Date post: | 10-Mar-2016 |
Category: |
Documents |
Upload: | carla-karen-ali |
View: | 10 times |
Download: | 0 times |
of 98
LOSA CIRCULAR DE HORMIGON ARMADO
CI 5 5 0 1 7 3 5 PT VILLAFUERTE OPORTO ELISEO JAHDIELCI 4 8 8 5 6 2 1 LP SUXO CHIGUA RONALD
ELEMENTO
LOSA CIRCULAR
3.1. CARGAS PERMANENTES
LOSA CIRCULAR MACIZA
LOSA MACIZAREVOQUE CIELO RASO (1)
(1 ) Valores extraidos de la Norma NBE - AE - 88 (*) Valores extraidos de la Norma Chilena NCh 1537 -86
3.2. CARGAS VARIABLES
ELEMENTO
LOSA
3.3. CARGAS MAYORADAS
2. PRE - DIMENSIONAMIENTO
3. CARGAS
COEFICIENTES DE MAYORACION EN CONDICIONES DE
CONTROL NORMAL
ELEMENTO
LOSA CIRCULAR
DIAMETRO DE LA LOSA [m]RADIO DE LA LOSA [m]CARGA TOTAL [KN/m2]
TABLA N 1 - CALCULO DE SOLICITACIONES
0.00.51.01.52.02.53.03.54.0
4. SISTEMA ESTATICO Y SOLICITACIONES
4. SOLICITACIONES A FLEXION Y CORTE
DISTANCIA DE CALCULO (r) [m]
4.55.0
1. GEOMETRIA DE LA LOSA
BASE (b)ALTURA (h)
ALTURA UTIL (d)
2. MATERIALES
MATERIAL
HORMIGONACERO
DEFORMACION
PLANILLA DE CALCULO
LOSA
1
1. GEOMETRIA DE LA LOSA
BASE (b)ALTURA (h)
ALTURA UTIL (d)
2. MATERIALES
5. DIMENSIONAMIENTO EN ESTADOS LIMITES ULTIMOS
5.1. DIMENSIONAMIENTO A FLEXION
Recubrimiento Mecanico
5.2. DIMENSIONAMIENTO A CORTE
Recubrimiento Mecanico
MATERIAL
HORMIGONACERO
DEFORMACION
PLANILLA DE CALCULO
LOSA
1
LOSA CIRCULAR DE HORMIGON ARMADO
VILLAFUERTE OPORTO ELISEO JAHDIELSUXO CHIGUA RONALD
CRITERIO h [cm]
10 31.42 25.000 1817.453
3.1. CARGAS PERMANENTES
LOSA CIRCULAR MACIZA
25 4.50REVOQUE CIELO RASO (1) - 16 0.16
TOTAL 4.657(1 ) Valores extraidos de la Norma NBE - AE - 88 (*) Valores extraidos de la Norma Chilena NCh 1537 -86
3.2. CARGAS VARIABLES
OBSERVACIONES
5.50 Oficinas Publicas, tiendas
3.3. CARGAS MAYORADAS
1.5
1.6
PRE - DIMENSIONAMIENTO
Diametro [m] Perimetro [m]h adop [cm]
lx /40[m]Perimetro/180[m]
PESO UNITARIO [Kg/m3]
CARGA [Kg/m2]
CARGA [KN/m2]
CARGA [KN/m2]
G
Q
4.66 6.99 5.50 8.80 10.16
DIAMETRO DE LA LOSA [m] 10.00 LOSA SIMPLEMENTE APOYADA EN TODO SU CONTORNORADIO DE LA LOSA [m] 5.00 Las solicitaciones situados en cada punto a una distancia r del centro seran:CARGA TOTAL [KN/m2] 15.79
Donde: Mr = Momento radialv = Coeficiente de PoissMt = Momento Tangenciala = Radio del contorno ciQ = Reaccion de Borde
RADIO DE LA LOSA (a)
TABLA N 1 - CALCULO DE SOLICITACIONES TABLA N 2 - RESUMEN DE RESULTADOS
81.392 81.392 0.000 0.0 81.392 -80.579 80.924 3.946 5.0 20.34878.137 79.518 7.893 5.0 - 39.46374.067 77.175 11.83968.370 73.894 15.78561.044 69.677 19.73252.091 64.522 23.67841.510 58.430 27.62429.301 51.401 31.570
CARGA PEMANENTE CARACTERISTICA
(Gk) [KN/m2]
CARGA PEMANENTE DE DISEO (Gd) [KN/m2]
CARGA VARIABLE
CARACTERISTICA (Qk)
[KN/m2]
CARGA VARIABLE DE DISEO (Qd) [KN/m2]
CARGA TOTAL CARACTERISTI
CA (PK) [KN/m2]
SISTEMA ESTATICO Y SOLICITACIONES
SOLICITACIONES A FLEXION Y CORTE
de Poisson relativo a las deformaciones elasticas bajo tensiones normales de utilizacion puede tomarse igual a 0.2, si bien en ciertos calculos pueden despreciarse el efecto de la dilatacion trasversal.
COEFICIENTE DE POISSON (v)
Reemplazando los valores en las formulas anteriores, las solicitaciones a flexion y a corte a una distacion "r" del centro de la losa seran:
Momento Radial (Mr) [KN-m/m]
Momento Tangencial (Mt) [KN-
m/m]
Esfuerzo de Corte (V) [KN/m]
DISTANCIA DE CALCULO
MAXIMO (r) [m]
Momento Tangencial (Mt) [KN-m/m]
Esfuerzo de Corte
(V) [KN/m]
Segn el parrafo 18.8 del libro de HORMIGON ARMADO I - CIV 209, para no calcular vigas a torsion, seran despreciables los momentos torsores producidos, es una buena practica adoptar para el calculo de esfuerzos en losas, el metodo de calcular el momento del vano de la losa como si la rigidez a torsion de la viga fuese nula y calcular el empotramiento de la losa en la viga para un momento flector igual a un 25% del adoptado para el vano. Esto hace que no se trasfieran los esfuerzos torsionales de losa a viga como esfuerzo distribuido, ya que aumentaran los giros en las vigas.
