Asset: P.S./I.S. 113 - QUEENS, 78-23 87TH STREET, New York, 11385
Inspection Id Inspection Type Time In Last Edited
SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM
AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment The following components are inaccessible: Interior/LockerRoom/Cellar-Boys, Girls (Full of Storages)
Principal(s) Information
Principal Name Alejandro Megias
Organization P.S./I.S. 113 - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows:1. The Building Management System (BMS) is not working to regulatethe heating and cooling.2. The Gymnasium flooring is damaged.
Custodian Patrick Dorney
Fireman Richard Balcerzak
Building Square Footage 97000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+C+Attic+PH
Comments on the Number of Classrooms 40
Comments on the Year Built 1928
Student Population 900
Staff Population 110
Weather Fair
Facade Photo
Corner of 87th Street and 79thAvenue-North View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 1 of 34
Main Entrance Photo
Facade A - 87th Street
Roof Photo
Roof 6 - North View
Have any Systems/Major Building Components been upgraded? Yes
Systems: New Playground Installation
Year: 2015
Systems: Original Building: Partial Exterior Walls repointing, newRetaining Walls, Gutters and Leaders unclogged andRestoration, Coping repairs
Year: 2014
Systems: Foundation Wall Waterproofing at the Electric PanelRoom
Year: 2012
Systems: Original Building Exterior Door replacement,Assembly/Multipurpose Room upgrade, Exterior Wallrepointing, Foundation Wall repairs, Areaway Drainsconnected to Sewer System, New HC Toilet Accessoriesupgrading, Library renovation
Year: 2009
Systems: Original Building: Asphalt Shingle Roofing replacement(Roofs 1-5),
Year: 2002
Systems: Original Building Window Replacement
Year: 1996
Have there been any New Building Additions? Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 2 of 34
Comments on New Building Additions 2000+4500 SF; 2009+35,200 SF
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps Yes Yes
Rooms & Spaces
Art Rooms Room 107 Yes Yes
Auditorium No
Cafeteria Cellar Yes Yes No Yes
Classrooms Cellar, 1st-3rd Floors Yes Yes
Computer Rooms No
Gymnasium Cellar Yes Yes Yes Yes
Library Room 133 Yes Yes
Main Office Room 101 Yes Yes
Multi-purpose Room 2nd Floor Yes Yes Yes Yes
Nurse's Room Room 139 Yes Yes
Pool No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 3 of 34
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Science Lab Room 201, 203 Yes Yes
Toilet Rooms (Boys) Cellar, 1st-2nd Floor Yes Yes
Toilet Rooms (Girls) Cellar, 1st-3rd Floors Yes Yes
Toilet Rooms (Staff) Cellar, 1st-3rd Floors Yes Yes
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1-AW12
Instance Condition 3 - Fair
Instance Quantity 12
Instance Quantity Uom EACH
Deficiency AREAWAY DRAINS: CLOGGED
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 4 of 34
Question Response
EXTERIOR
AREAWAY
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
AW10
Violations No violations recorded.
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 3 - Fair
Deficiency METAL CLAD: DETERIORATED DOOR - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 5 of 34
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo1
Facade B-Exit 5
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 53,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 4 - Between Fair and Poor
Instance Quantity 53,000
Instance Quantity Uom S.F.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 6 of 34
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency BRICK: MAJOR / THRU CRACKS
Roof Plan reference
Elevation
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 7 of 34
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS AND SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
Deficiency BRICK: DETERIORATED MASONRY SILLS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 8 of 34
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 100
Quantity Uom L.F.
Potential Action REMOVE AND REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: EFFLORESCENCE
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 9 of 34
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPOINT
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 10 of 34
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 4,400
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 4,400
Instance Quantity Uom C.F.
Deficiency CONCRETE: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 11 of 34
Question Response
EXTERIOR
PARAPETS
Deficiency Photo1
Roof 6 - Facade J
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 43,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Single Ply, Mechanically Fastened Roof: Roof 5A
Instance Condition 3 - Fair
Instance Quantity 1,300
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2000
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Asphalt Shingle: Roofs 1-5
Instance Condition 3 - Fair
Instance Quantity 13,600
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2003
Source of Installation Custodial Staff
Deficiency ASPHALT SHINGLE: ROOFING: DAMAGED, WORN-OUT ORMISSING SHINGLES CURLING UP
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 12 of 34
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
InspectedInstance on IRMA: Roofs 6-10
Instance Condition 3 - Fair
Instance Quantity 28,100
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2009
Source of Installation Custodial Staff
Deficiency IRMA: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 30
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 13 of 34
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 4 Vestibule
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CUPOLA/ SPIRES/ TOWERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 14 of 34
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D - Exit 6
Violations No violations recorded.
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency STONE: CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F - Exit 8
Violations No violations recorded.
WINDOWS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 15 of 34
Question Response
EXTERIOR
WINDOWS
Replacement Quantity 8,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: 1928 Original Building
Instance Condition 3 - Fair
Instance Quantity 3,700
Instance Quantity Uom S.F.
