+ All Categories
Home > Documents > MRI Mk3 Issue 1 - Home - P&B -- P&B · MRI (Mk3) Technical Manual P&B Engineering 20/7/99 Page 0...

MRI Mk3 Issue 1 - Home - P&B -- P&B · MRI (Mk3) Technical Manual P&B Engineering 20/7/99 Page 0...

Date post: 22-Jul-2018
Category:
Upload: phungliem
View: 222 times
Download: 1 times
Share this document with a friend
67
MRI (Mk3) Technical Manual P&B Engineering 20/7/99 Page 0 Issue 1 MRI (Mk3) Digital Overcurrent & Earth Fault Relay P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG Tel: 0161 230 6363 Fax: 0161 230 6464 Internet Address http://www.pbeng.co.uk E-mail [email protected]
Transcript

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 0 Issue 1

MRI (Mk3) Digital Overcurrent & Earth Fault Relay

P&B Engineering

Belle Vue Works

Boundary Street

Manchester

M12 5NG

Tel: 0161 230 6363

Fax: 0161 230 6464

Internet Address http://www.pbeng.co.uk

E-mail [email protected]

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page ii Issue 1

Contents

1. INTRODUCTION. .............................................................................................................................................................1

2. APPLICATION. .................................................................................................................................................................2

3. FEATURES AND CHARACTERISTICS........................................................................................................................3

4. DESIGN...............................................................................................................................................................................4

4.1. CONNECTIONS. ...............................................................................................................................................................4

4.1.1. Analogue input circuits...........................................................................................................................................8

4.1.2. Output relays. .........................................................................................................................................................8

4.1.3. Remote data communication. .................................................................................................................................9

4.2. FRONT PANEL. ................................................................................................................................................................9

4.2.1. Display....................................................................................................................................................................9

4.2.2. LED Indicators. ....................................................................................................................................................10

4.2.3. Push Buttons.........................................................................................................................................................11

4.3. CODE JUMPERS.............................................................................................................................................................11

4.3.1. Password Programming. ......................................................................................................................................12

4.3.2. Reset Function. .....................................................................................................................................................12

5. WORKING PRINCIPLES. .............................................................................................................................................13

5.1. ANALOGUE CIRCUITS....................................................................................................................................................13

5.2. DIGITAL CIRCUITS. .......................................................................................................................................................13

5.3. POWER SUPPLY.............................................................................................................................................................13

5.4. PHASE FAULT DIRECTIONAL FEATURE (OPTIONAL). ......................................................................................................14

5.5. EARTH FAULT DIRECTIONAL FEATURE (OPTIONAL). ......................................................................................................15

5.5.1. Earth fault direction feature for isolated or compensated earthed networks. ......................................................15 5.5.1.1. Isolated Systems. ...............................................................................................................................................................15

5.5.1.2. Compensated System.........................................................................................................................................................17

5.5.2.1. Solidly Earthed System. ....................................................................................................................................................18

5.5.2.2. Resistive Earthed System. .................................................................................................................................................19

5.6. REQUIREMENTS FOR THE MAIN CURRENT TRANSFORMERS. .........................................................................................20

5.7. BLOCKING INPUT. .........................................................................................................................................................20

5.8. RESET INPUT. ...............................................................................................................................................................20

5.9. RESET DELAY & DWELL TIME......................................................................................................................................21

5.9.1. Reset Delay...........................................................................................................................................................21

5.9.2. Dwell Time............................................................................................................................................................21

5.10. CIRCUIT BREAKER FAILURE PROTECTION (TCBFP). ......................................................................................................21

5.11. DISPLAY OF PICK-UP EVENT........................................................................................................................................21

5.12. DISPLAY OF MEASURING VALUES AS PRIMARY QUANTITIES (IPRIM PHASE). ..................................................................21

5.13. DISPLAY OF EARTH CURRENT AS PRIMARY QUANTITY (IPRIM EARTH). ........................................................................22

5.14. DISPLAY OF RESIDUAL VOLTAGE UE AS PRIMARY QUANTITY (UPRIM/USEC).................................................................22

6. OPERATION AND SETTING........................................................................................................................................23

6.1. LAYOUT OF THE CONTROL ELEMENTS. ..........................................................................................................................23

6.2. RELAY SETTING PRINCIPLES. .........................................................................................................................................23

6.2.1. Password protected parameter adjustment. .........................................................................................................24

6.3. SETTING PROCEDURE. ...................................................................................................................................................25

6.3.1. Starting current for phase overcurrent relay (I>). ...............................................................................................25

6.3.2. Time current Characteristic for phase overcurrent relay (CHAR I>)..................................................................25

6.3.3. Tripping time delay or time multiplier for phase overcurrent relay (tI>). ...........................................................25

6.3.4. Current setting for high set stage of phase overcurrent relay (I>>)....................................................................26

6.3.5. Tripping time delay for high set stage of phase overcurrent relay (tI>>). ..........................................................26

6.3.6. Starting current for earth fault relay (IE>). .........................................................................................................26

6.3.7. Time Current characteristic for earth fault relay (CHAR IE). .............................................................................26

6.3.8. Tripping time delay or time multiplier for earth fault relay (tIE>). .....................................................................26

6.3.9. Current setting for high set stage of earth fault relay (IE>>)..............................................................................27

6.3.10. Tripping time delay for high set stage of earth fault relay (tIE>>). ..................................................................27

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page iii Issue 1

6.3.11. Earthing type. .....................................................................................................................................................27 6.3.11.1. COS/SIN Measurement. ..................................................................................................................................................27

6.3.11.2. SOLI/RES Setting. ..........................................................................................................................................................27

6.3.12. Residual Earth Fault Voltage (VE). ...................................................................................................................27

6.3.13. Residual Earth Fault Voltage Measurement Method. ........................................................................................27

6.3.14. Earth Fault Response. ........................................................................................................................................27

6.3.15. Nominal frequency..............................................................................................................................................27

6.3.16. Assignments Of The Blocking Inputs. ................................................................................................................28

6.3.17. Blocking Of Protection Functions. ....................................................................................................................28

6.3.18. Programming Of Output Relays. .......................................................................................................................29

6.3.19. Parameter Switch. ..............................................................................................................................................31

6.3.20. Fault Recorder. .................................................................................................................................................31 6.3.20.1. Number of the fault recordings........................................................................................................................................31

6.3.20.2. Adjustment of trigger occurrences...................................................................................................................................32

6.3.20.3. Pre-trigger time (Tpre) ......................................................................................................................................................32

6.3.21. Adjustment of the clock.......................................................................................................................................32

6.3.22. Communication Settings. ....................................................................................................................................32 6.3.22.1. Slave Address. .................................................................................................................................................................32

6.3.22.2. Baud Rate. .......................................................................................................................................................................32

6.3.22.3. Parity. ..............................................................................................................................................................................33

6.3.23. Reset Setting (For Inverse Time Overcurrent Function). ...................................................................................33

6.3.24. Reset Setting (For Inverse Time Earth Fault Function). ....................................................................................33

6.3.25. Dwell Time..........................................................................................................................................................33

6.3.26. Relay Characteristic Angle (RCA)......................................................................................................................33

6.3.27. Pick Up Value For Residual Voltage UE. ...........................................................................................................33

6.3.28. Setting Summary.................................................................................................................................................34

6.4. INDICATION OF MEASURED VALUES AND FAULT DATA. .................................................................................................36

6.4.1. Indication of measured values..............................................................................................................................36 6.4.1.1. Measured Values as a Primary Value. ...............................................................................................................................37

6.4.2. Indication of fault data. ........................................................................................................................................38

6.4.3. Fault Recording....................................................................................................................................................39

6.5. TEST TRIP. ....................................................................................................................................................................40

6.6. RESET. ..........................................................................................................................................................................40

6.6.1. Hand reset. ...........................................................................................................................................................40

6.6.2. Reset input. ...........................................................................................................................................................40

6.7. SETTING VALUE CALCULATION. ....................................................................................................................................41

6.7.1. Low set stage. .......................................................................................................................................................41

6.7.2. High set stage. ......................................................................................................................................................41

6.7.3. Characteristic curve. ............................................................................................................................................41

6.7.4. Low set stage time multiplier/time delay. .............................................................................................................41

6.7.5. High set stage time delay......................................................................................................................................41

7. RELAY CASE. .................................................................................................................................................................41

7.1. INDIVIDUAL CASE. ........................................................................................................................................................41

7.2. RACK MOUNTING. .........................................................................................................................................................42

7.3. TERMINAL CONNECTIONS. ............................................................................................................................................42

8. TEST AND MAINTENANCE.........................................................................................................................................43

8.1. POWER ON....................................................................................................................................................................43

8.2. TESTING THE OUTPUT RELAYS AND LEDS. ...................................................................................................................43

8.3. CHECKING THE SET VALUES..........................................................................................................................................43

8.4. SECONDARY INJECTION TEST .......................................................................................................................................44

8.4.1. Test Equipment .....................................................................................................................................................44

8.4.3. Checking the input circuits and measured values ................................................................................................44

8.4.4. Checking the operating and resetting values of the relay. ...................................................................................45

8.4.5. Checking the relay operating time........................................................................................................................45

8.4.6. Checking the high set element of the relay. ..........................................................................................................45

8.4.7. Example of a test circuit for MRI relay with directional feature..........................................................................46

8.4.8. Test circuit earth fault directional feature............................................................................................................48

8.4.9. Checking the external blocking and reset functions. ............................................................................................49

8.4.10. Test of the CB failure protection. .......................................................................................................................49

8.5. PRIMARY INJECTION TEST. ............................................................................................................................................49

8.6. MAINTENANCE. ............................................................................................................................................................50

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page iv Issue 1

9. TECHNICAL DATA........................................................................................................................................................51

9.1 MEASURING INPUT CIRCUITS.........................................................................................................................................51

9.2 AUXILIARY POWER SUPPLY............................................................................................................................................51

9.3 COMMON DATA .............................................................................................................................................................51

9.4 SETTING RANGES AND STEPS..........................................................................................................................................52

9.4.1 Definite time phase overcurrent relay ...................................................................................................................52

9.4.2 Inverse time phase overcurrent relay ....................................................................................................................53

9.4.3 Direction unit for phase overcurrent relay............................................................................................................54

9.4.4 Direction unit for earth fault relay ........................................................................................................................54

9.5. INVERSE TIME CHARACTERISTICS .................................................................................................................................55

9.5.1 Inverse time Equations ..........................................................................................................................................56

9.6 OUTPUT CONTACT RATINGS ...........................................................................................................................................57

9.7 TYPE TESTS ...................................................................................................................................................................58

9.8 HOUSING .......................................................................................................................................................................61

9.9 TERMINAL CONNECTION DETAILS .................................................................................................................................62

10. ORDER FORM ..............................................................................................................................................................63

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 1 Issue 1

1. Introduction.

The application of powerful microprocessors opens a new chapter for power system protective

relaying. The digital processing of measured values and the ability to perform complex arithmetic and

logic operations, give digital protection relays significant performance and flexibility improvements

over their traditional analogue counterparts. Additional advantages - very small power consumption,

adaptability, self-supervision, fault diagnosis through fault data recording, smaller physical

construction and selectable relay characteristics - all combine to allow the implementation of accurate

and highly reliable protection schemes at a significantly reduced financial burden.

The development of microprocessor based protective relays and their introduction into the market has

been stimulated by the recent trend to replace analogue with digital equipment. This modern trend has

prompted the development of a new P&B protective relay family - the MR relay series. This

comprehensive family of protection relays can satisfy the demands of even the most complex

protection schemes:

MRI - Overcurrent Relay (Independent time/I.D.M.T + earth + directional facilities)

MRI-V - Voltage Dependent Overcurrent Relay

MSP - Voltage or Overcurrent (I.D.M.T + earth + directional) Relay

MREF - Restricted Earth Fault Relay

MRAR - Auto-Reclosing Relay

MRMF - Mains Failure Relay

MRVT - Voltage Protection

MRFT - Frequency Protection

MROS - Vector Surge

MRNS - Negative Sequence Relay

MRRP - Power Relay

MRCS - Check Synchronising Relay

MRFF - Field Failure Relay

MRDG - Differential Relay

The superiority of digital protective relaying over traditional analogue devices, as embodied by the

MR relay family, is summarised by the following features:

•••• Integration of many protective functions in a single compact case

•••• High accuracy owing to digital processing

•••• Digital relay setting with very wide setting ranges and fine setting steps

•••• Comfortable setting procedure through extensive human - relay dialogue

•••• Measured values and fault data indication by means of alpha-numeric display

•••• Data exchange with DCS/SCADA by means of RS485

•••• Operational reliability through self-supervision

The digital overcurrent and earth fault relay MRI, was designed as a universal overcurrent relay for

applications in medium voltage networks. A similar, but simplified version, the MIRI, with reduced

functions and without display, is also available. Similarly for protection against undervoltage,

overvoltage and neutral voltage displacement, a reduced function non-display relay, the MIRV is

available. To complement the MR series, a range of Auxiliary, Timing and Tripping devices are also

available. The MSP range of relays were added to create a new series of single pole, competitive

overcurrent or voltage protection relays. They have the added feature of a large LCD Display,

enabling greater display of data.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 2 Issue 1

2. Application.

The MRI is a universal digital multifunctional relay used for overcurrent and/or earth fault protection

in medium voltage networks with ring mains, parallel feeders or doubly infed lines. The protective

functions of the MRI are summarised as follows:

• Selectable protective functions between :

- Definite time overcurrent relay

- Inverse time overcurrent relay

• Inverse definite minimum time (IDMT) overcurrent relay with the following

selectable characteristics in accordance with BS 142 and IEC 60255-3:

- Normal Inverse

- Very Inverse

- Extremely Inverse

- RI-Inverse

- Long Time Inverse

• High set overcurrent unit with instantaneous or definite time function

• Two stage overcurrent relay both for phase and earth faults

• Built in direction unit for application to ring main or parallel feeders with adjustable relay

characteristic angle (Optional)

• Built in earth fault direction unit for application to power system networks with

solid/resistive neutral earthing or isolated/arc suppressing coil (Peterson Coil) neutral

earthing. (Optional)

• Two stage (Low and High Set) earth fault protection with definite or inverse time

characteristics

• Reset time selectable for inverse time characteristics ("pecking faults")

Furthermore, the MRI relay can be employed as back-up protection for distance and differential

protective relays.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 3 Issue 1

3. Features and characteristics.

• Complete digital processing of the sampled measured values

• Digital filtering of measured values using discrete fourier analysis to suppress high

frequency harmonics and d.c component induced by faults or system operations

• Extremely wide setting ranges with fine setting steps

• Two Parameter Sets

• Unauthorised user access control through password protection

• User defined password

• Continuous self-supervision of software and hardware

• Outstanding design flexibility for easy selection of appropriate operational scheme

for numerous applications

• Numerical display of setting values, actual measured values and their

active/reactive components and memorised fault data etc.

