1
Cutler-Hammer1
MPMP--30003000Motor ProtectionMotor Protection
Cutler-Hammer2
Motor Protection
MP-3000
Protects three phase induction motors of any size and any voltagePatented motor thermal model -field proven in over 20,000 applications world wideMaintenance-free microprocessor based relay designKeeps your motor running safelyRecognized to UL1053 Ground Fault Protection Standard
Award Winning Design!
2
Cutler-Hammer3
Motor Considerations
• Motor Importance• Motor Characteristics
– Horsepower rating– Rated Voltage, speed, service factor,
etc.• Motor starting condition• Motor Cost• Connected Power System
Cutler-Hammer4
Motor Failures
• Overload/overheating • Electrical Short Circuits
– Phase to ground Faults– Phase to phase faults
• Mechanical Failures– Bearings– Couplings
3
Cutler-Hammer5
Abnormal Conditions
• Phase Unbalance• Single Phase• Stall or locked rotor• Jam• Loss of load• Transition
Cutler-Hammer6
MP3000 Catalog Numbers• MP3000 Fixed case, 5 A• MP3001 Drawout case, 5 A, no
communications• MP3002 Drawout case, 5 A, INCOM
communications• 1 Amp versions available• MP3000 priced at $2250 vs. 269+ at $2837• Drawout option for MP3000 is $350 adder
versus Multilin $1100 adder
4
Cutler-Hammer7
MP3000 Value Packs
• MP3000 VPR: MP3000, URTD, RS-232 PONI and MPFO-5
• MP3000 VPI: MP3000, URTD, IPONI and MPFO-5
• Value Pack pricing competitive with 269+• MP3000-INCOM: MP3000 plus IPONI• MP3000-RS232: MP3000 plus RS232 PONI
Cutler-Hammer8
Motor Protection Accessories• Universal RTD module (URTD)
– One style supports up to 11 RTD inputs– Handles copper, nickel or platinum RTD’s– Mounting on back of relay or separately– Electrical or fiber optic communications to relay
• IQDCPS– DC to AC power supply for DC control power applications
• IPONI for MP-3000’s• MPFO-1 - 1 meter Fiber Optic Cable for URTD/MP3000• MPFO-5 - 5 meter Fiber Optic Cable for URTD /MP3000• MPFO-10 - 10 meter Fiber Optic Cable for URTD /MP3000
5
Cutler-Hammer9
Ampgard Pricing
• MP3000 fixed case $3,400• Multilin
– 269plus $7,050– 369 base $6,830
• RTD $400• Metering $1,630• Back Spin $3,220
– 469 $11,480
Cutler-Hammer10
MP-3000 Motor Relay
• Based on IQ 1000 II - the first microprocessor multifunction motor protection relay
• Development program toupdate the protection, hardware and user interface.
• Over 50 new features • Drawout case option UNIVERSAL
RTD MODULE
Cutler-Hammer
6
Cutler-Hammer11
Motor Protection
MP-3000
URTD
11 RTD’s
Electrical or Fiber Optic Interface
Motor
Protection Functions49/51 Overload I2T49S/51 Locked Rotor51R Jam/Stall37 Loss of Load/Underload46 Phase Loss/Unbalance50 Phase Instantaneous OC50G Ground Inst. OC66 Starts per time period
Cutler-Hammer12
MP-3000 Features• Microprocessor Technology
– Advanced protection algorithms– Self diagnostics
• Simple to use - On-line Help Feature• True RMS Current Sensing• Meets UL1053 Ground Fault Protection
Standard• Loss of voltage ride through time of 30
cycles
7
Cutler-Hammer13
Intel-I-TripTM
• Intelligent Motor Overload Protection with adaptive Characteristics
• Builds custom protection curve for each motor to insure accuratemotor protection
• Uses standard information from the motor manufacture - full load amps, locked rotor current, stall time and service factor
• Accurate positive and negative sequence current measurements• Patented, field proven motor thermal model used in over ten
thousand applications world-wide• Adaptive overload trip characteristics with RTD input based on
measured motor temperatures
Cutler-Hammer14
MP-3000 Processor Model
8
Cutler-Hammer15
Rotor I2t Protection
I I1I2
I = I1 (positive sequence) + k * I2 (negative sequence)
(Overload protection includes additional heating effect of negative sequence current)
Cutler-Hammer16
¦
MP3000 I1 and I2 Measurements
9
Cutler-Hammer17
MP 3000 New Features• Protection operational while in program mode• Long Acceleration time with Zero speed switch input • Enhanced RTD monitoring and diagnostics • Motor load shedding feature for external load control• User configurable inputs and outputs for greater application flexibility • Optional Quick Release draw out case• New Armed / Disarmed Function to ensure that false tripping will not
occur on installation and commissioning• Trip or alarm option on relay failure detection• Emergency Override resets thermal bucket and timers to permit motor
starting
Cutler-Hammer18
MP-3000 Communications• Requires optional IPONI or RS232 PONI• Can Daisy Chain up to 1000 devices on INCOM LAN.• Configure set points & set real time clock .• Backward compatible with IQ1000 II.• Alarm status available over INCOM.• Event logging with date and time stamp• New feature - motor starting curve data, average current vs time,
