdthe positioner shaft in position at the capor the switch (Fig. 16). The lever (1) mustrest on the follower clamp with springforce. Mount the positioner on the coverplate (10) using the two fixing screws.

6. Make sure that the tip of the gasket (16)projecting from the side of the connec-tion block (12) is positioned above theactuator symbol that corresponds withthe actuator with fail-safe action "Actua-tor stem extends" or "Actuator stem re-tracts." If necessary, remove the threefixing screws and the cover. Then repo-sition the gasket (16) turned by 180°.The previous version of the connectionblock (Fig. 4, bottom) requires the switchplate (13) to be turned such that the cor-responding actuator symbol points to themarking.

7. Place the connection block (12) with theassociated seal rings against thepositioner and the actuator yoke. Screwit tight using the fixing screw (12.1). Foractuators with fail-safe action "Actuatorstem retracts", additionally remove thestopper (12.2) and fit on the externalsignal pressure piping.

8. Mount cover (11) on the other side.Make sure that the vent plug pointsdownwards when the control valve is in-stalled to allow any condensed waterthat collects to drain off.

18 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 19: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 19

Attachment to the control valve – Mounting parts and accessories

Fig. 4 · Direct attachment – Signal pressure connection for Type 3277 Actuator with 240, 350 and 700 cm2

2

10 1415

1 2 3 11

SUPPLY

13

16

B

1.11.2

1212.1

12

12.1

12.2

A

1216 12.2SUPPLY

Cut-out ofcover plate (10)

Actuator stemretracts extends

Stem retracts

Stem extends

Marking

Connection block (old)with switch plate (13)

Lever M

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp10 Cover plate11 Cover12 Connection block

12.1 Screw12.2 Stopper or connection for

external piping13 Switch plate14 Gasket15 Formed seal16 Gasket

Page 20: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.2 Attachment according toIEC 60534-6

The positioner is attached to the controlvalve with a NAMUR bracket (10).

Refer to Table 3 on page 15 for the requiredmounting parts as well as the accessorieswith their order numbers.Note the travel table on page 13!

1. Screw the two bolts (14) to the bracket(9.1) of the stem connector (9), place thefollower plate (3) on top and use thescrews (14.1) to tighten.

Actuator size 2800 cm2:For a travel of 60 mm or smaller, screwthe longer follower plate (3.1) directly tothe stem connector (9). For a travel ex-ceeding 60 mm, mount the bracket (16)first and then the follower plate (3) to thebracket together with the bolts (14) andscrews (14.1).

2. Mount NAMUR bracket (10) to the con-trol valve as follows:For attachment to the NAMUR rib, usean M8 screw (11) and toothed lockwasher directly in the yoke bore.For attachment to valves with rod-typeyokes, use two U-bolts (15) around theyoke.Align the NAMUR bracket (10) in such away that the slot of the follower plate (3)is centrally aligned with the NAMURbracket at mid valve travel.

3. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gauges

(8) on the positioner, making sure bothseal rings (6.1) are seated properly.

4. Select required lever size (1) M, L or XLand pin position according to the actua-tor size and valve travels listed in the ta-ble below.Should you require a pin position otherthan position 35 with the standard in-stalled lever M, or require a lever size Lor XL, proceed as follows:

5. Screw the follower pin (2) in the as-signed lever bore (pin position) as listedin the table. Only use the longer followerpin (2) included in the mounting kit.

6. Place lever (1) on the positioner shaftand screw tight using the disk spring(1.2) and nut (1.1).

Note!If you have mounted a new lever (1), youmust move it once all the way as far as itwill go in both directions.

7. Place positioner on the NAMUR bracketin such a manner that the follower pin(2) rests in the slot of the follower plate(3, 3.1). Adjust the lever (1) correspond-ingly.Screw the positioner to the NAMURbracket using both its fixing screws.

20 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 21: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 21

Attachment to the control valve – Mounting parts and accessories

Fig. 5 · Attachment according to IEC 60534-6 (NAMUR)

10

11

6.1 6 7 8

1

1 14.1

3

3.1

16

15

14

11.21.12

9.19 Attachment to

NAMUR rib

Additional bracket foractuators with 2800 cm2

and travel ≥ 60 mm

Attachment to rod-type yokeRods with Ø max. 35 mm

Lever XL and L

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower plate3.1 Follower plate6 Connecting plate6.1 Seal rings7 Pressure gauge bracket8 Pressure gauge

mounting kit9 Stem connector9.1 Bracket10 NAMUR bracket11 Screw14 Bolt14.1 Screw15 U-bolt16 Bracket

Important!Always use the connecting plate (6) included in the accessories to connectsupply and output. Never screw threaded parts directly into the housing.

Page 22: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.3 Attachment to Type 3510Micro-flow Valve

The positioner is attached to the valve yokeusing a bracket.

Refer to Table 3 on page 15 for the requiredmounting parts as well as the accessorieswith their order numbers.Note the travel table on page 13!

1. Place clamp (3) on the valve stem con-nector, align at a right angle and screwtight.

2. Screw bracket (10) to the valve yoke us-ing two screws (11).

3. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gaugesto the positioner, making sure both sealrings (6.1) are seated properly.

4. Unscrew the standard installed lever M(1) including follower pin (2) from thepositioner shaft.

5. Take lever S (1) and screw follower pin(2) in the bore for pin position 17.

6. Place lever S on the positioner shaft andscrew tight using the disk spring (1.2)and nut (1.1).Move lever once all the way as far as itwill go in both directions.

7. Place positioner on the bracket (10) insuch a manner that the follower pinslides into the groove of the clamp (3).Adjust the lever (1) correspondingly.Screw the positioner to the bracket (10)using both its hexagon screws.

22 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 23: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 23

Attachment to the control valve – Mounting parts and accessories

Fig. 6 · Attachment to Type 3510 Micro-flow Valve

3

10

11

11

6

121.2 1.1

78

6.1

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Clamp6 Connecting clamp6.1 Seal rings7 Pressure gauge bracket8 Pressure gauge

mounting kit10 Bracket11 Screw

Important!Always use the connecting plate (6)included in the accessories to connectsupply and output.Never screw threaded parts directlyinto the housing.

Lever S

Page 24: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.4 Attachment to rotaryactuators

The positioner is mounted to the rotary actu-ator using two pairs of double brackets.

Refer to Table 4 on page 15 for the requiredmounting parts as well as the accessorieswith their order numbers.

Prior to the attachment of the positioner tothe SAMSON Type 3278 Rotary Actuator,you have to mount the associated adapter(5) to the free end of the rotary actuatorshaft.

Note!During the installation of the positioner asdescribed below, it is imperative that the ac-tuator's direction of rotation be observed.

1. Place follower clamp (3) on the slottedactuator shaft or the adapter (5).

2. Place coupling wheel (4) with flat sidefacing the actuator on the followerclamp (3). Refer to Fig. 8 to align slot sothat it matches the direction of rotationwhen the valve is in its closed position.

3. Screw coupling wheel and followerclamp tightly onto the actuator shaftusing screw (4.1) and disk spring (4.2).

4. Screw the bottom pair of brackets (10.1)with the bends pointing either to the in-side or to the outside (depending on theactuator size) to the actuator case. Posi-tion top pair of brackets (10) and screwtight.

5. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gaugesto the positioner, making sure bothO-rings are seated properly.For double-acting, springless rotary ac-tuators, a reversing amplifier is requiredto attach the positioner to the actuator,see section 2.5.

6. Unscrew the standard follower pin (2)from the positioner's lever M (1). Use themetal follower pin (Ø5) included in themounting kit and screw tight into thebore for pin position 90°.

7. Place positioner on the top pair ofbrackets (10) and screw tight. Con-sidering the actuator's direction of rota-tion, adjust lever (1) so that it engages inthe slot of the coupling wheel (4) with itsfollower pin (see Fig. 8). It must be guar-anteed that the lever (1) is parallel to thelong side of the positioner when the ac-tuator is at half its angle of rotation.

8. Stick scale plate (4.3) on the couplingwheel so that the arrow tip indicates theclosed position, and it can be easilyread when the valve is installed.

24 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Fig. 7 · Mounting the coupling wheel with Type 3278

1.21.1

1

2

4.1

4.2

53

Actuator flange

Page 25: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 25

Attachment to the control valve – Mounting parts and accessories

Fig. 8 · Attachment to rotary actuators

Slot

10

10.1

6(7, 8)

1.124.3

5

6.1

4

1.21

Control valve opens clockwise

Control valve opens counterclockwise

Slot

Important!Always use the connectingplate (6) included in theaccessories to connectsupply and output.Never screw threadedparts directly into thehousing.

Legends Figs. 7 and 81 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp (Fig. 7)4 Coupling wheel4.1 Screw4.2 Disk spring4.3 Scale plate4.3 Scale plate5 Actuator shaft

Adapter for Type 32786.1 Seal rings7 Pressure gauge bracket8 Pressure gauge

mounting kit10 Top pair of brackets10.1 Bottom pair of brackets

Page 26: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.5 Reversing amplifier fordouble-acting actuators

For the use with double-acting actuators, thepositioner must be fitted with a reversingamplifier. The reversing amplifier is listed asan accessory in the Table 5 on page 15.

The output signal pressure of the positioneris supplied at the output A1 of the reversingamplifier. An opposing pressure, whichequals the required supply pressure whenadded to the pressure at A1, is applied atoutput A2.The rule A1 + A2 = Z applies.

Mounting

1. Mount the connecting plate (6) from theaccessories in Table 5 to the positioner.Make sure that both O-rings (6.1) areseated correctly.

2. Thread the special nuts (1.3) from theaccessories of the reversing amplifierinto the boreholes of the connectingplate.

3. Insert the gasket (1.2) into the recess ofthe reversing amplifier and push boththe hollowed special screws (1.1) intothe connecting boreholes A1 and Z.

4. Place the reversing amplifier onto theconnecting plate (6) and screw tight us-ing both the special screws (1.1).

5. Use a screwdriver (8 mm wide) to screwthe enclosed filters (1.6) into the con-necting boreholes A1 and Z.

Note!The sealing plug (1.5) in the Type 3730Positioner should not be unscrewed out ofthe reversing amplifier.The rubber seal (1.4) is not required andcan be removed when the sealing plug isused.

Signal pressure connections

A1: Output A1 leading to the signal pressureconnection at the actuator which opens thevalve when the pressure increases

A2: Output A2 leading to the signal pressureconnection at the actuator which closes thevalve when the pressure increases

Set slide switch on positioner toAIR TO OPEN.

26 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 27: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 27

Attachment to the control valve – Mounting parts and accessories

Fig. 9 · Mounting a reversing amplifier

A1

1.5 1.6

1.3

6.266.1

1.2 1.1 1 1.6

Z

A2

1.4A1 A2

Z

A1

Output 38 Supply 9

Out

put 3

8Su

pply

9

1.3 1.21.1

1 Reversing amplifer1.1 Special screws1.2 Gasket1.3 Special nuts1.4 Rubber seal1.5 Sealing plug1.6 Filter

6 Connecting ring6.1 O-rings6.2 Screws

From the positioner

Control signals tothe actuator

Page 28: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.6 Attaching an externalposition sensor

Refer to Table 6 on page 33 for a list of themounting parts as well as the accessories re-quired for mounting the position sensor.Accessories for the pneumatic connection tothe positioner housing can be found in Ta-ble 7.

In the positioner version with an externalposition sensor, the sensor placed in a sepa-rate housing is attached over a plate orbracket to the control valve. The travelpick-off corresponds to that of a standarddevice.The positioner unit can be mounted as re-quired to a wall or a pipe.

For the pneumatic connection either a con-necting plate (6) or a pressure gaugebracket (7) must be fixed to the housing, de-pending on the accessory chosen. Makesure the seal rings (6.1) are correctly in-serted (see Fig. 5, bottom right).

For the electric connection the connectinglead must be fitted with an M12x1 connec-tor plug at one end. The lead end withoutthe plug can be shortened, if required, andwired to the connector included (section 3.2on page 35). The electrical and pneumaticconnections between the sensor and thepositioner unit may be a maximum of 10meters.

Note! In addition, the instructions in section3.1 and 3.2 apply for the pneumatic andelectrical connection.Operation and setting are described in sec-tions 4 and 5.

2.6.1 Mounting the position sensorwith direct attachment

Type 3277-5 Actuator with 120 cm2

The signal pressure from the positioner isrouted over the signal pressure connectionof the connecting plate (9, Fig. 11 left) to theactuator diaphragm chamber. To proceed,first screw the connecting plate (9) includedin the accessories onto the actuator yoke.

Turn the connecting plate (9) so that thecorrect symbol for the fail-safe position"Actuator stem extends" or "Actuatorstem retracts" is aligned with the mark-ing (Fig. 11, below).

Make sure that the gasket for the con-necting plate (9) is correctly inserted.

The connecting plate has boreholes withNPT and G threads.Seal the threaded connection that is notused with the rubber seal and squareplug.

28 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Fig. 10 · Positioner unit with sensor mounted on amicro-flow valve

Page 29: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Type 3277 Actuator with 240 to 700 cm2:

The signal pressure is routed to the connec-tion at the side of the actuator yoke for theversion "Actuator stem extends".For the fail-safe position "Actuator stem re-tracts" the connection on the top diaphragmcase is used. The connection at the side ofthe yoke must be fitted with a venting plug(accessories).

Mounting the position sensor

1. Place the lever (1) on the sensor inmid-position and hold it in place.Unthread the nut (1.1) and remove thelever together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto themounting plate (21).

3. Depending on the actuator size andrated travel of the valve, determine therequired lever and position of the fol-lower pin (2) from the travel table onpage 13.The positioner is delivered with lever Min pin position 35 on the sensor. If nec-essary, remove the follower pin (2) fromits pin position and move it to the bore-hole for the recommended pin positionand screw tight.

