DC ARC FAULTS IN PHOTOVOLTAIC
SYSTEMS
Submitted in fulfilment of the requirement for the degree of
Master of Philosophy
by
Weerasekara Mudiyanselage Madhawa Kamalajeewa Weerasekara
of
Power Engineering Discipline
School of Electrical Engineering and Computer Science,
Science and Engineering Faculty,
Queensland University of Technology.
2019
DC Arc Faults in Photovoltaic Systems i
Keywords
Arc faults, arc gap, arc impedance, Cassie model, circuit interrupters ,closing,
cooling power, DC arc, dilation, double ground faults, electrodes, erosion, father
wavelet, fault current, frequency domain, function blocks, grid, ground faults, high
frequency, hyperbolic-tangent function, irradiance, MATLAB-Simulink, maximum
power point, Mayr model, micro grids, modelling, Morphology, mother wavelet,
opening, parallel fault, Photo voltaic, power quality, pulse width modulation, random
noise, series fault, S-function, shading, single diode model, solar, strings, structuring
element, test bench, Wavelets.
ii DC Arc Faults in Photovoltaic Systems
DC Arc Faults in Photovoltaic Systems iii
Abstract
Arc faults in PV systems are difficult to study using models developed for
conventional power sources mainly due to non-linear behaviour of PV current and its
dependence on external factors such as irradiance, shading and maximum power
tracking controls. This research presents a unique model derived from fundamentals
of Mayr and Cassie arc models and introducing a hyperbolic tangent function to
approximate arc current at near zero gaps. Arc impedance is widely changed with
heat dissipated through arcs periphery. Unique feature of the proposed model is that
it takes into account this change of impedance with time which could be used to
analyse arcs with changing lengths due to movements of current carrying elements.
A test bench has been built with adjustable gap between two electrodes to conduct
experiments. Both experimental results and simulation outcomes are presented to
verify the proposed model.
Wavelet transform is another technique that can be successfully applied to
detect arc faults in a PV installation. The same test bench was used to capture fault
waveform signatures to develop a wavelet decomposition model that accurately
detected arc faults.
Use of Mathematical Morphology (MM) based filters to detect faults in power
systems has been discussed in recent literature [2-5]. These studies have been
predominantly focused on AC systems and associated arc faults. However, fault
detection applications based on MM filtering in DC systems have not been
adequately discussed. This research also presents how MM based filtering techniques
and its composite operations could be used to successfully detect arc faults in a PV
system. Throughout the analysis, series and parallel arc fault signatures obtained
from an actual PV system with maximum power point tracking (MPPT) control is
used. The effect of MM parameters on detection sensitivity is also explained.
iv DC Arc Faults in Photovoltaic Systems
Table of Contents
Keywords ........................................................................................................................ i
Abstract ......................................................................................................................... iii
Table of Contents .......................................................................................................... iv
List of Figures .............................................................................................................. vii
List of Tables ................................................................................................................. x
List of Abbreviations .................................................................................................... xi
Statement of Original Authorship ................................................................................ xii
Acknowledgements ..................................................................................................... xiii
Chapter 1: Introduction ............................................................................. 1
1.1 Background .......................................................................................................... 1
1.2 Context ................................................................................................................. 2
1.3 Purposes ............................................................................................................... 2
1.4 Significance, Scope and Definitions .................................................................... 3
1.5 Thesis Outline ...................................................................................................... 3
Chapter 2: Literature Review .................................................................... 5
2.1 Solar PV System .................................................................................................. 5
2.2 Faults in a pv system ............................................................................................ 6
2.3 Modeling of PV systems ...................................................................................... 7
2.4 Modeling of dc arcs in pv systems ....................................................................... 7
2.5 detection of dc arc faults using wavelet tranform ................................................ 8
DC Arc Faults in Photovoltaic Systems v
2.6 detection of ARC faults in a pv system using mathematical morphology ...........9
Chapter 3: Modelling of DC Arcs in PV Systems .................................... 10
3.1 Introduction ........................................................................................................10
3.2 DC Arc Test Bench ............................................................................................10
3.3 Test Results ........................................................................................................12
3.4 Proposed arc model ............................................................................................15
3.5 Simulation and Model Verification ....................................................................18
3.6 Conclusions ........................................................................................................21
Chapter 4: Detection of DC Faults using Wavelet Transform ................ 23
4.1 Introduction ........................................................................................................23
4.2 Test setup for arc generation ..............................................................................23
4.3 Experimental results ...........................................................................................24
4.4 Wavelet transform ..............................................................................................25
4.5 Reproduction of fault signatures ........................................................................27
4.6 Parallel fault decomposition ...............................................................................29
4.7 Series fault decomposition .................................................................................31
4.8 Conclusions ........................................................................................................33
Chapter 5: Detection of Arc Faults in a PV System using Mathematical
Morphology 34
5.1 Introduction ........................................................................................................34
5.2 Faults in a Grid connected PV System ...............................................................35
5.3 Mathamatical Morphology .................................................................................36
vi DC Arc Faults in Photovoltaic Systems
5.4 Test Setup for Arc Fault Generation .................................................................. 37
5.5 Parallel Arc Faults ............................................................................................. 39
5.6 Series arc faults .................................................................................................. 41
5.7 analysis of Arc waveforms ................................................................................ 43
5.8 Selection of Structured Element (SE) ................................................................ 45
5.9 Arc fault detection ............................................................................................. 45
5.10 Conclusions ..................................................................................................... 57
Chapter 6: Conclusions and future work ................................................. 58
6.1 Wavelet transform.............................................................................................. 58
6.2 Mathematical Morphology ................................................................................ 59
6.3 Future work ........................................................................................................ 59
Bibliography ................................................................................................ 61
DC Arc Faults in Photovoltaic Systems vii
List of Figures
Fig. 2.1. Components of a PV System ....................................................................... 5
Fig. 2.2. Faults in a PV System ................................................................................. 6
Fig. 3.1. Test Apparatus .......................................................................................... 11
Fig. 3.2. Variation of Arcing Gap ............................................................................ 12
Fig. 3.4. Arc voltages at different irradiance levels. ................................................ 13
Fig. 3.5. Behaviour of current through and voltage across the arc. ........................... 14
Fig. 3.6. Arc Voltage and Current (PU Values). ...................................................... 15
Fig. 3.7. Hyperbolic tangent function for Vs representing Vi and Vto ........................ 16
Fig. 3.8. Circuit model ............................................................................................ 17
Fig.3.9. Simulation block in MATLAB-Simulink ................................................... 18
Fig. 3.10. Simulation and Experimental Results ...................................................... 19
Fig.3.11. Simulation Voltage with increasing irradiance.......................................... 20
Fig. 3.12. Simulation Current with increasing irradiance. ........................................ 20
Fig.4.1. Test circuit ................................................................................................. 23
Fig.4.2. Series and parallel arc fault waveforms ...................................................... 25
Fig.4.3. Wavelet decomposition in Simulink ........................................................... 27
Fig.4.4. Parallel fault voltage signature from signal builder ..................................... 28
Fig.4.5. Series fault voltage signature from signal builder ....................................... 28
viii DC Arc Faults in Photovoltaic Systems
Fig.4.6. Decomposition results for parallel fault voltage. ........................................ 30
Fig.4.7. Parallel fault signal (upper) and its wavelet decomposition (lower)
results. ...................................................................................................... 31
Fig.4.8. Series fault decomposition results .............................................................. 32
Fig.4.9. Series fault signal (upper) and its wavelet decomposition (lower)
results. ...................................................................................................... 33
Fig.5.1 Grid connected PV system with nxm number of modules ............................ 35
Fig.5.2 Test circuit (top) and setup (bottom). .......................................................... 38
Fig.5.3. Parallel Arc waveforms ............................................................................. 39
Fig.5.4. Parallel arc current ..................................................................................... 40
Fig.5.5. Parallel arc voltage .................................................................................... 40
Fig.5.6. Series arc waveforms ................................................................................. 41
Fig.5.7. Series arc current ....................................................................................... 42
Fig.5.8. Series arc voltage ....................................................................................... 42
Fig.5.9. Dilation and Erosion of Parallel Fault Current ........................................... 46
Fig.5.10. Closing and Opening of Parallel Fault Current ......................................... 47
Fig.5.11. CODO Operation of Parallel Fault Current .............................................. 48
Fig.5.12. Dilation, Erosion, Closing, Opening and CODO functions of Parallel
Fault Voltage. ........................................................................................... 49
Fig.5.13. Dilation, Erosion, Closing, Opening and CODO functions of Series
Fault Current. ............................................................................................ 50
DC Arc Faults in Photovoltaic Systems ix
Fig.5.14. Dilation, Erosion, Closing, Opening and CODO functions of Series
Fault Voltage............................................................................................. 52
Fig.5.15. Effect of length of SE on CODO for Series Fault Voltage. ....................... 54
Fig.5.16. Effect of length of SE on CODO for Parallel Fault Voltage. ..................... 55
x DC Arc Faults in Photovoltaic Systems
List of Tables
Table.3.1. PV Module characteristics…………………………………………13
Table 5.1. Electrical characteristics of PV Module at normal operating cell
temperatures………………………………………………………………………....38
Table.5.2 Actual data set of arc waveform……………………………...……43
Table.5.3 Normalized data set of arc waveform………………………………44
DC Arc Faults in Photovoltaic Systems xi
List of Abbreviations
AC Alternating current
CODO Closing Opening Difference Operation
FFT Fast Fourier Transform
GFCI Ground Fault Circuit Interrupters
GFPD Ground Fault Protective Devices
HIF High Impedance Fault
HV High Voltage
IEA PVPS International Energy Agency Photovoltaic Power Systems Program
MM Mathematical morphology
MPPT Maximum power point tracking
OCPD Over Current Protective Devices
PV Photovoltaic
PWM Pulse width modulation
SE Structural Element
UHS Ultra-High Speed
WT Wavelet Transform
xii DC Arc Faults in Photovoltaic Systems
Statement of Original Authorship
The work contained in this thesis has not been previously submitted to meet
requirements for an award at this or any other higher education institution. To the
best of my knowledge and belief, the thesis contains no material previously
published or written by another person except where due reference is made.
