NET ZERO STUDY ON A COMMUNITY COLLEGE
By: Amanda O’Connell Doenges
My Background
University of Dayton Bachelor’s in Mechanical
Engineering Masters in Renewable and
Clean Energy Heapy Engineering – LEED
& Energy Services Energy Master Plan for
Sinclair Community College
Sinclair Pre-2004
Proactive campus Facilities department – energy aware IT development
Added monitors, projectors, etc. to classrooms and offices
What was already done
T12 to T8 lighting retrofits LED lighting CRT to LCD computer monitors De-lamping of exterior lighting Variable frequency drives to all air and
water side systems Addition of return air to 100% outside air
systems
House Bill 251
20% energy reduction by 2014 (compared to 2004)
Net-Zero?
HB 251 is a good first goal Possibility of going beyond 20%
reduction Steps:
Decrease current energy consumption Renewable Energy
Renewable Energy
Large Flat Roof Areas – Solar PV 2,200 MWh/year – could produce Current consumption at 300,000 MWh/year
(only electric) Low Velocity Wind Turbine
Utility Analysis + Benchmarking Campus Energy Use Intensity: 134
kBtu/sf Commercial Building Energy
Consumption Survey (CBECS) Database: 120 kBtu/sf
Campus density factor? Average Campus: 250-450 users per
100,000 GSF Urban Campus: 550-750 users per 100,000
GSF Sinclair: 970 users per 100,00 GSF Using Urban Campus Average = 179
kBtu/sf
Year to Year Comparison
Square Footage Occupants Weather (CDD and HDD) All
Energy Conservation Measures Daylight Harvesting
Occupancy Sensors
Revise Temperature Set Points to 75F and 70F
Energy Conservation Measures PC Automatic Shutoff
Energy Conservation Measures Vending Miser Exterior Lighting Controls
Energy Conservation Measures
Boiler Retrofits Very high base load natural gas
consumption Central boilers – DHW and Summer Reheat
Summer Boiler or Heat Recovery Chiller Boiler Plant Upgrades (Parallel positioning)
16%+ overall energy reduction through boiler replacements/retrofits
Retro-Commissioning
Identifies operational issues
Original design intent Lawrence Berkeley
National Laboratory Study 5-15% savings in total
building energy use Commission all new
buildings
Photo courtesy of CTG Energetics, Inc.
Next Steps
Energy Conservation Measures and Retro-Cx will help to move towards 20%, but will not be Net Zero
Future: Retro-Commissioning Energy Metering Sustainability Coordinator Education Renewable Energy
Energy Metering
Meter each building individually Sub meter large energy consuming
processes Lighting Ventilation Heating Cooling Plug Loads
ASHRAE Journal – April 2011 – 1-20% savings
Sustainability Coordinator
Individual or a firm Directly under a President or VP Position strictly focused on campus
energy and/or sustainability Education to address energy related
behavioral changes
Summary
Short Term Energy Savings Energy Conservation Measures + Retro-Cx Campus Awareness
Long Term Plan Capital Improvements Energy Metering Sustainability Coordinator Education Renewable Energy
Amanda O’Connell Doenges