2 2316d
rPM v a r
2 23 1 316d
tPM a v r v
2dP rV
25%apoyo vanoM M
15.465 43.434 35.5170.000 34.530 39.463
1. GEOMETRIA DE LA LOSA
1 [m]0.18 [m]0.15 [m]0.03 [m]
DESIGNACION
H - 25 25 1.5 16.667 3.60B-420-S 420 1.15 365.217
E=200000 [Mpa] 1.826
PLANILLA DE CALCULO
1 2 3 5 6
SECCION Md z[KN-m/m] [m]TRAMO (RADIAL) 81.39 0.21705 0.30967 DOM 3 0.87613 0.13142TRAMO (TANG) 81.39 0.21705 0.30967 DOM 3 0.87613 0.13142
APOYO A 20.35 0.05426 0.06977 DOM 2A 0.97209 0.14581APOYO B 20.35 0.05426 0.06977 DOM 2A 0.97209 0.14581
1. GEOMETRIA DE LA LOSA
1 [m]0.18 [m]0.15 [m]
0.03 [m]
Segn el parrafo 18.8 del libro de HORMIGON ARMADO I - CIV 209, para no calcular vigas a torsion, seran despreciables los momentos torsores producidos, es una buena practica adoptar para el calculo de esfuerzos en losas, el metodo de calcular el momento del vano de la losa como si la rigidez a torsion de la viga fuese nula y calcular el empotramiento de la losa en la viga para un momento flector igual a un 25% del adoptado para el vano. Esto hace que no se trasfieran los esfuerzos torsionales de losa a viga como esfuerzo distribuido, ya que aumentaran los giros en las vigas.
DIMENSIONAMIENTO EN ESTADOS LIMITES ULTIMOS
DIMENSIONAMIENTO A FLEXION
RESISTENACIA CARACTERISTI
CA [MPa]
COEFICIENTE DE
MINORACION
RESISTENACIA DE
CALCULO [MPa]
AsMIN Geometrica
[cm2]
=fcd/E
DIMENSIONAMIENTO A CORTE
2CD
1) Md Momento de DiseoMd2)
f bd
3) 1.25 1 1 2
1 YD
4) x d5) 1 0, 46) z d
1 Md7)As ASimplef z
cd 11 min
yd
1 min
f W8)As 0.25 Rotura Agria
f h
9)As 0.002 b h Geometrica
SLL
1'3
CU L CV 1 CDC
'CV CK 1 CD
C
200(5) 1d
A(6) 0,02
bd0,15(7) V 100 f dbo
Ndf f ; 1; 0; 1A
DESIGNACION
H - 25 25 1.5 16.67B-420-S 420 1.15 365.22
E=200000 [Mpa] 1.826
PLANILLA DE CALCULO
1 2 3 4 5 6
SECCION Vd AsL L[KN/m] [cm2/m]APOYO A 39.46 100 15 4.04 2 0.00269APOYO B 39.46 100 15 4.04 2 0.00269
RESISTENACIA CARACTERISTI
CA [MPa]
COEFICIENTE DE
MINORACION
RESISTENACIA DE
CALCULO [MPa]
=fcd/E
b [cm]
d [cm]
LOSA SIMPLEMENTE APOYADA EN TODO SU CONTORNOLas solicitaciones situados en cada punto a una distancia r del centro seran:
Mt = Momento Tangencial
TABLA N 2 - RESUMEN DE RESULTADOS
CENTROBORDEBORDE
de Poisson relativo a las deformaciones elasticas bajo tensiones normales de utilizacion puede tomarse igual a 0.2, si bien en ciertos calculos pueden despreciarse el efecto de la dilatacion
Reemplazando los valores en las formulas anteriores, las solicitaciones a flexion y a corte a una distacion "r" del centro de la
OBSERVACION
Segn el parrafo 18.8 del libro de HORMIGON ARMADO I - CIV 209, para no calcular vigas a torsion, seran despreciables los momentos torsores producidos, es una buena practica adoptar para el calculo de esfuerzos en losas, el metodo de calcular el momento del vano de la losa como si la rigidez a torsion de la viga fuese nula y calcular el empotramiento de la losa en la viga para un momento flector igual a un 25% del adoptado para el vano. Esto hace que no se trasfieran los esfuerzos torsionales de losa a viga como esfuerzo distribuido, ya que aumentaran los giros en
25%apoyo vanoM M
PLANILLA DE CALCULO
7 8 9 10As As min As
[cm2/m] [cm2/m] [cm2/m] [cm2/m]16.96 3.60 16.96 16.16 12 c/ 716.96 0.00 16.96 16.16 12 c/ 73.82 3.60 4.04 8.08 12 c/ 143.82 3.60 4.04 8.08 12 c/ 14
AsADOPTADO
1 YD
4) x d5) 1 0, 46) z d
1 Md7)As ASimplef z
cd 11 min
yd
1 min
f W8)As 0.25 Rotura Agria
f h
9)As 0.002 b h Geometrica
SLL
1'3
CU L CV 1 CDC
'CV CK 1 CD
C
200(5) 1d
A(6) 0,02
bd0,15(7) V 100 f dbo
Ndf f ; 1; 0; 1A
PLANILLA DE CALCULO
7 8 9fcv Vcu
[MPa] [KN/m]25.00 56.65 CUMPLE25.00 56.65 CUMPLE
OBSERVACION Vcu > Vd
12 c /14 R 12 c /14 D 12 7.0 12 c /14 R 12 c /14 D 12 7.0
12 14.012 14.0
ESPACIAMIENTO [cm]
MEMORIA DE CALCULO
DATOS DE PROYECTO
MATERIAL DESIGNACION
HORMIGON 16.667 H - 25 25 1.50ACERO 365.217 B-420-S 420 1.15
Algunos de los datos son adoptados por criterio propio:
DESCRIPCION DEL DATO SIMBOLO VALORAltura total del muro [m] H 6.5TERRENO N 1 - ConglomeradoPeso Volumetrico o Densidad [KN/m3] 1 18Angulo de Friccion Interna () 1 31Altura del conglomerado [m] H1 3.5TERRENO N 2 - ArcillaPeso Volumetrico o Densidad [KN/m3] 2 17Angulo de Friccion Interna () 2 20Cohesin [Kpa] c 23Altura de la arcilla [m] H2 3.0
Presion admisible del terreno [Kpa] 200.0Sobrcarga del terreno [KN/m2] q 10.0Angulo del talud de terreno [] 15.0Friccion entre el muro y el suelo 13.0Angulo de inclimacion del muro [] 90.0
Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de indentidad de los estudiantes proyectistas.
