Rooftop A/C
NeoCreator
1 2
Rooftop Packaged A/C
From 3 Tons to 30 Tons
Typical InstallationIndoor Air Duct Installation
StructureGuard grill
Fan
4-way
valve Wired-controller
panel
Motor support
Expansion valve
Compressor
Liquid receiver
Gas-liquid separator
Centrifugal fan
Motor
Condenser
Evaporator
Air inlet
langeFilter
Air outlet lange
Drain tray
Drain-pipe
Product lineups
T1Applications
Tropical (T3)Applications
Nominal ton* 4 5 6.2 7.5 8.5 10 12.5 17.515 20 25 30
Notes: 1. * Nominal ton only for reference. 2. means cooling type product; means heat pump type product.
3
NeoCreator is a new series optimized in design and capacity, maxizing container loading and better performance.
Introduction
Rooftop Packaged Air Conditioner is so called " Rooftop" because the installation location for the unit is mostly on the roof top. It is firstly developed and popular in USA and then widely applied around Latin America and the whole world.
The unit is compact design, which combines the evaporating and condensing side in the same casing, making it a "Package". Compact design and easy installation are the main features. It is widely applied in facilities and buildings like offices, shopping malls, big factories, where massive and continuous cooling is required. It is also suitable for houses or stores where rooms and spaces are big and require high air flow. In some circumstances, where hospitals requires clean air handling or clear air quality, sections such as HEPA, Filters fan sections and so on could be included and customized.
Rooftop A/C
3 4
Features
Wide cooling capacity range, from 36000Btu/h to 360000Btu/h.
Convenient for unit selectionWide cooling capacity range
Compact design.
Flanges of air flow inlet and outlet as standard.
It is suitable for installation in rooftop and ground.
Design flexibility
Pre-painted exterior cabinet panels pass 1000 hours Salt Spray Test for durability.
Weather-resistant construction with capped steams and sloped top panels.
G90 galvanized heavy gauge plate conforming to ASTM-A-653.
Outstanding reliabilityDurable construction
The rooftop package air conditioners with special anti-corrosion treatment are suitable for seaside areas or the areas
exposed to acidic substances.
Customized anti-corrosion treatment
Special anti-corrosion treatment of heat exchanger
provides 5 to 6 times greater resistance against acid
rain and salt corrosion.
All PCB parts in the unit are coated with double-side
moisture proof paint. The outer side of electric box
metal cover is spray-painted.
All screws are anti-rust.
Casings of the unit and motors are anti-rust.
Removable access door on the electric box. It is easy to
move the cover of the electric box.
Only connect the wires of power supply, and no need
to connect any signal wires.
Easy to installationConvenient for wires connection
Reserved external drainage port, quickly and accurately
connect the rubber drainage pipe.
Easily connect the drainage pipe
Famous brand compressor: Copeland, Hitachi, Danfoss,
etc. More reliable.
No complex internal suction and discharge valves for
quieter operation and higher reliability.
Compact, light-weight design, and fewer moving parts
design.
Reliable scroll compressor
Multi-measurement to ensure units operate normally
and reliably:
System current protection, High/low pressure switch
protection, Temperature sensor on/off protection, etc.
Three-phase protector can be customized.
Multi-protection design
Temperature sensorHP/LP switch
The unit provides external pressure gauge ports for convenient and fast checking
system pressure without removing the panel.
Easy to maintenanceExternal pressure gauge ports
Rooftop A/C
5 6
box sections.
and service.
Removable the access doors on the filter, fan motor, and electric
Provide convenient access to system components for mainenance
Easy access doors design
Press the ‘Check’ button, the LED display in PCB board of the unit will dislay the normal checking code.
If the unit is in running with abnormal operation, the LED display will show the error code.
System self-diagnostic
Washable ÿlter
Electric box
Access panel for electric box
Flexible choise of accessoriesControllers
Wired controller as standard.
Besides standard wired controller, others can be chosen too.
Multi-accessories
EHK (Electric Heater Kits) √
√
√
√
√
√
√
√
Filter
Three-phase protector
Network interface module
Anti-corrosion fin
Drainage pipe
Snap ring
Outlet drainage
Description
Standard accessories Optional accessories
NeoCreator series
Max.64
MD-NIM01 MD-NIM01 MD-NIM01 MD-NIM01
Centralized control function can be achieved through the centralized controller as optional. NIM01 should be connected between rooftop package units and centralized controller.
