"Auburn University is a Smoke-Free Campus" T-001 1 OF SHEET TITLE D R A W I N G I N D E X 2 OF 3 OF SHEET NUMBER SEQUENCE NUMBER 7 SITE PLAN TITLE SHEET COVER SHEET G-001 C-101 7 7 SHEET TITLE SHEET NUMBER SEQUENCE NUMBER PLUMBING PLAN, LEGENDS, NOTES P-100 5 OF 7 E-100 7 OF 7 D R A W I N G I N D E X 4 OF FLOOR PLAN / FOUNDATION PLAN AND DETAILS A-101 7 ELECTRICAL SITE PLAN E-001 6 OF 7 ELECTRICAL - LEGENDS AND NOTES VICINITY MAP LOCATION MAP "Safety is our first priority. Think Safety. Act Safely." Before you dig call ... Auburn University Work Management (334) 844-4357 Auburn University Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 (334) 844-4810 Fax: (334) 844-9458 Alabama Building Commission Project Number: 2017555 Auburn University Project Number: 16-484 Bid Set Date: 17 November 2017 FACILITIES MANAGEMENT University Project Lead: David Bess, RA, NCARB, Campus Architect Project Architect:Foil Wyatt Architects and Planners PLLC Project Engineers and Consultants: Edmonds Engineering North Auburn - New Fisheries Chemical Storage Building f o E T A T S A L A B A M A D E R E T S I G E R T C E T I H C R A 6763 E. E W Y A T MS JACKSON, B O W D N T Architects & Planners, PLLC SUITE 400 1510 NORTH STATE STREET JACKSON, MS 39202-1647 TELEPHONE: FAX: EMAIL: WEB: 601-352-3071 601-352-3078 [email protected] www.foilwyatt.com sheet no. of Facilities Management 1161 West Samford Avenue Auburn University, AL 36849 Phone: (334) 844-4810 Fax: (334) 844-9458 Safety is our first priority. Think Safety. Act Safely. Revision No. Date AU Project 16-484 North Auburn - New Fisheries Chemical Storage Building Schematic Phase 05/24/16 DLC 12-18-2017 - 16-494 DRAWN BY: CHECKED BY: FILE NUMBER: PROJECT NUMBER: SHEET NUMBER: SHEET TITLE: DATE: ABC 12/18/17 EBW T-001 COVER SHEET N PROJECT LOCATION N PROJECT LOCATION
Transcript

"Auburn University is a Smoke-Free Campus"

T-001 1 OF

SHEET TITLE

D R A W I N G I N D E X

2 OF

3 OF

SHEET NUMBER SEQUENCE NUMBER

7

SITE PLAN

TITLE SHEET

COVER SHEET

G-001

C-101

7

7

SHEET TITLE SHEET NUMBER SEQUENCE NUMBER

PLUMBING PLAN, LEGENDS, NOTES P-100 5 OF 7

E-100 7 OF 7

D R A W I N G I N D E X

4 OFFLOOR PLAN / FOUNDATION PLAN AND DETAILS A-101 7

ELECTRICAL SITE PLANE-001 6 OF 7ELECTRICAL - LEGENDS AND NOTES

VICINITY MAP LOCATION MAP"Safety is our first priority. Think Safety. Act Safely."

Before you dig call ...

Auburn UniversityWork Management

(334) 844-4357

Auburn UniversityFacilities Management

1161 West Samford AvenueAuburn University, AL 36849

(334) 844-4810 Fax: (334) 844-9458

Alabama Building Commission Project Number: 2017555Auburn University Project Number: 16-484

Bid Set Date: 17 November 2017

FACILITIES MANAGEMENT

University Project Lead: David Bess, RA, NCARB, Campus ArchitectProject Architect:Foil Wyatt Architects and Planners PLLCProject Engineers and Consultants: Edmonds Engineering

North Auburn - New Fisheries Chemical Storage Building

foETATS

ALABAMA

DERETSIG

ER T

CE

TIHCRA

6763

E.

E WYAT

MSJACKSON,

BOWD N

T

Arc

hite

cts &

Plan

ners

, PLL

CSU

ITE

400

1510

NO

RTH

STA

TE S

TREE

TJA

CKSO

N, M

S 3

9202

-164

7TE

LEPH

ON

E:FA

X:

EMA

IL:

WEB

:

601-

352-

3071

601-

352-

3078

fwjac

kson

@fo

ilwya

tt.co

mw

ww.fo

ilwya

tt.co

m

sheet no.

of

Facilities Management1161 West Samford Avenue

Auburn University, AL 36849Phone: (334) 844-4810

Fax: (334) 844-9458Safety is our first priority.Think Safety. Act Safely.

RevisionNo. Date

AU Pr

oject

16-48

4 Nort

h Aub

urn -

New

Fishe

ries C

hemi

cal S

torag

e Bu

ilding

Schematic Phase 05/24/16

DLC

12-18-2017

-

16-494

DRAWN BY:

CHECKED BY:

FILE NUMBER:

PROJECT NUMBER:

SHEET NUMBER:

SHEET TITLE:

DATE:

ABC 12/18/17

EBW

T-001

COVER SHEET

N

PROJECT LOCATION

N

PROJECT LOCATION

NORTH

TITLE

100

1

A

1

101

SCALE:

1A1.1

1

100

XX

100.0

100.0

G

S

E

W

G

S

E

W

1A0.1

1A1.1

1A1.1

1A1.1

1A0.1

GLASS BLOCK

MTL. ROOF

FACE BRICK #2

BRICK

CMU

FACE BRICK #1

MATERIALS, ELEVATION

MATERIALS, PLAN/SECTION

CONCRETE/PLASTER

WOOD, ROUGH (INTERRUPTED)

WOOD, FINISHED

PLYWOOD

METAL, SMALL SCALE

METAL, LARGE SCALE

INSULATION, RIGID

INSULATION, BATT

CONCRETE MASONRY UNITS

CONCRETE

MILLWORK

WOOD, ROUGH (CONTINUOUS)

SUSPENDED

STRUCTURAL

SPECIFICATIONS

TOP AND BOTTOMTONGUE AND GROOVE

TOOLED JOINT

TOP OF WALL

TOILET PAPER DISPENSER

TOP OF INLET

TOP OF CURB

TACK BOARDTILE BACKER BOARDTOWEL DISPENSERTOWEL DISPENSER ANDWASTE RECEPTACLE

TOP OF CONCRETETOP OF DECKTOP OF FOOTING

TOP OF PAVEMENTTOP OF STEELTOP OF WALL

WALL GUARD

WELDED WIRE FABRICWATERPROOF

WATER HEATERWIRE GLASS

WATER CLOSET

VINYL COMPOSITION TILE

VERIFY ON JOB

WELDED WIRE MESH

STN STAIN

D/V DATA/VOICE

N

P POWER

REF

REQ'DREINFREF

ROOM

RETREV

RH

ROROW

RM

S

RESIL

SOUTH (OR SWITCH)

