The Logic heat interface unit is the latest ‘intelligent’ range of Logic HIUs from Ideal.The Logic HIU is the complete solution for instantaneous hot water production and
space heating control.
This is a direct wall mounted HIU, providing 50kW indirect instantaneous priority Domestic Hot Water (DHW). Central Heating (CH) is dependent
upon the primary system design and pump specifi cation.
HEAT INTERFACE UNIT - 50 DIRECT MEDIUM TEMPERATURE (MT).
LOGIC HIU.
• Single plate design hydraulically separates the domestic water with the space heating supplied directly from the central primary supply
• Internal electronic control unit with LCD display
• Can be set to modulate the heating fl ow circuit for greater effi ciency and to compensate for changes in the external environment
• Complete with a heating support pump, as standard, including a pump bypass loop in case of complete radiator TRV shutdown
• Compact and lightweight• Fully insulated EPP front cover• Includes differential pressure control valve
(DPCV)* supplied and fi tted to the base of the unit
• Ability to pre-heating of the DHW exchanger
Ideal BoilersPO Box 103, National AvenueKingston upon HullEast Yorkshire, HU5 4JN
T: 01482 [email protected]
WWW.IDEALBOILERS.COM
This is a direct wall mounted HIU, providing 50kW indirect instantaneous priority Domestic Hot Water (DHW). Central Heating (CH) is dependent
upon the primary system design and pump specifi cation.
• Single plate design hydraulically separates the domestic water with the space heating supplied directly from the central primary supply
• Internal electronic control unit with LCD display
• Can be set to modulate the heating fl ow circuit for greater effi ciency and to compensate for changes in the external environment
• Complete with a heating support pump, as standard, including a pump bypass loop in case of complete radiator TRV shutdown
* Not shown on components illustration.
ABA B
CC
65mm
550mm
450mm
65mm65mm
Depth inc. cover: 265mm
** After shut-off valves are installed the connections become a female 3/4’’.
CONNECTION A B C
Thread G¾” G½” G1”**
OPERATION.LOGIC HIU 50 DIRECT MT.
211103 v3
Hydraulic Characteristics - Heating Function
SATK 20103 - low temperature unit - UPS 15-60 pump settings
Kv = 2.04 m³/h
0
10
20
30
40
50
60
Flowrate -l/s
Pre
ssure
loss
-kP
a
3
2
1
0
10
20
30
40
50
60
0 0.1 0.2 0.3 0.4 0.5 0.6
0 0.1 0.2 0.3 0.4 0.5 0.6
0 0.1 0.2 0.3 0.4 0.5 0.6
Flowrate -l/s
Pre
ssure
loss
-kP
a
Kv = 2.12 m³/h
3
2
1
Flowrate - l/s
50
10
1
0.5
20
30
2
3
5
Pre
ssure
loss
- k
Pa
Kv = 2.20 m³/h
0
10
20
30
40
50
60
Flowrate -l/s
Pre
ssure
loss
-kP
a
Kv = 2.12 m³/h
3
2
1
SATK 20203 - medium temperature unit - UPS 15-60 pump settings
SATK 20303 - high temperature unit
SATK 20403 - high temperature unit - UPS 15-60 pump settings
0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5
Maximum working pressure: 10 bar
Maximum temperature 85°C
Max. Percentage of glycol 30%
Max. Recommended primary circuit flow rate
1.2 m³/h
PRIMARY PERFORMANCE.
The temperature setting operates on the principle of set point regulation and can be fixed within application limits.
HEATING.
Heating Set Point 50 to 75°C
Nom. heating net output As primary and heating circuit controls permit
Heating circuit Maximum pressure rating: 10 bar as primary and heating circuit controls permit
Pump UPS 15/60
Pump bypass setting 0.45 bar
Heating control circuit VOLT FREE
The DHW function takes priority over the heating function controlled by the DHW priority flow switch.
Power supply 230 V (ac)±10% 50 Hz
Max. Power consumption 105 W
Protection class IP 40
Actuator Stepper 24 V
Probes NTC 10 kΩ
ELECTRICAL.
Frame RAL 9010 sprayed steel
Protective shell cover EPP (Expanded polypropylene)
Components Brass BS EN 12165 CW617N
Pipes Stainless steel
Exchanger Brazed stainless steel
CONSTRUCTION.
Set Point DHW temperature 42 to 60°C
Max. Domestic hot water pressure 10 bar
DHW circuit max. flow rate 18 l/m (0.3 l/s)
Min. flow rate to activate domestic flow sensor
2.7 l/m ±0.3
Max. Differential pressure on domestic water modulating valve
Δp 0.9 bar
Min. Differential pressure on domestic water modulating valve
Δp 0.35 bar
Nom. DHW heat exchanger net output
50 kW - Logic HIU 50 Direct MT
Flushing By-pass P
CF Echo II P
CF Ultramaxx V P
ACCESSORIES.
Heat Interface Unit MT P
Primary ball valve set P
Central heating flow & return valves P
DHW inlet and outlet connection valves P
Differential pressure control (DPC) P
INCLUDED AS STANDARD.
UIN PRODUCT NAME METERING OPTIONS
211095 Logic HIU Direct MT HIU only, meter not included
211348 Logic HIU Direct MT Factory fitted, CF Echo 11 MbBus 1
211352 Logic HIU Direct MT Factory fitted, CF Ultramaxx V MBus PS
HYDRAULIC CHARACTERISTICS HEATING - PRIMARY SIDE.
DOMESTIC HOT WATER - DHWINCLUDING OPTIONAL PRE HEAT FUNCTION.
DOMESTIC HOT WATER OUTPUT.
1,100
1,000
800
600
400
200
0 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800
Domestic Hot Water Flow Rate @ 48˚C - l/h
Pri
mary
Flo
w R
ate
I/h
LOGIC HIU 75 INDIRECT
LOGIC HIU 50 INDIRECT
Pri
mary
Flo
w R
ate
I/h
1,500
1,400
1,200
1,000
800
600
400
200
0 0 100 200 300 400 500 600 700 800 900 1,000 1,100
Domestic Hot Water Flow Rate @ 48˚C - l/h
Primary flow temperatures
55˚C
60˚C
65˚C
70˚C
75˚C
80˚C
85˚C
55˚C
65˚C
75˚C
85˚C
Primary flow temperatures