DATASHEET MPZ Reciprocating compressors R404A - R507A MAKING MODERN LIVING POSSIBLE
Transcript
Page 1: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

DATASHEET

MPZ Reciprocating compressorsR404A - R507A

MAKING MODERN LIVING POSSIBLE

Page 2: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and
Page 3: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Hd

D

Hs

H

P

Hp

S

W2

L1

L2

W1

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

MPZ038-4Reciprocating compressorR404A / R507A380-400V/3/50Hz - 460V/3/60Hz

General

Model numbers / on compressor nameplate MPZ038A4LB2A

Code number for single pack 120F0047

Code number for industrial pack 120F0057

Application

Application MBP

Frequency 50 Hz 60 Hz

Evaporating temperature range -30°C / +10°C -30°C / +10°C

Condensing temperature range +30°C / +60°C +30°C / +60°C

Voltage range 360 - 440V 414 - 506V

Cooling requirements

Suction gas cooling normally suffi cient

Motor

Nominal voltage 380-400 V 460V

Voltage range 360 - 440V 414 - 506V

Winding resistance (between phases) +/- 7% at 25°C 11.2 Ω

Maximum Continuous Current (MCC) 6.3 A

Locked Rotor Amp (LRA) 29.2 A

Motor protection Internal line break

Design

Displacement 38.1 cm3/rev

Oil quantity (type) 1.1 litre - POE - 160Z

Maximum refrigerant charge 2.5 kg

Net weight 27 kg

Dimensions

Height H 348 mm

Hs 346 mm

Hd 109 mm

Hp 152 mm

Length L1 234 mm

L2 190 mm

W1 243 mm

W2 190 mm

Suction connector location/I.D. | angle S 3/4” 90°

material | comment Copper | Rubber plug

Discharge connector location/I.D. | angle D 1/2“ 90°

material | comment Copper | Rubber plug

Process connector location/I.D. | angle P 3/8“ 90°

material | comment Copper | Rubber plug

Drawing number 85 01 040 b

FRCC.ED.MPZ038-4.Pr1.02

Page 4: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Superheat = 10 K R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at: to = -10, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

30 1.500 1.999 2.619 3.370 4.261 5.304 6.508 7.884 9.441 35 1.306 1.758 2.320 3.001 3.813 4.765 5.867 7.130 8.563 40 1.134 1.540 2.044 2.658 3.391 4.254 5.256 6.408 7.719 45 - 1.342 1.791 2.339 2.995 3.770 4.673 5.715 6.906 50 - - 1.558 2.041 2.621 3.309 4.115 5.049 6.122 55 - - 1.341 1.761 2.268 2.871 3.581 4.409 5.364 60 - - - 1.498 1.932 2.452 3.068 3.791 4.630

30 805 931 1.046 1.147 1.231 1.297 1.343 1.366 1.365 35 808 950 1.082 1.201 1.305 1.391 1.459 1.505 1.527 40 804 961 1.109 1.245 1.367 1.473 1.561 1.628 1.674 45 - 966 1.128 1.280 1.419 1.543 1.651 1.739 1.806 50 - - 1.141 1.307 1.462 1.604 1.729 1.837 1.924 55 - - 1.149 1.329 1.499 1.656 1.799 1.924 2.031 60 - - - 1.346 1.529 1.701 1.860 2.002 2.127

30 2.10 2.23 2.38 2.52 2.65 2.75 2.81 2.82 2.77 35 2.12 2.26 2.42 2.57 2.71 2.84 2.92 2.96 2.93 40 2.13 2.29 2.46 2.63 2.79 2.93 3.04 3.10 3.11 45 - 2.30 2.49 2.68 2.86 3.03 3.16 3.26 3.29 50 - - 2.51 2.72 2.93 3.12 3.29 3.41 3.49 55 - - 2.52 2.76 2.99 3.21 3.41 3.57 3.68 60 - - - 2.77 3.03 3.29 3.52 3.72 3.86

30 36 49 64 83 106 133 165 203 248 35 33 45 60 78 100 126 158 195 238 40 30 42 56 73 95 120 151 187 229 45 - 39 52 69 89 114 144 179 221 50 - - 49 65 85 108 137 172 212 55 - - 46 61 80 103 131 164 204 60 - - - 58 76 98 125 158 196

30 1.86 2.15 2.50 2.94 3.46 4.09 4.85 5.77 6.92 35 1.62 1.85 2.14 2.50 2.92 3.42 4.02 4.74 5.61 40 1.41 1.60 1.84 2.14 2.48 2.89 3.37 3.93 4.61 45 - 1.39 1.59 1.83 2.11 2.44 2.83 3.29 3.82 50 - - 1.36 1.56 1.79 2.06 2.38 2.75 3.18 55 - - 1.17 1.32 1.51 1.73 1.99 2.29 2.64 60 - - - 1.11 1.26 1.44 1.65 1.89 2.18

MPZ038-4

FRCC.ED.MPZ038-4.Pr1.02

Cooling capacity 2.995 WPower input 1.419 WCurrent consumption 2.86 AMass fl ow 89 kg/hC.O.P. 2.11

to: evaporating temperature at dew pointtc: condensing temperature at dew pointRating conditions: suction gas temp.= 20°C, subcooling = 0K

Sound power level 72 dB(A)

With accoustic hood dB(A)

Page 5: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Suction temp. = 20 °C R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at : to = -10°C, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