1. MATERIALESRESISTENACIA DE CALCULO
[MPa]
RESISTENACIA CARACTERISTIC
A [MPa]
COEFICIENTE DE
MINORACION
2. DATOS GENERALES
adm
3. PREDIMENSIONAMIENTO
Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.
A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:
Con base a estos criterios podemos predimensionar los elementos del muro de contencion:
DESCRIPCION VALORAltura total del muro [m] 6.50 6.5Base [m] 4.00 4Altura de talon y puntera [m] 0.65 0.65Ancho del muro cortina [m] 0.65 0.65Longitud de puntera [m] 1.35 1.35Longitud de talon [m] 2.00 2
Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.
0,30
1,35 0,65 2,00
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []
q = 10 [KN/m]
3,50
3,00
6,50
Donde:
Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos de los dos terrenos.
DATOS: TERRENO N 1 TERRENO N 2 18 0.314159265 31 0.541052068 15.0 0.261799388 13.0 0.226892803 90.0 1.570796327
0.734735781 3.717583409 h 0.198 h v 0.046 v
4. COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION
4.1 CALCULO DE EMPUJES SOBRE EL MURO
Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un proceso iterativo antes de disear el mismo.Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las caracteristicas del proyecto.Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo. La ecuaciones que se consideran en estos casos son:
= Es el coeficiente activo y viene dado por
4.2 CALCULO DE LOS COEFICIENTES ACTIVOS
0,30
1,35 0,65 2,00
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []
q = 10 [KN/m]
3,50
3,00
6,50
21
2TsenE H q H
sen
2
2
2 1
sen
sen sensen
sen sen
cv h tg
2 2h v
0.203
q [KN/m2] 10.0
Ley de Presiones para el terreno N 1
Ley de Presiones para el terreno N 2
Ley de Presiones para la sobrecarga
Ley de Presiones que produce la cohesionLa cohesion no se considera por no existir un metodo exacto que garantice su aplicacin (CALAVERA)
x [m] Pq [KN/m2] Pc [KN/m2]
0.00 0.000 2.100.25 0.913 2.100.50 1.826 2.100.75 2.738 2.101.00 3.651 2.101.25 4.564 2.101.50 5.477 2.101.75 6.389 2.102.00 7.302 2.102.25 8.215 2.102.50 9.128 2.102.75 10.040 2.103.00 10.953 2.103.25 11.866 2.103.50 12.779 2.103.50 17.160 2.82 0.003.75 18.317 2.82 0.004.00 19.475 2.82 0.004.25 20.632 2.82 0.004.50 21.790 2.82 0.00
4.2 CALCULO DEL DIAGRAMA DE PRESIONES
Para el calculo de las presiones sobre el muro debemos diferenciar entre los dos tipos de terreno, por consiguiente se tendran las siguientes leyes de presiones:
P1 [KN/m2]
P2 [KN/m2]
1 1 1 0 3.5P x x
2 2 1 2 23.5 3.5 6P x x
0 6qsenP q x
sen
2 3.5 6cP C x
4.75 22.948 2.82 0.005.00 24.105 2.82 0.005.25 25.263 2.82 0.005.50 26.420 2.82 0.005.75 27.578 2.82 0.006.00 28.736 2.82 0.006.25 29.893 2.82 0.006.50 31.051 2.82 0.00
La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:
En la figura se muestra el diagrama de presiones total:
4.3. CALCULO DEL EMPUJE TOTAL, HORIZONTAL Y VERTICAL
El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el estudio:
ADP = Area de cada diagrama de presiones
Ei = Empuje activo correspondiente a cada uno de los diagramas de presiones.yi = Posicion del centroide del area de los diagramas de presiones.
