Asset: HS FOR CONST.TRADES,ENGG.,& ARCH-Q, 94-06 104TH STREET, New York, 11416 Inspection Id Inspection Type Time In Last Edited SA : Q650 Architectural - Senior 2019-04-05 8:00 AM 2019-04-23 12:15 PM AA : Q650 Architectural - Associate 2019-04-05 8:58 AM 2019-04-05 8:23 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Basement Boys and Girls Shower Rooms were sealed up. Also, a Generator Enclosure was locked-no key. Principal(s) Information Principal Name Lakeisha Gordon Organization High School for Construction Trades, Engineering, & Architecture - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal commented that the HVAC system requires frequent repairs. Custodian Amin Quanungo Fireman William Vega Building Square Footage 136000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4+B Comments on the Number of Classrooms 51 Comments on the Year Built 2006 Student Population 1052 Staff Population 65 Weather Fair Facade Photo Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 Q650 PB/A&W Print Date: 6/20/2019 Page 1 of 30
Transcript
Page 1: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Asset: HS FOR CONST.TRADES,ENGG.,& ARCH-Q, 94-06 104TH STREET, New York, 11416

Inspection Id Inspection Type Time In Last Edited

SA : Q650 Architectural - Senior 2019-04-05 8:00 AM 2019-04-23 12:15 PM

AA : Q650 Architectural - Associate 2019-04-05 8:58 AM 2019-04-05 8:23 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment Basement Boys and Girls Shower Rooms were sealed up. Also, aGenerator Enclosure was locked-no key.

Principal(s) Information

Principal Name Lakeisha Gordon

Organization High School for Construction Trades, Engineering, & Architecture -Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal commented that the HVAC system requires frequentrepairs.

Custodian Amin Quanungo

Fireman William Vega

Building Square Footage 136000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 4+B

Comments on the Number of Classrooms 51

Comments on the Year Built 2006

Student Population 1052

Staff Population 65

Weather Fair

Facade Photo

Corner of 104th Street and 94th Avenue -Southwest View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 1 of 30

Page 2: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Main Entrance Photo

Facade A - 104th Street

Roof Photo

Roof 1 - Northeast View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Limited Roofing repairs

Year: 2019

Systems: Limited Roofing repairs

Year: 2012

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

Yes Broken Glass A broken glassblock withexposed sharpedges is apotential safetyhazard.

EXTERIOR |EXTERIORWALLS

Glass block wallof the 95thAvenue façade.

Amin Quanungo Custodian

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 2 of 30

Page 3: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No No

Interior Routes

Corridor and Lobby H/C Lifts Yes Yes

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps Yes Yes

Rooms & Spaces

Art Rooms Room 251 Yes Yes

Auditorium 1st Floor Yes Yes Yes Yes

Cafeteria Basement - Staff, Basement - Students Yes Yes Yes Yes

Classrooms 1st-4th Floors Yes Yes

Computer Rooms Rooms 224, 352, 356, 424 Yes Yes

Gymnasium Basement Yes Yes Yes Yes

Library Room 305 Yes Yes

Main Office Room 106 (HSCTEA), Room 143 (P233) Yes Yes

Multi-purpose Room No

Nurse's Room Room B30A Yes Yes

Pool No

Science Lab Rooms 320, 328 Yes Yes

Toilet Rooms (Boys) Basement-4th Floors Yes Yes

Toilet Rooms (Girls) Basement-4th Floors Yes Yes

Toilet Rooms (Staff) Basement-4th Floors Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 3 of 30

Page 4: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Does not Exist

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Does not Exist

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 2 - Between Good and Fair

Deficiency ROLL-UP DOOR: DETERIORATED DOOR - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 4 of 30

Page 5: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry, Steel

Replacement Quantity 30,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 30,000

Instance Quantity Uom S.F.

Deficiency BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE

Roof Plan reference

Elevation

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 5 of 30

Page 6: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo1

Facade C - Room 328

Violations No violations recorded.

Deficiency GLASS BLOCK: CHIPPED/ BROKEN PIECES

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE-IN-KIND

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Facade B

Violations No violations recorded.

EXTERIOR SOFFITS Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 6 of 30

Page 7: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

EXTERIOR

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 12,000

Replacement Uom C.F.

InspectedInstance on All Roofs

Instance Condition 2 - Between Good and Fair

Instance Quantity 12,000

Instance Quantity Uom C.F.

Deficiency No deficiencies recorded

PLAZA DECK Inspected

InspectedInstance on Pavers: Roof 5

Instance Condition 3 - Fair

Instance Quantity 2,000

Instance Quantity Uom S.F.

Installation Year 2006

Source of Installation Custodial Staff

Deficiency PAVERS: PAVERS IN POOR CONDITION

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 5 - Plaza Deck

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 7 of 30

Page 8: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

EXTERIOR

PLAZA DECK Inspected

Violations No violations recorded.