4. Place the lever (1) and disk spring (1.2)on the sensor shaft.

EB 8384-2 EN 29

Attachment to the control valve – Mounting parts and accessories

Fig. 11 · Mounting for Type 3277-5 Actuator (left) and Type 3277 Actuator (right)

2021

9

111.11.2

32

1

Signal pressure

Venting plug

Actuator stemextends retractsSymbol

Marking

Signal pressure

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp9 Connecting plate11 Cover20 Position sensor21 Mounting plate

Page 30: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

5. Place the follower clamp (3) on the actu-ator stem, align and fasten it, makingsure that the fastening screw rests in thegroove of the actuator stem.

6. Place the mounting plate (21) togetherwith the sensor onto the actuator yoke sothat the follower pin (2) rests on the topof the follower clamp (3). It must rest onit with spring force.Screw tight the mounting plate (21) ontothe actuator yoke using both fixingscrews.

7. Mount cover (11) on the other side.Make sure that the vent plug pointsdownwards when the control valve is in-stalled to allow any condensed waterthat collects to drain off.

2.6.2 Mounting the position sensorwith attachment according toIEC 60534-6

For the required mounting parts as well asthe accessories, refer to the order numberslisted in Tables 6 and 7 on page 33.

1. Place the lever (1) on the sensor inmid-position and hold it in place.Unthread the nut (1.1) and remove thelever together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto thebracket (21).

The standard attached lever M with the fol-lower pin (2) at position 35 is designed for120, 240 and 350 cm2 actuators with15 mm rated travel.

30 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Fig. 12 · Mounting according to IEC 60534-6 (NAMUR)

20 21 1.1, 1.2 14.1 3 14 99.1

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower plate9 Stem connector9.1 Bracket14 Bolt14.1 Screws20 Position sensor21 Bracket

Page 31: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

For other actuator sizes or travels, select thelever and pin position from the travel tableon page 13. Lever L and XL are included inthe mounting kit.

3. Place the lever (1) and disk spring (1.2)on the sensor shaft.Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

4. Screw both bolts (14) to the bracket(9.1) of the stem connector (9). Attachthe follower plate (3) and fix with thescrews (14.1).

5. Place the bracket with the sensor at theNAMUR rib in such a manner that thefollower pin (2) rests in the slot of the fol-lower plate (3), then screw the bracketusing its fixing screws onto the valve.

2.6.3 Mounting the position sensorto Type 3510 Micro-flowValve

For the required mounting parts as well asthe accessories, refer to the order numberslisted in Tables 6 and 7 on page 33.

1. Place the lever (1) in mid-position andhold it in place. Unscrew the nut (1.1)and remove the standard attached leverM (1) together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto thebracket (21).

3. Select the lever S (1) from the accesso-ries and screw the follower pin (2) intothe hole for pin position 17.Place the lever (1) and disk spring (1.2)on the sensor shaft.

Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

4. Place the follower clamp (3) on the stemconnector, align it at a right angle andscrew tight.

5. Position the bracket (21) with the posi-tion sensor on the valve yoke and screwtight, making sure the follower pin (2)slides into the groove of the followerclamp (3).

EB 8384-2 EN 31

Attachment to the control valve – Mounting parts and accessories

Fig. 13 · Mounting a micro-flow valve

20 211.11.2

1

3

2

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp20 Position sensor21 Bracket

Page 32: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

2.6.4 Mounting the position sensorto rotary actuators

For the required mounting parts as well asthe accessories, refer to the order numberslisted in Tables 6 and 7 on page 33.

1. Place the lever (1) in mid-position andhold it in place. Unscrew the nut (1.1)and remove the standard attached leverM (1) together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto thebracket (21).

3. Replace the follower pin (2) normally at-tached to the lever (1) with the metal fol-lower pin (∅ 5) from the accessoriesand screw it into the hole for pin posi-tion 90°.

4. Place the lever (1) and disk spring (1.2)on the sensor shaft.Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

Follow the instructions describing attachmentto the standard positioner in section 2.4Instead of the positioner, attach the positionsensor (20) with its mounting plate (21).

32 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Fig. 14 · Positioner unit with sensor mounted on rotary actuators

2021

2 1 1.1, 1.2

1 Lever1.1 Nut1.2 Disk spring2 Follower pin20 Position sensor21 Mounting plate

Page 33: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 33

Attachment to the control valve – Mounting parts and accessories

Table 6 Mounting parts for position sensor Order no.

Direct attachment Mounting parts for actuators with 120 cm2 see Fig. 11 left 1400-7472

Accessories foractuator 120 cm2

Connecting plate (9, old) for Actuator Type3277-5xxxxxx.00

G 1/81/8 NPT

1400-68201400-6821

Connecting plate (new) for Actuator Type 3277-5xxxxxx.01 (new) 1400-6823

Note: Only new switchover and connecting plates can be used with new actuators (Index01). Old and new plates are not interchangeable.

Direct attachment Mounting parts for actuators with 240, 350 and 700 cm2, see Fig. 11 right 1400-7471

NAMUR attachment Mounting parts for attachment to NAMUR rib w. lever L and XL, see Fig. 12 1400-7468

Attachment tomicro-flow valves Mounting parts for Type 3510 Micro-flow Valve, see Fig. 13 1400-7469

Attachment to rotaryactuators Mounting parts with follower clamp and coupling wheel, see Fig. 14 1400-7473

Table 7 Postioner accessories Order no.

Accessories

Connecting plate (6)G ¼¼ NPT

1400-74611400-7462

or pressure gauge bracket (7)G ¼¼ NPT

1400-74581400-7459

Pressure gauge mounting kit (8) (output and supply)St. steel/BrassSt.st./St. steel

1400-69501400-6951

Page 34: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

3 Connections

3.1 Pneumatic connections

Caution!The threads in the positioner housing are notdesigned for direct air connection!

The screw glands must be screwed into theconnecting plate, the pressure gauge mount-ing block or the connection block from theaccessories. The air connections are option-ally designed as a bore with ¼ NPT or G ¼thread.The customary fittings for metal and copperpipes or plastic hoses can be used.

Note!The supply air must be dry and free from oiland dust. The maintenance instructions forupstream pressure reducing stations must beobserved.Blow through all air tubes and hoses thor-oughly prior to connecting them.

If the positioner is attached directly to theType 3277 Actuator, the connection of thepositioner's output pressure to the actuatoris fixed. For attachment according toIEC 60534-6 (NAMUR), the signal pressurecan be routed to either the top or bottom di-aphragm chamber of the actuator, depend-ing on the actuator's fail-safe action "Actua-tor stem extends" or "Actuator stem re-tracts".For rotary actuators, the manufacturer'sspecifications for connection apply.

3.1.1 Signal pressure gauges

To monitor the supply air (Supply) and sig-nal pressure (Output), we recommend thatpressure gauges be attached (see accesso-ries in Tables 1 to 4).

3.1.2 Supply pressure

The required supply air pressure dependson the bench range and the actuator's oper-ating direction (fail-safe action).The bench range is registered on the name-plate either as spring range or signal pres-sure range depending on the actuator. dieThe direction of action is marked FA or FE,or by a symbol.

Actuator stem extends FA (Air to openATO)

Fail-safe position "Valve Closed"(for globe and angle valves):

Required supply pressure = Upper benchrange value + 0.2 bar, minimum 1.4 bar.

Actuator stem retracts FE (Air to close ATC)

Fail-safe position "Valve Open"(for globe and angle valves):For tight-closing valves, the maximum signalpressure pstmax is roughly estimated as fol-lows:

pstmax = F +d p

A

2

4⋅ ⋅

⋅π ∆

34 EB 8384-2 EN

Connections

Page 35: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

d = Seat diameter [cm]∆p = Differential pressure across the valve

[bar]A = Actuator diaphragm area [cm2]F = Upper bench range of the actuator

[bar]

If there are no specifications, calculate asfollows:

Required supply pressure =Upper bench range value + 1 bar

Note!The signal pressure at the output (Out-put 38) of the positioner can be limited to1.4, 2.4 or 3.7 bar over Code 16 or thepressure limit can be deactivated (MAX).

3.2 Electrical connections

For electrical installation, you are re-quired to observe the relevantelectrotechnical regulations and theaccident prevention regulations thatapply in the country of use. In Ger-many, these are the VDE regulationsand the accident prevention regula-tions of the employers' liability insur-ance association.

The following standards apply for assemblyand installation in hazardous areas:EN 60079-14: 2003 (VDE 0165 Part 1/8.98) "Electrical apparatus for explosive gasatmospheres" and EN 50281-1-2: 1999(VDE 0165 Part 2/11.99) "Electrical appa-ratus for use in the presence of combustibledust".For the interconnection of intrinsically safeelectrical equipment, the permissible maxi-mum values specified in the EC type exami-nation certificate apply (Ui or U0; Ii or I0; Pior P0; Ci or C0, and Li or L0).

The following applies for equipment withtype of protection EEx nA (non-sparking ap-paratus) according to the standard EN50021 (1999): Connecting, interrupting, orswitching circuits while energized is only al-lowed during installation, maintenance orrepair work.The following applies for equipment con-nected to energy-limited circuits with type ofprotection EEx nL (energy-limited apparatus)according to the standard EN 50021(1999): This type of equipment may beswitched under normal operating conditions.

EB 8384-2 EN 35

Connections

Page 36: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

For the interconnection of equipment to en-ergy-limited circuits with type of protectionEEx nL IIC, the permissible maximum valuesspecified in the statement of conformity orthe addenda to the statement of conformityapply.

Caution!The terminal assignment specified in the cer-tificate must be adhered to. Reversing theassignment of the electrical terminals maycause the explosion protection to become in-effective!Do not tamper with enameled screws insideor on the housing.

Note on the selection of cables and wires:To install intrinsically safe circuits, observesection 12 of the standard EN 60079-14:2003 (VDE 0165 Part 1). To run multi-corecables or lines with more than one intrinsi-cally safe circuit, section 12.2.2.7 of thisstandard applies.An additional cable gland can be installedwhen connecting the device over two sepa-rate cables. Cable entries left unused mustbe sealed with blanking plugs. Devices usedat ambient temperatures down to –20 °Cmust have metal cable entries.

The wires for the reference variable must beconnected to the terminals 11 and 12 lo-cated in the housing. Only use a currentsource!

Caution!The erroneous connection of a voltagesource of just around 7 V (or around 2 Vwhen connected to the wrong pole) candamage the positioner.

In general, it is not necessary to connect thepositioner to a bonding conductor. Shouldthis be required, however, this conductorcan be connected inside the device.Depending on the version, the positioner isequipped with inductive limit switchesand/or a solenoid valve.The position transmitter is operated on atwo-wire circuit. The usual supply voltage is24 V DC. Considering the resistance of thesupply leads, the voltage at the positiontransmitter terminals can be between 12and 30 V DC.Refer to Fig. 15 or the label on the terminalstrip for terminal assignment.Note! The minimum permissible referencevariable should not fall below 3.8 mA foroperating the positioner.

Accessories:Plastic cable gland M20 x 1.5:Black Order no. 1400-6985Blue Order no. 1400-6986Nickel-plated brass Order no. 1890-4875Adapter M20 x 1.5 to ½ NPTAluminum, powder-coated

Order no. 0310-2149

36 EB 8384-2 EN

Connections

Page 37: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Connection for version with external posi-tion sensorThe terminal assignment is fixed by the con-nector of the connecting lead.

Shorten the connecting lead to the re-quired length and strip the insulation off.Route the strands to the following con-tacts of the free connector:

Contact Cable color1 Brown2 White3 Blue4 Black shielding5 Green/yellow

Connect the fixed M12x1 plug connectorto the position sensor and the mountedconnector to the positioner unit.

3.2.1 Switching amplifiers

For operation of the limit switches, switchingamplifiers must be connected in the outputcircuit. To ensure the operating reliability ofthe positioner, the amplifiers should complywith the limit values of the output circuitsconforming to EN 60947-5-6.If the positioner is to be installed in hazard-ous areas, the relevant regulations must beobserved.

EB 8384-2 EN 37

Connections

Fig. 15 · Electric connections

G

+81 -82 +11 -12 +83 -84 +51 -52

A2A3 A1

+41 -42 +31 -32

ASwitching amplifieracc. to EN 60947-5-6

24 V DCsolenoid

valve

mAControl signal

A3Fault

indication

Limit switchesA2 A1

Software Softwareor inductive

2-wire transmittersupply unit for optional po-sition transmitter only

Optional Optional

Page 38: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

4 Operation

Note!A summary about operating and start upcan be found in section 8 on page 61. Aleaflet including the same summary is alsoenclosed with the positioner.

4.1 Operator controls anddisplay

Rotary pushbutton

The positioner is mainly operated with therotary pushbutton.

Turn the button to select and set codes,parameter and values. Press it to confirmthem.

Slide switch AIR TO OPEN or AIR TOCLOSE

This switch is used to adapt the positioner tothe operating direction of the actuator.

For actuator where the supply pressureopens the valve, fail-safe position: "springsclose valve": switch position AIR TO OPEN.

For actuator where the supply pressurecloses the valve, fail-safe position: "springsopen valve": switch position AIR TO CLOSE.

For positioners with an attached reversingamplifier for double-acting rotary actuators(section 2.5): switch position AIR TO OPEN.

The switch position is prompted prior to aninitialization. After an initialization has beencompleted, changing the switch positiondoes not have any effect on the operation ofthe positioner.

Volume restriction Q

The volume restriction is used to adapt theair delivery to the actuator size. Two fixedsettings are possible depending on how theair is routed at the actuator:

For actuators smaller than 240 cm2 witha loading pressure connection at the side(Type 3271-5), set restriction to MINSIDE.

For a connection at the back (Type3277-5), set restriction to MIN BACK.

For actuators 240 cm2 and larger, set toMAX SIDE for a side connection and toMAX BACK for a connection at the back.

