16
MPS - M A K I N G PA N TYPICAL AP PLICATIONS The Memshield 2 Modular Panelboard System complements our successful Memshield 2 - 125 and 200 MCCB Panelboard ranges and fulfils the requirement for higher rated more intricate systems. Memshield 2 MPS provides the choice of creating a simple panelboard consisting only of an incoming module and outgoing module or a comprehensive panelboard system. This could incorporate horizontal busbar modules that allow you to extend the system with a wide variety of outgoing modules, ancillary devices, accessories and even enables you to extend the system further in the future. Memshield 2 MPS is essentially a panelboard or switchboard in modular form. By choosing from the wide variety of modules you are able to create the ideal panelboard system for your application. Memshield 2 will provide far more flexibility than conventional panelboards and provide a lower cost alternative to an equivalent cubicle switchboard. Individual modules can be conveniently delivered and easily handled on site obviating the need for special access arrangements or handling equipment. Site assembly of modules is uncomplicated and a panelboard system can be quickly produced. Memshield 2 MPS can also be extended to accommodate any future requirements. In simple terms Memshield 2 MPS provides a choice of: Incoming modules, MCCB, fused combination switch (FCS) and direct connection options Outgoing modules, MCCB, MCB and FCS options Horizontal busbar modules Incoming / outgoing module accessories Plinth modules Ancillary modules including DIN - rail enclosures and meter packs Side cableway boxes Connection kits Modules offer IP3X protection and are formed of rust protected sheet steel finished in light grey BS4800 Shade 00A07. Completed systems can be wall / floor or frame mounted. FORMS OF SEPARATION: Form 2 Type 2 - All modules as standard. Form 3B Type 2 - All modules when shields are fitted to outgoing terminals of MCCB's. Form 4 Type 2 - On selected modules as indicated in tables from page 35. MODULAR CONVENIENCE All modules are 250mm deep. All modules are 750mm wide. Side cableway boxes are 250mm wide. All module heights increase in increments of 150mm. APPLICATION Memshield 2 MPS has been designed with inherent flexibility and installer convenience to accommodate the requirements of modern commercial and industrial applications. UNIQUE SOFTWARE ASSISTANCE Memshield 2 MPS offers a simple and effective software selection system - Memshield 2 MPS Advantage. This software can be used to produce layout drawings, establish pricing, identify dimensions and weights and also to output a completed order form. Memshield 2 MPS Advantage is available on request. 5 2 9 32
Transcript

M P S - M A K I N G P A N ET Y P I C A L A P P L I C A T I O N SThe Memshield 2 Modular Panelboard Systemcomplements our successful Memshield 2 - 125 and 200MCCB Panelboard ranges and fulfils the requirement forhigher rated more intricate systems.

Memshield 2 MPS provides the choice of creating asimple panelboard consisting only of an incoming moduleand outgoing module or a comprehensive panelboardsystem. This could incorporate horizontal busbar modulesthat allow you to extend the system with a wide variety ofoutgoing modules, ancillary devices, accessories and evenenables you to extend the system furtherin the future.

Memshield 2 MPS is essentially a

panelboard or switchboard in modular form.

By choosing from the wide variety of modules

you are able to create the ideal panelboard

system for your application. Memshield 2

will provide far more flexibility than

conventional panelboards and provide a

lower cost alternative to an equivalent

cubicle switchboard. Individual modules can

be conveniently delivered and easily handled

on site obviating the need for special access

arrangements or handling equipment.

Site assembly of modules is uncomplicated and

a panelboard system can be quickly produced.

Memshield 2 MPS can also be extended to

accommodate any future requirements.

In simple terms Memshield 2 MPS provides a

choice of:

■ Incoming modules, MCCB, fused

combination switch (FCS) and direct

connection options

■ Outgoing modules, MCCB, MCB and

FCS options

■ Horizontal busbar modules

■ Incoming / outgoing module accessories

■ Plinth modules

■ Ancillary modules including DIN - rail

enclosures and meter packs

■ Side cableway boxes

■ Connection kits

Modules offer IP3X protection and are formed of rust

protected sheet steel finished in light grey BS4800

Shade 00A07.

Completed systems can be wall / floor or frame mounted.

FORMS OF SEPARATION:

Form 2 Type 2 - All modules as standard.

Form 3B Type 2 - All modules when shields are fitted to

outgoing terminals of MCCB's.

Form 4 Type 2 - On selected modules as indicated in tables

from page 35.

MODULAR CONVENIENCE

■ All modules are 250mm deep.

■ All modules are 750mm wide.

■ Side cableway boxes are 250mm wide.

■ All module heights increase in increments of 150mm.

APPLICATIONMemshield 2 MPS has been designed with inherent flexibility and

installer convenience to accommodate the requirements of modern

commercial and industrial applications.

UNIQUE SOFTWARE ASSISTANCE

Memshield 2 MPS offers a simple and

effective software selection system -

Memshield 2 MPS Advantage. This

software can be used to produce layout

drawings, establish pricing, identify

dimensions and weights and also to

output a completed order form.

Memshield 2 MPS Advantage is

available on request.

5

2

9

32

Memshield 2 P1-46 1/8/02 9:35 Page 35

333

N E L B O A R D S S I M P L E

1

3

8

10

7

4

6

STANDARD MEMSHIELD 2 MPS CONFIGURATION

Front access, wall / floor mounting. Top or bottom

cable entry.

INCOMING MODULES

Choice of incoming devices up to 1250A; MCCB, fused

combination switch (FCS), direct connection. Contact us

for details of 1600/2000A ACB options.

HORIZONTAL BUSBAR MODULES

Enabling horizontal extension of the panelboard system.

OUTGOING MODULES

Choice of outgoing devices; MCCB, FCS, MCB.

TYPE B MCB DISTRIBUTION MODULE

ANCILLARY MODULES

MCB distribution modules.

Service centre modules.

Empty general purpose (filler) modules.

Meter pack modules (analogue or digital).

ACCESSORIES

Spare gland plates.

Spare side plates.

Fire barrier kits.

PLINTH MODULES

To form base of modular panelboard system.

SIDE CABLE WAY BOXES

Reducing the need for cable trunking.

