Asset: P.S. 106 - QUEENS, 180 BEACH 35 STREET, New York, 11691
Inspection Id Inspection Type Time In Last Edited
SA : Q106 Architectural - Senior 2020-03-05 11:02 AM 2020-03-17 12:17 PM
AA : Q106 Architectural - Associate 2020-03-05 10:51 AM 2020-03-05 4:46 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Rachelle Legions
Organization P.S. 106 - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal had no comments regarding the physical condition of thebuilding at this time.
Custodian Was not present
Fireman Rupert Palmer
Building Square Footage 23000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Number of Classrooms 12
Comments on the Year Built 1931
Student Population 210
Staff Population 49
Weather Fair
Facade Photo
Corner of Beach 35th Street and RockawayBoardwalk - Southeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 1 of 38
Main Entrance Photo
Facade A - Beach 35th Street
Roof Photo
Roof 1- Northeast View
Have any Systems/Major Building Components been upgraded? Yes
Systems: New Running Track, Playground, Play Equipment andSafety Surfacing, New Schoolyard paving, Site Benches,Site Paving near TCU's, Limited Site Fencingreplacement, Exterior Stair repairs near Exits 2 and 4.
Year: 2017
Systems: Flood Elimination Project including Structural ConcreteFireproofing repairs, limited Exterior Masonry repointingand repairs, Areaway restoration and Grating replacement,new Exterior Doors and Transoms, Louvres and BasementWindows and Roof
Year: 2016
Systems: Parapet and Exterior Masonry repointing and repairs, NewCoping and Roof Barriers
Year: 2009
Systems: Basement Flood Elimination Project including InjectionWaterproofing at Foundation Walls
Year: 2008
Systems: Limited Exterior Door replacement
Year: 2005
Systems: New Windows and Exterior Guards except Basement.
Year: 2000
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 2 of 38
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits No Saddle height > 1/2"
Exterior H/C Lifts No No
Exterior Ramps and Railings No Yes
Interior Routes
Corridor and Lobby H/C Lifts No Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria 1st Floor Yes No Not on Accessible Route No Yes
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms Room 316 Yes No Not on Accessible Route
Gymnasium No
Library No
Main Office Room 211 Yes No Not on Accessible Route
Multi-purpose Room 1st Floor Yes No Not on Accessible Route No Yes
Nurse's Room Room 323 Yes No Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 3 of 38
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1-AW2
Instance Condition 2 - Between Good and Fair
Instance Quantity 2
Instance Quantity Uom EACH
Deficiency No deficiencies recorded
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
DOOR HARDWARE Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 3 - Fair
Deficiency STEEL: MAJOR RUSTING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 4 of 38
Question Response
EXTERIOR
DOORS
LINTELS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
TRANSOM/SIDE LIGHT Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 7,500
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 7,500
Instance Quantity Uom S.F.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 5 of 38
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: DETERIORATED MASONRY SILLS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 6 of 38
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REMOVE AND REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: CRACKS AT BUILDING CORNERS
Roof Plan reference
Elevation
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 7 of 38
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 3,500
Replacement Uom C.F.
InspectedInstance on All Roofs
Instance Condition 2 - Between Good and Fair
Instance Quantity 3,500
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 7,500
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency RAILINGS/PANELS: DETERIORATED, MINOR RUSTING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 8 of 38
Question Response
EXTERIOR
ROOF
Roofing
ROOF BARRIER
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: Roof 1
Instance Condition 3 - Fair
Instance Quantity 7,300
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1995
Source of Installation Documented
Deficiency BUILT-UP: FLASHING: CAP FLASHING DAMAGED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 9 of 38
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Roof 1
Violations No violations recorded.
Deficiency BUILT-UP: FLASHING: CAP FLASHING MISSING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action INSTALL NEW
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 10 of 38
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Photo1
Facade A - Roof 1
Violations No violations recorded.
Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Built-Up: Roof 1
Deficiency Quantity 7,300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
InspectedInstance on Modified Bitumen: Roof 2, 3
Instance Condition 3 - Fair
Instance Quantity 200
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1995
Source of Installation Documented
Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Modified Bitumen: Roof 2, 3
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 3 - Fair
Deficiency DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 11 of 38
Question Response
EXTERIOR
ROOF
Roofing
ROOFING DRAINS
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 4 - Between Fair and Poor
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR AND FRAME
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 12 of 38
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 35
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
BH
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 13 of 38
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 5 - Poor
Deficiency BRICK: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 14 of 38
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo1
Facade A
Violations No violations recorded.
RAILINGS Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Roof Plan reference
Deficiency Quantity 25
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 5 - Poor
Deficiency STONE: WORN-OUT TREAD/RISER/NOSING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 15 of 38
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 4,120
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: Basement
Instance Condition 1 - Good
Instance Quantity 120
Instance Quantity Uom S.F.
Installation Year 2016
Source of Installation Documented
Deficiency No deficiencies recorded
InspectedInstance on Aluminum - Double Hung: All Facades except Basement
Instance Condition 3 - Fair
Instance Quantity 4,000
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 16 of 38
Question Response
EXTERIOR
WINDOWS
WINDOWS
Instance Quantity Uom S.F.
