Asset: P.S. 106 - QUEENS, 180 BEACH 35 STREET, New York, 11691 Inspection Id Inspection Type Time In Last Edited SA : Q106 Architectural - Senior 2020-03-05 11:02 AM 2020-03-17 12:17 PM AA : Q106 Architectural - Associate 2020-03-05 10:51 AM 2020-03-05 4:46 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Rachelle Legions Organization P.S. 106 - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal had no comments regarding the physical condition of the building at this time. Custodian Was not present Fireman Rupert Palmer Building Square Footage 23000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 12 Comments on the Year Built 1931 Student Population 210 Staff Population 49 Weather Fair Facade Photo Corner of Beach 35th Street and Rockaway Boardwalk - Southeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 Q106 PB/A&W Print Date: 9/13/2020 Page 1 of 38
Transcript
Page 1: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Asset: P.S. 106 - QUEENS, 180 BEACH 35 STREET, New York, 11691

Inspection Id Inspection Type Time In Last Edited

SA : Q106 Architectural - Senior 2020-03-05 11:02 AM 2020-03-17 12:17 PM

AA : Q106 Architectural - Associate 2020-03-05 10:51 AM 2020-03-05 4:46 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Rachelle Legions

Organization P.S. 106 - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal had no comments regarding the physical condition of thebuilding at this time.

Custodian Was not present

Fireman Rupert Palmer

Building Square Footage 23000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Number of Classrooms 12

Comments on the Year Built 1931

Student Population 210

Staff Population 49

Weather Fair

Facade Photo

Corner of Beach 35th Street and RockawayBoardwalk - Southeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 1 of 38

Page 2: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Main Entrance Photo

Facade A - Beach 35th Street

Roof Photo

Roof 1- Northeast View

Have any Systems/Major Building Components been upgraded? Yes

Systems: New Running Track, Playground, Play Equipment andSafety Surfacing, New Schoolyard paving, Site Benches,Site Paving near TCU's, Limited Site Fencingreplacement, Exterior Stair repairs near Exits 2 and 4.

Year: 2017

Systems: Flood Elimination Project including Structural ConcreteFireproofing repairs, limited Exterior Masonry repointingand repairs, Areaway restoration and Grating replacement,new Exterior Doors and Transoms, Louvres and BasementWindows and Roof

Year: 2016

Systems: Parapet and Exterior Masonry repointing and repairs, NewCoping and Roof Barriers

Year: 2009

Systems: Basement Flood Elimination Project including InjectionWaterproofing at Foundation Walls

Year: 2008

Systems: Limited Exterior Door replacement

Year: 2005

Systems: New Windows and Exterior Guards except Basement.

Year: 2000

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 2 of 38

Page 3: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits No Saddle height > 1/2"

Exterior H/C Lifts No No

Exterior Ramps and Railings No Yes

Interior Routes

Corridor and Lobby H/C Lifts No Yes

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies No Change in Elevation

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium No

Cafeteria 1st Floor Yes No Not on Accessible Route No Yes

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms Room 316 Yes No Not on Accessible Route

Gymnasium No

Library No

Main Office Room 211 Yes No Not on Accessible Route

Multi-purpose Room 1st Floor Yes No Not on Accessible Route No Yes

Nurse's Room Room 323 Yes No Not on Accessible Route

Pool No

Science Lab No

Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 3 of 38

Page 4: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1-AW2

Instance Condition 2 - Between Good and Fair

Instance Quantity 2

Instance Quantity Uom EACH

Deficiency No deficiencies recorded

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CORNICE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

DOOR HARDWARE Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 3 - Fair

Deficiency STEEL: MAJOR RUSTING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 4 of 38

Page 5: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

DOORS

LINTELS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C

Violations No violations recorded.

TRANSOM/SIDE LIGHT Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 7,500

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 7,500

Instance Quantity Uom S.F.

Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 5 of 38

Page 6: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency STONE: DETERIORATED MASONRY SILLS

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 6 of 38

Page 7: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REMOVE AND REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency STONE: CRACKS AT BUILDING CORNERS

Roof Plan reference

Elevation

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 7 of 38

Page 8: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

EXTERIOR WALLS

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 3,500

Replacement Uom C.F.

InspectedInstance on All Roofs

Instance Condition 2 - Between Good and Fair

Instance Quantity 3,500

Instance Quantity Uom C.F.