CONNECTION KITS

To electrically connect all required modules.

6

7

8

9

10

2

3

4

5

1

Empty general purpose module

Busbar system, fully extendable

Outgoing modules, MCB, MCCB or FCS

Incoming modules, MCCB or FCS

Memshield 2 P1-46 1/8/02 9:36 Page 36

4

13 IP3X PROTECTION

High integrity protection against ingress of foreign bodies

when mounted against a wall

14 COMPLIANCE IEC/BSEN 60439-1

Full compliance with the latest British and

International standards.

15 ANALOGUE OR DIGITAL METERING MODULES

CAN BE MOUNTED ON THE LINE OR LOAD SIDE

OF THE INCOMING CIRCUIT

Enables monitoring of both voltage and current levels.

16 STANDARD MECHANICALLY INTERLOCKED

DUAL INCOMER OPTION

Ideal for applications with mains and standby supplies.

17 GENERAL PURPOSE MODULES TO HOUSE

ANCILLARY DEVICES

Sub - distribution equipment such as MCB’s and modular

devices can be incorporated within the Memshield 2

MPS system.

18 FULLY SHROUDED PAN ASSEMBLIES

To prevent contact with live parts.

19 REMOVABLE PAN ASSEMBLIES

For easier installation and wiring.

20 REMOVABLE GLAND PLATES

Prevents any chance of foreign bodies entering into

device sections.

21 BLANKING MODULES

Prevents access to unused live busbar stabs and blanks

off apertures in front plates.

22 ALL SWITCHED DEVICES HAVE POSITIVE

CONTACT INDICATION

True indication of device contact status.

23 C O V E R S A N D D O O R S F I T W I T H I N

ENCLOSURE DIMENSIONS

Allows adjacent mounting.

24 D O O R S C O V E R A L L D E V I C E S A N D

F R O N T COVER SCREWS

Device sections can be locked to prevent unwanted access.

25 REMOVABLE DOORS

Aid access in restricted working areas.

26 ROBUST CONSTRUCTION

Will provide many years of service in industrial and

commercial applications.

27 MODERN AESTHETIC APPEARANCE

Blends well with modern building design and existing

Memshield 2 products providing a complete circuit

protection solution.

MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE Technical Support: 0121 685 2001

M P S - M A K I N G A P P L I C A T I O N C L E A RF E A T U R E S A N D B E N E F I T S

34

1 UNIQUE ‘MEMSHIELD 2 MPS ADVANTAGE’

SOFTWARE PACKAGE

Aids layout designs, produces price, dimensions,

weights and parts list for ordering. Speeds up and

simplifies the process from conception to ordering with

high accuracy.

2 FCS OR MCCB INCOMERS AND OUTGOERS

To suit fusegear or circuit breaker applications.

3 INCOMERS UP TO 1250A

An alternative to switchboards where the main

incoming supply is up to 1250A. For larger incomer

ratings up to 2000A contact Technical Support.

4 OUTGOERS UP TO 800A

Standard Memshield 2 MPS can cope with large loads.

5 CHOICE OF 3 OR 4 POLE INCOMING AND

OUTGOING CIRCUITS

Standard 3 pole switching or 4 pole where switching of

neutral circuits is required.

6 S T A N D A R D S I D E , T O P A N D B O T T O M

CABLE ENTRY

To suit cabling requirements of any application

7 CHOICE OF SELF ASSEMBLY OR FACTORY

BUILT ASSEMBLIES

Memshield 2 MPS modules available via MEM

Preferred Stockists on a quick lead-time for

site assembly. Optional factory assembled unit

when required.

8 FORM 2 TYPE 2 AS STANDARD, FORM 3B TYPE 2

OR FORM 4 TYPE 2 OPTIONS

To meet high degrees of device separation required by

the installation.

9 HORIZONTAL BUSBAR MODULE EXTENSION

Enables many modules to be assembled meeting

applications traditionally met by distribution

switchboards. Also allows future expansion.

10 UP TO 50KA FOR 1 SECOND RATED BUSBARS

Matches many standard switchboard specification

requirements in a panelboard design.

Busbar ratings below 630A-35kA for 1 second, 630A

and above - 50kA for 1 second.

11 CHOICE OF 1 TO AN ALMOST INFINITE NUMBER

OF OUTGOING WAYS

Can meet the needs of small to large installations.

12 MODULAR CONVENIENCE

All modules are 250mm deep. All modules are 750mm

wide. Side cableway boxes are 250mm wide. All

module heights increase in increments of 150mm.

Memshield 2 P1-46 31/7/02 16:01 Page 37

5

1. SELECT INCOMING MODULE

2. SELECT OPTIONAL HORIZONTAL BUSBAR MODULE

INCOMING POLES No. OF SUITABLE SELECT HEIGHT OF MODULE+ LIST No. DEVICE WAYS INCOMING DEVICE HEIGHT OF RATING Ie When used DEVICE FROM PAGE CABLE BOX MM

as outgoing Cable box includedmodule with incoming module

INCOMING OR OUTGOING MCCB MODULES - FORM 4 TYPE 2250A/400A TPN/4P 1 250A J frame MCCB, 39 300+300 MS1JK4✝

400A K frame MCCB

630A/800A TPN/4P 1 L frame MCCB 39 450+300 MS1L4✝

1000A/1250A TPN/4P 1 M frame MCCB 39 600+450 MS1M4✝

1600/2000A TP/4P incoming ACB - contact us for details

DUAL MCCB INCOMING MODULE c/w MECHANICAL INTERLOCK250A 4P N/A J frame MCCB x 2 Supplied fitted 450+300 MSDJ4400A 4P N/A K frame MCCB x 2 Supplied fitted 450+300 MSDK4INCOMING OR OUTGOING FUSED COMBINATION SWITCH MODULES - FORM 4 TYPE 2 250A 4P 1 250A FCS Supplied fitted* 300+300 MS1S2004400A 4P 1 400A FCS Supplied fitted* 300+300 MS1S4004 630A 4P 1 630A FCS Supplied fitted* 450+300 MS1S6304800A 4P 1 800A FCS Supplied fitted* 450+300 MS1S8004INCOMING DIRECT CONNECTION MODULES 400A/800A TPN N/A 800A direct connection lugs Supplied fitted 300+300 MS800DC 1250A TPN N/A 1250A direct connection lugs Supplied fitted 300+450 MS1250DC

RATING Ie POLES WIDTH MM HEIGHT OF MODULE MM LIST NoHORIZONTAL BUSBAR MODULES400A 4P 750 150 MS4HC800A 4P 750 150 MS8HC1250A 4P 750 150 MS12HC

35

M P S - M A K I N G S E L E C T I O N S T R A I G H T F O R W A R DC R E A T E Y O U R I D E A L P A N E L B O A R D

SIMPLE SELECTION STEPS....