T iDPE A E
ii i DP
T T
A yE yy
E A
19.98
Presion ejercidapor el terreno
0,30
6,50
3,50
3,00
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
+
Presion ejercidapor la sobrecarga
Conglomerado
Arcilla
x
=
DIAGRAMA DEPRESIONES
TOTALES
12.779
17.160
2.10
2.10
2.82
2.8231.051
2.01
14.88
33.871
Forma BASE TRIANGULAR 3.500 12.779 4.167 22.36
RECTANGULAR 3.000 17.160 1.500 51.479TRIANGULAR 3.000 13.891 1.000 20.84
RECTANGLUAR 3.500 2.100 4.750 7.350RECTANGULAR 3.000 2.820 1.500 8.460RECTANGULAR 3.000 0.000 1.500 0.000
110.49Las componentes del empuje total, horizontal y verical viene dado por:
Reemplazando los valores tenemos:
E 110.488 [KN/m]Eh 106.723 [KN/m]Ev 28.596 [KN/m]
y 2.16 [m]
Se realizara respecto al punto a (ver figura arriba)
ZONA
ZAPATA 2.600 25.000 65.000 2.000LOSA 1.755 25.000 43.875 1.850
LOSA FRONTAL 1.024 25.000 25.594 1.580
4.700 17.000 79.900 3.000
7.000 18.000 126.000 3.000
0.473 18.000 8.505 0.675
ALTURA
yi
AREA
El empuje se encuntra a una distancia de la base de:
4.4. CALCULO DEL PESO DEL MURO, TIERRAS, Y MOMENTO
VOLUMEN [m3]
DENSIDAD [KN/m3]
PESO [KN]
DISTANCIA DEL c.d.g AL
PUNTO A [m]
RELLENO SOBRE EL TALON 1RELLENO SOBRE EL TALON 2RELLENO SOBRE LA PUNTERA
cosh T
v T
E E
E E sen
19.98
Presion ejercidapor el terreno
0,30
6,50
3,50
3,00
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
+
Presion ejercidapor la sobrecarga
Conglomerado
Arcilla
x
=
DIAGRAMA DEPRESIONES
TOTALES
12.779
17.160
2.10
2.10
2.82
2.8231.051
2.01
14.88
33.871
0,30
6,50
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
Conglomerado
Arcilla
E
Eh
Ev
0,65
A
2,16
P [KN] 348.874 M [KN-m](*) El calculo se ha realizado tomando un ancho de muro de 1 [m]
Primeramente calculamos la excentricidad ep respecto al centro del cimiento:
M[KN-m] 875.048P [KN] 348.874B [m] 4.000
Reemplazando valores tenemos:xp [m] 2.51
ep [m] 0.508
La excentricidad ev respecto al centro del cimiento, de la componente vertical del empuje resulta:
ev [m] 0.000
Dado que N, resultante de las fuerzas normales al cimiento tiene un valor:
N [KN] 377.470
Finalmente tomando momentos respecto al centro del cimiento se obtine:
en [m] -0.141
VERIFICAMOS
Asumiendo una distribucion de tensiones lineal, las tenciones en en los bordes extremos son:
[KN/m2] 74.341 [KN/m2]
Se compruebaa que no supera la tenasion admisible del terreno.
4.5. VERIFICACION DE PRESIONES AL TERRENO
2p pBe x p
Mx
P
vN P E
p h v vn
P e E h E ee
N
0.142[ ] 0.67[ ]6nBe m m
2
6 nA
NeNB B
2
6 nB
NeNB B
Se debe cumplir con la condicion:
Csd 2.041
Se debe cumplir con la condicion: Me [KN-m] 875.048Mv [KN-m] 230.703
Csd 3.793
4.6. SEGURIDAD AL DESLIZAMIENTO
4.7. SEGURIDAD AL VUELCO
1.5sdNCE
1.8esvv
MCM
MEMORIA DE CALCULO
Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de
Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.
A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:
Con base a estos criterios podemos predimensionar los elementos del muro de contencion:
0,30
1,35 0,65 2,00
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []
q = 10 [KN/m]
3,50
3,00
6,50
Compomente Horizontal
Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos
TERRENO N 217 0.29720 0.349
15.0 0.26213.0 0.22790.0 1.571
0.88302222 3.3270.2650.061
COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION
Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un
Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las
Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo.
0,30
1,35 0,65 2,00
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []
q = 10 [KN/m]
3,50
3,00
6,50
21
2TsenE H q H
sen
2
2
2 1
sen
sen sensen
sen sen
0.272
Ley de Presiones para el terreno N 1
Ley de Presiones para el terreno N 2
Ley de Presiones para la sobrecarga
Ley de Presiones que produce la cohesionLa cohesion no se considera por no existir un metodo exacto que garantice su aplicacin (CALAVERA)
2.100 0,0.2099920040251743.013 0.25,0.3012685190261253.925 0.5,0.3925450340270764.838 0.75,0.4838215490280275.751 1,0.5750980640289786.664 1.25,0.6663745790299297.577 1.5,0.757651094030888.489 1.75,0.8489276090318319.402 2,0.940204124032782
10.315 2.25,1.0314806390337311.228 2.5,1.1227571540346812.140 2.75,1.2140336690356413.053 3,1.3053101840365913.966 3.25,1.3965866990375414.879 3.5,1.48786323.5,1.7159688824595719.980 3.5,1.9979532809254921.137 3.75,2.11371 3.75,1.8317286880223222.295 4,2.22947289 4,1.9474884935850723.452 4.25,2.34523 4.25,2.0632482991478224.610 4.5,2.46099254.5,2.17900810471057
Para el calculo de las presiones sobre el muro debemos diferenciar entre los dos tipos de terreno, por
PT [KN/m2]
25.768 4.75,2.57675 4.75,2.2947679102733226.925 5,2.69251211 5,2.4105277158360728.083 5.25,2.80827 5.25,2.5262875213988229.240 5.5,2.92403175.5,2.6420473269615730.398 5.75,3.03979 5.75,2.7578071325243131.556 6,3.15555133 6,2.8735669380870632.713 6.25,3.27131 6.25,2.9893267436498133.871 6.5,3.38707096.5,3.10508654921256
La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:
El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el
= Empuje activo correspondiente a cada uno de los diagramas de presiones.