30 1.372 1.853 2.459 3.204 4.101 5.162 6.400 7.824 9.441 35 1.174 1.605 2.151 2.824 3.638 4.607 5.744 7.060 8.563 40 999 1.381 1.867 2.470 3.204 4.082 5.119 6.329 7.719 45 843 1.179 1.607 2.141 2.795 3.585 4.523 5.627 6.906 50 703 994 1.366 1.834 2.411 3.112 3.954 4.953 6.122 55 - 826 1.144 1.546 2.047 2.662 3.408 4.303 5.364 60 - 669 935 1.274 1.700 2.231 2.883 3.676 4.630

30 805 931 1.046 1.147 1.231 1.297 1.343 1.366 1.365 35 808 950 1.082 1.201 1.305 1.391 1.459 1.505 1.527 40 804 961 1.109 1.245 1.367 1.473 1.561 1.628 1.674 45 796 966 1.128 1.280 1.419 1.543 1.651 1.739 1.806 50 783 965 1.141 1.307 1.462 1.604 1.729 1.837 1.924 55 - 961 1.149 1.329 1.499 1.656 1.799 1.924 2.031 60 - 955 1.154 1.346 1.529 1.701 1.860 2.002 2.127

30 2.10 2.23 2.38 2.52 2.65 2.75 2.81 2.82 2.77 35 2.12 2.26 2.42 2.57 2.71 2.84 2.92 2.96 2.93 40 2.13 2.29 2.46 2.63 2.79 2.93 3.04 3.10 3.11 45 2.14 2.30 2.49 2.68 2.86 3.03 3.16 3.26 3.29 50 2.13 2.31 2.51 2.72 2.93 3.12 3.29 3.41 3.49 55 - 2.29 2.52 2.76 2.99 3.21 3.41 3.57 3.68 60 - 2.26 2.51 2.77 3.03 3.29 3.52 3.72 3.86

30 43 57 74 93 117 144 175 209 248 35 39 53 69 88 110 137 167 201 238 40 36 49 64 83 104 130 159 192 229 45 33 46 60 78 99 123 152 184 221 50 31 42 56 73 93 117 145 177 212 55 - 40 53 69 88 111 138 169 204 60 - 37 50 65 84 106 132 162 196

30 1.70 1.99 2.35 2.79 3.33 3.98 4.76 5.73 6.92 35 1.45 1.69 1.99 2.35 2.79 3.31 3.94 4.69 5.61 40 1.24 1.44 1.68 1.98 2.34 2.77 3.28 3.89 4.61 45 1.06 1.22 1.42 1.67 1.97 2.32 2.74 3.24 3.82 50 0.90 1.03 1.20 1.40 1.65 1.94 2.29 2.70 3.18 55 - 0.86 0.99 1.16 1.37 1.61 1.90 2.24 2.64 60 - 0.70 0.81 0.95 1.11 1.31 1.55 1.84 2.18

FRCC.ED.MPZ038-4.Pr1.02

MPZ038-4

Cooling capacity 2.795 WPower input 1.419 WCurrent consumption 2.86 AMass fl ow 99 kg/hC.O.P. 1.97

to: evaporating temperature at dew pointtc: condensing temperature at dew pointRating conditions: superheat = 10K, subcooling = 0K

Sound power level 72 dB(A)

With accoustic hood dB(A)

Page 6: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and
Page 7: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Hd

D

Hs

H

P

Hp

S

W2

L1

L2

W1

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

MPZ048-4Reciprocating compressorR404A / R507A380-400V/3/50Hz - 460V/3/60Hz

General

Model numbers / on compressor nameplate MPZ048A4LB2A

Code number for single pack 120F0048

Code number for industrial pack 120F0058

Application

Application MBP

Frequency 50 Hz 60 Hz

Evaporating temperature range -30°C / +10°C -30°C / +10°C

Condensing temperature range +30°C / +60°C +30°C / +60°C

Voltage range 360 - 440V 414 - 506V

Cooling requirements

Suction gas cooling normally suffi cient

Motor

Nominal voltage 380-400 V 460V

Voltage range 360 - 440V 414 - 506V

Winding resistance (between phases) +/- 7% at 25°C 11.2 Ω

Maximum Continuous Current (MCC) 6 A

Locked Rotor Amp (LRA) 29.2 A

Motor protection Internal line break

Design

Displacement 48.1 cm3/rev

Oil quantity (type) 1.1 litre - POE - 160Z

Maximum refrigerant charge 2.5 kg

Net weight 27 kg

Dimensions

Height H 348 mm

Hs 346 mm

Hd 109 mm

Hp 152 mm

Length L1 234 mm

L2 190 mm

W1 243 mm

W2 190 mm

Suction connector location/I.D. | angle S 3/4” 90°

material | comment Copper | Rubber plug

Discharge connector location/I.D. | angle D 1/2“ 90°

material | comment Copper | Rubber plug

Process connector location/I.D. | angle P 3/8“ 90°

material | comment Copper | Rubber plug

Drawing number 85 01 040 b

FRCC.ED.MPZ048-4.Pr1.02

Page 8: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Superheat = 10 K R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at: to = -10, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

30 1.781 2.398 3.151 4.053 5.120 6.363 7.795 9.427 11.262 35 1.562 2.139 2.838 3.673 4.659 5.808 7.135 8.651 10.362 40 1.343 1.880 2.526 3.294 4.199 5.255 6.476 7.876 9.463 45 1.125 1.621 2.212 2.913 3.738 4.701 5.816 7.100 8.563 50 906 1.361 1.898 2.531 3.275 4.144 5.154 6.322 7.661 55 - 1.099 1.580 2.145 2.808 3.584 4.489 5.540 6.755 60 - 836 1.260 1.755 2.336 3.018 3.816 4.752 5.843