Displays

The LC display indicates symbols that areassigned to parameters, codes and func-tions.The bar graph in the operating modesmanual and automatic indicates thesystem deviation that depends on the sign(+/–) and the value. One bar graph elementappears per 1 % system deviation.

If the device has not yet been initialized (seesection 4.3.1), the lever position in degreesin relation to the longitudinal axis is indi-cated instead of the system deviation. Onebar graph element corresponds to approxi-mately a 5° angle of rotation.

If the fifth element blinks (value displayed> 30°), the permissible angle of rotation hasbeen exceeded. Lever and pin position mustbe checked.

38 EB 8384-2 EN

Operation

Page 39: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 39

Operation

Fig. 16 · Display and operator controls

AUtO Automatic modeCL ClockwiseCCL CounterclockwiseErr ErrorESC EscapeHI ix greater than 21.6 mALO ix smaller than 2.4 mALOW w too lowMAN Manual mode

MAX Maximum rangeNO Not availableNOM Nominal travelON ONOFF OFFRES ResetRUN StartSAFE Fail-safe positionSUb Substitute calibration

TunE Initialization in progressYES AvailableZP Zero calibration

Increasing/increasing Increasing/decreasing

Blinking Controlled operationBlinking Not initialized

Displays and their meaning

AIR

TOOPEN

CLO

SE

INIT C

AU

TION

VALVE

AC

TUA

TES

MIN

SIDE

MA

XBA

CK

MIN

BAC

KM

AX

SIDE Q

%S

mm

%S

mm

SERIAL

INTERFA

CE

Failure/fault Manual operation Control operation Code

Configurationenabled

Maintenance requirementMaintenance demand

Fail-safe positionactive

Bar graph forsystem deviationor lever position

Units

Limit switchAlarm 2

DesignationPositionParameter

Limit switchAlarm 1

Initialization key Cap or rotary switch Metal tag of proximity switch

SSP interface

Switch forfail-safe actionof the actuator

Volume restriction

Rotary pushbutton

Page 40: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

4.2 Enabling and selectingparameters

The codes which are marked with an aster-isk (*) in section 12 on page 66 onwardsmust be enabled with Code 3 before the as-sociated parameters can be configured asdescribed below.

Code 3Configurationnot enabled

Configurationenabled

From the current display, turn the rotarypushbutton until Code 3 and OFF ap-pear on the display.Confirm Code 3 by pressing the but-ton, the code number blinks.

Turn button until ON appears.Confirm setting by pressing the but-ton.

Configuration is enabled and is indicated bysymbol appearing on the display.

Now you can adjust the codes, parametersand values for the control valve in any de-sired order by turning the button. Con-firm settings by pressing the button.

Note!To cancel a value that you have just enteredunder a code, turn the button until ESCappears on the display and press to con-firm.

Canceling the setting

Note! If no settings are entered within120 seconds, the enabled configurationfunction becomes invalid and the display re-sets to Code 0.

The code list on page 66 onwards in section12 shows all parameters that can be ad-justed, including their description and theirdefault settings.

Important!After attaching the positioner to the valve aswell as setting the fail-safe position and thevolume restriction, it is sufficient for standardoperation to press the initialization key inorder to ensure optimum positioner opera-tion (section 5.5 on page 45).For this purpose, the positioner must be op-erated with its default values. If necessary, areset must be carried out (section 5.8 onpage 54).

40 EB 8384-2 EN

Operation

Page 41: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

4.3 Operating modes

4.3.1 Automatic and manualoperating modes

Prior to initialization:

If the positioner has not been initialized yet,the automatic operating AUtO cannot be se-lected.The valve can only be positioned manuallywith the positioner.

To proceed, turn button clockwise untilCode 1 appears, then confirm Code 1 bypressing the button.

If both the code number and the hand sym-bol are blinking, the valve can be manuallypositioned by turning the button.

After initialization:

After successful initialization in the MAX,NOM or MAN mode (section 5.5.1), thepositioner is in the automatic controloperation mode .

Standard

Switching to manual operating mode

Over Code 0, press the button, AUtOappears in the display, Code 0 blinks.

Turn button until MAN appears.

Press button to switchover to the manualoperating mode .

The switchover is smooth since the manualoperating mode starts up with the set pointlast used during automatic operating mode.The current position is displayed in %.

Adjusting the manual set point

Turn button until Code 1 appears.

Press button to confirm, Code 1 blinks.While Code 1 is blinking, you can move thevalve to the position required by turning thebutton. To proceed, turn the button untilenough the positioner has built up enoughpressure and the control valve starts to react.The positioner automatically returns to man-ual mode with Code 0 if the button is notactivated within two minutes.Switching from manual to automatic oper-ating mode works in the same manner.First, you must reset the positioner to Code 0and set it to automatic mode AUtO and con-firm.

EB 8384-2 EN 41

Operation

%

% %

Page 42: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

4.3.2 SAFE – Fail-safe position

If you want to move the valve to fail-safe po-sition, proceed as follows:

Select Code 0, press the button, AUtO orMAN appears on the display, Code 0blinks.

Turn the button until SAFE appears.

Press the button to confirm this setting.

Operating mode SAFE has been selected,symbol S for the fail-safe position appears.

Caution!The valve moves to the fail-safe position.

Once the positioner is initialized, the currentvalve position is indicated on the digital dis-play in %.

If you want to return the valve from thefail-safe position to the operating modeAUtO or MAN, the button must bepressed while Code 0 is active.

When the code number blinks, turn thebutton to switch to the desired operatingmode.Press the button to confirm.

5 Start-up and settings

Note!A summary about start-up and operationcan be found in section 8 on page 61. Aleaflet including the same summary is alsoenclosed with the positioner.

Connect pneumatic supply air(Supply 9), making sure the pressure iscorrect as described in section 3.1.

Apply an electrical reference variable of4 to 20 mA (terminals 11 and 12).

The voltage supply >19 V DC for versionwith a solenoid valve must be connectedat terminals 81 (+) und 82 (–).

Warning!The signal pressure supplied maycause the actuator stem to move, beaware of risk of injury!

5.1 Determining the fail-safeposition

To adapt the positioner to the operating di-rection of the actuator, set slide switch toAIR TO OPEN or AIR TO CLOSE .

AIR TO OPEN = Signal pressure opens thevalve, for fail-safe position: actuator stemextends/valve closedAIR TO CLOSE = Signal pressure closes thevalve, for fail-safe position: actuator stemretracts/valve open.

The switch position is prompted prior to aninitialization. After an initialization has beencompleted, changing the switch position

42 EB 8384-2 EN

Start-up and settings

S

Page 43: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

does not have any effect on the operation ofthe positioner.

5.2 Setting the volume restriction Q

For actuators smaller than 240 cm2 witha loading pressure connection at the side(Type 3271-5), set restriction to MINSIDE.

For a connection at the back(Type 3277-5), set restriction to MINBACK.

For actuators 240 cm2 and larger, set toMAX SIDE for a side connection and toMAX BACK for a connection at the back.

Note! The positioner must re-initialized if thevolume restriction setting is changed afterthe positioner has already been initialized.

Adapting the display

The data representation on the positionerdisplay can be turned by 180°.If the displayed data appear upside down,proceed as follows:

Reading direction for rightattachment of pneumaticconnections

Reading direction for leftattachment of pneumaticconnections

Turn the button until Code 2 appears,and press the button to confirm Code 2,Code 2 blinks.

Turn button until the display is ad-justed to the desired direction, then con-firm reading direction by pressing the

button.

5.3 Limiting the signal pressure

If the maximum actuator force may causedamage to the valve, the signal pressuremust be limited. Select Code 3 to enableconfiguration and then access Code 16 toset the pressure limit to 1.4, 2.4 or 3.7 bar.The pressure limit required is only automati-cally determined during initialization whenthe fail-safe position is set to AIR TO OPEN .

5.4 Checking the operatingrange of the positioner

To check the mechanical attachment and theproper functioning, the valve should bemoved through the operating range of thepositioner in the manual operating modewith the manual reference variable.

Code 0Selectmanual operationDefault MAN

Code 1Position valve using therotary pushbutton, thecurrent angle of rotation isindicated

1. Turn the button until Code 0 appears,then confirm Code 0 by pressing the

button.2. Turn the button until MAN appears in

the display, i.e. manual operating mode,

EB 8384-2 EN 43

Start-up and settings

Page 44: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

confirm selected operating mode bypressing the button.

3. Turn the button until Code 1 appears,confirm Code 1 by pressing button.The hand symbol and Code 1 blink.

4. Position control valve by turning thebutton several times until pressure buildsup, and the control valve moves to its fi-nal positions so that the travel/angle ofrotation can be checked.The permissible range has been ex-ceeded when the displayed angle ishigher than 30°, and the outer right orleft bar graph element blinks.If this is the case, it is absolutely neces-sary to check lever and pin position asdescribed in section 2.

Note!If the selected pin position is smaller than in-tended for the respective travel range, thepositioner switches to the SAFE mode, thevalve moves to the fail-safe position (seesection 4.3.2 on page 42).

5. Initialize positioner as described in sec-tion 5.5.

44 EB 8384-2 EN

Start-up and settings

Simplified start-up!For most applications, the positioner with its default settings is ready for operation,provided it has been properly attached.After the fail-safe position and the volume restriction have been set, the positioner onlyneeds to be initialized by pressing the INIT key.

Caution!Prior to starting the initialization procedure, check the maximum permissible supplypressure of the control valve to prevent the valve from being damaged. On initialization,the positioner supplies the maximum available supply pressure. If necessary, restrict thesignal pressure by using a pressure reducing valve upstream of the control valve.Initialization is run in default mode MAX (section 5.5.1). During this process, thepositioner adapts itself optimally to the maximum travel/angle of rotation range.The only parameter that must be checked is the direction of action, i.e. whether the defaultsetting (Code 7 to = increasing/increasing) matches the application or whether itmust be changed.The initialization modes described in following serve to individually adapt and optimizethe positioner to the way it is attached to the valve.

Page 45: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

5.5 Initialization

During initialization the positioner adapts it-self optimally to the friction conditions andthe signal pressure demand of the controlvalve.The type and extent of self-adaptation de-pends on the set initialization mode (seesection 5.5.1).MAX is the default setting for initializationbased on the maximum nominal range.

If configuration is enabled via Code 3, Code6 can be used to change to other initializa-tion modes.

If the positioner has been initialized once al-ready, it will automatically go to the operat-ing mode used last after the electrical refer-ence variable is applied, Code 0 appearson the display.If the positioner has not yet been initialized,the fault symbol appears on the displayand the hand symbol blinks.

Note!Every time you re-initialize the positioner, itshould be reset to its basic setting includingthe default values. Refer to section 5.8 onpage 54.

Start the initialization process by press-ing the INIT key with a suitable tool.

The time required for an initialization pro-cess depends on the transit time of the actu-ator and take several minutes.Positioners with EXPERT+ diagnostic func-tions start plotting the reference graphs after

the initialization process has been com-pleted. See note at the end of this section.

Warning!During initialization, the controlvalve moves through its entiretravel/angle of rotation range.Therefore, do not start initializationwhile a process is running, but onlyduring start-up, when all shut-offvalves are closed.Note! The initialization procedurecan be canceled while running bypressing . StOP appears threeseconds long and the positioner thenmoves to the fail-safe position.

Alternating displaysInitialization running

Bar graph displayindicating the progress ofthe initialization

Initialization successful,positioner in automaticoperating mode

After a successful initialization, thepositioner runs in control operation indi-cated by the control symbol.

The control position in % predetermined bythe reference variable appears on the dis-play.

EB 8384-2 EN 45

Start-up and settings

%

Page 46: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

A malfunctioning leads to the process beingcanceled automatically. The initialization er-ror appears on the display according tohow it has been classified by the condensedstatus. See section 5.6 on page 53.

If the slide switch is set to AIR TO CLOSE,the positioner automatically switches to thedirection of action increasing/decreasing() on successful completion of initializa-tion. This results in the following assignmentbetween reference variable and valve posi-tion:

Fail-safeposition

Direction ofaction

ValveClosed at Open at

Actuator stemextends FA

AIR TO OPEN 4 mA 20 mA

Actuator stemretracts FE

AIR TO CLOSE 20 mA 4 mA

The tight-closing function is activated.Set Code 15 (final position w>) to 99 % forthree-way valves.Further settings relevant for the valve can beentered subsequently.

Note!Positioner with integrated EXPERT+ diagnos-tics automatically start to plot the referencegraphs (drive signal Y d1 and hysteresis d2)after initialization has been completed. TESTd1 and d2 appear on the display in an al-ternating sequence.An unsuccessful plotting of the referencegraphs are indicated on the display byCode 81 (see error code list).After the initialization has been successfullycompleted, the positioner still works prop-erly, even though the reference graph plot-ting has not been completed successfully.

The reference graphs are required for theextended diagnostic functions of EXPERT+.

5.5.1 Initialization modes

After enabling configuration with Code 3and accessing Code 6, you can choose oneof the initialization modes MAX, NOM,MAN or SUb to start initialization.ZP, the zero calibration is described in sec-tion 5.7 on page 54.

MAX – Initialization based on maximumrange

Initialization mode for simplified start-up forvalves with two clearly defined mechanicaltravel stops, e.g. three-way valves.

The positioner determines travel/angle ofrotation of the closing member from theCLOSED position to the opposite side andadopts this travel/angle of rotation as theoperating range from 0 to 100 %.

46 EB 8384-2 EN

Start-up and settings

Page 47: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Enable configuration:

Default OFF

Turn → Code 3, press ,

Turn → ON, press .

After enabling:

Default MAX

Turn → Code 6, press ,

Turn → MAX, press .

Press INIT key to start initialization!

The initialization procedure maytake several minutes, depending onthe actuator size, as the valve movesthrough its entire travel/angle of ro-tation range.

Positioners with EXPERT+ diagnostic func-tions automatically start plotting the refer-ence graphs after the initialization processhas been completed. See section 5.5.

