+ All Categories
Home > Documents > Muro de Contencion

Muro de Contencion

Date post: 10-Mar-2016
Category:
Upload: carla-karen-ali
View: 10 times
Download: 0 times
Share this document with a friend
Description:
diseño de muro de contencion segun EHE

of 98

Transcript
  • LOSA CIRCULAR DE HORMIGON ARMADO

    CI 5 5 0 1 7 3 5 PT VILLAFUERTE OPORTO ELISEO JAHDIELCI 4 8 8 5 6 2 1 LP SUXO CHIGUA RONALD

    ELEMENTO

    LOSA CIRCULAR

    3.1. CARGAS PERMANENTES

    LOSA CIRCULAR MACIZA

    LOSA MACIZAREVOQUE CIELO RASO (1)

    (1 ) Valores extraidos de la Norma NBE - AE - 88 (*) Valores extraidos de la Norma Chilena NCh 1537 -86

    3.2. CARGAS VARIABLES

    ELEMENTO

    LOSA

    3.3. CARGAS MAYORADAS

    2. PRE - DIMENSIONAMIENTO

    3. CARGAS

    COEFICIENTES DE MAYORACION EN CONDICIONES DE

    CONTROL NORMAL

  • ELEMENTO

    LOSA CIRCULAR

    DIAMETRO DE LA LOSA [m]RADIO DE LA LOSA [m]CARGA TOTAL [KN/m2]

    TABLA N 1 - CALCULO DE SOLICITACIONES

    0.00.51.01.52.02.53.03.54.0

    4. SISTEMA ESTATICO Y SOLICITACIONES

    4. SOLICITACIONES A FLEXION Y CORTE

    DISTANCIA DE CALCULO (r) [m]

  • 4.55.0

    1. GEOMETRIA DE LA LOSA

    BASE (b)ALTURA (h)

    ALTURA UTIL (d)

    2. MATERIALES

    MATERIAL

    HORMIGONACERO

    DEFORMACION

    PLANILLA DE CALCULO

    LOSA

    1

    1. GEOMETRIA DE LA LOSA

    BASE (b)ALTURA (h)

    ALTURA UTIL (d)

    2. MATERIALES

    5. DIMENSIONAMIENTO EN ESTADOS LIMITES ULTIMOS

    5.1. DIMENSIONAMIENTO A FLEXION

    Recubrimiento Mecanico

    5.2. DIMENSIONAMIENTO A CORTE

    Recubrimiento Mecanico

  • MATERIAL

    HORMIGONACERO

    DEFORMACION

    PLANILLA DE CALCULO

    LOSA

    1

  • LOSA CIRCULAR DE HORMIGON ARMADO

    VILLAFUERTE OPORTO ELISEO JAHDIELSUXO CHIGUA RONALD

    CRITERIO h [cm]

    10 31.42 25.000 1817.453

    3.1. CARGAS PERMANENTES

    LOSA CIRCULAR MACIZA

    25 4.50REVOQUE CIELO RASO (1) - 16 0.16

    TOTAL 4.657(1 ) Valores extraidos de la Norma NBE - AE - 88 (*) Valores extraidos de la Norma Chilena NCh 1537 -86

    3.2. CARGAS VARIABLES

    OBSERVACIONES

    5.50 Oficinas Publicas, tiendas

    3.3. CARGAS MAYORADAS

    1.5

    1.6

    PRE - DIMENSIONAMIENTO

    Diametro [m] Perimetro [m]h adop [cm]

    lx /40[m]Perimetro/180[m]

    PESO UNITARIO [Kg/m3]

    CARGA [Kg/m2]

    CARGA [KN/m2]

    CARGA [KN/m2]

    G

    Q

  • 4.66 6.99 5.50 8.80 10.16

    DIAMETRO DE LA LOSA [m] 10.00 LOSA SIMPLEMENTE APOYADA EN TODO SU CONTORNORADIO DE LA LOSA [m] 5.00 Las solicitaciones situados en cada punto a una distancia r del centro seran:CARGA TOTAL [KN/m2] 15.79

    Donde: Mr = Momento radialv = Coeficiente de PoissMt = Momento Tangenciala = Radio del contorno ciQ = Reaccion de Borde

    RADIO DE LA LOSA (a)

    TABLA N 1 - CALCULO DE SOLICITACIONES TABLA N 2 - RESUMEN DE RESULTADOS

    81.392 81.392 0.000 0.0 81.392 -80.579 80.924 3.946 5.0 20.34878.137 79.518 7.893 5.0 - 39.46374.067 77.175 11.83968.370 73.894 15.78561.044 69.677 19.73252.091 64.522 23.67841.510 58.430 27.62429.301 51.401 31.570

    CARGA PEMANENTE CARACTERISTICA

    (Gk) [KN/m2]

    CARGA PEMANENTE DE DISEO (Gd) [KN/m2]

    CARGA VARIABLE

    CARACTERISTICA (Qk)

    [KN/m2]

    CARGA VARIABLE DE DISEO (Qd) [KN/m2]

    CARGA TOTAL CARACTERISTI

    CA (PK) [KN/m2]

    SISTEMA ESTATICO Y SOLICITACIONES

    SOLICITACIONES A FLEXION Y CORTE

    de Poisson relativo a las deformaciones elasticas bajo tensiones normales de utilizacion puede tomarse igual a 0.2, si bien en ciertos calculos pueden despreciarse el efecto de la dilatacion trasversal.

    COEFICIENTE DE POISSON (v)

    Reemplazando los valores en las formulas anteriores, las solicitaciones a flexion y a corte a una distacion "r" del centro de la losa seran:

    Momento Radial (Mr) [KN-m/m]

    Momento Tangencial (Mt) [KN-

    m/m]

    Esfuerzo de Corte (V) [KN/m]

    DISTANCIA DE CALCULO

    MAXIMO (r) [m]

    Momento Tangencial (Mt) [KN-m/m]

    Esfuerzo de Corte

    (V) [KN/m]

    Segn el parrafo 18.8 del libro de HORMIGON ARMADO I - CIV 209, para no calcular vigas a torsion, seran despreciables los momentos torsores producidos, es una buena practica adoptar para el calculo de esfuerzos en losas, el metodo de calcular el momento del vano de la losa como si la rigidez a torsion de la viga fuese nula y calcular el empotramiento de la losa en la viga para un momento flector igual a un 25% del adoptado para el vano. Esto hace que no se trasfieran los esfuerzos torsionales de losa a viga como esfuerzo distribuido, ya que aumentaran los giros en las vigas.