30 1.059 1.222 1.375 1.517 1.644 1.757 1.852 1.928 1.982 35 1.063 1.245 1.417 1.577 1.723 1.853 1.966 2.060 2.132 40 1.067 1.270 1.462 1.643 1.809 1.960 2.093 2.207 2.299 45 1.061 1.288 1.503 1.707 1.896 2.069 2.225 2.361 2.476 50 1.040 1.292 1.533 1.761 1.976 2.174 2.354 2.515 2.654 55 - 1.274 1.543 1.799 2.040 2.266 2.473 2.661 2.826 60 - 1.228 1.526 1.812 2.083 2.338 2.575 2.791 2.986

30 2.32 2.51 2.72 2.92 3.11 3.28 3.41 3.48 3.49 35 2.35 2.56 2.79 3.02 3.24 3.43 3.59 3.70 3.74 40 2.36 2.60 2.85 3.11 3.36 3.59 3.79 3.93 4.01 45 2.36 2.62 2.91 3.20 3.49 3.76 3.99 4.18 4.30 50 2.33 2.63 2.95 3.28 3.61 3.92 4.20 4.43 4.60 55 - 2.60 2.97 3.34 3.71 4.07 4.40 4.68 4.91 60 - 2.54 2.95 3.38 3.80 4.21 4.59 4.93 5.21

30 56 74 94 118 146 177 213 253 296 35 53 71 91 115 142 172 207 246 288 40 49 67 87 111 137 167 201 239 281 45 45 63 83 106 132 162 195 232 273 50 40 59 79 101 127 156 189 225 265 55 - 53 74 96 121 150 182 218 257 60 - 47 68 90 115 143 175 210 248

30 1.68 1.96 2.29 2.67 3.11 3.62 4.21 4.89 5.68 35 1.47 1.72 2.00 2.33 2.70 3.13 3.63 4.20 4.86 40 1.26 1.48 1.73 2.01 2.32 2.68 3.09 3.57 4.12 45 1.06 1.26 1.47 1.71 1.97 2.27 2.61 3.01 3.46 50 0.87 1.05 1.24 1.44 1.66 1.91 2.19 2.51 2.89 55 - 0.86 1.02 1.19 1.38 1.58 1.81 2.08 2.39 60 - 0.68 0.83 0.97 1.12 1.29 1.48 1.70 1.96

MPZ048-4

Cooling capacity 3.738 WPower input 1.896 WCurrent consumption 3.49 AMass fl ow 132 kg/hC.O.P. 1.97

FRCC.ED.MPZ048-4.Pr1.02

Sound power level 69 dB(A)

With accoustic hood dB(A)

Page 9: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Suction temp. = 20 °C R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at : to = -10°C, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

30 1.948 2.587 3.355 4.263 5.320 6.538 7.927 9.498 11.262 35 1.737 2.342 3.061 3.904 4.883 6.007 7.288 8.736 10.362 40 1.525 2.095 2.765 3.545 4.445 5.476 6.649 7.974 9.463 45 - 1.845 2.467 3.183 4.005 4.943 6.008 7.212 8.563 50 - - 2.163 2.816 3.561 4.407 5.365 6.446 7.661 55 - - 1.853 2.444 3.111 3.865 4.717 5.676 6.755 60 - - - 2.065 2.655 3.317 4.062 4.900 5.843

30 1.059 1.222 1.375 1.517 1.644 1.757 1.852 1.928 1.982 35 1.063 1.245 1.417 1.577 1.723 1.853 1.966 2.060 2.132 40 1.067 1.270 1.462 1.643 1.809 1.960 2.093 2.207 2.299 45 - 1.288 1.503 1.707 1.896 2.069 2.225 2.361 2.476 50 - - 1.533 1.761 1.976 2.174 2.354 2.515 2.654 55 - - 1.543 1.799 2.040 2.266 2.473 2.661 2.826 60 - - - 1.812 2.083 2.338 2.575 2.791 2.986

30 2.32 2.51 2.72 2.92 3.11 3.28 3.41 3.48 3.49 35 2.35 2.56 2.79 3.02 3.24 3.43 3.59 3.70 3.74 40 2.36 2.60 2.85 3.11 3.36 3.59 3.79 3.93 4.01 45 - 2.62 2.91 3.20 3.49 3.76 3.99 4.18 4.30 50 - - 2.95 3.28 3.61 3.92 4.20 4.43 4.60 55 - - 2.97 3.34 3.71 4.07 4.40 4.68 4.91 60 - - - 3.38 3.80 4.21 4.59 4.93 5.21

30 47 63 82 105 132 164 202 245 296 35 44 60 79 102 128 159 196 239 288 40 41 57 76 98 124 155 191 232 281 45 - 54 73 94 120 150 185 226 273 50 - - 69 90 115 145 179 219 265 55 - - 64 85 110 139 173 212 257 60 - - - 80 104 133 166 204 248