Other brand thermostat can be matched as optional solution.
Non-programmable thermostat
SW3: set to 1SW3
Three thickness filter: 0.5inch, 1inch and 2inch;
Two kinds of filter materials: Metal or Nylon + Metal frame.
EHK (Electric Heater Kits) and control box can be customized.
Adjustable pulley
Through changing the working pitch diameter of the pulley
mounted on driver shaft, in turn the revolutions per minute of the
driven shaft will increase or decrease to change air volume.
Air intake filter & EHK as optional
Rooftop A/C
7 8
SpecificationsT1 application,heat pump 380-415V 3Ph~ 50Hz
6.2RT & 7.5RT 8.5RT & 10RT 12.5RT
Notes:
1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;
Heating capacity test condition (2): Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 20°C DB / 15°C WB;
2. Units are suitable for operation to ±20% of nominal CFM;
3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.
4. Specifications are subject to change without prior notice for product improvement.
5. * Nominal ton only for reference.
6. Cooling or heating capacity as per specifications.
Nominal ton*
Cooling
Heating
Model
Air flow Indoor side
External static pressure
Max. power input
Max. current
Compressor
Indoor fan Type / Drive type
Outdoor fan Type / Drive type
Cooling
Heating
DimensionNet (W×H×D)
Weight
Ambienttemperature
Wired controller
Net / Gross
Packing (W×H×D)
CapacityBtu/h
kW
Btu/h.W
kW
Btu/h
kW
Btu/h.W
CFM
Pa
mm
dB(A)
mm
kg
kW
kW
A
Input
EER
Capacity
Input
COP
Type / Quantity
Brand
75,000
22.0
6.6
11.4
89,000
26.0
7.5
11.9
2,800
Default: 80; 0 ~ 250
18.3
Scroll / 1
Copeland
Centrifugal / Direct
Axial / Direct
KJR-25B
8,600
NAC-RF22HA/MX
1,475×840×1,130
1,495×870×1,150
229/234
10°C ~ 46°C
6.2
89,000
26.0
7.9
11.3
103,000
30.0
8.9
11.6
2,830
Default: 80; 0 ~ 250
24.8
Scroll / 1
Danfoss
Axial / Direct
KJR-25B
Centrifugal / Direct
12,000
NAC-RF26HA/MX
1,475×840×1,130
1,495×870×1,150
325/335
10°C ~ 46°C
7.5
103,000
30.0
9.3
11.1
120,000
35.0
10.6
11.3
3,500
Default: 80; 0 ~ 200
26.5
Scroll / 2
Hitachi
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
13,600
NAC-RF30HA/MX
1,483×1,138×1,231
1,500×1,255×1,155
340/350
10°C ~ 46°C
8.5
120,000
35.0
10.7
11.2
137,000
40.0
11.9
11.5
4,100
Default: 90; 0 ~ 250
28.8
Scroll / 2
Hitachi
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
16,000
NAC-RF35HA/MX
1,483×1,138×1,231
1,500×1,255×1,155
343/354
10°C ~ 46°C
10
150,000
44.0
13.3
11.3
154,000
45.0
13.2
11.7
5,500
Default: 110; 0 ~ 275
38.2
Scroll / 2
Copeland
Axial / Direct
KJR-12B/dP(T)-E
Centralized controller (Optional)
Sound pressure level
No
71.0 72.1 71.5 71.5
No Yes Yes Yes
71.8
Centrifugal / Belt
19,700
NAC-RF44HA/MX
1,965×1,230×1,130
1,995×1,255×1,160
451/471
10°C ~ 46°C
-9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C
12.5
SpecificationsT1 application, heat pump, 380~415V 3Ph~ 50Hz
Model
External static pressure
Nominal ton*
Cooling
Heating
Air flow Indoor side
Max. power input
Max. current
Compressor
Indoor fan Type / Drive type
Outdoor fan Type / Drive type
DimensionNet (W×H×D)
Weight
Ambient temperature
Wired controller
Centralized controller
Net / Gross
Packing (W×H×D)
Side-discharge Side-discharge Side-discharge
36,000 48,000 58,000
10.55 14.07 17.29
3.05 4.79 5.64
11.8 10.0 10.3
37,500 51,500 62,500
10.99 15.09 18.32
3.00 4.56 5.21
12.5 11.3 12.0
1,500 1,858 2,045
50 50 50
4.25 6.05 7.05
6.4 8.8 10.9
Scroll / 1 Scroll / 1 Scroll / 1
Copeland Copeland Copeland
Centrifugal / Direct
Axial / Direct Axial / Direct Axial / Direct
- - -
Centrifugal / Direct Centrifugal / Direct
NAC-RF10HA/M NAC-RF14HA/M NAC-RF17HA/M
Type
Btu/h
kW
Btu/h.W
CFM
Pa
1,116×830×744
No No
Sound pressure level 64.9 67.7 68.8
No
1,116×830×744 1,116×830×744
1,152×855×765 1,152×855×765 1,152×855×765
139/142 146/149 159/162
21°C ~ 43°C 21°C ~ 43°C 21°C ~ 43°C
mm
dB(A)
mm
kg
kW
Btu/h
kW
Btu/h.W
kW
kW
A
Capacity
Input
EER
Capacity
Input
COP
Type / Quantity
Brand
3 4 5
Notes:
1. Cooling capacity test condition: Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;
2. Heating capacity test condition: Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 20°C DB / 15°C WB;
3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.