Note!For MAX initialization, the positioner cannotindicate nominal travel/angle of rotation inmm/°, Code 5 remains disabled.In addition, the lower (Code 8) and the up-per (Code 9) x-range value can only be dis-played and modified in %.During MAX initialization, an increased sys-tem deviation (undefined final position of theactuator) in the upper control range may oc-cur with some control valves due to thepneumatic actuator design.

If you want the display to indicate mm/°,proceed as follows after configuration hasbeen enabled:

Turn → Code 4, press ,

turn → Select pin position entered dur-ing installation, press .

If you now switch to Code 5, the nominalrange appears in mm/°.The lower and upper x-range values forCode 8 and 9 are displayed in mm/° andcan be adapted accordingly.

NOM – Initialization based on nominalrange

Initialization mode for globe valves, espe-cially for valves with maximum ranges thatare clearly greater than the required nomi-nal range.For this initialization mode, the followingparameters must be entered: pin position(Code 4), nominal travel/angle (Code 5)and, if required, the direction of action(Code 7).

The calibrated sensor enables the effectivevalve travel to be preset very accurately.

EB 8384-2 EN 47

Start-up and settings

Page 48: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

During the initialization procedure, thepositioner checks whether the control valvecan move through the indicated nominalrange (travel or angle) without collision.In case of a positive result, the indicatednominal range is adopted with the limits oflower x-range and upper x-range values asthe operating range.

Note!The maximum possible travel must alwaysbe greater than the nominal travel entered.If this is not the case, the initialization iscanceled (error indication Code 52) be-cause the nominal travel is not achieved.

Enable configuration:

Default OFF

Turn → Code 3, press ,

turn → ON, press .

After enabling:

Default OFF

Turn → Code 4, press ,

turn → Select pin position entered dur-ing installation, press .

Default 15

Turn → Code 5, press ,

turn → Enter nominal valve travel,

press .

Default MAX

Turn → Code 6, press ,

turn → NOM, press .

Press INIT key to start initialization!

The initialization procedure maytake several minutes, depending onthe actuator size, as the valve movesthrough its entire travel/angle of ro-tation range.

Positioners with EXPERT+ diagnostic func-tions automatically start plotting the refer-ence graphs after the initialization processhas been completed. See note at the bottomof page 46.

48 EB 8384-2 EN

Start-up and settings

mm

mm

Page 49: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

MAN – Initialization based on a manuallyselected range

(with default upper x-range value by meansof manual adjustment).Initialization mode just as NOM, however,for starting up valves with unknown nominalrange.In this mode, the positioner expects the con-trol valve to be moved manually to the de-sired OPEN position prior to enabling theinitialization procedure.The upper range travel/angle of rotationvalue is adjusted using the rotarypushbutton. The positioner uses this OPENposition and the CLOSED position to calcu-late the differential travel/angle and acceptsit as the operating range with the lowerx-range value and upper x-range value be-ing the limits.

Enable configuration:

Default OFF

Turn → Code 3, press ,

turn → ON, press .

After enabling:

Turn → Code 4, press ,

turn → Select pin position entered dur-ing installation,press .

Turn → Code 6 , press ,

turn → MAN, press .

Default MAX

Turn → Code 0, press ,

turn → MAN, press .

Default MAN

Turn → Code 1, press ,Code 1 blinks.

Turn until the valve reaches its OPEN po-sition, press .

Press INIT key to start initialization!

The initialization procedure maytake several minutes, depending onthe actuator size, as the valve movesthrough its entire travel/angle of ro-tation range.

Positioners with EXPERT+ diagnostic func-tions automatically start plotting the refer-ence graphs after the initialization processhas been completed. See note at the bottomof page 46.

EB 8384-2 EN 49

Start-up and settings

Page 50: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

SUb

(substitute configuration, without initializa-tion)

This initialization mode is an emergencymode. The positioner parameters are esti-mated and not determined by an initializa-tion procedure, so that a high stationary ac-curacy cannot be expected.You should always select a different initial-ization mode if the plant allows it.

The initialization mode SUb is used to re-place a positioner while the process is in op-eration. For this purpose, the control valve isusually fixed mechanically in a certain posi-tion, or pneumatically by means of a pres-sure signal which is routed to the actuatorexternally. The blocking position ensuresthat the plant continues to operate with thisvalve position.The spare positioner should not be initial-ized. If necessary, reset the spare positionerusing Code 36.

After the old positioner has been replacedwith a new one, the following parametersmust be entered: pin position (Code 4),nominal range (Code 5), direction of action(Code 7) and closing direction (Code 34).The default travel limit of 100 % (Code 11)must be disabled with OFF.In addition, the blocking position (Code 35)must be adjusted with the button so thatit matches the position of the previouslyblocked valve.The parameters KP (Code 17), TV (Code 18)and the pressure limit (Code 16) should re-main set to their default values. If the config-uration data of the new positioner areknown, it is recommended to accept its KPand TV values.

After setting the AIR TO OPEN/CLOSEswitch for the fail-safe position, setting thevolume restriction and pressing the INIT key,the positioner calculates its configurationdata on the basis of the blocking positionand the closing direction as well as the otherentered data.The positioner switches to manual operation,subsequently the blocking position should becanceled as described on page 52.

Enable configuration:

Default OFF

Turn → Code , press ,

turn → ON, press .

After enabling:

Default OFF

Turn → Code 4, press ,

press → Select pin position entered dur-ing installation, press .

Default 15

Turn → Code 5, press ,

turn → Enter nominal travel/angle,

press .

50 EB 8384-2 EN

Start-up and settings

mm

mm

Page 51: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Default MAX

Turn → Code 6 , press ,

turn → SUb, press .

Default

Turn → Code 7, press ,

turn → Retain direction of action orselect .

Press .

Default 100.0

Turn → Code 11, press ,

turn → Deactivate travel limit,

press .

Default OFF

Turn → Code 16,

Retain default value for pressure limit,change value only if necessary.

Default 7

Turn → Code 17

Retain default. Proceed as follows only ifknown:

Press , turn → Select KP,

press .

Default 2

Turn → Code 18,

Retain default TV, change only if known.

Default CCL

Turn → Code 34 , press ,

turn → Select closing direction.

CCL = counterclockwise and CL = clockwise.

Direction of rotation which causes the valveto move to the CLOSED position (view ontothe rotary switch movement while positionercover is open).

Press .

EB 8384-2 EN 51

Start-up and settings

Page 52: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Default 0.0

Turn → Code 35, press ,

turn → Enter blocking position, e.g.5 mm (read off at travel indicator scale ofthe blocked valve or measure with a ruler).

Press .

Set switch for fail-safe position AIR TOOPEN or AIR TO CLOSE as described insection 5.1 on page 42.

Set volume restriction as described insection 5.2 on page 43.

Press INIT key!

The positioner switches to manualoperation!

The adjusted blocking posi-tion is indicated

As initialization has not been carried outcompletely, the error code 76 (no emer-gency mode) and possibly also error code57 may appear on the display.These indications do not influence thepositioner’s readiness for operation.

Canceling the blocking position

For the positioner to follow its referencevariable again, the blocking position must

be canceled and the positioner must be setto automatic operation AUtO as follows:

Press → Code 1, press ,

turn in order to move the valve slightlypast the blocking position, then cancel me-chanical blocking.

Press .

Turn → Code 0, press ,Code 0 blinks.

Turn until AUtO appears on the display.

Press to confirm the operating mode.

The positioner switches to automatic opera-tion!

The current valve position is indicated in %.

Note!If the positioner shows a tendency to oscil-late in automatic operating mode, the pa-rameters KP and TV must be slightly cor-rected. Proceed as follows:Set TV to 4 (Code 18).If the positioner still oscillates, the gain KP(Code 17) must be decreased until thepositioner shows a stable behavior.

Zero point correction

Finally, if process operations allow it, thezero point must be adjusted according tosection 5.7 on page 54.

Caution!The positioner automatically moves to zeropoint.

52 EB 8384-2 EN

Start-up and settings

mm

mm

Page 53: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

5.6 Fault/failure

All status and fault alarms are assigned aclassified status in the positioner.

To provide a better overview, the classifiedalarms are summarized in a condensedstatus for the positioner (see section 6).

The condensed status appears on the dis-play with the following symbols:

Condensed status Display

Failure

Maintenance request/maintenance demand

Function check Text

No alarm

If the positioner has not been initialized, thefault symbol appears on the display asthe positioner cannot follows its referencevariable.Additionally, a signal is issued over the faultalarm contact when certain faults occur (seeerror code list).

To access the error codes, turn the buttonpast the Code 50.Err appears on the display with the respec-tive error code.For the cause of the fault and its remedy, re-fer to the codes listed in section 12 on page66.

Display indicating anerror code

After an error code has occurred, first try toconfirm it as follows:

Enable configuration:

Turn → Code 3 , press ,

turn → ON, press .

Turn until the error code number ap-pears, then press to confirm it.

Should the error occur again, read the rem-edy instructions in the error code list.

Occurrences such as when the total valvetravel is exceeded or when the temperatureleaves the permissible temperature range af-fect the condensed state and cause a faultalarm to be displayed depending on its clas-sification.

The optional EXPERT+ diagnostics generatesadditional diagnostic alarms which are in-cluded in the condensed status with theircorresponding status classification.When a diagnostic alarm is issued byEXPERT+, this is displayed with Code 79(see error code list).

EB 8384-2 EN 53

Start-up and settings

S

Page 54: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

5.7 Zero calibration

In case of discrepancies with the closing po-sition of the valve, e.g. with soft-sealedplugs, it may become necessary torecalibrate the zero point.

Enable configuration:

Default OFF

Turn → Code 3, press ,

turn → ON, press .

After enabling:

Default MAX

Turn → Code 6, press ,

turn → ZP, press .

Press INIT key!

Zero calibration is started, the positionermoves the control valve to the CLOSED posi-tion and readjusts the internal electrical zeropoint.

The valve briefly moves from the cur-rent travel/angle of rotation positionto the closed position.

5.8 Reset to default values

This function resets all parameters to the fac-tory default values (see list of codes in sec-tion 12).

Enable configuration:

Default OFF

Turn → Code 3, press ,

turn → ON, press .

After enabling:

Default OFF

Turn → Code 36, press ,

turn → RUN, press .

All parameters are reset and can be recon-figured.

54 EB 8384-2 EN

Start-up and settings

Page 55: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

5.9 Start-up via local interface(SSP)

The positioner must be supplied with at least4 mA.The positioner can be connected directly tothe PC via the local serial interface and theserial interface adapter.

Use the TROVIS-VIEW software with 3730-2device module installed. Refer to section 13for more details.

For start-up and settings, proceed as de-scribed in section 5, 5.1 to 5.3 and thenproceed as described in section 13.

Note!Depending on the firmware installed in thepositioner, a certain minimum version of theTROVIS-VIEW device module is required forcommunication.If you have already installed the software,you can download updates atwww.samson.de (Support & Downloads -TROVIS VIEW Updates).

6 Status and diagnostic alarms

The Type 3730-2 Positioner contains an in-tegrated diagnostic approach to generateclassified status and diagnostic alarms.

There are two different on-board diagnosticsavailable: the standard integrated diagnos-tics (EXPERT) and the optional extendedEXPERT+ diagnostics.

6.1 Standard EXPERT diagnostics

The standard EXPERT diagnostics providesinformation about positioner states such asoperating hours counter, process monitor-ing, number of zero calibrations andinitializations, total valve travel, tempera-ture, initialization diagnostics, zero/controlloop errors, logging of the last 30 alarms,etc.

In addition, the standard EXPERT diagnosticsgenerates diagnostic and status alarmswhich allow faults to be pinpointed quicklywhen a fault occurs.

Alarms are classified in the following maingroups:

Status

Operation

Hardware

Initialization

Data memory

Temperature

EB 8384-2 EN 55

Status and diagnostic alarms

Page 56: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

6.2 Extended EXPERT+ diagnos-tics

In addition to the standard EXPERT diagnos-tic features, the optional EXPERT+ extendeddiagnostics provides the following onlineand offline test functions which enablesignificant statements on the condition of theentire control valve.

Online test functions (monitoring functions)

Data logger

Histogram

Cycle counter

Valve end position trend

Y = f (X) diagram (drive signal)

Hysteresis test

Offline test functions (manual functions)

Y = f (X) diagram over the entire valvetravel range

Hysteresis test over the entire valve travelrange

Static characteristic

Step response test

The diagnostic tests are completely inte-grated in the positioner. Further statusalarms are generated from the extensive in-formation gained in the diagnostic tests ofEXPERT+ which provide the user with infor-mation covering the whole control valve.The required reference curves are automati-cally plotted after initialization and saved inthe positioner if EXPERT+ is activated.The optional diagnostic functions providedby EXPERT+ can be selected when ordering

the positioner. Additionally, it is possible toactivate EXPERT+ at a later point in time inan existing positioner.For this purpose, an activation code can beordered, specifying the serial number of thepositioner.

6.3 Classification of the statusalarms and condensed status

The alarms are assigned a classificationstatus in the positioner. The following statesare differentiated between:

FailureThe positioner cannot perform its controltask due to a functional fault in the device orin one of its peripherals or an initializationhas not yet been successfully completed.

Maintenance demandThe positioner still performs its control task(with restrictions). A maintenance demandor above average wear has been deter-mined. The wear tolerance will soon be ex-hausted or is reducing at a faster rate thanexpected. Maintenance is necessary in themedium term.

Maintenance requirementThe positioner still performs its control task(with restrictions). A maintenance demandor above average wear has been deter-mined. The wear tolerance will soon be ex-hausted or is reducing at a faster rate thanexpected. Maintenance is necessary in theshort term.

Function checkTest or calibration procedures are beingperformed. The positioner is temporarily un-able to perform its control task until thisprocedure is completed.