ROOF Inspected

Roofing Inspected

Replacement Quantity 30,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on IRMA: Roofs 1-4

Instance Condition 4 - Between Fair and Poor

Instance Quantity 30,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2006

Source of Installation Custodial Staff

Deficiency IRMA: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE

Roof Plan reference

Deficiency Quantity 250

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 8 of 30

Page 9: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

EXTERIOR

ROOF Inspected

Roofing

ROOFING

Deficiency Photo1

Roof 1 - Room 404 (Roof 4 - Corridor near Room 358, 2Locations, and Roof 2 - Room 356 similar)

Violations No violations recorded.

Deficiency IRMA: ROOFING: DAMAGED INSULATION

Roof Plan reference

Deficiency Quantity 140

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 4

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 9 of 30

Page 10: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

EXTERIOR

ROOF

Specialties

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

WINDOWS Inspected

Replacement Quantity 6,000

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Other: All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 6,000

Instance Quantity Uom S.F.

Installation Year 2006

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FLOOR STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

AUDITORIUM Inspected

InspectedInstance on 1st Floor (363 Seats)

Ceiling

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 10 of 30

Page 11: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

AUDITORIUM

Ceiling

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

Does not ExistInstance on 1st Floor (363 Seats)

Fixed Seating

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seats B/1, E/101, G/101, 111, K/103, and others

Deficiency Quantity 7

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Seat K/103

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor (363 Seats)

Stage

InspectedInstance on 1st Floor (363 Seats)

Stage Inspected

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtain Rigging Inspected

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 11 of 30

Page 12: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

AUDITORIUM

Stage

Stage Curtains

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor (363 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor (363 Seats)

CAFETERIA Inspected

InspectedInstance on Basement - Staff (600 SF)

InspectedInstance on Basement - Students

Ceiling

InspectedInstance on Basement - Staff (600 SF)

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Rear

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Rear

Violations No violations recorded.

Door(s)

InspectedInstance on Basement - Staff (600 SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Students

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on Basement - Staff (600 SF)

Does not ExistInstance on Basement - Students

Floor Finish

InspectedInstance on Basement - Staff (600 SF)

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 12 of 30

Page 13: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

CAFETERIA

Floor Finish

Deficiency No deficiencies recorded

InspectedInstance on Basement - Students

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on Basement - Students

Does not ExistInstance on Basement - Staff (600 SF)

Stage

Does not ExistInstance on Basement - Staff (600 SF)

Does not ExistInstance on Basement - Students

Walls

InspectedInstance on Basement - Students

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Staff (600 SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on Basement - Staff (600 SF)

Does not ExistInstance on Basement - Students

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED - ACTIVELEAK

Deficiency Location/Instance Corridor near Room 358

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 358

Violations No violations recorded.

Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK

Deficiency Location/Instance Rooms 328, 356, 404

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 13 of 30

Page 14: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Room 328

Violations No violations recorded.

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Corridor near Rooms 130, 402, 413, 420

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 413

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET

Deficiency Location/Instance Rooms 208, 356

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 14 of 30

Page 15: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Room 208

Violations No violations recorded.

Deficiency EPOXY FLOORING: CRACKS/SPALLING

Deficiency Location/Instance Room 320

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 320

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Corridor near Room 352, Room 352

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 15 of 30

Page 16: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls Inspected

Room 352

Violations No violations recorded.

Specialties Inspected

Classroom Locker(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Seating Does not Exist

GYMNASIUM Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Office

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Door(s)

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Seating

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 16 of 30

Page 17: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

GYMNASIUM

Sliding-folding Partition

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage

Does not ExistInstance on Basement

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency MASONRY: CRACKS/SPALLING

Deficiency Location/Instance Near Room B35A2

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Room B35A2

Violations No violations recorded.

Deficiency WALL PADDING: DETERIORATED

Deficiency Location/Instance Near Visitor Locker Room, Near Office, Near Drinking Fountain

Deficiency Quantity 160

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Visitor Locker Room

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on Basement

INTERIOR DOOR HARDWARE Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 17 of 30

Page 18: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

INTERIOR DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Rooms B60A, B60J

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room B60J

Violations No violations recorded.

Door(s)

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 305

Built-in Furnishing

InspectedInstance on Room 305

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Ceiling

InspectedInstance on Room 305

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 18 of 30

Page 19: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

LIBRARY

Ceiling

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 305

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 305

Condition 2 - Between Good and Fair

Deficiency CARPET: TRIPPING HAZARD - ELECTRICAL OUTLET

Deficiency Location/Instance Room 305E

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Room 305E

Violations No violations recorded.

Walls

InspectedInstance on Room 305

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Right Side

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Right Side

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 19 of 30

Page 20: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

LIBRARY Inspected

Walls

Violations No violations recorded.