4. Specifications are subject to change without prior notice for product improvement.
5. * Nominal ton only for reference.
6. Cooling or heating capacity as per specifications.
3 RT & 4 RT & 5 RT
9
Rooftop A/C
10
SpecificationsT1 application, heat pump 380-415V 3Ph~ 50Hz
15RT 17.5RT & 20RT 25RT & 30RT
Notes:
1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;
Heating capacity test condition (2): Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 20°C DB / 15°C WB;
2. Units are suitable for operation to ±20% of nominal CFM;
3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.
4. Specifications are subject to change without prior notice for product improvement.
5. * Nominal ton only for reference.
6. Cooling or heating capacity as per specifications.
-9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C
Nominal ton*
Cooling
Heating
Model
Air flow Indoor side
External static pressure
Max. power input
Max. current
Compressor
Indoor fan Type / Drive type
Outdoor fan Type / Drive type
DimensionNet (W×H×D)
Weight
Wired controller
Net / Gross
Packing (W×H×D)
CapacityBtu/h
kW
Btu/h.W
kW
Btu/h
kW
Btu/h.W
CFM
Pa
mm
dB(A)
mm
kg
kW
kW
A
Input
EER
Capacity
Input
COP
Type / Quantity
Brand
180,000
53.0
16.7
10.8
191,000
56.0
17.2
11.1
7,000
Default: 110; 0 ~ 325
46.1
Scroll / 2
Copeland
Centrifugal / Belt
Axial / Direct
KJR-12B/dP(T)-E
25.0
NAC-RF53HA/MX
1,965×1,230×1,130
1,995×1,255×1,160
492/512
10°C ~ 46°C
15
208,000
61.0
19.1
10.9
218,000
64.0
19.5
11.2
7,600
Default: 110; 0 ~ 250
55.4
Scroll / 2
Copeland
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
27.0
NAC-RF61HA/MX
1,670×1,247×2,192
1,695×1,284×2,212
615/645
10°C ~ 46°C
17.5
240,000
70.0
22.6
10.6
260,000
75.0
23.6
11.0
8,800
Default: 120; 0 ~ 375
63.2
Scroll / 2
Copeland
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
32.5
NAC-RF70HA/MX
1,670×1,247×2,192
1,695×1,284×2,212
690/720
10°C ~ 46°C
20
300,000
88.0
28.9
10.4
330,000
97.0
30.3
10.9
10,000
Default: 130; 0 ~ 350
74.3
Scroll / 2
Danfoss
Axial / Direct
KJR-12B/dP(T)-E
Sound pressure level
Centrifugal / Belt
38.5
NAC-RF88HA/MX
2,320×1,245×2,220
2,330×1,275×2,230
940/970
10°C ~ 46°C
25
335,000
98.0
32.8
10.2
380,000
111.5
36.5
10.4
11,200
Default: 270; 25 ~ 400
81.7
Scroll / 2
Danfoss
Axial / Direct
KJR-12B/dP(T)-E
Centralized controller (Optional) Yes Yes Yes Yes
76.9 76.0 75.3 76.8 77.9
Yes
Centrifugal / Belt
49.5
NAC-RF105HA/MX
2,320×1,245×2,220
2,330×1,275×2,230
955/985
10°C ~ 46°C
30
Ambienttemperature
Cooling
Heating
SpecificationsTropical (T3) application, Cooling Only, 380-415V 3Ph~ 50Hz
6.2RT & 7.5RT 8.5RT
Notes:
1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;
Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;
2. Units are suitable for operation to ±20% of nominal CFM;
3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.