ROUGH OPENING

RESILIENTREQUIREDREINFORCEDREFRIGERATORREFERENCE

RETURNREVISION

RIGHT HAND

RIGHT OF WAY

SHELF

SCHEDSCD

SH

SF

SHR

SECT

SIMSHTG

SPEC

SNDSNW

SHT

STEEL

SQ

STOR

STL

SUSP

SUBFLSURF

T&BT&G

STRLSTORAGE

SQUARE

SIMILAR

SHEETSHOWER

SECTIONSCHEDULESEAT COVER DISPENSER

SQUARE FEET

SHEATHING

SANITARY NAPKIN DISPENSERSANITARY NAPKIN WASTERECEPTACLE

SUBFLOORSURFACE

TB

TDTBB

TDW

TCTEL

THICKTHKTJ

TOCTOD

TITHRESH

TOFTOILTOPTOSTOW

VINYL

TV

TRDTRTD

VTYPTOW

TPD

TYPICAL

TELEVISION

THRESHOLDTELEPHONE

TREAD

TOILET

TREATED

VESTVERTVCT

VCTVOJ

WEST

WOOD

WITHW

WDWC

WIN

W/

W/OWHWGL

WPWWFWWM

WG

WITHOUT

VESTIBULEVERTICAL

VINYL COMPOSITE TILE

WINDOW

VARIESVAR

KITCHENKICK PLATEKNEE SPACE

KITKPKS

LINTEL

POUNDSLAVATORYLAMINATE

LEFT HAND

LIGHTLIGHT WEIGHT

MACHINEMAINTENANCE

LOCKERLINT

LBSLAVLAM

LHLHR

LTWTLT

LSG

MACHMAINT

LKR

EQUIPMENTEQUALELECTRICAL PANEL

EXTERIOREXPANSIONEXISTINGEXHAUST

FLOOR DRAIN

FIRE ALARM

FIBER BOARD

EXISTING TO REMAIN

FIRE DEPARTMENT CONNECTION

EPEQ

EXH

EXTEXP

FA

FDFBD

AT

& OR

@

A/C

#

ADJACT

ALTAHU

APAPPROX

ALUM

AGGR

ANOD

AFF

APPROXIMATE

ALUMINUMALTERNATE

ADJUSTABLEABOVE FINISHED FLOOR

ACOUSTICAL CEILING TILEAIR CONDITIONING

POUND OR NUMBERDIAMETER OR ROUNDCENTERLINE

ANGLEAND

AGGREGATEAIR HANDLING UNIT

ANODIZEDACCESS PANEL

EQUIP

EXIST

ETR

FDC

MAXIMUM

MASONRYMATERIAL

MARKER BOARD

MINIMUMMIRRORMISCELLANEOUS

MANHOLEMANUFACTURER

MECHANICALMEMBRANE

MAX

MASMAT

MBMDF

MISCMIRMINMH

MECH

MFRMEMB

METAL

NORTH

MULLION

MOUNTED

ON CENTER

NOT TO SCALENOMINALNUMBER

N

NIC

MUL

MNTDMO

MTL

ODOC

NTSNOMNO

FINISH

OWNER

FIRE HOSE CABINETFIRE HYDRANT

FIRE EXTINGUISHER CABINETFIRE EXTINGUISHERFOUNDATION

FACTORY FINISH

CONTRACTOR

FLOORTENANT

FREEZERFOOT OR FEET

FACE OF STUDS

FACE OF CONCRETE

FLUORESCENTFACE OF BRICK

FACE OF FINISHFACE OF MASONRY

FIREPROOFING

FURNISHED AND INSTALLED BY

FURNISHED AND INSTALLED BY

FURNISHED AND INSTALLED BY

OFFICE

OPPOSITEOPENINGOPPOSITE HAND

PERFORATED

PRECAST

OPPOPNG

OFFOFD

OH

OSB

PERF

PAPCPCD

PLATEPHASE

PLYWOODPLASTER

PAIR

PROJECTION

PREFABRICATEDPRECAST

PUSH PLATEPLYWDPLASPLAMPLPH

PSFPROJ

PREFABPRCSTPRPP

FURRING

FOOTING

FUTURE

GRAB BAR

GAUGEGAS

GENERAL CONTRACTOR

GALVANIZED

FURNISHED BY TENANT,INSTALLED BY CONTRACTORFURNACE/FURNISH

GARBAGE DISPOSALGLASS FIBER REINFORCED

GLASS

CONCRETE

GYPSUM

PLASTER

HOSE BIBB

GYPSUMGYPSUM BOARD

GLASS FIBER REINFORCED

GLASS FIBER REINFORCED

GLUE-LAMINATED WOODGYPSUM WALL BOARD

FEFDN

FHFF

FIC

FIN

FIT

FL

FTFRZFP

BDBC

ARCH

BLKBLDG

BOTBLKNG

BRG

BITUM

B/UBSMT

CBCAP

CGCH

CORNER GUARDCATCH BASIN

BOTTOMBLOCKINGBLOCKBUILDING

BOARDBOTTOM OF CURB

ARCHITECTURAL

BITUMINOUS

BEARINGBASEMENTBUILT-UP

CAPACITY

COAT HOOK

FTG

FUT

GAG

GCGD

GB

GL

GYP

HB

CJCHRL

CLKGCLG

CLOS

CMUCOCOLCONCCOND

CLR

CTCPTCORR

CONTCOORD

DTLDBLD

DETAILDOUBLE

CERAMIC TILECARPETCORRIDOR

CONTINUOUS

CONCRETE

CONCRETE MASONRY UNIT

COLUMNCASED OPENING

CLEARCLOSETCAULKINGCEILINGCONTROL JOINTCHAIR RAIL

CONDITION

COORDINATE

CLOTHES DRYER

GYP BD

GALV

FURR

FOS

FOC

FLUOR.

FHC

FEC

FIO

FOB

FOFFOM

FTIC

FURN

GFRC

GFRG

GFRP

GLAMGWB

PAINTED

PARTITION

QUARRY TILE

PAVEMENT

QUARTER

PTRPTN

PTD/RPTDPTD

QT

PVCPVMT

QTR

ROOF DRAIN

RUBBER BASE

RECEPTIONRDRCPRB

RAG

RECEP

RADIUSRAD

HEIGHT

HANDRAIL

& AIR CONDITIONINGHEATING/VENTILATING

HORIZONTALHOLLOW METAL

HARDBOARD

INSULATIONINTERIOR

JANITOR

INVERT

INCHES

JOINTJOIST

INSULATING GLASSINSIDE DIAMETER (DIA.)

HGTHM

HR

IGIN

INT

JAN

INV

JNTJST

ID

DIFF

DNDISPDIM

DRDP

DWGDWR

DW

DS

EEAEBEDF

ELECEJ

ELEV

ELECTRIC DRINKING FOUNTAIN

ELECTRICALEXPANSION JOINT

EACHEAST

DRAWING

DOWNSPOUT

DRAWER

DOORDAMPPROOFINGDOWNDISPENSERDIMENSIONDIFFUSER

DISHWASHER

EXPANSION BOLT

ELEVATOR/ELEVATION

INSUL

HVAC

HORIZ

HDBDHANDICAP

DIAMETER

PSI

HCP

DIA

REINFORCED CONCRETE PIPE

RETURN AIR GRILLE

POLY VINYL CHLORIDEPAPER TOWEL RECEPTACLE

DISPENSER AND RECEPTACLECOMBINATION PAPER TOWELPAPER TOWEL DISPENSER

POUNDS PER SQUARE INCHPOUNDS PER SQUARE FOOT

PLASTIC LAMINATE

OUTSIDE DIAMETER (DIA.)

NOT IN CONTRACT

MASONRY OPENING

LEFT HAND REVERSE

LAMINATED SAFETY GLASS

MEDIUM DENSITY FIBERBOARD

OVERFLOW DRAIN

ORIENTED STRAND BOARD

PUBLIC ADDRESS

PAPER CUP DISPENSER

FB FIRE BLANKET

VENT THRU ROOFVTR

EXHAUST FANEF

PREFIN PRE-FINISHED

ERD EMERGENCY ROOF DRAIN

RDL ROOF DRAIN LEADER

SF STOREFRONT

VENT JOINTVJ

STD STANDARDSTAINLESS STEELST/ST

PAINTED GYPSUM BOARDPGB

PORCELAIN TILEPT

C

A

OFFICE

1/A-701

101

North Auburn - New Fisheries Chemical Storage Building

AU Project 16-484

INDICATES DETAIL NUMBER

INDICATES SHEET NUMBERON WHICH DETAIL IS SHOWN

INDICATES PARTITION TYPE

INDICATES WINDOW NUMBER

INDICATES DOOR NUMBER

INDICATES ROOM NUMBER

INDICATES ROOM NAME

INDICATES ELEVATION NUMBER

INDICATES ELEVATION SHOWN

INDICATES SHEET NUMBERON WHICH DETAIL IS SHOWN

INDICATES DETAIL NUMBER

INDICATES SHEET NUMBERON WHICH DETAIL IS SHOWN

INDICATES DETAIL NUMBER

INDICATES SHEET NUMBER ONWHICH SECTION IS SHOWN

INDICATES SECTION NUMBER

INDICATES SHEET NUMBER ONWHICH SECTION IS SHOWN

INDICATES SECTION NUMBER

COLUMN LINES

PARTITION TYPE

WINDOW TYPE

DOOR TYPE

ROOM IDENTIFICATION

INTERIOR ELEVATIONS

DETAIL

DETAIL

WALL SECTION

BUILDING SECTION

WORK POINT,CONTROL POINT ORDATUM POINT

REVISION

NORTH ARROW

PROPERTY LINE

EXISTING CONTOURS

NEW CONTOURS

EXISTING ELEVATION

NEW ELEVATION

FENCE LINE

GAS LINE

SEWER LINE

ELECTRIC LINE

WATER LINE

GRAPHIC SYMBOLSDESIGNATIONS

ABBREVIATIONS

foETATS

ALABAMA

DERETSIG

ER T

CE

TIHCRA

6763

E.