    2 2316d

    rPM v a r

    2 23 1 316d

    tPM a v r v

    2dP rV

    25%apoyo vanoM M

  • 15.465 43.434 35.5170.000 34.530 39.463

    1. GEOMETRIA DE LA LOSA

    1 [m]0.18 [m]0.15 [m]0.03 [m]

    DESIGNACION

    H - 25 25 1.5 16.667 3.60B-420-S 420 1.15 365.217

    E=200000 [Mpa] 1.826

    PLANILLA DE CALCULO

    1 2 3 5 6

    SECCION Md z[KN-m/m] [m]TRAMO (RADIAL) 81.39 0.21705 0.30967 DOM 3 0.87613 0.13142TRAMO (TANG) 81.39 0.21705 0.30967 DOM 3 0.87613 0.13142

    APOYO A 20.35 0.05426 0.06977 DOM 2A 0.97209 0.14581APOYO B 20.35 0.05426 0.06977 DOM 2A 0.97209 0.14581

    1. GEOMETRIA DE LA LOSA

    1 [m]0.18 [m]0.15 [m]

    0.03 [m]

    Segn el parrafo 18.8 del libro de HORMIGON ARMADO I - CIV 209, para no calcular vigas a torsion, seran despreciables los momentos torsores producidos, es una buena practica adoptar para el calculo de esfuerzos en losas, el metodo de calcular el momento del vano de la losa como si la rigidez a torsion de la viga fuese nula y calcular el empotramiento de la losa en la viga para un momento flector igual a un 25% del adoptado para el vano. Esto hace que no se trasfieran los esfuerzos torsionales de losa a viga como esfuerzo distribuido, ya que aumentaran los giros en las vigas.

    DIMENSIONAMIENTO EN ESTADOS LIMITES ULTIMOS

    DIMENSIONAMIENTO A FLEXION

    RESISTENACIA CARACTERISTI

    CA [MPa]

    COEFICIENTE DE

    MINORACION

    RESISTENACIA DE

    CALCULO [MPa]

    AsMIN Geometrica

    [cm2]

    =fcd/E

    DIMENSIONAMIENTO A CORTE

    2CD

    1) Md Momento de DiseoMd2)

    f bd

    3) 1.25 1 1 2

    1 YD

    4) x d5) 1 0, 46) z d

    1 Md7)As ASimplef z

    cd 11 min

    yd

    1 min

    f W8)As 0.25 Rotura Agria

    f h

    9)As 0.002 b h Geometrica

    SLL

    1'3

    CU L CV 1 CDC

    'CV CK 1 CD

    C

    200(5) 1d

    A(6) 0,02

    bd0,15(7) V 100 f dbo

    Ndf f ; 1; 0; 1A

  • DESIGNACION

    H - 25 25 1.5 16.67B-420-S 420 1.15 365.22

    E=200000 [Mpa] 1.826

    PLANILLA DE CALCULO

    1 2 3 4 5 6

    SECCION Vd AsL L[KN/m] [cm2/m]APOYO A 39.46 100 15 4.04 2 0.00269APOYO B 39.46 100 15 4.04 2 0.00269

    RESISTENACIA CARACTERISTI

    CA [MPa]

    COEFICIENTE DE

    MINORACION

    RESISTENACIA DE

    CALCULO [MPa]

    =fcd/E

    b [cm]

    d [cm]

  • LOSA SIMPLEMENTE APOYADA EN TODO SU CONTORNOLas solicitaciones situados en cada punto a una distancia r del centro seran:

    Mt = Momento Tangencial

    TABLA N 2 - RESUMEN DE RESULTADOS

    CENTROBORDEBORDE

    de Poisson relativo a las deformaciones elasticas bajo tensiones normales de utilizacion puede tomarse igual a 0.2, si bien en ciertos calculos pueden despreciarse el efecto de la dilatacion

    Reemplazando los valores en las formulas anteriores, las solicitaciones a flexion y a corte a una distacion "r" del centro de la

    OBSERVACION

    Segn el parrafo 18.8 del libro de HORMIGON ARMADO I - CIV 209, para no calcular vigas a torsion, seran despreciables los momentos torsores producidos, es una buena practica adoptar para el calculo de esfuerzos en losas, el metodo de calcular el momento del vano de la losa como si la rigidez a torsion de la viga fuese nula y calcular el empotramiento de la losa en la viga para un momento flector igual a un 25% del adoptado para el vano. Esto hace que no se trasfieran los esfuerzos torsionales de losa a viga como esfuerzo distribuido, ya que aumentaran los giros en

    25%apoyo vanoM M

  • PLANILLA DE CALCULO

    7 8 9 10As As min As

    [cm2/m] [cm2/m] [cm2/m] [cm2/m]16.96 3.60 16.96 16.16 12 c/ 716.96 0.00 16.96 16.16 12 c/ 73.82 3.60 4.04 8.08 12 c/ 143.82 3.60 4.04 8.08 12 c/ 14

    AsADOPTADO

    1 YD

    4) x d5) 1 0, 46) z d

    1 Md7)As ASimplef z

    cd 11 min

    yd

    1 min

    f W8)As 0.25 Rotura Agria

    f h

    9)As 0.002 b h Geometrica

    SLL

    1'3

    CU L CV 1 CDC

    'CV CK 1 CD

    C

    200(5) 1d

    A(6) 0,02

    bd0,15(7) V 100 f dbo

    Ndf f ; 1; 0; 1A

  • PLANILLA DE CALCULO

    7 8 9fcv Vcu

    [MPa] [KN/m]25.00 56.65 CUMPLE25.00 56.65 CUMPLE

    OBSERVACION Vcu > Vd

  • 12 c /14 R 12 c /14 D 12 7.0 12 c /14 R 12 c /14 D 12 7.0

    12 14.012 14.0

    ESPACIAMIENTO [cm]

  • MEMORIA DE CALCULO

    DATOS DE PROYECTO

    MATERIAL DESIGNACION

    HORMIGON 16.667 H - 25 25 1.50ACERO 365.217 B-420-S 420 1.15

    Algunos de los datos son adoptados por criterio propio:

    DESCRIPCION DEL DATO SIMBOLO VALORAltura total del muro [m] H 6.5TERRENO N 1 - ConglomeradoPeso Volumetrico o Densidad [KN/m3] 1 18Angulo de Friccion Interna () 1 31Altura del conglomerado [m] H1 3.5TERRENO N 2 - ArcillaPeso Volumetrico o Densidad [KN/m3] 2 17Angulo de Friccion Interna () 2 20Cohesin [Kpa] c 23Altura de la arcilla [m] H2 3.0

    Presion admisible del terreno [Kpa] 200.0Sobrcarga del terreno [KN/m2] q 10.0Angulo del talud de terreno [] 15.0Friccion entre el muro y el suelo 13.0Angulo de inclimacion del muro [] 90.0

    Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de indentidad de los estudiantes proyectistas.