• Display of measuring values as primary quantities

• Blocking e.g. of high set element (e.g. for selective fault detection through

downstream overcurrent protection units after unsuccessful Auto Reclose)

• Storage of trip values and switching off time (tCBFP) of 5 fault occurrences

• Recording of up to eight fault occurrences with time stamp

• Display of Date and Time

• Serial data communication facilities via RS485 interface with NETWORK GOLD

or Modbus RTU (Note For Modbus no fault recording is available)

• Wide voltage range for DC or AC power supply

• Withdrawable modules with automatic short circuit of C.T. inputs

• Circuit Breaker Failure Protection

• Programmable Output Relays

• Suppression of indication after an activation

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 4 Issue 1

4. Design.

4.1. Connections.

Application Diagram; Overcurrent and Earth Fault Directional

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

1 4

I3

M R I- IE DT y p ic a l E a r th in g S h o w n

5 4 5 55 3E x te r n a l R e s e t B lo c k in g In p u t

L N L

R E L A Y 13 3

3 1

2 9

3 2

3 03 4

4 85 2

5 0

4 5

4 3

4 1

4 4

4 24 6

4 0

3 8

3 6

3 7

3 53 9

+

7 9 1 0

G n d-

4 75 1

4 9

S E L F S U P E R V IS IO N

R E L A Y 4

R E L A Y 3

R E L A Y 2

R S 4 8 5

1 9

I2

1 5

1 7

I1

V 1

N

V 2

V 3

2 1

2 2

2 3

2 4

2 5

2 6

2 7

2 8

L 1

L 2

L 3

I1

I2

I3

IE

S 2P 2

P 1

S 1

A lte rn a t iv eE a r th in g

Application Diagram; Overcurrent and Only Earth Fault Directional

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

M R I-I-E X

T yp ica l E arth in g S h o w n

5 4 5553E x te rna l R e s e t B lo c king Inp ut

L N L

33

31

29

32

3034

4852

50

45

43

41

44

4246

40

38

36

37

3539

4751

49

S E L F S U P E R V IS IO N

+

7 9 10

G n d-R S 4 85

L 1

L 2

L 3

14

I319

I2

15

17

I1

V 1

N

V 2

V 3

Alte rn a tiveE a rth in g

21

22

23

24

25

26

I1

I2

I3

S 2P 2

P 1

S 1

IE

27

28

C B C T

R E L AY 1

R E L AY 4

R E L AY 3

R E L AY 2

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 5 Issue 1

Application Diagram; Overcurrent and Earth Fault

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

M R I-IET yp ic a l E a rth in g S h o w n

5 4 555 3

E x te rna l R e s e t B lo c k in g Inp u t

L N L

3 3

3 1

2 9

3 2

3 03 4

4 85 2

5 0

4 5

4 3

4 1

4 4

4 24 6

4 0

3 8

3 6

3 7

3 53 9

+

7 9 1 0

G n d-

4751

49

S E L F S U P E R V IS IO N

R S 4 85

21

22

2 3

2 4

2 5

2 6

2 7

2 8

L 1

L 2

L 3

I1

I2

I3

IE

S 2P 2

P 1

S 1

R E L A Y 1

R E L A Y 4

R E L A Y 3

R E L A Y 2

Application Diagram; Overcurrent and Earth Fault -Special Export Version

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

M R I-IE KT yp ic a l E a rth in g S h o w n

54 5 55 3

E x te rn a l R e s e t B lo c k in g In p u t

L N L

3 3

3 1

2 9

3 2

3 03 4

4 85 2

5 0

4 5

4 3

4 1

4 4

4 24 6

4 0

3 8

3 6

3 7

3 53 9

+

7 9 1 0

G n d-

4751

49

S E L F S U P E R V IS IO N

R S 4 85

2 1

2 2

23

24

25

26

27

28

L 1

L 2

L 3

I1

I2

I3

IE

S 2P 2

P 1

S 1

F O R T R IP /A L A R M F U N C T IO N S , R E F E R T O 4 .1 .2 .

R E L A Y 1

R E L A Y 4

R E L A Y 3

R E L A Y 2

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 6 Issue 1

Application Diagram; Earth Fault Directional

T y p ic a l e a r th in g s h o w n

A lte rn a tiv eE a r th in g

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

M R I-E X

5 4 5 55 3E x te rn a l R e s e t B lo c k in g In p u t

L N L

3 3

3 1

2 9

3 2

3 03 4

4 85 2

5 0

+

7 9 1 0

G n d-

4 75 1

4 9

S E L F S U P E R V IS IO N

R S 4 8 5

L 1

1 9

1 4

1 5

1 7

L 3

N

L 1

L 2

L 2

L 3

IE

2 7

2 8

C B C T

M R I-E D

R E L A Y 1

R E L A Y 4

Application Diagram; Earth Fault

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

M R I-E

5 4 5 55 3E x te rn a l R e s e t B lo c k in g In p u t

L N L

3 3

3 1

2 9

3 2

3 03 4

4 85 2

5 0

+

7 9 1 0

G n d-

4 75 1

4 9

S E L F S U P E R V IS IO N

R S 4 8 5

T y p ic a l e a r th in g s h o w n

L 1

L 2

L 3

IE

2 7

2 8

C B C T

R E L A Y 1

R E L A Y 4

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 7 Issue 1

Application Diagram; Overcurrent

PO W E R

SU PPL Y

1 2 C AS E

S upply

M R I-I

T yp ica l E arth ing Sh ow n

54 5553Externa l R esetB lo cking Inp ut

L N L

33

31

29

32

3034

4852

50

45

43

41

44

4246

40

38

36

37

3539

+

7 9 10

G nd-

S ELF S U PE R V IS IO N

R S 485

21

22

23

24

25

26

L 1

L2

L3

I1

I2

I3

S 2P 2

P 1

S 1

FO R TR IP /A L AR M FU N C TIO N S , R E FE R TO 4.1 .2.

R E L AY 1

R E L AY 4

R E L AY 3

R E L AY 2

Application Diagram; Overcurrent Directional

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

1 4

I3

M R I- IDT y p ic a l E a r th in g S h o w n

5 4 5 55 3E x te rn a l R e s e t B lo c k in g In p u t

L N L

3 3

3 1

2 9

3 2

3 03 4

4 85 2

5 0

4 5

4 3

4 1

4 4

4 24 6

4 0

3 8

3 6

3 7

3 53 9

+

7 9 1 0

G n d-

S E L F S U P E R V IS IO N

R S 4 8 5

1 9

I2

1 5

1 7

I1

V 1

N

V 2

V 3

2 1

2 2

2 3

2 4

2 5

2 6

L 1

L 2

L 3

I1

I2

I3

S 2P 2

P 1

S 1

A lte rn a t i v eE a r th in g

R E L A Y 1

R E L A Y 4

R E L A Y 3

R E L A Y 2

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 8 Issue 1

Application Diagram; Overcurrent Directional

Alternative Application Diagram using a 'v' connected voltage transformer 2 phase input.

P O W E R

S U P P L Y

1 2 C A S E

S u p p ly

1 4

I3

M R I- IDT y p ic a l E a r th in g S h o w n

5 4 5 55 3E x te r n a l R e s e t B lo c k in g In p u t

L N L

3 3

3 1

2 9

3 2

3 03 4

4 85 2

5 0

4 5

4 3

4 1

4 4

4 24 6

4 0

3 8

3 6

3 7

3 53 9

+

7 9 1 0

G n d-

S E L F S U P E R V IS IO N

R S 4 8 5

1 9

I2

1 5

1 7

I1

V 1

N

V 2

V 3

2 1

2 2

2 3

2 4

2 5

2 6

L 1

L 2

L 3

I1

I2

I3

S 2P 2

P 1

S 1

N u e tra l N o tC o n n e c t e d

R E L A Y 1

R E L A Y 4

R E L A Y 3

R E L A Y 2

4.1.1. Analogue input circuits.

The constantly monitored measuring values are galvanically decoupled, filtered and finally fed to the

analogue/digital converter. The protection unit receives these analogue input signals of the phase

currents I1, I2, I3 and residual current IE, and phase voltages V1, V2, V3 with a star point, each via

separate input transformers.

The residual voltage Ve, required for MRI units with earth fault directional facility, is formed

internally in the secondary circuit of the voltage transformers. Where only the earth fault directional

facility is required (ie phase fault directional facility unused) the residual voltage from an existing

open delta winding may be directly connected across L1 & N.

4.1.2. Output relays.

The MRI has five output relays, with single or dual pole change-over contacts as detailed in the

previous diagrams. With the exception of Relay 5, which is used only for self supervision output and

which is normally energised, the other Relays (1 to 4) are programmable to the users specification

(see Section 6.3.18). The factory default settings are given in table shown in section 6.3.18.

In the alarm mode, alarm outputs operate upon energisation.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 9 Issue 1

4.1.3. Remote data communication.

As an option, the MRI may have an RS485 interface for remote data communication with a control

centre. The unit provides the following information:

• Measured phase fault current values

• Measured earth fault current values

• Status signals

• Self supervision alarm signal

• Actual measured current values

• Relay settings

• Phase fault signalling

• Earth fault signalling

There is a choice in the communication protocol of the MRI relay. Both Modbus RTU and

NETWORK GOLD is available. Unfortunately fault recording is not available in a relay with

Modbus RTU.

4.2. Front Panel.

The front panel of the MRI comprises the following operation and indication elements:

• Alphanumeric display (4 Digits)

• 5 push buttons for setting and other operations

• Up to 23 LEDs for measured value indication and setting

4.2.1. Display.

The measured and set values, and recorded fault data, are shown alphanumerically on the display. The

meaning of the displayed values is easily interpreted from the LED indicators on the front panel. See

Section 6.4. for more details.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 10 Issue 1

4.2.2. LED Indicators.

The LEDs to the left of the display indicate measuring or tripping values. The purpose of the

corresponding LED is identified by the adjacent inscription, (e.g. L2 for current in phase 2).

The full list of LEDs are as follows:-

LED Indicates

L1 Current Phase 1

L2 Current Phase 2

L3 Current Phase 3

E Earth Current

Date And Time

IP Active Component

IQ Reactive Component

Relay Characteristic Angle / Direction *

RS Serial Address

FR Fault Recording

P2 Parameter Switch

C.B. Circuit Breaker Fail Protection

I> Pickup Current For Phase Overcurrent

CHAR I> Time Current Characteristics for Phase O/C

tI> Tine Delay or Time Multiplier for Phase O/C

I>> Current Setting for High Set Element

tI>> Time Delay for High Set Element

IE> Pickup Current for Earth Fault Element

CHAR IE Time Current Characteristics for E/F

tIE> Time Delay or Time Multiplier for E/F

IE>> Current Setting for High Set Element of E/F

tIE>> Trip Delay for High Set Element of E/F

UE> Residual Voltage

* For forward direction this LED is illuminated GREEN, and

For reverse direction this LED is illuminated RED.

Up to ten LEDs support the setting menu selection. They are arranged at the characteristic points on

the setting curves. Upto five are for phase fault characteristic and upto five are for earth fault

characteristic. Each indicate the corresponding menu point selected.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 11 Issue 1

4.2.3. Push Buttons.

The front panel contains five push buttons used for setting, measuring and other user functions.

The individual setting and measuring values can be selected in turn by pressing the

<SELECT/RESET> push button. This button also resets the relay if pressed for approximately 3

seconds.

The <UP> and <DOWN> push buttons are for incrementing and decrementing any selected

parameter. Continuous pressing of these push buttons will cause the parameter to change at an

increased rate.

The <ENTER> push button is used to transfer the indicated value to the internal parameter memory.

An unintended or unauthorised change of the selected parameter can be avoided through the

password protection facility.

The <TRIP> push button is used to test the output relay circuits, both for tripping and signalling.

This operation is also password protected.

4.3. Code Jumpers.

Behind the front panel of the MRI are two code

jumpers used to preset the following functions:

•••• Password programming

•••• Reset functions

The following figure shows the position and

designation of the code jumpers.

Note. If you have a Surface Mount Board (with Wide

range power supplies) there will be two extra jumpers.

These jumpers are used to choose the input voltage for

the external reset and the blocking input. The two

jumpers should always be the same.

Jumper 4 – Input voltage upto 240V

Jumper 5 – Input voltage upto 110V

J3 J2 J1

Code Jumper ON

Code Jumper OFF

Front Board

Code Jumper

Pre Wide Range Post Wide RangePower Supply. Power Supply.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 12 Issue 1

4.3.1. Password Programming.

The MRI relay is normally delivered with the preset password "∧∧∧∧∧∧∧∧∧∧∧∧∧∧∧∧", it can be reprogrammed

using the removable code jumper J1. After power on and the pressing of any push button, the MRI

relay enquires for a new password with the text "PSW?" appearing on the display. A new password

is then entered by pressing a combination of <SELECT/RESET>, <UP>, <DOWN> or

<ENTER>, as chosen by the user. After the new password has been given, the relay module is

extracted from its case and code jumper J1 removed.

