+ All Categories
Home > Engineering > Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

Date post: 10-Jan-2017
Category:
Upload: energytech2015
View: 1,406 times
Download: 3 times
Share this document with a friend
31
Imagination at work VSC HVDC Transmission and Emerging Technologies in DC Grids Neil Kirby EnergyTech2015 - Cleveland 30 th November 2015
Transcript
Page 1: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

Imagination at work

VSC HVDC Transmission and Emerging Technologies in DC Grids Neil Kirby

EnergyTech2015 - Cleveland

30th November 2015

Page 2: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Summary

HVDC Technologies

HVDC Grid Control

HVDC Grid Protection

Future Converters

2

Page 3: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Two HVDC technologies

Line Commutated Converters

LCC – HVDC/UHVDC

Voltage Source Converters

VSC – HVDC

Rating limited today : ~1GW More Versatile Control of MW / MVar Linear Bi-directional control Functionality suitable for “DC grid” Good for weak AC systems Higher Losses 1.0-1.2%

Higher Power Ratings : up to 10GW Longer History : In service since 1980’s Best for Overhead Line Transmission Asynchronous Interconnections Need AC Filters => Bigger Switchyard Lower losses < 0.8%

Uses Thyristors Uses Transistors

All HVDC Systems Need: Power Converters

HVDC Control & Protection Cooling Plant

Power Transformers AC Switchyards & Protection

DC Switchyards & Protection (Excl BTB) Auxiliary Power Supplies

Buildings Extensive Network Analysis

Page 4: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

VSC versus LCC HVDC

Line-Commutated

Converter (LCC) HVDC

Converter A Converter B

RDC

VDC_A VDC_B

IDC

Power flow A → B Power flow B → A

VDC_A

VDC_B IDC

Power flow A → B Power flow B → A

VDC_A

VDC_B

VDC_A

VDC_B

IDC

Voltage-Sourced

Converter (VSC) HVDC

Converter A Converter B

RDC

VDC_A VDC_B

IDC

VDC_A

VDC_B

IDC

Page 5: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Control of HVDC Grids

Many possible methods of controlling power flow in HVDC Grids

Two such methods proposed are:

• Slack Bus Control

• Droop Control

……. and many variations or both!

Market requires that HVDC Grids be multi-vendor …

… AND different control modes will be required for different

types of AC system…

…… AND different control modes might be used within a Grid

without adverse interaction…..

Page 6: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

• Converter A changes from Import (Rectifier) to Export (Inverter)

• Converter C (“Slack” converter) forced from Export (Inverter) to Import (Rectifier)

Converter D

Vdc

+Pdc

EXPORT IMPORT

OPB

-Pdc

Converter B

PdcB PdcD

PdcC = Σ (PdcA , PdcB , PdcD)

OPA

Converter A

PdcA

Converter C

OPC

PdcC

OPD

Converter A

OPA

PdcA PdcC

OPC

Converter C

Control of HVDC Grids – Slack Bus Control

Page 7: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Control of HVDC Grids - Droop Characteristic

All converters contribute to the “slack bus”.

“Sharing of change” by converters determined by relative droop settings of each converter.

DC power at each converter can be corrected/changed by either: – Re-dispatch from a central Grid Controller (requires telecommunication).

– Local control at the converter (autonomous control) e.g., constant power

– or AC frequency control.

LRSP

Vdc

OPA

Vdc

OPB

OPD OPC

OPB

Export

+Idc

Import

-Idc IoA IoB IoD IoC

Page 8: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

STATION A

STATION B

STATION C

LINK

Controller

Control of HVDC Grids - LINK controller

“LINK” Controller

• Operator control interface

• DC power flow solver

• Validation of power flow before

initiating change

• Automatic drift correction

Page 9: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

DC Grid Protection - Zones of protection

Keep the protections associated with Zones 4 and 5

physically separate in order to permit for future multi-vendor

upgrade to multi-terminal

Page 10: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Converter DC Side Faults

1. Faults across high

impedance ground

= High voltage

2. Fault across the converter

= High current

(pu)