Deficiency No deficiencies recorded

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 7,500

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Inspected

Condition 2 - Between Good and Fair

Deficiency RAILINGS/PANELS: DETERIORATED, MINOR RUSTING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 8 of 38

Page 9: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

ROOF

Roofing

ROOF BARRIER

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Built-Up: Roof 1

Instance Condition 3 - Fair

Instance Quantity 7,300

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1995

Source of Installation Documented

Deficiency BUILT-UP: FLASHING: CAP FLASHING DAMAGED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 9 of 38

Page 10: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - Roof 1

Violations No violations recorded.

Deficiency BUILT-UP: FLASHING: CAP FLASHING MISSING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action INSTALL NEW

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 10 of 38

Page 11: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Deficiency Photo1

Facade A - Roof 1

Violations No violations recorded.

Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Built-Up: Roof 1

Deficiency Quantity 7,300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

InspectedInstance on Modified Bitumen: Roof 2, 3

Instance Condition 3 - Fair

Instance Quantity 200

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1995

Source of Installation Documented

Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Modified Bitumen: Roof 2, 3

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 3 - Fair

Deficiency DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 11 of 38

Page 12: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

ROOF

Roofing

ROOFING DRAINS

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 4 - Between Fair and Poor

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE DOOR AND FRAME

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 12 of 38

Page 13: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1

BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 35

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

BH

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 13 of 38

Page 14: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 5 - Poor

Deficiency BRICK: CRACKS/SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C

Violations No violations recorded.

Deficiency STONE: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 14 of 38

Page 15: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Deficiency Photo1

Facade A

Violations No violations recorded.

RAILINGS Inspected

Condition 5 - Poor

Deficiency RUST - MAJOR

Roof Plan reference

Deficiency Quantity 25

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

STAIRS/RAMPS Inspected

Condition 5 - Poor

Deficiency STONE: WORN-OUT TREAD/RISER/NOSING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 15 of 38

Page 16: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 4,120

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: Basement

Instance Condition 1 - Good

Instance Quantity 120

Instance Quantity Uom S.F.

Installation Year 2016

Source of Installation Documented

Deficiency No deficiencies recorded

InspectedInstance on Aluminum - Double Hung: All Facades except Basement

Instance Condition 3 - Fair

Instance Quantity 4,000

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 16 of 38

Page 17: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

EXTERIOR

WINDOWS

WINDOWS

Instance Quantity Uom S.F.

Installation Year 2000

Source of Installation Documented

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency STEEL COLUMNS/BEAMS: MAJOR RUSTING

Deficiency Location/Instance Basement Storage Room

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Basement Storage Room

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Boiler Room

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 17 of 38

Page 18: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING

Deficiency Location/Instance Boiler Room

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS

Deficiency Location/Instance Boiler Room

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Boiler Room

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 18 of 38

Page 19: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete, Masonry

Condition 4 - Between Fair and Poor

Deficiency BRICK: CRACKED/SPALLED

Deficiency Location/Instance Boiler Room, near Paint Srorage Room

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE

Deficiency Location/Instance Boiler Room

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 19 of 38

Page 20: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS Inspected

Deficiency Photo1

Boiler Room

Violations 35415065N

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS, SPALLING

Deficiency Location/Instance Facade A

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Vault

Violations No violations recorded.

Slab Structure Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Vault/Ash Hoist Doors and Framing Does not Exist

AUDITORIUM Does not Exist

CAFETERIA Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 20 of 38

Page 21: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

CAFETERIA

Door(s)

InspectedInstance on 1st Floor

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Main Entrance

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance

Violations No violations recorded.

Deficiency WOOD: DAMAGED LOUVER

Deficiency Location/Instance Multi-Purpose Room Entrances

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Multi-Purpose Room Entrance

Violations No violations recorded.

Fixed Equipment

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Center, Near Entrance, South side, East side, North side, West side

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 21 of 38

Page 22: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

CAFETERIA

Floor Finish

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance Room 112

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Room 112

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 22 of 38

Page 23: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 316

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 316

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Main Entrance Vestibule, Rooms 211, 216, 316, 319, and others

Deficiency Quantity 11

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Floor Finish Inspected

Condition 3 - Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Rooms 217, 223, 317, Corridor near Stair B/3, Corridor near Exit 2,and others

Deficiency Quantity 900

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 23 of 38

Page 24: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Purpose of Action LEVEL 2

Deficiency Photo1

Room 223

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Corridor near Room 315

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 315

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Main Entrance Vestibule

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 24 of 38

Page 25: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Deficiency BRICK: CRACKS/SPALLING

Deficiency Location/Instance Exit 2 Vestibule

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit 2 Vestibule

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Main Entrance Vestibule

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 25 of 38

Page 26: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

Not RequiredInstance on 1st Floor

Door(s)

