AHU-8 AHU-3 TO REMAIN 1 AHU-3 VFD AHU-4 2 2 3 3 4 5 MEZZANINE 1 1 2 1 1 1 1 1 1 SSS 1 2 3 4 4 4 3 4 4 7 P 8 12 11 4 4 9 10 5 WAREHOUSE WOMENS MENS 7 E0.1 1 1/4" = 1' TESTING ELECTRICAL DEMOLITION - FLOORPLAN NORTH E0.1 2 1/4" = 1' TESTING ELECTRICAL DEMOLITION - MEZZANINE MEZZANINE KEYED NOTES 1 EXISTING AHU-3 TO REMAIN. 2 AHU IS TO BE REMOVED BY MC, DISCONNECT POWER AND REMOVE CABLES BACK TO BREAKER, LABEL BREAKER OR STARTER AS SPARE. 3 EXISTING AHU-4 & 8 CONTROLS TO BE REMOVED BY CONTROLS CONTRACTOR, CONTROLS BOX TO REMAIN. 4 EXISTING AHU-3 VFD TO REMAIN, MAINTAIN CIRCUIT. 5 EXISTING WATER HEATER TO REMAIN, MAINTAIN CIRCUIT. FLOORPLAN KEYED NOTES 1 REMOVE EXISTING LIGHTS, CONDUIT, WIRING AND SWITCHES. 2 REMOVE EXISTING GARAGE DOOR ELECTRICAL INCLUDING CONTROLS BACK TO BREAKER. CONDUIT ABOVE CEILING CAN BE ABANDONED. 3 REMOVE EXISTING DISCONNECT, STARTER, RECEPTACLE, CONDUIT, AND WIRING BACK TO BUS DUCT BREAKER. 4 REMOVE EXISTING RECEPTACLES, SWITCHES, JUNCTION BOXES, CONDUIT AND WIRING. 5 REMOVE EXISTING STROBE TO BE RELOCATED INTO NEW HALLWAY. 6 REMOVE EXPOSED DATA DROPS TO MEZZANINE LEVEL AND COIL WIRE. 7 REMOVE EXISTING EXIT SIGN. GENERAL NOTES DEMOLITION 1 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL ELECTRICAL DEMOLITION WORK. 2 REMOVE ALL UNUSED ELECTRICAL BACK TO BREAKER OR STARTER. LABEL BREAKERS AS SPARE. 8 FIRE ALARM PULL STATION TO REMAIN, MAINTAIN CIRCUIT. 9 REMOVE EXISTING SPEAKER, CONDUIT AND WIRING. 10 SECURITY BOX BESIDE GARAGE DOOR TO REMAIN, STATUS TO BE DETERMINED. 11 COIL LOOSE DATA CABLES BACK TO CORRIDOR WALL, LEAVE FOR POSSIBLE REUSE. 12 KEYED SWITCH BESIDE GARAGE DOOR TO REMAIN, STATUS TO BE DETERMINED. GENERAL NOTES (ALL ELECTRICAL SHEETS) 1 THIS DRAWING IS DIAGRAMMATIC AND INDICATES THE APPROXIMATE LOCATION OF DEVICES AND EQUIPMENT. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS ON SITE. MINOR ADJUSTMENTS AND OFFSETS SHALL BE PROVIDED WHERE REQUIRED AT NO ADDITIONAL COST TO THE OWNER. 2 PROVIDE ALL WORK IN COMPLIANCE WITH ALL STATE AND LOCAL CODES AND IN AN INDUSTRY STANDARD WORKMANLIKE MANNER. 3 NMC (ROMEX AND SE CABLE FOR FEEDERS) IS NOT ACCEPTABLE. AC/MC CABLE IS ACCEPTABLE IN CONCEALED AND UTILITY LOCATIONS. EMT CONDUITS SHALL BE USED IN EXPOSED LOCATIONS. DATA AND FIRE ALARM CABLE DOES NOT REQUIRE CONDUIT, EXCEPT WHERE EXPOSED. ALL CABLES MUST BE PROPERLY SUPPORTED. BUNDLE/SUPPORT POWER/DATA/FIRE ALARM. 