    Introduction 3.1

    Vector algebra 3.2

    Manipulation of complex quantities 3.3

    Circuit quantities and conventions 3.4

    Impedance notation 3.5

    Basic circuit laws, 3.6

    theorems and network reduction

    References 3.7

    3 F u n d a m e n t a l T h e o r y

  • 8/12/2019 net prot auton.pdf

    2/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 1 7

    3.1 INTRODUCTION

    The Protection Engineer is concerned with limiting theeffects of disturbances in a power system. Thesedisturbances, if allowed to persist, may damage plantand interrupt the supply of electric energy. They aredescribed as faults (short and open circuits) or powerswings, and result from natural hazards (for instancelightning), plant failure or human error.

    To facilitate rapid removal of a disturbance from a power

    system, the system is divided into 'protection zones'.Relays monitor the system quantities (current, voltage)appearing in these zones; if a fault occurs inside a zone,the relays operate to isolate the zone from the remainderof the power system.

    The operating characteristic of a relay depends on theenergizing quantities fed to it such as current or voltage,or various combinations of these two quantities, and onthe manner in which the relay is designed to respond tothis information. For example, a directional relaycharacteristic would be obtained by designing the relay

    to compare the phase angle between voltage and currentat the relaying point. An impedance-measuringcharacteristic, on the other hand, would be obtained bydesigning the relay to divide voltage by current. Manyother more complex relay characteristics may beobtained by supplying various combinations of currentand voltage to the relay. Relays may also be designed torespond to other system quantities such as frequency,power, etc.

    In order to apply protection relays, it is usually necessaryto know the limiting values of current and voltage, andtheir relative phase displacement at the relay location,for various types of short circuit and their position in thesystem. This normally requires some system analysis forfaults occurring at various points in the system.

    The main components that make up a power system aregenerating sources, transmission and distributionnetworks, and loads. Many transmission and distributioncircuits radiate from key points in the system and thesecircuits are controlled by circuit breakers. For thepurpose of analysis, the power system is treated as a

    network of circuit elements contained in branchesradiating from nodes to form closed loops or meshes.The system variables are current and voltage, and in

    3 Fu n d am en ta l T heo r y

  • 8/12/2019 net prot auton.pdf

    3/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    3

    Fundamenta

    lTheory

    1 8

    steady state analysis, they are regarded as time varyingquantities at a single and constant frequency. Thenetwork parameters are impedance and admittance;these are assumed to be linear, bilateral (independent ofcurrent direction) and constant for a constant frequency.

    3.2 VECTOR ALGEBRA

    A vector represents a quantity in both magnitude anddirection. In Figure 3.1 the vector OP has a magnitude|Z| at an angle with the reference axis OX.

    Figure 3.1

    It may be resolved into two components at right anglesto each other, in this case xandy. The magnitude orscalar value of vector Zis known as the modulus |Z|, and

    the angle is the argument, and is written as arg. Z.The conventional method of expressing a vectorZ

    is to

    write simply |Z|.

    This form completely specifies a vector for graphicalrepresentation or conversion into other forms.

    For vectors to be useful, they must be expressedalgebraically. In Figure 3.1, the vector

    Zis the resultant

    of vectorially adding its components x and y;algebraically this vector may be written as:

    Z=x +jy Equation 3.1

    where the operatorjindicates that the componentyisperpendicular to component x. In electricalnomenclature, the axis OC is the 'real' or 'in-phase' axis,and the vertical axis OY is called the 'imaginary' or'quadrature' axis. The operatorjrotates a vector anti-clockwise through 90. If a vector is made to rotate anti-clockwise through 180, then the operator j hasperformed its function twice, and since the vector hasreversed its sense, then:

    j xj orj2 =-1

    whence j = -1

    The representation of a vector quantity algebraically interms of its rectangular co-ordinates is called a 'complexquantity'. Therefore,x+jyis a complex quantity and isthe rectangular form of the vector |Z| where:

    Equation 3.2

    From Equations 3.1 and 3.2:Z= |Z| (cos +jsin) Equation 3.3

    and since cos and sin may be expressed inexponential form by the identities:

    it follows thatZmay also be written as:

    Z= |Z|ej Equation 3.4

    Therefore, a vector quantity may also be representedtrigonometrically and exponentially.

    3.3 MANIPULATION

    OF COMPLEX QUANTIT IES

    Complex quantities may be represented in any of thefour co-ordinate systems given below:

    a. Polar Z

    b. Rectangular x +jy

    c. Trigonometric |Z| (cos +jsin)

    d. Exponential |Z|ej

    The modulus |Z| and the argument are together knownas 'polar co-ordinates', and xand y are described as'cartesian co-ordinates'. Conversion between co-ordinate systems is easily achieved. As the operatorjobeys the ordinary laws of algebra, complex quantities inrectangular form can be manipulated algebraically, ascan be seen by the following:

    Z1 +

    Z2 = (x1+x2) +j(y1+y2) Equation 3.5

    Z1 -

    Z2 = (x1-x2) +j(y1-y2) Equation 3.6

    (see Figure 3.2)

    cos

    = e ej j

    2

    sin

    = e e

    j

    j j

    2

    Z x y

    y

    xx Z

    y Z

    = +( )

    =

    =

    =

    2 2

    1

    tan

    cos

    sin

    Figure 3.1: Vector OP

    0

    Y

    X

    P

    |Z|

    y

    x

    q

  • 8/12/2019 net prot auton.pdf

    4/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 1 9

    3

    Fundamenta

    lTheory

    Equation 3.7

    3.3.1 Complex variables

    Some complex quantities are variable with, for example,time; when manipulating such variables in differentialequations it is expedient to write the complex quantityin exponential form.

    When dealing with such functions it is important toappreciate that the quantity contains real and imaginary

    components. If it is required to investigate only onecomponent of the complex variable, separation intocomponents must be carried out after the mathematicaloperation has taken place.

    Example: Determine the rate of change of the realcomponent of a vector |Z|wtwith time.

    |Z|wt= |Z| (coswt+jsinwt)

    = |Z|ejwt

    The real component of the vector is |Z|coswt.

    Differentiating |Z|ejwt

    with respect to time:

    =jw|Z| (coswt+jsinwt)

    Separating into real and imaginary components:

    Thus, the rate of change of the real component of avector |Z|wtis:

    -|Z| w sinwt

    d

    dtZ e Z w wt jw wt jwt( )= +( )sin cos

    d

    dtZ e jw Z e jwt jwt =

    Z Z Z Z

    Z

    Z

    Z

    Z

    1 2 1 2 1 2

    1

    2

    1

    2

    1 2

    = +

    =

    3.3.2 Complex Numbers

    A complex number may be defined as a constant thatrepresents the real and imaginary components of aphysical quantity. The impedance parameter of anelectric circuit is a complex number having real andimaginary components, which are described as resistanceand reactance respectively.

    Confusion often arises between vectors and complexnumbers. A vector, as previously defined, may be acomplex number. In this context, it is simply a physicalquantity of constant magnitude acting in a constantdirection. A complex number, which, being a physicalquantity relating stimulus and response in a givenoperation, is known as a 'complex operator'. In thiscontext, it is distinguished from a vector by the fact thatit has no direction of its own.

    Because complex numbers assume a passive role in anycalculation, the form taken by the variables in the

    problem determines the method of representing them.

    3.3.3 Mathematical Operators

    Mathematical operators are complex numbers that areused to move a vector through a given angle withoutchanging the magnitude or character of the vector. Anoperator is not a physical quantity; it is dimensionless.

    The symbol j, which has been compounded withquadrature components of complex quantities, is an

    operator that rotates a quantity anti-clockwise through90. Another useful operator is one which moves avector anti-clockwise through 120, commonlyrepresented by the symbol a.

