Date post: | 03-Apr-2018 |
Category: |
Documents |
Upload: | anwar-syed |
View: | 214 times |
Download: | 0 times |
of 63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
1/63
NFPA20
Standard for the Installation of Stationary Pumps for Fire Protection
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
2/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
3/63
Codes and Standards
National Fire Protection Association -NFPA Establishes the norms that governs all fire
installation Continuously revises the codes (Last issue
2003)
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
4/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
5/63
Codes and Standards
NFPA Philosophy A fire pump system should operate irrespective
of any damage it may cause to itself
No element of the system under emergencyconditions should:
Prevent a fire pump from turning onCause a fire pump to turn off
Changes to the code must be substantiated bydata or experience (actual scenarios)
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
6/63
Codes and Standards
NFPA20 Structure: Definitions (3 pages) Centrifugal Fire Pumps (5 pages)
Positive Displacement Pumps (2 pages) Electric Motors (1 page) Diesel Engines (4 pages)
Controllers (12 pages) Pump Installation and RelatedComponents (10 pages)
Acceptance Tests and Maintenance (2pages)
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
7/63
Water Supply Where fire pumps are installed on a city main, a fire
flow test should be performed to determineminimum and maximum supply pressures as wellas suitability of supply for the fire protection system
Where adequate city supply water is unavailable, asuction tank or pit should be installed
Tank sizing must consider 150% of the fire pumprated flow
Total water requirements are defined in NFPA13(Sprinkler Systems), NFPA14 (Standpipe Systems),NFPA15 (Spray or Mist Systems), Mains)
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
8/63
Pump RequirementsCentrifugal fire pumps shall be listed for
fire protection service.
Pumps shall furnish not less than 150% of rated capacity at not less than 65% of total rated head. The shutoff head shallnot exceed 140% of rated head for any
type pump.
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
9/63
Pump Requirements
100% 150%
140%100%65%
%Rated Head
%Rated Flow
Max Shutoff Head
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
10/63
Pump SizingA stationary pump for fire protection should be
selected in the range of operation from 90percent to 150 percent of its rated capacity. Theperformance of the pump when applied atcapacities over 140 percent of rated capacity can
be adversely affected by the suction conditions. Application of the pump at capacities less than90 percent of the rated capacity is notrecommended. The selection and application of the fire pump should not be confused with pumpoperating conditions. With proper suctionconditions, the pump can operate at any point onits characteristic curve from shutoff to 150percent of its rated capacity.
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
11/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
12/63
Misinterpreted CodeRequirement
Sizing the fire pump - a listed pump shouldbe applied for flows from 90% to 150% of its rated point
Most fire pumps are sized to exceed theduty requirement of the fire protectionsystem
The rated flow is a convention used toregulate the listing of pumps
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
13/63
Pump Requirements
FM & UL require that fire pumps havepacking sealsULC allows mechanical sealsPacking requires periodic adjustment andreplacement as it hardens over time
The packing gland should be tighteneduntil the seal leaks 30 drips per minuteIf the gland is tightened to much, the sealreceives no lubrication and will burn
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
14/63
Allowable PumpTypes
Horizontal Split Case Vertical In-Line
End Suction Vertical Turbine
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
15/63
Horizontal Split Case FirePumps
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
16/63
HSC Fire Pumps
BENFITS Available in a wideflow and head range
Serviceable without
disturbing piping or driver Available in electric
or diesel drive
DRAWBACKS Large floor spacerequirement
Restricts mechanical
room layout due todirection of rotation More costly More difficult to
service
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
17/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
18/63
VIL Fire PumpsBENEFITS Compact Serviceable Reliable
Cost Effective
DRAWBACKS Only available up to
1500GPM Electric Drive Only Requires suction
strainer
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
19/63
End Suction Fire Pumps
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
20/63
End Suction Fire Pumps