30 1.84 2.12 2.44 2.81 3.24 3.72 4.28 4.93 5.68 35 1.63 1.88 2.16 2.48 2.83 3.24 3.71 4.24 4.86 40 1.43 1.65 1.89 2.16 2.46 2.79 3.18 3.61 4.12 45 - 1.43 1.64 1.86 2.11 2.39 2.70 3.05 3.46 50 - - 1.41 1.60 1.80 2.03 2.28 2.56 2.89 55 - - 1.20 1.36 1.52 1.71 1.91 2.13 2.39 60 - - - 1.14 1.27 1.42 1.58 1.76 1.96

FRCC.ED.MPZ048-4.Pr1.02

MPZ048-4

Cooling capacity 4.005 WPower input 1.896 WCurrent consumption 3.49 AMass fl ow 120 kg/hC.O.P. 2.11

Sound power level 69 dB(A)

With accoustic hood dB(A)

Page 10: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and
Page 11: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Hd

D

Hs

H

P

Hp

S

W2

L1

L2

W1

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

MPZ054-4Reciprocating compressorR404A / R507A380-400V/3/50Hz - 460V/3/60Hz

General

Model numbers / on compressor nameplate MPZ054A4LB2A

Code number for single pack 120F0049

Code number for industrial pack 120F0059

Application

Application MBP

Frequency 50 Hz 60 Hz

Evaporating temperature range -30°C / +10°C -30°C / +10°C

Condensing temperature range +30°C / +60°C +30°C / +60°C

Voltage range 360 - 440V 414 - 506V

Cooling requirements

Suction gas cooling normally suffi cient

Motor

Nominal voltage 380-400 V 460V

Voltage range 360 - 440V 414 - 506V

Winding resistance (between phases) +/- 7% at 25°C 11.2 Ω

Maximum Continuous Current (MCC) 6.4 A

Locked Rotor Amp (LRA) 29.2 A

Motor protection Internal line break

Design

Displacement 53.9 cm3/rev

Oil quantity (type) 1.1 litre - POE - 160Z

Maximum refrigerant charge 2.5 kg

Net weight 27 kg

Dimensions

Height H 348 mm

Hs 346 mm

Hd 109 mm

Hp 152 mm

Length L1 234 mm

L2 190 mm

W1 243 mm

W2 190 mm

Suction connector location/I.D. | angle S 3/4” 90°

material | comment Copper | Rubber plug

Discharge connector location/I.D. | angle D 1/2“ 90°

material | comment Copper | Rubber plug

Process connector location/I.D. | angle P 3/8“ 90°

material | comment Copper | Rubber plug

Drawing number 85 01 040 b

FRCC.ED.MPZ054-4.Pr1.02

Page 12: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Superheat = 10 K R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at: to = -10, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

30 2.075 2.782 3.635 4.648 5.836 7.211 8.789 10.583 12.608 35 1.864 2.542 3.351 4.305 5.418 6.705 8.179 9.854 11.744 40 1.635 2.278 3.037 3.926 4.960 6.151 7.515 9.065 10.815 45 - 1.996 2.699 3.518 4.465 5.555 6.803 8.222 9.826 50 - - 2.342 3.083 3.938 4.922 6.047 7.329 8.781 55 - - 1.971 2.629 3.386 4.256 5.254 6.392 7.686 60 - - - 2.160 2.813 3.564 4.427 5.416 6.546

30 1.142 1.339 1.527 1.700 1.852 1.980 2.077 2.139 2.161 35 1.158 1.375 1.584 1.781 1.960 2.117 2.245 2.341 2.398 40 1.165 1.402 1.633 1.855 2.061 2.247 2.407 2.536 2.630 45 - 1.420 1.674 1.920 2.154 2.369 2.561 2.725 2.855 50 - - 1.706 1.977 2.238 2.483 2.708 2.906 3.074 55 - - 1.729 2.025 2.314 2.589 2.846 3.079 3.284 60 - - - 2.063 2.380 2.686 2.976 3.244 3.487

30 2.40 2.66 2.91 3.16 3.39 3.59 3.75 3.85 3.88 35 2.46 2.73 3.01 3.28 3.54 3.77 3.96 4.09 4.17 40 2.49 2.79 3.10 3.41 3.70 3.96 4.19 4.37 4.49 45 - 2.83 3.18 3.52 3.86 4.17 4.44 4.67 4.84 50 - - 3.23 3.62 4.00 4.36 4.69 4.98 5.21 55 - - 3.24 3.69 4.13 4.55 4.94 5.29 5.58 60 - - - 3.72 4.22 4.70 5.16 5.58 5.95

30 50 68 89 114 145 181 223 273 331 35 47 66 87 112 142 178 220 270 327 40 44 62 84 109 139 174 216 265 321 45 - 58 79 104 134 168 210 258 314 50 - - 74 99 127 161 202 249 304 55 - - 68 92 120 153 192 238 292 60 - - - 84 111 143 181 226 278

30 1.82 2.08 2.38 2.73 3.15 3.64 4.23 4.95 5.83 35 1.61 1.85 2.12 2.42 2.76 3.17 3.64 4.21 4.90 40 1.40 1.63 1.86 2.12 2.41 2.74 3.12 3.57 4.11 45 - 1.41 1.61 1.83 2.07 2.35 2.66 3.02 3.44 50 - - 1.37 1.56 1.76 1.98 2.23 2.52 2.86 55 - - 1.14 1.30 1.46 1.64 1.85 2.08 2.34 60 - - - 1.05 1.18 1.33 1.49 1.67 1.88

FRCC.ED.MPZ054-4.Pr1.02

MPZ054-4

Cooling capacity 4.465 WPower input 2.154 WCurrent consumption 3.86 AMass fl ow 134 kg/hC.O.P. 2.07