    Operators are distinguished by one further feature; theyare the roots of unity. Using De Moivre's theorem, thenth root of unity is given by solving the expression:

    11/n = (cos2m + jsin2m)1/n

    where m is any integer. Hence:

    where m has values 1, 2, 3, ... (n-1)

    From the above expressionjis found to be the 4th rootand a the 3rd root of unity, as they have four and threedistinct values respectively. Table 3.1 gives some usefulfunctions of the a operator.

    1

    2 21/ cos sinn

    m

    n j m

    n= +

    Figure 3.2: Addition of vectors

    0

    Y

    X

    y1

    y2

    x2x1

    |Z1|

    |Z2|

  • 8/12/2019 net prot auton.pdf

    5/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    1=1+j0 =ej0

    1+ a + a2 = 0

    Table 3.1: Properties of the a operator

    3.4 CIRCUIT QUANTIT IES

    AND CONVENTIONS

    Circuit analysis may be described as the study of theresponse of a circuit to an imposed condition, forexample a short circuit. The circuit variables are currentand voltage. Conventionally, current flow results fromthe application of a driving voltage, but there iscomplete duality between the variables and either maybe regarded as the cause of the other.

    When a circuit exists, there is an interchange of energy;a circuit may be described as being made up of 'sources'and 'sinks' for energy. The parts of a circuit are describedas elements; a 'source' may be regarded as an 'active'element and a 'sink' as a 'passive' element. Some circuitelements are dissipative, that is, they are continuoussinks for energy, for example resistance. Other circuitelements may be alternately sources and sinks, forexample capacitance and inductance. The elements of acircuit are connected together to form a network havingnodes (terminals or junctions) and branches (seriesgroups of elements) that form closed loops (meshes).

    In steady state a.c. circuit theory, the ability of a circuitto accept a current flow resulting from a given drivingvoltage is called the impedance of the circuit. Sincecurrent and voltage are duals the impedance parametermust also have a dual, called admittance.

    3.4.1 Circuit Variables

    As current and voltage are sinusoidal functions of time,varying at a single and constant frequency, they areregarded as rotating vectors and can be drawn as plan

    vectors (that is, vectors defined by two co-ordinates) ona vector diagram.

    j a a=

    2

    3

    a a j =2 3

    1 32 = a j a

    1 3 2 =a j a

    a j ej

    2

    4

    31

    2

    3

    2= =

    a j ej

    = + =1

    2

    3

    2

    2

    3

    For example, the instantaneous value, e, of a voltagevarying sinusoidally with time is:

    e=Emsin(wt+) Equation 3.8

    where:

    Em is the maximum amplitude of the waveform;=2f, the angular velocity,

    is the argument defining the amplitude of thevoltage at a time t=0

    At t=0, the actual value of the voltage is Emsin. So ifEm is regarded as the modulus of a vector, whose

    argument is , then Emsin is the imaginary componentof the vector |Em|. Figure 3.3 illustrates this quantityas a vector and as a sinusoidal function of time.

    Figure 3.3

    The current resulting from applying a voltage to a circuitdepends upon the circuit impedance. If the voltage is asinusoidal function at a given frequency and theimpedance is constant the current will also varyharmonically at the same frequency, so it can be shownon the same vector diagram as the voltage vector, and isgiven by the equation

    Equation 3.9

    where:

    Equation 3.10

    From Equations 3.9 and 3.10 it can be seen that theangular displacement between the current and voltagevectors and the current magnitude |Im|=|Em|/|Z| is

    dependent upon the impedance

    Z. In complex form theimpedance may be written Z=R+jX. The 'realcomponent', R, is the circuit resistance, and the

    Z R X

    X LC

    XR

    = +

    =

    =

    2 2

    1

    1

    tan

    iE

    Zwt

    m= + ( )sin 3

    Fundamenta

    lTheory

    2 0

    Figure 3.3: Representationof a sinusoidal function

    Y

    X' X0

    Y'

    e

    t =0

    t

    |Em| Em

  • 8/12/2019 net prot auton.pdf

    6/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 2 1

    'imaginary component',X, is the circuit reactance. Whenthe circuit reactance is inductive (that is, wL>1/wC), thecurrent 'lags' the voltage by an angle , and when it iscapacitive (that is, 1/wC>wL) it 'leads' the voltage by anangle .

    When drawing vector diagrams, one vector is chosen asthe 'reference vector' and all other vectors are drawn

    relative to the reference vector in terms of magnitudeand angle. The circuit impedance |Z| is a complexoperator and is distinguished from a vector only by thefact that it has no direction of its own. A furtherconvention is that sinusoidally varying quantities aredescribed by their 'effective' or 'root mean square' (r.m.s.)values; these are usually written using the relevantsymbol without a suffix.

    Thus:

    Equation 3.11

    The 'root mean square' value is that value which has thesame heating effect as a direct current quantity of thatvalue in the same circuit, and this definition applies tonon-sinusoidal as well as sinusoidal quantities.

    3.4.2 Sign Conventions

    In describing the electrical state of a circuit, it is oftennecessary to refer to the 'potential difference' existing

    between two points in the circuit. Since wherever sucha potential difference exists, current will flow and energywill either be transferred or absorbed, it is obviouslynecessary to define a potential difference in more exactterms. For this reason, the terms voltage rise and voltagedrop are used to define more accurately the nature of thepotential difference.

    Voltage rise is a rise in potential measured in thedirection of current flow between two points in a circuit.

    Voltage drop is the converse. A circuit element with avoltage rise across it acts as a source of energy. A circuit

    element with a voltage drop across it acts as a sink ofenergy. Voltage sources are usually active circuitelements, while sinks are usually passive circuitelements. The positive direction of energy flow is fromsources to sinks.

    Kirchhoff's first law states that the sum of the drivingvoltages must equal the sum of the passive voltages in aclosed loop. This is illustrated by the fundamentalequation of an electric circuit:

    Equation 3.12

    where the terms on the left hand side of the equation arevoltage drops across the circuit elements. Expressed in

    iR

    Ldi

    dt C idt e+ + =

    1

    I I

    E E

    m

    m

    =

    =

    2

    2

    steady state terms Equation 3.12 may be written:

    Equation 3.13

    and this is known as the equated-voltage equation [3.1].

    It is the equation most usually adopted in electricalnetwork calculations, since it equates the drivingvoltages, which are known, to the passive voltages,

    which are functions of the currents to be calculated.

    In describing circuits and drawing vector diagrams, forformal analysis or calculations, it is necessary to adopt anotation which defines the positive direction of assumedcurrent flow, and establishes the direction in whichpositive voltage drops and voltage rises act. Twomethods are available; one, the double suffix method, isused for symbolic analysis, the other, the single suffix ordiagrammatic method, is used for numericalcalculations.

    In the double suffix method the positive direction ofcurrent flow is assumed to be from node a to node b andthe current is designated Iab . With the diagrammaticmethod, an arrow indicates the direction of current flow.

    The voltage rises are positive when acting in thedirection of current flow. It can be seen from Figure 3.4that

    E1 and

    Ean are positive voltage rises and

    E2 and

    Ebn are negative voltage rises. In the diagrammaticmethod their direction of action is simply indicated by anarrow, whereas in the double suffix method,

    Ean and

    Ebn

    indicate that there is a potential rise in directions na and nb.

