ITM UNIVERSIT PROJECT REPOR VOCATIONAL TRAINING AT Kanti Bijlee Utpadan Nigam Limite (A Joint Venture Of NTPC Ltd. & BSE Kanti , Muzaffarpur FROM 20/05/2015 TO 06/06/2015 SUBMITTED BY- ROHAN KUMAR ROLL NO-BETN1EE12020 B.TECH(ELECTRICAL ENGG.)
Transcript
Page 1: Ntpc Project Report(summer training )

ITM UNIVERSITYPROJECT REPORT

VOCATIONAL TRAINING ATKanti Bijlee Utpadan Nigam Limited .

(A Joint Venture Of NTPC Ltd. & BSEB)Kanti , Muzaffarpur

FROM 20/05/2015 TO 06/06/2015

SUBMITTED BY-

ROHAN KUMAR

ROLL NO-BETN1EE12020

B.TECH(ELECTRICAL ENGG.)

“VI” SEM

ITM UNIVERSITY GWALIOR(M.P)

Page 2: Ntpc Project Report(summer training )

PROJECT REPORTVOCATIONAL TRAINING AT

Kanti Bijlee Utpadan Nigam Limited .(A Joint Venture Of NTPC Ltd. & BSEB)

Kanti , Muzaffarpur.

FROM 20/05/2015 TO 06/06/2015

SUBMITTED BY-

ROHAN KUMAR

ROLL NO-BETN1EE12020

B.TECH(ELECTRICAL ENGG.)

“VI” SEM

ITM UNIVERSITY GWALIOR(M.P)

Page 3: Ntpc Project Report(summer training )

ACKNOWLEDGMENTI am highly indebted to HOD of C& I Department, all faculty members of department for providing me an opportunity to have practical exposure at KBUNL/MTPS Kanti (Joint venture of NTPC Ltd & BSEB) I express my sincere thanks to A.CHARKBORTY for giving me an opportunity to take such valuable vacational training in his department.

I also pay my sincere gratitude to Sh.J P Kushwaha (Dy. MGR,C&I) , Sh. Anjani Kr Verma (Asst. MGR,C&I), Sh. R N Verma (Asst. MGR,C&I), Vikas Kumravat(Asst. MGR,C&I) & Vikas Koshta(Asst. MGR,C&I) for their continuous assistance, guidence and valuable suggestions .

Last but not the least I am also thankful to Sh. Arun Kr Singh for his contribution.

My special thanks to HR deptt for faciliating me to impart training at this project.

Submitted by-

ROHAN KUMAR

B.TECH(ELECTRICAL ENGG.)

ITM UNIVERSITY GWALIOR(M.P)

ROLL NO-BETN1EE12020

Page 4: Ntpc Project Report(summer training )

ABSTRACT Any thermal power plant is converting the chemical energy of fossil fuel (coal) into electrical energy. The process involved for this conversion is based upon the Modified Rankine Cycle.

The major components that are used to accomplish the modified rankine cycle are

Boiler feed pump, The steam generator water walls (evaporator), Steam generator super heaters, Steam turbine, Reheater, Condenser, Regenerative feed heaters etc.

All components of a power generating cycle are vital and critical in operation. In Modified Rankin Cycle, the two most important aspects that is added are reheating & regenerative heating. By reheating we used to send the steam coming from exhaust of the turbines back to the reheater of the boiler so that its enthalpy increases and more work can be done by this steam the other purpose is to make steam dry so that no harm will be done to the blades of the turbine. In MTPS Kanti, we have three turbines in Tandem coupling namely one H.P Turbine, one I.P Turbine & one L.P Turbine coupled with the generator to which is synchronized with the grid to produce electricity at 50Hz.

In all my modesty, I wish to record here that a sincere attempt has been made for the presentation of this project report. I also trust that this study will not only prove to be of academic interest but also will be able to provide an insight into the area of technical management.

Page 5: Ntpc Project Report(summer training )

INDEXCONTENT PAGE NO.ABOUT NTPC LTD.--------------------------------------------

ABOUT KBNUL , KANTI--------------------------------------

OPERATION OF POWER PLANT--------------------------

PARTS OF POWER PLANT-----------------------------------

VARIOU CYCLE OCCUR IN POWER PLANT-----------

ELECTRICAL MAINTENANCE------------------------------

1 MOTOR----------------------------------------------------------------------

2.HIGH TENSION/LOW TENSION SWITCHGEAR----------------

3. COAL HANDLING PLANT-----------------------------------------------

4. TRANSFORMER-------------------------------------------------------------

5. GENERATOR-------------------------------------------------------------------

6. SWITCH YARD-----------------------------------------------------------------

CONTROL SYSTEM OF POWER PLANT----------------------

Page 6: Ntpc Project Report(summer training )

ABOUT NTPC India largest power company, NTPC was set up in 1975 to accelerate power development in India. NTPC is emerging as a diversified power major with presence in the entire value chain of the power generation business. Apart from power generation, which is the mainstay of the company, NTPC has already ventured into consultancy, power trading, ash utilization and coal mining. NTPC ranked 341st in the „2010, Forbes Global 2000‟ ranking of the World‟s biggest companies. NTPC became a Maharatna company in May, 2010, one of the only four companies to be awarded this status.

The total installed capacity of the company is 39,174 MW (including JVs) with 16 coal based and 7 gas based stations, located across the country. In addition under JVs, 7 stations are coal based & another station uses naptha/LNG as fuel. The company has set a target to have an installed power generating capacity of 1,28,000 MW by the year 2032. The capacity will have a diversified fuel mix comprising 56% coal, 16% Gas, 11% Nuclear and 17% Renewable Energy Sources(RES) including hydro. By 2032, non-fossil fuel based generation capacity shall make up nearly 28% of NTPC portfolio. NTPC has been operating its plants at high efficiency levels. Although the company has 17.75% of the total national capacity, it contributes 27.40% of total power generation due to its focus on high efficiency.

In October 2004, NTPC launched its Initial Public Offering (IPO) consisting of 5.25% as fresh issue and 5.25% as offer for sale by Government of India. NTPC thus became a listed company in November 2004 with the Government holding 89.5% of the equity share capital. In February 2010, the Shareholding of Government of India was reduced from 89.5% to 84.5% through Further Public Offer. The rest is held by Institutional Investors and the Public.

Page 7: Ntpc Project Report(summer training )

Strategies of NTPC

Vision “To be the world‟s largest and best power producer,

powering India‟s growth.”

Page 8: Ntpc Project Report(summer training )

Mission“Develop and provide reliable power, related products and services at competitive prices, integrating multiple energy sources with innovative and eco-friendly technologies and contribute to society.”

Core value-BE COMMITTED

B --------------------- Business EthicsE---------------------- Environmentally &

Economically Sustainable

C--------------------- Customer Focus O-------------------- Organizational &

Professional Pride M-------------------- Mutual Respect &

Trust M-------------------- Motivating Self &

othersI ------------------ Innovation &

Speed T------------------ Total Quality

for Excellence T------------------ Transparent &

Respected Organization

E ---------------- Enterprising D----------------- Devoted

“NTPC is the second largest owner of trees in the country after the Forest department”

Page 9: Ntpc Project Report(summer training )

Kanti Thermal Power StationKanti Thermal Power Station is located in Kanti, Muzaffarpur,90 km away from Patna, the capital of the Indian state of Bihar.It is managed by the Kanti Bijlee Utpadan Nigam Ltd (KBUN),-a joint venture between NTPC and BSEB Patna.The majority shares of the Joint Venture Company is hold by NTPC,with NTPC 64.57% and BSEB 35.43%.The plant has not been functional since 2003, however three successful trial runs have paved way for commercial production of Electricity by the end of 2013. In November 2013,Nitish Kumar said that another new 500MW power plant will be set up at Kanti. The first 195 MW unit was commissioned by BHEL at the 2x195 MW plant in May 2015.