Sound power level 68 dB(A)

With accoustic hood dB(A)

Page 13: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Suction temp. = 20 °C R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at : to = -10°C, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

30 1.897 2.579 3.414 4.420 5.616 7.018 8.642 10.504 12.608 35 1.675 2.321 3.107 4.050 5.170 6.483 8.007 9.758 11.744 40 1.440 2.044 2.774 3.648 4.685 5.903 7.319 8.953 10.815 45 1.199 1.754 2.421 3.220 4.167 5.282 6.585 8.095 9.826 50 956 1.456 2.055 2.771 3.622 4.628 5.810 7.188 8.781 55 - 1.157 1.681 2.308 3.056 3.946 5.000 6.239 7.686 60 - 864 1.306 1.837 2.475 3.242 4.159 5.252 6.546

30 1.142 1.339 1.527 1.700 1.852 1.980 2.077 2.139 2.161 35 1.158 1.375 1.584 1.781 1.960 2.117 2.245 2.341 2.398 40 1.165 1.402 1.633 1.855 2.061 2.247 2.407 2.536 2.630 45 1.164 1.420 1.674 1.920 2.154 2.369 2.561 2.725 2.855 50 1.153 1.429 1.706 1.977 2.238 2.483 2.708 2.906 3.074 55 - 1.429 1.729 2.025 2.314 2.589 2.846 3.079 3.284 60 - 1.418 1.741 2.063 2.380 2.686 2.976 3.244 3.487

30 2.40 2.66 2.91 3.16 3.39 3.59 3.75 3.85 3.88 35 2.46 2.73 3.01 3.28 3.54 3.77 3.96 4.09 4.17 40 2.49 2.79 3.10 3.41 3.70 3.96 4.19 4.37 4.49 45 2.50 2.83 3.18 3.52 3.86 4.17 4.44 4.67 4.84 50 2.46 2.84 3.23 3.62 4.00 4.36 4.69 4.98 5.21 55 - 2.80 3.24 3.69 4.13 4.55 4.94 5.29 5.58 60 - 2.71 3.21 3.72 4.22 4.70 5.16 5.58 5.95

30 59 79 102 129 160 195 236 281 331 35 56 77 100 126 157 192 233 278 327 40 53 73 96 123 153 188 228 272 321 45 48 68 91 117 148 182 221 265 314 50 43 63 85 111 141 174 213 256 304 55 - 56 78 103 132 165 203 245 292 60 - 49 70 94 122 154 191 232 278

30 1.66 1.93 2.24 2.60 3.03 3.54 4.16 4.91 5.83 35 1.45 1.69 1.96 2.27 2.64 3.06 3.57 4.17 4.90 40 1.24 1.46 1.70 1.97 2.27 2.63 3.04 3.53 4.11 45 1.03 1.23 1.45 1.68 1.93 2.23 2.57 2.97 3.44 50 0.83 1.02 1.20 1.40 1.62 1.86 2.15 2.47 2.86 55 - 0.81 0.97 1.14 1.32 1.52 1.76 2.03 2.34 60 - 0.61 0.75 0.89 1.04 1.21 1.40 1.62 1.88

FRCC.ED.MPZ054-4.Pr1.02

MPZ054-4

Cooling capacity 4.167 WPower input 2.154 WCurrent consumption 3.86 AMass fl ow 148 kg/hC.O.P. 1.93

Sound power level 68 dB(A)

With accoustic hood dB(A)

Page 14: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and
Page 15: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Hd

D

Hs

H

P

Hp

S

W2

L1

L2

W1

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

MPZ061-4Reciprocating compressorR404A / R507A380-400V/3/50Hz - 460V/3/60Hz

General

Model numbers / on compressor nameplate MPZ061A4LB2A

Code number for single pack 120F0050

Code number for industrial pack 120F0060

Application

Application MBP

Frequency 50 Hz 60 Hz

Evaporating temperature range -30°C / +10°C -30°C / +10°C

Condensing temperature range +30°C / +60°C +30°C / +60°C

Voltage range 360 - 440V 414 - 506V

Cooling requirements

Suction gas cooling normally suffi cient

Motor

Nominal voltage 380-400 V 460V

Voltage range 360 - 440V 414 - 506V

Winding resistance (between phases) +/- 7% at 25°C 8.6 Ω

Maximum Continuous Current (MCC) 8.5 A

Locked Rotor Amp (LRA) 38.1 A

Motor protection Internal line break

Design

Displacement 60.5 cm3/rev

Oil quantity (type) 1.1 litre - POE - 160Z

Maximum refrigerant charge 2.5 kg

Net weight 27 kg

Dimensions

Height H 348 mm

Hs 346 mm

Hd 109 mm

Hp 152 mm

Length L1 234 mm

L2 190 mm

W1 243 mm

W2 190 mm

Suction connector location/I.D. | angle S 3/4” 90°

material | comment Copper | Rubber plug

Discharge connector location/I.D. | angle D 1/2“ 90°

material | comment Copper | Rubber plug

Process connector location/I.D. | angle P 3/8“ 90°

material | comment Copper | Rubber plug

Drawing number 85 01 040 b

FRCC.ED.MPZ061-4.Pr1.02

Page 16: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Superheat = 10 K R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at: to = -10, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