    1. MATERIALESRESISTENACIA DE CALCULO

    [MPa]

    RESISTENACIA CARACTERISTIC

    A [MPa]

    COEFICIENTE DE

    MINORACION

    2. DATOS GENERALES

    adm

    3. PREDIMENSIONAMIENTO

    Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.

  • A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:

    Con base a estos criterios podemos predimensionar los elementos del muro de contencion:

    DESCRIPCION VALORAltura total del muro [m] 6.50 6.5Base [m] 4.00 4Altura de talon y puntera [m] 0.65 0.65Ancho del muro cortina [m] 0.65 0.65Longitud de puntera [m] 1.35 1.35Longitud de talon [m] 2.00 2

    Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.

    0,30

    1,35 0,65 2,00

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []

    q = 10 [KN/m]

    3,50

    3,00

    6,50

  • Donde:

    Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos de los dos terrenos.

    DATOS: TERRENO N 1 TERRENO N 2 18 0.314159265 31 0.541052068 15.0 0.261799388 13.0 0.226892803 90.0 1.570796327

    0.734735781 3.717583409 h 0.198 h v 0.046 v

    4. COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION

    4.1 CALCULO DE EMPUJES SOBRE EL MURO

    Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un proceso iterativo antes de disear el mismo.Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las caracteristicas del proyecto.Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo. La ecuaciones que se consideran en estos casos son:

    = Es el coeficiente activo y viene dado por

    4.2 CALCULO DE LOS COEFICIENTES ACTIVOS

    0,30

    1,35 0,65 2,00

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []

    q = 10 [KN/m]

    3,50

    3,00

    6,50

    21

    2TsenE H q H

    sen

    2

    2

    2 1

    sen

    sen sensen

    sen sen

    cv h tg

    2 2h v

  • 0.203

    q [KN/m2] 10.0

    Ley de Presiones para el terreno N 1

    Ley de Presiones para el terreno N 2

    Ley de Presiones para la sobrecarga

    Ley de Presiones que produce la cohesionLa cohesion no se considera por no existir un metodo exacto que garantice su aplicacin (CALAVERA)

    x [m] Pq [KN/m2] Pc [KN/m2]

    0.00 0.000 2.100.25 0.913 2.100.50 1.826 2.100.75 2.738 2.101.00 3.651 2.101.25 4.564 2.101.50 5.477 2.101.75 6.389 2.102.00 7.302 2.102.25 8.215 2.102.50 9.128 2.102.75 10.040 2.103.00 10.953 2.103.25 11.866 2.103.50 12.779 2.103.50 17.160 2.82 0.003.75 18.317 2.82 0.004.00 19.475 2.82 0.004.25 20.632 2.82 0.004.50 21.790 2.82 0.00

    4.2 CALCULO DEL DIAGRAMA DE PRESIONES

    Para el calculo de las presiones sobre el muro debemos diferenciar entre los dos tipos de terreno, por consiguiente se tendran las siguientes leyes de presiones:

    P1 [KN/m2]

    P2 [KN/m2]

    1 1 1 0 3.5P x x

    2 2 1 2 23.5 3.5 6P x x

    0 6qsenP q x

    sen

    2 3.5 6cP C x

  • 4.75 22.948 2.82 0.005.00 24.105 2.82 0.005.25 25.263 2.82 0.005.50 26.420 2.82 0.005.75 27.578 2.82 0.006.00 28.736 2.82 0.006.25 29.893 2.82 0.006.50 31.051 2.82 0.00

    La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:

    En la figura se muestra el diagrama de presiones total:

    4.3. CALCULO DEL EMPUJE TOTAL, HORIZONTAL Y VERTICAL

    El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el estudio:

    ADP = Area de cada diagrama de presiones

    Ei = Empuje activo correspondiente a cada uno de los diagramas de presiones.yi = Posicion del centroide del area de los diagramas de presiones.

    T iDPE A E

    ii i DP

    T T

    A yE yy

    E A

    19.98

    Presion ejercidapor el terreno

    0,30

    6,50

    3,50

    3,00

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    +

    Presion ejercidapor la sobrecarga

    Conglomerado

    Arcilla

    x

    =

    DIAGRAMA DEPRESIONES

    TOTALES

    12.779

    17.160

    2.10

    2.10

    2.82

    2.8231.051

    2.01

    14.88

    33.871

  • Forma BASE TRIANGULAR 3.500 12.779 4.167 22.36

    RECTANGULAR 3.000 17.160 1.500 51.479TRIANGULAR 3.000 13.891 1.000 20.84

    RECTANGLUAR 3.500 2.100 4.750 7.350RECTANGULAR 3.000 2.820 1.500 8.460RECTANGULAR 3.000 0.000 1.500 0.000

    110.49Las componentes del empuje total, horizontal y verical viene dado por:

    Reemplazando los valores tenemos:

    E 110.488 [KN/m]Eh 106.723 [KN/m]Ev 28.596 [KN/m]

    y 2.16 [m]

    Se realizara respecto al punto a (ver figura arriba)

    ZONA

    ZAPATA 2.600 25.000 65.000 2.000LOSA 1.755 25.000 43.875 1.850

    LOSA FRONTAL 1.024 25.000 25.594 1.580

    4.700 17.000 79.900 3.000

    7.000 18.000 126.000 3.000

    0.473 18.000 8.505 0.675

    ALTURA

    yi

    AREA

    El empuje se encuntra a una distancia de la base de:

    4.4. CALCULO DEL PESO DEL MURO, TIERRAS, Y MOMENTO

    VOLUMEN [m3]

    DENSIDAD [KN/m3]

    PESO [KN]

    DISTANCIA DEL c.d.g AL

    PUNTO A [m]

    RELLENO SOBRE EL TALON 1RELLENO SOBRE EL TALON 2RELLENO SOBRE LA PUNTERA

    cosh T

    v T

    E E

    E E sen

    19.98

    Presion ejercidapor el terreno

    0,30

    6,50

    3,50

    3,00

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    +

    Presion ejercidapor la sobrecarga

    Conglomerado

    Arcilla

    x

    =

    DIAGRAMA DEPRESIONES

    TOTALES

    12.779

    17.160

    2.10

    2.10

    2.82

    2.8231.051

    2.01

    14.88

    33.871

    0,30

    6,50

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    Conglomerado

    Arcilla

    E

    Eh

    Ev

    0,65

    A

    2,16

  • P [KN] 348.874 M [KN-m](*) El calculo se ha realizado tomando un ancho de muro de 1 [m]