E WYAT

MSJACKSON,

BOWD N

T

Arc

hite

cts &

Plan

ners

, PLL

CSU

ITE

400

1510

NO

RTH

STA

TE S

TREE

TJA

CKSO

N, M

S 3

9202

-164

7TE

LEPH

ON

E:FA

X:

EMA

IL:

WEB

:

601-

352-

3071

601-

352-

3078

fwjac

kson

@fo

ilwya

tt.co

mw

ww.fo

ilwya

tt.co

m

sheet no.

of

Facilities Management1161 West Samford Avenue

Auburn University, AL 36849Phone: (334) 844-4810

Fax: (334) 844-9458Safety is our first priority.Think Safety. Act Safely.

RevisionNo. Date

AU Pr

oject

16-48

4 Nort

h Aub

urn -

New

Fishe

ries C

hemi

cal S

torag

e Bu

ilding

Schematic Phase 05/24/16

DLC

12-18-2017

-

16-494

DRAWN BY:

CHECKED BY:

FILE NUMBER:

PROJECT NUMBER:

SHEET NUMBER:

SHEET TITLE:

DATE:

ABC 12/18/17

EBW

G-001

TITLE SHEET

ARCHITECT

FOIL WYATT ARCHITECTS & PLANNERS, PLLC1510 NORTH STATE STREET - SUITE 400

JACKSON, MS 39202T: (601) 352-3071

F: (601) 352 - [email protected]

MECHANICAL AND ELECTRICAL ENGINEERS

Edmonds Engineering2 Riverchase Office Plaza

Suite 205 Hoover, AL 35244 (o) 205.988.2069

www.edmondsengineering.com

REF.

T

S S

D

S

S

1"PVC

WCNAU2302

WUNAU2302

WUNAU2303

WV U23 06

WV U23 07

TEMP1"PVC

4"DI DOM

4"DI DOM.

6"DI

6"DI

4"DI FIRE

4"DI DOM.

6"DI

2"

4"PVCCAPPED

4"PVC LAKE WATER FEED

SSMH U23 03SSMH U23 02

SW U23 02

6"PVC

6"PVC 12"PLASTIC 4"PVC

8"

4"

10"

8"

6"PVC

21"PLASTIC

24"PVC

6"PVC

2"PVC

24"PVC

6"PVC

ACID TANKS

8"DI

6"PVC 4"PVC

2"PL

6"

2"PL

3/4"STEEL

ALAGASCO CO.

1-4"1-1"

6-4"NO CONC.

2"

4-4"1-3"

2-1"

1- 3 /4"

4-1 1 /4"

1-1"2-1"

2- 3/4"

2-5"NO CONCAL. POWER

4-4"

ALABAMAPOWER

OE

3-1

1-4"CHARTER

4-4"AU2-4"

2-4"

2-2"

2-4"AU

2-1 1 /4" CHARTER

AT&T

4"CHW

AQUATIC RES. MGMT. CTR.

LABORATORY

ADMINISTRATION

NEWCHEM STORAGEBLDG.

57' -

4"

18' -

0"

24' - 0" 22' - 1"

CONC. WALK

RE-DIRECT EXISTING WATERLINE AWAY FROM NEW BUILDING

EJ

EJ

6' - 0"

5

A-101

Sim

FFE 100.0

FFE 99.53

99.5

99.5

99.598.8

SLP UP SLP UP

10' - 0"6' - 0"

10' - 0"

1A-101

4" PVC CONNECTTO EXISTING

SAN SEWER M.H.

CO

99.95

NEW WATER LINE-SEE PLUMBING FOR CONNECTION

CONNECT NEW WATER LINETO EXISTING BUILDING SUPPLY-

REPAIR/PATCH EXISTING WALLS AND FINISHES TO MATCH EXISTING

WW

W

W

W

W

EXISTING M.H.

foETATS

ALABAMA

DERETSIG

ER T

CE

TIHCRA

6763

E.

E WYAT

MSJACKSON,

BOWD N

T

Arc

hite

cts &

Plan

ners

, PLL

CSU

ITE

400

1510

NO

RTH

STA

TE S

TREE

TJA

CKSO

N, M

S 3

9202

-164

7TE

LEPH

ON

E:FA

X:

EMA

IL:

WEB

:

601-

352-

3071

601-

352-

3078

fwjac

kson

@fo

ilwya

tt.co

mw

ww.fo

ilwya

tt.co

m

sheet no.

of

Facilities Management1161 West Samford Avenue

Auburn University, AL 36849Phone: (334) 844-4810

Fax: (334) 844-9458Safety is our first priority.Think Safety. Act Safely.

RevisionNo. Date

AU Pr

oject

16-48

4 Nort

h Aub

urn -

New

Fishe

ries C

hemi

cal S

torag

e Bu

ilding

Schematic Phase 05/24/16

DLC

12-18-2017

-

16-494

DRAWN BY:

CHECKED BY:

FILE NUMBER:

PROJECT NUMBER:

SHEET NUMBER:

SHEET TITLE:

DATE:

ABC 12/18/17

EBW

C-101

SITE PLAN

SCALE: 1" = 20'-0" C-101

SITE PLAN 1

NORTH

CHEM.STORAGE 1

CHEM. STORAGE 2

EXP. RELIEFPANELS

POWER PANEL

24' - 0"

18

' - 0

"

3' - 11" 6' - 0" 14' - 1"

EJ

2' - 6"

A-101 11

A-101

8

A-1019

A-101

10

EXH. FAN

EXH. FAN

22X22INTAKEVENT

22X22INTAKEVENT

HVACUNIT

6

A-101

Sim

REROUTED WATERLINE

REROUTED WATERLINE

FIRE PROTECTION NOTES:1. Ansul system to be installed by a contractor certified and permitted through the State of Alabama Fire

Marshal's Office.2 Fire alarm horn/strobe on roof to be listed for outside installation.

1' - 8"

4-#6 CONT.

#3 @16" O.C.

2' -

8"

0' -

1"

0' -

6"

6"x6" TUBE

10 GAGE PLATE

2X4@20"O.C.

7/8" CHANNELS AT 24" O.C.

5/8" GYP. BD. PAINTED

R-16.2 INSULATION

1" GRATING

10 GA. SUMP FLOOR

4" CHANNELS

2" INSULATION

14 GA. GALV. SUB-FLOOR

R-26 INSUL.

VA

RIE

S

99.53

98.447

0' -

6"

0' -

5"

1' - 4"

4-#6 CONT.

#3 @16" O.C.#4 @ 12" E.W.

2' -

0"

CHEM STORAGE BUILDING

24' - 0"

24' - 0"

18

' - 0

"

SLOPE 1/4"/FT

EXISTING STORMDRAIN TO REMAIN

RE-ROUTE EXISTINGWATERLINE TO AVOIDNEW SLAB

0' -

6"

8' -

0"

1' -

0"

8' -

0"

0' -

6"

0' - 6" 23' - 0" 0' - 6"

.

.

3

A-101

Sim 2

A-101

Sim

2

A-101

Sim

2

A-101

Sim

2

A-101

Sim

10' - 0" 6' - 0" 10' - 0"

#4 @12 EW

0' -

6"0

' - 6

"

LIMESTONE

EXIST. GRAVEL EXIST. GRAVEL

NEW GRAVELSLOPE UP TO NEW WALK

NEW GRAVELSLOPE UP TO NEW WALK

0' -

6"

0' -

5"

1' - 8"

4-#6 CONT.

#3 @16" O.C.

#4 @ 12" E.W.

2' -

8"

CHEM. STORAGE BUILDING(BY OTHERS)

0' -

3"

NEW CONC. WALK

EXIST. ASPHALT PAVING

1' -

9 1

/32

"

99.4599.53

1' -

1"

0' -

0 1

/2"

NEW CONC. WALK

EXISTING CONC.CURB/WALK

EXIST. BLDG.

#4 @12 EW

EXHAUST FAN

4'X7'DOOR

INTAKEVENT

EXPLOSION RELIEF PANELS

ELEC. PANEL

EXH. FAN

INTAKE VENT

WALL UNIT

HALON TANK

9' -

0"

9' -

0"

24' - 0"

C4X5.4@24" O.C. TYP.