4 RACEWAYS SHALL NOT BE RUN ON THE EXTERIOR OF BUILDING, OR IN INTERIOR EXPOSED AREAS OF MAIN FLOOR. 5 DATA AND TELEPHONE WORK SHALL INCLUDE DEVICE BOXES WITH CONDUIT TO IDF RACK IN TESTING IN TECHNOLOGY ROOM 1300, ALL DEVICES, COVER PLATES, CABLES, AND ALL TERMINATIONS AT DEVICES AND RACKS. RACK AND RACK MOUNTED EQUIPMENT ARE BY OWNER. RACKS HAVE 568A TERMINAL PANELS. ALL DATA CABLES TO BE CAT6A TERMINATED ON 568A PANELS AND ALL PHONE CABLES TO BE CAT6 TERMINATED ON 66 BLOCKS. 6 ALL WALLS AND PENETRATIONS SHALL BE REPAIRED AND SEALED, SEE ARCHITECTURAL FOR WALL CONSTRUCTION. 7 PROVIDE PULL STRINGS IN EMPTY CONDUITS. 8 PROVIDE (3) SPARE FUSES OF EACH TYPE USED. 9 RECEPTACLE AND SWITCH COVER PLATE SHALL BE STAINLESS STEEL, DEVICES SHALL BE IVORY COLOR. 10 PROVIDE ALL POWER CONNECTIONS AND TERMINATIONS TO MECHANICAL EQUIPMENT INCLUDING INSIDE THE EQUIPMENT. 11 ALL WALL PENETRATIONS TO BE APPROPRIATELY SEALED (FIRE RATED) BOTH OUTSIDE AND INSIDE CONDUIT (AFTER WIRES INSTALLED). 12 ALL DATA, PHONE, AND FIBER CABLES TO BE TESTED PER LATEST EDITION OF TIA STANDARDS AS LISTED ON PAGE 45 OF NC STS-1000. SCOPE OF WORK PROVIDE TEMPORARY CONSTRUCTION PHASE POWER AND LIGHTING FOR ALL TRADES AS NEEDED. REMOVE/DEMO ALL EXISTING ELECTRICAL EQUIPMENT BACK TO PANELS, UON. PROVIDE SUBMITTALS ON ALL LIGHTING, POWER, CONTROL AND FIRE ALARM EQUIPMENT. PROVIDE ALL ELECTRICAL SHOWN ON DRAWINGS AND SPECIFICATIONS AND AS NEEDED TO PROVIDE A COMPLETE FUNCTIONAL INSTALLATION IN COMPLIANCE WITH STATE AND LOCAL CODES. PROVIDE FIELD COORDINATION WITH OTHER TRADES AND PROVIDE RED-LINE MARKED UP DRAWINGS TO OWNER OF ALL FIELD CHANGES. TEST FOR FUNCTIONALLY OF ALL EQUIPMENT. ASSIST OTHER TRADES AS NEEDED. TEST AND CERTIFY FIRE ALARM EQUIPMENT. VERIFY THAT ALL DEVICES IN ADJACENT AREAS FUNCTION PROPERLY. TEST AND CERTIFY EXIT AND EGRESS LIGHTING. TEST AND ADJUST OUTDOOR LIGHTS PHOTOCELLS AFTER DARK. PROVIDE ALL REQUIRED ELECTRICALLY RELATED PERMITS AND INSPECTIONS. PROVIDE ONE YEAR WARRANTY ON ALL PARTS AND LABOR FROM DATE OF PROJECT ACCEPTANCE. 1 1
Transcript
Page 1: NORTH - Buncombe County Schools