4. Specifications are subject to change without prior notice for product improvement.
5. * Nominal ton only for reference.
6. Cooling or heating capacity as per specifications.
Nominal ton*
Cooling
Model
Air flow Indoor side
External pressure level
Max. power input
Max. current
Compressor
Indoor fan Type / Drive type
Outdoor fan Type / Drive type
DimensionNet (W×H×D)
Weight
Ambient temperature
Wired controller
Net / Gross
Packing (W×H×D)
Capacity (1)Btu/h
kW
Btu/h.W
kW
Btu/h
kW
Btu/h.W
CFM
Pa
mm
dB(A)
mm
kg
kW
kW
A
Input (1)
EER (1)
Capacity (2)
Input (2)
EER (2)
Type / Quantity
Brand
48,000
12.4
Scroll / 1
Copeland
Centrifugal / Direct
Axial / Direct
KJR-12B/dP(T)-E
6.2
NACT-RF14CA/MX
1,310×840×900
1,340×865×935
167/170
10°C ~ 52°C
4
58,000
15.5
Scroll / 1
Copeland
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Direct
7.4
NACT-RF17CA/MX
1,310×840×900
1,340×865×935
180/183
10°C ~ 52°C
5
75,000
22.0
6.6
11.4
61,400
18.0
7.8
7.9
2,800
Default: 80; 0 ~ 250
19.3
Scroll / 1
Copeland
Axial / Direct
KJR-25B
Centrifugal / Direct
9.0
NACT-RF22CA/MX
1,475×840×1,130
1,495×870×1,150
223/228
10°C ~ 52°C
6.2
89,000
26.0
7.9
11.3
69,600
20.4
9.0
7.8
2,830
Default: 80; 0 ~ 250
14.1
4.1
11.7
39,000
11.4
4.8
8.1
1,750
Default: 75; 0 ~ 200
17.0
5.0
11.6
47,900
14.0
5.9
8.1
2,000
Default: 75; 0 ~ 200
27.2
Scroll / 1
Danfoss
Axial / Direct
KJR-25B
Centralized controller (Optional) Yes Yes No
Sound pressure level 64.4 66.3 71.0
No
71.5
Centrifugal / Direct
13.6
NACT-RF26CA/MX
1,475×840×1,130
1,495×870×1,150
231/236
10°C ~ 52°C
7.5
4RT & 5RT
11
Rooftop A/C
12
SpecificationsTropical (T3) application, Cooling only 380-415V 3Ph~ 50Hz
8.5RT & 10RT 12.5RT
Notes:
1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;
Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;
2. Units are suitable for operation to ±20% of nominal CFM;
3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.
4. Specifications are subject to change without prior notice for product improvement.
5. * Nominal ton only for reference.
6. Cooling or heating capacity as per specifications.
Nominal ton*
Cooling
Model
Air flow Indoor side
External static pressure
Max. power input
Max. current
Compressor
Indoor fan Type / Drive type
Outdoor fan Type / Drive type
DimensionNet (W×H×D)
Weight
Ambient temperature
Wired controller
Net / Gross
Packing (W×H×D)
Capacity (1)Btu/h
kW
Btu/h.W
kW
Btu/h
kW
Btu/h.W
CFM
Pa
mm
dB(A)
mm
kg
kW
kW
A
Input (1)
EER (1)
Capacity (2)
Input (2)
EER (2)
Type / Quantity
Brand
102,000
30.0
9.2
11.1
80,700
23.7
10.3
7.9
3,500
Default: 80; 0 ~ 200
29.2
Scroll / 2
Hitachi
Centrifugal / Belt
Axial / Direct
KJR-12B/dP(T)-E
14.8
NACT-RF30CA/MX
1,483×1,231×1,138
1,500×1,255×1,155
331/342
10°C ~ 52°C
8.5
102,000
30.0
9.2
11.1
80,700
23.7
10.3
7.9
3,500
Default: 80; 0 ~ 200
29.2
Scroll / 1
Copeland
Axial / Direct
KJR-23B
Centrifugal / Belt
14.8
NACT-RF30CA/MXC
1,483×1,231×1,138
1,500×1,255×1,155
302/313
10°C ~ 52°C
8.5
120,000
35.0
10.7
11.2
100,200
29.4
12.6
8.0
4,100
Default: 90; 0 ~ 250
34.1
Scroll / 2
Hitachi
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
18.0
NACT-RF35CA/MX
1,483×1,231×1,138
1,500×1,255×1,155
335/346
10°C ~ 52°C
10
120,000
35.0
10.7
11.2
100,200
29.4
12.6
8.0
4,100
Default: 90; 0 ~ 250
34.1
Scroll / 1
Copeland
Axial / Direct
KJR-23B
Centrifugal / Belt
18.0
NACT-RF35CA/MXC
1,483×1,231×1,138
1,500×1,255×1,155
323/335
10°C ~ 52°C
10
150,000
44.0
13.3
11.3
125,400
36.8
16.1
7.8
5,500
Default: 110; 0 ~ 275
41.2
Scroll / 2
Copeland
Axial / Direct
KJR-12B/dP(T)-E
Centralized controller (Optional) Yes No Yes No
Sound pressure level 70.3 71.7 72.6 72.4
Yes
71.8
Centrifugal / Belt
21.0
NACT-RF44CA/MX
1,965×1,230×1,130
1,995×1,255×1,160
433/453
10°C ~ 52°C
12.5
SpecificationsTropical (T3) application, Cooling Only 380-415V 3Ph~ 50Hz
Notes:
1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;
Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;
2. Units are suitable for operation to ±20% of nominal CFM;
3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.