2

A-101

Sim

2

A-101

Sim

18

' - 0

"

foETATS

ALABAMA

DERETSIG

ER T

CE

TIHCRA

6763

E.

E WYAT

MSJACKSON,

BOWD N

T

Arc

hite

cts &

Plan

ners

, PLL

CSU

ITE

400

1510

NO

RTH

STA

TE S

TREE

TJA

CKSO

N, M

S 3

9202

-164

7TE

LEPH

ON

E:FA

X:

EMA

IL:

WEB

:

601-

352-

3071

601-

352-

3078

fwjac

kson

@fo

ilwya

tt.co

mw

ww.fo

ilwya

tt.co

m

sheet no.

of

Facilities Management1161 West Samford Avenue

Auburn University, AL 36849Phone: (334) 844-4810

Fax: (334) 844-9458Safety is our first priority.Think Safety. Act Safely.

RevisionNo. Date

AU Pr

oject

16-48

4 Nort

h Aub

urn -

New

Fishe

ries C

hemi

cal S

torag

e Bu

ilding

Schematic Phase 05/24/16

DLC

12-18-2017

-

16-494

DRAWN BY:

CHECKED BY:

FILE NUMBER:

PROJECT NUMBER:

SHEET NUMBER:

SHEET TITLE:

DATE:

ABC 12/18/17

EBW

A-101

FLOOR PLAN

SCALE: 1/4" = 1'-0" A-101

FLOOR PLAN 1

NORTH

SCALE: 1 1/2" = 1'-0" A-101

EXTERIOR GRADE BEAM 2

SCALE: 1 1/2" = 1'-0" A-101

INTERIOR GRADE BM 3

SCALE: 1/4" = 1'-0" A-101

FOUNDATION PLAN 4

NORTH

SCALE: 3/4" = 1'-0" A-101

CONC. WALK SECTION 5

SCALE: 1" = 1'-0" A-101

EXT GRADE BM @ WALK 6

SCALE: 3/4" = 1'-0" A-101

WALK AT EXIST. CURB 7

SCALE: 1/4" = 1'-0" A-101

NORTH 8

SCALE: 1/4" = 1'-0" A-101

EAST 9

SCALE: 1/4" = 1'-0" A-101

SOUTH 10

SCALE: 1/4" = 1'-0" A-101

WEST 11

SCALE: 1/4" = 1'-0" A-101

FOUNDATION PLAN 12

NORTH

ANSUL SYSTEM

FED FROM MDPA BKR. 9

120/208V,1PH,3W

PE

NORMAL = WHITE

NORMAL = BLACK

FED FROM PE BKR. 2,4

INDICATE VOLTAGE,

NO. OF PHASES,

NO. OF WIRES

ATTACH NAMEPLATE

WITH 2 SCREWS

NAMEPLATE COLOR:

LETTER (FILL) COLOR:

208V,1PH,3W

TWH-1

LETTERING SHALL

BE 1/4" HIGH

INDICATE WHERE THIS

EQUIPMENT IS FED

FROM

E-001

ELECTRICALLEGEND &

NOTES

WMK

CMB

BIRMINGHAM

TUSCALOOSA

JACKSON

NASHVILLE

www.edmondsengineering.com

Project Number :

(205) 988-2069

(205) 752-9915

(601) 362-6478

(615) 265-8071

BHM17041

BA

A

L

A

A

M

N

S

EE

C

I

D

L

N

E

E

R

I

G

N

E

PROFESSIONAL

No. 25095

W

I

L

I

A

M

M.

L

K

G

O

R

E

I

L

11-17-2017

sheet no.

of

Facilities Management1161 West Samford AvenueAuburn University, AL 36849

Phone: (334) 844-4810Fax: (334) 844-9458

Safety is our first priority.Think Safety. Act Safely.

RevisionNo. Date

AU

Proje

ct 16

-484 N

orth A

uburn

-Ne

w Fis

herie

s Che

mica

l Stor

age

Build

ing

Schematic Phase 05/24/16

12-18-2017

-

16-494

DRAWN BY:

CHECKED BY:

FILE NUMBER:

PROJECT NUMBER:

SHEET NUMBER:

SHEET TITLE:

DATE:

ABC 12/18/17

Arc

hit

ects

& P

lan

ner

s, P

LL

CSU

ITE

400

1510 N

OR

TH

ST

AT

E S

TR

EE

TJA

CK

SO

N, M

S 3

9202-1

647

TE

LE

PH

ON

E:

FA

X:

EM

AIL

:W

EB

:

601-3

52-3

071

601-3

52-3

078

fwja

ckso

n@

foilw

yatt

.co

mw

ww

.fo

ilwya

tt.c

om

ABC Comments 12/18/17

AutoCAD SHX Text
ELECTRICAL NOTES
AutoCAD SHX Text
UON
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
INSTALL BLANK COVER.
AutoCAD SHX Text
XRB
AutoCAD SHX Text
EXISTING, REMOVE DEVICE AND
AutoCAD SHX Text
EXISTING, REMOVE & RELOCATE
AutoCAD SHX Text
POLYVINYL CHLORIDE RACEWAY
AutoCAD SHX Text
AL
AutoCAD SHX Text
ALUMINUM
AutoCAD SHX Text
LIQUID TIGHT FLEXIBLE METAL CONDUIT
AutoCAD SHX Text
MOUNTING HEIGHT TO CENTERLINE
AutoCAD SHX Text
CLOSED TRANSITION TRANSFER SWITCH
AutoCAD SHX Text
H
AutoCAD SHX Text
HIGH INTENSITY DISCHARGE
AutoCAD SHX Text
ISOLATED GROUND
AutoCAD SHX Text
NIGHT LIGHT
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text
KILOVOLT-AMPERES
AutoCAD SHX Text
THOUSAND CIRCULAR MILS
AutoCAD SHX Text
NATIONAL ELECTRICAL CODE
AutoCAD SHX Text
MEDIUM VOLTAGE
AutoCAD SHX Text
HORSE POWER
AutoCAD SHX Text
KCMIL
AutoCAD SHX Text
NIC
AutoCAD SHX Text
NL
AutoCAD SHX Text
MV
AutoCAD SHX Text
N
AutoCAD SHX Text
NEC
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
KVA
AutoCAD SHX Text
LT
AutoCAD SHX Text
KW
AutoCAD SHX Text
HID
AutoCAD SHX Text
IG
AutoCAD SHX Text
HP
AutoCAD SHX Text
KILOWATT
AutoCAD SHX Text
CONDUIT RACEWAY
AutoCAD SHX Text
EXPLOSION PROOF
AutoCAD SHX Text
FLEXIBLE METAL CONDUIT
AutoCAD SHX Text
FORCED AIR COOLED
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
EMERGENCY
AutoCAD SHX Text
AMERICAN WIRE GAUGE
AutoCAD SHX Text
AUTOMATIC TRANSFER SWITCH
AutoCAD SHX Text
DIA
AutoCAD SHX Text
DIAMETER
AutoCAD SHX Text
G
AutoCAD SHX Text
FA
AutoCAD SHX Text
FMC
AutoCAD SHX Text
EC
AutoCAD SHX Text
EP
AutoCAD SHX Text
EM
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
CU
AutoCAD SHX Text
CKTS
AutoCAD SHX Text
CTTS
AutoCAD SHX Text
C
AutoCAD SHX Text
AWG
AutoCAD SHX Text
ATS
AutoCAD SHX Text
COPPER
AutoCAD SHX Text
CIRCUITS
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
VOLTS
AutoCAD SHX Text
EXISTING, RELOCATED
AutoCAD SHX Text
EXISTING, REMOVE
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
WEATHERPROOF, NEMA 3R.
AutoCAD SHX Text
WIRES
AutoCAD SHX Text
XR
AutoCAD SHX Text
XRR
AutoCAD SHX Text
XRL
AutoCAD SHX Text
EX
AutoCAD SHX Text
V
AutoCAD SHX Text
WP
AutoCAD SHX Text
W
AutoCAD SHX Text
OWNER FURNISHED
AutoCAD SHX Text
CONTRACTOR INSTALLED
AutoCAD SHX Text
OWNER INSTALLED
AutoCAD SHX Text
RIGID GALVANIZED STEEL
AutoCAD SHX Text
POWER FACTOR
AutoCAD SHX Text
PHASES
AutoCAD SHX Text
ON CENTER
AutoCAD SHX Text
POLES
AutoCAD SHX Text
OWNER FURNISHED
AutoCAD SHX Text
PVC
AutoCAD SHX Text
PH
AutoCAD SHX Text
RGS
AutoCAD SHX Text
OC
AutoCAD SHX Text
PF
AutoCAD SHX Text
P
AutoCAD SHX Text
OFCI
AutoCAD SHX Text
OFOI
AutoCAD SHX Text
AMBIENT AIR COOLED
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
AMPERES INTERUPTING CAPACITY
AutoCAD SHX Text
AA
AutoCAD SHX Text
AIC
AutoCAD SHX Text
AFF
AutoCAD SHX Text
A
AutoCAD SHX Text
AMPERES
AutoCAD SHX Text
CONTRACTOR FURNISHED
AutoCAD SHX Text
CONTRACTOR FURNISHED
AutoCAD SHX Text
OWNER INSTALLED
AutoCAD SHX Text
CONTRACTOR INSTALLED
AutoCAD SHX Text
CFOI
AutoCAD SHX Text
CFCI
AutoCAD SHX Text
XRP
AutoCAD SHX Text
EXISTING, REMOVE AND REPLACE W/ NEW
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
STANDARD MOUNTING HEIGHTS
AutoCAD SHX Text
CR
AutoCAD SHX Text
BACKSPLASH
AutoCAD SHX Text
1'-6"
AutoCAD SHX Text
NOTE 4
AutoCAD SHX Text
J
AutoCAD SHX Text
4'-6"
AutoCAD SHX Text
4'-0"
AutoCAD SHX Text
W
AutoCAD SHX Text
A
AutoCAD SHX Text
S
AutoCAD SHX Text
F
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
2" ABOVE
AutoCAD SHX Text
COUNTER
AutoCAD SHX Text
BACKSPLASH
AutoCAD SHX Text
4" ABOVE
AutoCAD SHX Text
WITHOUT
AutoCAD SHX Text
6'-8"
AutoCAD SHX Text
6'-6"
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
NOTES: NOTES: 1. MOUNTING HEIGHTS SHOWN ARE FROM FINISHED FLOOR TO CENTERLINE OF OUTLET, MOUNTING HEIGHTS SHOWN ARE FROM FINISHED FLOOR TO CENTERLINE OF OUTLET, UNLESS OTHERWISE NOTED. 2. LOCATIONS OF OUTLETS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL TAKE LOCATIONS OF OUTLETS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL TAKE PRECEDENCE OVER THESE MOUNTING HEIGHTS. FIELD LOCATE OUTLETS WITH ARCHITECT DURING ROUGH-IN. 3. INSTALL OUTLETS THAT ARE IN CLOSE PROXIMITY ON THE SAME CENTERLINE. OUTLETS INSTALL OUTLETS THAT ARE IN CLOSE PROXIMITY ON THE SAME CENTERLINE. OUTLETS THAT ARE WITHIN 2'-0" HORIZONTALLY AND WITHIN 1'-0" VERTICALLY SHALL BE INSTALLED ON THE SAME HORIZONTAL CENTERLINE LOCATED HALF WAY BETWEEN THE HEIGHTS SHOWN. OUTLETS THAT ARE MORE THAN 1'-0" APART VERTICALLY SHALL BE INSTALLED ON THE SAME VERTICAL CENTERLINE. 4. VERIFY MOUNTING HEIGHT WITH LOCAL AUTHORITY.VERIFY MOUNTING HEIGHT WITH LOCAL AUTHORITY.
AutoCAD SHX Text
RUN IN FLEXIBLE METAL CONDUIT.
AutoCAD SHX Text
NOTE: SHOWN 2#12 AND 1#12(G)-1/2"C,
AutoCAD SHX Text
RISER: UP, RUNNING TO SOURCE.
AutoCAD SHX Text
RISER: DOWN, RUNNING TO SOURCE.
AutoCAD SHX Text
SIZED IN ACCORDANCE WITH NEC TABLE 250-95.
AutoCAD SHX Text
NUMBER OF HASHMARKS DO NOT INCLUDE GROUND WIRE.
AutoCAD SHX Text
EACH LUMINAIRE IS TO BE INSTALLED WITH AN INDIVIDUAL FLEXIBLE CONNECTION.
AutoCAD SHX Text
REQUIRED INSTALLATION
AutoCAD SHX Text
BRANCH CIRCUIT WIRING FOR LIGHTING IS SHOWN SCHEMATICALLY.
AutoCAD SHX Text
CONDUIT SEAL FITTING: CROUSE-HINDS #EYS OR APPROVED EQUIVALENT.
AutoCAD SHX Text
EMPTY CONDUIT, 3/4" UNLESS OTHERWISE NOTED WITH NYLON PULL CORD.
AutoCAD SHX Text
CONDUCTORS OR AS NOTED. THE NUMBER IN THE CIRCUIT
AutoCAD SHX Text
10 3#10 AND 1#10(G)-3/4"C
AutoCAD SHX Text
10 2#10 AND 1#10(G)-3/4"C
AutoCAD SHX Text
3#12 AND 1#12(G)-3/4"C
AutoCAD SHX Text
4#12 AND 1#12(G)-3/4"C
AutoCAD SHX Text
HOMERUN TO PANELBOARD AND 20A, 1P BREAKER, UON.
AutoCAD SHX Text
INDICATES AWG WIRE SIZE AND HASHMARKS INDICATE
AutoCAD SHX Text
SIZE CONDUIT PER NEC FOR GREATER NUMBER OF
AutoCAD SHX Text
NUMBER OF WIRES REQUIRED. GROUND WIRE SHALL BE
AutoCAD SHX Text
CONCEALED IN OR BELOW FLOOR OR UNDERGROUND.
AutoCAD SHX Text
CONCEALED IN CEILING, WALL, OR IN CEILING SLAB.
AutoCAD SHX Text
FOR EXAMPLE:
AutoCAD SHX Text
SCHEMATIC
AutoCAD SHX Text
EXPOSED.
AutoCAD SHX Text
EMERGENCY.
AutoCAD SHX Text
E
AutoCAD SHX Text
J
AutoCAD SHX Text
J
AutoCAD SHX Text
J
AutoCAD SHX Text
BRANCH CIRCUITS
AutoCAD SHX Text
GROUND SYSTEM CONDUCTOR #3/0 BARE COPPER,
AutoCAD SHX Text
(2'-0" BELOW GRADE WHEN INSTALLED UNDERGROUND)
AutoCAD SHX Text
GROUND ROD, 3/4" DIA. X 10'-0" COPPER CLAD STEEL.
AutoCAD SHX Text
G
AutoCAD SHX Text
TOP DRIVEN TO 2'-0" BELOW FINISHED GRADE.
AutoCAD SHX Text
LIGHTNING PROTECTION AIR TERMINAL.
AutoCAD SHX Text
LIGHTNING PROTECTION & GROUNDING
AutoCAD SHX Text
POWER PANEL: SEE PANELBOARD SCHEDULE AND SPECIFICATIONS.
AutoCAD SHX Text
RECEPTACLE PANEL: SEE PANELBOARD SCHEDULE AND SPECIFICATIONS.
AutoCAD SHX Text