Signature:
Date: May 2019
QUT Verified Signature
DC Arc Faults in Photovoltaic Systems xiii
Acknowledgements
I would first like to thank my principal supervisor Professor Mahinda
Vilathgamuwa, Science and Engineering Faculty, Queensland University of
Technology. Professor was always there when ever I had a question about my
research or experiments.
I would also like to thank Dr.Yateendra Mishra, my associate supervisor, of
Science and Engineering Faculty. His expertise in practical applications of grid
connected PV systems was extremely helpful. Assistance and encouragements from
members of staff in the faculty is also noteworthy.
Last but not the least, I would like to thank my family, my wife and kids, for
spiritually supporting me during last few years of my study.
Thank you all.
Madhawa Weerasekara
Chapter 1: Introduction 1
Chapter 1: Introduction
1.1 BACKGROUND
Photovoltaic (PV) systems convert energy from solar radiation into useful and
usable electrical energy. As the concerns of environmental effects in the use of fossil
fuels for energy and energy security become critical in global energy scenario, use of
PV systems has increased significantly. For example, annual growth of installed PV
system capacity in 2015 in the International Energy Agency Photovoltaic Power
Systems Program (IEA PVPS) countries was around 26.5% to reach a total installed
capacity of around 230GW [1].
The first PV cell was developed by Fritz in 1883 and it’s efficiency was less
than 1% [6]. After several other developments by various scientists, first Silicon PV
cell with an efficiency of 6% was developed by Ohl in 1941 which was further
developed by Bell Laboratories to achieve 11% efficiency by 1954[6]. In 2019,
demonstrated efficiency of a thin film GaAs is as high as 29%[7].
Solar energy offers important benefits compared to other energy sources.
Availability in abundance, absence of moving parts, renewability and long effective
life are some of them. On the other hand, PV systems have issues such as high
dependency on time and weather conditions, rapid variation of energy output due to
cloud and shading and need of expensive power conversion equipment are
noteworthy. In addition, behaviour of PV systems under various faults is very much
different to that of conventional AC power systems.
As in the case of other energy sources and systems, such as Coal & Hydro
power, PV systems have fault scenarios which affect its life span, reliability,
efficiency and very importantly safety of personnel and property. But these fault
scenarios are very much different from that of other power sources mainly due to
nonlinear output and current-limiting nature of PV arrays’ operation [8] . Arc faults
in the DC side of a PV system in particular raises concerns as they are difficult to
detect using conventional protection equipment used in power systems. These arc
2 Chapter 1: Introduction
faults do not generate large fault currents, though they could create over heating of
cables and surroundings, and hence could remain undetected.
The fire hazards on April 5th
, 2009 in Bakersfield, California, and April 16th
,
2011 in Mount Holly, North Carolina are most quoted examples for evidence of lack
of effective fault isolation in PV systems.
1.2 CONTEXT
A fault in a PV system could create dangerously high temperatures around
faulty sections of the system yet to be undetected by traditional protection devices. A
PV panel is a nonlinear current source and also has very limited generation capacity
during low irradiance levels. Both these facts cause a fault in a PV system to produce
currents smaller than thresholds of protective switchgear. Hence an arc fault in a PV
system could remain undetected for prolong periods and could still generate enough
heat to ignite surrounding structures etc.
Behaviour of system current and voltage during an arc fault in the DC side is
confusingly similar to that of during rapid change of irradiance. Also, DC arc
current does not have periodic zero crossing and could result in sustained fault
currents.[9].
1.3 PURPOSES
This research will focus on a detailed study of various fault scenarios in a PV
system and their detection techniques. It will also look into different types of
inverters and converters that are used in distributed generation systems.
Among various faults, DC arcs are considered one of major reasons for
catastrophic failures that caused electrical fires [10]. Principal objective of the
research is to propose a method to detect DC arc faults by separating it from other
system noises even under low irradiance levels.
Chapter 1: Introduction 3
1.4 SIGNIFICANCE, SCOPE AND DEFINITIONS
Along with the drive to increase renewable energy usage, installed capacity of
solar power systems has grown exponentially. Protection of these systems against arc
faults is a challenge due to non-linear behaviour of PV cell’s voltage-current
relationship and effect of shading. It is of paramount importance to the growth of PV
energy usage that these systems are safe and have adequate protection equipment to
prevent dangers to public and property in case of a fault.
Being one of the most difficult faults to detect, timely detection of DC arc
faults plays a significant role in making PV systems safe.
This research investigates several options to detect arc faults in a PV
installation that consists of MPPT and a charge controller.
Both series and parallel arcs are studied using an experimental set up to
generate arcs and to store voltage and current waveforms. These waveforms are then
analysed with several novel approaches to detect arc faults.
Scope of the study is limited to series and parallel arc faults and does not
consider other faults such as ground, double ground or arc faults between different
strings of a solar power system.
1.5 THESIS OUTLINE
A comprehensive literature review was carried out to gather knowledge on
existing research in the field of arc faults detection in photovoltaic power systems.
Chapter 2 provides details of existing literature in different areas aligned with
boundaries of this thesis. Review is sub divided into several sections to present
information under each heading that forth coming chapters are arranged.
Chapter 3 presents a development of a model to represent DC arcs in PV
systems. Mayr and Cassie arc models were used as the base for this development and
experimental results of arc voltage and current were used to represent the arc in a PV
4 Chapter 1: Introduction
installation. Experimental results show a close match with model output proving the
suitability of this model for studies on DC arcs in PV systems.
Wavelet transform is another technique that could be used to detect arc faults.
An in-depth study as to how wavelet transformed could be used to detect arc faults in
a PV system is described in Chapter 4. It is proven at the end of this chapter that
wavelet transformation could also be used to identify if there is any series or parallel
arc in the electrical circuitry before MPPT/Charge controller of a PV installation.
Most important area of this study is described in Chapter 5 where a novel
method to detect arc faults using Mathematical Morphology is presented. This
section also uses experimental results of arc voltage and current waveforms as the
input for the proposed detection system.
A brief conclusion is given in Chapter 6. This research opens up some avenues
for future studies to develop same concepts further to address arc faults in practical
photovoltaic installations. These future activities are also described in this final
chapter.
Chapter 2: Literature Review 5
Chapter 2: Literature Review
2.1 SOLAR PV SYSTEM
Solar PV systems could either be grid connected or stand along. Stand along
systems feed a local load, generally small in capacity. Grid connected systems are
mostly used in commercial scales and comprises of four main components[11].
a. PV Array
b. MPPT Controller
c. Inverter
d. Grid Interface
Other than the PV array, other three components are usually incorporated
into one unit and it is usually called inverter.
Fig. 2.1. Components of a PV System
MPPT will control power flow in such a way that maximum power at a given
irradiance level is harnessed. The inverter then produces AC power from DC bus fed
from MPPT and grid interface synchronises AC supply with grids main system.
6 Chapter 2: Literature Review
2.2 FAULTS IN A PV SYSTEM
When a PV system is in normal operation, its output current is controlled by
Maximum Power Point Tracking (MPPT) system in order to maximize power
extraction. In case of a sudden fault, MPPT will shift the system to a new operating
point which gives maximum power output under post fault conditions. Hence any
fault detection system will have a very narrow time gap to detect the fault before
system re-settles at new operating points. This makes its challenging for traditional
protection equipment to detect the faults.
Also, if a fault occurs during low irradiance, fault currents may be below the
threshold currents of traditional detection devices. Even though fault currents may
also be very low at the beginning, once the system moves to normal irradiance levels,
for example, during night to day transition, fault currents can increase to dangerous
levels.
Existing literature discuses several fault scenarios in PV systems. These
include;
1. Ground Faults
2. Arc Faults
3. Line –to-line Faults
4. Double ground Faults
Fig. 2.2. Faults in a PV System
Chapter 2: Literature Review 7
A ground fault is a situation where there is an unintentional current path exists
to ground. In a typical AC system, ground faults are detected by ground fault circuit
interrupters (GFCI) which works by detecting mismatch of current flow in incoming
and outgoing conductors. But in case of a PV system, due to the fact that there are
several power sources and locations of potential faults, ground fault detection takes
the form of an overcurrent circuit breaker with a low detection threshold [12]. Three
commercially available ground fault detection equipment and their limitations are
described in [10].