AHU-8

AHU-3

TO REMAIN

1

AHU-3

VFD

AHU-4

2

2

3

3

4

5

MEZZANINE

1 1

2

1

1 1

1 1 1

SS

S

1

2

3

4

4

4

34

4

7

P

8 12

11

4

4

9

10

5

WAREHOUSE

WOMENS

MENS

7

E0.1

1

1/4" = 1'

TESTING ELECTRICAL DEMOLITION - FLOORPLAN

NORTH

E0.1

2

1/4" = 1'

TESTING ELECTRICAL DEMOLITION - MEZZANINE

MEZZANINE KEYED NOTES

1 EXISTING AHU-3 TO REMAIN.

2 AHU IS TO BE REMOVED BY MC, DISCONNECT POWER AND REMOVE CABLESBACK TO BREAKER, LABEL BREAKER OR STARTER AS SPARE.

3 EXISTING AHU-4 & 8 CONTROLS TO BE REMOVED BY CONTROLS CONTRACTOR,CONTROLS BOX TO REMAIN.

4 EXISTING AHU-3 VFD TO REMAIN, MAINTAIN CIRCUIT.

5 EXISTING WATER HEATER TO REMAIN, MAINTAIN CIRCUIT.

FLOORPLAN KEYED NOTES

1 REMOVE EXISTING LIGHTS, CONDUIT, WIRING AND SWITCHES.

2 REMOVE EXISTING GARAGE DOOR ELECTRICAL INCLUDING CONTROLS BACK TOBREAKER. CONDUIT ABOVE CEILING CAN BE ABANDONED.

3 REMOVE EXISTING DISCONNECT, STARTER, RECEPTACLE, CONDUIT, AND WIRING BACK TO BUS DUCT BREAKER.

4 REMOVE EXISTING RECEPTACLES, SWITCHES, JUNCTION BOXES, CONDUIT ANDWIRING.

5 REMOVE EXISTING STROBE TO BE RELOCATED INTO NEW HALLWAY.

6 REMOVE EXPOSED DATA DROPS TO MEZZANINE LEVEL AND COIL WIRE.

7 REMOVE EXISTING EXIT SIGN.

GENERAL NOTES DEMOLITION

1 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL ELECTRICAL DEMOLITION WORK.

2 REMOVE ALL UNUSED ELECTRICAL BACK TO BREAKER OR STARTER. LABELBREAKERS AS SPARE.

8 FIRE ALARM PULL STATION TO REMAIN, MAINTAIN CIRCUIT.

9 REMOVE EXISTING SPEAKER, CONDUIT AND WIRING.

10 SECURITY BOX BESIDE GARAGE DOOR TO REMAIN, STATUS TO BE DETERMINED.

11 COIL LOOSE DATA CABLES BACK TO CORRIDOR WALL, LEAVE FOR POSSIBLEREUSE.

12 KEYED SWITCH BESIDE GARAGE DOOR TO REMAIN, STATUS TO BE DETERMINED.

GENERAL NOTES (ALL ELECTRICAL SHEETS)

1 THIS DRAWING IS DIAGRAMMATIC AND INDICATES THE APPROXIMATE LOCATION OF DEVICES AND EQUIPMENT. THE CONTRACTOR SHALLFIELD VERIFY ALL EXISTING CONDITIONS ON SITE. MINOR ADJUSTMENTS AND OFFSETS SHALL BE PROVIDED WHERE REQUIRED AT NOADDITIONAL COST TO THE OWNER.

2 PROVIDE ALL WORK IN COMPLIANCE WITH ALL STATE AND LOCAL CODES AND IN AN INDUSTRY STANDARD WORKMANLIKE MANNER.

3 NMC (ROMEX AND SE CABLE FOR FEEDERS) IS NOT ACCEPTABLE. AC/MC CABLE IS ACCEPTABLE IN CONCEALED AND UTILITY LOCATIONS.EMT CONDUITS SHALL BE USED IN EXPOSED LOCATIONS. DATA AND FIRE ALARM CABLE DOES NOT REQUIRE CONDUIT, EXCEPT WHEREEXPOSED. ALL CABLES MUST BE PROPERLY SUPPORTED. BUNDLE/SUPPORT POWER/DATA/FIRE ALARM.