56 EB 8384-2 EN

Status and diagnostic alarms

Page 57: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Classification process in the positionerAn alarm is assigned to one of followingclassified states in the table:

Condensed status

To provide a better overview, the state of thepositioner is summarized in a condensedstatus which is made up from a summary ofall classified positioner alarms.

If an event is classified as “No alarm”, thisevent does not have any affect on the con-densed status of the positioner.

The condensed status is displayed in the en-gineering tool as well as on the positionerdisplay as in the following table:

Status modification

The classification of the status alarms can bechanged as required.They can be modified using TROVIS-VIEWsoftware over the local SSP interface.

Note!All additional alarms generated by EXPERT+

have the status “No alarm” by default.

EB 8384-2 EN 57

Status and diagnostic alarms

Status alarm Engineering tool

Alarm inactive

Alarm activeClassified as “No alarm”

Alarm activeClassified as “Maintenance requirement”/

”Maintenance demand”

Alarm activeClassified as “Function check”

Alarm activeClassified as “Failure”

Page 58: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Logging and displaying diagnosticfunctions/alarms

The last 30 alarms are logged in thepositioner. However, it is important to notethat the same alarm is only logged oncewhen it first occurs.The alarms and the condensed states ap-pear on the display as described in the codelist (section 12).In addition, the diagnostic parameters areissued over the communication interface ofthe positioner.

The diagnostic functions can easily bedisplayed and configured using theTROVIS-VIEW software connected over thelocal interface (SSP).

58 EB 8384-2 EN

Status and diagnostic alarms

Status alarm Engineering tool Positioner display

“Failure”

“Maintenance requirement”"Maintenance demand”

“Function check”Text

“No alarm”

Page 59: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 59

Page 60: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Setting the switching point:

Important!During adjustment or testing, the switchingpoint must always be approached frommid-position (50 %).

To ensure safe switching under any ambientconditions, the switching point should beadjusted to a value of approx. 5 % beforethe mechanical stop (OPEN – CLOSED).

For CLOSED position:

1. Initialize positioner.2. Use the MAN function to move the

positioner to 5 % (see LC display).3. Adjust the tag using the yellow adjust-

ment screw (2) until the tag enters orleaves the field and the switching ampli-fier responds. You can measure theswitching voltage as an indicator.

Contact function:Tag leaving the field > contact is made.Tag entering the field > contact is opened.

For OPEN position:

1. Initialize positioner.2. Use the MAN function to move the

positioner to 95 % (see LC display).3. Adjust the tag (1) using the yellow ad-

justment screw (2) until the tag enters orleaves the field of the proximity switch(3).You can measure the switching voltageas an indicator.

Contact function:

Tag leaving the field > Contact is made.Tag entering the field > Contact is opened.

60 EB 8384-2 EN

Adjusting the limit switch

Page 61: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

8 Quick start-up guide

8.1 Mounting

Direct attachment

to SAMSON Type 3277 Actuator

Travel mm Actuator cm2 Pin position

7.5 120 25

15 120/240/350 35

15/30 700 50

Note!Standard delivery includes lever M readyassembled with the follower pin on 35 mmpin position for 15 mm travel!

To mount the positioner, lift the lever so thatthe follower pin rests on the follower clampof the actuator stem.

NAMUR attachment

Determine the maximum travel range ofthe control valve from the closed positionto as far it will go in the other direction.

Select the lever to match the maximumtravel range as well the next largest pinposition and screw onto the shaft of thepositioner.

Lever option/pin distance:see pin position table (Code 4) or coverplate on the positioner.

Screw the NAMUR bracket onto thevalve yoke so that it is aligned centrallyto the slot of the follower plate when thetravel position is at 50 %.

Secure the positioner to the NAMURbracket, making sure that the followerpin is in the slot of the follower plate.Make sure the lever can still move.

Attachment to rotary actuators

Lever M pin position 90° Put the valve into the closed position, de-

termine the opening direction. Place the follower plate on the slotted ac-

tuator shaft and fasten it to the couplingwheel. Attach the top pair of bracketsand the bottom pair of brackets to theactuator.

Place the positioner on the brackets andscrew tight, making sure that the leverwith its follower pin engages the slot ofthe coupling wheel, while taking into ac-count the opening direction.It is important to make sure that the le-ver's mid position corresponds to the midtravel of the valve (lever's mid position =the lever is parallel to the long side of thepositioner casing).

Pneumatic connections

Screw the threaded connections only intothe attached connection block, connect-ing plate or pressure gauge block fromthe accessories.

EB 8384-2 EN 61

Quick start-up guide

Page 62: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

8.2 Start-up

Connect pneumatic supply air (1.4 to6 bar).

Apply an electrical reference variable (4 to20 mA).

Set the fail-safe position

Position the slide switch according tofail-safe position of the control valve:AIR TO OPEN or AIR TO CLOSE.

Adapt the volume restriction Q to the actu-ator size

Only set the restriction for actuators< 240 cm2 to:MIN SIDE for connection at the side orMIN BACK for connection at the back.

Note!After each change of the volume restrictionsetting, the positioner must be re-initialized.

Changing the reading direction of thedisplay

(if necessary)

Turn → Code 2 , press ,

turn → Display ok, press .

Operation

Selecting the parameters or values

Each parameter has a code number whichis shown in the display. Use the button toselect.Turn the button to select parameters or val-ues and then push to confirm.

Select and confirm ESC to prevent an en-tered value from being accepted.

Enabling parameters

Parameters that have a code marked withan asterisk (*) can only be changed whenthey are enabled beforehand using Code 3.

The configuration mode is shown in the dis-play with the symbol.

See list of codes from page 66 onwards orcover plate of the positioner for a descrip-tion of the menu codes.

62 EB 8384-2 EN

Quick start-up guide

Page 63: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

8.3 Initialization

Important!Perform a reset (Code 36) prior to each ini-tialization

Turn → Code 3, ↵

turn → ON, ↵

turn → Code 36, ↵

select RUN, ↵

Caution!During initialization, the valve runs throughits whole range of travel/angle of rotation.

8.3.1 Simplest method (MAX)

Mount and start up the positioner andpress the INIT key!READY!The positioner adapts itself automatically tothe maximum travel/angle of rotationrange of the control valve.

8.3.2 Precise method (NOM)

Positioner adapts itself precisely to the nomi-nal travel/rotational angle of the controlvalve!

Mount and start up the positioner, then pro-ceed as follows:

Turn → Code 3, ↵

turn → ON, ↵

turn → Code 4, ↵Select pin position, ↵

turn → Code 5, ↵

Enter nominal travel/range, ↵

turn → Code 6, ↵

select NOM, ↵

Press INIT key!

8.3.3 Manual method (MAN)

Initialization mode same as NOM, but forstart-up of control valves with unknownnominal ranges. The final position oftravel/angle of rotation (valve open) is en-tered manually.

Mount and start up the positioner, then pro-ceed as follows:

Turn → Code 0, ↵,

turn → select MAN, ↵

turn → Code 1, ↵,

turn → valve open position, ↵

turn → Code 3, ↵,

turn → ON, ↵

turn → Code 6, ↵, select MAN, ↵

Press INIT key!

Note!After imposing the electrical reference vari-able, the positioner is in the last used oper-ating mode. Code 0 appears in the display.If the positioner has not yet been initialized,the fault symbol appears on the displayand the symbol blinks.

EB 8384-2 EN 63

Quick start-up guide

Page 64: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

9 Retrofitting an inductive limitswitch

Required retrofit kit:Limit switch Order no. 1400-7460

1. Take off the rotary pushbutton (3) andcap (1), unthread the five fixing screws(2) and lift off the plastic cover (9).

2. Use a knife to cut an opening at themarked location (4).

3. Push the connector (11) with cablethrough the opening and secure theproximity switch (7) on the cover with adot of glue.

4. Remove the jumper at the socket ST1 ofthe top board and insert the cable con-nector (11).

5. Guide the cable in such a manner thatthe plastic cover can be placed backonto the positioner. Insert the fixingscrews (2) and screw tight. Attach theclamping plate (8) onto the proximityswitch.

6. Attach the rotary switch (5). Make surethe flattened side of the positioner shaftis turned so that the rotary switch (5) canbe attached with the metal tag next tothe proximity switch.

7. Important!On start-up of the positioner, set the op-tion "inductive alarm" under Code 38from NO to YES.

64 EB 8384-2 EN

Retrofitting an inductive limit switch

1 Cap2 Screws3 Rotary pushbutton4 Marking5 Rotary switch

6 Metal tag7 Proximity switch8 Clamping plate9 Plastic cover11 Connector Fig. 18 · Retrofitting an inductive limit switch

Socket ST1 (11)

9 7

1

2

4

3

5

8

7

6

Page 65: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

10 Maintenance

The positioner does not require any mainte-nance.

There are filters with a 100 µm mesh size inthe pneumatic connections for supply andoutput which can be removed and cleaned,if required.

The maintenance instructions of any up-stream supply air pressure reducing stationsmust be observed.

11 Servicing explosion-protecteddevices

If a part of the positioner on which the ex-plosion protection is based needs to be ser-viced, the positioner must not be put backinto operation until an expert has inspectedthe device according to explosion protectionrequirements, has issued a certificate statingthis or given the device a mark of confor-mity.

Inspection by an expert is not required if themanufacturer performs a routine check onthe device prior to putting it back into oper-ation. The passing of the routine check mustbe documented by attaching a mark of con-formity to the device.

Explosion-protected components may onlybe replaced by original, checked compo-nents from the manufacturer.

Devices that have already been used outsideof hazardous areas and are intended foruse in hazardous areas in future must com-ply with the safety demands placed on re-paired devices. Prior to operation, they mustbe tested according to the specificationsstipulated for "Repairing explosion-pro-tected devices".

EB 8384-2 EN 65

Maintenance

Page 66: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

12 Code list

Codeno.

Parameter – Display, values[default setting] Description

Important! Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

0 Operating mode[MAN]AUtOSAFEESC

AUtO = Automatic mode MAN = Manual modeSAFE = Fail-safe position ESC = EscapeSwitchover from automatic to manual mode is smooth.In fail-safe mode, the symbol S appears on the display.In MAN and AUtO mode, the system deviation is represented bythe bar graph elements.When the positioner is initialized, the numerical display indicatesthe valve position or the angle of rotation in %, otherwise the po-sition of the sensor in relation to the central axis is displayed indegrees °.

1 Manual w0 to 100 [0] %of the nominal range

Adjust the manual set point with the rotary pushbutton, thecurrent travel/angle is displayed in % when the positioner is ini-tialized, otherwise the sensor position in relation to the centralaxis is indicated in degrees °.

2 Reading directionNormal or upside downESC

The reading direction of the display is turned by 180°.

3 Enable configuration[OFF] ON ESC

Activates the option to modify data (automatically deactivatedwhen the rotary pushbutton has not been operated for 120 s.)

4* Pin position[OFF]17, 25, 35, 50 mm70, 100, 200 mm,90° with rotary actuatorsESC

Note!If you select a pin position inCode 4 that is too small, thepositioner switches to SAFEmode for reasons of safety

For initialization using NOM or SUb, the follower pin must be in-serted into the correct pin position according to the valvetravel/angle of rotation.

Pin position Standard Adjustment rangeCode 4 Code 5 Code 517 7.5 3.6 to 17.725 7.5 5.0 to 25.035 15.0 7.0 to 35.450 30.0 10.0 to 50.070 40.0 14.0 to 70.7100 60.0 20.0 to 100.0200 120.0 40.0 to 200.090° 90.0 24.0 to 110.0

66 EB 8384-2 EN

Code list

Page 67: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

5* Nominal range[15.0] mm or angle °ESC

For initialization using NOM or SUb, the nominal travel/angle ofrotation of the valve must be entered.The permissible adjustment range depends on the pin positionaccording to the table for Code 4.After initialization has been successfully completed, the maximumnominal travel/angle reached on initialization is displayed.

6* Init mode[MAX]NOMMANSUbZPESC

Select the initialization modeMAX: Maximum range of the control valve, the travel/angle of

the closure member from the CLOSED position to theopposite stop in the actuator.

NOM: Nominal range of the control valve, the travel/angle ofthe closure member measured from the CLOSED positionto the indicated OPEN position.

MAN: Manual adjustment: upper x-range valueSUb: No self-adjustment (emergency mode)ZP: Zero calibration

7* w/x[]

ESC

Direction of action of the reference variable w in relation to thetravel/angle of rotation x (increasing/increasing or in-creasing/decreasing)Automatic adaptation:AIR TO OPEN:On completion of initialization, the direction of action remains in-creasing/increasing (), a globe valve opens as the mA signalincreases.AIR TO CLOSE:On completion of initialization, the direction of action changes toincreasing/decreasing ( ), a globe valve closes as the mAsignal increases.

8* Lower x-range value0.0 to 80.0 [0.0] % of thenominal range,Specified in mm or angle ° providedCode 4 is set

ESC

Lower range value for the travel/angle of rotation in the nominalor operating range.The operating range is the actual travel/angle of the controlvalve and is limited by the lower x-range value (Code 8) and theupper x-range value (Code 9).Usually, the operating range and the nominal range are iden-tical. The nominal range can be limited to the operating range bythe lower and upper x-range values.Value is displayed or must be entered.The characteristic is adapted. See also the example in Code 9!

EB 8384-2 EN 67

Code list

Page 68: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

9* Upper x-range value20.0 to 100.0 [100.0] %nominal range,Specified in mm or angle ° provided

Code 4 is set

ESC

Upper range travel/angle of rotation in the nominal or operatingrange. Value is displayed or must be entered.The characteristic is adapted.Example: The operating range is modified, for example, to limitthe range of a control valve which has been sized too large. Forthis function, the entire resolution range of the reference variableis converted to the new limits. 0 % on the display corresponds tothe set lower limit and 100 % to the set upper limit.