HistoryFirst started in 1985, Kanti Power Plant has an installed capacity of 110×2 MW. An additional capacity of 195×2 MW is being erected and is due to be completed by December 2014.Bihar is the most power stricken state of India; and in the issue of uplifting our current nation, an excellent and clean 'Thermal Power station' is a necessity. Kanti thermal Power Plant came into existence in 1985 with the efforts of then MP of Muzaffarpur, 

OperationsTo take over Muzaffarpur Thermal Power Station (2*110MW), a subsidiary company named ‘Vaishali Power Generating Company Limited (VPGCL)’ with NTPC on 06/09/2006,-contributing 51% of equity; and the balance equity was contributed by Bihar State Electricity Board. The company was rechristened as ‘Kanti Bijlee Utpadan Nigam Limited’ on April 10, 2008. Present equity holding is 64.57% by NTPC & 35.43% by BSEB. The company is renovating and modernising the existing unit.The total cost of its renovation and modernization has been over Rs. 500 Crores.The station has an installed capacity of 2 X 110 MW. Both the units are under renovation and modernization.An additional capacity of 220MWx2 is being erected and is due to be completed by December 2014.In March 2013, the renovation work of two old units was completed.MTPS started commercial production from November 1, 2013 by sypplying 94 MW.This is first generation in 11 years since 2002.

Page 10: Ntpc Project Report(summer training )

StageUnit

Number

Installed Capacity

(MW)

Date of Commissioning

Status

Stage-1 1 110 1985 March

This unit went down in 2003 and then its renovation started by Bharat Heavy Electricals in April 2008 and is now running at full capacity since November 2013 .

Stage-1 2 110 1986 March

This unit too is non functional since 2003 and is also undergoing renovation by Bharat Heavy Electricals. But, since 14 November 2014 this unit has been functional after the renovation and modernisation work. Till now KBUNL has an installed capacity of 220 MW.

Stage-2 3 195 5th May, 2015 The original planned capacity of the unit was 250 MW but was reduced to 195 MW Scheduled after Airport Authority of India raised concern over its chimney height.

Page 11: Ntpc Project Report(summer training )

StageUnit

Number

Installed Capacity

(MW)

Date of Commissioning

Status

Bhel commissioned the first 195MW unit at Muzaffarpur Thermal Power Station in India on 5th May, 2015. The commissioning is the first of the two units at 390MW Muzaffarpur Thermal Power Station (TPS).

Stage-2 4 195Under Construction

Original planned capacity was 250 MW but reduced to 195 MW.

Total 610

OPERATION OF A POWER PLANT

Page 12: Ntpc Project Report(summer training )

Basic Principle: As per FARADAY’s Law-“Whenever the amount of magnetic flux linked with a circuit changes, an EMF is produced in the circuit. Generator works on the principle of producing electricity. To change the flux in the generator turbine is moved in a great speed with steam.” To produce steam, water is heated in the boilers by burning the coal.

In kanti bijlee utpadan nigam limited(A Subsidiary ofNTPC Ltd. Kanti Muzaffarpur) steam is produced and used to spin a turbine that operates a generator. Water is heated, turns into steam and spins a steam turbine which drives an electrical generator. After it passes through the turbine, the steam is condensed in a condenser; this is known as a Rankine cycle.

The electricity generated at the plant is sent to consumers through high-voltage power lines The In kanti bijlee utpadan nigam limited has Steam Turbine-Driven Generators which has a collective capacity of 220Mw(2*110Mw).

Page 13: Ntpc Project Report(summer training )

Basic Steps of Electricity GenerationThe basic steps in the generation of electricity from coal involves following steps:# Coal to steam# Steam to mechanical power# Mechanical power to electrical power

Coal to Electricity : Basics

Page 14: Ntpc Project Report(summer training )
Page 15: Ntpc Project Report(summer training )

Mechnical power to Electrical power

As blade of turbine rotate, the shaft of generator, which is coupled to the turbine also rotate.it result rotation of coil of the generator, which cause induced electricity to produce.

Page 16: Ntpc Project Report(summer training )

PARTS OF A POWER PLANT

The various parts are listed below:-

1.Cooling tower 2. Cooling water pump

3. Transmission line (3-phase)                           4. Unit transformer (3-phase)

5. Electric generator (3-phase) 6. Low pressure turbine

7. Condensate extraction pump 8. Condenser

9. Intermediate pressure turbine 10. Steam governor valve 11. High pressure turbine 12. Deaerator

13. Feed heater 14. Coal conveyor 15. Coal hopper 16. Pulverised fuel mill 17. Boiler drum 18. Ash hopper 19. Super heater 20. Forced draught fan 21. Reheater 22. Air intake 23. Economiser 24. Air preheater 25. Precipitator 26. Induced

27. Flue Gas

1. Cooling TowerCooling towers are heat removal devices used to transfer process waste heat to the atmosphere. Cooling towers may either use the evaporation of water to remove process heat and cool the working fluid to near the wet-bulb air temperature or in the case of closed circuit dry cooling towers rely solely on air to cool the working fluid to near the dry-bulb air temperature. Common applications include cooling the circulating water used in oil refineries, chemical plants, power stations and building cooling. The towers vary in size from small roof-top units to very large hyperboloid structures that can be up to 200 meters tall and 100 meters in diameter, or rectangular structures that can be over 40 meters tall and 80 meters long.

Page 17: Ntpc Project Report(summer training )

Smaller towers are normally factory-built, while larger ones are constructed on site. The absorbed heat is rejected to the atmosphere by the evaporation of some of the cooling water in mechanical forced-draft or inducedDraft towers or in natural draft hyperbolic shaped cooling towers as seen at most nuclear power plants.

2. Cooling Water Pump

it pumps the water from the cooling tower which goes to the condenser.

3. Three phase transmission line Three phase electric power is a common method of electric power transmission. It is a type of polyphase system mainly used to power motors and many other devices. A three phase system uses less conductive material to transmit electric power than equivalent single phase, two phase, or direct current system at the same voltage. In a three phase system, three circuits reach their instantaneous peak values at different times. Taking current in one conductor as the reference, the currents in the other two are delayed in time by one-third and two-third of one cycle .This delay between “phases” has the effect of giving constant power transfer over each cycle of the current and also makes it possible to produce a rotating magnetic field in an electric motor. At the power station, an electric generator converts mechanical power into a set of electric currents, one from each electromagnetic coil or winding of the generator. The current are sinusoidal functions of time, all at the same frequency but offset in time to give different phases. In a three phase system the phases are spaced equally, giving a phase separation of one-third of one cycle. Generators output at a voltage that ranges from hundreds of volts to 30,000 volts.

4. Unit transformer (3-phase) At the power station, transformers step-up this voltage to one more suitable for transmission. After numerous further conversions in the transmission and distribution network the power is finally transformed to the standard mains voltage (i.e. the “household” voltage). The power may already have been split into single phase at this point or it may still be three phase. Where the step-down is 3 phase, the output of this transformer is usually star connected with the standard mains voltage being the phase-23 neutral voltage. Another system commonly seen in North America is to have a delta connected secondary with a center tap on one of the windings supplying the ground and neutral. This allows for 240 V three phase as well as three different single phase voltages( 120 V between

Page 18: Ntpc Project Report(summer training )

two of the phases and neutral , 208 V between the third phase ( or wild leg) and neutral and 240 V between any two phase) to be available from the same supply.

5. Electrical generator An Electrical generator is a device that converts kinetic energy to electrical energy, generally using electromagnetic induction. The task of converting the electrical energy into mechanical energy is accomplished by using a motor. The source of mechanical energy maybe water falling through the turbine or steam turning a turbine (as is the case with thermal power plants). There are several classifications for modern steam turbines. Steam turbines are used in our entire major coal fired power stations to drive the generators or alternators, which produce electricity. The turbines themselves are driven by steam generated in "boilers “or "steam generators" as they are sometimes called. Electrical power stations use large steam turbines driving electric generators to produce most (about 86%) of the world‟s electricity. These centralized stations are of two types: fossil fuel power plants and nuclear power plants. The turbines used for electric power generation are most often directly coupled to their-generators .As the generators must rotate at constant synchronous speeds according to the frequency of the electric power system, the most common speeds are 3000 r/min for 50 Hz systems, and 3600 r/min for 60 Hz systems. Most large nuclear sets rotate at half those speeds, and have a 4-pole generator rather than the more common 2-pole one.