2.3 MODELING OF PV SYSTEMS
A PV system consists of solar PV modules arranged in an arrays and power
electronics converters. PV modules are connected in series to form a string and these
strings are then connected parallel to form the array. Number of PV panels in a string
will determine the voltage capacity of the installation, while current capacity is
determined by the number of strings connected in parallel.
PV systems have nonlinear output characteristics which depend on irradiance
and temperatures and these dependencies become more complicated under partially
shady situations. It is very important to understand behaviour of PV panels under
these different field and load conditions in order to harness maximum energy.
A model with a controlled current source and an S-Function block in
MATLAB-Simulink is presented in [13]. Various array and string combinations
could be set in this model with independent panel parameters such as irradiance and
temperature to model actual field conditions.
Effect of blocking and by-pass diodes is incorporated into a PV model in [14].
This model could be used to analyse MPPT systems under partial shading.
Identification of local and global maximum power points is very important to harness
total power available under shady conditions and this model could assist design of
effective maximum power point tracking circuits.
2.4 MODELING OF DC ARCS IN PV SYSTEMS
Studies on electrical arcs are fundamentally based around developing models to
approximate their behaviour under various supplies and load conditions. These
8 Chapter 2: Literature Review
models are widely used to design detection and isolation methods to protect power
networks from system deterioration and safety hazards. With the increased use of
DC sources and micro-grids, study of arcs in DC systems has become important in
recent years. In case of a Photovoltaic (PV) system, the source is essentially a
nonlinear current source with a magnitude that depends on factors such as irradiance
and panel parameters [15] which create special research space for arc faults in PV
power systems.
A literature survey conducted revealed that most of the studies on arc
modelling published are based on constant supply voltages which do not represent
PV sources [16-19]. An arc model using SPICE is developed in [20] to analyse series
and parallel arc faults in PV arrays. It was also identified different ways that the
inverter will react to arc faults depending on their severity during MPPT tracking
operation.
There exists a research area to investigate arc behaviour of systems fed by
nonlinear current sources and chapter 4 presents a model that could be used in
simulations and further studies of arc faults in PV systems.
2.5 DETECTION OF DC ARC FAULTS USING WAVELET TRANFORM
Prior research in to arc fault detection using frequency domain analysis in
terms of Fast Fourier Transform (FFT) and Wavelet decomposition exist in literature
[21-24]. These studies are either based on simulated arc faults and system noises or
experimental fault signals with simulated system noises in voltage and current
waveforms. Noises generated by MPPT under changing irradiance levels and due to
fault current itself are not considered and hence it creates a research space for a study
of the use of wavelet decomposition of faults in conjunction with MPPT noises.
A detection methodology for on-line voltage transients using wavelet transform
is proposed in [25]. This model detects the presence of voltage transients and also
distinguishes between various sources of these transients. But the proposed approach
works only under constant voltage AC systems and hence not suitable in studies of
arc faults in PV installations.
Chapter 2: Literature Review 9
2.6 DETECTION OF ARC FAULTS IN A PV SYSTEM USING
MATHEMATICAL MORPHOLOGY
Use of Mathematical Morphology (MM) based filters to detect faults in power
systems have been discussed in recent literature [2, 3, 26]. These studies have been
predominantly focused on AC systems and associated arc faults. However, fault
detection applications based on MM filtering in DC systems have not been
adequately discussed. Chapter 6 presents how MM based filtering techniques and
their composite operations could be used to successfully detect arc faults in a PV
system. Throughout the analysis, series and parallel arc fault signatures obtained
from an actual PV system with maximum power point tracking (MPPT) control is
used. Effect of MM parameters on detection sensitivity is explained.
The method described utilizes mathematical morphology to extract waveform
signatures of current and voltage of a PV array during a fault to identify faulty
condition.
A method of combined use of Multi-resolution Morphological Gradient and
Multi-filter units of MM was developed in [27]. It describes how this method could
successfully be used to detect fault generated transients of a HV transmission line.
Mathematical Morphology was used in [5] to propose an Ultra High Speed (UHS)
directional protection technique in AC power transmission lines. Morphological
Transforms are also used in [3] for power quality analysis in AC systems.
10 Chapter 3: Modelling of DC Arcs in PV Systems
Chapter 3: Modelling of DC Arcs in PV
Systems
3.1 INTRODUCTION
Arc faults in a PV system are difficult to study using models developed for
conventional power sources mainly due to non-linear behaviour of PV current and its
dependence on external factors such as irradiance, shading and maximum power
tracking controls.
This paper presents a unique model derived from fundamentals of Mayr and
Cassie arc models and introducing a hyperbolic tangent function to approximate arc
current at near zero gaps. Arc impedance widely changes with heat dissipated
through arcs periphery. Unique feature of the proposed model is that it takes into
account this change of impedance with time which could be used to analyse arcs with
changing lengths due to movements of current carrying elements.
A test bench has been built with adjustable gap between two electrodes to
conduct experiments is presented in para 3.2. Next section presents results of
experiments and finally a conclusion to summarise results. Both experimental results
and simulation outcomes are presented to verify the proposed model.
3.2 DC ARC TEST BENCH
A test apparatus was built with two copper electrodes that are moved away
from each other in axial direction at constant speed. Electrodes are connected in
series with a PV module and the gap between rounded tips of electrodes was kept at
zero distance before commencing the test. Current was allowed to pass through
electrodes while moving them away creating an arc in between. Arc voltage, arc
current and gap were measured and stored.
Chapter 3: Modelling of DC Arcs in PV Systems 11
As shown in Fig. 3.1, moving electrode was connected to a threaded shaft
which allows it to be moved horizontally by rotating drive wheel. Speed of gap
separation is governed by thread pitch of the shaft and speed of rotation of drive
wheel. A linear variable resistor was connected with drive wheel through a belt.
Increase of voltage drop across this resistor during electrodes’ separation was used to
measure gap distance. This allows a synchronized measurement of arc gap with arc
voltage and current using an AGILENT DSO-X 2024 200MHz oscilloscope.
In practical PV installations, arc gap during a fault is uncontrolled and random
and hence the arc impedance. By using a test bench with a controlled gap, it is
intended to study variation of arc impedance across complete range of possible arc
lengths with varying levels of irradiance. The gap between electrodes was increased
from zero at a fairly constant speed as shown in Fig. 3.2, till arc got extinguished.
Fig. 3.1. Test Apparatus
12 Chapter 3: Modelling of DC Arcs in PV Systems
Fig. 3.2. Variation of Arcing Gap
3.3 TEST RESULTS
Tests were conducted at various irradiance levels on a summer day morning
using a Hanwha SF220, 250W PV module.
Fig. 3.3. Measuring arrangement
Chapter 3: Modelling of DC Arcs in PV Systems 13
Arc was allowed to form by moving electrodes away and voltage across and
current through electrodes were measured. Voltage across separating electrodes
under different irradiance levels are illustrated in Fig. 3.4.
Table.3.1. PV Module characteristics.
Parameter Value
Maximum Power (Pmax)
Open Circuit Voltage (Voc)
Short Circuit Current (Isc)
Voltage at Maximum Power (Vmpp)
Current at Maximum Power (Impp)
182 W
34.2 V
7.07 A
27.7 V
6.58A
Fig. 3.4. Arc voltages at different irradiance levels.
14 Chapter 3: Modelling of DC Arcs in PV Systems
Irrespective of the level of irradiance available, there exists a voltage drop, Vi,
across electrodes at zero gap. This is due to touch resistance between surfaces of two
electrodes and is dependent on geometry and material of the same [19]. When the
gap is increased, an arc starts to form across electrodes and arc voltage jumps to a
turn-on voltage, Vto which again is dependent on material composition of electrodes
[19]. Maximum arc voltage before it extinguishes shows firm dependence on
irradiance level. With higher irradiance, PV module could maintain a current flow
through a longer arc which intern resulted in higher arc voltage. Once the arc is
extinguished, voltage settles down at PV module’s open circuit voltage.
Results of a test at 83,000 Lux, i.e. approximately 655 W/m2 irradiance, are
illustrated in Fig.3. 5 below.
Fig. 3.5. Behaviour of current through and voltage across the arc.
Chapter 3: Modelling of DC Arcs in PV Systems 15
Fig. 3.6. Arc Voltage and Current (PU Values).
In Fig. 3.5, as gap is increased linearly with time, waveforms are plotted
against time instead of gap length. At zero gaps, current fed by PV module is
equivalent to its short circuit current. Ultimately current will drop to zero as gap
length, or time, increases.
A sixth order polynomial approximation to power fed into the arc, product of
voltage and current, shows that it reaches a maximum value that closely matches
with PV modules maximum power output at normal operating temperature.
In order to display current and voltage independent of PV panel capacity, per
unit values were calculated by dividing arc current and voltage by panel’s short
circuit current and open circuit voltage respectively. These per unit values are plotted
in Fig. 3.6.