FRCC.ED.MPZ061-4.Pr1.02

30 2.219 2.989 3.930 5.058 6.391 7.943 9.730 11.764 14.049 35 1.954 2.675 3.548 4.593 5.824 7.259 8.913 10.801 12.928 40 1.689 2.360 3.168 4.129 5.260 6.577 8.099 9.841 11.813 45 1.422 2.044 2.786 3.663 4.695 5.896 7.287 8.884 10.700 50 1.153 1.725 2.400 3.195 4.127 5.213 6.473 7.925 9.587 55 - 1.401 2.009 2.721 3.553 4.524 5.653 6.962 8.470 60 - 1.073 1.611 2.238 2.970 3.826 4.825 5.991 7.346

30 1.359 1.588 1.799 1.993 2.168 2.323 2.459 2.574 2.668 35 1.374 1.632 1.872 2.092 2.291 2.471 2.629 2.765 2.879 40 1.372 1.663 1.933 2.182 2.410 2.617 2.800 2.961 3.098 45 1.350 1.676 1.981 2.263 2.522 2.759 2.971 3.159 3.322 50 1.307 1.671 2.013 2.331 2.625 2.895 3.139 3.358 3.550 55 - 1.645 2.028 2.385 2.717 3.023 3.302 3.555 3.779 60 - 1.596 2.022 2.422 2.795 3.140 3.458 3.747 4.007

30 3.23 3.48 3.78 4.08 4.38 4.65 4.87 5.00 5.03 35 3.30 3.56 3.87 4.20 4.52 4.81 5.06 5.22 5.28 40 3.35 3.64 3.97 4.33 4.69 5.02 5.30 5.51 5.62 45 3.37 3.69 4.06 4.46 4.86 5.24 5.57 5.84 6.00 50 3.34 3.71 4.13 4.58 5.04 5.47 5.87 6.19 6.43 55 - 3.67 4.15 4.66 5.19 5.69 6.16 6.56 6.87 60 - 3.55 4.10 4.69 5.29 5.88 6.43 6.92 7.32

30 69 92 118 147 182 221 266 315 370 35 66 88 114 143 177 215 259 307 360 40 62 84 109 138 172 209 252 299 351 45 57 79 105 134 166 203 245 291 341 50 51 74 99 128 160 197 237 283 332 55 - 68 93 122 154 190 230 274 322 60 - 60 86 115 146 182 221 265 312

30 1.63 1.88 2.18 2.54 2.95 3.42 3.96 4.57 5.27 35 1.42 1.64 1.90 2.20 2.54 2.94 3.39 3.91 4.49 40 1.23 1.42 1.64 1.89 2.18 2.51 2.89 3.32 3.81 45 1.05 1.22 1.41 1.62 1.86 2.14 2.45 2.81 3.22 50 0.88 1.03 1.19 1.37 1.57 1.80 2.06 2.36 2.70 55 - 0.85 0.99 1.14 1.31 1.50 1.71 1.96 2.24 60 - 0.67 0.80 0.92 1.06 1.22 1.40 1.60 1.83

MPZ061-4

Cooling capacity 4.695 WPower input 2.522 WCurrent consumption 4.86 AMass fl ow 166 kg/hC.O.P. 1.86

Sound power level 68 dB(A)

With accoustic hood dB(A)

Page 17: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Suction temp. = 20 °C R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at : to = -10°C, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

FRCC.ED.MPZ061-4.Pr1.02

30 2.427 3.225 4.185 5.319 6.641 8.162 9.895 11.853 14.049 35 2.173 2.929 3.827 4.881 6.104 7.507 9.104 10.907 12.928 40 1.917 2.631 3.469 4.443 5.568 6.854 8.316 9.964 11.813 45 - 2.327 3.106 4.002 5.030 6.201 7.528 9.023 10.700 50 - - 2.736 3.555 4.487 5.543 6.737 8.080 9.587 55 - - 2.356 3.100 3.936 4.879 5.940 7.133 8.470 60 - - - 2.632 3.375 4.205 5.135 6.178 7.346

30 1.359 1.588 1.799 1.993 2.168 2.323 2.459 2.574 2.668 35 1.374 1.632 1.872 2.092 2.291 2.471 2.629 2.765 2.879 40 1.372 1.663 1.933 2.182 2.410 2.617 2.800 2.961 3.098 45 - 1.676 1.981 2.263 2.522 2.759 2.971 3.159 3.322 50 - - 2.013 2.331 2.625 2.895 3.139 3.358 3.550 55 - - 2.028 2.385 2.717 3.023 3.302 3.555 3.779 60 - - - 2.422 2.795 3.140 3.458 3.747 4.007

30 3.23 3.48 3.78 4.08 4.38 4.65 4.87 5.00 5.03 35 3.30 3.56 3.87 4.20 4.52 4.81 5.06 5.22 5.28 40 3.35 3.64 3.97 4.33 4.69 5.02 5.30 5.51 5.62 45 - 3.69 4.06 4.46 4.86 5.24 5.57 5.84 6.00 50 - - 4.13 4.58 5.04 5.47 5.87 6.19 6.43 55 - - 4.15 4.66 5.19 5.69 6.16 6.56 6.87 60 - - - 4.69 5.29 5.88 6.43 6.92 7.32

30 58 78 102 131 165 205 252 306 370 35 55 75 99 127 160 199 245 298 360 40 52 72 95 123 155 194 239 291 351 45 - 68 91 119 151 188 232 283 341 50 - - 87 114 145 182 225 275 332 55 - - 81 108 139 175 218 266 322 60 - - - 102 133 168 210 257 312