19.98
Presion ejercidapor el terreno
0,30
6,50
3,50
3,00
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
+
Presion ejercidapor la sobrecarga
Conglomerado
Arcilla
x
=
DIAGRAMA DEPRESIONES
TOTALES
12.779
17.160
2.10
2.10
2.82
2.8231.051
2.01
14.88
33.871
93.18677.21920.83734.91112.6890.000
238.841Las componentes del empuje total, horizontal y verical viene dado por:
130.00081.16940.438
239.700
378.000
5.741
Ayi
MOMENTO [KN-m]
19.98
Presion ejercidapor el terreno
0,30
6,50
3,50
3,00
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
+
Presion ejercidapor la sobrecarga
Conglomerado
Arcilla
x
=
DIAGRAMA DEPRESIONES
TOTALES
12.779
17.160
2.10
2.10
2.82
2.8231.051
2.01
14.88
33.871
0,30
6,50
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
Conglomerado
Arcilla
E
Eh
Ev
0,65
A
2,16
875.048
Primeramente calculamos la excentricidad ep respecto al centro del cimiento:
La excentricidad ev respecto al centro del cimiento, de la componente vertical del empuje resulta:
CUMPLE
Asumiendo una distribucion de tensiones lineal, las tenciones en en los bordes extremos son:
114.394
CUMPLE
2
6 nB
NeNB B
CUMPLE
CUMPLE
0,0.419984008050348 0,0.4199840080503480.25,0.419984008050348 0.25,0.602537038052250.5,0.419984008050348 0.5,0.7850900680541520.75,0.419984008050348 0.75,0.9676430980560541,0.419984008050348 1,1.150196128057961.25,0.419984008050348 1.25,1.332749158059861.5,0.419984008050348 1.5,1.515302188061761.75,0.419984008050348 1.75,1.697855218063662,0.419984008050348 2,1.880408248065562.25,0.419984008050348 2.25,2.062961278067472.5,0.419984008050348 2.5,2.245514308069372.75,0.419984008050348 2.75,2.428067338071273,0.419984008050348 3,2.610620368073173.25,0.419984008050348 3.25,2.793173398075083.5,0.419984008050348 3.5,0 3.5,2.97572642807698
3.75,0.563968796931843 3.75,0 3.75,4.227426172976494,0.563968796931843 4,0 4,4.458945784101994.25,0.563968796931843 4.25,0 4.25,4.690465395227484.5,0.563968796931843 4.5,0 4.5,4.92198500635298
4.75,0.563968796931843 4.75,0 4.75,5.153504617478485,0.563968796931843 5,0 5,5.385024228603985.25,0.563968796931843 5.25,0 5.25,5.616543839729485.5,0.563968796931843 5.5,0 5.5,5.848063450854975.75,0.563968796931843 5.75,0 5.75,6.079583061980476,0.563968796931843 6,0 6,6.311102673105976.25,0.563968796931843 6.25,0 6.25,6.542622284231476.5,0.563968796931843 6.5,0 6.5,6.77414189535696
MEMORIA DE CALCULO
DATOS DE PROYECTO
MATERIAL DESIGNACION
HORMIGON 16.667 H - 25 25 1.50ACERO 365.217 B-420-S 420 1.15
Algunos de los datos son adoptados por criterio propio:
DESCRIPCION DEL DATO SIMBOLO VALORAltura total del muro [m] H 6.5TERRENO N 1 - ConglomeradoPeso Volumetrico o Densidad [KN/m3] 1 18Angulo de Friccion Interna () 1 31Altura del conglomerado [m] H1 3.5TERRENO N 2 - ArcillaPeso Volumetrico o Densidad [KN/m3] 2 17Angulo de Friccion Interna () 2 20Cohesin [Kpa] c 23Altura de la arcilla [m] H2 3.0
Presion admisible del terreno [Kpa] 200.0Sobrcarga del terreno [KN/m2] q 10.0Angulo del talud de terreno [] 15.0Friccion entre el muro y el suelo 13.0Angulo de inclimacion del muro [] 90.0
Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de indentidad de los estudiantes proyectistas.
1. MATERIALESRESISTENACIA DE CALCULO
[MPa]
RESISTENACIA CARACTERISTIC
A [MPa]COEFICIENTE DE
MINORACION
2. DATOS GENERALES
adm
3. PREDIMENSIONAMIENTO
Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.
A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:
Con base a estos criterios podemos predimensionar los elementos del muro de contencion:
DESCRIPCION VALORAltura total del muro [m] 6.50 6.5Base [m] 4.03 4Altura de talon y puntera [m] 0.65 0.65Ancho del muro cortina [m] 0.65 0.65Longitud de puntera [m] 1.34 1.35Longitud de talon [m] 2.04 2
Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.
Donde:
Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos de los dos terrenos.
DATOS: TERRENO N 1 TERRENO N 2 18 0.314159265 31 0.541052068 15.0 0.261799388 13.0 0.226892803 90.0 1.570796327
0.734735781 3.717583409 h 0.198 h v 0.046 v
4.8. COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION
4.8.1 CALCULO DE EMPUJES SOBRE EL MURO
Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un proceso iterativo antes de disear el mismo.Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las caracteristicas del proyecto.Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo. La ecuaciones que se consideran en estos casos son:
= Es el coeficiente activo y viene dado por
4.8.2 CALCULO DE LOS COEFICIENTES ACTIVOS
21
2TsenE H q H
sen
2
2
2 1
sen
sen sensen
sen sen
cv h tg
2 2h v
0.203
q [KN/m2] 10.0
Del diagrma de presiones:
x [m] Pq [KN/m2] Pc [KN/m2]
0.00 0.000 2.100.50 1.826 2.101.00 3.651 2.101.50 5.477 2.102.00 7.302 2.102.50 9.128 2.103.00 10.953 2.103.50 12.779 2.103.50 17.160 2.82 0.004.00 19.475 2.82 0.004.50 21.790 2.82 0.005.00 24.105 2.82 0.005.50 26.420 2.82 0.005.85 28.041 2.82 0.00
La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:
5. DIMENSIONAMIENTO DEL MURO COMO ESTRUCTURA DE HORMIGON ARMADO
Calculamos el empuje a nivel del muro cortina para disear el muro, ya que se considera que la flexion del muro cortina es producido por la componente horizontal del empuje activo.
P1 [KN/m2]
P2 [KN/m2]
5.1. CALCULO DEL EMPUJE TOTAL, HORIZONTAL Y VERTICAL
El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el estudio:
ADP = Area de cada diagrama de presiones
T iDPE A E
ii i DP
T T
A yE yy
E A
En la figura se muestra el diagrama de presiones total:
Forma BASE EMPUJETRIANGULAR 3.500 12.779 3.517 22.36
RECTANGULAR 2.350 17.160 1.175 40.325TRIANGULAR 2.350 10.881 0.783 12.79
RECTANGLUAR 3.500 2.100 4.100 7.350RECTANGULAR 2.350 2.820 1.175 6.627RECTANGULAR 2.350 0.000 1.175 0.000
89.45Las componentes del empuje total, horizontal y verical viene dado por:
Reemplazando los valores tenemos:
E 89.450 [KN/m]Eh 86.402 [KN/m]Ev 23.151 [KN/m]
Componente Horizontal con el cual se calculara el Momento de DiseoEl empuje se encuntra a una distancia de talon de:
y 1.94 [m]
La ley de momentos flecotres a los largo del muro, viene dado por la siguiente relacion:
x [m]
0.00 0.000 00.50 23.0411.00 46.0811.50 69.122
Ei = Empuje activo correspondiente a cada uno de los diagramas de presiones.yi = Posicion del centroide del area de los diagramas de presiones.