6. Low Pressure Turbine Energy in the steam after it leaves the boiler is converted into rotational energy as it passes through the turbine. The turbine normally consists of several stages with each stages consisting of a stationary blade (or nozzle) and a rotating blade. Stationary blades convert the potential energy of the steam into kinetic energy and direct the flow onto the 24 rotating blades. The rotating blades convert the kinetic energy into impulse and reaction forces, caused by pressure drop, which results in the rotation of the turbine shaft. The turbine shaft is connected to a generator, which produces the electrical energy. Low Pressure Turbine (LPT) consists of 4x2 stages. After passing through Intermediate Pressure Turbine steam is passed through LPT which is made up of two parts- LPC REAR & LPC FRONT. As water gets cooler here it gathers into a HOTWELL placed in lower parts of turbine.

Page 19: Ntpc Project Report(summer training )

7. Condensation Extraction Pump A Boiler feed water pump is a specific type of pump used to pump water into a steam boiler. The water may be freshly supplied or returning condensation of the steam produced by the boiler. These pumps are normally high pressure units that use suction from a condensate return system and can be of the centrifugal pump type or positive displacement type. Construction and operation: Feed water pumps range in size up to many horsepower and the electric motor is usually separated from the pump body by some form of mechanical coupling. Large industrial condensate pumps may also serve as the feed water pump. In either case, to force the water into the boiler, the pump must generate sufficient pressure to overcome the steam pressure developed by the boiler. This is usually accomplished through the use of a centrifugal pump. Feed water pumps usually run intermittently and are controlled by a float switch or other similar level-sensing device energizing the pump when it detects a lowered liquid level in the boiler. Some pumps contain a two-stage switch. As liquid lowers to the trigger point of the first stage, the pump is activated. If the liquid continues to drop, (perhaps because the pump has failed, its supply has been cut off or exhausted, or its discharge is blocked) the second stage will be triggered. This stage may switch off the boiler equipment (preventing the boiler from running dry and overheating), trigger an alarm, or both. 25

Page 20: Ntpc Project Report(summer training )

8. Condenser The steam coming out from the Low Pressure Turbine (a little above its boiling pump) is brought into thermal contact with cold water (pumped in from the cooling tower) in the condenser, where it condenses rapidly back into water, creating near Vacuum-like conditions inside the condenser chest.

9. Intermediate Pressure Turbine Intermediate Pressure Turbine (IPT) consists of 11 stages. When the steam has been passed through HPT it enters into IPT. IPT has two ends named as FRONT & REAR. Steam enters through front end and leaves from Rear end.

10. Steam Governor Valve Steam locomotives and the steam engines used on ships and stationary applications such as power plants also required feed water pumps. In this situation, though, the pump was often powered using a small steam engine that ran using the steam produced by the boiler a means had to be provided, of course, to put the initial charge of water into the boiler (before steam power was available to operate the steam-powered feed water pump).The pump was often a positive displacement pump that had steam valves and cylinders at one end and feed water cylinders at the other end; no crankshaft was required. In thermal plants, the primary purpose of surface condenser is to condense the exhaust steam from a steam turbine to obtain maximum efficiency and also to convert the turbine

Page 21: Ntpc Project Report(summer training )

exhaust steam into pure water so that it may be reused in the steam generator or boiler as boiler feed water. By condensing the exhaust steam of a turbine at a pressure below atmospheric pressure, the steam pressure drop between the inlet and exhaust of the turbine is increased, which increases the amount heat available for conversion to mechanical power. Most of the heat liberated due to condensation of the exhaust steam is carried away by the cooling medium (water or air) used by the surface condenser. Control valves are valves used within industrial plants and elsewhere to control operating conditions such as temperature, pressure, flow and liquid level by fully or partially opening or closing in response to signals received from controllers that compares a “set point” to a 26 “process variable” whose value is provided by sensors that monitor changes in such conditions. The opening or closing of control valves is done by means of electrical, hydraulic or pneumatic systems.

11.High Pressure Turbine Steam coming from Boiler directly feeds into HPT at a temperature of 540°C and at a pressure of 136 kg/cm2. Here it passes through 12 different stages due to which its temperature goes down to 329°C and pressure as 27 kg/cm2. This line is also called as CRH – COLD REHEAT LINE. It is now passed to a REHEATER where its temperature rises to 540°C and called as HRH-HOT REHEATED LINE.

12. Deaerator A Deaerator is a device for air removal and used to remove dissolved gases (an alternate would be the use of water treatment chemicals) from boiler feed water to make it noncorrosive. A dearator typically includes a vertical domed deaeration section as the deaeration boiler feed water tank. A Steam generating boiler requires that the circulating steam, condensate, and feed water should be devoid of dissolved gases, particularly corrosive ones and dissolved or suspended solids. The gases will give rise to corrosion of the metal. The solids will deposit on the heating surfaces giving rise to localized heating and tube ruptures due to overheating. Under some conditions it may give rise to stress corrosion cracking. Deaerator level and pressure must be controlled by adjusting control valves the level by regulating condensate flow and the pressure by regulating steam flow. If operated properly, most deaerator vendors will guarantee that oxygen in the deaerated water will not exceed 7 ppb by weight (0.005 cm3/L)

Page 22: Ntpc Project Report(summer training )

13. Feed water heater A Feed water heater is a power plant component used to pre-heat water delivered to a steam generating boiler. Preheating the feed water reduces the irreversibility involved in steam generation and therefore improves the thermodynamic efficiency of the system. This reduces plant operating costs and also helps to avoid thermal shock to the boiler 27 metal when the feed water is introduced back into the steam cycle. In a steam power (usually modelled as a modified Rankine cycle), feed water heaters allow the feed water to be brought up to the saturation temperature very gradually. This minimizes the inevitable irreversibility associated with heat transfer to the working fluid (water).

14. Coal conveyor Coal conveyors are belts which are used to transfer coal from its storage place to Coal Hopper. A belt conveyor consists of two pulleys, with a continuous loop of material- the conveyor Belt – that rotates about them. The pulleys are powered, moving the belt and the material on the belt forward. Conveyor belts are extensively used to transport industrial and agricultural material, such as grain, coal, ores etc.

15. Coal Hopper Coal Hoppers are the places which are used to feed coal to Fuel Mill. It also has the arrangement of entering Hot Air at 200°C inside it which solves our two purposes:- 1. If our Coal has moisture content then it dries it so that a proper combustion takes place. 2. It raises the temperature of coal so that its temperature is more near to its Ignite Temperature so that combustion is easy.

16. Pulverized Fuel Mill A pulveriser is a device for grinding coal for combustion in a furnace in a fossil fuel power plant.

17. Boiler drum Steam Drums are a regular feature of water tube boilers. It is reservoir of water/steam at the top end of the water tubes in the water-tube boiler. They store the steam generated in the water tubes and act as a phase separator for the steam/water mixture. The difference in densities between hot and cold water helps in the accumulation of the “hotter”- water/and saturated –steam into steam drum. Made from high-grade steel (probably 28 stainless) and its working involve temperature of 390°C and pressure well above 350psi (2.4MPa). The separated steam is drawn out from the top section of the drum. Saturated steam is drawn off the top of the drum. The steam will re-enter the furnace in through a super heater, while the saturated water at the bottom of steam drum flows down to the mud-

Page 23: Ntpc Project Report(summer training )

drum /feed water drum by down comer tubes accessories include a safety valve, water level indicator and fuse plug.

18. Ash Hopper A steam drum is used in the company of a mud-drum/feed water drum which is located at a lower level. So that it acts as a sump for the sludge or sediments which have a tendency to accumulate at the bottom.

19. Super Heater A Super heater is a device in a steam engine that heats the steam generated by the boiler again increasing its thermal energy. Super heaters increase the efficiency of the steam engine, and were widely adopted. Steam which has been superheated is logically known as superheated steam; non- superheated steam is called saturated steam or wet steam. Super heaters were applied to steam locomotives in quantity from the early 20th century, to most steam vehicles, and also stationary steam engines including power stations.