4.3.2. Reset Function.

Code jumper J3 - OFF

All output relays will be reset automatically after tripping, once the fault has been cleared.

Code jumper J3 - ON

All output relays remain activated and must be reset manually by pressing the <RESET> push

button, after the fault has been cleared.

Summarising the coding possibilities

Code jumper Function Code jumper Position Operation Mode

J1 Password OFF

ON

Normal position

Password programming

J3 Reset OFF

ON

Output relays will be reset

automatically.

Output relays will be reset

manually.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 13 Issue 1

5. Working Principles.

5.1. Analogue Circuits.

The incoming currents from the external current transformers are converted to internal signals in

proportion to the currents, via the internal input transducers and shunt resistors. The noise signals

caused by inductive and capacitive coupling are suppressed by an analogue RC filter circuit. The

analogue signals are fed to the A/D converter of the micro-processor and transformed to digital

signals through sample-hold circuits. The analogue signals are sampled with a sampling frequency

of 800 Hz, namely a sampling rate of 1.25 mS for every measured quantity.

In order to achieve a sensitive earth current measurement, an operational amplifier is connected to

the earth current input circuit before the analogue signal enters the A/D converter. The incoming

voltages from the external voltage transformers are fed to operational amplifiers through the input

transducers and RC filters. The analogue voltage signals are transformed into a logical binary signal,

which is used as a reference signal to detect fault direction. The residual voltage needed for earth

fault direction is formed internally from the secondary circuits of the input transducers.

5.2. Digital Circuits.

The essential component of the MRI relay is a powerful micro-controller. All of the operations,

from the analogue digital conversion to the relay trip decision, are carried out by the micro-

controller digitally. The relay program, located in EPROM, allows the CPU of the micro-controller

to calculate the three phase currents and earth fault current in order to detect a possible fault.

For the calculation of the current value, an efficient digital filter, based on the Fourier Analysis

(DFFT - Discrete Fast Fourier Transformation), is applied to suppress high frequency harmonics

and DC components caused by fault induced transients or other system disturbances. The actual

calculated current values are compared with the relay settings. When a current exceeds the starting

value the unit starts the corresponding time delay calculation. When the set time delay has elapsed, a

trip signal is given.

The relay setting values for all parameters are stored in EEPROM, so that the actual relay settings

cannot be lost, even in the event of auxiliary supply interruption. The micro-processor is supervised

through a built in "Watch-dog" timer. Should a failure occur the watch-dog timer resets the micro-

processor and gives an alarm signal via the self supervision output relay.

5.3. Power Supply.

A wide range auxiliary power supply is available:

Vaux = 16V to 360V DC

16V to 270V AC

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 14 Issue 1

5.4. Phase Fault Directional feature (optional). An integral directional element is available within the MRI-IED, MRI-ED, MRI-I-EX & MRI-ID

relays.

In order to achieve the reliable detection of fault current flow direction, the relay uses an internal

quadrature connection.

With this method;

the reference voltage for phase current I1 is taken from phase to phase voltage V23,

the reference voltage for phase current I2 is taken from phase to phase voltage V31,

the reference voltage for phase current I3 is taken from phase to phase voltage V12,

This method ensures that whilst the voltage may decrease on the faulted phase(s), the reference

voltage should still be available. Note that the CT & VT connections should be made as shown in

the appropriate application diagram.

The directional element analyses the relation between operating current and reference voltage, to

determine the fault direction. This is related to the relay characteristic angle (range 15° to 83°) as

selected by the user. Typically a relay characteristic angle of 45° is chosen for transformer feeders

and 30° for plain feeders as shown in Figure 5.4.1. This relates to a system characteristic angle of

45º or 60º respectively, due to the internal quadrature connection.

Fig. 5.4.1 Trip / No Trip region for directional element in the MRI (phase overcurrent)

The trip zone indicated by Figure 5.4.1 illustrates the operation for phase current I1 related to both

the phase voltage V1, and the directionalising element from voltage V23.

The operate zone is effectively bounded ±90° about the system characteristic angle for current levels

exceeding the set level, as detailed in 6.3.1 and 6.3.4.

The use of an efficient directional algorithm and high sensitivity voltage measurement, enables

accurate assessment of the phase angle, even for close three phase faults. In order to prevent

incorrect assessment, four consecutive direction measurements must occur before a trip operation

can be allowed.

The different time delays or time multipliers for forward and reverse direction, as detailed in 6.3.3

& 6.3.5, enables the user to achieve a high degree of system grading.

System characteristic angle 45°,generally used for transformer feeders,or feeders "earthed" in front of the relay

No tripRegion

V1

V23

V12V31

V3V2

Trip zone45° lead through

135° lag

V '23

45°

System characteristic angle 60°generally used for plain feeders,"earthed" behind the relay

V1

V23

V12V31

V3V2

Trip zone30° lead through150° lag

V '23

60°

No tripRegion

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 15 Issue 1

5.5. Earth fault directional feature (optional).

Within the MRI range, two versions of earth fault protection are available;

for application to:

Isolated or compensated earthed networks (5.5.1)

Solid or resistance earthed networks (5.5.2)

This selection must be made at the time of order.

5.5.1. Earth fault direction feature for isolated or compensated earthed networks.

5.5.1.1. Isolated Systems.

In an isolated system, although there is no direct connection between the system and earth, the

capacitance of cables and other equipment can effectively tie the system to earth. In the event of a

fault to earth, the disturbance causes a small capacitive current to flow which may be detected and

acted upon by the relay.

This residual current may be obtained by a Holmgreen connection of the line CT's. However, to

produce the required accuracy of measurement, a core balance CT should, in almost all cases, be

used.

In order to determine the fault direction a voltage reference is required. Usually, this is obtained

through the use of an additional broken delta winding on the Voltage Transformer. However, the

MRI range eliminates the need for this additional winding by forming the residual reference voltage

internally, from the three applied phase voltages. If this facility is employed, the applied voltages

must be obtained from either a 5 limb VT or 3 single phase VT's, and the measuring method

(6.3.13) should be set to "3PHA".

Where a broken delta winding is used, as shown in Figure 5.5.1.1(a), the measuring method (6.3.13)

should be set to "E-N".

Where a line VT is not available it is possible to use a secondary winding on the system earthing

transformer, as shown in Figures 5.5.1.1(b) & 5.5.1.1(c), and the measuring method (6.3.13) should

be set to "1:1".

15

14

MRI

a) Use of broken delta VT

15

14

MRIb) Use of earthing transformer

15

14

MRI

c) Use of generator/transformer earthing VT

G

Figure 5.5.1.1

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 16 Issue 1

Since the relay must determine the fault direction by evaluating a capacitive current, a SINE

function is employed. i.e;

A faulted line produces a 90° lagging current, whilst,

a non-faulted line would reflect a 90° leading current.

Figure 5.5.1.2 Trip / No Trip region for earth fault in an isolated system (SIN selection).

The trip zone indicated by Figure 5.5.1.2 illustrates the operation for the earth fault current Ie related

to the residual voltage Ve, for an isolated system.

The operate zone is determined by analysis of the capacitive component of the fault current for

magnitudes exceeding the set level, as outlined in 6.3.6 & 6.3.9.

Trip Region (Sin)

Ve

I e

(Faulted Line)

ReflectedFault Current

(Non-faulted Line)

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 17 Issue 1

5.5.1.2. Compensated System.

In a compensated earthed network the system is connected to earth via a reactance, matched to

balance the system capacitance. In the event of a fault to earth, the change in the balance of

capacitive current, between the phases, is compensated by the neutral earthing reactance.

Under these circumstances the relay must determine the direction of the fault by evaluating the

resistive current by using a COSINE function.

The residual current and voltage references are obtained as for an isolated system.

Figure 5.5.1.3 Trip/No Trip region for earth fault in a compensated system (COS selection).

The trip zone indicated by Figure 5.5.1.3 illustrates the operation for the earth fault current Ie related

to the residual voltage Ve, for an compensated system.

The operate zone is determined by analysis of the resistive component of the fault current for

magnitudes exceeding the set level, as outlined in 6.3.6 & 6.3.9.

Ve

I e

(Faulted Line)

ReflectedFault Current

(Non-faulted Line)

Trip Region (Cos)

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 18 Issue 1

5.5.2. Earth fault direction feature for solidly connected or resistive earthed networks.

The residual current may be obtained by a Holmgreen connection of the line CT's. However, a

core balance CT may be used for improved accuracy.

In order to determine the fault direction a voltage reference is required. Usually, this is obtained

through the use of an additional broken delta winding on the Voltage Transformer. However, the

MRI range eliminates the need for this additional winding by forming the residual reference voltage

internally, from the three applied phase voltages. If this facility is employed, the applied voltages

must be obtained from either a 5 limb VT or 3 single phase VT's. Alternatively a broken delta

winding may be used, as shown in Figure 5.5.1.1(a).

5.5.2.1. Solidly Earthed System.

In a solidly earthed system, the fault current will lag the remaining phase voltage Vr by

approximately 70°. However, the internally formed reference voltage Ve "seen" by the relay, will be

approximately 180° to the remaining phase voltage. Thus the relay has a characteristic phase angle

of -110°, as shown in Figure 5.5.2.1 (Soli).

Figure 5.5.2.1 Trip/No Trip region for earth fault in a solid system.

The operate zone is effectively bounded ±90° about the relay characteristic angle for current levels

exceeding the set level, as detailed in 6.3.6 and 6.3.9.

Vr

Trip Region (Soli)

-110°

Ve

Relay characteristic angle -110,

relay selected for solidearthed system.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 19 Issue 1

5.5.2.2. Resistive Earthed System.

In a resistive earthed system, the fault current will be approximately in phase with the residual

voltage Vr. As with a solidly earthed system, the internally formed reference voltage Ve "seen" by

the relay, will be approximately 180° to the voltage. Thus the relay has a characteristic phase angle

of 170°, as shown in Figure 5.5.2.2 (Resi).

Figure 5.5.2.2 Trip/No Trip region for earth fault in a resistive earthed system.

Vr

170°

Ve

Relay characteristic angle 170,relay selected for resistanceearthed system.

Trip Region (Resi)

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 20 Issue 1

5.6. Requirements for the main Current Transformers.

In order to ensure the correct operation of the MRI range of relays, protection class CT's must be

utilised. Instrument CT's are NOT a suitable alternative.

CT's should be chosen such that saturation, or loss of accuracy does not occur within the settings

and operation ranges of the relays. In the absence of known settings the following may be regarded

as an approximate guide.

Line CTs

For 1A secondary

CT class 5P20 or 10P20 2.5VA (Allowing for up to 1Ω of secondary lead resistance)

For 5A secondary

CT class 5P20 or 10P20 5VA (Allowing for up to 0.5Ω of secondary lead resistance)

Core Balance CTs

For solid and resistive earthed systems

CT Class 1.0/5P5, 2.5VA

For isolated/compensated systems where sensitive settings are required.

Special Core Balance CT Type Z, ratio 200mA/1.5mA for use with MRI-EX rated 1A.

Stabilising Resistor.

In the case where the earth fault input is supplied from the Holmgreen (residual) connection of 3

line CT's it may be necessary to fit an external stabilising resistor. Guildence on selecting a

suitable resistor is given in P&B Engineering Publication ref MR901.

NOTE.

with due regard to a suitable CT ratio and fault level capacity.

5.7. Blocking Input.

By applying a voltage within the auxiliary voltage operating range to terminals 55 - 54 ( terminal 54

is common to the RESET input ) the protection functions chosen by the user is blocked whilst the

voltage is applied, (see section 6.3.16).

5.8. Reset Input.

By applying a voltage within the auxiliary voltage operating range to terminals 53 - 54 ( terminal 54

is common to the BLOCKING input ) all output relays may be reset.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 21 Issue 1

5.9. Reset Delay & Dwell Time.

In order to provide better discrimination with Electromechanical relays two additional settings are

provided.

5.9.1. Reset Delay.

The reset delay delays the reset of the relay following a Flashing Fault (sometimes known as a

Pecking Fault) which simulates the time an electromechanical relay takes in order to “wind back” a

partially rotated Disk (IDMT). This may be selected as 0 or 60 seconds.

5.9.2. Dwell Time.

The dwell time, is an additional delay introduced on the output contacts used to prevent the contacts

opening during a tripping action. This may be selected as 0 or 200 mS.

5.10. Circuit Breaker Failure Protection (tCBFP).

The CB Failure Protection is based on supervision of phase currents during tripping events. This

protective function becomes active only after tripping. The test criterion is whether all phase curents

have dropped to <1% x In within tCBFP (Circuit Breaker Failure Protection adjustable between 0.1 -

1.6s) If one or more of the phase currents have not dropped to <1%xIn within this time, CB failure

is detected and the assigned output relay is activated. The CB failure protection function is

deactivated again as soon as all the phase currents have dropped to <1%xIn within tCBFP.

5.11. Display of Pick-up event.

If after a pick-up (starting) the existing current drops again below the pickup value, e.g. I>, without

a trip being initiated, LED I> signals that an activation has occurred by flashing fast. The LED

keeps falshing until it is reset again (push button <SELECT/RESET>). Flashing can be suppressed

when the parameter is set to NOFL. This applies also to the I>>, IE>, IE>> functions.

5.12. Display of Measuring values as primary quantities (Iprim phase).

With this parameter it is possible to show the indication as a primary measured value. For this

purpose the parameter must be set to be equal with the rated primary CT current. If the parameter is

set to "SEK" the measuring value is shown as a multiple of the rated secondary current.

Example:

The current transformer used is 1500/5A. The primary current is 1380A. The paramter is set to

1500A and on the display "1380 A" is shown. If the parameter is set to "SEK" the value shown on

the display is "0.92"xIn.

Note.

The pick-up value is set to a multiple of the rated secondary CT current.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 22 Issue 1

5.13. Display of Earth Current As Primary Quantity (Iprim earth).

The parameter of this function is to be set in the same way as that described under Section 5.12. If

the parameter is not set to "SEK" then the measuring value is shown as primary current in amperes

(this applies to MRI-IEX, MRI-IEK and MRI-EX as well). Apart from that the indication refers to

% of In.