1 Select incoming module.

2 Select optional horizontal busbar module for future extension.

3 Select outgoing module or modules.

4 Select optional ancillary module or modules.

5 Select optional accessories.

6 Select optional plinth module or modules.

7 Select optional side cableway boxes.

8 Select circuit breaker incoming / outgoing devices.

9 Select fused combination switch incoming /outgoing devices.

10 Select connection sets for your choice of modules.

AVAILABLE AUGUST 2001.

* Select fuses from page 41.

✝ This module should not be used as an outgoing unit when installed below any

horizontal busbar module.

Memshield 2 P1-46 31/7/02 16:01 Page 38

36

M P S - M A K I N G S E L E C T I O N S T R A I G H T F O R W A R DC R E A T E Y O U R I D E A L P A N E L B O A R D

3. SELECT OUTGOING MODULE OR MODULES Module list nos. MS683K and MS1283KThese can accept J and K frame outgoing MCCB’s on the left hand side of thebusbars and F frame outgoing MCCB’s on the right. Coupling devices allow Fframe MCCB’s to be fitted on the left instead of J or K frame MCCB’s. Seediagram below table. These modules MUST be fitted with a side cableway boxwhen installing J and K frame MCCB’s or when using cables of 50mm2 and above.

Module list nos. MS2S2004, MS68F4 and MS108F4To provide cabling space on these modules a side cableway box must be fitted on both sides.

MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE

Technical Support: 0121 685 2001

MODULE POLES No OF SUITABLE SELECT HEIGHT OF LIST NORATING Ie WAYS OUTGOING DEVICE DEVICE MODULE+ HEIGHT

FROM OF CABLE BOX MMPAGE Cable box included

with outgoing module

OUTGOING MCCB PANELBOARD MODULES400A busbar system TPN 6 G frame MCCB up to 125A 39 600 MS643G400A busbar system TPN 12 G frame MCCB up to 125A 39 900 MS1243G630A busbar system TPN 6 F frame MCCB up to 200A 39 750 MS663F630A busbar system TPN 12 F frame MCCB up to 200A 39 1050 MS1263F800A busbar system TPN 6 F frame MCCB up to 200A 39 900 MS683K

J frame MCCB up to 250A 39

K frame MCCB up to 400A 39

800A busbar system TPN 12 F frame MCCB up to 200A 39 1200 MS1283KJ frame MCCB up to 250A 39

K frame MCCB up to 400A 39

OUTGOING MCCB PANELBOARD MODULES - FORM 4 TYPE 2400A busbar system TPN/4P 6 G frame MCCB up to 125A 39 750 MS64G4400A busbar system TPN/4P 10 G frame MCCB up to 125A 39 1200 MS104G4800A busbar system TPN/4P 6 F Frame MCCB up to 200A 39 750 MS68F4800A busbar system TPN/4P 10 F Frame MCCB up to 200A 39 1200 MS108F4200A per way TPN/4P 3 F frame MCCB up to 200A 39 300+150 MS3F4✝

250A per way TPN/4P 3 J frame MCCB up to 250A 39 300+300 MS3J4✝

400A per way TPN/4P 2 K frame MCCB up to 400A 39 300+300 MS2K4✝

OUTGOING FUSED COMBINATION SWITCH PANELBOARD MODULES - FORM 4 TYPE 2400A busbar system TPN/4P 6 100A FCS 41 750 MS64S1004400A busbar system TPN/4P 10 100A FCS 41 1200 MS104S1004800A busbar system TPN/4P 6 100A FCS 41 750 MS68S1004800A busbar system TPN/4P 10 100A FCS 41 1200 MS108S1004125A per way TPN/4P 2 125A FCS 41 450 MS2S1254250A per way TPN/4P 2 250A FCS 41 600 MS2S2004

Description List No.

Coupler to allow fitment of ‘F’ frame MCCB in ‘K’ frame MCCB space 4PBCUK

Coupler to allow fitment of ‘F’ frame MCCB in ‘J’ frame MCCB space 4PBCUJ

COUPLERSRequired when fitting ‘F’ frame MCCBs on the left side of module list nos. MS683Kand MS1283K - see diagram below. There are two types of coupler: the first allowsfitment of an ‘F’ frame MCCB in the ‘K’ frame space, the second allows fitment of an‘F’ frame into any ‘J’ frame space.

This arrangement allows outgoing devices to be fitted covering a range from 16A up to 400A.

‘J’ frame160 - 250A

‘K’ frame250 - 400A

(1 max)

F-frame

16 - 200A TP16 - 200A SP

To fit an ‘F’ frameMCCB use coupler

List No 4PBCUJ

To fit an ‘F’ frameMCCB use coupler

List No 4PBCUK

AVAILABLE AUGUST 2001

✝ Only suitable for mounting above horizontal busbar modules.