20. Force Draught Fan External fans are provided to give sufficient air for combustion. The forced draught fan takes air from the atmosphere and, warms it in the air preheater for better combustion, injects it via the air nozzles on the furnace wall.

21. Reheater Reheater is a heater which is used to raise the temperature of steam which has fallen from the intermediate pressure turbine. 29

22. Air Intake Air is taken from the environment by an air intake tower which is fed to the fuel.

23. Economizers Economizer, or in the UK economizer, are mechanical devices intended to reduce energy consumption, or to perform another useful function like preheating a fluid. The term economizer is used for other purposes as well-Boiler, power plant, heating, ventilating and air-conditioning. In boilers, economizer are heat exchange devices that heat fluids , usually water, up to but not normally beyond the boiling point of the fluid. Economizers are so named because they can make use of the enthalpy and improving the boiler‟s efficiency. They are devices fitted to a boiler which save energy by using the exhaust gases from the boiler to preheat the cold water used to fill it (the feed water). Modern day boilers, such as those in cold fired power stations, are still fitted with economizer which is decedents of Green‟s original design. In this context there are turbines before it is

Page 24: Ntpc Project Report(summer training )

pumped to the boilers. A common application of economizer in steam power plants is to capture the waste heat from boiler stack gases (flue gas) and transfer thus it to the boiler feed water thus lowering the needed energy input , in turn reducing the firing rates to accomplish the rated boiler output . Economizer lower stack temperatures which may cause condensation of acidic combustion gases and serious equipment corrosion damage if care is not taken in their design and material selection.

24. Air Preheater Air preheater is a general term to describe any device designed to heat air before another process (for example, combustion in a boiler). The purpose of the air preheater is to recover the heat from the boiler flue gas which increases the thermal efficiency of the boiler by reducing the useful heat lost in the flue gas. As a consequence, the flue gases are also sent to the flue gas stack (or chimney) at a lower temperature allowing simplified design of the ducting and the flue gas stack. It also allows control over the temperature of gases leaving the stack. 30

25. Precipitator An Electrostatic precipitator (ESP) or electrostatic air cleaner is a particulate device that removes particles from a flowing gas (such as air) using the force of an induced electrostatic charge. Electrostatic precipitators are highly efficient filtration devices, and can easily remove fine particulate matter such as dust and smoke from the air steam. ESPs continue to be excellent devices for control of many industrial particulate emissions, including smoke from electricity-generating utilities (coal and oil fired), salt cake collection from black liquor boilers in pump mills, and catalyst collection from fluidized bed catalytic crackers from several hundred thousand ACFM in the largest coal-fired boiler applications. The original parallel plate-Weighted wire design (described above) has evolved as more efficient (and robust) discharge electrode designs, today focus is on rigid discharge electrodes to which many sharpened spikes are attached , maximizing corona production. Transformer –rectifier systems apply voltages of 50-100 Kilovolts at relatively high current densities. Modern controls minimize sparking and prevent arcing, avoiding damage to the components. Automatic rapping systems and hopper evacuation systems remove the collected particulate matter while on line allowing ESPs to stay in operation for years at a time.

Page 25: Ntpc Project Report(summer training )

26. Induced Draught Fan The induced draft fan assists the FD fan by drawing out combustible gases from the furnace, maintaining a slightly negative pressure in the furnace to avoid backfiring through any opening. At the furnace outlet and before the furnace gases are handled by the ID fan, fine dust carried by the outlet gases is removed to avoid atmospheric pollution. This is an environmental limitation prescribed by law, which additionally minimizes erosion of the ID fan.

27. Flue gas stack A Flue gas stack is a type of chimney, a vertical pipe, channel or similar structure through which combustion product gases called flue gases are exhausted to the outside air. Flue gases are produced when coal, oil, natural gas, wood or any other large combustion 31 device. Flue gas is usually composed of carbon dioxide (CO2) and water vapour as well as nitrogen and excess oxygen remaining from the intake combustion air. It also contains a small percentage of pollutants such as particulates matter, carbon mono oxide, nitrogen oxides and sulphur oxides. The flue gas stacks are often quite tall, up to 400 meters (1300 feet) or more, so as to disperse the exhaust pollutants over a greater area and thereby reduce the concentration of the pollutants to the levels required by government's environmental policies and regulations. The flue gases are exhausted from stoves, ovens, fireplaces or other small sources within residential abodes, restaurants, hotels through other stacks which are referred to as chimneys.

Page 26: Ntpc Project Report(summer training )

VARIOUS CYCLES AT POWER STATION

# PRIMARY AIR CYCLE

# SECONDARY AIR CYCLE

# COAL CYLCE

# ELECTRICITY CYCLE

# FLUE GAS CYCLE

# CONDENSATE CYCLE

# FEED WATER CYCLE

# STEAM CYCLE

Page 27: Ntpc Project Report(summer training )
Page 28: Ntpc Project Report(summer training )
Page 29: Ntpc Project Report(summer training )
Page 30: Ntpc Project Report(summer training )
Page 31: Ntpc Project Report(summer training )
Page 32: Ntpc Project Report(summer training )
Page 33: Ntpc Project Report(summer training )
Page 34: Ntpc Project Report(summer training )
Page 35: Ntpc Project Report(summer training )

ELECTRICAL MAINTENANCE DEPARTMENTElectrical maintenance include:

Motors

High Tension/Low Tension Switchgear

Coal handling plant

Generators

Transformers

Switch yard

MOTORS

Motors can be classified as AC and DC.

AC MOTORS

1. Squirrel cage motor

2. Wound motor

3. Slip ring induction motor

In modern thermal power plant three phase squirrel cage induction motors are used but sometime double wound motor is used when we need high starting torque e.g. in ball mill.

THREE PHASE INDUCTION MOTOR

Ns (speed) =120f/p

Stator can handle concentrated single layer winding, with each coil occupying one stator slot The most common type of winding are:

1. DISTRIBUTED WINDING : This type of winding is distributed over a number of slots.

2. DOUBLE LAYER WINDING : Each stator slot contains sides of two different coils

Page 36: Ntpc Project Report(summer training )

SQUIRREL CAGE INDUCTION MOTOR

Squirrel cage and wound cage have same mode of operation. Rotor conductors cut the rotating stator magnetic field. an emf is induced across the rotor winding, current flows, a rotor magnetic field is produced which interacts with the stator field causing a turning 43 motion. The rotor does not rotate at synchronous speed, its speed varies with applied load. The slip speed being just enough to enable sufficient induced rotor current to produce the power dissipated by the motor load and motor losses.

BEARINGS AND LUBRICATIONS

A good bearing is needed for trouble free operation of motor. Since it is very costly part of the motor, due care has to be taken by checking it at regular intervals. So lubricating plays an important role. Two types of lubricating are widely used

1. Oil lubrication

2. Grease lubrication

3. Insulation

INSULATION

Winding is an essential part so it should be insulated. Following types of insulation are widely used

TYPES OF INSULATION

CLASS TEMP UPTO WHICH THEY ARE EFFECTIVE

(DEGREE CENTIGRADE)

Y 90

A 105

E 120

B 130

F 155

Page 37: Ntpc Project Report(summer training )

H 180

C more than 180

# F class insulation is generally preferred.

MAIN MOTOR USED IN BOILER AND OFF SIDE AREA

1. ID FAN

It is located between EP and chimney used for creating induced draft in the furnace.

2. PA FAN

It is used for handling atmospheric air up to temperature 50 degree centigrade

3.FD FAN

It is used for handling secondary air for the boiler.

4. SCANNER FAN

It is required for requisite air for scanner cooling.

5. IGNITOR FAN

It supplies air for cooling of igniters.

INSTRUMENTS1. MICROMETER

This instrument is used for measuring inside as well as outside diameter of bearing.

2. MEGGAR

This instrument is used for measuring insulation resistance.

3. VIBRATION TESTER -- It measures the vibration of the motor. It is measured in three dimensions-axial, vertical and horizontal.