LIGHTING PANEL: SEE PANELBOARD SCHEDULE AND SPECIFICATIONS.
AutoCAD SHX Text
PANELBOARDS
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
GROUND RODS
AutoCAD SHX Text
PER SPECS
AutoCAD SHX Text
COLD WATER
AutoCAD SHX Text
PIPING
AutoCAD SHX Text
TO
AutoCAD SHX Text
STREET
AutoCAD SHX Text
GROUNDING BUSHING
AutoCAD SHX Text
TO GROUND CONDUIT
AutoCAD SHX Text
(TYPICAL).
AutoCAD SHX Text
MAIN DISCONNECT
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text
NEUTRAL BUS ISOLATED
AutoCAD SHX Text
FROM SERVICE DISCONNECT
AutoCAD SHX Text
FRAME.
AutoCAD SHX Text
GROUND BUS BOLTED
AutoCAD SHX Text
TO SERVICE DISCONNECT
AutoCAD SHX Text
FRAME
AutoCAD SHX Text
MAIN VALVE
AutoCAD SHX Text
BUILDING
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
MAIN BONDING JUMPER
AutoCAD SHX Text
GROUNDING ELECTRODE CONDUCTOR
AutoCAD SHX Text
GROUNDING ELECTRODE CONDUCTOR
AutoCAD SHX Text
GROUNDING ELECTRODE CONDUCTOR
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
DETAIL - GROUNDING
AutoCAD SHX Text
20 FEET OR MORE
AutoCAD SHX Text
2 INCHES
AutoCAD SHX Text
GROUNDING ELECTRODE CONDUCTOR
AutoCAD SHX Text
#4AWG OR LARGER, BARE COPPER CONDUCTOR.
AutoCAD SHX Text
CONCRETE FOUNDATION
AutoCAD SHX Text
GROUNDING ELECTRODE
AutoCAD SHX Text
SIZED PER NEC.
AutoCAD SHX Text
SIZED PER NEC.
AutoCAD SHX Text
MECHANICAL SPLICING DEVICE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
DETAIL - UFER GROUNDING
AutoCAD SHX Text
4" JUNCTION BOX
AutoCAD SHX Text
LINES.
AutoCAD SHX Text
WILL HAVE TWO
AutoCAD SHX Text
(TRANSFER SWITCHES
AutoCAD SHX Text
NORMAL = WHITE
AutoCAD SHX Text
EMERGENCY = RED
AutoCAD SHX Text
NAMEPLATE COLOR:
AutoCAD SHX Text
NORMAL = BLACK
AutoCAD SHX Text
EMERGENCY = WHITE
AutoCAD SHX Text
LETTER (FILL) COLOR:
AutoCAD SHX Text
INDICATE VOLTAGE,
AutoCAD SHX Text
NO. OF PHASES,
AutoCAD SHX Text
NO. OF WIRES
AutoCAD SHX Text
ATTACH NAMEPLATE
AutoCAD SHX Text
WITH 2 SCREWS
AutoCAD SHX Text
INDICATE WHERE
AutoCAD SHX Text
THIS EQUIPMENT
AutoCAD SHX Text
IS FED FROM
AutoCAD SHX Text
LETTERING SHALL
AutoCAD SHX Text
BE 1/4" HIGH
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
DETAIL - PANEL NAMEPLATE
AutoCAD SHX Text
SEE SINGLE LINE DIAGRAM
AutoCAD SHX Text
SLD
AutoCAD SHX Text
PANELBOARD
AutoCAD SHX Text
CURRENT TRANSFORMER
AutoCAD SHX Text
MEDIUM-VOLTAGE STRESS CONE
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
STATIONARY FUSE
AutoCAD SHX Text
STATIONARY CIRCUIT BREAKER
AutoCAD SHX Text
STATIONARY SWITCH
AutoCAD SHX Text
J
AutoCAD SHX Text
CONNECTED
AutoCAD SHX Text
NO CONNECTION
AutoCAD SHX Text
BUSSING OR BUSWAY
AutoCAD SHX Text
LOAD BREAK CONNECTION
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
PAD MOUNTED TRANSFORMER
AutoCAD SHX Text
RISER DIAGRAM SYMBOLS
AutoCAD SHX Text
TRANSIENT VOLTAGE SURGE SUPPRESSOR
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
OUTLET BOX - FLOOR MOUNTED, WITH FLEXIBLE HARD WIRED CONNECTION TO EQUIPMENT
AutoCAD SHX Text
OUTLET BOX - CEILING MOUTNED, WITH FLEXIBLE HARD WIRED CONNECTION TO EQUIPMENT
AutoCAD SHX Text
OUTLET BOX - WALL MOUNTED, WITH FLEXIBLE HARD WIRED CONNECTION TO EQUIPMENT
AutoCAD SHX Text
JUNCTION BOX - FLOOR MOUNTED
AutoCAD SHX Text
TELE DATA JUNCTION BOX - CEILING MOUNTED
AutoCAD SHX Text
POWER JUNCTION BOX - CEILING MOUNTED
AutoCAD SHX Text
JUNCTION BOX - CEILING MOUNTED
AutoCAD SHX Text
JUNCTION BOX - WALL MOUNTED
AutoCAD SHX Text
JUNCTION & OUTLET BOXES
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
XR
AutoCAD SHX Text
DRAWING CONVENTIONS
AutoCAD SHX Text
EXISTING TO REMOVE
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
NEW WORK
AutoCAD SHX Text
X
AutoCAD SHX Text
METER (WITH SOCKET ASSSEMBLY)
AutoCAD SHX Text
AUTOMATIC TRANSFER SWITCH
AutoCAD SHX Text
MANUAL TRANSFER SWITCH
AutoCAD SHX Text
CONTROL PANEL
AutoCAD SHX Text
VARIABLE SPEED / VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
CONTACTOR
AutoCAD SHX Text
CIRCUIT BREAKER, INDIVIDUALLY ENCLOSED
AutoCAD SHX Text
DISCONNECT SWITCH, UNFUSED, 30A, 3P UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
ELECTRIC MOTOR
AutoCAD SHX Text
RELAY
AutoCAD SHX Text
COMBINATION MAGNETIC STARTER & DISCONNECT SWITCH
AutoCAD SHX Text
MAGNETIC MOTOR STARTER
AutoCAD SHX Text
PHOTO-ELECTRIC / PHOTOCELL SWITCH
AutoCAD SHX Text
ELECTRIC CABINET HEATER
AutoCAD SHX Text
UNIT HEATER WITH FAN
AutoCAD SHX Text
ELECTRIC DUCT HEATER
AutoCAD SHX Text
FAN / FAN-COIL UNIT
AutoCAD SHX Text
POWER
AutoCAD SHX Text
DISCONNECT SWITCH, FUSED, 30A, 3P UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
ELECTRIC BASEBOARD HEATER
AutoCAD SHX Text
GENERATOR ALARM / ANNUNCIATOR PANEL
AutoCAD SHX Text
PACKAGED AIR CONDITIONING UNIT
AutoCAD SHX Text
TIME CLOCK SWITCH
AutoCAD SHX Text
TRANSFORMER, GENERAL PURPOSE DRY-TYPE, REFER TO SCHEDULE
AutoCAD SHX Text
%%UFIRE ALARM
AutoCAD SHX Text
FIRE ALARM SYSTEM: REMOTE ANNUNCIATOR.
AutoCAD SHX Text
FA
AutoCAD SHX Text
FIRE ALARM SYSTEM: SMOKE DETECTOR, CEILING MOUNTED
AutoCAD SHX Text
190 DEG. (THERMAL AND RATE OF RISE).
AutoCAD SHX Text
FIRE ALARM SYSTEM: HEAT DETECTOR, HIGH TEMPERATURE,
AutoCAD SHX Text
FIRE ALARM SYSTEM: MANUAL STATION, MOUNT 4'-0"H.
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
FIRE ALARM SYSTEM: CEILING MOUNTED FIRE SPEAKER.
AutoCAD SHX Text
F
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FIRE ALARM SYSTEM: CONTROL PANEL, SURFACE OR FLUSH MOUNTED. (AS SHOWN ON PLANS).
AutoCAD SHX Text
F
AutoCAD SHX Text
FIRE ALARM SYSTEM: ALARM SIGNAL STROBE.
AutoCAD SHX Text
G
AutoCAD SHX Text
FIRE ALARM SYSTEM: COMPONENTS WITH "G" REQUIRE A GUARD
AutoCAD SHX Text
FIRE ALARM SYSTEM: CONTROL MODULE.
AutoCAD SHX Text
CM
AutoCAD SHX Text
FIRE ALARM SYSTEM: MONITOR MODULE.
AutoCAD SHX Text
MM
AutoCAD SHX Text
FIRE ALARM SYSTEM: COMPONENTS WITH "S" ARE SURFACE MOUNTED
AutoCAD SHX Text
S
AutoCAD SHX Text
F
AutoCAD SHX Text
FIRE ALARM SYSTEM: CEILING MOUNTED ALARM SIGNAL STROBE.
AutoCAD SHX Text
C
AutoCAD SHX Text
FIRE ALARM SYSTEM: SMOKE DETECTOR IN A.C. SUPPLY OR RETURN DUCT WITH SAMPLING TUBES, ADDRESSABLE.
AutoCAD SHX Text
FIRE ALARM SYSTEM: COMBINATION HORN AND STROBE, WALL MOUNTED 7'-0"H. OR AS SHOWN ON ARCHITECTURAL ELEVATIONS. COORDINATE WITH GENERAL CONTRACTOR.
AutoCAD SHX Text
FIRE ALARM SYSTEM: SPRINKLER (FIRE PROTECTION) SYSTEM SUPERVISORY SWITCH INSTALLED ON MANUAL VALVE.
AutoCAD SHX Text
FIRE ALARM SYSTEM: FLOW VALVE, PROVIDE APPROPRIATE CONNECTION DEVICE TO ACTIVATE FIRE ALARM.
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
GROUNDING BUSHING
AutoCAD SHX Text
LOCKNUT
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text
E0.01
AutoCAD SHX Text
1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
DETAIL - CONDUIT TERMINATION
AutoCAD SHX Text
E0.01
AutoCAD SHX Text
3
AutoCAD SHX Text
E0.01
AutoCAD SHX Text
4
AutoCAD SHX Text
E0.01
AutoCAD SHX Text
5
AutoCAD SHX Text