4 RACEWAYS SHALL NOT BE RUN ON THE EXTERIOR OF BUILDING, OR IN INTERIOR EXPOSED AREAS OF MAIN FLOOR.

5 DATA AND TELEPHONE WORK SHALL INCLUDE DEVICE BOXES WITH CONDUIT TO IDF RACK IN TESTING IN TECHNOLOGY ROOM 1300, ALLDEVICES, COVER PLATES, CABLES, AND ALL TERMINATIONS AT DEVICES AND RACKS. RACK AND RACK MOUNTED EQUIPMENT ARE BY OWNER. RACKS HAVE 568A TERMINAL PANELS. ALL DATA CABLES TO BE CAT6A TERMINATED ON 568A PANELS AND ALL PHONE CABLESTO BE CAT6 TERMINATED ON 66 BLOCKS.

6 ALL WALLS AND PENETRATIONS SHALL BE REPAIRED AND SEALED, SEE ARCHITECTURAL FOR WALL CONSTRUCTION.

7 PROVIDE PULL STRINGS IN EMPTY CONDUITS.

8 PROVIDE (3) SPARE FUSES OF EACH TYPE USED.

9 RECEPTACLE AND SWITCH COVER PLATE SHALL BE STAINLESS STEEL, DEVICES SHALL BE IVORY COLOR.

10 PROVIDE ALL POWER CONNECTIONS AND TERMINATIONS TO MECHANICAL EQUIPMENT INCLUDING INSIDE THE EQUIPMENT.

11 ALL WALL PENETRATIONS TO BE APPROPRIATELY SEALED (FIRE RATED) BOTH OUTSIDE AND INSIDE CONDUIT (AFTER WIRES INSTALLED).

12 ALL DATA, PHONE, AND FIBER CABLES TO BE TESTED PER LATEST EDITION OF TIA STANDARDS AS LISTED ON PAGE 45 OF NC STS-1000.

SCOPE OF WORK

PROVIDE TEMPORARY CONSTRUCTION PHASE POWER AND LIGHTING FOR ALL TRADES AS NEEDED.

REMOVE/DEMO ALL EXISTING ELECTRICAL EQUIPMENT BACK TO PANELS, UON.

PROVIDE SUBMITTALS ON ALL LIGHTING, POWER, CONTROL AND FIRE ALARM EQUIPMENT.

PROVIDE ALL ELECTRICAL SHOWN ON DRAWINGS AND SPECIFICATIONS AND AS NEEDED TO PROVIDE A COMPLETE FUNCTIONAL INSTALLATION INCOMPLIANCE WITH STATE AND LOCAL CODES.

PROVIDE FIELD COORDINATION WITH OTHER TRADES AND PROVIDE RED-LINE MARKED UP DRAWINGS TO OWNER OF ALL FIELD CHANGES.

TEST FOR FUNCTIONALLY OF ALL EQUIPMENT. ASSIST OTHER TRADES AS NEEDED.

TEST AND CERTIFY FIRE ALARM EQUIPMENT. VERIFY THAT ALL DEVICES IN ADJACENT AREAS FUNCTION PROPERLY.

TEST AND CERTIFY EXIT AND EGRESS LIGHTING.

TEST AND ADJUST OUTDOOR LIGHTS PHOTOCELLS AFTER DARK.

PROVIDE ALL REQUIRED ELECTRICALLY RELATED PERMITS AND INSPECTIONS.

PROVIDE ONE YEAR WARRANTY ON ALL PARTS AND LABOR FROM DATE OF PROJECT ACCEPTANCE.

1

1

Page 2: NORTH - Buncombe County Schools

AHU-3

AHU-3

VFD

1

3

2

2

4

5

C

6

F

TP

FF F

TO

REMOTE

INDICATOR

9

TO OFFICE

LIGHTS

S

7

TP-13

8

TO PANEL 107 ON

COLUMN LINE 7-C

IN TESTING

OFFICE.