Memshield 2 P1-46 31/7/02 16:01 Page 39

37

C R E A T E Y O U R I D E A L P A N E L B O A R D

4. SELECT OPTIONAL ANCILLARY MODULE OR MODULES

TYPE OF POLES No OF SUITABLE OUTGOING SELECT HEIGHT OF LIST NoMODULE WAYS DEVICE DEVICE MODULE

FROM PAGE MM MCB DISTRIBUTION MODULES100A busbar system c/w 100A DP main lugs incomer

Type A SPN 10 Type B, C & D MCB’s & RCBO’s 40 300 MS10AType A SPN 16 Type B, C & D MCB’s & RCBO’s 40 300 MS16AType A SPN 2 x 10 Type B, C & D MCB’s & RCBO’s 40 300 MS10A2200A busbar system c/w 200A TP main lugs incomer

Type B TPN 8 Type B, C & D MCB’s & RCBO’s 40 600 MS8BType B TPN 16 Type B, C & D MCB’s & RCBO’s 40 900 MS16BType B TPN 2 x 8 Type B, C & D MCB’s & RCBO’s 40 600 MS8B2Type B TPN 2 x 12 Type B, C & D MCB’s & RCBO’s 40 750 MS12B2SERVICE CENTRE MODULES DIN - rail N/A 2 x 12 MCB’s & RCBO’s+DIN mounting devices 40 300 MS12D2DIN - rail N/A 12 MCB’s & RCBO’s+DIN mounting devices 40 300 MS12DDIN - rail N/A 18 MCB’s & RCBO’s+DIN mounting devices 40 300 MS18DType A + DIN - rail N/A 10+15 MCB’s & RCBO’s+DIN mounting devices 40 300 MS10A15DType A + DIN - rail N/A 16+9 MCB’s & RCBO’s+DIN mounting devices 40 300 MS16A9DMODULE HEIGHT OF LIST NoDESCRIPTION MODULE MMEMPTY GENERAL PURPOSE MODULESTo house equipment or use as filler box 150 MSEM1To house equipment or use as filler box 300 MSEM2To house equipment or use as filler box 450 MSEM3To house equipment or use as filler box 600 MSEM4TYPE OF DESCRIPTION OF HEIGHT OF LIST NoMODULE MEASUREMENT / RATING MODULE MMMETER PACK MODULES Require CT module of corresponding ratingAnalogue Vm+SS, Amm+SS / 250A 150 MSMA250Analogue Vm+SS, Amm + SS / 400A 150 MSMA400Analogue Vm+SS, Amm + SS / 800A 150 MSMA800Analogue Vm+SS, Amm + SS / 1250A 150 MSMA1250Analogue Vm+SS, 3 Amm / 400A 150 MSM3A400Analogue Vm+SS, 3 Amm / 800A 150 MSM3A800Analogue Vm+SS, 3 Amm / 1250A 150 MSM3A1250Digital Up to 1250A, phase Amps, phase Volts, line Volts, per phase PF, 150 MSMD

per phase kW, 3-phase PF, 3-phase kW, frequency, import kWH.

CURRENT TRANSFORMER MODULES Required for meter pack module of corresponding rating250A CT module 150 MS250CT400A CT module 150 MS400CT800A CT module 150 MS800CT1250A CT module 150 MS1250CT

Memshield 2 P1-46 31/7/02 16:02 Page 40

38

DESCRIPTION TO SUIT MODULE TO SUIT MODULE LIST No WIDTH MM HEIGHT MM

INCOMING / OUTGOING MODULE ACCESSORIESFire barrier kit 750 MSHIK Spare steel gland plate, gauge 2.5mm 750 MSGPSReplacement aluminium gland plate, gauge 5mm 750 MSGPASpare steel side plate 150 MSSP1Spare steel side plate 300 MSSP2Spare steel side plate 450 MSSP3Spare steel side plate 600 MSSP4Spare steel side plate 750 MSSP5Spare steel side plate 900 MSSP6Spare steel side plate 1050 MSSP7Spare steel side plate 1200 MSSP8Door cylinder lock AMDLIP3X kit; required to plug fixing holes

when freestanding. One kit per MSIP3Kmodule/cableway box of 300mm

high & above.

DESCRIPTION TO SUIT MODULE TO SUIT MODULE LIST No WIDTH MM HEIGHT MM

PLINTH MODULES150mm high plinth 750 MSMP150mm high plinth 250 MSCP

5. SELECT OPTIONAL ACCESSORIES

6. SELECT OPTIONAL PLINTH MODULE OR MODULES

7. SELECT OPTIONAL SIDE CABLEWAY BOXES

DESCRIPTION TO SUIT MODULE HEIGHT OF LIST NoWIDTH MM MODULE MM

SIDE CABLEWAY BOXESReplaces cable trunking 150 MSVCB1 and increases cabling space 300 MSVCB2

450 MSVCB3600 MSVCB4750 MSVCB5900 MSVCB61050 MSVCB7 1200 MSVCB8

SIDE CABLEWAY ACCESSORIESFire barrier kit, top or bottom 250 MSCBIKFire barrier kit, side 150 MSVIK1Fire barrier kit, side 300 MSVIK2 Fire barrier kit, side 450 MSVIK3Fire barrier kit, side 600 MSVIK4Fire barrier kit, side 750 MSVIK5Fire barrier kit, side 900 MSVIK6Fire barrier kit, side 1050 MSVIK7Fire barrier kit, side 1200 MSVIK8 Spare steel gland plate, gauge 2.5mm 250 MSCBGPSReplacement aluminium gland plate, gauge 5mm 250 MSCBGPA

MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE

Technical Support: 0121 685 2001

M P S - M A K I N G S E L E C T I O N S T R A I G H T F O R W A R DC R E A T E Y O U R I D E A L P A N E L B O A R D

Memshield 2 P1-46 31/7/02 16:02 Page 41

39

M P S - M A K I N G P R O T E C T I O N E L E M E N T A R YS E L E C T I N C O M I N G A N D O U T G O I N G D E V I C E S

BREAKING CAP. Icu (400/440V AC) CONDITIONAL SHORT CIRCUIT RATING, Icc36kA 36kA 65kA 65kA 35kA 35kA

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.TP (Adj) TPSN (Adj) TP (Hi Adj) TPSN (Hi Adj) TP SWITCH 4P SWITCH

250 MKLA2503 MKLA2504 MKHA2503 MKHA2504320 MKLA3203 MKLA3204 MKHA3203 MKHA3204 MKN3203400 MKLA4003 MKLA4004 MKHA4003 MKHA4004 MKN4003 MKN4004

BREAKING CAP. Icu (400/440V AC) SHORT CIRCUIT MAKING CAPACITY, Icm50kA 50kA 50kA 50kA 15kA 15kA

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.TP (Adj) TPSN (Adj) TP (Elec) TPSN (Elec) TP SWITCH 4P SWITCH

400 MLLA4003 MLLA4004630 MLLA6303 MLLA6304 MLLS6303 MLLS6304 MLN6303 MLN6304800 MLLA8003 MLLA8004 MLLS8003 MLLS8004 MLN8003 MLN8004

BREAKING CAP. Icu (440V AC) SHORT CIRCUIT MAKING CAPACITY, Icm65kA 65kA 32kA 32kA

LIST NO. LIST NO. LIST NO. LIST NO.TP (Elec) TPSN (Elec) TP SWITCH 4P SWITCH

1000 MMLS10003 MMLS100041250 MMLS12503 MMLS12504 MMN12503 MMN12504

FRAME SIZE LIST NO. NO. OF POLESG Frame PBGBP1 SP

F Frame 32PBBPJ Frame 34PBBJK Frame 34PBBPK

TP (Adjustableto fit SP, DP, TP)

J FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 160A-250A

K FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 250A-400A

L FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 400A-800A

For information on the full range of MCCB’s please refer to page 4.