    Primeramente calculamos la excentricidad ep respecto al centro del cimiento:

    M[KN-m] 875.048P [KN] 348.874B [m] 4.000

    Reemplazando valores tenemos:xp [m] 2.51

    ep [m] 0.508

    La excentricidad ev respecto al centro del cimiento, de la componente vertical del empuje resulta:

    ev [m] 0.000

    Dado que N, resultante de las fuerzas normales al cimiento tiene un valor:

    N [KN] 377.470

    Finalmente tomando momentos respecto al centro del cimiento se obtine:

    en [m] -0.141

    VERIFICAMOS

    Asumiendo una distribucion de tensiones lineal, las tenciones en en los bordes extremos son:

    [KN/m2] 74.341 [KN/m2]

    Se compruebaa que no supera la tenasion admisible del terreno.

    4.5. VERIFICACION DE PRESIONES AL TERRENO

    2p pBe x p

    Mx

    P

    vN P E

    p h v vn

    P e E h E ee

    N

    0.142[ ] 0.67[ ]6nBe m m

    2

    6 nA

    NeNB B

    2

    6 nB

    NeNB B

  • Se debe cumplir con la condicion:

    Csd 2.041

    Se debe cumplir con la condicion: Me [KN-m] 875.048Mv [KN-m] 230.703

    Csd 3.793

    4.6. SEGURIDAD AL DESLIZAMIENTO

    4.7. SEGURIDAD AL VUELCO

    1.5sdNCE

    1.8esvv

    MCM

  • MEMORIA DE CALCULO

    Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de

    Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.

  • A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:

    Con base a estos criterios podemos predimensionar los elementos del muro de contencion:

    0,30

    1,35 0,65 2,00

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []

    q = 10 [KN/m]

    3,50

    3,00

    6,50

  • Compomente Horizontal

    Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos

    TERRENO N 217 0.29720 0.349

    15.0 0.26213.0 0.22790.0 1.571

    0.88302222 3.3270.2650.061

    COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION

    Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un

    Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las

    Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo.

    0,30

    1,35 0,65 2,00

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []

    q = 10 [KN/m]

    3,50

    3,00

    6,50

    21

    2TsenE H q H

    sen

    2

    2

    2 1

    sen

    sen sensen

    sen sen

  • 0.272

    Ley de Presiones para el terreno N 1

    Ley de Presiones para el terreno N 2

    Ley de Presiones para la sobrecarga

    Ley de Presiones que produce la cohesionLa cohesion no se considera por no existir un metodo exacto que garantice su aplicacin (CALAVERA)

    2.100 0,0.2099920040251743.013 0.25,0.3012685190261253.925 0.5,0.3925450340270764.838 0.75,0.4838215490280275.751 1,0.5750980640289786.664 1.25,0.6663745790299297.577 1.5,0.757651094030888.489 1.75,0.8489276090318319.402 2,0.940204124032782

    10.315 2.25,1.0314806390337311.228 2.5,1.1227571540346812.140 2.75,1.2140336690356413.053 3,1.3053101840365913.966 3.25,1.3965866990375414.879 3.5,1.48786323.5,1.7159688824595719.980 3.5,1.9979532809254921.137 3.75,2.11371 3.75,1.8317286880223222.295 4,2.22947289 4,1.9474884935850723.452 4.25,2.34523 4.25,2.0632482991478224.610 4.5,2.46099254.5,2.17900810471057

    Para el calculo de las presiones sobre el muro debemos diferenciar entre los dos tipos de terreno, por

    PT [KN/m2]

  • 25.768 4.75,2.57675 4.75,2.2947679102733226.925 5,2.69251211 5,2.4105277158360728.083 5.25,2.80827 5.25,2.5262875213988229.240 5.5,2.92403175.5,2.6420473269615730.398 5.75,3.03979 5.75,2.7578071325243131.556 6,3.15555133 6,2.8735669380870632.713 6.25,3.27131 6.25,2.9893267436498133.871 6.5,3.38707096.5,3.10508654921256

    La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:

    El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el

    = Empuje activo correspondiente a cada uno de los diagramas de presiones.

    19.98

    Presion ejercidapor el terreno

    0,30

    6,50

    3,50

    3,00

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    +

    Presion ejercidapor la sobrecarga

    Conglomerado

    Arcilla

    x

    =

    DIAGRAMA DEPRESIONES

    TOTALES

    12.779

    17.160

    2.10

    2.10

    2.82

    2.8231.051

    2.01

    14.88

    33.871

  • 93.18677.21920.83734.91112.6890.000

    238.841Las componentes del empuje total, horizontal y verical viene dado por:

    130.00081.16940.438

    239.700

    378.000

    5.741

    Ayi

    MOMENTO [KN-m]

    19.98

    Presion ejercidapor el terreno

    0,30

    6,50

    3,50

    3,00

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    +

    Presion ejercidapor la sobrecarga

    Conglomerado

    Arcilla

    x

    =

    DIAGRAMA DEPRESIONES

    TOTALES

    12.779

    17.160

    2.10

    2.10

    2.82

    2.8231.051

    2.01

    14.88

    33.871

    0,30

    6,50

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    Conglomerado

    Arcilla

    E

    Eh

    Ev

    0,65

    A

    2,16

  • 875.048

    Primeramente calculamos la excentricidad ep respecto al centro del cimiento:

    La excentricidad ev respecto al centro del cimiento, de la componente vertical del empuje resulta:

    CUMPLE

    Asumiendo una distribucion de tensiones lineal, las tenciones en en los bordes extremos son:

    114.394

    CUMPLE

    2

    6 nB

    NeNB B

  • CUMPLE

    CUMPLE

  • 0,0.419984008050348 0,0.4199840080503480.25,0.419984008050348 0.25,0.602537038052250.5,0.419984008050348 0.5,0.7850900680541520.75,0.419984008050348 0.75,0.9676430980560541,0.419984008050348 1,1.150196128057961.25,0.419984008050348 1.25,1.332749158059861.5,0.419984008050348 1.5,1.515302188061761.75,0.419984008050348 1.75,1.697855218063662,0.419984008050348 2,1.880408248065562.25,0.419984008050348 2.25,2.062961278067472.5,0.419984008050348 2.5,2.245514308069372.75,0.419984008050348 2.75,2.428067338071273,0.419984008050348 3,2.610620368073173.25,0.419984008050348 3.25,2.793173398075083.5,0.419984008050348 3.5,0 3.5,2.97572642807698