3.4 PROPOSED ARC MODEL
Mayr and Cassie arc models are widely used in literature in modelling arc
behaviour. Both these models are based on the fact that energy stored in the arc is
16 Chapter 3: Modelling of DC Arcs in PV Systems
equal to the difference between energy supplied into the arc by source voltage and
energy dissipated from arc into its surrounding environment.
In Mayr model, arc is assumed to be a cylinder having constant radius where
energy dissipation is only caused by thermal conduction through its outer surfaces.
This model is best applicable to small currents and hence used in this study. Dynamic
characteristics of the arc are governed by the equation (1) in which Z, τ and Pin are
arc impedance, arc time constant and power fed into the arc respectively. P0 is the
cooling power loss.
���� = �
� �1 − �� (1)
P0 is power fed into the arc when arc is stable [28]. In the experiment, as arc
length is increased, P0 is assumed to be time (t) dependent, as a result of linear
relationship of arc gap with time, and can be approximated by a linear relationship
a+bt and equation (1) could be re-written as,
���� = �
� �1 − �� .�(����) (2)
Electric arc is assumed to be purely resistive and power fed into the arc, Pin, is
presented in terms of arc impedance and current flowing through the arc.
Fig. 3.7. Hyperbolic tangent function for Vs representing Vi and Vto
Chapter 3: Modelling of DC Arcs in PV Systems 17
As shown in Fig. 3.7, at the time an arc is formed across the electrodes, there
exist two voltage drops Vi and Vto. Combination of these two voltage drops, Vs, can
be approximated by a hyperbolic-tangent function given by (3) where A,B,α and β
are constants.
�� = �. tanh ��( −∝)" + $ (3)
Fig.4.7. illustrates Vs for A=0.18, B=0.25, α=0.01 and β=300.
In the circuit model given in Fig.3.8, R and L are resistance and inductance of
circuit from PV module to arc location. Z represents arc impedance and Rs
corresponds to the circuit element responsible for voltage Vs.
Fig. 3.8. Circuit model
Circuit equations for this are:
% = &(' + () + ) ���� + ��
���� = *+ ,% − &(' + () − �. tanh ��( −∝)" + $- (4)
On the other hand, as derived in [15], single diode model of a PV module could
be used to derive a relationship between PV voltage U and current i, in a PV array
composed of several connected PV cells. This relationship is given in (5):
& = ./0 − .1 23456789:; < − 1= − >�?8�?@ (5)
18 Chapter 3: Modelling of DC Arcs in PV Systems
Ipv and I0 are photovoltaic and saturation currents of the array of Ns cells in
series and Np cells in parallel. Thermal voltage of the array, Vt=Ns k T/q, where q is
the charge of electron (1.60217646×10−19
C) and k is Boltzmann constant
(1.3806503×10−23
J/K). Temperature of p-n junction in Kelvin is T.
3.5 SIMULATION AND MODEL VERIFICATION
Equations (2) to (5) were modelled in MATLAB-Simulink environment. In
order to avoid convergent issues in simulations, PV block of MATLAB was used
instead of equation (5).
Fig.3.9. Simulation block in MATLAB-Simulink
Vz in Fig. 3.8 is obtained by simulating equation (2) to get arc impedance Z and
multiplying it by PV current i. Simulation of equation (3) gives us Vs and hence
voltage drop across the arc (Vz+ Vs). This voltage and PV current i were plotted
against time and compared with experimental results. Time is selected as
independent variable instead of gap length due to linear relationship between them.
Chapter 3: Modelling of DC Arcs in PV Systems 19
Fig. 3.10. Simulation and Experimental Results
Simulation results of arc voltage shows close agreement with test results.
Experimental arc current has slightly higher readings compared to simulation results,
especially towards the end of the arc duration. This still gives a fair match for
modelling purposes. Simulation circuit does not produce any high frequency noise
that is present in actual current and voltage signals during an arc. This difference is
also visible in the results.
Fig. 3.11 and Fig. 3.12 illustrate simulation results at different irradiance
levels.
20 Chapter 3: Modelling of DC Arcs in PV Systems
Fig.3.11. Simulation Voltage with increasing irradiance
Fig. 3.12. Simulation Current with increasing irradiance.
It is evident from Fig. 3.10 that simulated arc voltage and current show close
match with experimental results. Experimental current has high frequency noise
Chapter 3: Modelling of DC Arcs in PV Systems 21
captured by high resolution of measuring instrument whereas simulation current only
shows steady values. Simulation current is slightly less that experimental current
which may have caused by approximations of constants and resistance of cables etc.
Arc voltage curve clearly shows two voltage drops Vi and Vto that were
explained earlier. With increasing irradiance, arc is able to continue to exist for
longer duration that is equivalent to longer arc gap.
Short circuit current of PV module increases with increasing irradiance. This
is visible in Fig. 3.11, where current at zero gap increases with irradiance.
3.6 CONCLUSIONS
An arc model to study high impedance arc faults in a PV system was
developed. Originality of the model is that it considers change of arc length which
improves accuracy of modelling and takes into account resistances that appear just
before and after arc’s initialization.
Simulated and measured currents and voltages show good agreement with
experimental results. Though the model disregards high frequency noise generated
during the arc, it could be used to model general behaviour of arc current and voltage
across the arc in a PV system.
In reality, arc length does not vary smoothly. The length of arc could also
change randomly with time and this was not modelled due to limitations of the
experimental setup.
Modelling under random gap separation instead of constant speed is an area
for further development which could be used to better represent actual field
scenarios.
Chapter 4: Detection of DC Faults using Wavelet Transform 23
Chapter 4: Detection of DC Faults using
Wavelet Transform
4.1 INTRODUCTION
Arc faults in DC systems have become a concern in the recent past due to rapid
growth of PV installations. Presence of cable connectors could lead to series arc
faults due to aging and accidental damages to cables and rodent bites could create
parallel arcs between current carrying parts of an installation [29].
This chapter is structured in the following sections: the test bench used for safe
generation and digitally storing series and parallel arc fault experiments,
experimental results obtained by created arc faults, a description of wavelet
transform, wavelet decomposition of fault signatures and finally a conclusion.
4.2 TEST SETUP FOR ARC GENERATION
A test bench was created with a PV module and a PWM controller having
MPPT as illustrated in Fig.4.1. A digital storage oscilloscope was used to store arc
waveforms.
Fig.4.1. Test circuit
PV module was directly connected to PWM charge controller which has inbuilt
MPPT function. 12Vdc battery and a DC load were connected to create sufficient
24 Chapter 4: Detection of DC Faults using Wavelet Transform
load and series and parallel arc tests were done at approximately 500W/m2 and 330
W/m2 irradiances respectively.
An arc was formed by moving two contact points of Series Fault away from
each other and a parallel arc was formed by a short circuit across positive and
negative sides of the PV module. In each case, waveforms of voltage across PWM
and current through the fault were recorded.
4.3 EXPERIMENTAL RESULTS
Results obtained were the waveforms of current and voltage signatures of arcs.
For comparison purposes, waveforms were recorded from a point of time prior to arc
occurrence. This portion of the waveforms contains noises created by PWM during
its normal operation.
Arc current and arc voltage are plotted against time in Fig.4.2 below and it
gives an indication of high frequency noise and random nature of both current and
voltage.
-4.00
-3.00
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
-5.E
-06
-4.E
-06
-2.E
-06
-3.E
-07
1.E
-06
3.E
-06
4.E
-06
6.E
-06
8.E
-06
9.E
-06
Arc
Cu
rre
nt
[A]
Arc
Vo
lta
ge
[V
]
Time [S]
SERIES ARC FAULT
DC Voltage ARC Current
Chapter 4: Detection of DC Faults using Wavelet Transform 25
Fig.4.2. Series and parallel arc fault waveforms
Pre fault current of series fault scenario is the load current that flows into
charge controller. This current changes randomly and rapidly during the arc and once
the arc is fully extinguished, it settles down at zero.
Current that flows through the parallel arc prior to the fault is zero as there is
no conductive path across. Once the contacts are closed and opened to create an arc,
this current also changes rapidly and reaches zero once contacts are wide open and
there is no more arc across.
In both series and parallel faults, pre fault voltage is the same and it depends on
irradiance and connected load based on PV modules I-V characteristics. Post fault
voltage of series fault will rise towards PV panels open circuit voltage where as that
of parallel fault settles down at pre fault voltage if there is no change in irradiance
and connected loads.
4.4 WAVELET TRANSFORM
Just like Fourier Transform, Wavelet transform (WT) is a linear transformation
but it allows more accurate time localization of different signal components.
Due to the wide variety of signals and problems encountered in power
engineering, there are various applications of wavelet transform, such as fault
detection, load forecasting, and power system measurement. The wavelet analysis
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
5.00
0.00
5.00
10.00
15.00
20.00
25.00
-3.E
-04
-2.E
-04
-2.E
-04
-1.E
-04
-8.E
-05
-3.E
-05
2.E
-05
7.E
-05
1.E
-04
2.E
-04
Arc
Cu
rre
nt
[A]
Arc
Vo
lta
ge
[V
]
Time [S]
PARALLEL ARC FAULT
ARC Voltage [V] ARC Current [A]
26 Chapter 4: Detection of DC Faults using Wavelet Transform
procedure is based on a pair of wavelet prototype functions, called the wavelet
function (mother wavelet) and scaling function (father wavelet) –together they
provide a localized signal processing method to decompose the differential signal
into a series of wavelet components, each of which is a time-domain signal that
covers a specific frequency band [24].