    Figure 3.4 Methods or representing a circuit

    E I Z =

    3

    Fundamenta

    lTheory

    (a) Diagrammatic

    (b) Double suffix

    a b

    n

    abI

    Z3

    Z2Z1

    E1

    Zan

    Zab

    Ean

    Zbn

    Ebn

    E2

    E1-E2=(Z1+Z2+Z3)I

    Ean-Ebn=(Zan+Zab+Zbn)Iab

    I

    Figure 3.4 Methods of representing a circuit

  • 8/12/2019 net prot auton.pdf

    7/23

  • 8/12/2019 net prot auton.pdf

    8/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 2 3

    Since the voltages are symmetrical, they may beexpressed in terms of one, that is:

    Ea =

    Ea

    Eb = a2

    Ea

    Ec= a

    Ea Equation 3.17

    where a is the vector operator ej2/3. Further, if the phasebranch impedances are identical in a balanced system, itfollows that the resulting currents are also balanced.

    3.5 IMPEDANCE NOTATION

    It can be seen by inspection of any power systemdiagram that:

    a. several voltage levels exist in a system

    b. it is common practice to refer to plant MVA in

    terms of per unit or percentage valuesc. transmission line and cable constants are given in

    ohms/km

    Before any system calculations can take place, thesystem parameters must be referred to 'base quantities'and represented as a unified system of impedances ineither ohmic, percentage, or per unit values.

    The base quantities are power and voltage. Normally,they are given in terms of the three-phase power in MVAand the line voltage in kV. The base impedance resulting

    from the above base quantities is:

    ohms Equation 3.18

    and, provided the system is balanced, the baseimpedance may be calculated using either single-phaseor three-phase quantities.

    The per unit or percentage value of any impedance in thesystem is the ratio of actual to base impedance values.

    Hence:

    Equation 3.19

    where MVAb = base MVA

    kVb = base kV

    Simple transposition of the above formulae will refer theohmic value of impedance to the per unit or percentage

    values and base quantities.Having chosen base quantities of suitable magnitude all

    Z p u Z ohms MVA

    kV

    Z Z p u

    b

    b

    . .

    % . .

    ( )= ( )( )

    ( )= ( )

    2

    100

    ZkV

    MVAb=

    ( )2

    system impedances may be converted to those basequantities by using the equations given below:

    Equation 3.20

    where suffix b1 denotes the value to the original base

    and b2 denotes the value to new base

    The choice of impedance notation depends upon thecomplexity of the system, plant impedance notation andthe nature of the system calculations envisaged.

    If the system is relatively simple and contains mainlytransmission line data, given in ohms, then the ohmicmethod can be adopted with advantage. However, theper unit method of impedance notation is the mostcommon for general system studies since:

    1. impedances are the same referred to either side ofa transformer if the ratio of base voltages on thetwo sides of a transformer is equal to thetransformer turns ratio

    2. confusion caused by the introduction of powers of100 in percentage calculations is avoided

    3. by a suitable choice of bases, the magnitudes ofthe data and results are kept within a predictablerange, and hence errors in data and computationsare easier to spot

    Most power system studies are carried out usingsoftware in per unit quantities. Irrespective of themethod of calculation, the choice of base voltage, andunifying system impedances to this base, should beapproached with caution, as shown in the followingexample.

    Z Z MVA

    MVA

    Z Z kV

    kV

    b bb

    b

    b bb

    b

    2 1

    2

    1

    2 1

    1

    2

    2

    =

    =

    3

    Fundamenta

    lTheory

    Figure 3.6: Selection of base voltages

    11.8kV 11.8/141kV

    132kVOverhead line

    132/11kV

    Distribution11kV

    Wrong selection of base voltage

    11.8kV 132kV 11kV

    Right selection

    11.8kV 141kV x 11=11.7kV141132

  • 8/12/2019 net prot auton.pdf

    9/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    From Figure 3.6 it can be seen that the base voltages inthe three circuits are related by the turns ratios of theintervening transformers. Care is required as thenominal transformation ratios of the transformersquoted may be different from the turns ratios- e.g. a110/33kV (nominal) transformer may have a turns ratioof 110/34.5kV. Therefore, the rule for hand calculationsis: 'to refer an impedance in ohms from one circuit to

    another multiply the given impedance by the square ofthe turns ratio (open circuit voltage ratio) of theintervening transformer'.

    Where power system simulation software is used, thesoftware normally has calculation routines built in toadjust transformer parameters to take account ofdifferences between the nominal primary and secondaryvoltages and turns ratios. In this case, the choice of basevoltages may be more conveniently made as the nominalvoltages of each section of the power system. Thisapproach avoids confusion when per unit or percentvalues are used in calculations in translating the finalresults into volts, amps, etc.

    For example, in Figure 3.7, generators G1 and G2 have asub-transient reactance of 26% on 66.6MVA rating at11kV, and transformers T1 and T2 a voltage ratio of11/145kV and an impedance of 12.5% on 75MVA.Choosing 100MVA as base MVA and 132kV as basevoltage, find the percentage impedances to new basequantities.

    a. Generator reactances to new bases are:

    b. Transformer reactances to new bases are:

    NOTE: The base voltages of the generator and circuits

    are 11kV and 145kV respectively, that is, the turns

    ratio of the transformer. The corresponding per unit

    values can be found by dividing by 100, and the ohmic

    value can be found by using Equation 3.19.

    Figure 3.7

    12 5 100

    75

    145

    132

    20 1

    2

    2. . %

    ( )

    ( )=

    26 100

    66 6

    11

    132

    0 27

    2

    2

    ( )

    ( )=

    .. %

    3.6 BASIC CIRCUIT LAWS,

    THEOREMS AND NETWORK REDUCTION

    Most practical power system problems are solved byusing steady state analytical methods. The assumptionsmade are that the circuit parameters are linear andbilateral and constant for constant frequency circuitvariables. In some problems, described as initial value

    problems, it is necessary to study the behaviour of acircuit in the transient state. Such problems can besolved using operational methods. Again, in otherproblems, which fortunately are few in number, theassumption of linear, bilateral circuit parameters is nolonger valid. These problems are solved using advancedmathematical techniques that are beyond the scope ofthis book.

    3.6.1 Circuit Laws

    In linear, bilateral circuits, three basic network lawsapply, regardless of the state of the circuit, at anyparticular instant of time. These laws are the branch,

    junction and mesh laws, due to Ohm and Kirchhoff, andare stated below, using steady state a.c. nomenclature.

    3.6.1.1 Branch law

    The currentI in a given branch of impedance

    Z is

    proportional to the potential differenceV appearing

    across the branch, that is,V=

    I

    Z.

    3.6.1.2 Junction law

    The algebraic sum of all currents entering any junction(or node) in a network is zero, that is:

    3.6.1.3 Mesh law

    The algebraic sum of all the driving voltages in anyclosed path (or mesh) in a network is equal to thealgebraic sum of all the passive voltages (products of theimpedances and the currents) in the componentsbranches, that is:

    Alternatively, the total change in potential around aclosed loop is zero.

    3.6.2 Circuit Theorems

    From the above network laws, many theorems have beenderived for the rationalisation of networks, either toreach a quick, simple, solution to a problem or to

    represent a complicated circuit by an equivalent. Thesetheorems are divided into two classes: those concernedwith the general properties of networks and those

    E Z I=

    I= 0

    3

    Fundamenta

    lTheory

    2 4

    Figure 3.7: Section of a power system

    G1

    T1

    T2

    G2

    132kVoverheadlines

  • 8/12/2019 net prot auton.pdf

    10/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 2 5

    concerned with network reduction.

    Of the many theorems that exist, the three mostimportant are given. These are: the SuperpositionTheorem, Thvenin's Theorem and Kennelly's Star/DeltaTheorem.

    3.6.2.1 Superposition Theorem(general network theorem)

    The resultant current that flows in any branch of anetwork due to the simultaneous action of severaldriving voltages is equal to the algebraic sum of thecomponent currents due to each driving voltage actingalone with the remainder short-circuited.