MEZZANINE

C C2

TP-1

1

1

1

1

S

3

S

3

SSS

3

S

3

S

SS

S

I

S

TP-4

C

2

4

5

6

C

C C

C1 C1

C1 C1

S

4

S

4

8

8

2

2

2

2

2

2

EL1

TP-3

9

TO MEZZANINE

LIGHTS

7

C

C

S

TO MEZZANINE

LIGHTS

TO DUCT SMOKE

DETECTOR

TP-15

P

9

75

30

EX

13

12

11

14

CORRIDOR

0070

CORRIDOR

0065

TESTING

1215

OFFICE

1217

OFFICE

1219

G

EX

17

2

2

12

TP-17

15

2 +3'

+12'

+12'16

18

ADDITIONAL

FIXTURES

EL1

120VAC

H N

INBOARD

BALLAST

OUTBOARD

BALLAST

ER

C1

C1

S

S

NORTH

E1.1

1

1/4" = 1'

TESTING ELECTRICAL CONSTRUCTION - FLOORPLAN

E1.1

2

1/4" = 1'

TESTING ELECTRICAL CONSTRUCTION - MEZZANINE

MEZZANINE KEYED NOTES

1 EXISTING AHU-3 TO REMAIN, MAINTAIN CIRCUIT.

2 EXISTING AHU-3 VFD AND EMPTY CONTROL BOXES, MAINTAIN CIRCUIT.

3 EXISTING WATER HEATER TO REMAIN, MAINTAIN CIRCUIT.

4 EXISTING SPRINKLER BRANCH PIPING TO REMAIN.

5 IF EXISTING DUCT SMOKE DETECTOR IS UNUSABLE EC/FAC TO FURNISH NEWDUCT SMOKE DETECTOR. MC TO INSTALL DUCT SMOKE DETECTOR AND EC/FACTO WIRE. PROVIDE REMOTE INDICATING LIGHT.

6 PROVIDE FA CONTROL RELAY TO SHUT DOWN VFD. PROVIDE WITHIN 36" OFVFD.

7 PROVIDE MEZZANINE LIGHT SWITCH BY ACCESS LADDER.

8 PROVIDE 1-1/2"C, (4) #2, #6G.

9 CHAIN HUNG AT 8'-9' AFF, TYPICAL.

FLOORPLAN KEYED NOTES

1 WIRE RECEPTACLES AS SHOWN BACK TO PANEL TP. PANEL TP IS ON THE MEZZANINE.

2 PROVIDE 4 WAY SWITCHING FOR MAIN ROOM LIGHTS.

3 REMOTE DUCT DETECTOR INDICATOR STATION, MOUNT AT 5'-6" AFF.

4 WIRE TO AHU-3 DUCT SMOKE DETECTOR.

5 PROVIDE NEW LIGHTS MOUNTED AT 18'-6" AFF. TIE INTO EXISTING HALLWAYLIGHT CIRCUIT.

6 PROVIDE BOX AND 3/4" CONDUIT TO 6" ABOVE CEILING FOR DATA.

7 PROVIDE BOX AND 3/4" CONDUIT TO 6" ABOVE CEILING FOR PHONE.

E1.1

3

NTS

ROOM LIGHTING CIRCUIT

8 ANY EXPOSED CONDUIT TO BE PAINTED TO MATCH WALL. ANY EXPOSED CONDUIT ABOVE 18' IS TO BE PAINTED BLACK. PAINTING BY GC.

9 FIRE ALARM PULL STATION TO REMAIN, MAINTAIN CIRCUIT.

10 PROVIDE NEW FIRE ALARM DEVICES COMPATIBLE WITH EXISTING SYSTEM. FIREALARM CONTROL PANEL IS HONEYWELL NOTIFIER MODEL #DR-C4, NFS 3030DLOCATED IN ROOM D201.

11 PROVIDE LADDER RACK/CABLE TRAY AT 10' AFF (TOP OF CMU WALL). MATCH TOMINITORIUM RACK/CABLE TRAY, WIREMOLD PRO-10, 12" TRAY.