Discrete Wavelet Transform (DWT) is defined as,
A(B, D) = ∑ F(G)HI,J(�)K∈� (1)
B ∈ M, D ∈ (
where s(n) is the signal to be analysed and C(j,k) is the corresponding wavelet
coefficient. Also n is the sample number and gj,k(n) is the discrete scaling function.
Scaling function is defined by
gj ,k (n) = 2g− j /2
g (2− j
n − k ) (2)
In order to analyse fault waveforms, a 12th
order asymmetric Daubechies
Wavelet transform with 10 levels were used in MATLAB Simulink. Signals were
converted into a frame output of 1024 samples before applying wavelet transform.
Chapter 4: Detection of DC Faults using Wavelet Transform 27
Fig.4.3. Wavelet decomposition in Simulink
4.5 REPRODUCTION OF FAULT SIGNATURES
Fault signatures recorded in 4.3 above were transformed into a signal builder in
MATLAB-Simulink so that they could be used as the input for Wavelet
decomposition model. Time axis limits were selected in such a way that fault occurs
around the midpoint of measured range. This allows differentiate pre-fault and post
fault regions of the waveform concerned.
28 Chapter 4: Detection of DC Faults using Wavelet Transform
Fig.4.4. Parallel fault voltage signature from signal builder
Fig.4.5. Series fault voltage signature from signal builder
Chapter 4: Detection of DC Faults using Wavelet Transform 29
4.6 PARALLEL FAULT DECOMPOSITION
Once the parallel fault voltage was generated using a signal builder, it was fed
into wavelet decomposition model and resulted waveforms could be plotted against
time.
Fig.4.6 gives a comparison of decomposition results for each frequency sub
band. Graphs “A” to “K” represent results in frequency sub bands from 1 to 11
respectively.
First few sub band results do not show much difference in the shape of signal
between faulty and non-faulty regions. But, as sub band frequency increases, shape
of the output signal changes in the faulty region and signal “I” appears to represent
faulty region better. After this step, noise in the input signal start to appear in the
non-faulty sections.
All resulted waveforms vary around zero volts and hence the result is
independent of the normal amplitude of the measured signal.
30 Chapter 4: Detection of DC Faults using Wavelet Transform
Fig.4.6. Decomposition results for parallel fault voltage.
A close comparison of parallel fault voltage and its wavelet decomposition “I”
result is presented below:
Chapter 4: Detection of DC Faults using Wavelet Transform 31
Fig.4.7. Parallel fault signal (upper) and its wavelet decomposition (lower) results.
In order to avoid start up noise being identified as a fault, first 0.5x10-4
seconds
portion of measured signal was omitted. Rest of the measured voltage remains stable
other than during arc fault. During this period of stable voltage, wavelet
decomposition signal remains close to zero. Once the arc starts to form, amplitude of
decomposition signal varies between -25V and +15V approximately.
4.7 SERIES FAULT DECOMPOSITION
Similar to the way that parallel fault voltage was analysed, series fault voltage
was also decomposed using wavelet transform.
As the level of decomposition increases, amplitude of resulted waveform
increases. There is also shift of signal along time axis that results in a delay to detect
arc fault. Third level signal gives adequate separation of faulty region of the signal
and it could be used for detecting purposes.
32 Chapter 4: Detection of DC Faults using Wavelet Transform
Fig.4.8. Series fault decomposition results
Chapter 4: Detection of DC Faults using Wavelet Transform 33
Fig.4.9. Series fault signal (upper) and its wavelet decomposition (lower) results.
Most importantly, resulted signal amplitude is either zero or very close to zero
during healthy operation of the system. During arc fault its amplitude increases and
varies between -6V and +6V making it a reliable source to detect a series arc fault.
4.8 CONCLUSIONS
Wavelet analysis was used to study two most common real arc faults, series
arcs and parallel arcs, in a PV system. Different frequency sub bands were used to
investigate best suitability to detect series and parallel faults. Separate fault
signatures from the test set up were used to apply proposed detection approach.
Results prove that Wavelet transform approach could be used as a tool to detect and
separate arc faults conditions from healthy operation in a PV system by measuring
voltage across DC side MPTT controller/inverter.
Different frequency sub bands are to be used to detect arc fault depending on
the fact that the fault is a parallel or a series arc fault.
34 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
Chapter 5: Detection of Arc Faults in a PV
System using Mathematical
Morphology
5.1 INTRODUCTION
Mathematical morphology (MM) is a non-linear signal transformation tool that
could be used to modify the shape of a signal [30]. It provides an approach to process
images based on a function known as Structuring Element (SE) by analysing the way
this SE fits into the original image. MM deals with the shape of a signal in time
domain and hence defers itself from approaches such as Fourier transform and
Wavelet transform which functions in frequency domain.
Arc faults in a PV power network draw much lesser currents that are not
sufficient to activate conventional protective switchgear [31]. Detection of such
faults in a PV system becomes more challenging due to specific nature of Voltage
/Current behaviour of PV modules and also due to effect of MPPT. This Chapter
investigates how MM could be used in detecting series and parallel Arc in a PV
system.
Section 5.2 investigates various faults in grid connected PV systems followed
by explanation of MM in section 5.3. Analysis of parallel and series arc faults are
presented in para 5.5 and 5.6 respectively. The waveforms obtained from
experiments are analysed in section 5.7 which explains modifications done in order
to prepare these waveform data to be able to use in MATLAB.
Section 5.8 describes selection of structural element for MM transformation
and section 5.9 presents results from MM analysis followed by a conclusion.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 35
5.2 FAULTS IN A GRID CONNECTED PV SYSTEM
A grid connected PV system typically will have several parallel connected
strings to provide adequate current capacity and each string will have series
connected PV modules which in turn decide DC voltage of the system.
Fig.5.1 below shows major components of a typical grid connected PV system.
Fig.5.1 Grid connected PV system with nxm number of modules
Generally PV systems are protected against over current and earth leakages by
Over Current Protective Devices (OCPD) and Ground Fault Protective Devices
(GFPD) respectively. These devices are located just prior to the inverter which also
operates as MPPT device.
Line to line faults and ground faults are the most common types of faults that
could create hazardous overheating of cables and associated equipment[32]. Line-
line fault could be classified as an accidental short circuiting of two points of PV
array with different potentials. This could be between two points in two different
strings (A of Fig.5.1), between two points in the same string (B of Fig.5.1) or
between two feeder cables (C in Fig.5.1). In case of high impedance faults, all of
these faults could be considered as parallel faults.
36 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
A series arc fault could occur at any point of discontinuity in the array and this
chapter only studies a series fault that occurs at a feeder cable (D of Fig.5.1). Any
such imperfect connection could be a result of contact separation that leads to a
series arc condition [19].
All types of parallel faults discussed above provide a closed path for the fault
current that does not pass through the protective devices located at the end of feeder
cables. Furthermore, series arc faults will also reduce the current that flows through
protection devices making it impossible for these devices to detect any of above
faults.
This chapter proposes a method to use variations of the voltage across inverter
terminals, which are a result of currents passing through arc fault to detect faulty
conditions.
5.3 MATHAMATICAL MORPHOLOGY
Mathematical Morphology is a theory that provides an algebraic formulation to
apply neighbourhood operations on signals by interaction between the signal under
analysis and a SE [3] . The signal and SE are considered sets of points and SE acts as
a sliding window which moves through the signal while interacting with the shape of
the signal and detects specific features in the neighbourhood of every point in the
signal.
Erosion and Dilation are two basic operations of MM, which are defined as
below:
Let input signal be denoted by (G) , defined in domain NO = PQ1, Q*, … , QKS , SE by H(T) in domain NU = PV1, V*, … , VWS where G and T are integers such that
G > T.
Dilation of Y(G) by H(T), denoted by (Y ⊕ H)(G), is defined as,
(Y ⊕ H)(G) = T[QPY(G − T) + H(T)S, 0 ≤ (G − T) ≤ G,T ≥ 0 (1)
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 37
Erosion of Y(G) by H(T), denoted by (Y ⊖ H)(G), is defined as,
(Y ⊖ H)(G) = T&GPY(G + T) − H(T)S, 0 ≤ (G + T) ≤ G,T ≥ 0 (2)
Basic operations defined above could be used to define two derivatives called
opening and closing. Opening of Y(G) byH(T), defined as dilation of the eroded
signal (Y ⊖ H) by (T) , which is denoted by (Y ∘ H)(G), is defined as
(Y ∘ H)(G) = ((Y ⊖ H) ⊕ H)(G) (3)
Similarly, closing of Y(G) byH(T), defined as erosion of the dilated signal
(Y ⊕ H) by (T) , which is denoted by(Y.H)(G), is defined as
(Y.H)(G) = ((Y ⊕ H) ⊖ H)(G) (4)
There are several composite operators present in literature that are derived
from above four basic operators. Among other operations, Closing Opening
Difference Operation (CODO) explained in [26] , defined by (5), has shown smooth
and very small output for stable input signals.