8a. SELECT CIRCUIT BREAKER INCOMING / OUTGOING DEVICES

BREAKING CAP. Icu (SP 220/240V AC, TP, TPSN 380/415V AC)16kA 16kA 22kA 25kA 25kA 25kA

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP TP SP TP TP(Hi Adj) TPSN (Hi Adj)

16 MGL161 MGL163 MGH161 MGH163 20 MGL201 MGL203 MGH201 MGH203 MGHAT253 MGHAT25432 MGL321 MGL323 MGH321 MGH323 MGHAT323 MGHAT32440 MGL401 MGL403 MGH401 MGH403 MGHAT453 MGHAT45450 MGL501 MGL503 MGH501 MGH50363 MGL631 MGL633 MGH631 MGH633 MGHAT633 MGHAT63480 MGL801 MGL803 MGH801 MGH803 MGHAT853 MGHAT854100 MGL1001 MGL1003 MGH1001 MGH1003125 MGL1251 MGL1253 MGH1253 MGHAT1253 MGHAT1254

G FRAME MCCB’s 16A-125A OUTGOING

M FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 1000A-1250A

MCCB BLANKING PLATE

BREAKING CAP. Icu (SP 220/240V AC, TP, TPSN 400/440V AC)25kA 25kA 25kA 25kA 45kA 65kA 65kA

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. SP TP TP(Adj) FP(Adj) TP(Hi Break) TP(Hi Adj) TPSN (Hi Adj)

16 MFL161 MFL163 MFH16320 MFL201 MFL203 MFH20332 MFL321 MFL323 MFH32340 MFL401 MFL403 MFH40350 MFL501 MFL503 MFLA503 MFLA504 MFH503 MFHA503 MFHA50463 MFL631 MFL633 MFLA633 MFLA634 MFH633 MFHA633 MFHA63480 MFL801 MFL803 MFLA803 MFLA804 MFH803 MFHA803 MFHA804100 MFL1001 MFL1003 MFLA1003 MFLA1004 MFH1003 MFHA1003 MFHA1004125 MFL1251 MFL1253 MFLA1253 MFLA1254 MFH1253 MFHA1253 MFHA1254160 MFL1601 MFL1603 MFLA1603 MFLA1604 MFH1603 MFHA1603 MFHA1604200 MFL2003 MFH2003

F FRAME MCCB’s 16A-200A OUTGOING

BREAKING CAP. Icu (400/440V AC) CONDITIONAL SHORT CIRCUIT RATING, Icc36kA 36kA 65kA 65kA 35kA 35kA

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.TP (Adj) TPSN (Adj) TP (Hi Adj) TPSN (Hi Adj) TP SWITCH 4P SWITCH

160 MJLA1603 MJLA1604 MJHA1603 MJHA1604200 MJLA2003 MJLA2004 MJHA2003 MJHA2004250 MJLA2503 MJLA2504 MJHA2503 MJHA2504 MJN2503 MJN2504

RATING A

Memshield 2 P1-46 31/7/02 16:03 Page 42

M P S - M A K I N G P R O T E C T I O N E L E M E N T A R YS E L E C T I N C O M I N G A N D O U T G O I N G D E V I C E S

40

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP SPSN* DP TP 4P*

1 MBH101 MBH101N MBH201 MBH301 MBH4012 MBH102 MBH102N MBH202 MBH302 MBH4024 MBH104 MBH104N MBH204 MBH304 MBH4046 MBH106 MBH106N MBH206 MBH306 MBH4068 MBH108 MBH108N MBH208 MBH308 MBH40810 MBH110 MBH110N MBH210 MBH310 MBH41013 MBH113 MBH113N MBH213 MBH313 MBH41316 MBH116 MBH116N MBH216 MBH316 MBH41620 MBH120 MBH120N MBH220 MBH320 MBH42025 MBH125 MBH125N MBH225 MBH325 MBH42532 MBH132 MBH132N MBH232 MBH332 MBH43240 MBH140 MBH140N MBH240 MBH340 MBH44050 MBH150 MBH150N MBH250 MBH350 MBH45063 MBH163 MBH163N MBH263 MBH363 MBH463

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP SPSN* DP TP 4P*

1 MCH101 MCH101N MCH201 MCH301 MCH4012 MCH102 MCH102N MCH202 MCH302 MCH4024 MCH104 MCH104N MCH204 MCH304 MCH4046 MCH106 MCH106N MCH206 MCH306 MCH4068 MCH108 MCH108N MCH208 MCH308 MCH40810 MCH110 MCH110N MCH210 MCH310 MCH41013 MCH113 MCH113N MCH213 MCH313 MCH41316 MCH116 MCH116N MCH216 MCH316 MCH41620 MCH120 MCH120N MCH220 MCH320 MCH42025 MCH125 MCH125N MCH225 MCH325 MCH42532 MCH132 MCH132N MCH232 MCH332 MCH43240 MCH140 MCH140N MCH240 MCH340 MCH44050 MCH150 MCH150N MCH250 MCH350 MCH45063 MCH163 MCH163N MCH263 MCH363 MCH463

RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP SPSN* DP TP 4P*

1 MDH101 MDH101N MDH201 MDH301 MDH4012 MDH102 MDH102N MDH202 MDH302 MDH4024 MDH104 MDH104N MDH204 MDH304 MDH4046 MDH106 MDH106N MDH206 MDH306 MDH4068 MDH108 MDH108N MDH208 MDH308 MDH40810 MDH110 MDH110N MDH210 MDH310 MDH41013 MDH113 MDH113N MDH213 MDH313 MDH41316 MDH116 MDH116N MDH216 MDH316 MDH41620 MDH120 MDH120N MDH220 MDH320 MDH42025 MDH125 MDH125N MDH225 MDH325 MDH42532 MDH132 MDH132N MDH232 MDH332 MDH43240 MDL140** MDL140N** MDL240** MDL340** MDL440**50 MDL150** MDL150N** MDL250** MDL350** MDL450**63 MDL163** MDL163N** MDL263** MDL363** MDL463**

MCB BLANKING PLATE LIST No. MBP

MINIATURE CIRCUIT BREAKERS TYPE B 10kA

MINIATURE CIRCUIT BREAKERS TYPE C 10kA

MINIATURE CIRCUIT BREAKERS TYPE D 10kA

MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE

Technical Support: 0121 685 2001

8b. SELECT CIRCUIT BREAKER INCOMING / OUTGOING DEVICES/RCBO’s

RATING A SENSITIVITY COMPLETE FIELD FITTABLEmA RCBO SUFFIX RC POD LIST NO.

1 - 63 A 30mA R30 MR301 - 63 A 100mA R100 MR1001 - 63 A 100mA time delayed R100D MR100D1 - 63 A 300mA time delayed R300D MR300D

RCBO’s

For complete factory assembled RCBO's add one of the following suffixes to any standard

SP or SPSN MCB or choose a field fittable RC pod to add to your MCB on site.

For information on the full range of

MCB's and accessories please refer to

page 48.

*Suitable for DIN Modules Only. ** 6kA breaking capacity

Memshield 2 P1-46 31/7/02 16:03 Page 43

41

S E L E C T I N C O M I N G A N D O U T G O I N G D E V I C E S

MAX. FCS SUITABLE HRC MOTOR SUITABLE NO. OF POLES FCS LIST NO.RATING A FUSE CURRENT RATING A HRC FUSE

RATING A LIST NO.100 16 16SB3

20 20SB325 25SB332 32SB340 40SB450 50SB4

TPN 100S3N100

63 63SB4 TPSN 100S3SN100

80 80SO100 100SO100 125 100SOM125100 160 100SOM160

125 80 80SD5100 100SD5125 125SD6

TPN 125S3N125

100 160 100SD5M160TPSN 125S3SN125

100 200 100SD5M200250 125 125SF6

160 160SF6TPN 250S3N250

200 200SF6250 250SF7 TPSN 250S3SN250

200 315 200SF6M315400 250 250SF7 FCS

315 315SF7 TPSN SUPPLIED

400 400SF8 FITTED630 250 250SG7

315 315SG7

FCS400 400SH8SUPPLIED450 450SH9

500 500SH9TPSN

FITTED

560 560SH9630 630SH9

800 250 250SG7315 315SG7400 400SH8

FCS450 450SH9SUPPLIED500 500SH9 TPSN

560 560SH9 FITTED630 630SH9710 710SH10800 800SH10

9. SELECT FUSED COMBINATION SWITCHINCOMING / OUTGOING DEVICES

FUSED COMBINATION SWITCHES (FCS) 100 - 800A

INCOMING/OUTGOING

FCS modules of 400A, 630A and 800A are supplied with FCS devices

already fitted as standard.

Fuselinks must be ordered separately in each case by selecting from the table below.

Memshield 2 P1-46 31/7/02 16:04 Page 44

M P S - M A K I N G I N S T A L L A T I O N E A S I E RC O N N E C T I N G M O D U L E S

42

10. SELECT CONNECTION SETS FOR YOUR CHOICE OF MODULES

TO CONNECT MCCB / FCS / DIRECT CONNECTION INCOMING

MODULE TO MCCB / FCS OUTGOING MODULE

MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE

Technical Support: 0121 685 2001

MCC

B / F

CSOU

TGOI

NG

MOD

ULE

LIS

T N

O.

FCS INCOMING MODULE LIST NO.

MS2S1254 MS2S2004 MS1S2004 MS1S4004 MS1S6304 MS1S8004INCOMINGMODULE TOP OR TOP OR

BOTTOM TOP BOTTOM TOP BOTTOM TOP BOTTOMMOUNTING BOTTOM BOTTOMPOSITIONMS643G MSCLS2003G MSCLS2004G MSCLS4003G MSCLS4004GMS1243G MSCLS2003G MSCLS2004G MSCLS4003G MSCLS4004GMS663F MSCLS2003F MSCLS2004F MSCLS4003F MSCLS4004F MSCLS8003F MSCLS8004FMS1263F MSCLS2003F MSCLS2004F MSCLS4003F MSCLS4004F MSCLS8003F MSCLS8004FMS683K MSCLS4003F MSCLS8003F MSCLS8003FMS1283K MSCLS4003F MSCLS8003F MSCLS8003F

TOP OR BOTTOM TOP OR BOTTOM TOP OR BOTTOM TOP OR BOTTOMMS64S1004 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS104S1004 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS68S1004 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS108S1004 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS2S1254 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS2S2004 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS64G4 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS104G4 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS68F4 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS108F4 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100

MCC

B / F

CSOU

TGOI

NG

MOD

ULE

LIS

T N

O.

MCCB / DIRECT CONNECTION INCOMING MODULE LIST NO.