10* Lower x-limit[OFF]0.0 to 49.9 % of theoperating rangeESC

Limitation of the travel/angle of rotation downwards to the en-tered value, the characteristic is not adapted.

The characteristic is not adapted to the reduced range. See alsoexample in Code 11.

11* Upper x-limit[100 %]50.0 to 120.0 [100] % ofthe operating rangeor OFFESC

Limitation of the travel/angle of rotation upwards to the enteredvalue, the characteristic is not adapted.Example: In some applications, it makes sense to limit the valvetravel, e.g. if a certain minimum medium flow is required or amaximum flow must not be reached.The lower limit must be adjusted with Code 10, and the upperlimit with Code 11. If a tight-closing function has been set up, ithas priority over the travel limitation!When set to OFF, the valve can be opened past the nominaltravel with a reference variable outside of the 4 to 20 mA range.

12* w-start0.0 to 75.0 [0.0] % of thereference variable rangeESC

Lower range value of the applicable reference variable rangemust be smaller than the final value w-end, 0 % = 4 mAThe reference variable range is the difference between w-endand w-start, and must be ∆w ≥ 25 % = 4 mA.For an adjusted reference variable range of 0 to 100 % = 4 to20 mA, the control valve must move through its entire operatingrange from 0 to 100 % travel/angle of rotation.In split-range operation, the valves operate with smaller refer-ence variables. The control signal of the control unit to controltwo valves is divided such, for instance, that the valves movethrough their full travel/angle of rotation at only half the inputsignal (first valve set to 0 to 50 % = 4 to 12 mA and second valveset to 50 to 100 % =12 to 20 mA reference variable).

13* w-end25.0 to 100.0 [100.0] % ofthe reference variable rangeESC

Upper range value of the applicable reference variable range,must be greater than w-start.100 % = 20 mA

68 EB 8384-2 EN

Code list

Page 69: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

14* Final position w <0.0 to [1.0] %of the span adjusted viaCode 12/13OFFESC

If w approaches up to 1 % towards the final value that causes thevalve to close, the actuator is immediately completely vented(with AIR TO OPEN) or filled with air (with AIR TO CLOSE).This action always lead to maximum tight-closing of the valve.

Codes 14/15 have priority over Codes 8/9/10/11.

15* Final position w >[OFF]50.0 to 100.0 %of the span adjusted viaCode 12/13ESC

If w approaches up to 99 % towards the final value that causesthe valve to open, the actuator is immediately completely filledwith air (with AIR TO OPEN) or vented (with AIR TO CLOSE).This action always lead to the valve being completely opened.Codes 14/15 have priority over Codes 8/9/10/11.Example: Set the final position w > to 99 % for three-way valves.

16* Pressure limit[OFF]1.4 2.4 3.7 barESC

The signal pressure can adopt the value of the applied supplypressure at the maximum [OFF] or it can be limited in stages of1.4, 2.4 or 3.7 bar. This pressure limitation is already effectiveduring the initialization.Note: After changing a pressure limit already set, the actuatormust be vented once (e.g. by selecting the fail-safe position overCode 0).

17* KP step0 to 17 [7]ESC

Displaying or changing KP

Note on changing the KP and TV steps:During the initialization of the positioner, the KP and TV values areoptimized.Should the positioner show a tendency for impermissibly highpost-pulse oscillation due to additional interference, the KP and TVsteps can be adapted after the initialization.For this, either the TV step can be increased in increments untilthe desired response behavior is reached or, when the maximumvalue of 4 is reached, the KP step can be decreased in incre-ments.

CAUTION! Changing the KP step influences the system deviation.This effect decreases as the KP step increases.

18* TV step[2]1 2 3 4 OFFESC

Displaying or changing TV,See note under KP stepA change of the TV step has no effect on the system deviation.

EB 8384-2 EN 69

Code list

Page 70: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

19* Tolerance band0.1 to 10.0 [5] % of theoperating rangeESC

Used for error monitoringDetermination of the tolerance band in relation to the operatingrange.Associated lag time [30] s is a reset criterion.If, during initialization, a transit time is determined which is6 times > 30 s, the 6fold transit time is accepted as lag time.

20* Characteristic0 to 9 [0]ESC

Select the characteristic:0: Linear 5: Rotary plug valve linear1: Equal percentage 6: Rotary plug valve eq. perc.2: Reverse equal percentage 7: Segmented ball valve linear3: Butterfly valve linear 8: Segmented ball valve eq. p.4: Butterfly valve eq. percentage 9: User-defined ** Definition over SAMSON TROVIS-VIEW software

21* w-ramp Open0 to 240 s [0]ESC

The time required to pass through the operating range when thevalve opens.Limitation of the transit time (Code 21 and 22):For some applications it is recommendable to limit the transit timeof the actuator to prevent it from engaging too fast in the runningprocess.

22* w-ramp Closed0 to 240 s [0]ESC

The time required to pass through the operating range when thevalve closes.

23* Total valve travel0 to 9999 [0]subsequently 10E3-99E7

RESESC

Totaled double valve travel.

Can be reset to 0 via RES.

24* LV total valve travel1000 to 9999 [100 000]subsequently 10E3-99E7ESC

Limit value of total valve travel. If the limit value is exceeded, thefault symbol and the wrench symbol appear.Exponential display for 10 000 travel cycles onwards.

70 EB 8384-2 EN

Code list

Page 71: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

25* Alarm mode0 to 3 [2]ESC

Switching mode of software limit switches alarm A1 and A2 inresponding state (when positioner initialized).

1) Explosion-protected version according to EN 60947-5-60: A1 ≥ 2.1 mA A2 ≤ 1.2 mA1: A1 ≤ 1.2 mA A2 ≤ 1.2 mA2: A1 ≥ 2.1 mA A2 ≥ 2.1 mA3: A1 ≤ 1.2 mA A2 ≥ 2.1 mA

2) Version without explosion protection0: A1 R = 348 Ω A2 Non-conducting1: A1 Non-conducting A2 Non-conducting2: A1 R = 348 Ω A2 R = 348 Ω3: A1 Non-conducting A2 R = 348 ΩWhen a positioner has not been initialized, the software limitswitches always register the signal as in the state of no response.If there is no mA signal at the terminals 11/12, the software limitswitches both switch to ≤ 1.2 mA signal (Ex) or non-conducting(without explosion protection).

26* Limit value A1OFF0.0 to 100.0 [2.0] % of theoperating rangeESC

Displaying or changing the software limit value A1 in relation tothe operating range.Setting has no effect when an inductive limit switch has been in-stalled.

27* Limit value A2OFF0.0 to 100.0 [98.0] % of theoperating rangeESC

Displaying or changing the software limit value A2 in relation tothe operating range.

28* Alarm TestReading direction:Standard Turned[OFF] [OFF]RUN 1 1 RUNRUN 2 2 RUNRUN 3 3 RUNESC ESC

Testing the software limit switches alarm A1 and A2 in additionto the fault alarm contact A3.If the test is activated, the respective limit switches five times.RUN1/1 RUN: Software limit switch A1RUN2/2 RUN: Software limit switch A2RUN3/3 RUN: Fault alarm contact A3

EB 8384-2 EN 71

Code list

Page 72: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

29* Position transmitter x/ix 3)

[]

ESC

Operating direction of the position transmitter; indicates how thetravel/angle position is assigned to the output signal i, based onthe closed position.The operating range (see Code 8) of the valve is represented bythe 4 to 20 mA signal. Values exceeding or falling below thelimits 2.4 to 21.6 mA can be represented.When a positioner has not been initialized (reference variableless than 3.6 mA), the power consumption of the feedback signalis effective (current approx. 1.8 mA).When YES is set in Code 32 , the position transmitter issues thevalue as per Code 30 during initialization or zero calibration.When NO is set in Code 32, 4 mA is issued during a runningself-adaptation.

30* Fault alarm ix 3)

[OFF] HI LOESC

Used to select whether faults causing the fault alarm contact toswitch should also be signaled through the position transmitteroutput and how they should be signaledHI ix > 21.6 mA or LO ix < 2.4 mA

31* Position transmitter test 3)

–10.0 to 110.0 [x before thefunction is triggered] % ofthe operating rangeESC

Testing the position transmitter. Values can be entered in relationto the operating range.The current actual value is used in initialized positioners locallyas the start value (bumpless changeover to the test mode). Ontesting over software, the entered simulation value is issued asthe position feedback signal for 30 seconds.

3)Analog position transmitter: Code 29/30/31 can only be selected if the position transmitter (optional) is installed.

32* Display special functionsNO [YES]ESC

Fault alarm via display and fault alarm contact for special func-tions, e.g. zero calibration, initialization and position transmittertest (Code 31).

33* Display total valve travelNO [YES]ESC

Fault alarm via display and fault alarm contact when the limitvalue for the total valve travel is exceeded.

34* Closing directionCL [CCL]ESC

CL: Clockwise, CCL: CounterclockwiseTurning direction in which the valve is moved to the Closed posi-tion (view onto the rotary switch motion when the positionercover is open).Needs only be entered in initialization mode SUb (Code 6).

35* Blocking position[0] mm/° /%ESC

Entering the blocking position.Distance up to the Closed position.Only necessary in initialization mode SUb.

72 EB 8384-2 EN

Code list

Page 73: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

36* Reset[OFF] RUNESC

Resets all parameters to default (factory setting).Note: After setting RUN, the positioner must be re-initialized.

37 Position transmitterYes No

Display only,indicates whether the position transmitter option is installed.

38* Inductive alarm[NO] YESESC

Indicates whether the inductive limit switch option is installed ornot.

39 System deviation e info–99.9 to 999.9 % ,

Display only,indicates the deviation from the set point position.

40 Transit time Open info0 to 240 s [0]

Display only,minimum opening time is determined during initialization

41 Transit time Closed info0 to 240 s [0]

Display only,minimum closing time is determined during initialization

42 Auto-w info0.0 to 100.0 % of the span4 to 20 mA

Display only,indicates the supplied automatic reference variable corre-sponding 4 to 20 mA.

43 Firmware infoXxxx

Display only,indicates the current firmware version of the positioner.

44 y info[0] OP0 to 100 %MAX

Display only, blocked prior to initialization.After initialization: indicates the actuator pressure in %.0 to 100 % corresponds to the pressure range which adjusts thetravel/angle range from 0 to 100 %.If the actuator pressure is 0 bar, e.g. due to tight-closing onbottom or fail-safe action, 0 P appears on the display.If the actuator pressure is higher than the pressure required for X= 100 %, e.g. due to tight-closing on top, MAX appears on thedisplay.Value is determined during initialization.

45 Solenoid valve infoYesNo

Display only,indicates whether a solenoid valve is installed.

EB 8384-2 EN 73

Code list

Page 74: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

48 Diagnostics

d Diagnostic parameters

d0 Current temperature–55 to 125

Operating temperature [°C] inside the positioner

d1 Minimum temperature[20]

The lowest temperature below 20 °C that has ever occurred.

d2 Maximum temperature[20]

The highest temperature above 20 °C that has ever occurred.

d3 Number of zerocalibrations

The number of zero calibrations since the last initialization.

d4 Number of initializations The number of initializations that have been performed.

d5 Zero point limit[5 %]0.0 to 100.0 %

Limit for the zero point monitoring.

d6 Condensed status Condensed status, made up from the individual states.OK: Okay, C: Maintenance requirement, CR: Maintenance de-mand, B: Failure, I: Function check.

d7 Start reference run[OFF]ONESC 1

Triggering of a reference run for the functions: Drive signal Ystationary and drive signal Y hysteresis.The reference run can only be activated in manual operation asthe valve moves through its entire travel range.If EXPERT+ is activated at later point in time, the reference graphsmust be plotted in order to activate the diagnostic functions.

d8 EXPERT+ activation Enter the activation code for EXPERT+.After the activation procedure has been successfully completed,YES appears under d8.

74 EB 8384-2 EN

Code list

Page 75: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Error codes – Remedy Condensed status alarm active, when prompted, Err appears.

Initialization error(indicated on the display by the condensed status with the corresponding classification)

50 x < range The value supplied by the measuring signal is either too high ortoo low, the measuring sensor is close to its mechanical limit.• Pin positioned incorrectly.• Bracket slipped in case of NAMUR attachment or positioner is

not central.• Follower plate incorrectly attached.

Remedy Check attachment and pin position, set operating mode fromSAFE to MAN and re-initialize the positioner.

51 ∆x > range The measuring span of the sensor is too low.• Pin positioned incorrectly.• Wrong lever.A rotational angle smaller than 11° at the positioner shaft createsjust an alarm. An angle below 6° leads to the initialization beingcanceled.

Remedy Check attachment and re-initialize the positioner.

52 Attachment • Positioner attachment incorrect.• Nominal travel/angle (Code 5) could not be achieved on

initialization under NOM or SUb (no tolerance downwardspermissible)

• Mechanical or pneumatic error, e.g. wrong lever selected orsupply pressure too low to move to the required position orpneumatic fault

Remedy Check attachment and supply pressure. Re-initialize thepositioner.Under certain circumstances, it may be possible to check themaximum travel/angle by entering the actual pin position andthen performing an initialization under MAX.After initialization has been completed, the Code 5 indicates themaximum achieved travel or angle.

53 Init time > The initialization routine lasts too long. The positioner returns toits previous operating mode.• No pressure on the supply line or there is a leak.• Supply air failure during initialization.

Remedy Check attachment and supply pressure.Re-initialize the positioner.

EB 8384-2 EN 75

Code list

Page 76: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

54 Init – Solenoid valve 1) A solenoid valve is installed (Code 45 = YES) and wasnot or not properly connected so that an actuator pressurecould not be built up. The message appears when youattempt to initialize the positioner.

2) If you attempt to initialize the device from the fail-safeposition (SAFE).

Remedy Re. 1) Check connection and supply voltage of the solenoidvalve.

Re. 2) Set the MAN operating mode over Code 0. Then initializethe positioner.