BENFITS Moderate floor spacerequirement
Flexibility in
mechanical roomlayout Available in electric
or diesel drive
Serviceable
DRAWBACKS Only available up to1500gpm
Single suction
design limitshydraulic efficiency
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
21/63
Vertical Turbine FirePumps
Used where aflooded suction
cannot bemaintainedUnderground water sources or belowground tanks withabove ground pumproom
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
22/63
Vertical Turbine Fire
PumpsBENFITS Will operate under
suction lift Available in electric
or diesel drive Available over wide
flow and head range
DRAWBACKS More costly
More difficult toservice and install
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
23/63
Typical ApplicationWet Pit - Electric
Motor Driver
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
24/63
Typical ApplicationWet Pit - Diesel Engine Driver
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
25/63
Suction &DischargeGauges Air Release
Valve
Pressure Relief Valve three pressureranges adjustable on site
NFPA RequiredPump Accessories
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
26/63
Suction gauge must be of the compound type (capableof reading negative pressureor vacuum)Discharge gauge must readtwo times the workingpressure of the pump andnot less than 200psi
NFPA RequiredPump Accessories
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
27/63
1/2 Air Release Valve isrequiredException: top centre-line
discharge end suction andvertical fire pumps
Air Release Valve
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
28/63
3/4 up to 2500usgpm1 over 3000usgpmShould be set between themaximum suction pressure andminimum suction pressure plusthe closed valve pressure of thepump
Piped before the fire pumpdischarge check valve
Casing Relief Valve
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
29/63
Suction OS&Y Gate Valve Discharge Butterfly Valve Both must be supervised Discharge Butterfly Valve
Installed after Test Teeand pressure sensing line
Isolation Valves
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
30/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
31/63
Hose Valve Systems
Provides testing means Sized by pump rated
capacity
There are hundreds of different thread typesdepending on jurisdiction- type should bespecified on projects
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
32/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
33/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
34/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
35/63
Main Relief Valves
and Waste Cones Sized by pump ratedcapacity
Spring or pilot operated Waste cone provides
visibility of flow throughthe valve
When it is used:1) Diesel driven systems
2) Electric systems ???
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
36/63
Main Relief Valve -Diesel Pumps
1000
30
165
130
psi
GPM
Shutoff Head
@ Rated Speed
20
1500
Shutoff Head@ 10% Overspeed179
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
37/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
38/63
Main Relief Valve -Electric Pumps
1000
60
180
130
psi
GPM
Max Shutoff Head
20
1500
Rated Head
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
39/63
Misinterpreted CodeRequirement
Devices in the discharge piping - mainrelief or pressure reducing valves shouldonly be installed where absolutely
necessary Valves introduce a failure mode and
should only be used when required
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
40/63
Piping, Relief Valves, Metering Devices, andHose Valves should be sized according to
Table 2-20 on Page 20-13.
NFPA Fitting Sizing
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
41/63
NFPA RequiredPump AccessoriesFire Pump Rating
GPM (L/s)Suction
Size (in.)DischargeSize (in.)
Relief ValveSize (in.)
Relief ValveDischarge
(in.)
Flow Meter Size (in.)
Number &Size of Hose
Valves
Hose ValveManifoldSize (in.)
25 (95) 1 1 1 1 1 - 1 150 (189) 1 1 1 1 2 1 - 1 1100 (379) 2 2 1 2 2 1 - 2 2150 (568) 2 2 2 2 3 1 - 2 2200 (757) 3 3 2 2 3 1 - 2 2
250 (946) 3 3 2 2 3 1 - 2 3300 (1136) 4 4 2 3 3 2 - 2 3400 (1514) 4 4 3 5 4 2 - 2 4450 (1703) 5 5 3 5 4 2 - 2 4500 (1892) 5 5 3 5 5 2 - 2 4
750 (2839) 6 6 4 6 5 3 - 2 61000 (3785) 8 6 4 8 6 4 - 2 61250 (4731) 8 8 6 8 6 6 - 2 81500 (5677) 8 8 6 8 8 6 - 2 82000 (7570) 10 10 6 10 8 6 - 2 8
2500 (9462) 10 10 6 10 8 8 - 2 103000 (11,355) 12 12 8 12 8 12 - 2 10
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
42/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
43/63
Jockey PumpsJockey (pressure maintenance) pumps and
jockey controllers need not be listed for fireprotection service.
The primary or standby fire pump shall not beused as a pressure maintenance pump.
A jockey pump should be sized such that itCANNOT meet the flow demand of a singlesprinkler fixture.
