Presentation on
Industrial Training
At
Submitted by-
Nikhilesh Joshi
• National Fertilizers Ltd, Vijaipur unit is one of the four units of M/S
National Fertilizers Limited.
• It is a Government of India undertaking.
• The other units are located at Nangal and Bhatinda in Punjab and at
Panipat in Haryana.
• NFL Vijaipur is at 1st place on the basis of Production.
• It is operated with 2 separate units i.e. Line 1 and Line 2.
• The Line 1 plant had gone in Commercial Production on July 1988.
• Line 2 started the Commercial Production on 31st March 1997.
• The total capacity of both lines is Ammonia 3100 ton/day and Urea
6300ton/day.
• Captive Power refers to power generation from a unit
set up by industry for its exclusive consumption.
• Industrial sector is one of the largest consumers of
electrical energy in India.
• Industries are now increasingly relying on their own
generation (captive and cogeneration) rather than on
grid supply.
WHY ON CAPTIVE POWER PLANT???
Non-availability of adequate grid supply
Poor quality and reliability of grid supply
High tariff as a result of heavy cross subsidisation
30% of the total energy requirement of the Indian industry is currently
met through in house power plants
Steam Power
Plant
45%
Diesel Run
Power Plant
40%
Gas/Naptha Run
Power plant
15%
• In NFL, CPP is based on power generation by Gas Turbine
Generators (GTG).
•Gas turbine works on Joule's Cycle or Brayton Cycle.
•There are 3 units of Gas turbine Generators.
•Each unit has the capacity of 17.225 MW.
•The total power consumption of whole plant is 32MW.
• Only 2 GTGs are operated at a time and the 3rd is kept in
stand by.
PLANT POWER REQUIRED
AMMONIA I 1490 -3170 KW
AMMONIA II 1000 – 3500 KW
UREA I 3500 – 4000 KW
UREA II 3500 – 4000 KW
C. P .P 300 – 1250 KW
COOLING TOWER 6500 – 7500 KW
OFF SIDE 1100 – 4500 KW
•Main GT Manufactures are General Electrics, Simons
Westinghouse & Alstom.
•Efficiency approx 40% for gas turbine.(even higher for
cogenerated plant).
•Low Green Gas Emission (C02, NOx & Sox)
•Cheaper comparing to other technology e.g. CCS.
•Lifetime 30-40 years.
• Gas turbine Accessories including Diesel engine, Lubrication
Pump, Coupling.
• Suction air Filters
•17 stage Axial flow Compressor.
•10 Interconnected Combustion chambers with 1 Electric
Igniter.
•2 Stage Radial flow Turbine.
•Reduction gear arrangement with the reduction of 0.60.
• Generators and Exciter.
GENERATOR
WATTS 17.22 MW
VOLT 11.0 K
PF 0.83
Freq 50.0 Hz
HPV NG Supply
14.3 bar
LPV
EXHAUST
539° C
Reduction
Gear
Compressor Turbine
Exciter
Air
6.89 bar
DIESEL ENGINE - 1.A diesel engine to rotate the shaft at1500 rpm for primary start up.2. By the using of clutch the connection of diesel engine and shaft are disconnected.
Compressor- 1.It is a 17 stage compressor which gives pressure ratio of 6.88/1.2. These blades are operated on 56 degrees for GTG I and GTG II. 3 In case of abnormal heating it used to operate up to 85 degrees.
Combustion Chamber- 1.10 Combustion Chambers are fitted
radially outward of the compressor.
2.Theses are equipped with Igniter, Linear and Transition set .
3. The mixing of compressed air and NG takes place in Linear.
4.The Transition set provides the path for air flow.
Turbine- 1. 2 stage turbine is used in GTG.
2. Which rotate at 5100rpm by the action of hot flue gases.
Reduction Gear- 1. It reduces the rpm up to 3100 while
transferring to the generator.
Generator- It is a device to generate the electricity by
converting the mechanical energy into electrical energy.
Exciter- It charges the rotor within the generating
alternator.