MS1JK4 MS1L4 MS800DCTOP OR BOTTOM TOP OR BOTTOMTOP OR BOTTOM *Bottom mounted only *Bottom mounted only**Top mounted only

TP J FRAME MCCB 4P J FRAME MCCB TP K FRAME MCCB 4P K FRAME MCCB TP L FRAME MCCB 4P L FRAME MCCBINCOMER INCOMER INCOMER INCOMER INCOMER INCOMER

MS643G MSCL3JG MSCL4JG MSCL3KG MSCL4KG MSCLDCGMS1243G MSCL3JG MSCL4JG MSCL3KG MSCL4KG MSCLDCGMS663F MSCL3JF MSCL4JF MSCL3KF MSCL4KF MSCLLF MSCLLF MSCLLFMS1263F MSCL3JF MSCL4JF MSCL3KF MSCL4KF MSCLLF MSCLLF MSCLLFMS683K MSCLLF * MSCLLF ** MSCLLF *MS1283K MSCLLF * MSCLLF ** MSCLLF *

TP OR 4P TP OR 4P TP OR 4PMS64S1004 MSCLJS100 MSCLKS100 MSCL8CDS100MS104S1004 MSCLJS100 MSCLKS100 MSCL8CDS100MS68S1004 MSCLLS100 MSCL8CDS100MS108S1004 MSCLLS100 MSCL8CDS100MS2S1254 MSCLLS100 MSCL8CDS100MS2S2004 MSCLLS100 MSCL8CDS100MS64G4 MSCLJS100 MSCLKS100 MSCL8CDS100MS104G4 MSCLJS100 MSCLKS100 MSCL8CDS100MS68F4 MSCLLS100 MSCL8CDS100MS108F4 MSCLLS100 MSCL8CDS100

INCOMINGMODULE

MOUNTINGPOSITION

Memshield 2 P1-46 31/7/02 16:04 Page 45

C O N N E C T I N G M O D U L E S

43

TO CONNECT MCCB INCOMING / OUTGOING MODULE TO

HORIZONTAL BUSBAR MODULE

HORI

ZONT

AL B

USBA

R M

ODUL

E LI

ST N

O

INCOMING / OUTGOING MCCB MODULE LIST NO.

MS643G MS1243G MS663F MS1263F MS3F4 MS3J4ONE ONE

CONNECTION CONNECTIONSET REQUIRED SET REQUIREDPER OUTGOING PER OUTGOING

WAY WAY

MS4HC MSCLHCG MSCLHCG MSCLHCF MSCLHCF MSCLHCF4 MSCLHCJ4

MS8HC MSCLHCG MSCLHCG MSCLHCF MSCLHCF MSCLHCF4 MSCLHCJ4

MS12HC MSCLHCG MSCLHCG MSCLHCF MSCLHCF MSCLHCF4 MSCLHCJ4

HORI

ZONT

AL B

USBA

R M

ODUL

E LI

ST N

O

INCOMING / OUTGOING MCCB MODULE LIST NO.

MS2K4 MS64G4 MS104G4 MS68F4 MS108F4ONE

CONNECTIONSET REQUIREDPER OUTGOING

WAY

MS4HC MSCLHCK4 MSCLHCS100 MSCLHCS100 MSCLHCS100 MSCLHCS100

MS8HC MSCLHCK4 MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100

MS12HC MSCLHCK4 MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100

HORI

ZONT

AL B

USBA

R M

ODUL

E LI

ST N

O

INCOMING / OUTGOING MCCB MODULE LIST NO.

MS683K MS1283K MS1JK4 MS1L4 MS1M4

WHERE J WHERE KFRAME FRAME

MCCB TO MCCB TOBE FITTED BE FITTED

MS4HC MSCLHCF MSCLHCF MSCLHCJ4 MSCLHCK4 MSCLHCL4 MSCLHCM4

MS8HC MSCLHCF MSCLHCF MSCLHCJ4 MSCLHCK4 MSCLHCL4 MSCLHCM4

MS12HC MSCLHCF MSCLHCF MSCLHCJ4 MSCLHCK4 MSCLHCL4 MSCLHCM4

Memshield 2 P1-46 1/8/02 10:19 Page 46

M P S - M A K I N G I N S T A L L A T I O N E A S I E RC O N N E C T I N G M O D U L E S

44

TO CONNECT FCS INCOMING / OUTGOING MODULE

TO HORIZONTAL BUSBAR MODULE

TO CONNECT INCOMING DIRECT CONNECTION MODULE

TO HORIZONTAL BUSBAR MODULE

TO CONNECT CT MODULE TO HORIZONTAL BUSBAR MODULE

INCOMING / OUTGOING FCS MODULE LIST No.

MS64S1004 MS104S1004 MS68S1004 MS108S1004 MS2S1254

MS4HC MSCLHCS100 MSCLHCS100 MSCLHCS100

MS8HC MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100

MS12HC MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100HORI

ZONT

AL B

USBA

RM

ODUL

E LI

ST N

O.

MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE

Technical Support: 0121 685 2001

INCOMING / OUTGOING FCS MODULE LIST No.

MS2S2004 MS1S2004 MS1S4004 MS1S6304 MS1S8004

MS4HC MSCLHCS100 MSCLHCS200 MSCLHCS400

MS8HC Qty 2 MSCLHCS100 MSCLHCS200 MSCLHCS400 MSCLHCS800 MSCLHCS800

MS12HC Qty 2 MSCLHCS100 MSCLHCS200 MSCLHCS400 MSCLHCS800 MSCLHCS800HORI

ZONT

AL B

USBA

RM

ODUL

E LI

ST N

O.

CT MODULE LIST NO.

MS250CT MS400CT MS800CT MS1250CT

MS4HC MSCLCT400HC MSCLCT400HC

MS8HC MSCLCT400HC MSCLCT400HC MSCLCT800HC

MS12HC MSCLCT400HC MSCLCT400HC MSCLCT800HC MSCLCT1250HCHORI

ZONT

AL B

USBA

RM

ODUL

E LI

ST N

O.

DIRECT CONNECTION MODULE

MS800DC MS1250DC

MS4HC MSCLHC8DC MSCLHC12DC

MS8HC MSCLHC8DC MSCLHC12DC

MS12HC MSCLHC8DC MSCLHC12DCHORI

ZONT

AL B

USBA

RM

ODUL

E LI

ST N

O.