30 1.79 2.03 2.33 2.67 3.06 3.51 4.02 4.61 5.27 35 1.58 1.79 2.04 2.33 2.66 3.04 3.46 3.94 4.49 40 1.40 1.58 1.79 2.04 2.31 2.62 2.97 3.37 3.81 45 - 1.39 1.57 1.77 1.99 2.25 2.53 2.86 3.22 50 - - 1.36 1.53 1.71 1.91 2.15 2.41 2.70 55 - - 1.16 1.30 1.45 1.61 1.80 2.01 2.24 60 - - - 1.09 1.21 1.34 1.49 1.65 1.83

MPZ061-4

Cooling capacity 5.030 WPower input 2.522 WCurrent consumption 4.86 AMass fl ow 151 kg/hC.O.P. 1.99

Sound power level 68 dB(A)

With accoustic hood dB(A)

Page 18: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and
Page 19: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Hd

D

Hs

H

P

Hp

S

W2

L1

L2

W1

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

MPZ068-4Reciprocating compressorR404A / R507A380-400V/3/50Hz - 460V/3/60Hz

General

Model numbers / on compressor nameplate MPZ068A4LB2A

Code number for single pack 120F0051

Code number for industrial pack 120F0061

Application

Application MBP

Frequency 50 Hz 60 Hz

Evaporating temperature range -30°C / +10°C -30°C / +10°C

Condensing temperature range +30°C / +60°C +30°C / +60°C

Voltage range 360 - 440V 414 - 506V

Cooling requirements

Suction gas cooling normally suffi cient

Motor

Nominal voltage 380-400 V 460V

Voltage range 360 - 440V 414 - 506V

Winding resistance (between phases) +/- 7% at 25°C 8.6 Ω

Maximum Continuous Current (MCC) 9 A

Locked Rotor Amp (LRA) 38.1 A

Motor protection Internal line break

Design

Displacement 67.9 cm3/rev

Oil quantity (type) 1.1 litre - POE - 160Z

Maximum refrigerant charge 2.5 kg

Net weight 27 kg

Dimensions

Height H 348 mm

Hs 346 mm

Hd 109 mm

Hp 152 mm

Length L1 234 mm

L2 190 mm

W1 243 mm

W2 190 mm

Suction connector location/I.D. | angle S 3/4” 90°

material | comment Copper | Rubber plug

Discharge connector location/I.D. | angle D 1/2“ 90°

material | comment Copper | Rubber plug

Process connector location/I.D. | angle P 3/8“ 90°

material | comment Copper | Rubber plug

Drawing number 85 01 040 b

FRCC.ED.MPZ068-4.Pr1.02

Page 20: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Superheat = 10 K R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at: to = -10, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

FRCC.ED.MPZ068-4.Pr1.02

30 2.571 3.443 4.504 5.774 7.273 9.019 11.029 13.320 15.895 35 2.275 3.086 4.065 5.232 6.606 8.207 10.054 12.164 14.546 40 1.987 2.740 3.639 4.706 5.959 7.419 9.106 11.039 13.229 45 1.703 2.399 3.222 4.191 5.327 6.649 8.179 9.938 11.940 50 1.418 2.059 2.808 3.682 4.703 5.890 7.267 8.854 10.672 55 - 1.715 2.390 3.172 4.081 5.137 6.363 7.783 9.419 60 - 1.364 1.965 2.656 3.454 4.381 5.460 6.716 8.175

30 1.563 1.824 2.072 2.308 2.529 2.734 2.921 3.090 3.237 35 1.584 1.871 2.146 2.407 2.653 2.882 3.093 3.284 3.455 40 1.595 1.912 2.216 2.505 2.779 3.036 3.273 3.491 3.686 45 1.592 1.942 2.278 2.600 2.905 3.192 3.459 3.706 3.931 50 1.573 1.959 2.331 2.688 3.027 3.348 3.649 3.928 4.184 55 - 1.962 2.372 2.767 3.144 3.502 3.839 4.154 4.446 60 - 1.947 2.399 2.835 3.253 3.651 4.027 4.382 4.712

30 3.53 3.83 4.16 4.51 4.86 5.18 5.44 5.64 5.73 35 3.59 3.92 4.29 4.68 5.06 5.41 5.71 5.94 6.07 40 3.63 4.00 4.41 4.84 5.27 5.66 6.01 6.28 6.46 45 3.63 4.05 4.52 5.00 5.48 5.93 6.33 6.66 6.89 50 3.59 4.08 4.60 5.15 5.70 6.21 6.68 7.07 7.37 55 - 4.05 4.66 5.28 5.90 6.49 7.03 7.51 7.88 60 - 3.99 4.68 5.38 6.09 6.77 7.40 7.95 8.42

30 80 106 135 168 207 251 301 357 418 35 77 102 130 163 201 244 292 346 405 40 73 98 126 158 195 236 283 335 393 45 68 93 121 153 189 229 275 325 381 50 63 88 116 148 183 222 267 316 369 55 - 83 111 142 177 215 258 306 359 60 - 77 105 136 170 208 250 297 348

30 1.64 1.89 2.17 2.50 2.88 3.30 3.78 4.31 4.91 35 1.44 1.65 1.89 2.17 2.49 2.85 3.25 3.70 4.21 40 1.25 1.43 1.64 1.88 2.14 2.44 2.78 3.16 3.59 45 1.07 1.24 1.41 1.61 1.83 2.08 2.36 2.68 3.04 50 0.90 1.05 1.20 1.37 1.55 1.76 1.99 2.25 2.55 55 - 0.87 1.01 1.15 1.30 1.47 1.66 1.87 2.12 60 - 0.70 0.82 0.94 1.06 1.20 1.36 1.53 1.74