ALTURA
yi
5.2. CALCULO DEL MOMENTO FLECTOR Y ESFUERZO DE CORTE
Md [KN-m/m]
Vd [KN/m]
ii i DP
T T
A yE yy
E A
cosh T
v T
E E
E E sen
13d f h
M E x 1.6f d hV E
0,30
6,50
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
Conglomerado
Arcilla EEh
Ev
0,65
A
Md Vd
269.575[KN-m/m]
86.402[KN/m]
1,94
2.00 92.1622.50 115.2033.00 138.2433.50 161.2844.00 184.3244.50 207.3655.00 230.4065.50 253.4465.85 269.575 86.402
1. GEOMETRIA DE LA LOSA
BASE (b) 1 [m]ALTURA (h) 0.65 [m]
ALTURA UTIL (d) 0.60 [m]0.05 [m]
2. MATERIALES
MATERIAL DESIGNACION
HORMIGON H - 25 25 1.5 16.667ACERO B-420-S 420 1.15 365.217
DEFORMACION E=200000 [Mpa] 1.826
3. CUANTIA MINIMA
12.36 13.00
5.3. DISEO A FLEXION
Recubrimiento Mecanico
RESISTENACIA CARACTERISTICA
[MPa]COEFICIENTE DE
MINORACIONRESISTENACIA DE CALCULO
[MPa]
=fcd/E
AsMIN Mecanica [cm2]
AsMIN Geometrica [cm2]
2CD
1) Md Momento de DiseoMd2)
f bd
3) 1.25 1 1 2
1 YD
4) x d5) 1 0,46) z d
1 Md7)As ASimplef z
cd 11 min
yd
1 min
f W8)As 0.25 Rotura Agria
f h
9)As 0.002 b h Geometrica
0,30
6,50
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
Conglomerado
Arcilla EEh
Ev
0,65
A
Md Vd
269.575[KN-m/m]
86.402[KN/m]
1,94
Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica minima para secciones sometidas a flexion simple o compuesta segn la EHE.
Us = Capacidad mecanica del aceroUc = Capacidad mecanica del hormigon
Reemplazando datos tenemos: Us 458.95 [KN]Uc 10833.33 [KN]
0.04Uc 433.33 [KN]
CUMPLE
Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propiadel hormigon, efectos que no suelen tenerse en cuenta en el calculo.
ARMADURA VERTICAL La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.
Asv [cm2] 3.77 12 c/ 20
3. VERIFICACION DE CUANTIAS MINIMAS
3.1. CUANTIA MECANICA MINIMA
3.1. CUANTIA MECANICA MINIMA
0.04s cU U
s s ydU A f c c cdU A f
0.04s cU U
ARMADURA VERTICAL La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004
Ash [cm2] 6.50 10 c/ 20
RESUMEN DE RESULTADOS
ARMADURA LONGITUDINAL TRASDOS 12 c/ 9ARMADURA LONGITUDINAL INTRADOS 12 c/ 20
ARMADURA TRASVERSAL TRASDOS 10 c/ 20ARMADURA TRASVERSAL INTADOS 10 c/ 20
La distribucion de presiones sobre el talon se indica en la siguiente figura
Caculamos el peso del terreno por unidad de longitud:
qt 102.95 [KN/m2]
El peso del hormigon por unidad de longitud es:
qt 16.25 [KN/m2]
[KN/m2] 74.341
[KN/m2] 114.394
El momento flector en la seccion D-D' es:
M [KN-m/m] -26.069
Md [KN-m/m] -41.710
Calculando el acero de refuerzo
ARMADURA LONGITUDINAL 12 c/ 9.5ARMADURA TRANSVERSAL (20% AsL) 8 c/ 20
6. DIMENSIONAMIENTO DEL TALON
0,65
1,35 0,65 2,00
D
D
89.71 [KN/m2]
102.95 [KN/m2]
108.813 [KN/m2]
70.602 [KN/m2]
16.25 [KN/m2]
Se llevara la misma armadura del muro o alzado
ARMADURA LONGITUDINAL 12 c/ 9ARMADURA TRANSVERSAL (20% AsL) 10 c/ 20
7. DIMENSIONAMIENTO DE LA PUNTERA
MEMORIA DE CALCULO
Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de
Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.
A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:
Con base a estos criterios podemos predimensionar los elementos del muro de contencion:
Compomente Horizontal
Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos
TERRENO N 217 0.29720 0.349
15.0 0.26213.0 0.22790.0 1.571
0.88302222 3.3270.2650.061
COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION
Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un proceso
Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las
Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo. La
2
2
2 1
sen
sen sensen
sen sen
0.272
2.100 2.100 0,0 0,0.4199840080503483.925 3.925 0.5,0.182553030001902 0.5,0.4199840080503485.751 5.751 1,0.365106060003804 1,0.4199840080503487.577 7.577 1.5,0.547659090005706 1.5,0.4199840080503489.402 9.402 2,0.730212120007608 2,0.419984008050348
11.228 11.228 2.5,0.912765150009511 2.5,0.41998400805034813.053 13.053 3,1.09531818001141 3,0.41998400805034819.260 14.879 3.5,1.27787121001332 3.5,0.41998400805034819.260 2.820 3.5,0 4,0.56396879693184322.295 2.820 4,0 4.5,0.56396879693184324.610 2.820 4.5,0 5,0.56396879693184326.925 2.820 5,0 5.5,0.56396879693184329.240 2.820 5.5,0 5.85,0.56396879693184330.861 2.820 5.85,0 #REF!