Does not ExistInstance on 1st Floor

Floor Finish

Not RequiredInstance on 1st Floor

Walls

Not RequiredInstance on 1st Floor

LIBRARY Does not Exist

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

Not RequiredInstance on 1st Floor

Fixed Equipment

Does not ExistInstance on 1st Floor

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

InspectedInstance on 1st Floor

Stage Inspected

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtain Rigging Does not Exist

Does not ExistInstance on 1st Floor

Stage Curtains Does not Exist

Does not ExistInstance on 1st Floor

Walls

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 26 of 38

Page 27: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 3 - Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stairs A/Basement, B/1

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair A/Basement

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Stair B/Basement

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 27 of 38

Page 28: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Deficiency Photo1

Stair B/Basement

Violations No violations recorded.

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 5 - Poor

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Stairs A/1, 2

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair A/2

Violations No violations recorded.

Deficiency VINYL TILES: WORN-OUT TILES

Deficiency Location/Instance Stair B/3

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 28 of 38

Page 29: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Deficiency Photo1

Stair B/3

Violations No violations recorded.

Deficiency STONE: BROKEN/MISSING

Deficiency Location/Instance Main Entrance Vestibule

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Deficiency ROLLED ASPHALT: CRACKS

Deficiency Location/Instance Stairs A/Basement, 1, B/Basement, 1, 2, Bulkhead, and others

Deficiency Quantity 500

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/Basement

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 29 of 38

Page 30: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency STONE MOLDINGS: CRACKS/SPALLING

Deficiency Location/Instance Stair A/2

Deficiency Quantity 5

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair A/2

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stairs A/Basement, B/1, 3

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/3

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 3 - Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 308

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 30 of 38

Page 31: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

TOILET ROOMS - STAFF

Ceiling

Deficiency Photo1

Room 308

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 5 - Poor

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Room 228

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 228

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 3 - Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Rooms 308, 328

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 31 of 38

Page 32: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

INTERIOR

TOILET ROOMS - STAFF

Walls

Deficiency Photo1

Room 328

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Rooms 228, 308, 328

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 328

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Stalls Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Walls Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 32 of 38

Page 33: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

LIFE SAFETY Inspected

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Inspected

Condition 5 - Poor

Deficiency CONTAINER DAMAGED

Deficiency Location/Instance East side of TCU

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

East side of TCU

Violations No violations recorded.

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Does not Exist

Culverts - Concrete Covering Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Drainage System for Soil Inspected

Catch Basins/Manhole - Surrounded by Soil Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Soil Covering Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance Beach 34th Street, Beach 35th Street

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 33 of 38

Page 34: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

SITE Inspected

FENCES

Deficiency Photo1

Beach 35th Street

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance Beach 35th Street

Deficiency Quantity 120

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 35th Street

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Near TCU

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 34 of 38

Page 35: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

SITE

PAVING

Student Non-Use

Asphalt

Deficiency Photo1

Near TCU

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Schoolyard

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 35 of 38

Page 36: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

SITE

PAVING

Student Use

Concrete

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Pavers Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Near TCU

Deficiency Quantity 125

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near TCU

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED CURBS

Deficiency Location/Instance Beach 34th Street, Beach 35th Street

Deficiency Quantity 45

Quantity Uom L.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 36 of 38

Page 37: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 35th Street

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Beach 34th Street, Beach 35th Street

Deficiency Quantity 475

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 35th Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard

Benches

Does not ExistInstance on Schoolyard

Fence

Does not ExistInstance on Schoolyard

Pavement

Does not ExistInstance on Schoolyard

Play Equipment

InspectedInstance on Schoolyard

Condition 1 - Good

Deficiency No deficiencies recorded

Safety Surfacing

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106

PB/A&W Print Date: 9/13/2020Page 37 of 38

Page 38: NYC Department of Education - NYCSCA · SA : Q106 Architectural - Senior 2019-04-11 7:33 AM 2019-06-05 5:04 PM AA : Q106 Architectural - Associate 2019-04-11 8:24 AM 2019-04-11 6:06

Question Response

SITE

PLAYGROUNDS

Safety Surfacing

InspectedInstance on Schoolyard

Condition 1 - Good

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Schoolyard

PLAYING SURFACE Inspected

Playing Field Does not Exist

Running Track Inspected

InspectedInstance on Schoolyard

Instance Condition 1 - Good

Deficiency No deficiencies recorded

RETAINING WALLS Does not Exist

SEATING Inspected

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance North side of Schoolyard

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side of Schoolyard

Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q106