Page 38: Ntpc Project Report(summer training )

SWITCH GEARINTRODUCTION

Switchgear is one that makes or breaks the electrical circuit. It is a switching device that opens& closes a circuit that defined as apparatus used for switching, Lon rolling & protecting the electrical circuit & equipments. The switchgear equipment is essentially concerned with switching & interrupting currents either under normal or abnormal operating conditions. The tubular switch with ordinary fuse is simplest form of switchgear & is used to control & protect& other equipments in homes, offices etc. For circuits of higher ratings, a High Rupturing Capacity (H.R.C) fuse in condition with a switch may serve the purpose of controlling &protecting the circuit. However such switchgear cannot be used profitably on high voltage system (3.3 KV) for 2 reasons. Firstly, when a fuse blows, it takes some time to replace it &consequently there is interruption of service to customer. Secondly, the fuse cannot successfully interrupt large currents that result from the High Voltage System. In order to interrupt heavy fault currents, automatic circuit breakers are used. There are very few types of circuit breakers in B.P.T.S they are VCB, OCB, and SF6 gas circuit breaker. The most expensive circuit breaker is the SF6 type due to gas. There are various companies which manufacture these circuit breakers: VOLTAS, JYOTI, and KIRLOSKAR. Switchgear includes switches, fuses, circuit breakers, relays & other equipments.

THE EQUIPMENTS THAT NORMALLY FALL IN THIS CATEGORY ARE:-

1. ISOLATOR

An isolator is one that can break the electrical circuit when the circuit is to be switched on no load. These are used in various circuits for isolating the certain portion when required for maintenance etc. An operating mechanism box normally installed at ground level drives the isolator. The box has an operating mechanism in addition to its contactor circuit and auxiliary contacts may be solenoid operated pneumatic three phase motor or DC motor transmitting

Page 39: Ntpc Project Report(summer training )

through a spur gear to the torsion shaft of the isolator. Certain interlocks are also provided with the isolator

These are---

1. Isolator cannot operate unless breaker is open

2. Bus 1 and bus 2 isolators cannot be closed simultaneously

3. The interlock can be bypass in the event of closing of bus coupler breaker.

4. No isolator can operate when the corresponding earth switch is on

2. SWITCHING ISOLATOR

Switching isolator is capable of:

1. Interrupting charging current

2. Interrupting transformer magnetizing current

3. Load transformer switching.

Its main application is in connection with the transformer feeder as the unit makes it possible to switch gear one transformer while the other is still on load.

3.CIRCUIT BREAKER

One which can make or break the circuit on load and even on faults is referred to as circuit breakers. This equipment is the most important and is heavy duty equipment mainly utilized for protection of various circuits and operations on load. Normally circuit breakers installed are accompanied by isolators

4. LOAD BREAK SWITCHES

These are those interrupting devices which can make or break circuits. These are normally on same circuit, which are backed by circuit breakers

5. EARTH SWITCHES

Devices which are used normally to earth a particular system, to avoid any accident happening due to induction on account of live adjoining circuits. These

Page 40: Ntpc Project Report(summer training )

equipments do not handle any appreciable current at all. Apart from this equipment there are a number of relays etc. which are used in switchgear.

LT SWITCHGEAR

In LT switchgear there is no interlocking. It is classified in following ways:-

1. MAIN SWITCH

Main switch is control equipment which controls or disconnects the main supply. The main switch for 3 phase supply is available for the range 32A, 63A, 100A, 200Q, 300A at 500V grade.

2. FUSES

With Avery high generating capacity of the modern power stations extremely heavy carnets would flow in the fault and the fuse clearing the fault would be required to withstand extremely heavy stress in process. It is used for supplying power to auxiliaries with backup fuse protection. With fuses, quick break, quick make and double break switch fuses for 63A and 100A, switch fuses for 200A,400A, 600A, 800A and 1000A are used.

3. CONTACTORS

AC Contractors are 3 poles suitable for D.O.L Starting of motors and protecting the connected motors.

4. OVERLOAD RELAY

For overload protection, thermal overload relay are best suited for this purpose. They operate due to the action of heat generated by passage of current through relay element.

5. AIR CIRCUIT BREAKERS

It is seen that use of oil in circuit breaker may cause a fire. So in all circuits breakers at large capacity air at high pressure is used which is maximum at the time of quick tripping of contacts. This reduces the possibility of sparking. The pressure may vary from 50-60kg/cm^2 for high and medium capacity circuit breakers.

Page 41: Ntpc Project Report(summer training )

CONTACTORS

HT SWITCHGEAR

1. MINIMUM OIL CIRCUIT BREAKER

These use oil as quenching medium. It comprises of simple dead tank row pursuing projection from it. The moving contracts are carried on an iron arm lifted by a long insulating tension rod and are closed simultaneously pneumatic operating mechanism by means of tensions but throw off spring to be provided at mouth of the control the main current within the controlled device.

Type-HKH 12/1000c·

Rated Voltage-66 KV

Normal Current-1250A·

Frequency-5Hz·

Breaking Capacity-3.4+KA Symmetrical

3.4+KA Asymmetrical

360 MVA Symmetrical

Page 42: Ntpc Project Report(summer training )

Motor Voltage-220 V/DC

2. AIR CIRCUIT BREAKER

In this the compressed air pressure around 15 kg per cm^2 is used for extinction of arc caused by flow of air around the moving circuit . The breaker is closed by applying pressure at lower opening and opened by applying pressure at upper opening. When contacts operate, the cold air rushes around the movable contacts and blown the arc:

It has the following advantages over OCB:-

i. Fire hazard due to oil are eliminated.ii. Operation takes place quickly. iii. There is less burning of contacts since the duration is short and consistent. iv. Facility for frequent operation since the cooling medium is replaced

constantly. v. Rated Voltage-6.6 KV vi. Current-630 A vii. Auxiliary current-220 V/DC 51

3. SF6 CIRCUIT BREAKER

This type of circuit breaker is of construction to dead tank bulk oil to circuit breaker but the principle of current interruption is similar to that of air blast circuit breaker. It simply employs the arc extinguishing medium namely SF6. When it is broken down under an electrical stress, it will quickly reconstitute itself.

Circuit Breakers-HPA

Standard-1 EC 56

Rated Voltage-12 KV

Insulation Level-28/75 KV

Rated Frequency-50 Hz

Breaking Current-40 KA

Page 43: Ntpc Project Report(summer training )

Rated Current-1600 A

Making Capacity-110 KA

4.VACUUM CIRCUIT BREAKER

It works on the principle that vacuum is used to save the purpose of insulation and. In regards of insulation and strength, vacuum is superior dielectric medium and is better that all other medium except air and sulphur which are generally used at high pressure.

Rated frequency-50 Hz·

Rated making Current-10 Peak KA

Rated Voltage-12 KV

Supply Voltage Closing-220 V/DC

GENERATORS

The generator works on the principle of electromagnetic induction. There are two components stator and rotor. The rotor is the moving part and the stator is the stationary part. The rotor, which has a field winding, is given a excitation through a set of 3000rpm to give the required frequency of HZ. The rotor is cooled by Hydrogen gas, which is locally manufactured by the plant and has high heat carrying capacity of low density. If oxygen and hydrogen get mixed then they will form very high explosive and to prevent their combining in any way there is seal oil system. The stator cooling is done by de-mineralized (DM) water through hollow conductors. Water is fed by one end by Teflon tube. A boiler and a turbine are coupled to electric generators. Steam from the boiler is fed to the turbine through the connecting pipe. Steam drives the turbine rotor. The turbine rotor drives the generator rotor which turns the electromagnet within the coil of wire conductors.

Carbon dioxide is provided from the top and oil is provided from bottom to the generator. With the help of carbon dioxide the oil is drained out to the oil tank. Hydrogen gas is used to cool down the rotor.

Page 44: Ntpc Project Report(summer training )

Lube oil is used to cool the bearings.

DM water is used to cool the stator

Seal oil is used to prevent hydrogen leakage

Seal oil coolers are present to cool the seal oil

Hydrogen dryer are used which removes the moisture from hydrogen gas and then is supplied to the generator.