La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:
DIMENSIONAMIENTO DEL MURO COMO ESTRUCTURA DE HORMIGON ARMADO
Calculamos el empuje a nivel del muro cortina para disear el muro, ya que se considera que la flexion del muro cortina es producido por la componente horizontal del empuje activo.
Pt [KN/m2]
El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el
78.65047.38210.01130.1347.7860.000
173.963Las componentes del empuje total, horizontal y verical viene dado por:
Componente Horizontal con el cual se calculara el Momento de Diseo
La ley de momentos flecotres a los largo del muro, viene dado por la siguiente relacion:
1.60 0,0 0,00.5,0.46 5.85,3.456084111076021,0.9216224296202711.5,1.38243364443041
= Empuje activo correspondiente a cada uno de los diagramas de presiones.
Ayi
0,30
6,50
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
Conglomerado
Arcilla EEh
Ev
0,65
A
Md Vd
269.575[KN-m/m]
86.402[KN/m]
1,94
2,1.843244859240542.5,2.304056074050683,2.764867288860813.5,3.225678503670954,3.686489718481084.5,4.147300933291225,4.608112148101355.5,5.068923362911495.85,5.39149121327858
1 2
LOSA SECCIONMd
5.3. DISEO A FLEXION
1 YD
4) x d5) 1 0,46) z d
1 Md7)As ASimplef z
cd 11 min
yd
1 min
f W8)As 0.25 Rotura Agria
f h
9)As 0.002 b h Geometrica
0,30
6,50
q = 10 [KN/m]
? = 18 [KN/m3]f = 31 []
? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]
1,35 0,65 2,00
Conglomerado
Arcilla EEh
Ev
0,65
A
Md Vd
269.575[KN-m/m]
86.402[KN/m]
1,94
LOSA SECCION[KN-m/m]
1TRAMO (RADIAL)0.00 #DIV/0!TRAMO (TANG)0.00
APOYO A 0.00 #DIV/0!APOYO B 0.00 #DIV/0!
Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica
Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propia
La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.
La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004
12 c/ 9.5
0,65
1,35 0,65 2,00
D
D
89.71 [KN/m2]
102.95 [KN/m2]
108.813 [KN/m2]
70.602 [KN/m2]
16.25 [KN/m2]
0,0.4199840080503480.5,0.419984008050348 0.5,0.785090068054152
1,1.150196128057961.5,0.419984008050348 1.5,1.51530218806176
2,1.880408248065562.5,0.419984008050348 2.5,2.24551430806937
3,2.610620368073173.5,0.419984008050348 3.5,2.97572642807698
4,0.5639687969318434.5,0.563968796931843 4.5,0.563968796931843
5,0.5639687969318435.5,0.563968796931843 5.5,0.5639687969318435.85,0.563968796931843 5.85,0.563968796931843
#REF!
3 4 5 6 7 8
x
z As As min
[cm]
[m] [cm2/m] [cm2/m]
#DIV/0! DOM 3 #DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00DOM 3 0.00
DOM 2A #VALUE! 0.00DOM 2A #VALUE! 0.00
9 10As AsADOPTADO
[cm2/m] [cm2/m]#DIV/0! #DIV/0! c/
c/ #VALUE! c/ #VALUE! c/
1. GEOMETRIA DE LA LOSA
BASE (b) 1 [m]ALTURA (h) 0.65 [m]
ALTURA UTIL (d) 0.6 [m]0.05 [m]
2. MATERIALES
MATERIAL DESIGNACION
HORMIGON H - 25 25 1.5ACERO B-420-S 420 1.15
DEFORMACION E=200000 [Mpa]
PLANILLA DE CALCULO
1 2
MURO DISPOSICION Md [KN-m/m]
1LONGITUDINAL 269.57 0.04493
TRANVERSAL Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal
Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica minima para secciones sometidas a flexion simple o compuesta segn la EHE.
Us = Capacidad mecanica del aceroUc = Capacidad mecanica del hormigon
5.3. DIMENSIONAMIENTO A FLEXION
Recubrimiento Mecanico
RESISTENACIA CARACTERISTICA
[MPa]COEFICIENTE DE
MINORACION
=fcd/E
3. VERIFICACION DE CUANTIAS MINIMAS
3.1. CUANTIA MECANICA MINIMA
GQ
2CD
1) Md Momento de DiseoMd2)
f bd
3) 1.25 1 1 2
0.04s cU U
s s ydU A f c c cdU A f
Reemplazando datos tenemos: UsUc
0.04Uc
CUMPLE
Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propiadel hormigon, efectos que no suelen tenerse en cuenta en el calculo.
ARMADURA VERTICAL La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.
Asv [cm2] 3.77 12 c/ 20
ARMADURA VERTICAL La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004
Ash [cm2] 6.50 10 c/ 20
RESUMEN DE RESULTADOS
ARMADURA LONGITUDINAL TRASDOS 12 c/ 9ARMADURA LONGITUDINAL INTRADOS 12 c/ 20
ARMADURA TRASVERSAL TRASDOS 10 c/ 20ARMADURA TRASVERSAL INTADOS 10 c/ 20
DISEO EN ESTADO LIMITE ULTIMO A FLEXION1. GEOMETRIA DE LA LOSA
BASE (b) 1 [m]ALTURA (h) 0.65 [m]
ALTURA UTIL (d) 0.6 [m]0.05 [m]
2. MATERIALES
3.1. CUANTIA MECANICA MINIMA
6.1. DIMENSIONAMIENTO A FLEXION DEL TALON
Recubrimiento Mecanico
0.04s cU U
2CD
1) Md Momento de DiseoMd2)
f bd
3) 1.25 1 1 2
MATERIAL DESIGNACION
HORMIGON H - 25 25 1.5ACERO B-420-S 420 1.15
DEFORMACION E=200000 [Mpa]
PLANILLA DE CALCULO
1 2
MURO DISPOSICION Md [KN-m/m]
1LONGITUDINAL 41.71 0.00695
TRANVERSAL Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal
RESISTENACIA CARACTERISTICA
[MPa]COEFICIENTE DE
MINORACION
=fcd/E
3. CUANTIA MINIMA
16.667 11.87 13.00 7.80365.217
1.826
PLANILLA DE CALCULO
3 4 5 6 7 8 9
x z As Asmin
[cm] [m] [cm2/m] [cm2/m] [cm2/m]0.05748 3.44899 0.97701 0.58620 12.59 11.87 12.57
Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal
Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica minima para secciones sometidas a flexion simple o compuesta segn la EHE.