    3.6.2.2 Thvenin's Theorem(active network reduction theorem)

    Any active network that may be viewed from twoterminals can be replaced by a single driving voltageacting in series with a single impedance. The driving

    voltage is the open-circuit voltage between the twoterminals and the impedance is the impedance of thenetwork viewed from the terminals with all sourcesshort-circuited.

    3.6.2.3 Kennelly's Star/Delta Theorem(passive network reduction theorem)

    Any three-terminal network can be replaced by a delta orstar impedance equivalent without disturbing theexternal network. The formulae relating the replacementof a delta network by the equivalent star network is as

    follows (Figure 3.8):Zco =

    Z13

    Z23 / (

    Z12 +

    Z13 +

    Z23)

    and so on.

    Figure 3.8: Star/Delta network reduction

    The impedance of a delta network corresponding to andreplacing any star network is:

    Z12 =

    Zao +

    Zbo +

    Zao

    Zbo

    Zco

    and so on.

    3.6.3 Network Reduction

    The aim of network reduction is to reduce a system to asimple equivalent while retaining the identity of thatpart of the system to be studied.

    For example, consider the system shown in Figure 3.9.The network has two sources E and E, a line AOBshunted by an impedance, which may be regarded as the

    reduction of a further network connected betweenA andB, and a load connected between O andN. The object ofthe reduction is to study the effect of opening a breakeratA or B during normal system operations, or of a faultatA or B. Thus the identity of nodesA and B must beretained together with the sources, but the branch ONcan be eliminated, simplifying the study. Proceeding,A,B,N, forms a star branch and can therefore be convertedto an equivalent delta.

    Figure 3.9

    = 51 ohms

    =30.6 ohms

    = 1.2 ohms (since ZNO>>> ZAOZBO)

    Figure 3.10

    Z Z Z Z Z

    ZAN AO BO

    AO BO

    NO

    = + +

    = + + 0 45 18 85 0 45 18 850 75

    . . . .

    .

    Z Z Z Z Z

    Z

    BN BO NOBO NO

    AO

    = + +

    = + + 0 75 18 85 0 75 18 850 45

    . . . .

    .

    Z Z Z Z Z

    ZAN AO NO

    AO NO

    BO

    = + +

    3

    Fundamenta

    lTheory

    Figure 3.8: Star-Delta network transformation

    c

    Zao

    Zbo

    Z12

    Z23

    Z13

    Oa b 1 2

    3

    (a) Star network (b) Delta network

    Zco

    Figure 3.9: Typical power system network

    E' E''

    N

    0A B

    1.6

    0.75 0.45

    18.85

    2.55

    0.4

  • 8/12/2019 net prot auton.pdf

    11/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    The network is now reduced as shown in Figure 3.10.

    By applying Thvenin's theorem to the active loops, thesecan be replaced by a single driving voltage in series withan impedance as shown in Figure 3.11.

    Figure 3.11

    The network shown in Figure 3.9 is now reduced to thatshown in Figure 3.12 with the nodesA and B retainingtheir identity. Further, the load impedance has beencompletely eliminated.

    The network shown in Figure 3.12 may now be used tostudy system disturbances, for example power swingswith and without faults.

    Figure 3.12

    Most reduction problems follow the same pattern as theexample above. The rules to apply in practical networkreduction are:

    a. decide on the nature of the disturbance ordisturbances to be studied

    b. decide on the information required, for examplethe branch currents in the network for a fault at a

    particular location

    c. reduce all passive sections of the network notdirectly involved with the section underexamination

    d. reduce all active meshes to a simple equivalent,that is, to a simple source in series with a singleimpedance

    With the widespread availability of computer-basedpower system simulation software, it is now usual to usesuch software on a routine basis for network calculations

    without significant network reduction taking place.However, the network reduction techniques given aboveare still valid, as there will be occasions where suchsoftware is not immediately available and a handcalculation must be carried out.

    In certain circuits, for example parallel lines on the sametowers, there is mutual coupling between branches.Correct circuit reduction must take account of thiscoupling.

    Figure 3.13

    Three cases are of interest. These are:

    a. two branches connected together at their nodes

    b. two branches connected together at one node only

    c. two branches that remain unconnected

    3

    Fundamenta

    lTheory

    2 6

    Figure 3.10: Reduction usingstar/delta transform

    E'

    A

    51 30.6

    0.4

    2.5

    1.21.6

    N

    B

    E''

    Figure 3.12: Reduction of typicalpower system network

    N

    A B

    1.2

    2.5

    1.55

    0.97E'

    0.39

    0.99E''

    Figure 3.11: Reduction of active meshes:Thvenin's Theorem

    E'

    A

    N

    (a) Reduction of left active mesh

    N

    A

    (b) Reduction of right active mesh

    E''

    N

    B B

    N

    E''

    31

    30.630.6

    31

    0.4 x30.6

    52.6

    1.6 x51

    E'52.6

    5151

    1.6

    0.4

    Figure 3.13: Reduction of two brancheswith mutual coupling

    (a) Actual circuit

    IP Q

    P Q

    (b) Equivalent whenZaaZbb

    (c) Equivalent whenZaa=Zbb

    P Q

    21Z= (Zaa+Zbb)

    Zaa

    Zbb

    Z=ZaaZbb-Z

    2ab

    Zaa+Zbb-2Zab

    Zab

    Ia

    Ib

    I

    I

  • 8/12/2019 net prot auton.pdf

    12/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 2 7

    Considering each case in turn:

    a. consider the circuit shown in Figure 3.13(a). Theapplication of a voltage Vbetween the terminals Pand Q gives:

    V = IaZaa + IbZab

    V = IaZab + IbZbb

    where Ia and Ib are the currents in branches a andb, respectively and I= Ia +Ib , the total currententering at terminal Pand leaving at terminal Q.

    Solving for Ia and Ib :

    from which

    and

    so that the equivalent impedance of the originalcircuit is:

    Equation 3.21

    (Figure 3.13(b)), and, if the branch impedances areequal, the usual case, then:

    Equation 3.22

    (Figure 3.13(c)).

    b. consider the circuit in Figure 3.14(a).

    Z Z Zaa ab= +( )1

    2

    Z V

    I

    Z Z Z

    Z Z Z

    aa bb ab

    aa bb ab

    = =

    +

    2

    2

    I I IV Z Z Z

    Z Z Za b

    aa bb ab

    aa bb ab

    = + = + ( )

    2

    2

    IZ Z V

    Z Z Z

    b

    aa ab

    aa bb ab

    = ( )

    2

    IZ Z V

    Z Z Za

    bb ab

    aa bb ab

    = ( )

    2

    The assumption is made that an equivalent starnetwork can replace the network shown. Frominspection with one terminal isolated in turn and avoltage Vimpressed across the remaining terminalsit can be seen that:

    Za+Zc=Zaa

    Zb+Zc=Zbb

    Za+Zb=Zaa+Zbb-2Zab

    Solving these equations gives:

    Equation 3.23

    -see Figure 3.14(b).

    c. consider the four-terminal network given in Figure3.15(a), in which the branches 11' and 22' areelectrically separate except for a mutual link. Theequations defining the network are:

    V1=Z11I1+Z12I2

    V2=Z21I1+Z22I2

    I1=Y11V1+Y12V2

    I2=Y21V1+Y22V2

    where Z12=Z21 and Y12=Y21 , if the network is

    assumed to be reciprocal. Further, by solving theabove equations it can be shown that:

    Equation 3.24

    There are three independent coefficients, namelyZ12, Z11, Z22, so the original circuit may be

    replaced by an equivalent mesh containing fourexternal terminals, each terminal being connectedto the other three by branch impedances as shownin Figure 3.15(b).

