Asset: I.S. 53 - QUEENS, 10-45 NAMEOKE STREET, New York, 11691
Inspection Id Inspection Type Time In Last Edited
SA : Q053 Architectural - Senior 2018-10-11 7:50 AM 2018-11-09 2:38 PM
AA : Q053 Architectural - Associate 2018-10-11 8:52 AM 2018-10-30 4:32 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Security Lighting, Exterior Soffits, Exterior Guards and WindowLintels were inaccessible due to construction scaffolding and netting.
Boys Locker Room was being used for storage and the Boys ShowerRoom has been sealed - both rooms were inaccessible for inspection.
Principal(s) Information
Principal Name Andrea Yard
Organization I.S. 53 - Brian Piccolo School - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? No
Principal Name Doris Lee
Organization Village Academy - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: The Auditorium in need ofrenovation. Seating is in poor condition.
Principal Name Ty Redmond
Organization Success Academy - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian David Paretti
Fireman Daniel Hourihan
Building Square Footage 164000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4+B (Partial)
Comments on the Number of Classrooms 64
Comments on the Year Built 1972
Student Population 890
Staff Population 157
Weather Fair
Facade Photo
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 1 of 33
Nameoke Street - North view
Main Entrance Photo
Facade A - Nameoke Street
Roof Photo
Roof 1 - West view
Have any Systems/Major Building Components been upgraded? Yes
Systems: Girls Locker Room converted to Exercise Room
Year: 2018
Systems: Toilet renovations all Toilets 1st to 4th Floor
Year: 2017
Systems: Courtyard repairs to Parapets, Coping and Flashing; Roof4 Railing Replacement.
Year: 2013
Systems: New Student Toilet Rooms in the Cafeteria and the 3rdFloor; Partial Coping replacement; New Window Guards;New Gymnasium Floor
Year: 2008
Systems: New Schoolyard and Window Curtains; Repairs toAuditorium Ceiling.
Year: 2007
Systems: New Roofing, Flashing and Skylights; Exterior Masonryrepointing and repairs.
Year: 1997
Have there been any New Building Additions? No
Tandem Schools? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 2 of 33
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No Potential FallingDebris
Deterioratedspalled concretefloor slab withexposedreinforcement isa potentialfalling debrishazard.
INTERIOR |STRUCTURAL| FLOORSTRUCTURE
Room B13 -Science LabAcid TankStorage Room
Daniel Hourihan Fireman
No Potential FallingDebris
Leaning Fenceis a potentialsafety hazard
SITE | FENCES South ofSchoolyard
Daniel Hourihan Fireman
No ProtrudingElements
Protruding metalwith sharp edgeis a potentialsafety hazard.
INTERIOR |AUDITORIUM| Fixed Seating
Seats B/2, D/2 Daniel Hourihan Fireman
No Tripping Hazard Heaving SafetySurface is apotentialtripping hazard
SITE |PLAYGROUNDS | SafetySurfacing
Left Side Daniel Hourihan Fireman
Yes Tripping Hazard Heaving DOT isa potentialsafety hazard.
SITE | PAVING| DOT Sidewalk| Concrete
Bayport Place Daniel Hourihan Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 3 of 33
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps Yes No Railing Height < 34 or >38 Inches
Rooms & Spaces
Art Rooms No
Auditorium 3rdFloor Yes No H/C Lift Inoperable No No
Cafeteria 1st Floor Yes Yes Yes Yes
Classrooms 1st - 4th Floors Yes Yes
Computer Rooms Room 268 Yes Yes
Gymnasium 1st Floor Yes Yes Yes Yes
Library Room 347 Yes Yes
Main Office Room 109 - I.S. 53 - Queens, Room 311 -Success Academy, Room 447B - VillageAcademy
Yes Yes
Multi-purpose Room No
Nurse's Room Room 113 Yes Yes
Pool No
Science Lab Room 279, Room 406, Room 408 Yes Yes
Toilet Rooms (Boys) 1st - 4th Floors Yes Yes
Toilet Rooms (Girls) 1st - 4th Floors Yes Yes
Toilet Rooms (Staff) 1st - 4th Floors Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 4 of 33
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1
Instance Condition 3 - Fair
Instance Quantity 1
Instance Quantity Uom EACH
Deficiency AREAWAY GRATINGS: MAJOR RUSTING AND / OR BROKENSUPPORTS
Roof Plan reference
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 5 of 33
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW1
Violations No violations recorded.
AWNINGS AND CANOPIES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CHIMNEY Under Construction
COPING Under Construction
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 8
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 5
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 6 of 33
Question Response
EXTERIOR
DOORS
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Does not Exist
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 72,000
Replacement Uom S.F.
Under ConstructionInstance on All Facades
Instance Quantity 72,000
Instance Quantity Uom S.F.
EXTERIOR SOFFITS Inaccessible
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 9,000
Replacement Uom C.F.