Clarified water in cooling tower is used to cool down the hydrogen gas

RATINGS OF THE GENERATORS USED

Turbo generator 110MW

The 110 MW generator generates 11.00 KV. The voltage is stepped up to 220 KV with the help of generator transformer and is connected to the grid

The voltage is stepped down to 6.6 KV with the help of UNIT AUXILLARY TRANSFORMER (UAT) and this voltage is used to drive the HT motors. The voltage is further stepped down to 415 V and then to 220 V and this voltage is used to drive Lt Motors.

TRANSFORMERSINTRODUCTION

It is a static machine which increases or decreases the AC voltage without changing the frequency of the supply. It is a device that:

Transfer electric power from one circuit to another.

It accomplishes this by electromagnetic induction.

In this the two electric circuits are in mutual inductive influence of each other

Page 45: Ntpc Project Report(summer training )

WORKING PRINCIPLE:

It works on FARADAY‟S LAW OF ELECTROMAGNETIC INDUCTION (self or mutual induction depending on the type of transformer)

MAIN PARTS:

1.CONSERVATOR

It is used generally to conserve the insulating property of the oil from deterioration& protect the transformer against failure on account of bad quality of oil.

2.SILICAGEL DEHYDRATING BREATHER

It is used to prevent entry of moisture inside the transformer tank. The breather consists of silica gel

Page 46: Ntpc Project Report(summer training )

3.GAS OPERATED RELAY (BUCHHOLZ RELAY) It is a gas actuated relay used for protecting oil immersed transformer against all types of faults. It indicates presence of gases in case of some minor fault & take out the transformer out of circuit in case of serious fault.

4. BUSHINGS It is made from highly insulating material to insulate & to bring out the terminals of the transformer from the container. The bushings are of 3 types:

a. Porcelain bushings used for low voltage transformer

b. Oil filled bushings used for voltage up to 33KV.

c. Condensed type bushings used for voltage above 33KV

5.OIL GUAGE

Every transformer with an oil guage to indicate the oil level. The oil guage may be provided with the alarm contacts which gave an alarm the oil level has dropped beyond permissible height due to oil leak etc.

6.TAPPINGS

The transformer are usually provided with few tappings on secondary side so that output voltage can be varied for constant input voltage.

7.RADIATORS

It increases the surface area of the tank & more heat is thus radiated in less time.

8.WINDINGS TEMPERATURE INDICATOR (OIL GUAGE)

Device which indicates the temperature of winding of transformer & possible damage to the transformer due too overload can be prevented.

COOLING OF TRANSFORMERS OF LARGE MVA

As size of transformer becomes large, the rate of the oil circulating becomes insufficient to dissipate all the heat produced & artificial means of increasing the

Page 47: Ntpc Project Report(summer training )

circulation by electric pumps. In very large transformers, special coolers with water circulation may have to be employed.

TYPES OF COOLING

Air cooling

1. Air Natural (AN)

2. Air Forced (AF)

Oil immersed cooling

1. Oil Natural Air Natural (ONAN)

2. Oil Natural Air Forced (ONAF)

3. Oil Forced Air Natural (OFAN)

4. Oil Forced Air Forced (OFAF)

Oil immersed Water cooling

1. Oil Natural Water Forced (ONWF)

2. Oil Forced Water Forced (OFWF)

UNIT AUXILIARY TRANSFORMER (UAT)

The UAT draws its input from the main bus-ducts. The total KVA capacity of UAT required can be determined by assuming 0.85 power factor & 90% efficiency for total auxiliary motor load. It is safe & desirable to provide about 20% excess capacity then circulated to provide for miscellaneous auxiliaries & possible increase in auxiliary.

Page 48: Ntpc Project Report(summer training )

STATION TRANSFORMER

It is required to feed power to the auxiliaries during startups. This transformer is normally rated for initial auxiliary load requirements of the unit in typical cases; this load is of the order of 60% of the load at full generating capacity. It is provided with on load tap change to cater to the fluctuating voltage of the grid.

NEUTRAL GROUNDED TRANSFORMER

This transformer is connected with supply coming out of UAT in stage-2. This is used to ground the excess voltage if occurs in the secondary of UAT in spite of rated voltage.

SWITCH YARDAs we know that electrical energy can‟t be stored like cells, so what we generate should be consumed instantaneously. But as the load is not constants therefore we generate electricity according to need i.e. the generation depends upon load. The

Page 49: Ntpc Project Report(summer training )

yard is the places from where the electricity is send outside. It has both outdoor and indoor equipments.

OUTDOOR EQUIPMENTS

i. BUS BAR.ii. LIGHTENING ARRESTER iii. WAVE TRAP iv. BREAKER v. CAPACITATIVE VOLTAGE TRANSFORMERvi. EARTHING RODvii. CURRENT TRANSFORMER. viii. POTENTIAL TRANSFORMER ix. LIGHTENING MASK

INDOOR EQUIPMENTS

i. RELAYS.ii. CONTROL PANELSiii. CIRCUIT BREAKERS

BUS BAR

Bus bars generally are of high conductive aluminum conforming to IS-5082 or copper of adequate cross section .Bus bar located in air insulated enclosures & segregated from all other components .Bus bar is preferably cover with polyurethane.

BY PASS BUS

This bus is a backup bus which comes handy when any of the buses become faulty. When any operation bus has fault, this bus is brought into circuit and then faulty line is removed there by restoring healthy power line.

LIGHTENING ARRESTOR

It saves the transformer and reactor from over voltage and over currents. It grounds the overload if there is fault on the line and it prevents the generator transformer. The practice is to install lightening arrestor at the incoming terminal

Page 50: Ntpc Project Report(summer training )

of the line. We have to use the lightning arrester both in primary and secondary of transformer and in reactors. A meter is provided which indicates the surface leakage and internal grading current of arrester.

WAVE TRAP

Power line carrier communication (PLCC) is mainly used for telecommunication, tele-protection and tele-monitoring between electrical substations through power lines at high voltages, such as 110 kV, 220 kV, and 400 kV. PLCC integrates the transmission of communication signal and 50/60 Hz power signal through the same electric power cable. The major benefit is the union of two important applications in a single system. WAVETRAP is connected in series with the power (transmission) line. It blocks the high frequency carrier waves (24 KHz to 500 KHz) and let power waves (50 Hz - 60 Hz) to pass-through.

BREAKER

Circuit breaker is an arrangement by which we can break the circuit or flow of current. A circuit breaker in station serves the same purpose as switch but it has many added and complex features. The basic construction of any circuit breaker requires the separation of contact in an insulating fluid that servers two functions: i. extinguishes the arc drawn between the contacts when circuit breaker opens.

ii. It provides adequate insulation between the contacts and from each contact to earth.

CAPACITATIVE VOLTAGE TRANSFORMER

A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra high voltage signals and provide low voltage signals either for measurement or to operate a protective relay. It is located in the last in the switchyard as it increases the ground resistance. Finally the voltage from CVT in the switchyard is sent out from the station through transmission lines.

EARTHING ROD

Normally un-galvanized mild steel flats are used for earthling. Separate earthing electrodes are provided to earth the lightening arrestor whereas the other

Page 51: Ntpc Project Report(summer training )

equipments are earthed by connecting their earth leads to the rid/ser of the ground mar.

CURRENT TRANSFORMER

It is essentially a step up transformer which step down the current to a known ratio. It is a type of instrument transformer designed to provide a current in its secondary winding proportional to the alternating current flowing in its primary.

POTENTIAL TRANSFORMER

It is essentially a step down transformer and it step downs the voltage to a known ratio.

RELAYS

Relay is a sensing device that makes your circuit ON or OFF. They detect the abnormal conditions in the electrical circuits by continuously measuring the electrical quantities, which are different under normal and faulty conditions, like current, voltage frequency. Having detected the fault the relay operates to complete the trip circuit, which results in the opening of the circuit breakers and disconnect the faulty circuit. There are different types of relays:

i. Current relayii. Potential relayiii. Electromagnetic relayiv. Numerical relay etc.

AIR BREAK EARTHING SWITCH

The work of this equipment comes into picture when we want to shut down the supply for maintenance purpose. This help to neutralize the system from induced voltage from extra high voltage. This induced power is up to 2KV in case of 400 KV lines.

