Nameplate Accuracy for New SF 6 Gas Circuit Breakers Todd Irwin, Keith McLaughlin, Michael Broglio
Transcript
Page 1: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Nameplate Accuracy for New SF6 Gas Circuit Breakers

Todd Irwin, Keith McLaughlin, Michael Broglio

Page 2: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

SF6 Nameplate Accuracy

§ Materials Tolerances

§ Factory Measuring

§ Site Accuracy

Page 3: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Example Baseline

§ DT1-72.5 FKF1

§ 72.5kV

§ 3000A

§ 40kA, 3 cycles

§ SF6 Gas Insulated

§ FK3-1 Spring/Spring Operating mechanism

§ Gang Operated

Page 4: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

NEMA SF6 Coalition

“…the nameplate is meant to indicate the approximate mass of SF6 that the GIE will hold once it is filled to the proper density.”

https://www.nema.org/Products/Documents/Sf6-ReportingChallenges.pdf

Page 5: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

SF6 Pressure Curve

1 – Nominal (67)2 – Alarm (52) 3 – Lockout (48) 4 – Liquefaction Curve

Page 6: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Gas Nameplate Weight

29 Pounds

Page 7: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

IEEE C37.04-2018

Page 8: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

IEEE C37.04-2018

Page 9: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

CARB sf6-gis-discussion-draft-20190815

5% of 29lbs = +/-1.45 lbs

Page 10: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Aluminum Tank: +/- 0.5mm to 2mm

Page 11: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Porcelain Insulator: +/- 6mm

Page 12: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Component Tolerances – 72.5kV

Variables§ Tank § Bushing Insulators§ Bushing Conductors§ Solid Insulation§ Interrupter Components

Calculated Weight (79.32 lb/m3 67psig @ 20°C)§ Minimum = 28.43 lbs§ Nominal = 29.17 lbs§ Maximum = 29.91 lbs

§+/- 0.74 lbs§+/- 2.53%

Page 13: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Achievable Nameplate Accuracy

§ For Theoretical Nameplate Weight

§ +/- 2.5% may be reasonable for lower voltage CB

§ Larger volume may display wider manufacturing tolerance

§ +/- 5% anticipated in California regulation is reasonable.

Page 14: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Other Variables

§ Temperature (expansion/contraction)• Relatively stable in factory environment

§ Atmospheric Pressure

§ Gas temperature normalization period• Especially when filling from liquid

Page 15: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Factory Measurement Equipment

§ Pressure Gauge

§ Temperature Gauge

§ Scales

§ Mass Flow

§+/-1%

Page 16: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Site FillingMeasuring

§ Pressure Gauge (+/- 0.5%)

§ Temperature Gauge (+/- 1°)

§ Scales/Mass Flow (+/- 0.1 lb)

+/- 1.5 psi @ 70°F+/- 2.4 % (67 psig)+/- 3% @ min/max temp

+/- 1% @ 70°F+/- 2.5% @ min/max temp

Site Conditions

§ Ambient Temperature, Gas Temperature

§ Atmospheric Pressure

+/- 1% @ 70°F

Page 17: Nameplate Accuracy for New SF6Gas Circuit Breakers · 2019-11-14 · §FK3-1 Spring/Spring Operating mechanism §Gang Operated. NEMA SF 6Coalition “…the nameplate is meant to

Summary

§ Nameplate weight is a theoretical ideal• Dependent on manufacturing tolerances

§ Factory mass flow can yield +/-1% accuracy (with extra time/cost)• Installed accuracy dependent on site-filling

§ High Accuracy site filling = best installed accuracy.