Memshield 2 P47-91 1/8/02 10:00 Page 1

45

C O N N E C T I N G M O D U L E S

CT MODULE LIST NO.MS250CT MS400CT MS800CT MS1250CT

MS643G MSCLCT400G MSCLCT400GMS1243G MSCLCT400G MSCLCT400GMS663F MSCLCT400F MSCLCT800FMS1263F MSCLCT400F MSCLCT800FMS683K MSCLCT800FMS1283K MSCLCT800FMS64S1004 MSCLCT400S100 MSCLCT400S100MS104S1004 MSCLCT400S100 MSCLCT400S100MS68S1004 MSCLCT800S1008MS108S1004 MSCLCT800S1008MS2S1254 MSCLCT400S100 MSCLCT400S100 MSCLCT800S1008MS2S2004 MSCLCT800S1008MS64G4 MSCLCT400S100 MSCLCT400S100MS104G4 MSCLCT400S100 MSCLCT400S100MS68F4 MSCLCT800S1008MS108F4 MSCLCT800S1008MS1S2004 MSCLS200CT250MS1S4004 MSCLS400CT400MS1S6304 MSCLS800CT800MS1S8004 MSCLS800CT800MS1JK4 TP MCCB = MSCL3JCT250 TP MCCB = MSCL3KCT400MS1JK4 4P MCCB = MSCL4JCT250 4P MCCB = MSCL4KCT400MS1L4 MSCLLCT800MS1M4 3P MCCB = MSCL3MCT1250MS1M4 4P MCCB = MSCL4MCT1250MS800DC MSCL8DCCT800 MSCL8DCCT800MS1250DC MSCL3MCT1250

MCC

B / F

CS /

DIRE

CT C

ONN

ECTI

ON IN

COM

ING

/ OU

TGOI

NG

MOD

ULE

LIS

T N

O.

TO CONNECT MCCB / FCS / DIRECT CONNECTION INCOMING / OUTGOING

MODULE TO CT MODULE

TO CONNECT HORIZONTAL BUSBAR MODULE TO HORIZONTAL BUSBAR MODULE

To connect horizontal busbar modules across a side cableway space between modules add

suffix VCB1 to the connection set list number from the table, e.g. MSCL400BBVCB1.

This provides additional connections to bridge the space.

400A horizontal busbar modules require 1 off MSCL400BBVCB1.

800/1250A horizontal busbar modules require 2 off MSCL400BBVCB1.

In each case a 150mm high side cableway box is required list no MSVCB1 which must

be fitted between appropriate height side cableway boxes.

Cabling cannot pass vertically through this connection.

HORIZONTAL BUSBAR MODULE LIST NO.

MS4HC MS8HC MS12HC

MS4HC MSCL400BB

MS8HC QTY 2 MSCL400BB

MS12HC QTY 2 MSCL400BBHORI

ZONT

AL B

USBA

RM

ODUL

E LI

ST N

O.

Memshield 2 P47-91 1/8/02 10:01 Page 2

46

M P S - M A K I N G L A Y O U T S U N C O M P L I C A T E DL A Y O U T G R I D

LAYOUT GRID SCALE 1/16 OF ACTUAL SIZE

The Grid below will help you plan a Memshield 2 Modular Panelboard System up to three

modules wide including a side cable way box at each end and up to 2400mm high.

All modules are 250mm deep.

All modules are 750mm wide.

Side cableway boxes are 250mm wide.

All module heights increase in increments of 150mm.

750mm

250mm

2400m

m

150m

m

Memshield 2 P47-91 1/8/02 10:01 Page 3

47

T E R M I N A L C A P A C I T I E S

MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE

Technical Support: 0121 685 2001

R/Y/B Phase Neutral Phase EarthTunnel Clamp Stud Tunnel Clamp Stud Stud

G frame 16A - 125A 70mm2 side fed - 70mm2 - M8/M10F frame 16A - 200A 120mm2 side fed - - M8 M8/M10J frame 160A - 250A 150mm2 - 150mm2 - M10K frame 250A - 400A 240mm2 - 240mm2 - M10L frame 400A - 800A - M12 - M12 M10M frame 1000A - 1250A - M12 - M12 M10

R/Y/B Phase Neutral Phase EarthFCS Tunnel Clamp Stud Tunnel Clamp Stud StudSize 2 100A - M6 - M6 M10Size 3 160A - M8 - M8 M10Size 4 200/250A - M10 - M10 M10Size 5 400A - M14 - M14 M10Size 6 630/800A - M12 - M12 M10DIRECT CABLE R/Y/B Phase Neutral Phase EarthCONNECTION Tunnel Clamp Stud Tunnel Clamp Stud Stud400A lugs - M16 - M16 M10800A lugs - M16 - M16 M101250A lugs - M16 - M16 M10

INCOMING CABLE TERMINATION SIZE (MAX)

R/Y/B Phase Neutral Phase EarthTunnel Clamp Stud Tunnel Clamp Stud Tunnel Clamp Stud

G frame 16A - 125A 70mm2 - 70mm2 - 70mm2 -F frame 16A - 200A 120mm2 - 70mm2 M8 70mm2 -J frame 160A - 250A 150mm2 - 150mm2 - - M8/M10K frame 250A - 400A 240mm2 - 240mm2 - - M8/M10L frame 400A - 800A - M12 - - - M10M frame 1000A - 1250A - - - - - -

R/Y/B Phase Neutral Phase EarthFCS Tunnel Clamp Stud Tunnel Clamp Stud Tunnel Clamp StudSizes 2 100A - M6 - M6 - M6Sizes 3 160A - M8 - M8 - M8Sizes 4 200/250A - M10 - M10 - M8Sizes 5 400A - M14 - M14 - M10Sizes 6 630/800A - M12 - M12 - M10DIRECT CABLE R/Y/B Phase Neutral Phase EarthCONNECTION Tunnel Clamp Stud Tunnel Clamp Stud Tunnel Clamp Stud400A lugs - - - - - -800A lugs - - - - - -1250A lugs - - - - - -

OUTGOING CABLE TERMINATION SIZE (MAX)

DEVICE TYPEMCCB

DEVICE TYPEMCCB

NOTES

G and F frame distribution modules have the following Earth and Neutral Tunnel

Terminations - 6 x 25mm2, 25 x 50mm2, 6 x 70mm2 (plus 2 M8 stud adapters for larger

cable F frame only).

K frame distribution Modules have the following Earth and Neutral Tunnel

Terminations - 6 x 25mm2, 25 x 50mm2, 6 x 70mm2, 4 x 150mm2 and a M12 stud

for 240mm2.

Memshield 2 P47-91 1/8/02 10:01 Page 4


Recommended