Installation Year 1996
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Aluminum - Double Hung: 2000 Addition
Instance Condition 3 - Fair
Instance Quantity 400
Instance Quantity Uom S.F.
Installation Year 2000
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Aluminum - Other: 2009 Addition
Instance Condition 2 - Between Good and Fair
Instance Quantity 3,900
Instance Quantity Uom S.F.
Installation Year 2009
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 4 - Between Fair and Poor
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING
Deficiency Location/Instance Basement- Oil Tank Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 16 of 34
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Photo1
Basement- Oil Tank Room
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement- Cellar Boiler Room, Mechanical Equipment Room, Attic at1928 Original Building
Deficiency Quantity 270
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement- Boiler Room, B05 Storage
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 17 of 34
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE Inspected
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 3 - Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance 1st Floor-Electrical Panel Room, Cellar Boiler Room
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
1st Floor-Electrical Panel Room
Violations No violations recorded.
Deficiency CONCRETE: WATER INFILTRATION IN ELECTRICAL PANELROOM
Deficiency Location/Instance Cellar Floor, 1st Floor - Electrical Panel Room
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 18 of 34
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS Inspected
Deficiency Photo1
Cellar - Electrical Panel Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance PH, Attic at 1928 Original Building
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
PH
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Attic
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 19 of 34
Question Response
INTERIOR
STRUCTURAL
ROOF STRUCTURE Inspected
Deficiency Photo1
Attic
Violations No violations recorded.
VAULTS-BUNKERS Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on Cellar
Ceiling
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Cellar
Floor Finish
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Cellar
Stage
Does not ExistInstance on Cellar
Walls
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Cellar
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Room 203 Corridor near Room 203, 211
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 20 of 34
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 203
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 335
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 335
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 253, 254 Corridor near Room 139, 238B, 241, and others
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 21 of 34
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Corridor near Room 238B
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Corridor near Room 201, 211
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 201
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on Cellar
Ceiling
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 22 of 34
Question Response
INTERIOR
GYMNASIUM
Floor Finish
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage
Does not ExistInstance on Cellar
Walls
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Cellar
INTERIOR DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Cellar
Ceiling
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Cellar
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 133
Built-in Furnishing
Does not ExistInstance on Room 133
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 23 of 34
Question Response
INTERIOR
LIBRARY
Ceiling
InspectedInstance on Room 133
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 133
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 133
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 133
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InaccessibleInstance on Cellar - Boys (162 lockers)
InaccessibleInstance on Cellar - Girls
MULTI-PURPOSE ROOM Inspected
InspectedInstance on 2nd Floor
Ceiling
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 2nd Floor
Floor Finish
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 2nd Floor
Stage
InspectedInstance on 2nd Floor
Stage Inspected
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 24 of 34
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Stage
Stage Curtains
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near Entrance
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Window Curtains/Shades/Blinds
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 201, 203
Alternative use No
Fixed Equipment
InspectedInstance on Room 201, 203
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SCIENCE PREP ROOM Inspected
InspectedInstance on Room 201A, 203A
Alternative use No
Fixed Equipment
InspectedInstance on Room 201A, 203A
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 25 of 34
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair E/1 (Exit Vestibule 5)
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair E/1 (Exit Vestibule 5)
Violations No violations recorded.
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Exit Vestibule 8, 9
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit Vestibule 8
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 26 of 34
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Location/Instance Stair D/1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair D/1
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room 238
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 238
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 27 of 34
Question Response
INTERIOR
TOILET ROOMS - STAFF
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Room 238
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 238
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 214C
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 214C
Violations No violations recorded.
Floor Finish Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 28 of 34
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room 140
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 140
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Inspected
Condition 3 - Fair
Deficiency MINOR RUSTING
Deficiency Location/Instance Facade A - Entry 10
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Entry 10
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 29 of 34
Question Response
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance 87th Street, 79th Avenue
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
87th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance 79th Avenue
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 30 of 34
Question Response
SITE
FENCES
Deficiency Photo1
79th Avenue
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 31 of 34
Question Response
SITE
PAVING
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Exit to 87th Street
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit to 87th Street
Violations No violations recorded.
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED CURBS
Deficiency Location/Instance 87th Street
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
87th Street
Violations No violations recorded.
Deficiency HEAVING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 32 of 34
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Location/Instance 79th Avenue, 88th Street
Deficiency Quantity 125
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
88th Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 78th Avenue, 79th Avenue , 88th Street
Deficiency Quantity 225
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
78th Avenue
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard
Benches
Does not ExistInstance on Schoolyard
Fence
InspectedInstance on Schoolyard
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavement
InspectedInstance on Schoolyard
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113
PB/A&W Print Date: 6/21/2019Page 33 of 34
Question Response
SITE
PLAYGROUNDS
Pavement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Play Equipment
InspectedInstance on Schoolyard
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Schoolyard
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q113