12 PROVIDE (2) 2" NIPPLES THRU NEW WALL AT 4"-6" ABOVE CABLE TRAY.

13 PROVIDE (1) 2" CONDUIT AT 20' AFF THRU WALL AND DOWN TO CABLE TRAY.

14 USE EXISTING 3" BRIDLE RINGS AT 20' AFF TO TECHNOLOGY ROOM, 1300, ABOUT125' TO WEST. PROVIDE 2" CONDUIT PENETRATIONS INTO ROOM ABOVE CEILING.

1

1

1

1

1

1

1

1

1

15 PROVIDE 3/4"X6'X4' TELECOMM BOARD MOUNTED AT 1'-7' AFF. CIRCUIT TELECOMM BOARD RECEPTACLE TO PANEL TP-17. PLYWOOD SHALL BE FIRERETARDANT AND PAINTED WITH (2) COATS OF EPOXY LATEX PAINT, COORDINATE COLOR WITH OWNER. MOUNT RECEPTACLE AT 36" AFF. PROVIDE3/16"X2"X12" COPPER GROUND BAR ON 2" STANDOFFS DIRECTLY UNDER CENTER OF BOARD AT 9" AFF. PROVIDE 250 STRAND, 30AWG #6 WELDING CABLEFROM GROUND BAR TO STEEL COLUMN AND BOND USING BARREL TYPE CRIMPCONNECTORS AND CONNECTION GREASE.

16 PROVIDE LADDER RACK/CABLE TRAY AT 6" ABOVE CEILING ALONG ENTIRE LENGTH OF WALL. MATCH TO MINITORIUM RACK/CABLE TRAY, WIREMOLD PRO-10, 12" TRAY.

17 INSTALL (1) 25 PAIR CABLE AND (1) 50 MICRON SINGLE MODE FIBER CABLE, BOTHFURNISHED BY OWNER, FROM NEW TELECOMM BOARD TO TECHNOLOGY ROOM1300 (~170'), USE EXISTING BRIDLE RINGS (AT ~20' AFF). COORDINATE WITH OWNER'S REP: MIKE WINEBARGER (775-2120). MAKE TERMINATIONS OF 25 PAIRCABLE AT BOTH ENDS ON 66 BLOCKS AND TERMINATE FIBER OPTIC CABLE ONBOTH ENDS AS DIRECTED BY OWNER'S REP.

18 PROVIDE GROUND BOND ON COLUMN AT 12' AFF.1

1

1 TESTING

TECHNOLOGY1

1

Page 3: NORTH - Buncombe County Schools

GENERAL ELECTRICAL LEGEND

SYMBOL DESCRIPTION

TYPICAL LIGHT FIXTURES

LETTER INDICATES TYPE

TYPICAL EXIT SIGN - NUMBER OF FACES AND DIRECTIONAL

ARROWS INDICATED, LETTER INDICATES TYPE

EMERGENCY LIGHTING UNIT

TELEPHONE OUTLET WITH RJ-45 JACK

COMBINATION DATA/TELEPHONE OUTLET WITH RJ-45 JACKS

DATA OUTLET WITH 2 RJ-45 JACKS UON

NON-FUSIBLE DISCONNECT SWITCH, 60 AMP RATED, HP RATED FOR

MOTORS NEMA ENCLOSURE RATING(3R) AS SHOWN. 3R: RAIN TIGHT.

60

3R

DUPLEX RECEPTACLE, NEMA CONFIGURATION 5-20R

ABOVE COUNTER DUPLEX RECEPTACLE, MOUNT CENTER AT 44" AFFC

S 20A, 120/277VAC SINGLE POLE SNAP SWITCH

S 20A, 120/277VAC THREE WAY SNAP SWITCH

3

S ULTRASONIC CEILING SENSOR

S

LIGHT SWITCH/OCCUPANCY SENSOR, INFARED

SWITCHED CIRCUIT

UNSWITCHED CIRCUIT

HOMERUN CIRCUIT TO PANEL - CIRCUIT INDICATED

EXISTING EQUIPMENT

NEW EQUIPMENT

OCCUPANCY SENSOR, DUAL UV/IROS

I

STANDARD MOUNTING HEIGHTS FOR DEVICES

(ALL DIMENSIONS ARE TO CENTERLINE OF DEVICE AFF OR AFG)