    3.75,0.563968796931843 3.75,0 3.75,4.227426172976494,0.563968796931843 4,0 4,4.458945784101994.25,0.563968796931843 4.25,0 4.25,4.690465395227484.5,0.563968796931843 4.5,0 4.5,4.92198500635298

  • 4.75,0.563968796931843 4.75,0 4.75,5.153504617478485,0.563968796931843 5,0 5,5.385024228603985.25,0.563968796931843 5.25,0 5.25,5.616543839729485.5,0.563968796931843 5.5,0 5.5,5.848063450854975.75,0.563968796931843 5.75,0 5.75,6.079583061980476,0.563968796931843 6,0 6,6.311102673105976.25,0.563968796931843 6.25,0 6.25,6.542622284231476.5,0.563968796931843 6.5,0 6.5,6.77414189535696

  • MEMORIA DE CALCULO

    DATOS DE PROYECTO

    MATERIAL DESIGNACION

    HORMIGON 16.667 H - 25 25 1.50ACERO 365.217 B-420-S 420 1.15

    Algunos de los datos son adoptados por criterio propio:

    DESCRIPCION DEL DATO SIMBOLO VALORAltura total del muro [m] H 6.5TERRENO N 1 - ConglomeradoPeso Volumetrico o Densidad [KN/m3] 1 18Angulo de Friccion Interna () 1 31Altura del conglomerado [m] H1 3.5TERRENO N 2 - ArcillaPeso Volumetrico o Densidad [KN/m3] 2 17Angulo de Friccion Interna () 2 20Cohesin [Kpa] c 23Altura de la arcilla [m] H2 3.0

    Presion admisible del terreno [Kpa] 200.0Sobrcarga del terreno [KN/m2] q 10.0Angulo del talud de terreno [] 15.0Friccion entre el muro y el suelo 13.0Angulo de inclimacion del muro [] 90.0

    Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de indentidad de los estudiantes proyectistas.

    1. MATERIALESRESISTENACIA DE CALCULO

    [MPa]

    RESISTENACIA CARACTERISTIC

    A [MPa]COEFICIENTE DE

    MINORACION

    2. DATOS GENERALES

    adm

    3. PREDIMENSIONAMIENTO

    Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.

  • A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:

    Con base a estos criterios podemos predimensionar los elementos del muro de contencion:

    DESCRIPCION VALORAltura total del muro [m] 6.50 6.5Base [m] 4.03 4Altura de talon y puntera [m] 0.65 0.65Ancho del muro cortina [m] 0.65 0.65Longitud de puntera [m] 1.34 1.35Longitud de talon [m] 2.04 2

    Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.

  • Donde:

    Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos de los dos terrenos.

    DATOS: TERRENO N 1 TERRENO N 2 18 0.314159265 31 0.541052068 15.0 0.261799388 13.0 0.226892803 90.0 1.570796327

    0.734735781 3.717583409 h 0.198 h v 0.046 v

    4.8. COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION

    4.8.1 CALCULO DE EMPUJES SOBRE EL MURO

    Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un proceso iterativo antes de disear el mismo.Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las caracteristicas del proyecto.Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo. La ecuaciones que se consideran en estos casos son:

    = Es el coeficiente activo y viene dado por

    4.8.2 CALCULO DE LOS COEFICIENTES ACTIVOS

    21

    2TsenE H q H

    sen

    2

    2

    2 1

    sen

    sen sensen

    sen sen

    cv h tg

    2 2h v

  • 0.203

    q [KN/m2] 10.0

    Del diagrma de presiones:

    x [m] Pq [KN/m2] Pc [KN/m2]

    0.00 0.000 2.100.50 1.826 2.101.00 3.651 2.101.50 5.477 2.102.00 7.302 2.102.50 9.128 2.103.00 10.953 2.103.50 12.779 2.103.50 17.160 2.82 0.004.00 19.475 2.82 0.004.50 21.790 2.82 0.005.00 24.105 2.82 0.005.50 26.420 2.82 0.005.85 28.041 2.82 0.00

    La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:

    5. DIMENSIONAMIENTO DEL MURO COMO ESTRUCTURA DE HORMIGON ARMADO

    Calculamos el empuje a nivel del muro cortina para disear el muro, ya que se considera que la flexion del muro cortina es producido por la componente horizontal del empuje activo.

    P1 [KN/m2]

    P2 [KN/m2]

    5.1. CALCULO DEL EMPUJE TOTAL, HORIZONTAL Y VERTICAL

    El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el estudio:

    ADP = Area de cada diagrama de presiones

    T iDPE A E

    ii i DP

    T T

    A yE yy

    E A

  • En la figura se muestra el diagrama de presiones total:

    Forma BASE EMPUJETRIANGULAR 3.500 12.779 3.517 22.36

    RECTANGULAR 2.350 17.160 1.175 40.325TRIANGULAR 2.350 10.881 0.783 12.79

    RECTANGLUAR 3.500 2.100 4.100 7.350RECTANGULAR 2.350 2.820 1.175 6.627RECTANGULAR 2.350 0.000 1.175 0.000

    89.45Las componentes del empuje total, horizontal y verical viene dado por:

    Reemplazando los valores tenemos:

    E 89.450 [KN/m]Eh 86.402 [KN/m]Ev 23.151 [KN/m]

    Componente Horizontal con el cual se calculara el Momento de DiseoEl empuje se encuntra a una distancia de talon de:

    y 1.94 [m]

    La ley de momentos flecotres a los largo del muro, viene dado por la siguiente relacion:

    x [m]

    0.00 0.000 00.50 23.0411.00 46.0811.50 69.122

    Ei = Empuje activo correspondiente a cada uno de los diagramas de presiones.yi = Posicion del centroide del area de los diagramas de presiones.