1.50

1.00

0.50

0.00

-0.50

-1.00

-1.50

-2.00

DC Pole 1 Voltage

DC Pole 2 Voltage

(kA

)

20.0

0.00

0.0990 0.1000 0.1010 0.1020 0.1030 0.1040 0.1050 0.1060

DC Current

(pu)

1.50

1.00

0.50

0.00

-0.50

-1.00

-1.50

-2.00

DC Pole 1 Voltage

DC Pole 2 Voltage

(kA

)

20.0

0.00

0.0990 0.1000 0.1010 0.1020 0.1030 0.1040 0.1050 0.1060

DC Current

Page 11: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Clearance of DC Side Faults - Today

Voltage Source

Converters use the

mechanical AC breaker

as the Primary Protection

Line Commutated

Converters use the

power electronics as

the Primary Protection

Page 12: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Clearance of DC Side Faults - Tomorrow

Half-Bridge Voltage Source

Converters can use a hybrid

DC breaker as the Primary

Protection

Full-Bridge Voltage source

Converters use the power

electronics as the Primary

Protection

Page 13: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Protection requirements – AC vs. DC faults

Load

V

I

L Load

V

I

L

AC fault DC fault

Main : Graphs

0.240 0.250 0.260 0.270 0.280 0.290 0.300 0.310 0.320 0.330 0.340 ...

...

...

0

25

50

75

100

125

150

175

200

y

Vbreakerdc

Main : Graphs

0.240 0.250 0.260 0.270 0.280 0.290 0.300 0.310 0.320 0.330 0.340 ...

...

...

0

25

50

75

100

125

150

175

200

y

Vsystemdc

Main : Graphs

0.240 0.250 0.260 0.270 0.280 0.290 0.300 0.310 0.320 0.330 0.340 ...

...

...

0.0

1.0

2.0

3.0

4.0

5.0

y

Idc

Main : Graphs

0.240 0.250 0.260 0.270 0.280 0.290 0.300 0.310 0.320 0.330 0.340 ...

...

...

-150

-100

-50

0

50

100

150

y

Vsystem

Main : Graphs

0.240 0.250 0.260 0.270 0.280 0.290 0.300 0.310 0.320 0.330 0.340 ...

...

...

-4.0

-3.0

-2.0

-1.0

0.0

1.0

2.0

3.0

4.0

5.0

6.0

y

Iac

Main : Graphs

0.240 0.250 0.260 0.270 0.280 0.290 0.300 0.310 0.320 0.330 0.340 ...

...

...

-150

-100

-50

0

50

100

150

y

Vbreaker

• Natural zero crossings

• Magnitude decays over time

• Typically higher inductance

• No zero crossings

• Magnitude quickly raises over time

• Typically lower inductance

Page 14: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Review of options for HVDC circuit breaker

Topology Illustration Conclusions

Direct interruption using

arc voltage

Widely used at up to 2-3 kV

(e.g. railways) but

impossible for HVDC

Passive resonant

current zero creation

OK for HVDC load switching

but much too slow for fault

clearing

Active resonant current

zero creation

1. With standard circuit

breakers: much too slow

2. With vacuum switches:

high contact erosion

Solid state Very fast but

Very high losses (MW range)

Hybrid Fast enough and low losses.

Best solution.

Circuit Breaker

Circuit Breaker

Circuit Breaker

+

Power

Electronic

Switch

Ultra-fast

disconnectorPower

Electronic

Switch 1

Power

Electronic

Switch 2

Page 15: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Hybrid DC breaker – operating principle

PE2

PE1

Ultra-fast

disconnector

time

time

Nominal Vdc

Fault

occurs

PE1

turns off

Ultra-fast disconnector

fully open; PE2 turns off

Ibreaker

Vbreaker

Ibreaker

Vbreaker

Page 16: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

DC breaker – the importance of speed

Current

time

Fault

occurs

PE1

turns off

Ultra-fast disconnector

fully open; PE2 turns off

Clearing time Pre-clearing

time

Detection,

selectivity &

relay time

Voltage

rise time

I0

t1 Ipeak = I0 + di/dtfault . t1

Depends on

system strength

Depends on

breaker design

and protection

philosophy

To minimise the peak current rating of the breaker:

1. Detection, selectivity & relaying time to be as short as possible

2. Pre-clearing time to be as short as possible

Page 17: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

DC breaker – the effect of inductance

Current

time

I0

Additional inductance is a double-edged sword!