LOCKER ROOM Inspected

InspectedInstance on Basement - Boys (490 Lockers)

Alternative use No

InspectedInstance on Basement - Girls (486 Lockers)

Alternative use No

InspectedInstance on Basement - Visitors (31 Lockers)

Alternative use No

Ceiling

Does not ExistInstance on Basement - Visitors (31 Lockers)

Does not ExistInstance on Basement - Boys (490 Lockers)

Does not ExistInstance on Basement - Girls (486 Lockers)

Door(s)

InspectedInstance on Basement - Boys (490 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Girls (486 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Visitors (31 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Basement - Boys (490 Lockers)

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Near Locker 38

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Locker 38

Violations No violations recorded.

Locker Room Lockers

InspectedInstance on Basement - Boys (490 Lockers)

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 20 of 30

Page 21: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

LOCKER ROOM Inspected

Locker Room Lockers

Deficiency DAMAGED UNITS

Deficiency Location/Instance Lockers 368, 376, 409, 474

Deficiency Quantity 4

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Locker 474

Violations No violations recorded.

Walls

InspectedInstance on Basement - Boys (490 Lockers)

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Near Locker 1

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Locker 1

Violations No violations recorded.

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Inspected

InspectedInstance on Rooms 310, 316, 332, 336

Alternative use No

Fixed Equipment

InspectedInstance on Rooms 310, 316, 332, 336

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 21 of 30

Page 22: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

SCIENCE LAB Inspected

InspectedInstance on Room 320

Alternative use No

InspectedInstance on Room 328

Alternative use No

Fixed Equipment

InspectedInstance on Room 320

Condition 2 - Between Good and Fair

Deficiency CABINETRY: MISSING/DAMAGED

Deficiency Location/Instance Room 320

Deficiency Quantity 2

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 320

Violations No violations recorded.

SCIENCE PREP ROOM Inspected

InspectedInstance on Room 324

Alternative use No

Fixed Equipment

InspectedInstance on Room 324

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SHOWER ROOM Inspected

InspectedInstance on Basement - Visitors

Alternative use Yes

InaccessibleInstance on Basement - Girls

InaccessibleInstance on Basement - Boys

Ceiling

InspectedInstance on Basement - Visitors

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Basement - Visitors

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Basement - Visitors

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 22 of 30

Page 23: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

SHOWER ROOM

Floor Finish

Deficiency No deficiencies recorded

Walls

InspectedInstance on Basement - Visitors

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Partition Does not Exist

Railings Inspected

Condition 3 - Fair

Deficiency METAL: BROKEN BRACKET

Deficiency Location/Instance Stair B/1

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/1

Violations No violations recorded.

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency MASONRY: CRACKS/SPALLING

Deficiency Location/Instance Stair B/1,3,4

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 23 of 30

Page 24: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo1

Stair B/4

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Does not Exist

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Room 417

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 417

Violations No violations recorded.

Door(s) Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 24 of 30

Page 25: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FENCES Inspected

Condition 3 - Fair

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance Schoolyard

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 25 of 30

Page 26: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

SITE

FENCES Inspected

Deficiency Photo1

Schoolyard

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 3 - Fair

Deficiency LOCALIZED SINK AREA

Deficiency Location/Instance Schoolyard

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 300

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 26 of 30

Page 27: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

SITE

PAVING

Student Use

Asphalt

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Site Sidewalks & Walkways Inspected

Asphalt Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Near 95th Avenue

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near 95th Avenue

Violations No violations recorded.

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Along 104th Street, Along 95th Avenue

Deficiency Quantity 50

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 27 of 30

Page 28: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Concrete

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Along 104th Street

Violations No violations recorded.

Pavers Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED CURBS

Deficiency Location/Instance 94th Avenue

Deficiency Quantity 5

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

94th Avenue

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 104th Street, 94th Avenue, 95th Avenue

Deficiency Quantity 350

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 28 of 30

Page 29: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Purpose of Action LEVEL 2

Deficiency Photo1

104th Street

Violations No violations recorded.

Pavers Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard

Benches

Does not ExistInstance on Schoolyard

Fence

Does not ExistInstance on Schoolyard

Pavement

Does not ExistInstance on Schoolyard

Play Equipment

InspectedInstance on Schoolyard

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard

Condition 2 - Between Good and Fair

Deficiency DETERIORATED/MISSING

Deficiency Location/Instance Schoolyard

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 29 of 30

Page 30: NYC Department of Education · 2019-06-20 · Corner of 104th Street and 94th Avenue - Southwest View NYC Department of Education ... Corridor and Lobby H/C Lifts Yes Yes ... Roof

Question Response

SITE

PLAYGROUNDS

Safety Surfacing

Schoolyard

Violations No violations recorded.

Unpaved Area

Does not ExistInstance on Schoolyard

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Inspected

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 2 - Between Good and Fair

Deficiency MASONRY UNIT: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Schoolyard, Near 95th Avenue

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q650

PB/A&W Print Date: 6/20/2019Page 30 of 30