ELECTROSTATIC PRECIPITATOR

An electrostatic precipitator ( ESP) or electrostatic air cleaner is a particulate collection device that removes particles from a flowing gas (such as air) using the force of an induced electrostatic charge. Electrostatic precipitators are highly

Page 52: Ntpc Project Report(summer training )

efficient filtration devices that minimally impede the flow of gases through the device, and can easily remove fine particulate matter such as dust and smoke from the air stream.

In contrast to wet scrubbers which apply energy directly to the flowing fluid medium, an ESP applies energy only to the particulate matter being collected and therefore is very efficient in its consumption of energy (in the form of electricity).The most basic precipitator contains a row of thin vertical wires, and followed by a stack of large flat metal plates oriented vertically, with the plates typically spaced about 1 cm to18 cm apart, depending on the application. The air or gas stream flows horizontally through the spaces between the wires, and then passes through the stack of plates. A negative voltage of several thousand volts is applied between wire and plate. If the applied voltage is high enough an electric (corona) discharge ionizes the gas around the electrodes. Negative ions flow to the plates and charge the gas-flow particles. The ionized particles, following the negative electric field created by the power supply, move to the grounded plates. Particles build up on the collection plates and form a layer. The layer does not collapse, thanks to electrostatic pressure (given from layer resistivity, electric field, and current flowing in the collected layer).

Page 53: Ntpc Project Report(summer training )

CONTROL & INSTRUMENTATIONINTRODUCTION

This division basically calibrates various instruments and takes care of any faults occur in any of the auxiliaries in the plant. “Instrumentation can be well defined as a technology of using instruments to measure and control the physical and chemical properties of a material.”

C&I LABS

Manometry Lab.

Protection and Interlocks Lab.

Automation Lab.

Electronics Lab.

Water Treatment Plant.

Furnaces Safety Supervisory System Lab

OPERATION AND MAINTAINANCE

Control and Instrumentation Department has following Control Units:

1. Unit Control Board.

2. Main Control Board

3. Analog & Digital Signal Control

4. Current Signal Control

This department is the brain of the plant because from the relays to transmitters followed by the electronic computation chipsets and recorders and lastly the controlling circuitry, all fall under this.

MANOMETRY LAB

Page 54: Ntpc Project Report(summer training )

TRANSMITTERS

It is used for pressure measurements of gases and liquids, its working principle is that the input pressure is converted into electrostatic capacitance and from there it is conditioned and amplified. It gives an output of 4-20 ma DC. It can be mounted on a pipe or a wall. For liquid or steam measurement transmitters is mounted below main process piping and for gas measurement transmitter is placed above pipe.

MANOMETER

It‟s a tube which is bent, in U shape. It is filled with a liquid. This device corresponds to a difference in pressure across the two limbs.

BOURDEN PRESSURE GAUGE

It‟s an oval section tube. Its one end is fixed. It is provided with a pointer to indicate the pressure on a calibrated scale. It is of 2 types :

(a) Spiral type: for Low pressure measurement.

(b) Helical Type: for High pressure measurement. While selecting Pressure Gauge these parameters should keep in mind-

1. Accuracy

2. Safety

3. Utility

4. Price

ACCURACY

Higher Accuracy implies Larger Dial Size for accuracy of small and readable pressure scale increments.

SAFETY

Page 55: Ntpc Project Report(summer training )

While selecting Pressure Gauge it should consider that Gauge Construction Material should be chemically compatible with the environment either inside or outside it.

UTILITY

It should keep it mind that range of the Gauge should be according to our need else Overpressure Failure may occur resulting in damage of Gauge.

PRICE

Lager the Gauge‟s Dial size larger would be our price. Better Gauge‟s Construction material also increases the cost. So they must be chosen according to our need.

2. PROTECTION AND INTERLOCKING

INTERLOCKING

It is basically interconnecting two or more equipments so that if one equipment fails other one can perform the tasks. This type of interdependence is also created so that equipments connected together are started and shut down in the specific sequence to avoid damage. For protection of equipments tripping are provided for all the equipments. Tripping can be considered as the series of instructions connected through OR GATE, which trips the circuit. The main equipments of this lab are relay and circuit breakers. Some of the instrument uses for protection are:

RELAY

It is a protective device. It can detect wrong condition in electrical circuits by constantly measuring the electrical quantities flowing under normal and faulty conditions. Some of the electrical quantities are voltage, current, phase angle and velocity. 2. FUSES it is a short piece of metal inserted in the circuit, which melts when heavy current flows through it and thus breaks the circuit. Usually silver is used as a fuse material because:

a. The coefficient of expansion of silver is very small. As a result no critical fatigue occurs and thus the continuous full capacity normal current ratings are assured for the long time.

Page 56: Ntpc Project Report(summer training )

b. The conductivity of the silver is unimpaired by the surges of the current that produces temperatures just near the melting point c. Silver fusible elements can be raised from normal operating temperature to vaporization quicker than any other material because of its comparatively low specific heat.

Miniature Circuit Breaker

They are used with combination of the control circuits to.

a) Enable the staring of plant and distributors.

b) Protect the circuit in case of a fault. In consists of current carrying contacts, one movable and other fixed. When a fault occurs the contacts separate and are is stuck between them. There are three types of trips

. I. MANUAL TRIP

II. THERMAL TRIP

III. SHORT CIRCUIT TRIP

Protection and Interlock System-

1) HIGH TENSION CONTROL CIRCUIT

for high tension system the control system is excited by separate D.C supply. For starting the circuit conditions should be in series with the starting coil of the equipment to energize it. Because if even a single condition is not true then system will not start.

2) LOW TENSION CONTROL CIRCUIT

For low tension system the control circuits are directly excited from the 0.415 KV A.C supply.

The same circuit achieves both excitation and tripping. Hence the tripping coil is provided for emergency tripping if the interconnection fails.

3. AUTOMATION LAB

This lab deals in automating the existing equipment and feeding routes. Earlier, the old technology dealt with only (DAS) Data Acquisition System and came to be

Page 57: Ntpc Project Report(summer training )

known as primary systems. The modern technology or the secondary systems are coupled with (MIS) Management Information System. But this lab universally applies the pressure measuring instruments as the controlling force. However, the relays are also provided but they are used only for protection and interlocks.

4. PYROMETRY LAB

LIQUID IN GLASS THERMOMETER

Mercury in the glass thermometer boils at 340° C which limits the range of temperature that can be measured. It is L shaped thermometer which is designed to reach all inaccessible places.

ULTRA VIOLET SENSOR-This device is used in furnace and it measures the intensity of ultra violet rays there and according to the wave generated which directly indicates the temperature in the furnace.

THERMOCOUPLES- This device is based on SEEBACK and PELTIER effect. It comprises of two junctions at different temperature. Then the emf is induced in the circuit due to the flow of electrons. This is an important part in the plant.

RTD (RESISTANCE TEMPERATURE DETECTOR)- It performs the function of thermocouple basically but the difference is of a resistance. In this due to the change in the resistance the temperature difference is measured. In this lab, also the measuring devices can be calibrated in the oil bath or just boiling water (for low range devices) and in small furnace (for high range devices) .

5. FURNACE SAFETY AND SUPERVISORY SYSTEM LAB

This lab has the responsibility of starting fire in the furnace to enable the burning of coal. For first stage coal burners are in the front and rear of the furnace and for the second and third stage corner firing is employed. Unburnt coal is removed using forced draft or induced draft fan. The temperature inside the boiler is 1100°C and its heights 18 to 40 m. It is made up of mild steel. An ultra violet sensor is employed in furnace to measure the intensity of ultra violet rays inside the furnace and according to it a signal in the same order of same mV is generated which directly indicates the temperature of the furnace. For firing the furnace a 10 KV spark plug is operated for ten seconds over a spray of diesel fuel and pre-

Page 58: Ntpc Project Report(summer training )

heater air along each of the feeder-mills. The furnace has six feeder mills each separated by warm air pipes fed from forced draft fans. In first stage indirect firing is employed that is feeder mills are not fed directly from coal but are fed from three feeders but are fed from pulverized coalbunkers. The furnace can operate on the minimum feed from three feeders but under no circumstances should anyone be left out under operation, to Prevent creation of pressure different with in the furnace, which threatens to blast it.