4. Specifications are subject to change without prior notice for product improvement.
5. * Nominal ton only for reference.
6. Cooling or heating capacity as per specifications.
15RT 17.5RT & 20RT 25RT & 30RT
Nominal ton*
Cooling
Model
Air flow Indoor side
External static pressure
Max. power input
Max. current
Compressor
Indoor fan Type / Drive type
Outdoor fan Type / Drive type
DimensionNet (W×H×D)
Weight
Ambient temperature
Wired controller
Net / Gross
Packing (W×H×D)
Capacity (1)Btu/h
kW
Btu/h.W
kW
Btu/h
kW
Btu/h.W
CFM
Pa
mm
dB(A)
mm
kg
kW
kW
A
Input (1)
EER (1)
Capacity (2)
Input (2)
EER (2)
Type / Quantity
Brand
180,000
53.0
16.7
10.8
146,000
42.8
18.7
7.8
7,000
Default: 110; 0 ~ 325
48.0
Scroll / 2
Copeland
Centrifugal / Belt
Axial / Direct
KJR-12B/dP(T)-E
25.0
NACT-RF53CA/MX
1,965×1,230×1,130
1,995×1,255×1,160
470/490
10°C ~ 52°C
15
208,000
61.0
19.1
10.9
181,100
53.1
22.6
8.0
7,600
Default: 110; 0 ~ 250
55.0
Scroll / 2
Copeland
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
26.5
NACT-RF61CA/MX
1,670×1,247×2,192
1,695×1,284×2,212
590/620
10°C ~ 52°C
17.5
240,000
70.0
22.6
10.6
199,200
58.4
25.1
7.9
8,800
Default: 120; 0 ~ 375
66.9
Scroll / 2
Copeland
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
33.0
NACT-RF70CA/MX
1,670×1,247×2,192
1,695×1,284×2,212
670/700
10°C ~ 52°C
20
300,000
87.0
28.0
10.7
251,700
73.8
32.0
7.9
10,000
Default: 110; 0 ~ 350
77.4
Scroll / 2
Danfoss
Axial / Direct
KJR-12B/dP(T)-E
Centrifugal / Belt
40.5
NACT-RF88CA/MX
2,320×1,245×2,220
2,330×1,275×2,230
895/925
10°C ~ 52°C
25
360,000
105.0
34.3
10.5
336,300
98.6
41.8
8.0
12,000
Default: 270; 0 ~ 400
94.1
Scroll / 2
Danfoss
Axial / Direct
KJR-12B/dP(T)-E
Centralized controller Yes Yes Yes Yes
Sound pressure level 75.5 75.0 75.3 76.8
Yes
77.9
Centrifugal / Belt
49.5
NACT-RF105CA/MX
2,320×1,245×2,220
2,330×1,275×2,230
910/940
10°C ~ 52°C
30
Rooftop A/C
13 14
DimensionsT1 application, 380~415V, 3Ph~, 50Hz NAC-RF10HA/M,NAC-RF14HA/M,NAC-RF17HA/M ((Units: mm)
121.
