WEIGHT AND DIMENSION24 Kg
: 350 mm: 167 mm: 180 mm: 183 mm
COVER AND CONTAINER: A.B.S. UL94-HB, UL94-V0 Optional.: NSAP 12-80 Ah: F11/F15
OTHER-20°C to 60°C Discharge0°C to 50°C Charge-20°C to 60°C Storage
PT. NIPRESS TbkJl. Raya Narogong Km. 2616710 Klapanunggal - Bogor
TECHNICAL SHEET
Battery WeightLength
NSAP 12-80 Ah is a top terminal battery with AGM technology is specially designed for Telecom use with over 10 years design life at 25 °C. NSAP type also comply with IEC 60896-21/22, standard battery for telecommunication. The adoption of centralized venting system make sure the battery can be installed in any location and guarantees high security and reliability.
DIMENSIONS
Terminal
Operating Temperature
Range
Self Discharge
: NSAP batteries can be stored for more than 6 months
batteries before using
: 5.5 mΩ (at 1KHz)
Recommended Maximum Charging Current Limit
at 25°C. Self-discharge ratio
PERFORMANCE
TERMINAL SIZE
VIEW
NSAP 12-80
WidthContainer Height
Total Height
: Approximate
Material
Type
: 24 A
: 14.6 to 14.8 VDC/unit@25°C
Nominal Voltage
Max Discharge CurrentInternal Resistance
: 12 V: 80 Ah: 800 A (5 sec)
less than 3% per month at 25°C. Please charge
Capacity 10 h (C10)
Float charging Voltage
Equalization and Cycle Service
Normal Operating Temp. Range : 25°C±5°C: 13.6 to 13.8 VDC/unit@25°C
5
M6Ø14
20
7.518
8
Ø8.5
167350
180 183
Constan Current Discharge (Amperes) at 25 °C5 min 10 min 15 min 30 mim 1 h 2 h 3h 4 h 5 h 8 h 10 h 20 h182.70 142.40 116.80 70.68 46.41 28.08 19.57 15.46 13.53 8.93 7.91 3.95213.90 159.30 130.20 73.47 47.53 29.26 19.96 15.96 13.62 9.00 8.01 4.12237.00 174.70 141.20 75.98 48.20 29.50 20.20 16.24 13.69 9.04 8.08 4.16264.00 189.30 148.30 78.14 48.80 29.89 20.38 16.49 13.81 9.12 8.16 4.24272.00 196.20 150.70 79.35 49.27 30.21 20.56 16.65 13.90 9.20 8.24 4.32280.10 206.20 153.80 80.38 49.93 30.83 20.95 16.89 14.02 9.24 8.32 4.41
Constant Power Discharge (Watt/cell) at 25 °C5 min 10 min 15 min 30 mim 1 h 2 h 3h 4 h 5 h 8 h 10 h 20 h
2086.00 1609.00 1295.00 839.60 550.70 334.20 233.30 185.60 162.80 107.20 95.19 47.972375.00 1779.00 1439.00 863.30 559.10 347.20 237.30 188.30 163.40 108.00 96.24 49.752607.00 1930.00 1556.00 884.20 566.30 349.80 240.00 194.80 164.20 108.40 97.20 50.232864.00 2073.00 1632.00 902.60 570.00 354.30 241.90 197.50 165.50 109.40 98.16 51.202897.00 2129.00 1650.00 910.50 573.40 356.90 243.00 199.40 166.50 110.20 99.04 52.172955.00 2196.00 1677.00 920.10 578.70 361.30 246.70 202.20 168.00 110.60 99.83 53.09
All mentioned values are average values ( Tolerance ± 2 %)
1.60 V/cell
1.65 V/cell1.60 V/cell
F.V/Time1.85 V/cell1.80 V/cell1.75 V/cell1.70 V/cell
F.V/Time1.85 V/cell1.80 V/cell1.75 V/cell1.70 V/cell1.65 V/cell
Storage Characteristic
TECHNICAL SHEET
Graphic Life Cycle
Charge characteristic curve for cyclic use Discharge Characteristic Curve
Effect of Temperature Temperature Effects in Relation of Battery Capacity
Supplementary charge required(Carry out supplementary charge before use if 100% capacity is requires)
Supplementary charge requiredbefore use.This supplementary charge will help to recover the capacity and should be made as early as possible.
Supplementary charge may oftenfail to recover the capacity.The battery should never be left standing till this state is reached
Supplementary charge and storage guidelines
30℃
Storage Time (months)
20
0
Cap
acity
(%)
40
60
100
80
40℃
10℃
0℃
2 4 6 8 10 12 14 16 18 20 22 24
20℃
0.1CA0.25CA0.6CA
-30 -20 -10 0 10 20 30 40 50 60Temperature (°C)
20
40
60
80
100
120
Cap
acity
(%
)
5000
DOD
(%)
Cycles1000 1500 2000
102030405060708090
100
150
3
5
10
Desig
n Life
(years
)
Temperature (°C)
20 25 30 35 40 45 50
12
4
6789
1112