Under ConstructionInstance on Brick
Instance Quantity 8,000
Instance Quantity Uom C.F.
Under ConstructionInstance on Concrete
Instance Quantity 1,000
Instance Quantity Uom C.F.
PLAZA DECK Inspected
Under ConstructionInstance on Concrete: Roof 4
Instance Quantity 10,000
Instance Quantity Uom S.F.
ROOF Inspected
Roofing Inspected
Replacement Quantity 48,500
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Under Construction
ROOF BARRIER Under Construction
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
Under ConstructionInstance on Modified Bitumen: Roofs 1, 2, 3, 5
Instance Quantity 48,500
Instance Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 7 of 33
Question Response
EXTERIOR
ROOF
Roofing Inspected
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Under Construction
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Inspected
Condition 2 - Between Good and Fair
Deficiency HEIGHT LESS THAN 18"
Roof Plan reference
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1 No photo recorded
Violations No violations recorded.
SKYLIGHT/ROOF VENT Under Construction
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
RAILINGS Under Construction
STAIRS/RAMPS Under Construction
WINDOWS Inspected
Replacement Quantity 20,000
Replacement Uom S.F.
EXTERIOR GUARDS Inaccessible
LINTELS Inaccessible
WINDOWS Inspected
Material Type(s) Aluminum
Under ConstructionInstance on Aluminum - Double Hung: All Facades
Instance Quantity 2,000
Instance Quantity Uom S.F.
Under ConstructionInstance on Aluminum - Other: All Facades
Instance Quantity 18,000
Instance Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 8 of 33
Question Response
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency CONCRETE BEARING WALL:CRACKED/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Room 446 - 4th Floor Fan Room, Facade B
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Facade B view from Rom 279
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Multiple locations throughout the cations throughout the Basementincluding the Electrical Room, Fan Room, Corridors and StorageRoms
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Room B11
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Room B13 - Science Lab Acid TankRoom
Deficiency Quantity 25
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 9 of 33
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room B13 - Science Lab Acid TankRoom
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Room 446, 4th Floor connecting corridor, Kitchen Storage Room, OilTank Room
Deficiency Quantity 160
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Room 446 - Fan Room(Room 446, 4th Floor connecting corridor,Kitchen Storage Room , Oil Tank Room similar)
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 3 - Fair
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Corridor near AW1
Deficiency Quantity 70
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 10 of 33
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Corridor near AW1
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Room 447, Corridor near Stair D
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Room 447 ( Corridor new Stair D similar)
Violations No violations recorded.
VAULTS-BUNKERS Does not Exist
AUDITORIUM Inspected
InspectedInstance on 3rd Floor - 695 Seats
Ceiling
InspectedInstance on 3rd Floor - 695 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 3rd Floor - 695 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
InspectedInstance on 3rd Floor - 695 Seats
Condition 5 - Poor
Deficiency INOPERABLE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 11 of 33
Question Response
INTERIOR
AUDITORIUM
Fixed H/C Lift
Deficiency Location/Instance Right Side
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Fixed Seating
InspectedInstance on 3rd Floor - 695 Seats
Condition 5 - Poor
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats B/2, D/2
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Seat D/2
Violations No violations recorded.
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats A/7, C/4, D/4, F/2, H/6 and others
Deficiency Quantity 80
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat A/7
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 12 of 33
Question Response
INTERIOR
AUDITORIUM
Floor Finish
InspectedInstance on 3rd Floor - 695 Seats
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near Entrance, Near Stage
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Sliding-folding Partition
InspectedInstance on 3rd Floor - 695 Seats
Condition 5 - Poor
Deficiency MOTOR: INOPERABLE
Deficiency Location/Instance Center of Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Stage
InspectedInstance on 3rd Floor - 695 Seats
Stage Inspected
InspectedInstance on 3rd Floor - 695 Seats
Condition 3 - Fair
Deficiency DAMAGED FASCIA
Deficiency Location/Instance Right Side
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 13 of 33
Question Response
INTERIOR
AUDITORIUM
Stage
Stage
Deficiency Photo1
Right Side
Violations No violations recorded.
Deficiency DAMAGED FLOOR
Deficiency Location/Instance Right Side
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Right Side
Violations No violations recorded.
Stage Curtain Rigging Inspected
InspectedInstance on 3rd Floor - 695 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 3rd Floor - 695 Seats
Condition 3 - Fair
Deficiency WORN/DETERIORATED
Deficiency Location/Instance Left Side
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 14 of 33
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Curtains
Deficiency Photo1
Left Side
Violations No violations recorded.
Walls
InspectedInstance on 3rd Floor - 695 Seats
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Stage
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stage
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor - 695 Seats
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
Does not ExistInstance on 1st Floor
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 15 of 33
Question Response
INTERIOR
CAFETERIA
Floor Finish
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Rooms 163, 159, 157, 155
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 163
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 3 - Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Lobby, Corridor near Gymnasium, Corridor near Cafeteria
Deficiency Quantity 2,700
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 16 of 33
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Lobby
Violations No violations recorded.