LInear
Combustion
Chamber
Transition
Set
Combustor
Linear
Points GTG1 and GTG2 GTG3
Model PG5361P PG5371PA
Compressor 17 Stage 17 Stage
Turbine Alstom TI
Cycle Open/Cogeneration Open/Cogeneration
Fuel Naphtha/NG/Diesel Naphtha/NG/Diesel
Power 17.225 MW 17.225MW
•Heat coming from GTG is used in HRU.
•Heat recovery unit(HRU) is boiler in NFL.
•Boilers are Kawasaki water tube boiler in HRU 1,2 and 3.
•HRU(Boiler) Produces steam by GTG exhaust and
Supplementary firing .
•Supplementary firing is needed for producing steam at
required pressure.
Point of comparison HRU 1 and 2 HRU 3
Steam generated per hour 150 tones 120 tones
Pressure of generated steam 40 atm. (40kg/cm2) 120 atm. (120kg/cm2)
Steam temperature 382ºC 562ºC
Drum pressure 100kg/cm2 130kg/cm2
Type of boiler Water tube Water tube
Superheating Yes up to 382ºC Yes up to 562ºC
Economizer Yes Yes
Power generated 17MW 20MW
Steam drum 50% steam 50%steam
No. of drums 2 2
Maximum rating 180 tones/hr 120 tones/hr
Bypass Stack
NG
Drum
Econ
omiz
er
BFWBurners (6)
(Supplement fire)Screen
SH2SH1
QuenchingSteam
FD Fan
325 deg C
537 degree
115 deg
506d
egTurbine
•Type of boiler=Kawasaki Water tube type(Horizontal).
•Maximum continuous rating=180 ton / hr
•Maximum allowable working pressure=53 kg/cm²
•Steam temp. ( at super heater outlet )=382 ºc
•Feed water temp. ( at Economizer inlet )=115 ºc ( NG as fuel )
•Draft method=forced draft
•Heat source=gas turbine exhaust with supplementary fuel (NG or
Naphtha )
•Heating surface area=economizer : 9563 m², superheater : 600 m²
• Location= outdoor
•Type of boiler-Horizontal, Water tube boiler.
•Maximum continuous rating=120 ton / hr
•Operating pressure-115 kg/cm²
•Steam temp.-525 + or - 5 ºc
•Feed water temp. ( At economizer inlet )=115 ºc ( NG as fuel )
•Draft method=forced draft
•Heat source=gas turbine exhaust with supplementary fuel ( NG or
Naphtha )
•Heating surface area=2005 m².
•Location-Outdoor.
•Water containing dissolved gases causes many corrosion problem.•Dissolved oxygen causes pitting corrosion. •Carbon dioxide corrosion is frequently encountered in condensate system.•Hence deaerator is widely used to remove dissolved gases from water & thereby control corrosion.•Pressure deaeration with steam as the purse gas is used to prepare boiler feed water. Steam is chosen as the purse gas because:1. It is readily available 2. It heats the water & reduces the solubility constant 3. It does not contaminate BFW4. Most of the steam condensed& becomes a part of the deaerated water.
•Pre treatment plant is used for treatment of Raw water before
using in the plant and drinking water.
•Water pre treatment consist of the following-1-Pre chlorinator
2-Aerator
3-Flash mixture
4-Clarifloculator
5-Gravity sand filter
Preclorinator-Chlorine dosing in raw water at the rat of 5-7 ppm
depends on bacterial count of raw water.
Aerator- 1.Air and water are brought into intimate contact.
2.The air and water contact time and the water volume ratio must be
sufficient for adding oxygen and reduce dissolved gases like NH3,
CO2, H2S.
Flash mixer- Helps in the formation of micro flocks and proper
utilization of coagulant and other chemicals dosed at the flash mixer.
Clarifloculator- To remove finally divided and suspended particles
presented in raw water which imparts turbidity of water.
Gravity sand filter- Sand filter essentially consists of rows of earthen
ware pipes having holes at regular intervals to accommodate.
•Balancing of the impeller shaft of pump-oThe pump is used in water treatment plant.
oThe shaft had unbalance at the angle of 130º
oThe material was removed from the rotor and unbalance is reduced to
2 microns.
•2 day’s Preventive Maintenance of Urea Storage Silos-
including Scrapper Machine.oFitting the bucket of conveyor.
oThe drive shaft of the 2 Chain gear box was changed because of
failure.