55 Transit time < The actuator transit times determined during the initialization areso short that the positioner cannot adapt itself optimally.

Remedy Check the volume restriction setting as described in section 5.2,re-initialize the positioner.

56 Pin pos. Initialization was canceled because you are required to enter thepin position for the selected initialization modes NOM and SUb.

Remedy Enter pin position over Code 4 and nominal travel/angle overCode 5. Re-initialize the positioner.

Operational error (indicated on the display by the condensed status with the correspondingclassification)

57 Control loop

Additional message at the faultalarm contact!

Control loop fault, the control valve does not react within the tol-erable times of the controlled variable (tolerance band alarmCode 19).• Actuator mechanically blocked.• Attachment of the positioner subsequently postponed.• Supply pressure not sufficient.

Remedy Check attachment.

58 Zero point Zero point incorrect. Error may arise when the mounting posi-tion/linkage of the positioner moves or when the valve seat trimis worn, especially with soft-sealed plugs.

Remedy Check valve and mounting of the positioner. If OK, perform azero calibration over Code 6 (see section 5.7 on page 54).

59 Autocorrection Should an error occur in the data range of the positioner, theself-monitoring function recognizes it and automatically correctsit.

Remedy Automatic

76 EB 8384-2 EN

Page 77: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

60 Fatal error

Additional message at the faultalarm contact!

An error was detected in the data relevant for safety,autocorrection is not possible. This may be due to EMC distur-bances.The control valve is moved to the fail-safe position.

Remedy Reset over Code 36.Re-initialize the positioner.

Hardware error (indicated on the display by the condensed status with the corresponding classification)

62 x signal

Additional message at the faultalarm contact!

Determination of the measured value for the actuator has failed.Conductive plastic element is defective.The positioner continues to run in emergency mode, but shouldbe replaced as soon as possible.The emergency mode on the display is indicated by a blinkingcontrol symbol and 4 dashes instead of the position indication.Note on the control:If the measuring system has failed, the positioner is still in a reli-able state. The positioner switches to emergency mode where theposition cannot be accurately controlled anymore. However, thepositioner continues operation according to its reference variablesignal so that the process remains in a safe state.

Remedy Return the positioner to SAMSON AG for repair.

63 w too small The reference variable is much smaller than 4 mA (0 %); occurs ifthe power source that drives the positioner does not comply withthe standard.This state is indicated on the positioner display by a blinkingLOW.

Remedy Check reference variable.If necessary, limit the current source downwards so that no valuesbelow 4 mA can be issued.

64 i/p converter (y) The circuit of the i/p converter has been interrupted.

Remedy Cannot be remedied.Return the positioner to SAMSON AG for repair.

EB 8384-2 EN 77

Code list

Page 78: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Error appendix

65 Hardware

Additional message at the faultalarm contact!

A hardware error has occurred, the positioner moves to thefail-safe position SAFE.

Remedy Confirm error and return to the automatic operating mode, orperform a reset and re-initialize the device. If this is not suc-cessful, return device to SAMSON AG for repair.

66 Data memoryAdditional message at the faultalarm contact!

The writing of data to the data memory does not work anymore,e.g. when the written data deviate from the read data.Valve moves to the fail-safe position.

Remedy Return the positioner to SAMSON AG for repair.

67 Test calculationAdditional message at the faultalarm contact!

The hardware positioner is monitored by means of a test calcula-tion.

Remedy Confirm error. If this is not possible, return the positioner toSAMSON AG for repair.

Data error

68 Control parameterAdditional message at the faultalarm contact!

Control parameter error, e.g. due to EMC disturbances.

Remedy Confirm error, perform reset and re-initialize the positioner.

69 Poti parameterAdditional message at the faultalarm contact!

Parameter error of the digital potentiometer.

Remedy Confirm error, perform reset and re-initialize the positioner.

70 CalibrationAdditional message at the faultalarm contact!

Error in the production calibration data, e.g. due to EMC distur-bances. Subsequently, the device runs on default values

Remedy Return the positioner to SAMSON AG for repair.

71 General parameters Parameter errors that are not critical for the control.

Remedy Confirm error.Check and, if necessary, reset required parameters.

72 Start-up parameters Start-up parameter errors

Remedy Confirm error, perform reset and re-initialize the positioner.

78 EB 8384-2 EN

Code list

Page 79: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

73 Internal device error 1 Internal device error

Remedy Return the positioner to SAMSON AG for repair.

75 Parameter info Error in the parameter info which is not critical for the control.

Remedy Confirm error.Check and, if necessary, reset required parameters.

76 No emergency mode The travel measuring system of the positioner has a self-moni-toring function (see Code 62).A controlled emergency mode is not available on certain actua-tors, such as double-acting actuators. For this reason, thepositioner moves into the fail-safe position when a measuringerror occurs. During the initialization, the positioner checkswhether the actuator has such a function or not.

Remedy Merely information, confirm, if necessary.No further action necessary.

77 Program loading errorAdditional message at the faultalarm contact!

When the device starts operation for the first time after the inputsignal has been applied, it carries out a self-test (tEStinG runsacross the display).If the device loads a program that does not correspond to that ofthe positioner, the valve is moved into the fail-safe position. It isnot possible to make the valve leave this fail-safe position againby operating the positioner.

Remedy Interrupt current supply and restart positioner. Otherwise, returnthe positioner to SAMSON AG for repair.

78 Options parameter Errors in options parameters, e.g. due to EMC disturbances.

Remedy Return the positioner to SAMSON AG for repair.

79 Diagnostic alarms Alarms are generated in the EXPERT+ extended diagnostics ifEXPERT+ has been successfully activated in Code 48.

80 Diagnostic parameters Error which is not critical for control.

Remedy Confirm error.Check and, if necessary, start new reference run.

81 Reference graphs Error on plotting the reference graphs of drive signal Y stationaryor drive signal Y hysteresis.• Reference run was interrupted• Reference line Y stationary or Y hysteresis was not adopted.

EB 8384-2 EN 79

Code list

Page 80: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

13 Setting with TROVIS-VIEW software – Parameter list

13.1 General

A CD-ROM containing the program for installing the TROVIS-VIEW Configuration and Op-erator Interface is provided by SAMSON.

Insert the installation CD-ROM to start the installation program. Once inserted, the CD-ROMusually starts the installation program automatically depending on the configuration of theoperating system.If the program does not start automatically, double-click setup.exe in the root directory of theCD-ROM in order to install TROVIS-VIEW.Follow the on-screen prompts and instructions of the installation program.

The system requirements are specified in the readme.txt file in the root directory of theCD-ROM.

The TROVIS-VIEW Operator Interface can be used for different SAMSON devices. Note thatthe installation program also offers you the option of installing a demo module. To use thesoftware without restrictions, the software needs to be activated as described below:

After installation, a dialog box will appear, prompting you to enter the CD key, which youwill find on the cover of the original CD-ROM. Once you have entered the correct CD keyand initiated the activation process, a request code will be automatically generated. The Ac-tivation dialog box will come up displaying the generated request code and an Internet linkto SAMSON’s activation server where a unique activation code will then be generated anddisplayed. Enter this activation code into TROVIS-VIEW’s Activation dialog box. The soft-ware is now ready for use without any restrictions in the purchased scope.

To enable communication with the PC, connect the serial interface to the serial interface(5-pole female socket) of the positioner using a SAMSON connecting cable with serial inter-face adapter (order no. 1400-7700).

The positioner settings configured in TROVIS-VIEW can be directly transferred over theSAMSON connecting cable to the positioner on site. This online connection enables you toread any entered settings as well as providing a diagnostic function.

13.2 Starting TROVIS-VIEW and performing basic settings

Settings may be entered into the TROVIS-VIEW operator interface when either the positioner isconnected or not connected. When the positioner is connected, the data uploaded from the po-sitioner can be overwritten.

80 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 81: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

When the positioner is not connected, the default settings appear on the operator interfacedisplay or, alternatively, a stored TROVIS-VIEW file (*.tro) can be loaded and written over inthe File menu by selecting Open.

Connection to the positioner is established by clicking the symbols on top right on the buttonbar:

Upload data from the positioner and displayed in the operator interface

Download data onto the positioner from the operator interface

The positioner is in online mode, indicated by the TROVIS-VIEW 3 logo on the topright in the blue bar

The positioner is in offline mode.

You can also activate the listed functions in the Device menu.

EB 8384-2 EN 81

Setting with TROVIS-VIEW software – Parameter list

Page 82: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

1. Start TROVIS-VIEW

Make required settings in View menu by activating or deactivating functions.

When the Trend Viewer is activated, all operating data are uploaded cyclically from thepositioner in online mode and shown in the form of graphs.Right-click on the graph to edit the graph format or to copy the logged data to a file.

2. Select required language in Options menu.The selected language can be changed at any time except in online mode.

82 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 83: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

3. Select Communication fromthe Options menu and choose.communication settings.

4. Click on Port settings and select port as well asserver setting.

5. Select Convert in the File menu to selectthe firmware version of the positioner.It must match the version specified in thebar at the top.

6. Enter more details about the plant,if necessary, in Customer Data in theEdit menu.

7. Select Load Factory Defaults in Edit menu to upload default settings to the operator inter-face.

EB 8384-2 EN 83

Setting with TROVIS-VIEW software – Parameter list

Page 84: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

13.3 Setting the parameters

Click on one of the folders listed in the left column to open a window listing the settings of thecorresponding parameters. Place the mouse arrow on the parameter name to open a tool tipproviding information about that particular parameter.

Double-click on a parameter to open a window to enable the parameter to be modified.

Right-click on the parameter to open a drop-down menu pro-viding further editing options.

The parameters in all the folders are listed in the following parameter list.

84 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 85: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

13.4 Parameter list

Parameter Values Defaultsetting

DescriptionRefer to section 12 for the description of thecodes

Identification – Operation unit

TAG Max. 32characters

Tag identification of operation unit

Long TAG

Bus address 0 Code 46

Description Freely available text fields

Message

Text field 1 to 5

Positioner serialnumber

Serial number of the positioner

Positioner productnumber

3730-3 xxx Manufacturer model number of the positioner

Firmware version x.xx Current firmware version of device, Code 43

Diagnosis level EXPERT

Final assemblynumber

0...16777215 0 Any number assignable to clearly identify theentire field device

Date (day) 1...31 1Date that can be entered. Stored in thepositioner

Date (month) January

Date (year) 1900...2155 2003

Certification Indicates whether the positioner can be used inhazardous area

Identification – Positioner

Device type 3730-2 Indicates exact model designation

EB 8384-2 EN 85

Setting with TROVIS-VIEW software – Parameter list

Page 86: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Identification – Positioner – Actuator

Type identificationactuator

Manufacturer ID number of the actuator that thepositioner is mounted upon

Actuator type Single-actingDouble-acting

Single-acting Actuator with or without spring returnmechanism

Attachment Integral/NAMUR

Integral Defines the attachment of the positioner on thecontrol valve

Booster Not present/present

Not present Pneumatic volume booster

Actuator size 60...5600 240 cm2 Effective diaphragm or piston area of theactuator

Signal pressurelower value

0.0...6 0.2 bar Initial value of the actuator bench range

Signal pressureupper value

0.0...6 1.0 bar Final value of the actuator bench range

Supply pressure 0.0...6 6.0 bar Supply pressure of compressed air network

Identification – Positioner – Valve

Type identificationvalve

Manufacturer ID number of the valve that thepositioner is mounted upon

Direction of flow Flow-to-open(FTO)/Flow-to-close(FTC)

Flow-to-open(FTO)

Indicates in which direction the process mediumflows to the valve plug.

Packing Adjustable/Self-adjusting/Bellows seal

Self-ad-justing

Sealing of the plug stem to the atmosphere

Seating surface(leakage class)

Metal sealing/Lapped-in metal/Soft sealing/Nickel sealing

Metal sealing Type of sealing between seat and plug

Pressure balancing Without/With (PTFE)/With (Graphite)

Without Plug with pressure balancing to compensate forforces

Flow characteristic Linear 30:1/Eq. perc. 30:1/Linear 50:1/Eq. perc. 50:1/Other

Linear 50:1 Valve characteristic: Flow to valve travel

86 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 87: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Parameter Values Default Description

Valve dimensionsstandard

DIN/ANSI DIN Valve dimensions according to DIN or ANSI

Nominal size DN 8...2100 50 Nominal size in mm (DIN) or inch (ANSI)

Kvs coefficient 0.0001...20000.0000

1.0000 Kv Valve flow coefficient

Kvs unit Kv/cv Kv Flow coefficient, metric unit (Kvs) or US Amer-ican units (cv)

Seat diameter of thevalve

2.0...500.0 6.0 mm Diameter of valve seat bore

Identification – Positioner – Additional components

Solenoid valveNotinstalled

Code 45

Position transmitter Code 37

Inductive limitswitch

Installed/Not installed

Code 38

Operation unit

Start with defaultsettings

Code 36

Positioner – Operating mode

Current operatingmode

Indicated the current operating mode used bythe device

Target operatingmode

Automatic/Manual/Fail-safeposition

Automatic Code 0

Positioner – Process data

Reference variablew

Displays currentprocess variables

Code 42

Controlled variablex

Current position

EB 8384-2 EN 87

Setting with TROVIS-VIEW software – Parameter list

Page 88: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Status

Condensed state Summarized state of the positioner.The condensed status is made up from the var-ious states.The condensed status can take on the followingstates:

No alarm

Maintenance requirement

Maintenance demand

Failure

Function check

The condensed states “Maintenance require-ment” and “Maintenance demand” are also in-dicated on the positioner display by .The condensed status “Failure” causes thefault alarm symbol to appear on the display.