VCODO = (Y.H)(G) − (Y ∘ H)(G) (5)
5.4 TEST SETUP FOR ARC FAULT GENERATION
Same test bench illustrated in chapter 4 was used in analysing arc faults for
MM as well. Fig.5.1 shows the PV panel, oscilloscope and lux meter that were used
in the experiment. Same apparatus used in previous chapters was used to generate
arcs.
PV
PWM
MPPT
Load
Battery
Series Fault
Parallel Fault
38 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
Fig.5.2 Test circuit (top) and setup (bottom).
An arc was formed by moving two contact points of Series Fault away from
each other and a parallel arc was formed by a short circuit across positive and
negative sides of the PV module. In each case, waveforms of voltage across PWM
and current through the fault were recorded.
Table 5.1. Electrical characteristics of PV Module at normal operating cell temperatures.
Parameter Value
Maximum Power (Pmax)
Open Circuit Voltage (Voc)
Short Circuit Current (Isc)
Voltage at Maximum Power (Vmpp)
Current at Maximum Power (Impp)
182 W
34.2 V
7.07 A
27.7 V
6.59A
An AGILENT DSOX2024A digital oscilloscope was used to store current and
voltage traces at 10 Giga samples per second rate.
Results obtained were the waveforms of current and voltage signatures of arcs.
For comparison purposes, waveforms were recorded from a point of time prior to arc
occurrence. This portion of the waveform contains noise created by pulse width
modulation operations of maximum power point tracking algorithms during pre-fault
normal operation of the system.
For each fault scenario, several tests were done and voltage and current
waveforms were recorded. One of the traces was randomly selected for further study.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 39
5.5 PARALLEL ARC FAULTS
Current and voltage traces during a parallel fault are illustrated in Fig. 5.3
below.
Fig.5.3. Parallel Arc waveforms
5.5.1 Parallel Arc Current
Before the fault is introduced, system behaves under normal conditions.
Current drawn is influenced by the connected load and remaining capacity of battery
storage. Based on the irradiance level, MPPT controller adjusts total current. Noise
created by PWM is also visible in the waveforms.
-5.00
0.00
5.00
10.00
15.00
20.00
0.00
5.00
10.00
15.00
20.00
25.00
0.00E+00 9.00E-05 1.80E-04
CU
RR
EN
T [
A]
VO
LTA
GE
[V
]
TIME [SEC]
PARALLEL ARC FAULT
VOLTAGE CURRENT
40 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
Fig.5.4. Parallel arc current
At the end of the arc, fault becomes a short circuit between positive and
negative lines from PV panel. There is still a resistance created by cables connecting
PV panel and electrodes as well as contact resistance between two electrodes of test
apparatus. Hence the post fault current is higher than pre-fault current but is limited
by maximum current available at the irradiance level present during testing.
5.5.2 Parallel Arc Voltage
Fig.5.5. Parallel arc voltage
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 41
Similar to arc current, voltage has high frequency noise induced by PWM
function of the MPPT controller. Pre fault voltage is determined by irradiance and
connected load. Post fault voltage drops to near zero due to low resistance between
two supply lines due to short circuit across electrodes.
During the fault, voltage trace has more significant random fluctuations
compared to its current counterpart.
5.6 SERIES ARC FAULTS
Series fault was also initiated at around 10ms. The fault lasts for few
milliseconds and then voltage and current settle down to their post-fault values.
MPPT is still in force trying to adjust current drawn and system noises continue to
appear in the waveforms. In addition, spikes of random currents due to arc fault and
corresponding voltage spikes are also visible.
Series fault voltage and current traces are illustrated in Fig.5.6 below.
Fig.5.6. Series arc waveforms
5.6.1 Series Arc Current
In generating an arc across the electrodes that are in series with load of PV
system, there are two initial conditions that the experiment could be started with. The
-5.00
-3.00
-1.00
1.00
3.00
5.00
7.00
0.00
5.00
10.00
15.00
20.00
0.00E+00 9.00E-05 1.80E-04
CU
RR
EN
T [
A]
VO
LTA
GE
[V
]
TIME [SEC]
SERIES ARC FAULT
VOLTAGE
CURRENT
42 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
gap between electrodes could be kept closed or open and then move them toward or
away from each other to create an arc in between.
Arc was generated starting from an open air gap in the experiment and voltage
and current signatures were recorded.
Fig.5.7. Series arc current
During the arc, current increases to a maximum dependent of arc impedance
and connected load. High frequency random noise is visible during the arcing.
5.6.2 Series Arc Voltage
Fig.5.8. Series arc voltage
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 43
Voltage across the arc that corresponds to current flowing through could rise
up to a maximum determined by impedance of arc and rest of the load circuit.
Waveform has a significantly different shape during the arc that could be used to
detect its presence.
5.7 ANALYSIS OF ARC WAVEFORMS
Waveforms stored in the oscilloscope have to be streamlined in order to use
with MATLAB for calculation of morphological derivations.
A sample time of 1x10-7
S was selected and waveform data was sampled down.
A total of 2,000 samples were used to represent each waveform. Actual voltages and
currents during a fault depend on the capacity of the PV system concerned. Measured
values could be normalized by dividing actual readings by respective peak values
before analysing with morphology. This help compare results from different systems.
Table.5.2 Actual data set of arc waveform
SAMPLE
# TIME I_Series V_Series I-Parallel V_Parallel
[S] [A] [V] [A] [V]
1 0 - 0.10520 10.19573 8.57726 13.56935
2 0.0000001 - 0.10520 10.01884 4.55716 12.64472
3 0.0000002 - 0.10520 10.01884 8.57726 12.64472
4 0.0000003 - 0.10520 10.01884 4.55716 13.56935
5 0.0000004 - 0.10520 10.01884 6.56721 13.56935
6 0.0000005 - 0.10520 10.19573 4.55716 12.64472
7 0.0000006 0.09580 10.01884 6.56721 12.64472
8 0.0000007 - 0.10520 10.01884 6.56721 13.56935
9 0.0000008 - 0.10520 10.01884 6.56721 13.56935
10 0.0000009 - 0.10520 10.19573 6.56721 13.56935
11 0.000001 - 0.10520 10.01884 6.56721 13.56935
12 0.0000011 - 0.10520 10.01884 4.55716 13.56935
13 0.0000012 - 0.10520 10.01884 6.56721 13.56935
14 0.0000013 - 0.10520 10.01884 6.56721 13.56935
15 0.0000014 0.09580 10.19573 4.55716 12.64472
16 0.0000015 - 0.10520 10.01884 6.56721 12.64472
- - - - - -
- - - - - -
- - - - - -
1,998 0.0001997 - 0.10520 7.71935 8.57726 0.624623
1,999 0.0001998 0.09580 7.71935 8.57726 0.624623
2,000 0.0001999 - 0.30621 7.71935 8.57726 0.624623
44 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
I_Series = Actual Current during Series Arc Fault
V_Series = Actual Voltage during Series Arc Fault
I_Parallel = Actual Current during Parallel Arc Fault
V_Parallel = Actual Voltage during Parallel Arc Fault
With an open circuit voltage of 34.2V and a short circuit current of 7.07A,
normalized data set is given below.
Table.5.3 Normalized data set of arc waveform
SAMPLE
# TIME In_Series Vn_Series In-Parallel Vn_Parallel
[S] [A] [V] [A] [V]
1 - - 0.01488 0.29812 1.21319 0.39676
2 0.0000001 - 0.01488 0.29295 0.64458 0.36973
3 0.0000002 - 0.01488 0.29295 1.21319 0.36973
4 0.0000003 - 0.01488 0.29295 0.64458 0.39676
5 0.0000004 - 0.01488 0.29295 0.92888 0.39676
6 0.0000005 - 0.01488 0.29812 0.64458 0.36973
7 0.0000006 0.01355 0.29295 0.92888 0.36973
8 0.0000007 - 0.01488 0.29295 0.92888 0.39676
9 0.0000008 - 0.01488 0.29295 0.92888 0.39676
10 0.0000009 - 0.01488 0.29812 0.92888 0.39676
11 0.0000010 - 0.01488 0.29295 0.92888 0.39676
12 0.0000011 - 0.01488 0.29295 0.64458 0.39676
13 0.0000012 - 0.01488 0.29295 0.92888 0.39676
14 0.0000013 - 0.01488 0.29295 0.92888 0.39676
15 0.0000014 0.01355 0.29812 0.64458 0.36973
16 0.0000015 - 0.01488 0.29295 0.92888 0.36973
- - - - - -
- - - - - -
- - - - - -
1998 0.0001997 - 0.01488 0.22571 1.21319 0.01826
1999 0.0001998 0.01355 0.22571 1.21319 0.01826
2000 0.0001999 - 0.04331 0.22571 1.21319 0.01826
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 45
In_Series = Normalized Current during Series Arc Fault
Vn_Series = Normalized Voltage during Series Arc Fault
In_Parallel = Normalized Current during Parallel Arc Fault
Vn_Parallel = Normalized Voltage during Parallel Arc Fault
5.8 SELECTION OF STRUCTURED ELEMENT (SE)
No specific criterion for selection of SE for power system studies is reported in
literature.