• It helps you on the way up…

• But makes life harder on the way down again

Without added

system inductance

With additional

inductance

Best of both worlds?

Needs something

smarter than just a

plain inductor

Page 18: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

The Grid Solutions Hybrid DC Breaker Power Electronics switch 1 (commutation module)

PE2

PE1

Ultra-fast

disconnector

• Multiple IGBTs in parallel

• Two inverse-series per commutation module

• Number of commutation blocks required depends on DC voltage

• Number of IGBTs in parallel is more than is needed for thermal reasons alone

− Lowest possible losses − Simplification of cooling

• Natural convection air cooling only

− No forced cooling − No phase change media − Nothing to leak

Page 19: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

The Grid Solutions hybrid DC breaker Power electronics switch 2 (auxiliary branch)

PE2

PE1

Ultra-fast

disconnector

• Well-known solution: multiple IGBTs in series (and inverse-series)

• Alstom considered this, but ultimately chose a different solution for the demonstrator

• Novel solution based on thyristors

• Very robust and capable of very high currents

• Number of time-delaying branches can be modified based on fault level and operating voltage

First time-delaying branch

Second time-delaying branch

Arming branch

Page 20: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

The Grid Solutions DC breaker demonstrator

Built and tested at Grid Solutions’ switchgear research facility in Villeurbanne, near Lyon, France

Key ratings:

• Rated voltage: 120 kV

• Rated direct current: 1500 A

• Overload current in closed state > 3000 A for 1 minute

Test programme agreed with and witnessed by RTE

• Dielectric tests between the terminals of an (open) breaker

• Continuous and short-time current through a (closed) breaker

• Interruption tests

Part of EU FP7 “Twenties” project

Page 21: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

HVDC Circuit Breaker

Page 22: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

TO

ANOTHER

DC GRID

HVDC Tomorrow DC Breakers used to separate out the DC network

DC/AC

Breaker

DC/AC

DC/AC

DC/AC

AC/DC

AC/DC

Breake

r

DC Sub-Network

AC/DC

AC/DC

AC/DC

DC Sub-Network

Page 23: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Where are we going?

Page 24: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Modular Multi-level Converter

DC Pole to Pole Fault:-

T2 Diode Conducts

Fault current uncontrolled

Fault current can only be

stopped by

a) AC breaker

b) DC breaker

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

T1

C

T2

+ T1

C

T2

+ T1

C

T2

+

Page 25: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

←Valve voltage

←Line-to-line voltage

We don’t just have to use sinewaves!

Page 26: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Modular Multi-level Converter – Full Bridge

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

S

M

T

1

C T

2

+

Vm

T

3

T

4

+Vc

Vm

-Vc

T

1

C T

2

+ T

3

T

4

T2 + T3

conducting

T

1

C T

2

+ T

3

T

4

T1 + T3

OR

T2 + T4

conducting

T

3

T

4

T

1

C T

2

+

T1 + T4

conducting

Page 27: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

T1

C

T2

+

Modular Multi-level Converter

Page 28: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Full-Bridge

Series Valve Alternate Arm Converter

Page 29: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Series Bridge Converter

Red, H-Bridge converts 80% of

power

Switching losses are minimised

by, Yellow, half-bridge chain-links

providing zero voltage soft-

switching

6th harmonic voltage cleaned by a

few full-bridge, blue, chain-links on

H-bridge output

Benefits Low footprint (over HB-MMC) as only

one HB Chain-link valve across the

DC rail

Cost savings over HB-MMC

Half-Bridge

Full-Bridge

Series Valve

Page 30: Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids

© 2015 General Electric Company - All rights reserved

Controlled Transition Bridge

Parallel converter style

approach

Allows switching losses to be

managed by Chain-links

Reduces filtering requirements

over LCC

Maintains high current

capability

Chain-link capacitor small

Complex control requirements

Half-Bridge

Full-Bridge


Recommended