1. THE ELECTRICAL CONTRACTOR OR (E.C.) SHALL BE RESPONSIBLE FOR CONFORMITY TO ALL THE ELECTRICAL CONTRACTOR OR (E.C.) SHALL BE RESPONSIBLE FOR CONFORMITY TO ALL LOCAL CODES AND ORDINANCES, THE NATIONAL ELECTRIC CODE AND ANY ADDITIONAL JURISIDICTIONS RELATING TO THE WORK. 2. THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY FOR ALL NECESSARY FEES. THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY FOR ALL NECESSARY FEES. 3. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT, WIRE, BOXES, THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT, WIRE, BOXES, SWITCHES, LIGHT FIXTURES (WITH LAMPS), RECEPTACLES, SERVICE DEVICES, SWITCHBOARDS AND PANELBOARDS, ETC., REQUIRED FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. 4. REFER TO THE MECHANICAL DRAWINGS FOR THE EXACT LOCATIONS OF EQUIPMENT, RATINGS, REFER TO THE MECHANICAL DRAWINGS FOR THE EXACT LOCATIONS OF EQUIPMENT, RATINGS, RELAYS, TIME SWITCHES, SNAP SWITCHES, AND OTHER CONTROL AND AUXILIARY DEVICES AND CONTROL WIRING DIAGRAMS. 5. CEILING CLEARANCES ARE CRITICAL FOR THIS PROJECT. GENERAL CONTRACTOR MUST CEILING CLEARANCES ARE CRITICAL FOR THIS PROJECT. GENERAL CONTRACTOR MUST COORDINATE ALL TRADES TO AVOID POTENTIAL INTERFERENCES. CONFLICTS BETWEEN TRADES SHALL BE REFERRED TO THE ARCHITECT FOR RESOLUTION. 6. ALL CONDUITS CROSSING EXPANSION JOINTS SHALL HAVE EXPANSION TYPE FITTINGS. ALL CONDUITS CROSSING EXPANSION JOINTS SHALL HAVE EXPANSION TYPE FITTINGS. 7. THESE DRAWINGS ARE A PART OF A COMPLETE SET OF ARCHITECTURAL/ENGINEERING CONTRACT THESE DRAWINGS ARE A PART OF A COMPLETE SET OF ARCHITECTURAL/ENGINEERING CONTRACT DOCUMENTS. ELECTRICAL CONTRACTOR SHOULD REFER TO THE ARCHITECTURAL DRAWINGS FOR ACTUAL LOCATION OF ITEMS WHERE SPECIFIED (LOCATIONS SHOWN ON THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER THOSE SHOWN ON THE ELECTRICAL DRAWINGS). SEE SAID CONFIGURATIONS FOR WALL DEFINITIONS, ELEVATIONS, CASEWORK, REFLECTED CEILING PLAN, ETC. ROUGH-IN INSTALLATIONS WHICH ARE NOT LOCATED ACCORDING TO THE ARCHITECTURAL ELEVATIONS SHALL BE RELOCATED AT NO ADDITIONAL COST. 6. ALL OUTLET BOXES MOUNTED BACK-TO-BACK IN WALLS SHALL HAVE FIREPROOF SOUND ALL OUTLET BOXES MOUNTED BACK-TO-BACK IN WALLS SHALL HAVE FIREPROOF SOUND INSULATING MATERIAL INSTALLED BETWEEN THE BOXES TO PREVENT SOUND TRANSMISSION FROM ONE ROOM TO THE OTHER. 8. ALL WALL OUTLETS NOT PROVIDED WITH A DEVICE BY THIS CONTRACTOR SHALL BE PROVIDED ALL WALL OUTLETS NOT PROVIDED WITH A DEVICE BY THIS CONTRACTOR SHALL BE PROVIDED WITH BLANK WALL PLATES. 9. ALL BRANCH CIRCUITS SHALL INCLUDE A GREEN COVERED GROUND WIRE SIZED PER NEC OR AS ALL BRANCH CIRCUITS SHALL INCLUDE A GREEN COVERED GROUND WIRE SIZED PER NEC OR AS SHOWN. CONNECT TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. MULTIPLE WIRE BRANCH CIRCUITS WITH COMMON NEUTRAL REQUIRE ONLY ONE GROUND WIRE. NUMBER OF WIRES SHOWN ON DRAWINGS DOES NOT INCLUDE GROUND WIRE. 10. FINAL EQUIPMENT CONNECTIONS - THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL FINAL EQUIPMENT CONNECTIONS - THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL LABOR & MATERIALS REQUIRED TO MAKE FINAL CONNECTIONS TO ALL EQUIPMENT FURNISHED BY THIS CONTRACTOR AND/OR EQUIPMENT FURNISHED BY OTHERS. VERIFY ALL REQUIREMENTS, CONDUCTOR SIZE, OVERCURRENT PROTECTION, PHASE, VOLTAGE, MOTOR ROTATION, ETC., WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN. PROVIDE FUSED DISCONNECT IF REQUIRED BY MANUFACTURER. 11. VERIFY EXISTING PROJECT CONDITIONS, EQUIPMENT REQUIREMENTS AND EXACT LOCATIONS OF VERIFY EXISTING PROJECT CONDITIONS, EQUIPMENT REQUIREMENTS AND EXACT LOCATIONS OF PANELBOARDS AND DISCONNECTS BEFORE SUBMITTING BID. 12. IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON THE PLANS IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON THE PLANS AND/OR SPECIFICATIONS OR WITH CODE REQUIREMENTS, THE NOTE, SPECIFICATION OR CODE WHICH PRESCRIBES AND ESTABLISHES THE MORE COMPLETE JOB OR THE HIGHER STANDARD SHALL PREVAIL. 13. ALL SYMBOLS SHOWN ON THIS LEGEND MAY NOT BE USED. ALL SYMBOLS SHOWN ON THIS LEGEND MAY NOT BE USED. 14. ALL BRANCH CIRCUIT CONDUITS SHALL BE GALVANIZED EMT. 1/2" CONDUIT MINIMUM. ALL BRANCH CIRCUIT CONDUITS SHALL BE GALVANIZED EMT. 1/2" CONDUIT MINIMUM. 15. ALL PANELBOARDS ARE 3 , 4WIRE UNLESS NOTED OTHERWISE. ALL PANELBOARDS ARE 3 , 4WIRE UNLESS NOTED OTHERWISE. 16. ALL FLUSH MOUNTED PANELS SHALL HAVE 3-1" EMPTY CONDUITS STUBBED OUT ABOVE ALL FLUSH MOUNTED PANELS SHALL HAVE 3-1" EMPTY CONDUITS STUBBED OUT ABOVE ACCESSIBLE CEILING FOR FUTURE CIRCUITS. 17. FIELD MARKING: SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE FIELD MARKING: SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE FAULT CURRENT PER NEC 110.24. THE FIELD MARKING(S) SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. REFER TO ANSI Z535.4-2011 FOR GUIDELINES FOR THE DESIGN AND DURABILITY OF SAFETY SIGNS AND LABELS FOR APPLICATION TO ELECTRICAL EQUIPMENT. 18. PROVIDE ARC-FLASH WARNING LABELS THAT COMPLY WITH NEC 110.16 ON NEW ELECTRICAL PROVIDE ARC-FLASH WARNING LABELS THAT COMPLY WITH NEC 110.16 ON NEW ELECTRICAL EQUIPMENT AND EXISTING EQUIPMENT THAT IS MODIFIED.. 19. ALL SWITCHBOARDS, SWITCHGEAR, AND PANELBOARDS SUPPLIED BY A FEEDER(S) SHALL BE ALL SWITCHBOARDS, SWITCHGEAR, AND PANELBOARDS SUPPLIED BY A FEEDER(S) SHALL BE MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE POWER ORIGINATES PER NEC 408.4(B). 20. FOR 120V OR 208V CIRCUITS, CONTRACTOR SHALL INCREASE WIRE SIZE FROM THAT SHOWN ONE FOR 120V OR 208V CIRCUITS, CONTRACTOR SHALL INCREASE WIRE SIZE FROM THAT SHOWN ONE A.W.G. SIZE FOR EVERY 100' HOMERUN LENGTH, AND ONE A.W.G. SIZE EVERY 200' FOR 277V AND 480V CIRCUITS. 21. FURNISH & INSTALL FIRE ALARM DEVICES THAT CONFORM TO ALL NATIONAL, STATE AND LOCAL FURNISH & INSTALL FIRE ALARM DEVICES THAT CONFORM TO ALL NATIONAL, STATE AND LOCAL CODES AND ARE COMPATIBLE WITH THE EXISTING ADDRESSABLE FIRELITE PANEL. PROVIDE ADDITIONAL DEVICES AS REQUIRED. PROVIDE TO THE ARCHITECT A COMPLETE SET OF MANUFACTURER'S SYSTEM INSTALLATION PLANS INCLUDING RISER DIAGRAM, CONDUIT AND WIRING, INTERCONNECTION DIAGRAMS, DEVICE LOCATIONS AND ALL REQUIRED CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS. PROVIDE CONDUIT AND WIRING AS DIRECTED BY SYSTEM SUPPLIER. FIRE ALARM CONTRACTOR TO HOLD A CURRENT LICENSE TO CONDUCT BUSINESS AND A PERMIT ISSUED BY THE STATE OF ALABAMA FIRE MARSHAL'S OFFICE. 22. ANY ADDITION OR ALTERATION TO AN EXISTING FIRE ALARM SYSTEM REQUIRES TESTING AND ANY ADDITION OR ALTERATION TO AN EXISTING FIRE ALARM SYSTEM REQUIRES TESTING AND DOCUMENTATION AS REQUIRED BY NFPA 72. THIS WORK SHALL BE PREFORMED BY "QUALIFIED PERSONNEL", NFPA 72 (2013) 10.5.2.1.
AutoCAD SHX Text
E0.01
AutoCAD SHX Text
2
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
DETAIL - TYPICAL DISCONNECT LABEL
AutoCAD SHX Text
1
AutoCAD SHX Text
1