Selection of an optimum SE depends on the type and frequency of the
disturbance and sampling rate of measurement [33]. In case of straight line SE, other
variables are the length and angle of SE. Length of SE determines the width of the
data window used for MM transformation. Each operation of Mathematical
Morphology creates a delay that is equal to ∆T(m-1)/2 seconds[2]. Here ∆T is the
sampling interval and m is the length of SE in terms of number of samples.
In general, very high sampling rates could be used to feed in signal data into a
processor that computes MM transformation. But protection equipment may not be
capable of responding to such high frequencies and a slower interface would be more
effective to communicate with protection equipment. In this scenario, a longer SE
could provide adequate time for protection equipment to respond. Effect of size of
SE on secondary equipment responsiveness is also investigated by using different
sized SE with same fault waveform data.
5.9 ARC FAULT DETECTION
Above waveform signatures were analysed in MATLAB. Two functions
“imdilate” and “imerode” were used to calculate dilation and erosion of the
waveform. Closing and Opening functions were derived by “imclose” and “imopen”
operations and then CODO was derived by subtracting opening from closing
functions.
46 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
The MATLAB code used for this is as below:
t=(0:0.0000001:0.0001999);%Definition of time span and sampling rate File1='waveform.xlsx'; %Read waveform from excel file. A=xlsread(File1)
SE1=strel('line',10,0); % Straight Line structuring element with
length 10 and angle 0 degree dA1=imdilate(A,SE1); % Calculation of Dilation eA1=imerode(A,SE1); % Calculation of Erosion cA1=imclose(A,SE1); % Calculation of Closing oA1=imopen(A,SE1); % Calculation of opening
CODO1=cA1-oA1; % Calculation of CODO
5.9.1 Morphological functions of parallel fault waveform signatures
In order to illustrate basic functions of MM for parallel fault current waveform,
dilation and erosion were calculated using above MATLAB codes and could be
plotted as shown in Fig.5.9. A straight line SE of length 10 was used for these basic
MM function plots.
Fig.5.9. Dilation and Erosion of Parallel Fault Current
Closing and Opening function of the same current waveform is plotted in
Fig.5.10.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 47
Fig.5.10. Closing and Opening of Parallel Fault Current
All of these basic MM operations outline the boundary of original current
waveform signature. Average of these operations is similar to that of original
waveform under test. Pre fault current varies around 6 Amps mark and all four basic
MM operations resulted in waveforms that vary in the same region. Hence there is no
much difference between actual fault current and waveform of morphological
operations.
On the other hand, during parallel fault, shape of fault current signature and
resulted shapes of morphological basic operations are almost similar other than fact
that those operations represent the contour of fault current waveform.
Both above similarities among waveform signatures make these basic
morphological operations not suitable for differentiating faulty and non-faulty
regions of parallel fault current waveforms.
48 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
Fig.5.11. CODO Operation of Parallel Fault Current
CODO function on fault current results in a waveform which is separate and
independent of normal current waveform. During pre-fault time, CODO is a near
zero signal. There are significantly distinguishable spikes in the CODO output during
fault. This is more suitable than results of basic MM operations for detecting faults.
Voltage signature during parallel fault was similarly analysed using same MM
operations and results are plotted in following figures.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 49
Fig.5.12. Dilation, Erosion, Closing, Opening and CODO functions of Parallel Fault Voltage.
Similar to MM functions of fault current, CODO operation provides better
possibility of separating faulty region for Voltage signature as well. Output from
basic MM operations on voltage again only provides signals that are similar to
measured waveform. But in case of CODO operation, pre-fault signal is almost zero
in magnitude and faulty region has large spikes that are easily distinguishable.
5.9.2 Morphological functions of series fault waveform signatures
Current through a series fault and voltage across input terminals of
MPPT/PWM controller were also analysed with mathematical morphology. A
straight line structuring element of length 10 was used with MATLAB functions
described in 6.9 above.
50 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
Fig.5.13. Dilation, Erosion, Closing, Opening and CODO functions of Series Fault Current.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 51
Out of all morphological functions used, CODO function produced an outcome
that is easy to recognize compared to current waveform and its fault signature.
CODO output always remain close to zero areas other than during fault. It also
remained close to zero during time slots that current gradually increased or reduced
but generated clearly visible spikes whenever high frequency noise is present in the
fault current. Hence, this will not trigger any protective gears during a normal
increase or decrease of current due to changes in irradiance and shading.
Voltage measured across inverter DC side terminals produced MM results that
are illustrated below. A straight line structured element of length 10 was used for all
these plots.
52 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
Fig.5.14. Dilation, Erosion, Closing, Opening and CODO functions of Series Fault Voltage.
Similar to the results from series fault current analysis, opening, closing,
erosion and dilation follow the shape of fault voltage signature. But in case of
CODO, resulted waveform is near zero during pre-fault time span and produced
some spikes during fault. Hence CODO is more suitable to detect series faults using
voltage across inverter DC terminals.
5.9.3 Effect of length of Structuring Element
From the results presented in 5.9.1 and 5.9.2, it is evident that CODO operation
gives most appropriate results for fault detection. Resulted waveforms were produces
with a straight line structured element of length 10 and this section will investigate
the effect of length of SE on CODO function results.
Size of the SE plays a significant role on the shape of final outcome from
CODO operation. Also, it determines the delay involved in filtering the signal as
higher the length of SE higher the number of samples that are taken for MM
operations.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 53
In order to understand the effect of length of SE in filtered signal output,
voltage across charge controller and current fed into the controller were analysed by
CODO operation using a SE of length 10, 20, 100 and 250 samples.
54 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
Fig.5.15. Effect of length of SE on CODO for Series Fault Voltage.
Amplitude of CODO signal remains near zero during non-faulty regions and
higher than 1 Volt during fault. Time that the CODO signal remains high increases
with increasing length of SE. Other than the initial peak of CODO signal at the
starting of the fault, SE length 250 produces more than 4 Volts output during fault.
But it could also be seen that shape of pre-fault CODO signal is also affected and it
tend to move away from zero before fault which could adversely affect detection
process.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 55
Fig.5.16. Effect of length of SE on CODO for Parallel Fault Voltage.
Similarly, as illustrated in Fig. 5.16, CODO output of parallel fault voltage
traces gives promising results under different SE lengths. Output value for the faulty
56 Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology
region of the trace is significantly higher than that of during normal operation
irrespective of the presence of system noise.
Though increasing length of SE has a significant effect on the shape of CODO
output signal, it also depends on the shape of original signal which will be totally
different every time a fault occurs. An SE of length 10 displays sufficient separation
of faulty and normal operational regions of measured signal.
Not like in series fault voltage analysis at 250 long SE, parallel fault voltage
pre-fault CODO signal is not affected by the length of SE. Hence, SE 250 samples
length gives a longer and affective CODO output signal. This could be a result of
fairly constant pre-fault voltage that was present during parallel fault analysis.
Chapter 5: Detection of Arc Faults in a PV System using Mathematical Morphology 57
5.10 CONCLUSIONS
High impedance faults of a PV system were analysed using Mathematical
Morphology and its associated derivatives. All the measurements were done at the
input ports to the MPPT controller which eliminates necessity of additional cabling
to capture fault signatures in a practical installation.
Current and voltage waveforms of series and parallel faults were used as the
measurement for fault detection. Fault current waveforms provide evidence that there
is no much difference of current magnitude during the fault compared to that of
during normal operation. Several current spikes could be present but the duration is
very short that traditional over current protection switchgear may not effectively
detect and isolate faulty circuits.
Among the basic morphological functions and its derivatives, CODO operation
exhibited strong separation of faulty and non-faulty regions of the waveforms
analysed.
It was also revealed that both series and parallel arc faults could be identified
with the use of very short structuring elements, in the range of 10 samples, which
paves the way for speedy detection of faults. Longer SEs slow down detection speed
due to larger number of samples analysed though it makes it easier to separate
faulted waveform from a healthy segment of measured signals.
When it comes to measurement of voltage and current at high sampling rates
similar to that used in this study, it is more economical to use voltage as measured
signal than current. Mathematical morphology could be used effectively to detect
faults by measuring only voltage across MPPT controller for both series and parallel
arcs.
58 Chapter 6: Conclusions and future work
Chapter 6: Conclusions and future work
Photovoltaic systems behave as a current source of which the capacity depends
on factors such as irradiance, shading, configurations of individual PV modules etc.
Hence amount of energy dissipated through an arc fault in a PV installation also
depends on such factors.
Current and voltage magnitudes associated with an arc fault could be smaller
than maximum values that could be present during healthy operation of the system if
the fault occurs during low irradiance or shaded conditions; this makes it impossible
to detect such faults using conventional protection equipment.
In order to successfully detect arc faults in a PV system, protection switchgear
should be capable of identifying changes in the voltage and current signatures in
addition to the magnitudes of those signals.
Two separate methods that could be used to identify changes in shape of arc
fault current and voltage were discussed and tested in this research work. Both those
systems were proved to be effective in detecting arc faults in a PV system whether
the fault is a series or parallel arc.