RESISTENACIA DE
CALCULO [MPa]
AsMIN Mecanica
[cm2]
AsMIN Geometrica Horizontal
[cm2]
AsMIN Geometrica
Vertical [cm2]
AsADOPTADO
2CD
1) Md Momento de DiseoMd2)
f bd
3) 1.25 1 1 2
1 YD
4) x d5) 1 0,46) z d
1 Md7)As ASimplef z
cd1 min
yd
1 min Horizontal
1 min Vertical
TRANS 1
f b h8)As 0.04 Rotura Agria
f
9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal
458.95 [KN]10833.33 [KN]
433.33 [KN]
Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propia
La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.
5.65 12 20.0
La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004
4 10 20.0
DISEO EN ESTADO LIMITE ULTIMO A FLEXION
3. CUANTIA MINIMA
2CD
1) Md Momento de DiseoMd2)
f bd
3) 1.25 1 1 2
1 YD
4) x d5) 1 0, 46) z d
1 Md7)As ASimplef z
cd1 min
yd
1 min Horizontal
1 min Vertical
TRANS 1
f b h8)As 0.04 Rotura Agria
f
9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal
16.666667 11.87 26.00 7.80365.21739
1.826
PLANILLA DE CALCULO
3 4 5 6 7 8 10
x z As Asmin
[cm] [m] [cm2/m] [cm2/m] [cm2/m]
0.00872 0.52320 0.99651 0.59791 1.91 11.87 11.90
Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal 2.37 2.51
RESISTENACIA DE
CALCULO [MPa]
AsMIN Mecanica
[cm2]
AsMIN Geometrica Horizontal
[cm2]
AsMIN Geometrica
Vertical [cm2]
AsADOPTADO
PLANILLA DE CALCULO
9
[cm2/m] 12 c/ 9 12 c /14 R 12 c /14 D
AsADOPTADO
cd1 min
yd
1 min Horizontal
1 min Vertical
TRANS 1
f b h8)As 0.04 Rotura Agria
f
9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal
DISEO EN ESTADO LIMITE ULTIMO A FLEXION
cd1 min
yd
1 min Horizontal
1 min Vertical
TRANS 1
f b h8)As 0.04 Rotura Agria
f
9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal
PLANILLA DE CALCULO
[cm2/m]
12 c/ 9.5 12 c /14 R 12 c /14 D 8 c/ 20
AsADOPTADO
12 9.0
8 20.0
ESPACIAMIENTO [cm]
12 9.5
8 20.0
ITEM: HORMIGON - RESISTECIA CARACTERISTICA 25 [Mpa] - H25UNIDAD: M3
LOSA H o L [m] N Elementos
MURO 5.400 1.000 1 5.40TOTAL 5.40
269.62 5.40
49.93
Area [m2]VOLMUEN DE HORMIGON
[M3]
PESO DE ACERO [Kg]
VOLMUEN DE HORMIGON
[M3]
CUANTIA VOLUMETRI
CA [Kg A/m3 H]
ITEM: ACERO DE DUREZA NATURAL - B 400 SUNIDAD: KG
PLANILLA DE FIERROS
POSICION Longitud [m] Cantidad
1 12 5.800 6.280 11 1 112 10 1.000 3.400 40 1 403 12 6.750 7.230 5 1 54 10 1.000 3.400 30 1 305 12 1.950 2.430 11 1 116 8 1.000 1.320 11 1 117 12 1.000 5.050 11 1 118 12 3.560 5.050 2 1 2
[mm]
Longitud Unitaria
[m]N
ELEMENTOSCantidad
Total
LONGITUDES DE ANCLAJE - PATILLA BASICA - P/UL
d [mm]
6 0.15 0.0600 8 0.16 0.0800 10 0.20 0.1000 12 0.24 0.1200 16 0.32 0.1600 20 0.48 0.2000 25 0.75 0.2500 32 1.23 0.3200
ACERO DE DUREZA NATURAL - B 400 S
0.620 42.8300.620 84.3200.620 22.413 R P0.620 63.240 5 31.4160.620 16.573 4.67 29.3420.400 5.808 4.34 27.2690.620 34.441 4.01 25.1960.620 6.262
TOTAL [Kg] 269.624
Longitud de Anclaje [m]
PATILLA [m]
Peso/U-longitud [Kg/m]
Peso [Kg]
LONGITUDES DE ANCLAJE - PATILLA BASICA - P/UL DIAMETRO DE MANDRIL LONGITUDES DE ANCLAJE [m]
d [mm] d [mm]
0.220 6 2.40 60.400 8 3.20 80.620 10 4.00 100.890 12 4.80 121.580 16 6.40 162.470 20 8.00 203.850 25 10.00 256.310 32 12.80 32
PESO/UL [Kg/m]
RADIO DE CURVATURA
[cm]
LONGITUDES DE ANCLAJE [m]
POSICION I
m
12 4.32 12.00 12.00 15.00 0.1512 7.68 16.00 16.00 15.00 0.1612 12.00 20.00 20.00 15.00 0.2012 17.28 24.00 24.00 15.00 0.2412 30.72 32.00 32.00 15.00 0.3212 48.00 40.00 48.00 15.00 0.4812 75.00 50.00 75.00 15.00 0.7512 122.88 64.00 122.88 15.00 1.23
Lb1 [cm] fyk(/20)
[cm] Lb1 [cm]
Lb-min [cm]
Lb adop [m]
DATOSMURO DE CONTENCIONDIMENSIONAMIENTODISEO FLEXIONPLANILLA DE ACEROS