    ALTURA

    yi

    5.2. CALCULO DEL MOMENTO FLECTOR Y ESFUERZO DE CORTE

    Md [KN-m/m]

    Vd [KN/m]

    ii i DP

    T T

    A yE yy

    E A

    cosh T

    v T

    E E

    E E sen

    13d f h

    M E x 1.6f d hV E

    0,30

    6,50

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    Conglomerado

    Arcilla EEh

    Ev

    0,65

    A

    Md Vd

    269.575[KN-m/m]

    86.402[KN/m]

    1,94

  • 2.00 92.1622.50 115.2033.00 138.2433.50 161.2844.00 184.3244.50 207.3655.00 230.4065.50 253.4465.85 269.575 86.402

    1. GEOMETRIA DE LA LOSA

    BASE (b) 1 [m]ALTURA (h) 0.65 [m]

    ALTURA UTIL (d) 0.60 [m]0.05 [m]

    2. MATERIALES

    MATERIAL DESIGNACION

    HORMIGON H - 25 25 1.5 16.667ACERO B-420-S 420 1.15 365.217

    DEFORMACION E=200000 [Mpa] 1.826

    3. CUANTIA MINIMA

    12.36 13.00

    5.3. DISEO A FLEXION

    Recubrimiento Mecanico

    RESISTENACIA CARACTERISTICA

    [MPa]COEFICIENTE DE

    MINORACIONRESISTENACIA DE CALCULO

    [MPa]

    =fcd/E

    AsMIN Mecanica [cm2]

    AsMIN Geometrica [cm2]

    2CD

    1) Md Momento de DiseoMd2)

    f bd

    3) 1.25 1 1 2

    1 YD

    4) x d5) 1 0,46) z d

    1 Md7)As ASimplef z

    cd 11 min

    yd

    1 min

    f W8)As 0.25 Rotura Agria

    f h

    9)As 0.002 b h Geometrica

    0,30

    6,50

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    Conglomerado

    Arcilla EEh

    Ev

    0,65

    A

    Md Vd

    269.575[KN-m/m]

    86.402[KN/m]

    1,94

  • Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica minima para secciones sometidas a flexion simple o compuesta segn la EHE.

    Us = Capacidad mecanica del aceroUc = Capacidad mecanica del hormigon

    Reemplazando datos tenemos: Us 458.95 [KN]Uc 10833.33 [KN]

    0.04Uc 433.33 [KN]

    CUMPLE

    Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propiadel hormigon, efectos que no suelen tenerse en cuenta en el calculo.

    ARMADURA VERTICAL La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.

    Asv [cm2] 3.77 12 c/ 20

    3. VERIFICACION DE CUANTIAS MINIMAS

    3.1. CUANTIA MECANICA MINIMA

    3.1. CUANTIA MECANICA MINIMA

    0.04s cU U

    s s ydU A f c c cdU A f

    0.04s cU U

  • ARMADURA VERTICAL La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004

    Ash [cm2] 6.50 10 c/ 20

    RESUMEN DE RESULTADOS

    ARMADURA LONGITUDINAL TRASDOS 12 c/ 9ARMADURA LONGITUDINAL INTRADOS 12 c/ 20

    ARMADURA TRASVERSAL TRASDOS 10 c/ 20ARMADURA TRASVERSAL INTADOS 10 c/ 20

    La distribucion de presiones sobre el talon se indica en la siguiente figura

    Caculamos el peso del terreno por unidad de longitud:

    qt 102.95 [KN/m2]

    El peso del hormigon por unidad de longitud es:

    qt 16.25 [KN/m2]

    [KN/m2] 74.341

    [KN/m2] 114.394

    El momento flector en la seccion D-D' es:

    M [KN-m/m] -26.069

    Md [KN-m/m] -41.710

    Calculando el acero de refuerzo

    ARMADURA LONGITUDINAL 12 c/ 9.5ARMADURA TRANSVERSAL (20% AsL) 8 c/ 20

    6. DIMENSIONAMIENTO DEL TALON

    0,65

    1,35 0,65 2,00

    D

    D

    89.71 [KN/m2]

    102.95 [KN/m2]

    108.813 [KN/m2]

    70.602 [KN/m2]

    16.25 [KN/m2]

  • Se llevara la misma armadura del muro o alzado

    ARMADURA LONGITUDINAL 12 c/ 9ARMADURA TRANSVERSAL (20% AsL) 10 c/ 20

    7. DIMENSIONAMIENTO DE LA PUNTERA

  • MEMORIA DE CALCULO

    Al igual que en proyectos anteriores, los datos del proyecto estaran en funcion del carnet de

    Al disear muros de contencion o sostenimiento, un ingeniero debe suponer algunas de las dimensiones , lo que se llama predimensionamiento, que permite al ingeniero revisar las secciones de prueba por estabilidad.

  • A continuacion se presenta algunas sugerencia de algunos autores como ser Braja M. Das:

    Con base a estos criterios podemos predimensionar los elementos del muro de contencion:

  • Compomente Horizontal

    Componente VerticalAhora como tenemos diferentes terrenos, entonces existira una diferencia entre los coeficientes activos

    TERRENO N 217 0.29720 0.349

    15.0 0.26213.0 0.22790.0 1.571

    0.88302222 3.3270.2650.061

    COMPROBACION DE TENSIONES SOBRE EL TERRENO DE CIMENTACION

    Para dimensionar el muro como elemento de hormigon, primeramente debemos comprobar las tensiones que este transmite al terreno de fundacion y que no deben sobrepasar las mismas, por eso se considera un proceso

    Para calcular el Empuje Activo del terreno se recurre a la teoria de Coulom, y que estara en funcion de las

    Como se muestra en la figura anterior, el se presentan dos clases de suelos, uno granular y el otro cohesivo. La

    2

    2

    2 1

    sen

    sen sensen

    sen sen

  • 0.272

    2.100 2.100 0,0 0,0.4199840080503483.925 3.925 0.5,0.182553030001902 0.5,0.4199840080503485.751 5.751 1,0.365106060003804 1,0.4199840080503487.577 7.577 1.5,0.547659090005706 1.5,0.4199840080503489.402 9.402 2,0.730212120007608 2,0.419984008050348

    11.228 11.228 2.5,0.912765150009511 2.5,0.41998400805034813.053 13.053 3,1.09531818001141 3,0.41998400805034819.260 14.879 3.5,1.27787121001332 3.5,0.41998400805034819.260 2.820 3.5,0 4,0.56396879693184322.295 2.820 4,0 4.5,0.56396879693184324.610 2.820 4.5,0 5,0.56396879693184326.925 2.820 5,0 5.5,0.56396879693184329.240 2.820 5.5,0 5.85,0.56396879693184330.861 2.820 5.85,0 #REF!

    La posicion de la resultante del empuje total, medido desde la base del muro, esta dada por la relacion:

    DIMENSIONAMIENTO DEL MURO COMO ESTRUCTURA DE HORMIGON ARMADO

    Calculamos el empuje a nivel del muro cortina para disear el muro, ya que se considera que la flexion del muro cortina es producido por la componente horizontal del empuje activo.