6.1 WAVELET TRANSFORM
Wavelet transformation of fault voltage could successfully be used to identify
both series and parallel arc faults. Voltage signature itself gives adequate results and
there is no need to monitor current to identify the fault.
Level of decomposition or frequency sub band that gives optimum results is
different for series and parallel faults. But these sub bands are closer to each other
that overall level of decomposition required to detect both types of faults is small. In
this research, it is shown that both series and parallel faults could be detected by
using up to 9th
frequency sub band.
Also, measurement of voltage was done at input terminals to MPPT controller
and hence there is no need for additional cabling or current transformers.
Chapter 6: Conclusions and future work 59
6.2 MATHEMATICAL MORPHOLOGY
Basic morphological functions as well and their derivatives were used to
analyse arc fault voltage and current signatures. Among the basic morphological
functions and its derivatives, CODO operation exhibited most prominent separation
of faulty and non-faulty regions of the waveforms analysed.
Length of the structuring element plays a significant role in the shape of output
waveform signatures. Both series and parallel arc faults could be identified with the
use of very short structuring elements, in the range of 10 samples. Such short SEs
paves the way for speedy detection of faults. Longer SEs slow down detection speed
due to larger number of samples analysed though it makes it easier to separate
faulted waveform from a healthy segment of measured signals.
When it comes to measurement of voltage and current at high sampling rates
similar to that used in this study, it is more economical to use voltage as measured
signal than current. Mathematical morphology could be used effectively to detect
faults by measuring only voltage across MPPT controller for both series and parallel
arcs.
6.3 FUTURE WORK
Throughout this research, arc fault waveforms that were obtained by creating
an arc in the specially designed test bench were used. Arc was formed by manually
adjusting the gap between fixed and moving electrodes.
In reality, arc gap doesn’t change gradually but it also changes rapidly and
randomly. The test bench could be further developed by introducing a controlled way
of changing the gap between electrodes and it could be used to analyse more
complex arc faults. When arc length rapidly changes, frequency composition of
measured signals vary and its worthwhile to see if wavelet transform and
mathematical morphology could still be used to detect arc faults. Such a developed
system could be used to replicate falling cables by separating the gap at acceleration
equal to gravity.
60 Chapter 6: Conclusions and future work
In this research arc faults that occur closer to MPPT controller and between
final positive and negative cables were considered. In a real world PV installation,
arcs could occur at various places of the installation. For example, a series fault
could easily occur at terminal boxes of any PV module. A further study should be
done to see if similar techniques could be used to accurately locate the location of the
arc fault.
In addition to series and parallel arcs, a fault that occurs between live parts and
ground or adjacent structures also poses great risks. Same approach of detection may
be useful to detect and locate such faults and creates space for a future study.
Once the fault is identified and located, the affected portion of the installation
should be isolated to make sure safety of property and human lives. In order to
achieve this, measurement and analysis system could be incorporated with a micro
controller. Another area of further development is to design and program such a
controller and also to investigate possibility of having this as a part of MPPT or
charge controller.
Bibliography 61
Bibliography
1. International Energy Agency Photovoltaic Power Systems, IEA PVPS.(2016).
Trends in photovoltaic applications. Survey report of selected IEA countries
between 1992 and 2015. Int. Energy Agency Photovoltaic Power Syst. (IEA
PVPS). {Online}. Available at: http://www.iea-
pvps.org/fileadmin/dam/public/report/national/IEA-PVPS_-_Trends_2015_-
_MedRes.pdf
2. Gautam, S. and S.M. Brahma. Overview of mathematical morphology in
power systems - A tutorial approach.
3. Lu, Z., et al. Morphological transform for detection of power quality
disturbances. IEEE.
4. Sen, O. and R. Zhen. Application of Improved Mathematical Morphology
Method in the Power Quality Monitoring. IEEE.
5. Zou, L., et al. Applications of multi-resolution morphological analysis in
ultra high speed protection of transmission line. IEEE.
6. Singh, G.K., Solar power generation by PV (photovoltaic) technology: A
review. Energy, 2013. 53(C): p. 1-13.
7. Green, M.A., et al., Solar cell efficiency tables (Version 53). Progress In
Photovoltaics, 2019. 27(1): p. 3-12.
8. Zhao, Y., et al., Line-Line Fault Analysis and Protection Challenges in Solar
Photovoltaic Arrays. IEEE Transactions on Industrial Electronics, 2013.
60(9): p. 3784-3795.
9. Flicker, J. and J. Johnson, Electrical simulations of series and parallel PV
arc-faults. 2013, IEEE. p. 3165-3172.
10. Alam, M.K., et al., A Comprehensive Review of Catastrophic Faults in PV
Arrays: Types, Detection, and Mitigation Techniques. IEEE Journal of
Photovoltaics, 2015. 5(3): p. 982-997.
11. Grid Connected Photovoltaic Systems. Science Direct. Online available at
'https://www.sciencedirect.com/topics/engineering/grid-connected-
photovoltaic-systems/pdf', 2011.
12. Braun, H., M. Banavar, and A. Spanias, Signal Processing for Solar Array
Monitoring, Fault Detection, and Optimization. 2012, San Rafael: Morgan &
Claypool Publishers.
13. Ding, K., et al., A MATLAB-Simulink-Based PV Module Model and Its
Application Under Conditions of Nonuniform Irradiance. IEEE Transactions
on Energy Conversion, 2012. 27(4): p. 864-872.
14. Patel, H. and V. Agarwal, MATLAB-Based Modeling to Study the Effects of
Partial Shading on PV Array Characteristics. IEEE Transactions on Energy
Conversion, 2008. 23(1): p. 302-310.
15. Villalva, M.G., et al., Comprehensive Approach to Modeling and Simulation
of Photovoltaic Arrays. IEEE Transactions on Power Electronics, 2009. 22;
24(5): p. 1198-1208.
62 Bibliography
16. Ammerman, R.F., et al., DC-Arc Models and Incident-Energy Calculations.
IEEE Transactions on Industry Applications, 2010. 46(5): p. 1810-1819.
17. Andrea, J., P. Schweitzer, and E. Tisserand. A New DC and AC Arc Fault
Electrical Model. 2010.
18. Gammon, T., et al., A Review of Commonly Used DC Arc Models. IEEE
Transactions on Industry Applications, 2015. 51(2): p. 1398-1407.
19. Uriarte, F.M., et al., A DC Arc Model for Series Faults in Low Voltage
Microgrids. IEEE Transactions on Smart Grid, 2012. 3(4): p. 2063-2070.
20. Flicker, J. and J. Johnson. Electrical simulations of series and parallel PV
arc-faults. IEEE.
21. Mayordomo, J.G. and R. Asensi, A Frequency Domain Approach for
Modeling DC Arc Furnaces under Fluctuating Conditions. IEEE
Transactions on Power Delivery, 2007. 22(3): p. 1722-1735.
22. Yao, X., et al., Characteristic Study and Time-Domain Discrete- Wavelet-
Transform Based Hybrid Detection of Series DC Arc Faults. IEEE
Transactions on Power Electronics, 2014. 29(6): p. 3103-3115.
23. Wang, Z. and R.S. Balog, Arc Fault and Flash Signal Analysis in DC
Distribution Systems Using Wavelet Transformation. IEEE Transactions on
Smart Grid, 2015. 6(4): p. 1955-1963.
24. Wang, Z., et al. Arc fault signal detection - Fourier transformation vs.
wavelet decomposition techniques using synthesized data. IEEE.
25. Karimi, M., H. Mokhtari, and M.R. Iravani, Wavelet based on-line
disturbance detection for power quality applications. IEEE Transactions on
Power Delivery, 2000. 15(4): p. 1212-1220.
26. Gautam, S. and S.M. Brahma, Detection of High Impedance Fault in Power
Distribution Systems Using Mathematical Morphology. IEEE Transactions on
Power Systems, 2013. 28(2): p. 1226-1234.
27. Jing, M., et al. Single-ended transient positional protection of transmission
lines using mathematical morphology. IEEE.
28. King-Jet, T., W. Yaoming, and D.M. Vilathgamuwa, An experimentally
verified hybrid Cassie-Mayr electric arc model for power electronics
simulations. Power Electronics, IEEE Transactions on, 1997. 12(3): p. 429-
436.
29. Strobl, C. and P. Meckler. Arc Faults in Photovoltaic Systems.
30. Gautam, S. and S. Brahma. Properties of Mathematical Morphology based
filter for online filtering of power system signals. 41st North
American Power Symposium, October 2009, pp.1-5
31. Chen, J.C., et al. Arcing current features extraction using wavelet transform.
Proceedings of 2014 International Symposium on Electrical Insulating
Materials, June 2014, pp.221-224.
32. Weerasekara, M., Vilathgamuwa M, and Mishra Y, Modelling of DC arcs for
photovoltaic system faults. 2016, IEEE. 2nd Annual Southern Power
Electronics Conference (SPEC), December 2016, p. 1-4.
33. Tingfang, Y., et al. Application of Adaptive Generalized Morphological Filter
in Disturbance Identification for Power System Signatures. International
Conference on Power System Technology, October 2006, pp.1-7 .