CHEM.STORAGE 1

CHEM.STORAGE 2

E-100

ELECTRICAL SITEPLAN

SCALE:1/4 = 1' - 0"

E-100

ELECTRICAL SITE PLAN

1

NORTH

WMK

CMB

BIRMINGHAM

TUSCALOOSA

JACKSON

NASHVILLE

www.edmondsengineering.com

Project Number :

(205) 988-2069

(205) 752-9915

(601) 362-6478

(615) 265-8071

BHM17041

BA

A

L

A

A

M

N

S

EE

C

I

D

L

N

E

E

R

I

G

N

E

PROFESSIONAL

No. 25095

W

I

L

I

A

M

M.

L

K

G

O

R

E

I

L

11-17-2017

sheet no.

of

Facilities Management1161 West Samford AvenueAuburn University, AL 36849

Phone: (334) 844-4810Fax: (334) 844-9458

Safety is our first priority.Think Safety. Act Safely.

RevisionNo. Date

AU

Proje

ct 16

-484 N

orth A

uburn

-Ne

w Fis

herie

s Che

mica

l Stor

age

Build

ing

Schematic Phase 05/24/16

12-18-2017

-

16-494

DRAWN BY:

CHECKED BY:

FILE NUMBER:

PROJECT NUMBER:

SHEET NUMBER:

SHEET TITLE:

DATE:

ABC 12/18/17

Arc

hit

ects

& P

lan

ner

s, P

LL

CSU

ITE

400

1510 N

OR

TH

ST

AT

E S

TR

EE

TJA

CK

SO

N, M

S 3

9202-1

647

TE

LE

PH

ON

E:

FA

X:

EM

AIL

:W

EB

:

601-3

52-3

071

601-3

52-3

078

fwja

ckso

n@

foilw

yatt

.co

mw

ww

.fo

ilwya

tt.c

om

ABC Comments 12/18/17

AutoCAD SHX Text
EX GFI
AutoCAD SHX Text
EX MDPA
AutoCAD SHX Text
EX LA
AutoCAD SHX Text
EX PB
AutoCAD SHX Text
EX PA
AutoCAD SHX Text
EX EA
AutoCAD SHX Text
PE
AutoCAD SHX Text
(2)1" E.C. WITH PULLSTRING FOR FIRE ALARM AND SPARE
AutoCAD SHX Text
PE
AutoCAD SHX Text
TWH 208V/1PH, 4.9KW 30/2, WP NF
AutoCAD SHX Text
MM
AutoCAD SHX Text
10
AutoCAD SHX Text
EX FIRE ALARM
AutoCAD SHX Text
MM
AutoCAD SHX Text
MM
AutoCAD SHX Text
30cd
AutoCAD SHX Text
30cd
AutoCAD SHX Text
1
AutoCAD SHX Text
30cd WP
AutoCAD SHX Text
OUTDOOR FIRE ALARM STROBE, PROVIDED BY OTHERS. VERIFY COMPATIBILITY WITH EXISTING FIRE ALARM SYSTEM. REPLACE WITH NEW IF NOT UL LISTED AS COMPATIBLE.
AutoCAD SHX Text
1
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
ELECTRICAL RISER DIAGRAM
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
1.
AutoCAD SHX Text
400/3
AutoCAD SHX Text
2
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
3
AutoCAD SHX Text
10-12
AutoCAD SHX Text
(3)-SPACES
AutoCAD SHX Text
225/3
AutoCAD SHX Text
1
AutoCAD SHX Text
400/3
AutoCAD SHX Text
FIRST FLOOR
AutoCAD SHX Text
COORDINATE EXACT LOCATION AND REQUIREMENT OF FEEDER CONDUIT WITH EXISTING CONDITIONS
AutoCAD SHX Text
1200/3
AutoCAD SHX Text
125/3
AutoCAD SHX Text
4
AutoCAD SHX Text
200/3
AutoCAD SHX Text
6
AutoCAD SHX Text
100/3
AutoCAD SHX Text
5
AutoCAD SHX Text
100/3
AutoCAD SHX Text
7
AutoCAD SHX Text
--/3
AutoCAD SHX Text
8
AutoCAD SHX Text
9
AutoCAD SHX Text
EX MDPA 1200A, 208/120V, 3P, 4W
AutoCAD SHX Text
NEW 100/2
AutoCAD SHX Text
NEW PE
AutoCAD SHX Text
EX PA & EX PB
AutoCAD SHX Text
EX PC & EX PD
AutoCAD SHX Text
EX H & EX HA
AutoCAD SHX Text
EX B
AutoCAD SHX Text
EX EA
AutoCAD SHX Text
EX LA
AutoCAD SHX Text
EX OVERHEAD CRANE
AutoCAD SHX Text
EX CT-1
AutoCAD SHX Text
GENERAL POWER NOTES: 1. PE PANEL, 208/120V, 1PH, 100A PANEL WITH 100A MAIN BREAKER IN 3R ENCLOSURE. PANEL PROVIDED BY STORAGE EQUIPMENT PROVIDER. COORDINATE FINAL CONNECTIONS WITH OWNER. 5.5KW GENERAL POWER LOAD AND 4.9KW WATER HEATER LOAD. 2. PROVIDE 30/2 BREAKER AND 2#10 & 1#10 G, 3/4" C FOR TANKLESS WATER HEATER. BREAKER SHALL MATCH MANUFACTURER AND AIC RATING OF NEW PE PANEL. 3. PROVIDE MONITOR MODULES CIRCUITED TO EXISTING FIRE ALARM PANEL. MONITOR NEW ANSUL SYSTEM FOR "ALARM", "TROUBLE", AND "SUPERVISORY".
AutoCAD SHX Text
NEW
AutoCAD SHX Text
EX 1#3/0(G)
AutoCAD SHX Text
-3"C.
AutoCAD SHX Text
1#1/0(G)
AutoCAD SHX Text
-3/4"C.
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
NOTE 2
AutoCAD SHX Text
2.
AutoCAD SHX Text
COORDINATE LIGHTNING PROTECTION SYSTEM (PROVIDED BY OTHERS) CONNECTION WITH BUILDING GROUND.
AutoCAD SHX Text
1

Recommended