    Pt [KN/m2]

    El calculo del empuje total sera la suma del area que forman los diagramas de presiones que actuan en el

  • 78.65047.38210.01130.1347.7860.000

    173.963Las componentes del empuje total, horizontal y verical viene dado por:

    Componente Horizontal con el cual se calculara el Momento de Diseo

    La ley de momentos flecotres a los largo del muro, viene dado por la siguiente relacion:

    1.60 0,0 0,00.5,0.46 5.85,3.456084111076021,0.9216224296202711.5,1.38243364443041

    = Empuje activo correspondiente a cada uno de los diagramas de presiones.

    Ayi

    0,30

    6,50

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    Conglomerado

    Arcilla EEh

    Ev

    0,65

    A

    Md Vd

    269.575[KN-m/m]

    86.402[KN/m]

    1,94

  • 2,1.843244859240542.5,2.304056074050683,2.764867288860813.5,3.225678503670954,3.686489718481084.5,4.147300933291225,4.608112148101355.5,5.068923362911495.85,5.39149121327858

    1 2

    LOSA SECCIONMd

    5.3. DISEO A FLEXION

    1 YD

    4) x d5) 1 0,46) z d

    1 Md7)As ASimplef z

    cd 11 min

    yd

    1 min

    f W8)As 0.25 Rotura Agria

    f h

    9)As 0.002 b h Geometrica

    0,30

    6,50

    q = 10 [KN/m]

    ? = 18 [KN/m3]f = 31 []

    ? = 17 [KN/m3]f = 20 []C = 23 [KN/m2]

    1,35 0,65 2,00

    Conglomerado

    Arcilla EEh

    Ev

    0,65

    A

    Md Vd

    269.575[KN-m/m]

    86.402[KN/m]

    1,94

  • LOSA SECCION[KN-m/m]

    1TRAMO (RADIAL)0.00 #DIV/0!TRAMO (TANG)0.00

    APOYO A 0.00 #DIV/0!APOYO B 0.00 #DIV/0!

    Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica

    Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propia

    La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.

  • La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004

    12 c/ 9.5

    0,65

    1,35 0,65 2,00

    D

    D

    89.71 [KN/m2]

    102.95 [KN/m2]

    108.813 [KN/m2]

    70.602 [KN/m2]

    16.25 [KN/m2]

  • 0,0.4199840080503480.5,0.419984008050348 0.5,0.785090068054152

    1,1.150196128057961.5,0.419984008050348 1.5,1.51530218806176

    2,1.880408248065562.5,0.419984008050348 2.5,2.24551430806937

    3,2.610620368073173.5,0.419984008050348 3.5,2.97572642807698

    4,0.5639687969318434.5,0.563968796931843 4.5,0.563968796931843

    5,0.5639687969318435.5,0.563968796931843 5.5,0.5639687969318435.85,0.563968796931843 5.85,0.563968796931843

    #REF!

  • 3 4 5 6 7 8

    x

    z As As min

  • [cm]

    [m] [cm2/m] [cm2/m]

    #DIV/0! DOM 3 #DIV/0! #DIV/0! #DIV/0! #DIV/0! 0.00DOM 3 0.00

    DOM 2A #VALUE! 0.00DOM 2A #VALUE! 0.00

  • 9 10As AsADOPTADO

  • [cm2/m] [cm2/m]#DIV/0! #DIV/0! c/

    c/ #VALUE! c/ #VALUE! c/

  • 1. GEOMETRIA DE LA LOSA

    BASE (b) 1 [m]ALTURA (h) 0.65 [m]

    ALTURA UTIL (d) 0.6 [m]0.05 [m]

    2. MATERIALES

    MATERIAL DESIGNACION

    HORMIGON H - 25 25 1.5ACERO B-420-S 420 1.15

    DEFORMACION E=200000 [Mpa]

    PLANILLA DE CALCULO

    1 2

    MURO DISPOSICION Md [KN-m/m]

    1LONGITUDINAL 269.57 0.04493

    TRANVERSAL Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal

    Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica minima para secciones sometidas a flexion simple o compuesta segn la EHE.

    Us = Capacidad mecanica del aceroUc = Capacidad mecanica del hormigon

    5.3. DIMENSIONAMIENTO A FLEXION

    Recubrimiento Mecanico

    RESISTENACIA CARACTERISTICA

    [MPa]COEFICIENTE DE

    MINORACION

    =fcd/E

    3. VERIFICACION DE CUANTIAS MINIMAS

    3.1. CUANTIA MECANICA MINIMA

    GQ

    2CD

    1) Md Momento de DiseoMd2)

    f bd

    3) 1.25 1 1 2

    0.04s cU U

    s s ydU A f c c cdU A f

  • Reemplazando datos tenemos: UsUc

    0.04Uc

    CUMPLE

    Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propiadel hormigon, efectos que no suelen tenerse en cuenta en el calculo.

    ARMADURA VERTICAL La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.

    Asv [cm2] 3.77 12 c/ 20

    ARMADURA VERTICAL La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004

    Ash [cm2] 6.50 10 c/ 20

    RESUMEN DE RESULTADOS

    ARMADURA LONGITUDINAL TRASDOS 12 c/ 9ARMADURA LONGITUDINAL INTRADOS 12 c/ 20

    ARMADURA TRASVERSAL TRASDOS 10 c/ 20ARMADURA TRASVERSAL INTADOS 10 c/ 20

    DISEO EN ESTADO LIMITE ULTIMO A FLEXION1. GEOMETRIA DE LA LOSA

    BASE (b) 1 [m]ALTURA (h) 0.65 [m]

    ALTURA UTIL (d) 0.6 [m]0.05 [m]

    2. MATERIALES

    3.1. CUANTIA MECANICA MINIMA

    6.1. DIMENSIONAMIENTO A FLEXION DEL TALON

    Recubrimiento Mecanico

    0.04s cU U

    2CD

    1) Md Momento de DiseoMd2)

    f bd

    3) 1.25 1 1 2

  • MATERIAL DESIGNACION

    HORMIGON H - 25 25 1.5ACERO B-420-S 420 1.15

    DEFORMACION E=200000 [Mpa]

    PLANILLA DE CALCULO

    1 2

    MURO DISPOSICION Md [KN-m/m]

    1LONGITUDINAL 41.71 0.00695

    TRANVERSAL Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal

    RESISTENACIA CARACTERISTICA

    [MPa]COEFICIENTE DE

    MINORACION

    =fcd/E

  • 3. CUANTIA MINIMA

    16.667 11.87 13.00 7.80365.217

    1.826

    PLANILLA DE CALCULO

    3 4 5 6 7 8 9

    x z As Asmin

    [cm] [m] [cm2/m] [cm2/m] [cm2/m]0.05748 3.44899 0.97701 0.58620 12.59 11.87 12.57

    Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal

    Debemos comprobar que la armadura longitudinal cumple con la condicion de cuantia mecanica minima para secciones sometidas a flexion simple o compuesta segn la EHE.