    Y Z

    Y Z

    Y Z

    Z Z Z

    11 22

    22 11

    12 12

    11 22 122

    =

    =

    =

    =

    Z Z Z

    Z Z Z

    Z Z

    a aa ab

    b bb ab

    c ab

    =

    =

    =

    3

    Fundamenta

    lTheory

    Figure 3.14: Reduction of mutually-coupled brancheswith a common terminal

    A

    C

    B

    (b) Equivalent circuit

    B

    C

    A

    (a) Actual circuit

    Zaa

    Zbb

    Zab

    Za=Zaa-Zab

    Zb=Zbb-Zab

    Zc=Zab

    Figure 3.15 : Equivalent circuits forfour terminal network with mutual coupling

    (a) Actual circuit

    2

    1

    2'

    1'

    2'

    1'

    (b) Equivalent circuit

    2

    1

    Z11

    Z22

    Z11

    Z22

    Z12 Z12 Z12 Z12Z21

  • 8/12/2019 net prot auton.pdf

    13/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    defining the equivalent mesh in Figure 3.15(b), andinserting radial branches having impedances equalto Z11 and Z22 in terminals 1 and 2, results inFigure 3.15(d).

    3.7 REFERENCES

    3.1Power System Analysis.

    J. R. Mortlock andM. W. Humphrey Davies. Chapman & Hall.

    3.2 Equivalent Circuits I. Frank M. Starr, Proc. A.I.E.E.Vol. 51. 1932, pp. 287-298.

    3

    Fundamenta

    lTheory

    2 8

    Figure 3.15: Equivalent circuits forfour terminal network with mutual coupling

    2'

    1'

    (d) Equivalent circuit

    11

    C 2

    (c) Equivalent with all

    nodes commoned except 1

    Z11 Z12

    Z11

    Z12

    Z12

    Z12

    -Z12 -Z12Z12

    In order to evaluate the branches of the equivalentmesh let all points of entry of the actual circuit becommoned except node 1 of circuit 1, as shown inFigure 3.15(c). Then all impressed voltages exceptV1 will be zero and:

    I1 = Y11V1

    I2 = Y12V1

    If the same conditions are applied to the equivalentmesh, then:

    I1 = V1Z11

    I2 = -V1/Z12 = -V1/Z12

    These relations follow from the fact that the branchconnecting nodes 1 and 1' carries current I1 andthe branches connecting nodes 1 and 2' and 1 and2 carry current I2. This must be true since branchesbetween pairs of commoned nodes can carry no

    current.By considering each node in turn with theremainder commoned, the following relationshipsare found:

    Z11 = 1/Y11

    Z22 = 1/Y22

    Z12 = -1/Y12

    Z12 = Z1 2 = -Z21 = -Z12

    Hence:

    Z11 = Z11Z22-Z212_______________Z22

    Z22 = Z11Z22-Z212_______________Z11

    Z12 = Z11Z22-Z212_______________Z12 Equation 3.25

    A similar but equally rigorous equivalent circuit isshown in Figure 3.15(d). This circuit [3.2] followsfrom the fact that the self-impedance of any circuitis independent of all other circuits. Therefore, it

    need not appear in any of the mutual branches if itis lumped as a radial branch at the terminals. Soputting Z11 and Z22 equal to zero in Equation 3.25,

  • 8/12/2019 net prot auton.pdf

    14/23

  • 8/12/2019 net prot auton.pdf

    15/23

    Introduction 4.1

    Three phase fault calculations 4.2

    Symmetrical component analysis 4.3of a three-phase network

    Equations and network connections 4.4for various types of faults

    Current and voltage distribution 4.5in a system due to a fault

    Effect of system earthing 4.6on zero sequence quantities

    References 4.7

    4 F a u l t C a l c u l a t i o n s

  • 8/12/2019 net prot auton.pdf

    16/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 3 1

    4.1 INTRODUCTION

    A power system is normally treated as a balancedsymmetrical three-phase network. When a fault occurs,the symmetry is normally upset, resulting in unbalancedcurrents and voltages appearing in the network. The onlyexception is the three-phase fault, which, because itinvolves all three phases equally at the same location, isdescribed as a symmetrical fault. By using symmetricalcomponent analysis and replacing the normal system

    sources by a source at the fault location, it is possible toanalyse these fault conditions.

    For the correct application of protection equipment, it isessential to know the fault current distributionthroughout the system and the voltages in differentparts of the system due to the fault. Further, boundaryvalues of current at any relaying point must be known ifthe fault is to be cleared with discrimination. Theinformation normally required for each kind of fault ateach relaying point is:

    i. maximum fault current

    ii. minimum fault current

    iii. maximum through fault current

    To obtain the above information, the limits of stablegeneration and possible operating conditions, includingthe method of system earthing, must be known. Faultsare always assumed to be through zero fault impedance.

    4.2 THREE-PHASE FAULT CALCULATIONS

    Three-phase faults are unique in that they are balanced,that is, symmetrical in the three phases, and can becalculated from the single-phase impedance diagramand the operating conditions existing prior to the fault.

    A fault condition is a sudden abnormal alteration to thenormal circuit arrangement. The circuit quantities,current and voltage, will alter, and the circuit will passthrough a transient state to a steady state. In thetransient state, the initial magnitude of the fault currentwill depend upon the point on the voltage wave at whichthe fault occurs. The decay of the transient condition,

    until it merges into steady state, is a function of theparameters of the circuit elements. The transient currentmay be regarded as a d.c. exponential current

    4 Fault Calc ulat io ns

  • 8/12/2019 net prot auton.pdf

    17/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    4

    Fault

    Calculations

    3 2

    superimposed on the symmetrical steady state faultcurrent. In a.c. machines, owing to armature reaction,the machine reactances pass through 'sub transient' and'transient' stages before reaching their steady statesynchronous values. For this reason, the resultant faultcurrent during the transient period, from fault inceptionto steady state also depends on the location of the faultin the network relative to that of the rotating plant.

    In a system containing many voltage sources, or havinga complex network arrangement, it is tedious to use thenormal system voltage sources to evaluate the faultcurrent in the faulty branch or to calculate the faultcurrent distribution in the system. A more practicalmethod [4.1] is to replace the system voltages by a singledriving voltage at the fault point. This driving voltage isthe voltage existing at the fault point before the faultoccurs.

    Consider the circuit given in Figure 4.1 where the driving

    voltages are

    Eand

    E, the impedances on either side of

    fault point FareZ1and

    Z1 , and the current through

    point Fbefore the fault occurs isI.

    Figure 4.1:

    The voltageVat Fbefore fault inception is:

    V=

    E-

    I

    Z =

    E +

    I

    Z

    After the fault the voltageVis zero. Hence, the change

    in voltage is - V. Because of the fault, the change in thecurrent flowing into the network from Fis:

    and, since no current was flowing into the network fromFprior to the fault, the fault current flowing from thenetwork into the fault is:

    By applying the principle of superposition, the loadcurrents circulating in the system prior to the fault may

    If I VZ Z

    Z Z= =

    +( ) 1 1

    1 1

    ' ''

    ' ''

    I V

    ZV

    Z Z

    Z Z= =

    +( )1

    1 1

    1 1

    ' ''

    ' ''

    be added to the currents circulating in the system due tothe fault, to give the total current in any branch of thesystem at the time of fault inception. However, in mostproblems, the load current is small in comparison to thefault current and is usually ignored.

    In a practical power system, the system regulation issuch that the load voltage at any point in the system is

    within 10% of the declared open-circuit voltage at thatpoint. For this reason, it is usual to regard the pre-faultvoltage at the fault as being the open-circuit voltage,and this assumption is also made in a number of thestandards dealing with fault level calculations.