over INCOM.– Begin 100 ms after start declaration– End 5 cycles after run transition or trip– Data points per time based on locked rotor time.– Sends both recorded curve and calculated thermal trip curve for
margin comparison
10
Cutler-Hammer19
STARTING CURRENT PROFILE
MP3000 Overload Trip Curve
Locked RotorMotor
AccelerationCurve
Cutler-Hammer20
Application: Reduced Voltage Starters
TRANSITION CURRENT SETTING
Amps
On
Off
MOTOR CURRENT
TRANSITIONRELAY
• Smooth transition from reduced voltage to full voltage based on motor starting current, time or a combination of time and/or current
• Prolonged autotransformer/reactor life by quicker removal • Incomplete sequence verifies proper transition
11
Cutler-Hammer21
Motors with RTDs• Separate Universal RTD Module -- Reduces installed cost by mounting
module near motor• Fiber optic connector -- Eliminates need of Copper Wire Connection to
MP-3000 (or connect both for redundancy) • One catalog number for all RTDs -- Simplifies Inventory & Ordering • Adjusts Overcurrent Algorithm -- Reduces Nuisance Trips• Extra RTD input -- Increases Temperature Monitoring Capability• Stand-alone Capability -- Lowers Cost of Monitoring Temperature of
Motors, Transformers, Other Equipment• Relay will check coherency of URTD data - e.g. rate of temperature change.• Alarming and diagnostics - will use URTD diagnostic data.• Fail-safe behavior on communications loss
Cutler-Hammer22
MP3000 MMI• Four interface operating modes• Setting mode for changing settings• Monitor mode for readout of operating
conditions• History mode for motor operation history• Log mode for detail records of trip, alarm and
start operations
12
Cutler-Hammer23
Monitor Mode
• Current-displays motor currents• RTD-displays motor, bearing and load temperatures• Motor-displays motor run and start data
Cutler-Hammer24
History Mode
• Motor Statistics• Number of trip events• Number of alarm events• Permanent history• Time and date that event occurred, or time and date
counting began, is available• The time/date start-point can be reset for the whole
page
13
Cutler-Hammer25
Log Mode
• Log book- records 100 events with date and time stamping
• Event- detailed record of 20 trip & alarm events with date and time stamping
• Start- detailed record of the last 4 starts with date and time stamping
Cutler-Hammer26
Log Event• Alarms and trips
– type of trip or alarm– date and time of event is recorded– phase and ground currents at time of trip– % of I2T capability at time of trip– phase unbalance at time of trip– Highest RTD temp in each of 4 groups
• Up to 20 events stored
14
Cutler-Hammer27
Log Start Event
• Date and time of event is recorded• Highest phase and ground current during start• Highest phase unbalance during start• The average current at the time of transition• The time taken from start to current transition• The time taken from start to actual transition
Cutler-Hammer28
Program Mode• Motor Page• RTD Page• Trip Page• Alarm Page• Start Page• Discrete Input Pages• Alarm and Auxiliary Relay Output Pages• Analog Output Page• System Page• Test Page• Reset Page
15
Cutler-Hammer29
System Page
• Output relays individually configurable as mode 1 or mode 2 (fail-safe mode)
• Real Time Clock setting.• 24 or 12 hour time format ; M/D/Yr or D/M/Yr date format.• Select MP-3000 mode or IQ1000 II emulation mode for
IMPACC.• New feature - Armed / Disarmed Function
– Requested for hot-plug-in replacements.– Unique feature to ensure that false tripping will not occur
Cutler-Hammer30
More Pages
Test Page• Ability to toggle any one of 4 outputs individually• Force Analog output to 4, 12, or 20 ma• Read the state of both discrete inputs
Reset Page • History pages can be reset in groups• Permanent History can not be reset
16
Cutler-Hammer31
MPMP--30003000Motor ProtectionMotor Protection
Hardware ConnectionsHardware Connections
Cutler-Hammer32
17
Cutler-Hammer33
Cutler-Hammer34
18
Cutler-Hammer35
Cutler-Hammer36
19
Cutler-Hammer37
Cutler-Hammer38
20
Cutler-Hammer39
Cutler-Hammer40
MPMP--30003000Motor ProtectionMotor Protection
Trip CharacteristicsTrip Characteristics
21
Cutler-Hammer41
Motor Current Profile
Cutler-Hammer42
I2t & Instantaneous
22
Cutler-Hammer43
Underload & Jam
Cutler-Hammer44
Trip Characteristics without RTDs
23
Cutler-Hammer45
Trip Characteristics with RTDs
Cutler-Hammer46
MPMP--30003000Motor Protection Motor Protection PowerNet Screens PowerNet Screens
Relay SettingsRelay Settings
24
Cutler-Hammer47
Cutler-Hammer48
25
Cutler-Hammer49
Cutler-Hammer50
26
Cutler-Hammer51
Cutler-Hammer52
27
Cutler-Hammer53
Cutler-Hammer54
28
Cutler-Hammer55
Cutler-Hammer56
29
Cutler-Hammer57