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
44/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
45/63
Fire Pump Operation Fire pumps are designed to start on a
pressure switch setting Some fire pumps can be started automatically
based on a deluge valve opening, or a remotesignal
The pressure sensing line is the lifeline for thefire protection system
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
46/63
Fire Pump Operation Pressure switches should be rated for maximum
pressure conditions Sensing lines must be 1/2 non -ferrous (copper)
with two check valves with a 3/32 hole drilled in the
flapper Check valves are for damping of pressure when thepump starts to protect the pressure switch
Check valves are installed 5 feet apart and mustopen on a pressure drop in the sensing line
Check valves close when the pump starts Jockey pump and fire pump sensing lines must be
separate
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
47/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
48/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
49/63
System gradually loosespressure
50
9095100
110
Jockey startFire Pump start
Stop PointPump shutoff
psi
Time period
boost
Fire Pump Operation
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
50/63
Critical New Code Requirements(2003)
Extensive changes to NFPA20 includingchapter numbers
Fire pump sizing will move from the
Appendix to the main text of the code Greater clarity on devices in the discharge
piping
Provisions for the acceptance of electronicspeed governors on diesel engines Reference to NEMA ICS 14-2001 as
Appendix B (Application Guide for ElectricFire Pump Controllers)
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
51/63
Critical New Code Requirements(2003)
Diesel tank supervision and markings Alternate valve arrangement for diesel
cooling lines
Provision for reading amperage andvoltage on limited service controllers
Variable speed drivers as pressure limiting
devices Copper lines and fittings not allowed for
diesel piping
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
52/63
Typical System Performance - 500gpm, 160psiincluding 85psi Suction Pressure
100
110
120
130
140
150
160
170
180
190
200
210
220
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800
Flow - GPM
H e a
d -
P S I
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
R P M
PLT OFF 85psi SuctPLT ON 85psi SuctPLT ON 85psi RPMPLT OFF 85psi RPM
System PressureLimit
Pressure LimitingControl Range
RPM
System Pressure
RPM
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
53/63
FIRE PUMP CONTROLLERS
Diesel or ElectricFull Service or Limited Service
HP of the motor Voltage of the installationWithstand rating
Starting method
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
54/63
Across the Line Limited Service - Under 30hp Full Service
Reduced Voltage Auto Transformer Wye Delta - Special Motor
Required Part Winding - Special Motor
Required
Primary Resistor
CONTROLLER STARTING METHOD
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
55/63
CONTROLLER STARTING METHOD600
% of FullLoad
Current
Full speed
390
252200
FULL VOLTAGE
PRIM.RESISTOR
PART WINDING
AUTO-TRANSFORMER
WYE DELTA
FULL LOADCURRENT
420
100
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
56/63
AUTOMATIC TRANSFERSWITCHES
What is it? An additional controller used
in case of a power failure
Why use it? To transfer the power toanother source (generator or diesel)
When to use it? If Authorities Require One If Power Source not Reliable
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
57/63
Serve Three Basic Functions : Start the Diesel Engine in an emergency Monitor the Operation and Condition of the
Diesel Engine Keep the batteries charged
DIESEL CONTROLLERS
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
58/63
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
59/63
Diesel Can be Stopped by TwoMethods : Manually by Pushing the Stop Button
Automatically after 30 minutes duringweekly test
Overspeed shutdown:
A diesel fire pump will shut down in anemergency condition if the diesel operatesmore than 20% faster than the ratedspeed
DIESEL CONTROLLERS
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
60/63
Diesel Controller Alarms Battery and Charger Failures Diesel operating condition (High Coolant
Temperature, Low Oil Pressure, Overspeed,Failure to Start) Contacts for remote indication of alarm
conditions Optional Pump Room Alarms (Low suction
pressure, flow meter on, Main Relief Valveopen, Low/High Pump Room temperature, Low
fuel level, Others )
DIESEL CONTROLLERS
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
61/63
Pump Maintenance
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
62/63
Pump MaintenancePump acceptance tests are defined in NFPA20
Chapter 11Inspection and maintenance are defined in NFPA25Chapter 5Seals and bearings are the highest maintenance itemfor a pumpThe packing should be checked and adjusted eachtime the pump is tested
As fire pumps do not run often, bearings should bechecked for cleanliness and to ensure that adequateoil or grease has been applied (depending on the typeof bearing)Motor bearin s should also be checked
7/27/2019 nfpa20presentationfirepumps-120904080550-phpapp02 (1)
63/63