    For an example of practical three-phase faultcalculations, consider a fault atA in Figure 3.9. With thenetwork reduced as shown in Figure 4.2, the load voltageatA before the fault occurs is:

    Figure 4.2:

    V= 0.97

    E - 1.55

    I

    For practical working conditions,E 1.55

    I and

    E 1.207

    I. Hence

    E

    E

    V.

    Replacing the driving voltagesE and

    E by the load

    voltageVbetweenA andNmodifies the circuit as shown

    in Figure 4.3(a).

    The nodeA is the junction of three branches. In practice,the node would be a busbar, and the branches arefeeders radiating from the bus via circuit breakers, asshown in Figure 4.3(b). There are two possible locationsfor a fault atA; the busbar side of the breakers or theline side of the breakers. In this example, it is assumedthat the fault is atX, and it is required to calculate thecurrent flowing from the bus toX.

    The network viewed from AN has a driving point

    impedance |Z1| = 0.68ohms.

    The current in the fault is.

    V

    Z1

    V E I= + +

    +

    0 99 1 2 2 5

    2 5 1 2 0 39.

    . .

    . ..''

    Figure 4.1: Network with fault at F

    N

    FZ '1 Z''1

    I

    VE' E''

    Figure 4.2: Reduction of typical

    power system network

    N

    1.55A B

    2.5

    1.2

    0.39

    0.99E ''0.97E '

  • 8/12/2019 net prot auton.pdf

    18/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 3 3

    4

    Fault

    Calculations

    Let this current be 1.0 per unit. It is now necessary tofind the fault current distribution in the various branchesof the network and in particular the current flowing fromA toXon the assumption that a relay atXis to detectthe fault condition. The equivalent impedances viewedfrom either side of the fault are shown in Figure 4.4(a).

    Figure 4.3

    Figure 4.4

    The currents from Figure 4.4(a) are as follows:

    From the right:

    From the left:

    There is a parallel branch to the right ofA

    1 21

    2 760 437

    .

    . .=

    p.u.

    1 55

    2 760 563

    .

    ..= p.u.

    Therefore, current in 2.5 ohm branch

    and the current in 1.2 ohm branch

    Total current enteringXfrom the left, that is, fromA toX, is 0.437 + 0.183 = 0.62p.u. and from B to X is0.38p.u. The equivalent network as viewed from therelay is as shown in Figure 4.4(b). The impedances oneither side are:

    0.68/0.62 = 1.1ohmsand

    0.68/0.38 = 1.79ohms

    The circuit of Figure 4.4 (b) has been included becausethe Protection Engineer is interested in these equivalentparameters when applying certain types of protectionrelay.

    4.3 SYMMETRICAL COMPONENT ANALYSISOF A THREE-PHASE NETWORK

    The Protection Engineer is interested in a wider variety offaults than just a three-phase fault. The most commonfault is a single-phase to earth fault, which, in LV

    systems, can produce a higher fault current than a three-phase fault. Similarly, because protection is expected tooperate correctly for all types of fault, it may benecessary to consider the fault currents due to manydifferent types of fault. Since the three-phase fault isunique in being a balanced fault, a method of analysisthat is applicable to unbalanced faults is required. It canbe shown [4.2] that, by applying the 'Principle ofSuperposition', any general three-phase system ofvectors may be replaced by three sets of balanced(symmetrical) vectors; two sets are three-phase but

    having opposite phase rotation and one set is co-phasal.These vector sets are described as the positive, negativeand zero sequence sets respectively.

    The equations between phase and sequence voltages aregiven below:

    Equation 4.1

    E E E E

    E a E aE E

    E aE a E E

    a

    b

    c

    = + +

    = + +

    = + +

    1 2 0

    21 2 0

    12

    2 0

    = =2 5 0 563 3 7

    0 38. .

    .. p.u.

    =

    =1 2 0 563

    3 70 183

    . .

    .. p.u.

    Figure 4.3: Network with fault at node A

    N

    A

    V

    B

    A

    X

    (b) Typical physical arrangement of node A with a fault shown at X

    (a) Three - phase fault diagram for a fault at node A

    BusbarCircuit breaker

    1.55

    1.2

    2.5

    0.39

    Figure 4.4: Impedances viewed from fault

    N

    V

    A

    N

    V

    X

    1.55 1.21

    1.791.1

    (a) Impedance viewed from node A

    (b) Equivalent impedances viewed from node X

  • 8/12/2019 net prot auton.pdf

    19/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    Equation 4.2

    where all quantities are referred to the reference phaseA. A similar set of equations can be written for phaseand sequence currents. Figure 4.5 illustrates theresolution of a system of unbalanced vectors.

    Figure 4.5

    When a fault occurs in a power system, the phase

    impedances are no longer identical (except in the case ofthree-phase faults) and the resulting currents andvoltages are unbalanced, the point of greatest unbalancebeing at the fault point. It has been shown in Chapter 3that the fault may be studied by short-circuiting allnormal driving voltages in the system and replacing thefault connection by a source whose driving voltage isequal to the pre-fault voltage at the fault point. Hence,the system impedances remain symmetrical, viewed fromthe fault, and the fault point may now be regarded as thepoint of injection of unbalanced voltages and currents

    into the system.This is a most important approach in defining the faultconditions since it allows the system to be representedby sequence networks [4.3] using the method ofsymmetrical components.

    4.3.1 Positive Sequence Network

    During normal balanced system conditions, only positivesequence currents and voltages can exist in the system,and therefore the normal system impedance network is a

    positive sequence network.

    When a fault occurs in a power system, the current in the

    E E aE a E

    E E a E aE

    E E E E

    a b c

    a b c

    a b c

    12

    22

    0

    1

    3

    1

    3

    1

    3

    = + +( )

    = + +( )

    = + +( )

    fault branch changes from 0 toI and the positive

    sequence voltage across the branch changes fromVto

    V1;

    replacing the fault branch by a source equal to the changein voltage and short-circuiting all normal driving voltagesin the system results in a current

    I flowing into the

    system, and:

    Equation 4.3

    whereZ1 is the positive sequence impedance of the

    system viewed from the fault. As before the fault nocurrent was flowing from the fault into the system, itfollows that

    I1 , the fault current flowing from the

    system into the fault must equal - I . Therefore:

    V1 =

    V-

    I1

    Z1 Equation 4.4

    is the relationship between positive sequence currentsand voltages in the fault branch during a fault.

    In Figure 4.6, which represents a simple system, thevoltage drops

    I1

    Z1 and

    I1

    Z1 are equal to (

    V-

    V1 )

    where the currentsI1 and

    I1 enter the fault from the

    left and right respectively and impedancesZ1 and

    Z1

    are the total system impedances viewed from either sideof the fault branch. The voltage

    Vis equal to the open-

    circuit voltage in the system, and it has been shown thatV

    E

    E (see Section 3.7). So the positive sequence

    voltages in the system due to the fault are greatest at thesource, as shown in the gradient diagram, Figure 4.6(b).

    Figure 4.6

    4.3.2 Negative Sequence Network

    If only positive sequence quantities appear in a powersystem under normal conditions, then negative sequence

    quantities can only exist during an unbalanced fault.