    RESISTENACIA DE

    CALCULO [MPa]

    AsMIN Mecanica

    [cm2]

    AsMIN Geometrica Horizontal

    [cm2]

    AsMIN Geometrica

    Vertical [cm2]

    AsADOPTADO

    2CD

    1) Md Momento de DiseoMd2)

    f bd

    3) 1.25 1 1 2

    1 YD

    4) x d5) 1 0,46) z d

    1 Md7)As ASimplef z

    cd1 min

    yd

    1 min Horizontal

    1 min Vertical

    TRANS 1

    f b h8)As 0.04 Rotura Agria

    f

    9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal

  • 458.95 [KN]10833.33 [KN]

    433.33 [KN]

    Sedispondra de armaduras de retraccion y temperatura, con el objeto de controlarla fisuracion producida por las variaciones de temperatura o por retraccion propia

    La cuantia minima vertical en correspondiente a la armadura de traccion. Se recomiendadisponer en la cara opuesta una armadura minima igual al 30% de la consignada.

    5.65 12 20.0

    La armadura horizontal debera repartirse en cada con una cuantia geometrica del 0.004

    4 10 20.0

    DISEO EN ESTADO LIMITE ULTIMO A FLEXION

    3. CUANTIA MINIMA

    2CD

    1) Md Momento de DiseoMd2)

    f bd

    3) 1.25 1 1 2

    1 YD

    4) x d5) 1 0, 46) z d

    1 Md7)As ASimplef z

    cd1 min

    yd

    1 min Horizontal

    1 min Vertical

    TRANS 1

    f b h8)As 0.04 Rotura Agria

    f

    9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal

  • 16.666667 11.87 26.00 7.80365.21739

    1.826

    PLANILLA DE CALCULO

    3 4 5 6 7 8 10

    x z As Asmin

    [cm] [m] [cm2/m] [cm2/m] [cm2/m]

    0.00872 0.52320 0.99651 0.59791 1.91 11.87 11.90

    Segn la instruccin EHE se dispondra del 20% e la Armadura Longitudinal 2.37 2.51

    RESISTENACIA DE

    CALCULO [MPa]

    AsMIN Mecanica

    [cm2]

    AsMIN Geometrica Horizontal

    [cm2]

    AsMIN Geometrica

    Vertical [cm2]

    AsADOPTADO

  • PLANILLA DE CALCULO

    9

    [cm2/m] 12 c/ 9 12 c /14 R 12 c /14 D

    AsADOPTADO

    cd1 min

    yd

    1 min Horizontal

    1 min Vertical

    TRANS 1

    f b h8)As 0.04 Rotura Agria

    f

    9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal

  • DISEO EN ESTADO LIMITE ULTIMO A FLEXION

    cd1 min

    yd

    1 min Horizontal

    1 min Vertical

    TRANS 1

    f b h8)As 0.04 Rotura Agria

    f

    9)As 0.004 b h Geometrica9)As 0.0012 b h Geometrica10)As 20% As Transversal

  • PLANILLA DE CALCULO

    [cm2/m]

    12 c/ 9.5 12 c /14 R 12 c /14 D 8 c/ 20

    AsADOPTADO

  • 12 9.0

    8 20.0

    ESPACIAMIENTO [cm]

  • 12 9.5

    8 20.0

  • ITEM: HORMIGON - RESISTECIA CARACTERISTICA 25 [Mpa] - H25UNIDAD: M3

    LOSA H o L [m] N Elementos

    MURO 5.400 1.000 1 5.40TOTAL 5.40

    269.62 5.40

    49.93

    Area [m2]VOLMUEN DE HORMIGON

    [M3]

    PESO DE ACERO [Kg]

    VOLMUEN DE HORMIGON

    [M3]

    CUANTIA VOLUMETRI

    CA [Kg A/m3 H]

  • ITEM: ACERO DE DUREZA NATURAL - B 400 SUNIDAD: KG

    PLANILLA DE FIERROS

    POSICION Longitud [m] Cantidad

    1 12 5.800 6.280 11 1 112 10 1.000 3.400 40 1 403 12 6.750 7.230 5 1 54 10 1.000 3.400 30 1 305 12 1.950 2.430 11 1 116 8 1.000 1.320 11 1 117 12 1.000 5.050 11 1 118 12 3.560 5.050 2 1 2

    [mm]

    Longitud Unitaria

    [m]N

    ELEMENTOSCantidad

    Total

  • LONGITUDES DE ANCLAJE - PATILLA BASICA - P/UL

    d [mm]

    6 0.15 0.0600 8 0.16 0.0800 10 0.20 0.1000 12 0.24 0.1200 16 0.32 0.1600 20 0.48 0.2000 25 0.75 0.2500 32 1.23 0.3200

    ACERO DE DUREZA NATURAL - B 400 S

    0.620 42.8300.620 84.3200.620 22.413 R P0.620 63.240 5 31.4160.620 16.573 4.67 29.3420.400 5.808 4.34 27.2690.620 34.441 4.01 25.1960.620 6.262

    TOTAL [Kg] 269.624

    Longitud de Anclaje [m]

    PATILLA [m]

    Peso/U-longitud [Kg/m]

    Peso [Kg]

  • LONGITUDES DE ANCLAJE - PATILLA BASICA - P/UL DIAMETRO DE MANDRIL LONGITUDES DE ANCLAJE [m]

    d [mm] d [mm]

    0.220 6 2.40 60.400 8 3.20 80.620 10 4.00 100.890 12 4.80 121.580 16 6.40 162.470 20 8.00 203.850 25 10.00 256.310 32 12.80 32

    PESO/UL [Kg/m]

    RADIO DE CURVATURA

    [cm]

  • LONGITUDES DE ANCLAJE [m]

    POSICION I

    m

    12 4.32 12.00 12.00 15.00 0.1512 7.68 16.00 16.00 15.00 0.1612 12.00 20.00 20.00 15.00 0.2012 17.28 24.00 24.00 15.00 0.2412 30.72 32.00 32.00 15.00 0.3212 48.00 40.00 48.00 15.00 0.4812 75.00 50.00 75.00 15.00 0.7512 122.88 64.00 122.88 15.00 1.23

    Lb1 [cm] fyk(/20)

    [cm] Lb1 [cm]

    Lb-min [cm]

    Lb adop [m]

  • DATOSMURO DE CONTENCIONDIMENSIONAMIENTODISEO FLEXIONPLANILLA DE ACEROS


Recommended