565
6
110
5040
43.8
Control box access panelHole for control wires
Hole for power wires
Hole for other purpose
299
293
830
89333
103195744
965
1,116
Retu
rn
Supply
Drain connection holeLow prussure gauge portHigh prussure gauge port
DimensionsTropical (T3) application: NACT-RF14CA/MX,NACT-RF17CA/MX
Units: mm)
Maintain orifice for air supply motor
Hole for bottom installation8-15×25
8871,294
840
63 60273
5181,310
42169
647
900
736
776
211
238
478
211
855
900
3961,2651,310
518
60
100314
280
370
250
285
310
280327
280
180
Rooftop A/C
15 16
T1 application: NAC-RF22HA/MX,NAC-RF26HA/MX Tropical (T3) application: NACT-RF22CA/MX,NACT-RF26CA/MX (Units: mm)
Condenser fan
Maintain orifice for air supply motor
Hole for bottom installation8-15×20
1,4591,115
840
6063
280
6681,475
42189
857
1,130
60
306
102
1,016
966
1,430
668 404
231
1,08
566
8
1,13
0
1,475
370327
328
294
310
285
370
327
310
328
294
285
T1 application: NAC-RF30HA/MX,NAC-RF35HA/MXTropical (T3) application: NACT-RF30CA/MX,NACT-RF35CA/MX NACT-RF30CA/MXD,NACT-RF35CA/MXD (Units: mm)
Condenser fan
Maintain orifice for air supply motor
1462
1117
1222
123
123388
700
105
105
284
560
392423
338 36
9
165
580 60
4
2952
3981,1
0
820
655
105
180
559
1,09
0
180
1,13
0
655
952982
581
369
339
423392
123265265 7001,4351,475
Hole for bottom installation10-15×20
Rooftop A/C
17 18
ClimaCreator seriesT1 application: NAC-RF44HA/MX,NAC-RF53HA/MX Tropical (T3) application: NACT-RF44CA/MX,NACT-RF53CA/MX (Units: mm)
Hole for bottom installation12-15×20
74506 801 506
232
232
665
74
972
467
555
335
67 165
67165666
75
75508
800
508
Condenser fan
Maintain orifice for air supply motor
1,130
1,965
1,22
7
1,1151,953
ClimaCreator seriesT1 application: NAC-RF61HA/MX,NAC-RF70HA/MX Tropical (T3) application: NACT-RF61CA/MX,NACT-RF70CA/MX (Units: mm)
Condenser fan
Compressor panel
Hole for bottom installation
14-15×20
8×Φ4.2
14×Φ4.2
Horizontal supply opening
Horizontal return opening
Maintain orifice for air supply motor
2,1711,654
1,247
2,192125
125
800
125
695
800
1,670 125434
Control panel
2,192
569
804
569
125
1,670800 310 12520
2,014
512
438 394 394 394
404 315 403 578
102 512 512 512
32.5
641
2520
230
020
232
731
108
297
Rooftop A/C
19 20
NEWEX INTERNATIONAL CO.,LTDSourcing Manager/ Sales Manager: Mr. Justin
Whatsapp/Mobile/Wechat: +8613928822021
Email: [email protected], [email protected]
Website: https://www.philexi.com, http://www.newexintl.com
ClimaCreator seriesT1 application: NAC-RF88HA/MX,NAC-RF105HA/MX Tropical (T3) application: NACT-RF88CA/MX,NACT-RF105CA/MX (Units: mm)
Hole for wires
Drain connection hole
Maintain orifice for air supply motor
Condenser fan
Horizontal supply opening
Horizontal return opening
Hole for bottom installation
16-15×20
2,220900
1,24
5
9002,320
130 130650 450900
130
130
500
500
900
490300
450 450 450
1,960
450
450
320
300
360
640
250
250
Controllers
Wired controllers
KJR-12B/dP(T)-E
Controller with Follow Me function, it helps making the
room environment comfortable.
Daily timer function.
4 ON/OFF indication
5
6
7
31
2
Follow me function
Fan speed indication
Lock
Temperature display zone
Mode indication
Timer ON/OFF
It is easy and convenient to select cooling, heating
and fan operation mode.
Digital display, seting temperature in 1°C.
4-4-minute delay function. The restarted compressor can be delayed for 4 minutes
this controller.
Filter-monitor function. When the run-time of operations reaches certain hours, the
Filter-change Indicatior of controller will flash to remind checking the filter of unit.
Easy to change °C and °F in site.
KJR-23B
KJR-25B