5.14. Display of Residual Voltage UE as Primary Quantity (Uprim/Usec).

The residual voltage can be shown as primary measured value. For this parameter the

transformation ratio of the VT has to be set accordingly. If the parameter is set to "SEK", the

measuring value is shown as rated secondary voltage.

Example.

The voltage transformer used is 10kV/100V. The transformation ratio is 100 and this value has to be

set accordingly. If rated secondary voltage should be shown , the parameter is to be set to 1.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 23 Issue 1

6. Operation and setting

6.1. Layout of the control elements.

All control elements required for the operation and adjustment of the MRI are located on the front

panel. They are divided according to function into the three following groups:

• Alphanumeric Display: Indication of parameter set values, actual measured values and

recorded fault data.

• LED's: Indication of selected parameters and measured quantities.

• Push Buttons: Selection of parameter to be adjusted, quantity to be measured and

adjustment of parameter values. Where;

<SELECT / RESET> Selection of the parameter to be set and the relay quantities

to be measured. Continuous pressing as the reset function.

<UP> Increment of the setting values for the parameter selected.

<DOWN> Decrement of the setting values for the parameter selected.

<ENTER> Storage of the setting values for the selected parameter.

<TRIP> Testing of the output relay circuits.

6.2. Relay setting principles.

Up to ten basic relay parameters may be set by the user, dependent upon relay type;

Phase overcurrent:

• I> Starting current for phase overcurrent

• CHAR I> Time current characteristic for phase overcurrent

• tI> Tripping time delay for definite time overcurrent or time

multiplier for inverse time overcurrent

• I>> Current setting for high set overcurrent

• tI>> Tripping time delay for high set overcurrent

Earth Fault: (optional)

• IE> Starting current for earth fault

• CHAR IE Time current characteristic for earth fault

• tIE> Tripping time delay for definite time earth fault or

time multiplier for inverse time earth fault

• IE>> Current setting for high set earth fault

• tIE>> Tripping time delay for high set earth fault

By pressing the <SELECT/RESET> push button, the parameter to be modified is reached. The

corresponding LED illuminates on the curve and the present set value of the selected parameter is

indicated on the display. This set value may then be increased or decreased by pressing the <UP> or

<DOWN> buttons respectively. The selected set value is only stored after pressing the <ENTER>

push button and inputting the correct password. This means that adjustment of the unit is only

possible by authorised users.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 24 Issue 1

6.2.1. Password protected parameter adjustment.

The adjustment of all relay settings are password protected, however, to enable ease of adjustment,

for authorised users, application of the password is usually only required once for multiple

parameter adjustment. The following step by step sequence is given to illustrate the implementation

of the password protection facility, where a new relay setting is to be applied:

• After the present setting value has been selected and changed using the <UP>,

<DOWN> push buttons, the <ENTER> push button should be pressed.

• The message "SAV?" appears on the display, to confirm that the new setting value is

to be saved.

• After pressing <ENTER> again, the password will be requested. The message

"PSW?" is displayed.

• After the password has been given correctly, as indicated by the message "SAV!",

the new setting value may be stored by pressing the <ENTER> push button for at

least 3 seconds. The new setting parameter then reappears on the display.

A password consists of four push button operations. The pressed push buttons and their sequence

define the password. If the four push buttons are defined by the following symbols:

<SELECT/RESET> = S

<DOWN> = ∨∨∨∨

<UP> = ∧∧∧∧

<ENTER> = E

Then a password "∨∨∨∨E∧∧∧∧S" is achieved by the following sequence:

<DOWN> <ENTER> <UP> <SELECT/RESET>.

After a password is given correctly, parameter setting is permitted for five minutes. Subsequent

parameter setting made within the five minute period after the password was inputted, does not

require renewed password entry. Furthermore, the valid period for parameter setting is automatically

extended for a further 5 minutes after each push button operation.

If no push button is pressed within the 5 minute period then the validity of the password will be

suspended. To enter further parameters after this period re-application of the password is required.

During the 5 minute period when changes may be made, a new set value, acknowledged by

"SAV?" then "SAV!" , may be stored by pressing <ENTER> for approximately 3 seconds.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 25 Issue 1

6.3. Setting procedure.

The following sections describe in detail the setting of all relay parameters. Some sections are only

applicable to the more comprehensive devices, eg earth or directional elements.

6.3.1. Starting current for phase overcurrent relay (I>).

The displayed setting value for this parameter is related to the nominal rated current (IN) of the

relay. Thus;

Starting current (IS) = Displayed Value x Rated Current (IN)

e.g. If Displayed Value = 1.25, then IS = 1.25 x IN

6.3.2. Time current Characteristic for phase overcurrent relay (CHAR I>).

By setting this parameter, one of the following four options is displayed:

DEFT - Definite Time

NINV - Normal Inverse

VINV - Very Inverse

EINV - Extremely Inverse

RINV - RI Inverse

LINV - Long Time Inverse

Any one of these six characteristics can be chosen by using the <UP> <DOWN> keys and can be

stored by pressing <ENTER>. For more details on the characteristic curves see Section 9.5.

6.3.3. Tripping time delay or time multiplier for phase overcurrent relay (tI>).

After the time/current characteristic has been selected, the time delay (or time multiplier) should be

changed accordingly. In order to avoid an unsuitable arrangement of relay modes the following

precautions are taken:

Adjustment of the time delay setting is automatically prompted for after a change in the set

time/current characteristic. LED tI> flashes yellow to remind the operator to change the time

delay setting accordingly. After pressing the <SELECT/RESET> push button, the present time

delay setting value is shown on the display. A new setting value may then be entered.

If the relay characteristic has been changed (e.g. from DEFT to NINV), but the time delay setting

has not, the relay will, after 5 minutes, automatically set itself to the most sensitive time setting

value available for that selected characteristic. The most sensitive time setting value implies the

fastest tripping for the selected relay characteristic. If the time delay or the time multiplier is set

out of range, "EXIT" appears on the display, and the low set stage of the relay is blocked.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 26 Issue 1

Where the MRI is fitted with a directional element, the different tripping time delays or time

multipliers may be chosen for both forward and reverse faults.

When setting the tripping time delay, the set value for forward faults appears on the display first

and the LED under the "arrows" illuminates GREEN. The set value may be changed with the

<UP> and <DOWN> push buttons, and then stored. By pressing the <SELECT/RESET>

button the tripping time delay for reverse faults appears on the display and indicator changes

from GREEN to RED.

If the time delays are set equally for both forward and reverse faults, the relay trips in both cases

with the same time delay, effectively nullifying the directional feature. If the time delay for

reverse faults is set out of range, "EXIT" on the display, the relay is blocked for reverse faults.

The low set stage of the overcurrent relay may also be blocked via terminals 54 and 55 (see

Section 6.3.17).

It is also possible to inhibit the alarm relay for a fault in the reverse direction. The display shows

either "NOWA" - No alarm when a fault occurs in the reverse direction, or "WBAK" - Alarm

relay is activated when a fault occurs in the reverse direction. During this procedure the LED is

illuminated RED.

6.3.4. Current setting for high set stage of phase overcurrent relay (I>>).

The current setting value of this parameter is related to the nominal rated current of the relay.

Thus;

I>> = Displayed Value x Rated Current (IN)

e.g. If Displayed Value = 20, then I>> = 20 x IN

The high set stage of the overcurrent relay is blocked if the setting value is set to "EXIT".

The high set stage may also be blocked via terminals 54/55, see Section 6.3.17.

6.3.5. Tripping time delay for high set stage of phase overcurrent relay (tI>>).

Independent from the chosen tripping characteristic for I>, the high set stage I>> always has a

definite time tripping characteristic. An trip delay value in seconds appears on the display.

The setting procedure for forward or reverse faults described in paragraph 6.3.3 is also valid for the

tripping time of the high set stage.

6.3.6. Starting current for earth fault relay (IE>).

(Similar to 6.3.1)

6.3.7. Time Current characteristic for earth fault relay (CHAR IE).

(Similar to 6.3.2)

6.3.8. Tripping time delay or time multiplier for earth fault relay (tIE>).

(Similar to 6.3.3)

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 27 Issue 1

6.3.9. Current setting for high set stage of earth fault relay (IE>>).

(Similar to 6.3.4)

6.3.10. Tripping time delay for high set stage of earth fault relay (tIE>>).

(Similar to 6.3.5)

6.3.11. Earthing type.

6.3.11.1. COS/SIN Measurement.

Where an isolated or compensated earthed system version of the relay is supplied, the directional

element for earth faults must be set to SIN or COS as appropriate. Please refer to Section 5.5.1 for

more details.

6.3.11.2. SOLI/RES Setting.

Where a solid or resistive earthed system version of the relay is supplied, the directional element for

earth faults must be set to SOLI or RESI as appropriate. Please refer to Section 5.5.2 for more

details.

6.3.12. Residual Earth Fault Voltage (VE).

Operation of the earth fault (directional) element is inhibited for residual voltage below this preset

value, (isolated earth system).

6.3.13. Residual Earth Fault Voltage Measurement Method.

The measuring method must be set to "3PHA", "E-N" or "1:1" as required. (5.5.1, isolated earth

system).

6.3.14. Earth Fault Response.

The response to earth faults may be selected to "TRIP" or "WARN", ie to allow an alarm without

causing a trip function, (isolated earth system).

6.3.15. Nominal frequency.

The FFT Algorithm employed requires the nominal frequency as a parameter for correct digital

filtering of the input currents.

By pressing <SELECT> the display shows "f=50" or "f=60". The desired nominal frequency may

then be selected and stored.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 28 Issue 1

6.3.16. Assignments Of The Blocking Inputs.

The blocking input of the MRI relays can be programmed so that the blocking input will only block

certain functions. The blocking inputs are found at the beginning of assignment mode. By pressing

push buttons <ENTER> and <TRIP> simultaneously, the assignment mode is selected.

The first function that can be blocked has its LED light up and the display shows whether it is

blocked or not. To switch the blocking on (display shows BLOC) or off (NOBL) press the

<VALUE UP> or <VALUE DOWN> buttons and then save the parameter.

The following functions can be blocked.

Low Set Overcurrent

High Set Overcurrent

Low Set Earth Fault Overcurrent

High Set Earth Fault Overcurrent

The assignment mode can be terminated at any time by pressing the <SELECT/RESET> push

button for approximately 3 seconds.

6.3.17. Blocking Of Protection Functions.

The blocking function of the MRI can be set according to requirement. By applying the auxiliary

voltage to 55 and 56, the functions chosen by the user can be blocked. Setting of the parameter

should be done as follows:

1.) When pressing push buttons <ENTER> and <TRIP> at the same time the message "BLOK" is

displayed (i.e. the respective function is blocked) or "NO_B" (i.e. the respective function is not

blocked). The LED allocated to the first protection function I> is illuminated.

2.) By pressing push buttons <VALUE UP> and <VALUE DOWN> the value displayed can be

changed.

3.) The changed value is stored by pressing <ENTER> and entering the password.

4.) By pressing the <SELECT/RESET> push button, any further protection function which can be

blocked is displayed.

5.) Thereafter the blocking menu is left by pressing <SELECT/RESET> again.

Function Display LED/Colour

I> Overcurrent (Low Set) NO_B I> yellow

I>> Overcurrent (High Set) BLOC I>> yellow

IE> Earth Current (1 element) NO_B IE> yellow

IE>> Earth Current (2 element) NO_B IE>> yellow

tCBFP Switch Failure Protection NO_B CB green

Table 6.3.17. Default settings of both parameter sets.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 29 Issue 1

6.3.18. Programming Of Output Relays.

Output relays 1-4 of the MRI are normally de-energised and can be assigned as alarm or tripping

relays to the overcurrent functions. The fifth output relay is not assignable and is provided as a

permanent alarm relay for self-supervision, and is normally energised. The assignment of the output

relays is similar to the setting of parameters, however, only whilst in the assignment mode. The

assignment mode is accessible via the blocking mode, see above.

The output relays can be assigned to each of the protections functions as follows:-

Low Set Overcurrent

High Set Overcurrent

Low Set Earth Fault Overcurrent

High Set Earth Fault Overcurrent

Trip and Alarm relays are assigned as follows:-

When the protection function is highlighted by pressing the <SELECT/RESET> button the value

LED refers to the ALARM output and the time delay LED refers to the TRIP output.

Now one or several of the four output relays can be assigned to the protection function chosen as

either an alarm or trip relay. Indication ‘1_ _ _’ means that output relay 1 is assigned to this

protection function. When the display shows ‘ _ _ _ _’, no alarm relay is assigned to this protection

function. The assignment of output relays 1,2,3 & 4 to the protection function can be changed by

pressing value up and value down push buttons. The selected assignment can be stored by pressing

push button <ENTER> and subsequent input of the password.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 30 Issue 1

By repeated pressing of the <SELECT/RESET> push button and assignment of the relays all

parameters can be assigned separately to the relays. The assignment mode can be terminated at any

time by pressing the <SELECT/RESET> push button for approximately 3 seconds.

EXAMPLE

Outputs Relays Display-

indication

LED

Illuminated.

Relay Number 1 2 3 4

Terminal Number 29-34 35-40 41-46 47,49,51

Function

I>(F) alarm X _ 2 _ _ I>

tI>(F) Tripping X 1 _ _ _ tI>

I>(R) alarm X _ 2 _ _ I>

tI>(R) Tripping X 1 _ _ _ tI>

I>>(F) alarm X _ _3 _ I>>

tI>>(F) Tripping X 1 _ _ _ tI>>

I>>(R) alarm X _ _3 _ I>>

tI>>(R) Tripping X 1 _ _ _ tI>>

IE>(F) alarm X _ _ _ 4 IE>

tIE>(F) Tripping X 1 _ _ _ tIE>

IE>(R) alarm X _ _ _ 4 IE>

tIE>(R) Tripping X 1 _ _ _ tIE>

IE>>(F) alarm X _ _ _ 4 IE>>

tIE>>(F) Tripping X 1 _ _ _ tIE>>

IE>>(R) alarm X _ _ _ 4 IE>>

tIE>>(R) Tripping X 1 _ _ _ tIE>>

tCBFP Tripping _ _ _ _ C.B. red

X=Default Values.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 31 Issue 1

6.3.19. Parameter Switch.

The relay is able to store two different sets of setting parameters. This could be used , for example,

in planned alternative network configurations where different characteristics may be required for co-

ordination purposes.