    If no negative sequence quantities are present in the

    I

    V V

    Z=

    )( 11

    4

    Fault

    Calculations

    3 4

    Figure 4.6: Fault at F:Positive sequence diagrams

    (a) System diagramN

    F

    X

    N

    X

    F

    N'

    (b) Gradient diagram

    ZS1 Z'1

    Z'1

    Z'1

    Z''1

    I'1

    I'1

    I'1

    I1

    V1

    V1

    V'1+I'1Z'1

    V

    I''1

    E' E''

    Figure 4.5: Resolution of a systemof unbalanced vectors

    a2E2

    a2E1

    aE1

    aE2

    Eo

    Eo

    Eo

    E1

    E2

    Ea

    Eb

    Ec

  • 8/12/2019 net prot auton.pdf

    20/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 3 5

    fault branch prior to the fault, then, when a fault occurs,the change in voltage is

    V2 , and the resulting current

    I2

    flowing from the network into the fault is:

    Equation 4.5

    The impedances in the negative sequence network are

    generally the same as those in the positive sequencenetwork. In machines Z1 Z2 , but the difference is

    generally ignored, particularly in large networks.

    The negative sequence diagrams, shown in Figure 4.7, aresimilar to the positive sequence diagrams, with twoimportant differences; no driving voltages exist beforethe fault and the negative sequence voltage

    V2 is

    greatest at the fault point.

    Figure 4.7

    4.3.3 Zero Sequence Network

    The zero sequence current and voltage relationshipsduring a fault condition are the same as those in thenegative sequence network. Hence:

    V0 = -

    I0

    Z0Equation 4.6

    Also, the zero sequence diagram is that of Figure 4.7,substituting

    I0 for

    I2 , and so on.

    The currents and voltages in the zero sequence networkare co-phasal, that is, all the same phase. For zerosequence currents to flow in a system there must be areturn connection through either a neutral conductor orthe general mass of earth. Note must be taken of thisfact when determining zero sequence equivalent circuits.Further, in general

    Z1

    Z0 and the value of

    Z0 varies

    according to the type of plant, the winding arrangement

    and the method of earthing.

    I V

    Z2

    2

    2

    =

    4.4 EQUATIONS AND NETWORK CONNECTIONSFOR VARIOUS TYPES OF FAULTS

    The most important types of faults are as follows:

    a. single-phase to earth

    b. phase to phase

    c. phase-phase-earth

    d. three-phase (with or without earth)

    The above faults are described as single shunt faultsbecause they occur at one location and involve aconnection between one phase and another or to earth.

    In addition, the Protection Engineer often studies twoother types of fault:

    e. single-phase open circuit

    f. cross-country fault

    By determining the currents and voltages at the fault

    point, it is possible to define the fault and connect thesequence networks to represent the fault condition.From the initial equations and the network diagram, thenature of the fault currents and voltages in differentbranches of the system can be determined.

    For shunt faults of zero impedance, and neglecting loadcurrent, the equations defining each fault (using phase-neutral values) can be written down as follows:

    a. Single-phase-earth (A-E)

    Equation 4.7

    b. Phase-phase (B-C)

    Equation 4.8

    c. Phase-phase-earth (B-C-E)

    Equation 4.9

    d. Three-phase (A-B-C or A-B-C-E)

    Equation 4.10

    It should be noted from the above that for any type offault there are three equations that define the faultconditions.

    I I I

    V V

    V V

    a b c

    a b

    b c

    + + =

    =

    =

    0

    I

    V

    V

    a

    b

    c

    =

    =

    =

    0

    0

    0

    I

    I I

    V V

    a

    b c

    b c

    =

    =

    =

    0

    I

    I

    V

    b

    c

    a

    =

    =

    =

    0

    0

    0

    4

    Fault

    Calculations

    Figure 4.7: Fault at F:Negative sequence diagram

    (a) Negative sequence networkN

    F

    X

    F

    X

    N

    (b) Gradient diagram

    ZS1

    Z'

    1

    Z'1

    Z''1

    I'2

    I2

    V2

    V2

    V2 + I'2Z'1

    I''2

  • 8/12/2019 net prot auton.pdf

    21/23

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

    When there is a fault impedance, this must be taken intoaccount when writing down the equations. For example,with a single-phase-earth fault through fault impedanceZf, Equations 4.7 are re-written:

    Equation 4.11

    Figure 4.8

    4.4.1 Single-phase-earth Fault (A-E)

    Consider a fault defined by Equations 4.7 and by Figure4.8(a). Converting Equations 4.7 into sequencequantities by using Equations 4.1 and 4.2, then:

    Equation 4.12

    V1 = - (

    V2 +

    V0 ) Equation 4.13

    Substituting forV1 ,

    V2 and

    V0 in Equation 4.13 from

    Equations 4.4, 4.5 and 4.6:V-

    I1

    Z1 =

    I2

    Z2 +

    I0

    Z0

    but, from Equation 4.12,I1 =

    I2 =

    I0 , therefore:

    V=

    I1 (

    Z1 +

    Z2 +

    Z3) Equation 4.14

    The constraints imposed by Equations 4.12 and 4.14indicate that the equivalent circuit for the fault is

    obtained by connecting the sequence networks in series,as shown in Figure 4.8(b).

    4.4.2 Phase-phase Fault (B-C)

    From Equation 4.8 and using Equations 4.1 and 4.2:I1 = -

    I2 Equation 4.15

    I0 = 0V1 =

    V2 Equation 4.16

    From network Equations 4.4 and 4.5, Equation 4.16 canbe re-written:

    V-

    I1

    Z1 =

    I2

    Z2 +

    I0

    Z0

    I I I I o a1 21

    3= = =

    I

    I

    V I Z

    b

    c

    a a f

    =

    =

    =

    0

    0

    V-

    I1

    Z1 =

    I2

    Z2

    and substituting forI2 from Equation 4.15:

    V=

    I1 (

    Z1 +

    Z2 ) Equation 4.17

    The constraints imposed by Equations 4.15 and 4.17indicate that there is no zero sequence networkconnection in the equivalent circuit and that the positive

    and negative sequence networks are connected inparallel. Figure 4.9 shows the defining and equivalentcircuits satisfying the above equations.

    Figure 4.9

    4.4.3 Phase-phase-earth Fault (B-C-E)

    Again, from Equation 4.9 and Equations 4.1 and 4.2:I1 = -(

    I2 +

    Io) Equation 4.18

    andV1 =

    V2 =

    V0 Equation 4.19

    Substituting for V2 and V0 using network Equations 4.5and 4.6:

    I2

    Z2 =

    I0

    Z0

    thus, using Equation 4.18:

    Equation 4.20

    Equation 4.21

    Now equating V1 and V2 and using Equation 4.4 gives:V-

    I1

    Z1 = -

    I2

    Z2

    orV=

    I1

    Z1 -

    I2

    Z2

    Substituting forI2 from Equation 4.21:

    or

    Equation 4.22I V

    Z Z

    Z Z Z Z Z Z 1

    0 2

    1 0 1 2 0 2

    =+ )(

    + +

    V Z Z Z

    Z ZI= +

    +

    1

    0 2

    0 2

    1

    I Z I

    Z Z2

    0 1

    0 2

    = +

    I Z I

    Z Z0

    2 1

    0 2

    = +

    4

    Fault

    Calculations

    3 6

    Figure 4.8: Single-phase-earth fault at F

    (a) Definition of fault

    F

    C

    B

    A

    (b) Equivalent circuit

    Ia

    Ib

    VaF1

    N1

    N2 N0

    F2 F0

    Vb

    Vc

    Ic

    Ib =0

    Ic=0

    Va=0

    V

    Z1 Z2 Z0

    Figure 4.9: Phase-Phase fault at F

    (a) Definition of fault

    F

    C

    B

    A

    (b) Equivalent circuit

    Ia

    Ia=0

    Ib=-Ic

    Vb=-Vc

    Ib

    Ic

    F1

    N1

    N2 N0

    F2 F0

    Vb

    Va

    Vc

    V

    Z1 Z2 Z0

  • 8/12/2019 net prot auton.pdf

    22/23

    Types of busbar protection systems . . 15.4 . . . . . . . . 235

    Typical examples of timeand current grading,overcurrent relays . . . . . . . . . . . . . 9.20 . . . . . . . . 143