Installation Year 2000
Source of Installation Documented
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: MAJOR RUSTING
Deficiency Location/Instance Basement Storage Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement Storage Room
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Boiler Room
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 17 of 38
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING
Deficiency Location/Instance Boiler Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS
Deficiency Location/Instance Boiler Room
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Boiler Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 18 of 38
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete, Masonry
Condition 4 - Between Fair and Poor
Deficiency BRICK: CRACKED/SPALLED
Deficiency Location/Instance Boiler Room, near Paint Srorage Room
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Boiler Room
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 19 of 38
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS Inspected
Deficiency Photo1
Boiler Room
Violations 35415065N
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS, SPALLING
Deficiency Location/Instance Facade A
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Vault
Violations No violations recorded.
Slab Structure Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Vault/Ash Hoist Doors and Framing Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 20 of 38
Question Response
INTERIOR
CAFETERIA
Door(s)
InspectedInstance on 1st Floor
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Main Entrance
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Violations No violations recorded.
Deficiency WOOD: DAMAGED LOUVER
Deficiency Location/Instance Multi-Purpose Room Entrances
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Multi-Purpose Room Entrance
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Center, Near Entrance, South side, East side, North side, West side
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 21 of 38
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Room 112
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 112
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 22 of 38
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 316
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 316
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Main Entrance Vestibule, Rooms 211, 216, 316, 319, and others
Deficiency Quantity 11
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Floor Finish Inspected
Condition 3 - Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 217, 223, 317, Corridor near Stair B/3, Corridor near Exit 2,and others
Deficiency Quantity 900
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 23 of 38
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Purpose of Action LEVEL 2
Deficiency Photo1
Room 223
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Corridor near Room 315
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 315
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 24 of 38
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Deficiency BRICK: CRACKS/SPALLING
Deficiency Location/Instance Exit 2 Vestibule
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 2 Vestibule
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 25 of 38
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
Not RequiredInstance on 1st Floor
Door(s)
Does not ExistInstance on 1st Floor
Floor Finish
Not RequiredInstance on 1st Floor
Walls
Not RequiredInstance on 1st Floor
LIBRARY Does not Exist
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
Not RequiredInstance on 1st Floor
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
InspectedInstance on 1st Floor
Stage Inspected
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Does not Exist
Does not ExistInstance on 1st Floor
Stage Curtains Does not Exist
Does not ExistInstance on 1st Floor
Walls
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 26 of 38
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stairs A/Basement, B/1
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/Basement
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Stair B/Basement
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 27 of 38
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Deficiency Photo1
Stair B/Basement
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 5 - Poor
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Stairs A/1, 2
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/2
Violations No violations recorded.
Deficiency VINYL TILES: WORN-OUT TILES
Deficiency Location/Instance Stair B/3
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 28 of 38
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Photo1
Stair B/3
Violations No violations recorded.
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance Stairs A/Basement, 1, B/Basement, 1, 2, Bulkhead, and others
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/Basement
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 29 of 38
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency STONE MOLDINGS: CRACKS/SPALLING
Deficiency Location/Instance Stair A/2
Deficiency Quantity 5
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/2
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stairs A/Basement, B/1, 3
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/3
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 308
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 30 of 38
Question Response
INTERIOR
TOILET ROOMS - STAFF
Ceiling
Deficiency Photo1
Room 308
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 5 - Poor
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room 228
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 228
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 308, 328
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 31 of 38
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Deficiency Photo1
Room 328
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 228, 308, 328
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 328
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Stalls Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Walls Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 32 of 38
Question Response
LIFE SAFETY Inspected
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance East side of TCU
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
East side of TCU
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Does not Exist
Culverts - Concrete Covering Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Beach 34th Street, Beach 35th Street
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 33 of 38
Question Response
SITE Inspected
FENCES
Deficiency Photo1
Beach 35th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance Beach 35th Street
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 35th Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Near TCU
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 34 of 38
Question Response
SITE
PAVING
Student Non-Use
Asphalt
Deficiency Photo1
Near TCU
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Schoolyard
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 35 of 38
Question Response
SITE
PAVING
Student Use
Concrete
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Near TCU
Deficiency Quantity 125
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near TCU
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED CURBS
Deficiency Location/Instance Beach 34th Street, Beach 35th Street
Deficiency Quantity 45
Quantity Uom L.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 36 of 38
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 35th Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Beach 34th Street, Beach 35th Street
Deficiency Quantity 475
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 35th Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard
Benches
Does not ExistInstance on Schoolyard
Fence
Does not ExistInstance on Schoolyard
Pavement
Does not ExistInstance on Schoolyard
Play Equipment
InspectedInstance on Schoolyard
Condition 1 - Good
Deficiency No deficiencies recorded
Safety Surfacing
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 37 of 38
Question Response
SITE
PLAYGROUNDS
Safety Surfacing
InspectedInstance on Schoolyard
Condition 1 - Good
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Schoolyard
PLAYING SURFACE Inspected
Playing Field Does not Exist
Running Track Inspected
InspectedInstance on Schoolyard
Instance Condition 1 - Good
Deficiency No deficiencies recorded
RETAINING WALLS Does not Exist
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance North side of Schoolyard
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Schoolyard
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q106
PB/A&W Print Date: 9/13/2020Page 38 of 38