It is possible to change between the two parameter sets either over the communications port, using

suitable software, when the parameter switch is set at "SET 1" or "SET 2 " or by using the available

digital inouts. The MRI has two inputs, the blocking inout and the reset input. By selecting the

parameter switch to "BLOC", the blocking input can be used to choose the parameter set.

Alternatively by selecting the parameter switch to "RST" the reset input can be used to change the

parameter set. This is summarised below.

Software Parameter Blocking input used as RESET input used as

SET 1 Blocking input RESET input

SET 2 Blocking input RESET input

BLOC Parameter set change over RESET input

RST Blocking input Parameter set change over

When settings SET1 or SET2 are used, the parameter set is activated by software by pressing the

<SELECT/RESET> button when the P2 LED is lit. Terminals 53, 54 and 55 are then available as

external inputs for RESET or BLOCKING:

The setting BLOC uses the BLOCKING input (terminals 54, 55) for the change over procedure and

the setting RST uses the RESET input (terminals 53, 54) for this procedure. When aux. Voltage is

applied to one of these two external inputs, then the parameter set is changed over from Set 1 to Set

2. When parameter set 2 is active, LED P2 lights up. If the aux. Voltage is disconnected, it

automatically changes over to parameter set 1 again.

Important Note:

When functioning as parameter change over facility, the external input RESET is not available for

resetting. When using the external input BLOCKING the protection functions must be deactivated

by software blocking separately (refer to Section 6.3.17).

6.3.20. Fault Recorder.

The MRI is equipped with a fault recorder (see Section 6.4.3.). Three parameters can be

determined.

6.3.20.1. Number of the fault recordings

The number of max. recordings requested has to be determined in advance. There is a choice of 2, 4

or 8 recordings and the duration of the individual fault recordings are dependent upon the number

chosen, as shown below:

2 recordings for a duration of 8 s

4 recordings for a duration of 4 s

8 recordings for a duration of 2 s

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 32 Issue 1

6.3.20.2. Adjustment of trigger occurrences.

There is a choice between four different occurrences:

P_UP (PickUP) Storage is initiated after recognition of a general activation.

TRIP Storage is initiated after a trip has occurred.

A_PI (After Pickup) Storage is initiated after the last activation threshold was fallen short of.

TEST Storage is initiated by the RESET function.

6.3.20.3. Pre-trigger time (Tpre)

The time setting Tpre determines the period of time prior to the trigger occurrence which should be

recorded as well. It is possible to adjust the time between 0.05s and 8s. With keys <+> and <-> the

values can be changed and with <ENTER> be saved.

6.3.21. Adjustment of the clock

When adjusting the date and time the LED lights up and the clock setting parameters are

displayed on the alpha-numeric display. Each setting is accessed using the <SELECT/RESET>

button. The adjustment method is as follows:

Date: Year Y=00

Month M=00

Day D=00

Time: Hour h=00

Minute m=00

Second s=00

The clock starts with the set date and time as soon as the supply voltage is switched on. The time is

safe guarded against short-term voltage failures (min. 6 minutes).

6.3.22. Communication Settings.

6.3.22.1. Slave Address.

This setting range 1 to 32, with a default setting of 1, identifies the relay to the XCell unit (or any

software capable of communicating to a Data highway) to which the RS485 Data Highway of the

MRI is connected.

6.3.22.2. Baud Rate.

This value determines the speed at which the relay communicates through its RS485 port. It can be

set to 1200, 4800, 9600 or 19200 Baud with a default setting of 9600. If you have chosen an MRI

relay with MODBUS Comms Protocol you are able to change this setting, otherwise it is set to 9600

and cannot be changed.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 33 Issue 1

6.3.22.3. Parity.

The following three parity settings are available:

"even" = even parity

"odd" = odd parity

"no" = no parity check.

Again this setting is only available if you have a relay with MODBUS comms protocol

6.3.23. Reset Setting (For Inverse Time Overcurrent Function).

This time delay can be set to either 0sec or 60sec. Please refer to Section 5.9.1. for more details.

6.3.24. Reset Setting (For Inverse Time Earth Fault Function).

This time delay can be set to either 0sec or 60sec. Please refer to Section 5.9.1. for more details.

6.3.25. Dwell Time.

This can be set to either 0sec or 200mS. Please refer to Section 5.9.2. for more details.

6.3.26. Relay Characteristic Angle (RCA).

This angle is for the directional; feature in the overcurrent functions and can be set to either 15°,

27°, 38°, 49°, 61°, 72° or 83°. Please refer to section 5.4. for more details.

6.3.27. Pick Up Value For Residual Voltage UE.

Regardless of the earth fault current settings an earth fault trip is only enabled if the residual voltage

exceeds this setting. The range is 1.01 to 6500 volts.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 34 Issue 1

6.3.28. Setting Summary

PHASE OVERCURRENT SETTINGS LED RANGE APPLIES TO

Starting Current I> 0.2 to 4xIn -I, -IE, -ID, -IED

Time Current Characteristic CHAR I> DEFT, NINV, VINV -I, -IE, -ID, -IED

EINV, RINV, LINV

Time Delay (For DEFT Only) tI> 0.03 - 260s -I, -IE, -ID, -IED

Time Multiplier (For INV) tI> 0.05 - 10.0 -I, -IE, -ID, -IED

High Set Stage Starting Current I>> 0.5 to 40xIn -I, -IE, -ID, -IED

Time Delay tI>> 0.03 to 10s -I, -IE, -ID, -IED

Reset Delay For INV Only 0 or 60s

EARTH PHASE O/C SETTINGS LED RANGE APPLIES TO

Starting Current IE> 0.01 to 2.0xIn -IE, -E

Time Current Characteristic CHAR IE> DEFT, NINV, VINV -IE, -E

EINV, RINV, LINV

Time Delay (For DEFT Only) tIE> 0.04 - 260s -IE, -E

Time Multiplier(For INV) tIE> 0.06 - 10.0 -IE, -E

High Set Stage Starting Current IE>> 0.01 to 15xIn -IE, -E

Time Delay tIE>> 0.04 to 10s -IE, -E

Reset Delay For INV Only 0 or 60s

SENSITIVE E/F O/C SETTINGS LED RANGE APPLIES TO

Starting Current IE> 0.1% to 20% -EX

Time Current Characteristic CHAR IE> DEFT, NINV, VINV -EX

EINV, RINV, LINV

Time Delay (For DEFT Only) tIE> 0.04 - 260s -EX

Time Multiplier (For INV) tIE> 0.06 - 10.0 -EX

High Set Stage Starting Current IE>> 0.1% to 150% -EX

Time Delay tIE>> 0.04 to 2.0s -EX

Reset Delay For INV Only 0 or 60s

DIRECTIONAL E/F O/C SETTINGS LED RANGE APPLIES TO

FOR SOLID GROUNDED SYSTEMS

Starting Current IE> 0.01 to 2.0xIn -ED, -IED

Time Current Characteristic CHAR IE> DEFT, NINV, VINV -ED, -IED

EINV, RINV, LINV

Time Delay (For DEFT Only) tIE> 0.04 - 260s -ED, -IED

Time Multiplier (For INV) tIE> 0.06 - 10.0 -ED, -IED

High Set Stage Starting Current IE>> 0.01 to 15xIn -ED, -IED

Time Delay tIE>> 0.04 to 10s -ED, -IED

Reset Delay For INV Only 0 or 60s

DIRECTIONAL E/F O/C SETTINGS LED RANGE APPLIES TO

FOR ISOLATED SYSTEMS

Starting Current IE> 0.01 to 0.45xIn -ED, -IED

Time Current Characteristic CHAR IE> DEFT, NINV, VINV -ED, -IED

EINV, RINV, LINV

Time Delay (For DEFT Only) tIE> 0.05 - 260s -ED, -IED

Time Multiplier (For INV) tIE> 0.06 - 10.0 -ED, -IED

High Set Stage Starting Current IE>> 0.01 to 0.45xIn -ED, -IED

Time Delay tIE>> 0.05 to 2s -ED, -IED

Reset Delay For INV Only 0 or 60s

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 35 Issue 1

Setting Summary

COMMUNICATION LED RANGE APPLIES TO

Slave Address RS 1-32 Full Range

Baud Rate RS 1200-9600 Relays with MODBUS

Parity Check RS Even, Odd, No Relays with MODBUS

DIRECTIONAL SETTINGS LED RANGE APPLIES TO

Earthing Type SIN or COS -IED, -ED, EX

Residual E/F Voltage Setting VE 1 -70V For 3 PHA, E-N and Un = 100V -IED, -ED, EX

2-160V For 3 PHA, E-N and Un = 230V -IED, -ED, EX

5-300V For 3 PHA, E-N and Un = 400V -IED, -ED, EX

1-120V For 1:1 and Un = 100V -IED, -ED, EX

2-300V For 1:1 and Un = 230V -IED, -ED, EX

5-500V For 1:1 and Un = 400V -IED, -ED, EX

Measuring Method VE 3 PHA, E-N or 1:1 -IED, -ED, EX

Earthing Networks SOLI or RES -IED, -ED, EX

Relay Characteristic Angle 15, 27, 38, 49, 61, 72 or 83°°°° -IED, -ED, EX

Pickup Value For Residual Voltage 1.01 to 6500V -IED, -ED, EX

Earth Fault Response TRIP or WARN

FAULT RECORDING LED RANGE APPLIES TO

No Of Fault Occurrences FR 2, 4, 8 Relays with Network Gold

Trigger Signal FR TEST, P_UP, A_PR, TRIP Relays with Network Gold

Pre Trigger Time FR 0.05 to 8s Relays with Network Gold

Date Year, Month, Day Full Range

Time Hour, Minute, Second Full Range

Dwell Time 0 or 200ms Full Range

Inhibit Alarm Delay NOWA or WBAK Full Range

Nominal Frequency 50/60Hz Full Range

Parameter Switch P2 Set1, Set 2, BLOC, RST Full Range

Pick Up LED Flash FLSH, NOFL Full Range

Circuit Breaker Failure CB 0.1 to 1.6s Full Range

Display Phase Current SEK, 0.001 to 50KA (Prim) Full Range

Display Earth Phase Current SEK, 0.001 to 50KA (Prim) Full Range

Display Residual Voltage SEK, 0.001 to 50KV (Prim) Full Range

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 36 Issue 1

6.4. Indication of measured values and fault data.

6.4.1. Indication of measured values.

Any one of the following measured quantities may be indicated on the display during normal service

by pressing the <SELECT> button and lighting the corresponding LED:

Value Displayed on LCD Corresponding LED

Apparent Current in Phase 1 LED L1 Green

Active Current in Phase 1 LED L1 and IP Green

Reactive Current in Phase 1 LED L1 and IQ Green

Apparent Current in Phase 2 LED L2 Green

Active Current in Phase 2 LED L2 and IP Green

Reactive Current in Phase 2 LED L2 and IQ Green

Apparent Current in Phase 3 LED L3 Green

Active Current in Phase 3 LED L3 and IP Green

Reactive Current in Phase 3 LED L3 and IQ Green

Apparent Earth Current LED E Green

Active Earth Current LED E and IP Green

Reactive Earth Current LED E and IQ Green

Residual Voltage LED UE yellow

Angle Between IE and UE LED E green and LED IE and UE Yellow

Note: The IP and IQ functions are only for those relays with the directional feature built in.

IP = In phase component of measured current

IQ = Quadrature component of measured current

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 37 Issue 1

6.4.1.1. Measured Values as a Primary Value.

The MRI is able to display the measured values as either a multiple of the rated value or as primary

current. The values displayed are as follows:-

Phase Currents (I1, I2, I3)

Range Unit

Secondary Current 0.00-40.0 xIn

Active Portion IP ±.00-40 xIn

Reactive Portion IQ ±.00-40 xIn

Primary Current .000-999

k000-k999

1k00-9k99

10k0-99k0

100k-999k

1M00-2M00

A

kA

kA

kA

kA

MA

Active Portion IP ±.00 - ±999

±k00 - ±k99

±1k0 - ±9k9

±10k - ±99k

±M10 - ±M99

±1M0 - ±2M0

A

kA

kA

kA

MA

MA

Reactive Portion IQ ±.00 - ±999

±k00 - ±k99

±1k0 - ±9k9

±10k - ±99k

±M10 - ±M99

±1M0 - ±2M0

A

kA

kA

kA

MA

MA

Earth Current (IE)

Range Unit

Secondary Current .000-15.0 xIn

Active Portion IP ±.00-40 xIn

Reactive Portion IQ ±.00-40 xIn

Primary Current .000-999

k000-k999

1k00-9k99

10k0-99k0

100k-999k

1M00-2M00

A

kA

kA

kA

kA

MA

Active Portion IP ±.00 - ±999

±k00 - ±k99

±1k0 - ±9k9

±10k - ±99k

±M10 - ±M99

±1M0 - ±2M0

A

kA

kA

kA

MA

MA

Reactive Portion IQ ±.00 - ±999

±k00 - ±k99

±1k0 - ±9k9

±10k - ±99k

±M10 - ±M99

±1M0 - ±2M0

A

kA

kA

kA

MA

MA

Earth Voltage (UE)

Range Unit

Secondary Voltage 000V-999V V

Primary Voltage .000-999

k000-k999

1k00-9k99

10k0-99k0

100k-999k

1M00-3M00

V

kV

kV

kV

kV

MV

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 38 Issue 1

6.4.2. Indication of fault data.

Visual indication of faults detected by the relay is given on the front panel. The four phase LEDs

L1, L2, L3 and E as well as the four function LEDs I>, I>>, IE> and IE>> are used to

indicate/specify fault events.