Deficiency EPOXY FLOORING: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 279, 279A
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 279
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Corridor near Room 377, 285, 279
Deficiency Quantity 90
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 377
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 17 of 33
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 461, 445, 268, 159, Corridor near Room 319 and others
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 455
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 477
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 477
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 461, 447A, 127
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 18 of 33
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo1
Room 447A
Violations No violations recorded.
Specialties Inspected
Classroom Locker(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Seating Does not Exist
GYMNASIUM Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Office
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 19 of 33
Question Response
INTERIOR
GYMNASIUM
Floor Finish
InspectedInstance on 1st Floor
Condition 4 - Between Fair and Poor
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Near Office (Picture doesn't show bubbling of the Floor)
Deficiency Quantity 350
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Office
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Seating
Does not ExistInstance on 1st Floor
Sliding-folding Partition
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Near Entrance
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 20 of 33
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Locker room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Locker room
Violations No violations recorded.
Floor Finish
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 21 of 33
Question Response
INTERIOR
KITCHEN
Floor Finish
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency QUARRY TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Center
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Room 128
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 128
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
Under ConstructionInstance on Room 347
LOCKER ROOM Inspected
InaccessibleInstance on 1st Floor
MULTI-PURPOSE ROOM Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 22 of 33
Question Response
INTERIOR
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 279
Alternative use No
InspectedInstance on Room 406
Alternative use No
InspectedInstance on Room 408
Alternative use No
Fixed Equipment
InspectedInstance on Room 406
Condition 3 - Fair
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Room 406
Deficiency Quantity 8
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 406
Violations No violations recorded.
SCIENCE PREP ROOM Inspected
InspectedInstance on Room 279A
Alternative use No
InspectedInstance on Room 414
Alternative use Yes
Fixed Equipment
InspectedInstance on Room 414
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Room 279A
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SHOWER ROOM Inspected
InaccessibleInstance on 1st Floor
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 23 of 33
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Stair E/1,4
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair E/4
Violations No violations recorded.
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency METAL: MISSING
Deficiency Location/Instance Corridor near Room 373
Deficiency Quantity 7
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Corridor near Room 373
Violations No violations recorded.
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 24 of 33
Question Response
INTERIOR
TOILET ROOMS - STAFF
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Boys Locker Room
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Boys Locker Room
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency RUST - MAJOR
Deficiency Location/Instance Boys Locker Room
Deficiency Quantity 1
Quantity Uom EACH
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 25 of 33
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Boys Locker Room
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency FENCING MISSING
Deficiency Location/Instance Near Exit 2
Deficiency Quantity 750
Quantity Uom S.F.
Potential Action INSTALL NEW
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance Near Exit 2
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 26 of 33
Question Response
SITE
CONTAINERIZATION
Deficiency Photo1
Near Exit 2
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FENCES Inspected
Condition 3 - Fair
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance South of Schoolyard
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
South of Schoolyard
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 27 of 33
Question Response
SITE
FENCES Inspected
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Near Exit 2
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Exit 2
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Near Exit 2
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Exit 2
Violations No violations recorded.
Pavers Does not Exist
Student Use Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 28 of 33
Question Response
SITE
PAVING Inspected
Student Use
Gravel Exists? No
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 1,050
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Back of Building
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Back of Building
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 29 of 33
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Asphalt Inspected
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Nameoke Street
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Nameoke Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency HEAVING
Deficiency Location/Instance Bayport Place
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Bayport Place
Violations No violations recorded.
Deficiency HEAVING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 30 of 33
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Location/Instance Bayport Place
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Bayport Place
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Nameoke Street, Beach 18th Street, Foam Place, Bayport Place
Deficiency Quantity 1,225
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Nameoke Street
Violations No violations recorded.
Deficiency DAMAGED CURBS
Deficiency Location/Instance Nameoke Street, Beach 18th Street
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 31 of 33
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
Nameoke Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard
Benches
Does not ExistInstance on Schoolyard
Fence
Does not ExistInstance on Schoolyard
Pavement
Does not ExistInstance on Schoolyard
Play Equipment
InspectedInstance on Schoolyard
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard
Condition 2 - Between Good and Fair
Deficiency DETERIORATED/MISSING
Deficiency Location/Instance Left Side
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Left Side
Violations No violations recorded.
Unpaved Area
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 32 of 33
Question Response
SITE
PLAYGROUNDS Inspected
Unpaved Area
Does not ExistInstance on Schoolyard
PLAYING SURFACE Inspected
Playing Field Inspected
InspectedInstance on Schoolyard
Instance Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Running Track Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Inspected
Benches Inspected
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q053
PB/A&W Print Date: 6/21/2019Page 33 of 33