    U

    Unbalanced loading (negative sequence protection):- of generators . . . . . . . . . . . . . . 17.12 . . . . . . . . 293- of motors . . . . . . . . . . . . . . . . . 19.7 . . . . . . . . 346

    Underfrequency protectionof generators . . . . . . . . . . . . . . 17.14.2 . . . . . . . . 295

    Under-power protectionof generators . . . . . . . . . . . . . . 17.11.1 . . . . . . . . 293

    Under-reach of a distance relay . . 11.10.3 . . . . . . . . 187

    Under-reach of distance relayon parallel lines . . . . . . . . . . . . 13.2.2.2 . . . . . . . . 204

    Undervoltage (Power Quality) . . . . 23.3.9 . . . . . . . . 415

    Unit protection: . . . . . . . . . . 10.1-10.13 . . . . 153-169- balanced voltage system . . . . . . . 10.5 . . . . . . . . 156- circulating current system . . . . . . 10.4 . . . . . . . . 154- digital protection systems . . . . . . 10.8 . . . . . . . . 158- electromechanical protection

    systems . . . . . . . . . . . . . . . . . . 10.7 . . . . . . . . 156

    - numerical protection systems . . . .

    10.8 . . . . . . . .

    158- static protection systems . . . . . . . 10.7 . . . . . . . . 156- summation arrangements . . . . . . 10.6 . . . . . . . . 156

    Unit protection schemes:- current differential . . . . . . 10.4, 10.10 . . . . 154-160- examples of . . . . . . . . . . . . . . . 10.12 . . . . . . . . 167- multi-ended feeders . . . . . . . . . . 13.3 . . . . . . . . 207- parallel feeders . . . . . . . . . . . . 13.2.1 . . . . . . . . 204- phase comparison . . . . . . . . . . . 10.11 . . . . . . . . 162- signalling in . . . . . . . . . . . . . . . . 8.2 . . . . . . . . 113- Teed feeders . . . . . . . . . 13.3.2-13.3.4 . . . . 207-209

    - Translay . . . . . . . . . . . . 10.7.1, 10.7.2 . . . . 156-157- using carrier techniques . . . . . . . . 10.9 . . . . . . . . 160

    Unit transformer protection(for generator unittransformers) . . . . . . . . . . . . . . 17.6.2 . . . . . . . . 286

    Urban secondary distributionsystem automation . . . . . . . . . . . . 25.4 . . . . . . . . 447

    V

    Vacuum circuit breakers (VCBs) . . 18.5.5 . . . . . . . . 322

    Van Warrington formulafor arc resistance . . . . . . . . . . . . . 11.7.3 . . . . . . . . 177

    Variation of residual quantities . . . . 4.6.3 . . . . . . . . 42

    Vector algebra . . . . . . . . . . . . . . . . 3.2 . . . . . . . . 18

    Very inverse overcurrent relay . . . . . . 9.6 . . . . . . . . 128

    Vibration type test . . . . . . . . . . . . 21.5.5 . . . . . . . . 381

    Voltage and phase reversalprotection . . . . . . . . . . . . . . . . . 18.10 . . . . . . . . 327

    Voltage control using substationautomation equipment . . . . . . . . . . 24.5 . . . . . . . . 430

    Voltage controlled overcurrentprotection . . . . . . . . . . . . . . . . 17.7.2.1 . . . . . . . . 287

    Voltage dependent overcurrentprotection . . . . . . . . . . . . . . . . . 17.7.2 . . . . . . . . 287

    Voltage dips (Power Quality) . . . . 23.3.1 . . . . . . . . 413

    Voltage distribution due toa fault . . . . . . . . . . . . . . . . . . . . 4.5.2 . . . . . . . . 40

    Voltage factors for voltagetransformers . . . . . . . . . . . . . . . . 6.2.2 . . . . . . . . . 81

    Voltage fluctuations (Power Quality) . 23.3.6 . . . . . . . . 415

    Voltage limit for accurate reachpoint measurement . . . . . . . . . . . . 11.5 . . . . . . . . 174

    Voltage restrained overcurrentprotection . . . . . . . . . . . . . . . . 17.7.2.2 . . . . . . . . 287

    Voltage spikes (Power Quality) . . . 23.3.2 . . . . . . . . 413Voltage surges (Power Quality) . . 23.3.2 . . . . . . . . 413

    Voltage transformer: . . . . . . . . . 6.2-6.3 . . . . . . 80-84- capacitor . . . . . . . . . . . . . . . . . . 6.3 . . . . . . . . 83- cascade . . . . . . . . . . . . . . . . . . 6.2.8 . . . . . . . . 82- construction . . . . . . . . . . . . . . . 6.2.5 . . . . . . . . . 81- errors . . . . . . . . . . . . . . . . . . . 6.2.1 . . . . . . . . 80- phasing check . . . . . . . . . . . . 21.9.4.3 . . . . . . . . 389- polarity check . . . . . . . . . . . . 21.9.4.1 . . . . . . . . 388- ratio check . . . . . . . . . . . . . . 21.9.4.2 . . . . . . . . 389- residually-connected . . . . . . . . . 6.2.6 . . . . . . . . . 81- secondary leads . . . . . . . . . . . . . 6.2.3 . . . . . . . . . 81- supervision in distance relays . . 11.10.7 . . . . . . . . 188- supervision in numerical relays . . . 7.6.2 . . . . . . . . 108- transient performance . . . . . . . . 6.2.7 . . . . . . . . 82- voltage factors . . . . . . . . . . . . . 6.2.2 . . . . . . . . . 81

    Voltage unbalance(Power Quality) . . . . . . . . . . . . . 23.3.7 . . . . . . . . 415

    Voltage vector shift relay . . . . . . 17.21.3 . . . . . . . . 307

    WWarrington, van, formulafor arc resistance . . . . . . . . . . . . . 11.7.3 . . . . . . . . 177

    Index

    N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e 4 9 6

    Section Page Section Page

  • 8/12/2019 net prot auton.pdf

    23/23

    Wattmetric protection, sensitive . . 9.19.2 . . . . . . . . 142

    Wound primary currenttransformer . . . . . . . . . . . . . . . . 6.4.5.1 . . . . . . . . 87

    ZZero sequence equivalent circuits:- auto-transformer . . . . . . . . . . . 5.16.2 . . . . . . . . 60- synchronous generator . . . . . . . . 5.10 . . . . . . . . 55- transformer . . . . . . . . . . . . . . . . 5.15 . . . . . . . . 57

    Zero sequence network . . . . . . . . . 4.3.3 . . . . . . . . 35

    Zero sequence quantities,effect of system earthing on . . . . . . . 4.6 . . . . . . . . . 41

    Zero sequence reactance:- of cables . . . . . . . . . . . . . . . . . . 5.24 . . . . . . . . 69

    - of generator . . . . . . . . . . . . . . . 5.10 . . . . . . . . 55- of overhead lines . . . . . . . . 5.21, 5.24 . . . . . . 66-69- of transformer . . . . . . . . . . 5.15, 5.17 . . . . . . 57-60

    Zone 1 extension scheme(distance protection) . . . . . . . . . . . 12.2 . . . . . . . . 194

    Zone 1 extension scheme inauto-reclose applications . . . . . . . 14.8.2 . . . . . . . . 226

    Zones of protection . . . . . . . . . . . . . 2.3 . . . . . . . . . 8

    Zones of protection,

    distance relay . . . . . . . . . . . . . . . .

    11.6 . . . . . . . .

    174

    Index

    Section Page Section Page


Recommended