When a fault initiates an available relay function, the corresponding function LED illuminates

yellow. At the same time, the phase LED(s) flash(es) red to indicate the faulty phase or phases.

After the set time delay has elapsed, the relay trips and the LED(s) for the faulty phase(s) become a

constant red. The function LED remains illuminated. The fault currents measured at the instant of

trip are recorded in registers for fault indication.

The direction indicator also illuminates for units with directional elements; GREEN when faults

occur in the forward direction and RED in the reverse direction.

After the occurrence of a trip, fault data for all three phases and the residual circuit current may be

displayed in turn by repeatedly pressing the <SELECT/RESET> key. After all phase and residual

currents have been indicated, the LEDs return to red indicating the fault event. By pressing the

<SELECT/RESET> button for approximately 3 seconds the relay is reset to its original status. If

however, the relay was initiated by the occurrence of a fault, which then fell below a detectable

level, a slowly flashing LED corresponding to the detected fault is displayed. This can also be reset

using the <SELECT/RESET> button.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 39 Issue 1

6.4.3. Fault Recording.

The MRI has a fault recorder which records the measured analogue values as instantaneous values.

The instantaneous values:-

I1, I2, I3, IE, UE

are scanned at a rate of 1.25ms(at 50 Hz) and 1.041ms (at 60Hz) and saved in a cyclic buffer. It is

possible to store 2 - 8 fault occurrences with a total recording time of 16s per channel.

Via the RS485 interface the data can be read and processed by means of a PC. The data is

graphically edited and displayed. Binary tracks are recorded as well, e.g. starting and trip.

When the relay is energised or trips, all fault data and times are stored in a non-volatile memory.

The MRI is provided with a fault value recorder for a maximum eight fault occurrences. In the

event of additional trips the oldest data set is always written over.

For fault indication the trip values are recorded and also the status of LED’s are stored. Fault

values are indicated when push buttons <VALUE DOWN> or <VALUE UP> are pressed during

normal measuring value indication.

• Normal measuring values are selected by pressing the <SELECT/RESET> button.

• When then the <VALUE DOWN> button is pressed, the latest fault data set is

shown. By repeated pressing the <VALUE DOWN> button the last but one fault

data set is shown etc. For indication of fault data sets abbreviations FLT1, FLT2,

FLT3, ...are displayed (FLT1 means the latest fault data set recorded). At the same

time the parameter set active at the occurrence is shown.

• By pressing <SELECT/RESET> the fault measuring values can be scrolled.

• By pressing <VALUE UP> it can be scrolled back to a more recent fault data set.

At first FLT8, FLT7, ...are always displayed. When fault recording is indicated

(FLT1 etc), the LED’s flash in compliance with the stored trip information, i.e. those

LED’s which showed a continuous light when the fault occurred are now blinking to

indicate that it is not a current fault. LED’s which were blinking during trip

conditions, (element had picked up) just briefly flash.

• If the relay is still in trip conditions and not yet reset (TRIP is still displayed), no

measuring values can be shown.

• To delete the trip store, the push button combination <SELECT/RESET> AND

<VALUE DOWN> has to be pressed for about 3s. The display shows “wait”.

Tpre

RECORDING DURATION

TRIGGER OCCURENCE

[S]

Recording scheme of the fault recorder with lead time.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 40 Issue 1

Recorded Fault Values :-

Value Displayed Relevant LED

Phase currents L1, L2, L3 in I/In L1, L2, L3

Earth Current I, in I/In E

C.B. switching time in s C>B

Expired tripping time of I> in % of tI> I>

Expired tripping time of I, in % of tIE> Ir

Time Stamp

Date: Y = 99

M = 04

D = 20

Time: h = 11

m = 59

s = 13

Note.

C.B. tripping time:

Time between energising of the trip output relay and switching of the C.B. (current < 1 % In).

Expired Tripping time:

Time between pickup and release of the low set element. This value is only displayed for I> and I.

6.5. Test Trip.

The whole tripping circuit of the protection system may be tested by simulating a fault with the

<TRIP> push button. This button is also used to interrogate the relay for its software version

number. A single press reveals the first half of the software version number and a second press

reveals the second half. A third press will be responded to by "PSW?". Entering the correct

password will be responded to by "TRI?" . Pressing <TRIP> again energises all output relays in

turn with a delay time of 1 second. All relays will stay energised until manually reset.

6.6. Reset.

There are two ways in which to reset the MRI relay:

6.6.1. Hand reset.

By pressing the <SELECT/RESET> for approximately 3 seconds the relay is reset.

6.6.2. Reset input.

Please refer to section 5.8.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 41 Issue 1

6.7. Setting value calculation.

In order to ensure that protection relays form an integral part of any system, a full protection co-

ordination study should normally be undertaken which considers both upstream and downstream

equipment. Further details may be obtained by contacting P&B Engineering.

In the absence of a suitable study, the following provides a brief guide;

6.7.1. Low set stage.

For plain and transformer feeders, the low set stage pickup is normally taken as 120% of any

downstream protection and 80% any upstream protection

In the absence of upstream and downstream protection setting information, a setting of 150% of the

full load current is normally used for transformer feeders.

6.7.2. High set stage.

For plain feeders, this is not normally used. However, when used with a suitable time delay setting

it is normally taken as 120% and 80% of any downstream and upstream high set protection

respectively.

For transformer feeders, this is normally set to 120% of the actual through fault level for secondary

faults.

6.7.3. Characteristic curve.

This is normally selected to co-ordinate with the upstream and downstream protection

characteristic to achieve the minimum of crossover.

6.7.4. Low set stage time multiplier/time delay.

This is normally selected to give sufficient time delay between upstream and downstream operating

times to allow for breaker clearance and measurement errors etc. This is usually taken as 0.3 - 0.4

seconds

6.7.5. High set stage time delay.

This is normally set at the minimum possible, or as 6.7.4.

7. Relay case.

The MRI is delivered in an individual case for flush mounting.

7.1. Individual case.

The MRI is supplied in a UK manufactured industry standard drawout case suitable for flush

mounting. For case dimension and cut-out, refer to Technical Data.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 42 Issue 1

7.2. Rack mounting.

MRI relays may be supplied mounted in 19" racks if specified by the user.

7.3. Terminal connections.

The MRI plug in module is supplied in a case which has a very compact plug and socket

connector. The current terminals are equipped with self closing short circuit contacts. Thus the

MRI module can be unplugged even with current flowing without endangering personnel.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 43 Issue 1

8. Test and maintenance.

The test instructions following below help to verify the protection relay performance before or

during commissioning of the protection system. To avoid relay damage and to ensure a correct

relay operation, be sure that:

• The auxiliary power supply rating corresponds to the auxiliary voltage on site.

• The rated current and rated voltage of the relay correspond to the plant data on site.

• The current transformer circuits and voltage transformer circuits are connected to the relay

correctly.

• All signal circuits and output relay circuits are connected correctly.

8.1. Power On.

NOTE!

Prior to switching on the auxiliary power supply, be sure that the auxiliary supply voltage

corresponds with the rated data on the type plate.

Switch on the auxiliary power supply to the relay and check that the message “P&B” appears on

the display and the self supervision alarm relay (watchdog) is energized (Contact terminals 48 and

52 closed).

8.2. Testing the output relays and LEDs.

NOTE!

Prior to commencing this test interrupt the trip circuit to the circuit breaker if tripping is not

desired. By pressing the push button <TRIP> twice the display shows the second part of the

software version of the relay (e.g. “8.01”). (The software version should be quoted in all

correspondence.) Pressing the <TRIP> button once more the display shows “PSW?”. Please enter

the correct password to proceed with the test. The message “TRI?” will follow. Confirm this

message by pressing the push button <TRIP> again. All output relays should then be activated and

the self supervision alarm relay (watchdog) be deactivated one after another with a time interval of

3 second and all LEDs with a delay of 0.5 seconds, with the self supervision relay dropping. There

after reset all output relays back to their normal positions by pressing the push button <SELECT /

RESET> for about 3s.

8.3. Checking the set values

By repeatedly pressing the push button <SELECT/RESET>, all relay set values may be checked.

Set value modification can be done with the push button <+> <-> and <ENTER>. For detailed

information about changing the setting parameters please refer to Section 6.

For a correct relay operation, be sure that the frequency set value (F=50/60) has been selected

according to your system frequency (50 or 60 Hz).

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 44 Issue 1

8.4. Secondary Injection Test

8.4.1. Test Equipment

• Voltmeter, Ammeter with class 1 or better.

• Auxiliary power supply with the voltage corresponding to the rated data on the type plate.

• Single-phase current supply unit (adjustable from 0 to > 4 x In)

• Single-phase voltage supply unit (adjustable from 0 to >1.2 x Un) (Only for relays with

directional feature)

• Timer to measure the operating time. (Accuracy class < ± 10 ms)

• Switching device

• Test leads and tools

8.4.2. Example of test circuit for MRI relays without directional feature

For testing MRI relays without directional feature only current input signals are required. Figur 8.1

shows a simple example of a single phase test circuit with ad-justable current energizing the MRI

relay under test.

POWER

SUPPLY

1 2 CASE

Supply

MRI-IE

54 5553External ResetBlocking Input

L N L

33

31

29

32

3034

4852

50

45

43

41

44

4246

40

38

36

37

3539

+

7 9 10

Gnd-

4751

49

SELF SUPERVISION

RS485

21

22

23

24

25

26

27

28

I1

I2

I3

IE

RELAY 1

RELAY 4

RELAY 3

RELAY 2

A

Variable

VoltageSource

SwitchingDevice

Series Resistor

Ammeter

Start Timer

+

-

-Stop

+

Figure 8.1. Test Circuit.

8.4.3. Checking the input circuits and measured values

Inject a current, which is less than the relay pickup current set values in phase 1 (terminals 22-23),

and check the measured current on the display by pressing the push button <SELECT/RESET>.

For a relay with rated current In = 5A, for example, a secondary current injection of 1A should be

indicated on the display with about 0.2 (0.2 x In) and at 5A the indication is 1.00 (A). The current

can be also injected into the other current input circuits (Phase 2: terminals 23-24, Phase 3:

terminals 25-26).

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 45 Issue 1

Compare the displayed current value with the reading of the ammeter. The deviation must not

exceed 3% or 1% In. By using an RMS metering instrument, a greater deviation may be observed

if the test current contains harmonics. Because the MRI relay measures only the fundamental

component of the input signals, the harmonics will be rejected by the internal DFFT-digital filter.

Whereas the RMS metering instrument measures the RMS-value of the input signals.

8.4.4. Checking the operating and resetting values of the relay.

Inject a current which is less that the relay set values in phase 1 of the relay and gradually increase

the current until the relay starts, i.e. at the moment when the LED I> and L1 light up or the alarm

output relay I> is activated. Read the operating current indicated by the ammeter. The deviation

must not exceed 3 % of the set operating value or 1 % In.

Furthermore, gradually decrease the current until the relay resets, i.e. the alarm output relay I> is

disengaged. Check that the resetting current is smaller than 0.97 times the operating current.

Repeat the test on phase 2, phase 3 and earth current input circuits in the same manner. (Accuracy

of earth current measuring ±3 % of measuring value or 0.1 % of In for E-type: 0.01 % of In for X-

type).

8.4.5. Checking the relay operating time

To check the relay operating time a timer must be connected to the trip output relay contact. The

timer should be started simultaneously with the current injection in the currrent input circuit and

stopped by the trip relay contact. Set the current value and inject the current instantaneously. The

operating time measured by the timer should have a deviation of less than 3% of the set value or ±

10ms (DEFT). Accuracy for inverse time characteristics refer to IEC 60255-3.

Repeat the test on the other phases or with the inverse time characteristics in the similar manner.

In case of inverse time characteristics the injected current should be selected according to the

characteristic curve, i.e. two times Is. The tripping time may be red from the characteristic curve

diagram of calculated with the equations given under “Technical Data”.

Please observe that during the secondary injection test the test current must be very stable, no

deviation more than 1 %. Otherwise the test results may be wrong.

8.4.6. Checking the high set element of the relay.

Set a current above the set operating value of I>>. Inject the current instantaneously and check that

the alarm output relay I>> operates. Check the tripping time of the high set element according

Section 8.4.5. Check the accuracy of the operating current setting by gradually increasing the

injected current until the I>> element picks up. Read the current value form the ammeter and

compare with the desired setting. Repeat the entire test on other phases and earth current input

circuits in the same manner.

NOTE!

Where test currents >4 x IN are used, the thermal withstand capability of the current paths has to be

considered (see Technical Data, Section 9.1).

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 46 Issue 1

8.4.7. Example of a test circuit for MRI relay with directional feature.

POWER

SUPPLY

1 2 CASE

Supply 54 5553

External ResetBlocking Input

L N L

33

31

29

32

30

34

48

52

50

45

43

41

44

42

46

40

38

36

37

35

39

+

7 9 10

Gnd-

47

51

49

SELF SUPERVISION

RS485

21

22

23

24

25

26

I1

I2

I3

RELAY 1

RELAY 4

RELAY 3

RELAY 2

A

Variable

Voltage

Source

Switching

DeviceSeries Resistor

Ammeter

Start Timer

+

-

-

Stop

+

14

I3

MRI-ID

19

I2

15

17

I1

V1

N

V2

V3

Switching

Device

V

V1

V2V3

I1

V23

45

45

Voltmeter

Variable Voltage

Source With

Phase Shifting

*

*

Figure 8.2. Test Circuit.

For testing relays with directional feature, current and voltage input signals with adjustable phase

shifting are required. Figure 8.2 shows an example of a singled phase test circuit with adjustable

voltage and current energizing the MRI relay under test.