Fault exists(fault alarm contact)

Display and alarm

Status of the fault alarm contact

Status of limit switchA1

Status of the switching output for limit switch A1

x falls below A1 Indicates whether the controlled variable x hasfallen below the limit for A1

Status of limit switchA2

Status of the switching output for limit switch A2

x exceeds A2 Indicates whether the controlled variable x hasexceeded the limit for A2

Operational status Indicates the current operational status of theinternal control

Temperature Current temperature in the positioner

88 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 89: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Parameter Value Default Description

Positioner – Reference variable

Direction of action Increasing/increasing >>Incr./decr. <>

Increasing/increasing >>

Code 7

Lower referencerange value

0.0...75.0 % 0.0 % Code 12

Upper referencerange value

25.0...100.0 % 100.0 % Code 13

Enable final posi-tion smaller than w

On/Off On Code 14

Final position whenw is smaller

0.0...49.9 % 1.0 % Code 14

Enable final posi-tion greater than w

On/Off Off Code 15

Final position whenw is greater

50.0...100.0 % 100.0 % Code 15

Required transittime OPEN

0...240 s 0 s Code 21

Required transittime CLOSED

0...240 s 0 s Code 22

Positioner – Working range

Initial value oftravel range/angleof rotation range

0.0...12.0 mm 0.0 % Code 8

Final value of travelrange/angle of ro-tation range

3.0...15.0 mm 100.0 % Code 9

Enable travel/angleof rotation lowerlimit

On/Off Off Code 10

Travel/angle of ro-tation lower limit

0.0...49.9 % 0.0 % Code 10

Enable travel/angleof rotation upperlimit

On/Off On Code 11

Travel/angle of ro-tation upper limit

50.0...120.0 % 100.0 % Code 11

EB 8384-2 EN 89

Setting with TROVIS-VIEW software – Parameter list

Page 90: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Positioner – Characteristic

Characteristicselection

LinearEqual percentageEq. perc. reverse

SAMSONbutterfly valves

lineareq. perc.

VETEC rotaryplug valves

lineareq. perc.

Segmented ballvalves

lineareq. perc.

User defined

Linear Code 20

Graphs of the user-defined characteristics,loading and saving characteristics.See example on the next page.

Characteristic type Free text for describing the user-defined char-acteristic

90 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 91: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Example for user-defined characteristic

• Select User defined characteristic in Characteristic selection parameter.• Double-click on Edit, open or save characteristic to open a window where the characteristic can be

edited.Click on Characteristic button on the bottom right to open and save a characteristic.

EB 8384-2 EN 91

Setting with TROVIS-VIEW software – Parameter list

Page 92: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Parameter Values Default Description

Positioner – Performance characteristics

Required propor-tional-action coeffi-cient KP (step)

0...17 7 Code 17

Proportional-actioncoefficient KP (step)

Code 17

Required deriva-tive-action time TV(step)

Off/1/2/3/4 2 Code 18

Derivative-actiontime TV (step)

Code 18

Positioner – Fail-safe action

Fail-safe position Closing Fail-safe action of the actuator upon air/auxil-iary power failure or device start-up.Determined during initialization by the positionof the slide switch (see section 5.1).In double-acting actuators, the fail-safe positionrelates only to the failure of the auxiliary powersupply. There is no defined position when thesupply air fails.

Positioner – Error control

Tolerance band 0.1...10.0 % 5.0 % Code 19

Delay time 0...9999 s 30 s Reset criterion for running control loop moni-toring.A control loop error is issued when the delaytime is exceeded and the system deviation is notwithin the tolerance band.

Total valve travel 1 Code 23

Limit of the totalvalve travel

1000...990 000 000

1 000 000 Code 24

Alarm mode A1 Conducting/highA2 Non-conduc./low

A1 Non-conduc./lowA2 Non-conduc./low

A1 Conducting/highA2 Conduc./high

A1 Non-conduc./lowA2 Conducting/high

A1Conducting/highA2Conducting/high

Code 25

92 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 93: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Enable limit valueA1

On/Off On Code 26

Limit value A1 0.0...100.0 % 2.0 % Code 26

Enable limit valueA2

On/Off On Code 27

Limit value A2 0.0...100.0 % 98.0 % Code 27

Fault alarmspecial functions

Yes/No Yes Code 32

Fault alarmtotal valve travel

Yes/No Yes Code 32

Zero point limit 0.0...100.0 % 5.0 % Limit for zero point monitoring

Positioner – Error control – Classification report

Condensed status error alarms

Note!Each error alarm has a status assigned to it.The possible states are placed in order starting with the lowest priority:

Maintenance demand Lowest

Maintenance requirement

Failure

Function check Highest priority

No alarm Alarm is not added to the condensed status

The fault alarm present in the device with the highest priority determines which condensedstatus is dis-played.The condensed states “Maintenance requirement” and “Maintenance demand” are also indicated onthe positioner display by .The condensed status “Failure” causes the fault alarm symbol to appear on the display.

93 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 94: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

x > range

Determines the individual statusfor each alarm

with symbol

an alarm is not added tothe condensed status

Symbol

for maintenance requirementand

maintenance demand

Symbol

for failure

or symbol

for function check

Code 50

Delta x < range Code 51

Attachment Code 52

Initialization timeexceeded

Code 53

Initialization/solenoid valve

Code 54

Transit time notachieved

Code 55

Pin position Code 56

Control loop Code 57

Zero point Code 58

Autocorrection Code 59

x signal Code 62

w too small Code 63

Control parameter Code 68

Poti parameter Code 69

Calibration param-eter

Code 70

General parameters Code 71

Internaldevice error 1

Code 73

Parameter info Code 75

No emergencymode

Code 76

Options parameter Code 78

Total valve travelexceeded

Determines the condensed status when a faultoccurs

Temperature< –40 °C

Temperature fell below –40 °C duringoperation

Temperature> 80 °C

Temperature exceeded +80 °C duringoperation

94 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 95: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Positioner – Start-up

Reading direction Pneumaticconnectionright/left

Pneumaticconnectionright

Code 2

Pin position Off17/25/35/50/70/100/200 mm90°

Off Code 4

Initialization mode Nominal rangeMaximum rangeManual adjust-mentSubstitution

Maximumrange

Code 6

Pressure limit Off /2.4 /3.7 /1.4 bar

Off Code 16

Determined nom-inal range

Code 5

Minimum transittime OPEN

Code 40

Minimum transittime CLOSED

Code 41

Fail-safe action Fail-safe action of the actuator upon air/auxil-iary power failure or device start-up.Determined during initialization by the positionof the slide switch (see section 5.1).In double-acting actuators, the fail-safe positionrelates only to the failure of the auxiliary powersupply. There is no defined position when thesupply air fails.

EB 8384-2 EN 95

Setting with TROVIS-VIEW software – Parameter list

Page 96: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Positioner – Start-up – Initialization

Initialization mode Nominal rangeMaximum rangeManual adjust-mentSubstitution

Maximumrange

Code 6

Device initialized Status of device initialization

Initialization Starting of initialization procedure.The initialization mode parameter must be firstset to the required initialization procedure.

Initialization status Status of the running initialization procedure

Initializationcanceled

Running initialization procedure has been can-celed. The control valve moves to its fail-safeposition.

Target operatingmode

AutomaticManualSAFE

Automatic Code 0

Current operatingmode

Indicates current operating mode of positioner

Initialization error

x > range

Alarm

Code 50

Delta x < range Code 51

Attachment Code 52

Initialization timeexceeded

Code 53

Initialization/sole-noid valve

Code 54

Transit time too short Code 55

Pin position Code 56

No emergencymode

Code 76

Positioner – Start-up – Substitution

Initialized in Submode

Indicates whether the substitute configuration(sub mode) has been performed

Closing direction Counter-clockwise

Code 34

Blocking position 0.0 % Code 35

96 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 97: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Positioner – Maintenance

Start zero calibration

Zero calibration Starts zero calibration

Initialization status Status of running initialization procedure

Initializationcanceled

Running initialization procedure has been can-celed. The control valve moves to fail-safe posi-tion.

Target operatingmode

AutomaticManualSAFE

Automatic Code 0

Current operatingmode

Indicates current operating mode of positioner

Parameter folder Values Default Description

Positioner – Simulation

Alarm test A1 Code 28

Alarm test A2 Code 28

Alarm test A3(alarm fault output)

Code 28

Diagnosis

Diagnosis levelsetting

Expert

Current operatingmode

Automatic Indicates current operating mode of positioner

EB 8384-2 EN 97

Setting with TROVIS-VIEW software – Parameter list

Page 98: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Diagnosis – Status alarms

Status

Condensed status Alarm symbol Summarized condensed status.Made up from various states.

Operating hourscounter

Display or status

Time elapsed since first initialization

Device in closedloop

Time elapsed in closed loop since first initializa-tion

Device switched onsince lastinitialization

Time elapsed since last initialization

Device in closedloop since lastinitialization

Time elapsed in closed loop since last initializa-tion

Error occured (faultalarm output)

Status of fault alarm output

Solenoid valvestatus

Status of optional solenoid valve

Fail-safe position Fail-safe action of actuator upon airsupply/auxiliary power failure or devicestart-up.Determined during initialization.

Device initialized Status of device initialization

Start performedwith default settings

Indicates whether a start has been performedwith default settings.

Local operationactive

Local operation is active

Configurationchanged

Status of device status bit configurationchanged.

Number of zerocalibrations

Number of zero calibrations performed sincelast initialization

Number ofinitializations

Number of initializations performed

Zero point limit Limit for zero point monitoring

98 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 99: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Operation

Control loop

Alarm

Code 57

Zero point Code 58

Autocorrection Code 59

Fatal error Code 60

w too small Code 63

Total valve travelexceeded

Status of total valve travel limit

Temperatureexceeded

Status alarm resulting from diagnosis analysis

Hardware

x-signal

Alarm

Code 62

i/p converter Code 64

Hardware Code 65

Data memory Code 66

Control calculation Code 67

Program load error Code 77

Initialization

x range

Alarm

Code 50

Delta x < range Code 51

Attachment Code 52

Initialization timeexceeded

Code 53

Initialization/solenoid valve

Code 54

Transit time tooshort

Code 55

Pin position Code 56

No emergencymode

Code 76

EB 8384-2 EN 99

Setting with TROVIS-VIEW software – Parameter list

Page 100: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Data memory

Control parameter

Alarm

Code 68

Poti parameter Code 69

Calibration param-eter

Code 70

General parameters Code 71

Internal deviceerror 1

Code 73

Info parameter Code 75

Option parameter Code 78

Diagnosticparameters

Code 80

Temperature

Min. temperature

Display

Lowest temperature recorded in the positioner

Max. temperature Highest temperature recorded in the positioner

Min. temperature(time)

Operating hours counter logging when thelowest temperature was recorded in thepositioner

Max. temperature(time)

Operating hours counter logging when thehighest temperature was recorded in thepositioner

Diagnosis – Status messages – Data logger

Alarms(1) to (30)

Alarm

Recorded alarms issued by the positioner

Operating hours counter logging of each alarm

Operating hourssince firstinitialization

100 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 101: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Diagnosis – Status alarms – Reset

Reset absolute totaltravel

Resetting correspondingalarms

Reset counter for absolute total valve travelback to 0

Resetdefault values flag

Set back default values flag to 0

Resetconfigurationchanged

Reset device status bitconfiguration changed.

Reset initialization error

Resetx > range

Resetting correspondingalarms

Code 50

ResetDelta x < range

Code 51

Reset attachment Code 52

Resetinitializationexceeded

Code 53

Resetinitialization/sole-noid valve

Code 54

Resettransit time tooshort

Code 55

Reset pin position Code 56

Reset operational error

Reset zero point Resetting correspondingalarms

Code 58

Reset autocorrection Code 59

Reset hardware error

Reset hardware

Resetting correspondingalarms

Code 65

Reset controlcalculation

Code 67

EB 8384-2 EN 101

Setting with TROVIS-VIEW software – Parameter list

Page 102: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

Reset data error

Reset control pa-rameter

Resetting correspondingalarms

Code 68

Reset poti param-eter

Code 69

Resetgeneral parameters

Code 71

Reset options pa-rameter

Code 78

Reset diagnosticparameters

Code 80

Reset statistical information

Reset data logger Measured data in the data logger buffermemory are deleted

102 EB 8384-2 EN

Setting with TROVIS-VIEW software – Parameter list

Page 103: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

14 Dimensions in mm

EB 8384-2 EN 103

Dimensions in mm

A1 Z

A2

40

34

210

28

1480

164 Output (38) Supply (9)

86

70

15

46

3470

7028

Schild

Output A1

Output A2

Supply (9)

50 80

58

58

58

130

495979

76

50

or connecting plate

Direct attachment

NAMUR attachmentExternal

position sensor

Pressure gaugebracket

Lever mmS = 17M = 50L = 100XL = 200

ConnectingplateG ¼ or¼ NPT Reversing amplifier

(option)

M20 x 1.5

Attachment to rotary actuatorsVDI/VDE 3845

for all sizes of fixing level 2

Page 104: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

104 EB 8384-2 EN

Page 105: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 105

Page 106: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

106 EB 8384-2 EN

Page 107: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 107

Page 108: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

108 EB 8384-2 EN

Page 109: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 109

Page 110: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

110 EB 8384-2 EN

Page 111: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 111

Page 112: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

112 EB 8384-2 EN

Page 113: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 113

Page 114: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

114 EB 8384-2 EN

Page 115: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 115

Page 116: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

116 EB 8384-2 EN

Page 117: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 117

Page 118: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

118 EB 8384-2 EN

Page 119: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

EB 8384-2 EN 119

Page 120: Mounting and Operating Instructions EB 8384-2 EN · Version with solenoid valve If the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module

SAMSON AG · MESS- UND REGELTECHNIKWeismüllerstraße 3 · 60314 Frankfurt am Main · GermanyPhone: + 49 69 4009-0 · Fax: +49 69 4009-1507Internet: http://www.samson.de EB 8384-2 EN S/

Z20

05-0

4


Recommended