MPZ068-4

Cooling capacity 5.327 WPower input 2.905 WCurrent consumption 5.48 AMass fl ow 189 kg/hC.O.P. 1.83

Sound power level 68 dB(A)

With accoustic hood dB(A)

Page 21: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Performance data at 50 Hz, EN 12900 rating conditions, Suction temp. = 20 °C R404A

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Cond. temp. in °C (tc)

Evaporating temperature in °C (to)

-30 -25 -20 -15 -10 -5 0 5 10

Cooling capacity in W

Power input in W

Current consumption in A

Mass fl ow in kg/h

Coeffi cient of performance (C.O.P.)

Nominal performance at : to = -10°C, tc = 45 °C

Maximum HP switch setting 27.7 bar(g)

Minimum LP switch setting 0.2 bar(g)

LP pump down setting 0.9 bar(g)

Pressure switch settings

Sound power data

All performance data +/- 5%

FRCC.ED.MPZ068-4.Pr1.02

30 2.811 3.714 4.796 6.072 7.557 9.267 11.216 13.420 15.895 35 2.530 3.379 4.384 5.561 6.923 8.488 10.270 12.284 14.546 40 2.256 3.054 3.985 5.065 6.308 7.732 9.349 11.177 13.229 45 - 2.731 3.592 4.579 5.707 6.992 8.449 10.093 11.940 50 - - 3.200 4.098 5.114 6.264 7.563 9.027 10.672 55 - - 2.803 3.614 4.522 5.540 6.686 7.974 9.419 60 - - - 3.123 3.925 4.816 5.811 6.925 8.175

30 1.563 1.824 2.072 2.308 2.529 2.734 2.921 3.090 3.237 35 1.584 1.871 2.146 2.407 2.653 2.882 3.093 3.284 3.455 40 1.595 1.912 2.216 2.505 2.779 3.036 3.273 3.491 3.686 45 - 1.942 2.278 2.600 2.905 3.192 3.459 3.706 3.931 50 - - 2.331 2.688 3.027 3.348 3.649 3.928 4.184 55 - - 2.372 2.767 3.144 3.502 3.839 4.154 4.446 60 - - - 2.835 3.253 3.651 4.027 4.382 4.712

30 3.53 3.83 4.16 4.51 4.86 5.18 5.44 5.64 5.73 35 3.59 3.92 4.29 4.68 5.06 5.41 5.71 5.94 6.07 40 3.63 4.00 4.41 4.84 5.27 5.66 6.01 6.28 6.46 45 - 4.05 4.52 5.00 5.48 5.93 6.33 6.66 6.89 50 - - 4.60 5.15 5.70 6.21 6.68 7.07 7.37 55 - - 4.66 5.28 5.90 6.49 7.03 7.51 7.88 60 - - - 5.38 6.09 6.77 7.40 7.95 8.42

30 68 90 117 149 188 233 285 347 418 35 64 87 113 145 182 225 276 336 405 40 61 83 110 140 176 219 268 326 393 45 - 80 106 136 171 212 260 316 381 50 - - 101 131 165 206 252 307 369 55 - - 97 126 160 199 245 298 359 60 - - - 121 154 193 237 289 348

30 1.80 2.04 2.31 2.63 2.99 3.39 3.84 4.34 4.91 35 1.60 1.81 2.04 2.31 2.61 2.94 3.32 3.74 4.21 40 1.41 1.60 1.80 2.02 2.27 2.55 2.86 3.20 3.59 45 - 1.41 1.58 1.76 1.96 2.19 2.44 2.72 3.04 50 - - 1.37 1.52 1.69 1.87 2.07 2.30 2.55 55 - - 1.18 1.31 1.44 1.58 1.74 1.92 2.12 60 - - - 1.10 1.21 1.32 1.44 1.58 1.74

MPZ068-4

Cooling capacity 5.707 WPower input 2.905 WCurrent consumption 5.48 AMass fl ow 171 kg/hC.O.P. 1.96

Sound power level 68 dB(A)

With accoustic hood dB(A)

Page 22: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and
Page 23: MPZ Reciprocating compressors - Frigocommerce · 2012-10-14 · Hd D Hs H P Hp S W2 L1 L2 W1 Danfoss can accept no responsibility for possible errors in catalogues, brochures and

Controls for Commercial Refrigeration

Controls forIndustrial Refrigeration

Industrial Automation

Household Compressors Commercial Compressors ThermostatsSub-Assemblies

Electronic Controls & Sensors

We are off ering a single source for one of the widest ranges of innovative refrigeration

and air conditioning components and systems in the world. And, we back technical

solutions with business solution to help your company reduce costs,

streamline processes and achieve your business goals.

Danfoss A/S • www.danfoss.com

FRCC.ED.MPZ Produced by Danfoss CC- DSS - 09/2006

The Danfoss product range for therefrigeration and air conditioning industryDanfoss Refrigeration & Air Conditioning is

a worldwide manufacturer with a leading

position in industrial, commercial and

supermarket refrigeration as well as air

conditioning and climate solutions.

We focus on our core business of making

quality products, components and systems

that enhance performance and reduce

total life cycle costs – the key to major

savings.


Recommended