6. ELECTRONICS LAB

This lab undertakes the calibration and testing of various cards. It houses various types of analytical instruments like oscilloscopes, integrated circuits, cards auto analyzers etc. Various processes undertaken in this lab are:

1. Transmitter converts mV to mA.

2. Auto analyzer purifies the sample before it is sent to electrodes. It extracts the magnetic portion.

ANNUNCIATIN CARDS They are used to keep any parameter like temperature etc. within limits. It gets a signal if parameter goes beyond limit. It has a switching transistor connected to relay that helps in alerting the UCB.

CONTROL & MONITORING MECHANISMS

There are basically two types of Problems faced in a Power Plant

1. Metallurgical

2. Mechanical

Mechanical -Problem can be related to Turbines that is the max speed permissible for a turbine is3000 rpm so speed should be monitored and maintained at that level. Metallurgical Problem can be view as the max Inlet Temperature for Turbine is 1060° C so temperature should be below the limit. Monitoring of all the parameters is necessary for the safety of both:

1. Employees

2. Machines

Page 59: Ntpc Project Report(summer training )

So the Parameters to be monitored are:

1. Speed

2. Temperature

3. Current

4. Voltage

5. Pressure

6. Eccentricity

7. Flow of Gases

8. Vacuum Pressure

9. Valves

10. Level

11. Vibration

PRESSURE MONITORING

Pressure can be monitored by three types of basic mechanisms

1. Switches

2. Gauges

3. Transmitter type

For gauges we use Bourdon tubes. The Bourdon Tube is a non-liquid pressure measurement device. It is widely used in applications where inexpensive static pressure measurements are needed. A typical Bourdon tube contains a curved tube that is open to external pressure input on one end and is coupled mechanically to an indicating needle on the other end, as shows schematically below.

Page 60: Ntpc Project Report(summer training )

For Switches pressure switches are used and they can be used for digital means of monitoring as switch being ON is referred as high and being OFF is as low. All the monitored data is converted to either Current or Voltage parameter.

The Plant standard for current and voltage are as under

• Voltage : 0 –10 Volts range

• Current : 4 –20 milli-Amperes

We use 4mA as the lower value so as to check for disturbances and wire breaks. Accuracy of such systems is very high.

ACCURACY: ± 0.1 % Programmable Logic Circuits (PLCs) are used in the process as they are the heart of Instrumentation

TEMPERATURE MONITORING

We can use Thermocouples or RTDs for temperature monitoring. Normally RTDs are used for low temperatures. Thermocouple selection depends upon two factors:

1. Temperature Range

2. Accuracy Required

Normally used Thermocouple is K Type Thermocouple:

Page 61: Ntpc Project Report(summer training )

In this we use Chromel (Nickel-Chromium Alloy) / Alumel (Nickel-Aluminium Alloy) as two metals. This is the most commonly used general purpose thermocouple. It is inexpensive and, owing to its popularity, available in a wide variety of probes. They are available in the−200°C to +1200°C range. Sensitivity is approximately 41 μV/°C.

RTDs are also used but not in protection systems due to vibrational errors.

We pass a constant current through the RTD. So that if R changes then the Voltage also changes

RTDs used in Industries are Pt100 And Pt1000

Pt100: 0°C – 100 Ω ( 1 Ω = 2.5 0C )

Pt1000: 0°C - 1000Ω

Pt1000 is used for higher accuracy.

The gauges used for Temperature measurements are mercury filled Temperature gauges.

For Analog medium thermocouples are used and for Digital medium Switches are used which are basically mercury switches.

FLOW MEASUREMENT

Flow measurement does not signify much and is measured just for metering purposes and for monitoring the processes

ROTAMETERS:

A Rotameter is a device that measures the flow rate of liquid or gas in a closed tube. It is occasionally misspelled as 'Rotometer'. It belongs to a class of meters called variable area meters, which measure flow rate by allowing the cross sectional area the fluid travels through to vary, causing some measurable effect. A rotameter consists of a tapered tube, typically made of glass, with a float inside that is pushed up by flow and pulled down by gravity. At a higher flow rate more area (between the float and the tube) is needed to accommodate the flow, so the float rises. Floats are made in many different shapes, with spheres and spherical ellipses

Page 62: Ntpc Project Report(summer training )

being the most common. The float is shaped so that it rotates axially as the fluid passes. This allows you to tell if the float is stuck since it will only rotate if it is not.

For Digital measurements Flap system is used.

For Analog measurements we can use the following methods

1. Flow meters

2. Venturimeters / Orifice meters

3. Turbines

4. Mass flow meters (oil level)

5. Ultrasonic Flow meters

6. Magnetic Flow meter (water level )

Selection of flow meter depends upon the purpose, accuracy and liquid to be measured so different types of meters used.

TURBINE TYPE:

They are simplest of all. They work on the principle that on each rotation of the turbine a pulse is generated and that pulse is counted to get the flow rate.

VENTURIMETERS :

Referring to the diagram, using Bernoulli's equation in the special case of incompressible fluids (such as the approximation of a water jet), and the theoretical pressure drop at the constriction would be given by (ρ/2)(v2 2- v1 2). And we know that rate of flow is given by: Flow = k √ (D.P) Where DP is Differential Pressure or the Pressure Drop.

Page 63: Ntpc Project Report(summer training )

CONTROL VALVES

A valve is a device that regulates the flow of substances (either gases, fluidized solids, slurries, or liquids) by opening, closing, or partially obstructing various passageways. Valves are technically pipe fittings, but usually are discussed separately. Valves are used in a variety of applications including industrial, military, commercial, residential, transportation. Plumbing valves are the most obvious in everyday life, but many more are used.

Some valves are driven by pressure only, they are mainly used for safety purposes in steam engines and domestic heating or cooking appliances. Others are used in a controlled way, like in Otto cycle engines driven by a camshaft, where they play a major role in engine cycle control.

Many valves are controlled manually with a handle attached to the valve stem. If the handle is turned a quarter of a full turn (90°) between operating positions, the valve is called a quarter-turn valve. Butterfly valves, ball valves, and plug valves are often quarter-turn valves. Valves can also be controlled by devices called actuators attached to the stem. They can be electromechanical actuators such as an electric motor or solenoid, pneumatic actuators which are controlled by air pressure, or hydraulic actuators which are controlled by the pressure of a liquid such as oil or water. So there are basically three types of valves that are used in power industries besides the handle valves.

They are

Page 64: Ntpc Project Report(summer training )

:· PNEUMATIC VALVES –They are air or gas controlled which is compressed to turn or move them·

HYDRAULIC VALVES – They utilize oil in place of Air as oil has better compression·

MOTORISED VALVES – These valves are controlled by electric motors

FURNACE SAFEGUARD SUPERVISORY SYSTEMFSSS is also called as Burner Management System (BMS). It is a microprocessor Based programmable logic controller of proven design incorporating all protection facilities required for such system. Main objective of FSSS is to ensure safety of the boiler.

The 95 MW boilers are indirect type boilers. Fire takes place in front and in rear side. That‟s why it‟s called front and rear type boiler.

The 210 MW boilers are direct type boilers (which means that HSD is in direct contact with coal) firing takes place from the corner. Thus it is also known as corner type boiler.

IGNITER SYSTEM

Igniter system is an automatic system, it takes the charge from 110kv and this spark is brought in front of the oil guns, which spray aerated HSD on the coal for coal combustion. There is a 5 minute delay cycle before igniting, this is to evacuate or burn the HSD. This method is known as PURGING.

PRESSURE SWITCH

Pressure switches are the devices that make or break a circuit. When pressure is applied, the switch under the switch gets pressed which is attached to a relaythat makes or break the circuit.

Time delay can also be included in sensing the pressure with the help of pressure valves.

Page 65: Ntpc Project Report(summer training )

Examples of pressure valves:

1. Manual valves (tap)

2. Motorized valves (actuator) –works on motor action

3. Pneumatic valve (actuator) - works due to pressure of compressed air

4. Hydraulic valve