For testing a relay with directional feature, one of the input energizing quantity (voltage) shall be

applied to the relay with a constant value within its effective range. The other input energizing

quantity (current) and phase angle shall be appropriately varied.

MRI is a three phase directional time overcurrent relay with relay connection angle of 0º. The relay

input currents and their corresponding reference voltages are shown in the following table (refer to

Section 5.4):

Current Input Reference Voltage

I1 U23

I2 U31

I3 U12

If the single phase test circuit as illustrated in Figure 8.2 is applied to test the directional feature of

the relay and the current source is connected to phase 1 current input (21-22), then the voltage

source should be connected to relay terminals 17-19.

In order to test the directional feature, all activation points should first be set to “EXIT”. Then a

test voltage equivalent to the rated voltage is connected to terminals 17-19 and a current of 1 x In is

impressed upon the current inputs 21-22.

It is now possible to read and check all measured values in accordance with Table 8.1. If the phase

position is changed by 90º, for example, the measured value for current input I1 must be 1.0 and ±

0.0 for IQ.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 47 Issue 1

Determining the change in direction

The angle of greatest sensitivity for determining the phase direction is adjustable between 15º and

83º. Consequently, the greatest sensitivity is achieved with setting 49º if the input current leads the

input voltage by 49º. This setting results in a tripping range in advance direction of 139º leading to

41º lagging if the marginal regions are neglected on account of lack in measuring precision.

Current

Input

Terminals Reference

Voltage

Terminals Display

S2/S1 L/N Phase 1p 1o

11 21-22 U23 17-19 1.00 + 3% In + 0.0 + 3% In + 1.0 + 3% In

12 23-24 U31 15-19 1.00 + 3% + 0.0 + 3% In + 1.0 + 3% In

13 25-26 U12 15-17 1.00 + 3% + 0.0 + 3% In + 1.0 + 3% In

E* 27-28 U1 17-14 1.00 + 5% + 1.0 + 5% In + 0.0 + 5% In

Table 8.1

In order to check this, the following parameters should be set:

Parameter Setting

I> 0.5 x In

tI> (F) EXIT

tI> (R) EXIT

IE> 0.5 x In

tIE> (F) EXIT

tIE> (R) EXIT

Table 8.2

For relay assignment:

Parameter Relays

I> Alarm (F) -2---

I> Alarm (R) ---3-

IE> Alarm (F) -2---

IE> Alarm (R) ---3-

Table 8.3

A test current of 1 x In is impressed upon the current Input. The voltage source is to be connected

as provided for in Table 8.1. With an angle setting of 490 leading, Relay 2 must respond and LED

lights up green. If the angle is now changed beyond the marginal regions, The LED changes

from green to red. Relay 2 drops And relay 3 responds. This test must be repeated for current

Inputs 12 and 13.

In order to determine the direction in the earth current circuit refer to Fig 5.5.2.1. with the

characteristic angle in the ridge grid (SOLI) and to Fig 5.5.2.2. with the characteristic angle in the

grid with resistance earthing (RESI).

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 48 Issue 1

To check the trip delays for forward and backward direction they have to be set differently,

because there’s only one trip relay for both directions. Great care must be taken to connect the test

current and test voltage to the relay in correct polarity are indicated by a * mark near the

terminals. The markings indicate that the relay will trip in its maximum sensitive angle when the

voltage drop from the marked end to the non-marked end in the voltage input circuit has 49°

phase angle lagging the current flowing from the marked end to the non-marked in the current

level must be above the pickup value.

8.4.8. Test circuit earth fault directional feature.

POWER

SUPPLY

1 2 CASE

Supply 54 5553External ResetBlocking Input

L N L

33

31

29

32

3034

4852

50

45

43

41

44

4246

40

38

36

37

3539

+

7 9 10

Gnd-

4751

49

SELF SUPERVISION

RS485

27

28IE

RELAY 1

RELAY 4

RELAY 3

RELAY 2

A

VariableVoltageSource

SwitchingDevice

Series Resistor

Ammeter

Start Timer

+

-

-Stop

+

14

I3

MRI-ED

19

I2

15

17

I1

V1

N

V2

V3

SwitchingDevice

V

V1

V2V3

I1

V23

45

45

Variable VoltageSource With

Voltmeter

Phase Shifting

*

*

Figure 8.3. Test Circuit.

For testing relays with earth fault directional feature current and voltage input signals with

adjustable phase shifting are required. Figure 8.3 shows an example of a single phase test circuit

with adjustable voltage and current energizing the MRI relay under test. For testing a relay with

earth fault directional feature one of the input energizing quantity (voltage) shall be applied to the

relay with a constant value within its Effective range. The other input energizing quantity

(current) and phase angle shall be appropriately varied.

With the aid of phase ange indicated on the display The correct function of the relay can be

checked.

Parameters IE> and IE>> should be set to EXIT.

The following measured values are shown:

Measured vlue LED

Earth current E, IE>

Active share E, Ip

Reactive share E, I0

Earth voltage E, UE>

Angel E, IE>, UE>

Table 8.4

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 49 Issue 1

8.4.9. Checking the external blocking and reset functions.

The external blocking input inhibits e.g. the function of The high set element of the phase current.

To test the Blocking function apply auxiliary supply voltage to the External blocking input of the

relay (terminals 54-55). He time delay tI> should be set to EXIT for this test. Inject a test current

which could cause a high set (I>>) Tripping. Observe that there is no trip and alarm for the high

set element.

Remove the auxiliary supply voltage from the blocking input. Inject a test current to trip the relay

(message “Trip” on the display). Interrupt the test current and apply auxiliary supply voltage to

the external reset input of the relay (terminals 53-54). The display and LED indications should

be reset immediately.

8.4.10. Test of the CB failure protection.

For testing the tripping time a test current of about 2 times the rated current should be injected.

The timer is started upon tripping of the relay of a protection function (I>, I>>, IE>, IE>>) and

stopped as soon as the relay for the CB failure protection has picked up. Message “CBFP” is

displayed. The tripping time ascertained by the timer should not deviate more than 1% Or, at

short trip delay, less than 10ms from the set Tripping time.

Alternatively, the timer can be started when the Aux. Voltage and the test current are injected

simultaneously. The timer stops when the corresponding output relay for circuit breaker failure

protection trips. In this case the previously measured tripping delay (see Section 8.4.5) has to be

subtracted from the total tripping time measured.

8.5. Primary injection test.

Generally, a primary injection test could be carried out in the similar manner as the secondary

injection test described above. With the difference that the protected power system should be, in

this case, connected To the installer relays under test “on line”, and the test currents and voltages

should be injected to the relay through the current and voltage transformers with the primary side

energized. Since the cost and potential hazards are very high for such a test, primary injection

tests are usually limited to very important protective Relays in the power system.

Because of its powerful combined indicating and measuring functions, the MRI relay may be

tested in the manner of a primary injection test without extra expenditure and time consumption.

In actual service, for example, the measured current values on the MRI relay displayed may be

compared phase by phase with the current indications of the ammeter of the switchboard to verify

that the relay works and measures correctly. In case of a MRI relay with directional feature, the

active and reactive parts of the measured currents may be checked and the actual power factor

may be calculated and compared it with the cost-meter indication on the switchboard to verify that

the relay is connected to the power system with the correct polarity

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 50 Issue 1

8.6. Maintenance.

Maintenance testing is generally done on site at regular intervals. There intervals vary among

users depending on many factors: e.g. the type of protective relays employed; the user’s past

experience with the relay, etc. For electromechanical or static relays, maintenance testing will be

performed at least once a year according to experience. For digital relays like MRI, this interval

can be substantially longer. This is because.

• The MRI relays are equipped with very wide Self Supervision functions, so that many

faults in the relay can be detected and signalized during service. Important: The self-

supervision output relay must be connected to a central alarm panel!

• The combined measuring functions of MRI relays enable supervision the relay functions

during service.

• The combined TRIP test function of the MRI relay allows to test the relay output circuits.

A testing interval of two years for maintenance will, therefore, be recommended. During a

maintenance test, the relay functions including the operating values and relay tripping

characteristics as well as the operating time should be tested.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 51 Issue 1

9. Technical Data.

9.1 Measuring Input Circuits

Rated Data

Rated current, IN 1A or 5A

Rated voltage, VN 10V, 230V or 400V

Rated frequency, fN 50Hz, 60Hz

Burden

@ IN = 1A 0.2 VA

@ IN = 5A 0.1 VA

In voltage circuit < 1 VA

Thermal withstand

Half wave 250 x IN

for 1 second 100 x IN

for 10 seconds 30 x IN

Continuously 4 x IN

In voltage circuit 1.5 x VN

9.2 Auxiliary power supply Supply Voltage

Vaux = 16V to 360V DC

16V to 270V AC

Power Consumption

Quiescent Approx. 3W

Operating Approx. 6W

9.3 Common data Drop Off/Pick Up ratio >97%

Drop Off time 30mS

Time Lag error ± 10mS

Minimum operating time 30mS

Transient over-reach ≤ 5%

Factors affecting current measurement:

Auxiliary voltage in the range 0.8xVaux(min) to 1.2xVaux(max)

No changes measured

Frequency harmonics in the range 0.9 < f/fN < 1.1 = < 0.20% /Hz

Up to 20% of the third harmonic = < 0.08% /Hz

Up to 20% of the fifth harmonic = < 0.07% /Hz

Factors affecting delay times:- No influences could be measured.

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 52 Issue 1

9.4 Setting ranges and steps

9.4.1 Definite time phase overcurrent relay

Setting range / step Tolerance

I> Is

tI>

0.5...4 x IN / 0.05; 0.1 x IN

0.03...165s / 0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0;

2.0; 5.0s

± 5% from set value

± 3% or ± 10mS

I>> I

tI>>

2...40 x IN / 0.1; 0.2; 0.5; 1.0 x IN

0.03...2s / 0.01; 0.02; 0.05s

± 5% from set value

± 3% or ± 10mS

IE> Is

tIE>

0.01...0.45 x IN / 0.001; 0.002; 0.005 x IN

0.06...165s / 0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0;

2.0; 5.0s

± 5% or ± 3mA from set value

± 3% or ± 10mS

Isolated or

IE>> IE

tIE>>

0.01...0.45 x IN / 0.01; 0.02 x IN

0.06...2s / 0.01; 0.02; 0.05s

± 5% or ± 3mA from set value

± 3% or ± 10mS Compensated

System

VE> VE Vn = 100 1 - 100V

Vn = 230 2 - 230V

Vn = 400 4 - 400V

1V or ± 5% from set value

2V or ± 5% from set value

3V or ± 5% from set value

IE> Is

tIE>

0.001...0.045 x IN / 0.0001; 0.0002; 0.0005 x IN

0.06...165s / 0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0;

2.0; 5.0s

± 5% or ± 3mA from set value

± 3% or ±10mS

Isolated or

IE>> IE

tIE>>

0.001...0.045 x IN / 0.001; 0.002 x IN

0.06...2s / 0.01; 0.02; 0.05s

± 5% or ± 3mA from set value

± 3% or ± 10mS Compensated

System

VE>

VE Vn = 100 1 - 100V

Vn = 230 2 - 230V

Vn = 400 4 - 400V

1V or ± 5% from set value

2V or ± 5% from set value

3V or ± 5% from set value

Low Setting

EX Version

IE> Is

tIE>

0.01...2.0 x IN / 0.1 x IN

0.05...165s / 0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0;

2.0; 5.0s

± 5% or ± 3mA from set value

± 3% or ± 10mS

Solid or

Resistive

IE>> IE

tIE>>

0.01...15 x IN / 0.1; 0.2; 0.5 x IN

0.05...2s / 0.01; 0.02; 0.05s

± 5% or ± 3mA from set value

± 3% or ± 10mS Earthed

System

Iprim

IEprim

(SEK) 0.001 - 50.0

0.001, 0.002,0.005,0.01,0.02,0.05,0.1,0.2

UE>

(Uprim/

USEK)

(SEK) 1.01 - 6500

0.01, 0.02, 0.05,0.1,0.2,0.5,1,2,5,10,20,50

tCBFP 0.1 - 2.0s: EXIT

0.01, 0.02, 0.05, 0.1s ±1% bzw +10ms

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 53 Issue 1

9.4.2 Inverse time phase overcurrent relay

Characteristics according to IEC 255-4 or BS 142 (See Section 9.5)

Inverse time phase overcurrent relay setting ranges and steps

Setting Range Tolerance

I> Is

tI>

0.2 -- 1.0

1.0 -- 2.0

2.0 -- 4.0

0.05 --0.5

0.5 -- 1.0

1.0 -- 2.0

2.0 -- 5.0

5.0 -- 10.0

0.01

0.05

0.1

0.01

0.02

0.05

0.1

0.2

± 5% from set value

± 5% for NI and VI

± 7.5% for EI at 10 x Is

I>> I

tI>>

1.0 -- 2.0

2.0 -- 4.0

4.0 -- 10.0

10.0 -- 20.0

20.0 -- 40.0

0.03 -- 0.4

0.4 -- 1.0

1.0 -- 2.0

0.05

0.1

0.2

0.5

1.0

0.01

0.02

0.05

± 5% from set value

± 3% or ± 10mS

IE>

*

Is

tIE>

0.01 -- 0.05

0.05 -- 0.1

0.1 -- 0.2

0.2 -- 0.5

0.5 -- 1.0

1.0 -- 2.0

0.06 -- 0.5

0.5 -- 1.0

1.0 -- 2.0

2.0 -- 5.0

5.0 -- 10.0

0.001

0.002

0.005

0.01

0.02

0.05

0.01

0.02

0.05

0.1

0.2

± 5% or ± 3mA from set value

± 5% for NI and VI

± 7.5% for EI at 10 x Is

IE>>

*

IE

tIE>>

0.01 -- 0.05

0.05 -- 0.1

0.1 -- 0.2

0.2 -- 0.5

0.5 -- 1.0

1.0 -- 2.0

2.0 -- 5.0

5.0 -- 10.0

10.0 -- 15.0

0.04 -- 0.5

0.5 -- 1.0

1.0 -- 2.0

0.001

0.002

0.005

0.01

0.02

0.05

0.1

0.2

0.5

0.01

0.02

0.05

± 5% or ± 3mA from set value

± 3% or ± 10mS

* refers to Solid or Resistive Earthed System

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 54 Issue 1

9.4.3 Direction unit for phase overcurrent relay

Directional sensitivity for voltage input circuit:

Phase circuit = < 0.25% VN (phase to phase voltage)@ I = 1 x IN

Connection angle = 90°

Characteristic angle = selectable 15°, 27°, 38°,49°,61°,72°,83°

Relay Effective Angle = ± 78° related to relay characteristic angle at Vn

9.4.4 Direction unit for earth fault relay

Measuring principle (Isolated/Compensated systems):

Active component for compensated systems = IE x Cos φ

Reactive component for isolated systems = IE x Sin φ

Angle Measuring Accuracy = +3° at IE cosφ or IE sinφ >5%Ie

Measuring principle (Solid/Resistive Earthed System)

Characteristic Angle = "SOLI" setting 110°

= "RESI" setting 170°

Effective Ange = ±70° related to relay characteristic angle at VN/√3

Residual Voltage Sensitivity = <0.2&VN at I=0.1xIN

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 55 Issue 1

9.5. Inverse time characteristics

Normal Inverse (Type A)

Extremely Inverse (Type C)

Very Inverse (Type C)

RI-Inverse

10

8

6

4

3

2

10.9

0.1

0.2

0.3

0.4

0.50.60.70.8

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 56 Issue 1

[236.0

339.0

1st

Is

I

t I >

=

Long Time Inverse

0.1

1

10

100

1000

10000

10

8

6

4

3

2

0.1

0.2

0.3

0.40.5

0.60.7

0.80.9

1

Definite Time

I/I s

9.5.1 Inverse time Equations

Characteristics according to IEC 60255-3 or BS 142

Normal Inverse Very Inverse

(Type A) (Type C)

Extremely Inverse Long Time Inverse

(Type C)

RI Inverse Time Where

t = Tripping Time

tI> = Time Multiplier

I = Fault Current

Is = Setting Current

][

1

14.002.0

st

Is

It I >

= ][

1

5.13st

Is

It I >

=

][

1

802

st

Is

It I >

= ][

1

120st

Is

It I >

=

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 57 Issue 1

9.6 Output contact ratings

Number of relays = 5

Contacts = 2 change over contacts for trip signal, I> alarm, & I>> alarm.

1 change over contact for IE> alarm & self supervision.

Maximum breaking capacity

250V AC / 1500VA / continuous current 6A

for DC voltage:

ohmic L/R = 4ms L/R = 7ms

300 V DC 0.3 A / 90 W 0.2 A / 63 W 0.18 A / 54 W

250 V DC 0.4 A / 100 W 0.3 A / 70 W 0.15 A / 40 W

110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.2 A / 22 W

60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.3 A / 17 W

24 V DC 6 A / 144 W 4.2 A / 100 W 2.5 A / 60 W

Max. rated making current: 64A(IEC65)

mechanical life span: 3 × 106 operating cycles

electrical life span: 2 × 105 operating cycles at 220 V AC / 6A

Contact material Silver Cadmium Oxide (AgCdO)

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 58 Issue 1

9.7 Type Tests

F1 Functional Tests

Internal Design

Specifications &

IEC60255-6

IEC60255-3

Performance in line with Specification &

Standards

Climatic Tests

C1 Temperature Dry Cold

(Relay operational)

IEC60068-2-1 -20 deg C , 96 hours

C2 Temperature Dry Cold

Transportation & Storage

IEC60068-2-1 -40 deg C, 96 hours

C3 Temperature Dry Heat

(Relay operational)

IEC60068-2-2 70 deg C, 96 hours

C4 Temperature Dry Heat

Transportation & Storage

IEC60068-2-2 85 deg C, 96 hours

C5 Damp Heat Steady State

(Relay operational)

IEC60068-2-3 93% @ 40 deg C , 56 days

Enclosure

C6 Enclosure IEC 529 front IP52 , rear IP00

Mechanical (Relay operational)

M1 Vibration IEC60255-21-1 Class I

Vibration response (relay operational)

10Hz~150Hz - peak displacement 0.035mm

below 58/60Hz,0.5g above ,1 sweep cycle in

each axis

Vibration endurance (relay de-energised)

10Hz~150Hz 1g , 20 sweep cycles in each

axis(160 minutes at 1 octave /min)

M2 Shock & Bump IEC60255-21-1 Class I

Shock response (relay operational) 5g 11mS 3

pulse in each axis

Shock withstand (relay de-energised) 15g 11mS

3 pulses in each axis

Bump (relay de-energised) 10g 16mS 1000

pulses in each axis

M3 Seismic IEC60255-21-1 Class I

Method A single axis sine sweep

1Hz~35Hz – below 8/9Hz 3.5mm peak

displacement horizontal axis, 1.5mm vertical

axis

above 8/9Hz 1g horizontal,0.5g vertical

1 sweep cycle in each axis

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 59 Issue 1

Electrical E1 Insulation resistance

>100MΩ

IEC60255-5 500 Vdc , 5 sec between all terminals & case

earth, between terminals of independent circuits

including contact circuits and across open

contacts

E2 DC & AC Supply Voltage

(Relay operational)

IEC60255-6 Voltage range, upper & lower limit continuous

withstand , ramp up & down over 1 minute

E3 Voltage Dips , Short

Interruptions & Voltage

variations immunity

(Relay operational)

IEC60255-11

IEC 1000-4-11

3 dips & 3 interruptions at 10 sec intervals of

duration between 10mS and 500mS at zero

crossings & at other points on wave

variation:100% to 40% over 2s,hold for 1s,return

to 100% over 2s

E4 Ripple in dc supply

(Relay operational)

IEC60255-11 12% ac ripple

E5 Dielectric Test (Relay de-

energised)

No breakdown or flashover

Test voltage 45~65Hz

sinusoidal

Or with dc voltage at 1.4x the

stated ac values

IEC60255-5 Series C of table 1 2.0 kV 50Hz , 1 minute

between all terminals & case earth

2.0 kV 50Hz , 1 minute between terminals of

independent circuits including contact circuits.

1.0 kV 50Hz , across open contacts , 1 minute.

2.5kV 50Hz, between terminals of CT Circuits

and Earth

E6 High Voltage Impulse

(Relay de-energised)

IEC60255-5 5 kV peak 1.2/50uS,0.5J - 3 positive , 3 negative

between all terminals to case earth

between independent circuits

E7 VT input Thermal Withstand 1.5x Vn , continuous

E8 CT input Thermal Withstand 250xIn half wave

100xIn for 1 second

30 xIn for 10 second

4 xIn continuously

E9 Contact performance &

endurance tests

IEC60255-14,15

IEC60255-23

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 60 Issue 1

Electromagnetic Compatibility R1 Electrical fast Transient/Burst

(Relay operational)

IEC60255-22-4

IEC601000-4-4

Class IV-4.0kv All Circuits.

1 minute each polarity

R2 Oscillatory Waves

1 Mhz Burst

(Relay operational)

IEC60255-22-1 Class III

longitudinal 2.5 kVpeak , 2sec between

independent circuits & case earth

transverse 1.0 kVpeak , 2sec across

terminals of the same circuit

R3 Electrostatic Discharge

(Relay operational )

IEC60255-22-2 Class III

15kV air discharge with cover in place , 8 kV

contact with cover removed - 10 discharges ,

both polarities at 1 sec intervals

R4 Conducted Disturbance

RF fields

(Relay operational)

IEC61000-4-6 0.15 to 80 Mhz

Severity Level 10Vrms

+sweeps 0.05-0.15MHz & 80-100MHz

R5 Radiated e-m field

from digital portable telephones

(Relay operational)

ENV 50204 900 & 1890Mhz at 10V/m

R6 Radiated RF e-m field immunity test

(Relay operational)

IEC60255-22-3 Class III test method A

+sweep 500-1000Mhz

or IEC 1000-4-3 80-1000Mhz

severity 10V/m 80% modulated 1 kHz

R7 Surge Immunity capacitively

coupled

(relay operational)

IEC61000-4-5

Class 5

Test level 4

short circuit combination wave generator

1.2uS/50uS open circuit

8uS/20uS short circuit ,+ & - polarity

phase shifting 0~360o ac line phase angle

repetition rate 1 per minute

Power supply, ct & vt circuits –

4kV common mode 2 ohm source

2kV differential mode 12 ohm source

Output relays 42ohm source

Comms 2 ohm screen to earth only

R8 Power Frequency Magnetic Field

(Relay operational)

IEC61000-4-8 1000A/m for 1 sec

100A/m for 1 minute

in each of 3 axes

R9 Power Frequency Interference on

communications circuits

(Relay operational)

EA TS48-5

class 3, Table 2,

Appendix A(i)

For circuit length 100-1000 metres (0.1%

unbalanced)

R10 Power Frequency interference on

other circuits except 50 Hz inputs

(Relay operational)

EATS 48-5

Appendix A(ii)

All output contact circuits.

R11 Pulse Magnetic Field

(Relay operational)

IEC 1000-4-9 6.4/16uS , 1000A/m

R14 Conducted & Radiated RF

Interference Emission

(Relay operational)

EN55022 or

EN55011or

EN50081-2

IEC60255-25

Class A interference limits

R15 Power frequency, conducted

common mode

IEC 1000-4-16

IEC60255-22-7

D.C. to 150kHz Test Level 4

300V at 16 2/3Hz and 50Hz

Weight = Approx 2Kg

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 61 Issue 1

9.8 Housing

Throughout the MR series range a modular housing system has been employed, utilising the latest

high quality UK manufactured industry standard case components. This approach affords

maximum flexibility for both the relay scheme designer and the maintenance engineer. The relay

modules are fully withdrawable for ease of maintenance and where applicable incorporate

automatic short-circuiting CT connections to avoid dangerous open circuit CT overvoltages. A

clear plastic front cover is provided for inspection purposes.

MRI units are supplied in standard height (179mm≅7in.) cases, complying with IEC 297 size 4U.

The rigid case wall is manufactured from a single sheet of hot dipped galvanized steel coated

externally with Plastisol PVC and internally with a low gloss alkyd paint finish. This construction

technique provides improved thermal transfer characteristics over plastic walled cases and

combines exceptional corrosion and flame resilience with good electromagnetic and electrostatic

screening properties allowing many relays to be freely situated in close proximity and hazardous

environments. When the relay is inserted a leaf spring along the top edge of the module makes

contact with a solidly bonded nickel plated steel strip on the interior of the case, providing

excellent earth continuity. This strip is brought out at the rear of the case, above the terminal block,

where it forms a separate earthing terminal. A rigid front mounting flange is provided allowing the

entire range of standard cases to be flush mounted without alteration. These flanges are also used to

mount the relay inspection cover which is secured by thumbscrews. Securely bonded channels can

be provided on the top and bottom surfaces toward the rear of the case allowing large rigid

assemblies to be created by the use of joining strips located in these channels.

This uniform but highly flexible housing system integrates excellent mechanical strength with good

electrical practice in industry standard sizes.

PANEL CUT OUT FLUSH

MOUNTING FIXING DETAILS

4 HOLES 4.4mm DIAMETER

99

168 159

52 23.5

10

97

45

PUSH BUTTON

PROJECTION 10mm

NOT SHOWN TO SCALE

103

177

212

Clearance

25 min

157

32

OPTIONAL

OPTIONAL

OPTIONAL

Min28

NOTE Minimum gap between vertical

spacing is required in order to

withdraw relay from the case above.

178

Required to open caseSIZE 100 CASE

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 62 Issue 1

9.9 Terminal Connection Details

The rear terminal block accepts both pre-insulated screw and push-on blade type connectors which

may be used singly or in combination. Each terminal has 1 screw type and 2 blade type connectors.

Screw: Each connection uses a 4mm (M4) screw outlet and accepts standard

L-shaped ring type connectors designed for 4mm screws.

(Reccomended for 5A Rated relays)

Blade: Each connection facilitates 2 pre-insulated push-on blades 4.8mm wide

0.8mm thick complying with BS5057.

Combinations: Each terminal will accept either;

2 ring type connectors

or 2 push-on blade type connectors

or 1 ring type connector & 1 push-on blade type connector

1

3

5

7

9

11

13

15

17

19

21

23

25

27

2

4

6

8

10

12

14

16

18

20

22

24

26

28

Earth

Rear terminal block connections.

Each terminal

1 screw &2 spade

29

31

33

35

37

39

41

43

45

47

49

51

53

55

30

32

34

36

38

40

42

44

46

48

50

52

54

56

All information subject to change without notice

Publication number Issue 1

MRI (Mk3) Technical Manual P&B Engineering

20/7/99 Page 63 Issue 1

10. Order Form

Digital Overcurrent & Earth Fault Relay MRI

MRI

3 Phase Overcurrent I

3 Phase Overcurrent, Directional ID

3 Phase Overcurrent & Earth Fault IE

3 Phase Overcurrent & Earth Fault ( spec ) IEK

3 Phase O/C & E/F, Directional IED

3 Phase O/C & E/F, with E/F Directional IEX

Earth Fault Only E

Earth Fault Directional ED

Earth Fault Directional Low Setting Range EX

Rated Current, 1A 1

5A 5

Directional Measurement Voltage, 100 V (110V) 1

230 V (240V) 2

400 V (415V) 4

System Earthing Isolated/Arc Suppression I

Solid/Resistive S

Data Communications, NETWORK GOLD G

MODBUS M

Housing, 19" Rack A

Flush Mounting D

PBSI Ltd Trading as

P&B ENGINEERING

Bell Vue Works,

Boundary Street,

Manchester.

M12 5NG.

Tel: 0161-230-6363

Fax: 0161-230-6464


Recommended