POWER

1'-6"RECEPTACLES - GENERAL

RECEPTACLES - COUNTER* 3' TO 3'-9" OR 4" ABOVE BACK SPLASH

RECEPTACLES - REFRIGERATOR 3' TO 3'-9"

RECEPTACLES - TV OR MONITOR ON WALL 6' TO 8'

RECEPTACLES - TV OR MONITOR ON WALL 6' TO 8'

AUDIO/VISUAL

TELEPHONE/DATA - GENERAL 1'-6"

TELEPHONE/DATA - COUNTER* 3' TO 3'-9" OR 4" ABOVE BACK SPLASH

TELEPHONE/DATA - ON WALL 48" TO 54"

COAX/DATA - GENERAL 1'-6"

COAX/DATA - ON WALL FOR AV 6' TO 8'

PANEL BOARDS 100 - 400 AMP 6'-6" TO 7'

DISTRIBUTION PANELS 400 - 1,200 AMP 7'-8"

HIGHEST BREAKER HANDLE 6' TO 6'-5"

LIGHTING

EXIT SIGNS 8' TO 10', DO NOT EXCEED 12'

EMERGENCY LIGHTS 8' TO 10'

LIGHTS - GENERAL 7'-8" MINIMUM

LIGHTS - HALLWAY WALLS 6'-8" MINIMUM

LIGHT SWITCHES/DIMMERS 45"

LIGHT SWITCHES/DIMMERS, 2 ROWS TOP 54" MAXIMUM

PHOTOCELLS 8' TO 10'

SECURITY/MOTION LIGHTS 9' TO 12'

OUTDOOR WALL MOUNTED LIGHTS 8' TO 12'

MISCELLANEOUS

MOTION DETECTORS 8' TO 10'

TIME CLOCKS/CONTROL PANELS 6'

CONTROL STATIONS 45"

* COORDINATE WITH ARCHITECTURAL DETAILS

GENERAL FIRE ALARM LEGEND

SYMBOL DESCRIPTION

EXISTING EQUIPMENT

NEW EQUIPMENT

PFIRE ALARM PULL STATION, MOUNT AT 45" AFF

PHOTOELECTRIC SMOKE DETECTOR, MOUNT 3' FROM AIR GRILLES

RETURN AIR DUCT PHOTOELECTRIC SMOKE DETECTOR, FURNISHED

AND WIRED BY EC, INSTALLED BY MC

1

15

FIRE ALARM HORN/STROBE. WATTAGE AND CANDELA RATING INDICATED,

MOUNT AT 90" - 96" AFF

30

FIRE ALARM STROBE OR INDICATOR, CANDELA RATING IS 15 UNLESS

OTHERWISE INDICATED, MOUNT AT 90" - 96" AFF

R

REMOTE ALARM INDICATOR FOR DUCT SMOKE DETECTOR,

MOUNT AT 54" AFF

DHELECTRIC DOOR HOLDER

PPULL BOX

C

FIRE ALARM SYSTEM ADDRESSABLE CONTROL RELAY, MOUNT WITHIN

18" OF DEVICE BEING CONTROLLED

1 HR FIRE WALL

ABBREVIATIONS

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDING UNIT

AL ALUMINUM

ATC ASTRONOMICAL TIME CLOCK

ATS AUTOMATIC TRANSFER SWITCH

BFG BELOW FINISHED GRADE

C CONDUIT (AND DEVICE COUNTER HEIGHT)

CU COPPER

EF EXHAUST FAN

EX EXIT SIGN

EXK EXISTING TYPE K

G GROUND

DS DISCONNECT SWITCH

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

N NEUTRAL

NIC NOT IN CONTRACT

PE PHOTOCELL

PNL PANELBOARD

RSC RIGID STEEL CONDUIT

SC SPRINKLER CONTRACTOR

SS SURGE SUPPRESSOR

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

UON UNLESS OTHERWISE NOTED

W WET LOCATION RATED

WIR WIRE (SIZE/RATING)