Page 1: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.
Page 2: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

OBJECTIVESOBJECTIVES

1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable installation. 3. Describe the basic operation of the telephone system in the United States. 4. Identify the wire types used in telephone systems. 5. Describe the accepted color coding strategies that are commonly used in telephone installations. 6. Identify typical physical topologies, and state the advantages and disadvantages for each. 7. List the accepted logical topologies. 8. State the general instructions for running copper cabling. 9. Given a specific application, identify the grade of cabling that would be appropriate.10. Identify Type-66 and Type-110 insulation displacement connectors.11. Identify the various types of modular jacks that are commonly used with telecommunications systems.

Page 3: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-1: Basic Telco Organization

Page 4: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-2: Analog Waveform

Page 5: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-3: Digital Waveform

Page 6: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Table 2-1: Decimal Column Values

Page 7: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Table 2-2: Binary Column Values

Page 8: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Table 2-3: Digital to Binary Conversion Table

Page 9: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Table 2-3: Digital to Binary Conversion Table (continued)

Page 10: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Table 2-3: Digital to Binary Conversion Table (continued)

Page 11: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-4: Square Wave Noise

Page 12: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-5: Frequency Components of a 1kHz Square Wave

Page 13: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-6: Harmonic Distortion with Inadequate Bandwidth

Page 14: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-7: Flat 4-Conductor Telephone Cable

Page 15: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-8: 24AWG UTP Telephone Cable

Page 16: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-9: Noise Distortion of a Data Signal

Page 17: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Pair #1: Green/Red (tip/ring).

The solid-color twisted pair marking system method uses one color to identify each of six wires.

Pair #2: Black/Yellow (tip/ring).

Pair #3: White/Blue (tip/ring).

Page 18: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The standard color-coding method uses band-striped twisted pair markings:

Pair #1: White/Blue. The tip wire is predominantly white with blue bands. The ring wire is predominantly blue with white bands.

Pair #2: White/Orange. The tip wire is primarily white with orange bands. The ring wire is primarily orange with white bands.

Pair #3: White/Green. The tip wire is mostly white with green bands. The ring wire is mostly green with white bands.

Page 19: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The standard color-coding method uses band-striped twisted pair markings: (continued)

Pair #4: White/Brown. The tip wire is predominantly white with brown bands. The ring wire is predominantly brown with white bands.

Page 20: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-10: Color Coded Wire

Page 21: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Table 2-4: Color Coding for 25-Pair Cables

Page 22: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-11: UTP Connectors for Telephone and Data Wiring

Page 23: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-12: Coaxial Cable

Page 24: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-13: Thicknet Connection

Page 25: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-14: Attachment Unit Interface

Page 26: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-15: Intrusive Tap

Page 27: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-16: Vampire Tap

Page 28: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-17: Thinnet Arrangement

Page 29: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 OBJECTIVESLAB 1 OBJECTIVESCable Identification

To identify the cable types provided To identify the cable types provided with this coursewith this course

To identify the parts that make To identify the parts that make up the Thicknet active tap kitup the Thicknet active tap kit

Page 30: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-18: Cable Types

CAT5 UTP

Type-1A STP

RG6 Coax

RG58 Coax

RG8 Coax

CAT5 STP

Page 31: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-18: Thicknet Tap (continued)

Thicknet Active Tap Kit

Page 32: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The cable’s jacket should indicate that it is a Category 5 cable, and it may be either light gray, or white, in color.

TIPTIP

Page 33: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The cable’s jacket should indicate that it is a shielded Category 5 cable, and it may be blue in color.

TIPTIP

Page 34: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The cable’s jacket should indicate that it is a shielded cable, specified for IBM, and it will probably be black in color. The cable itself may appear somewhat flattened.

TIPTIP

Page 35: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

This cable’s jacket should indicate that it is designed for cable television transmission (CATV designation), and will probably display its 75-ohm impedance as well. It is normally black in color.

TIPTIP

Page 36: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

RG58 is probably the smallest diameter cable in the sample set. Its jacket should be black, and will be marked with the RG58 designation.

TIPTIP

Page 37: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

RG8 is probably the largest diameter cable in the sample set. Its jacket should be yellow or orange, and may be marked with the Ethernet designation. It will also indicate an impedance of 50 ohms.

TIPTIP

Page 38: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The AMP Thicknet tap kit is basically composed of the clamp assembly, pressure block, button-head socket screw (tightened with the included hex wrench), braid terminators (2), tap body, and a probe assembly. An application tool is used to drill through the cable to the center conductor and to thread the probe assembly.

TIPTIP

Page 39: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 QUESTIONSLAB 1 QUESTIONS

Which one of the cable types included in this lab procedure is used for cable television transmission?

11

Page 40: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 QUESTIONSLAB 1 QUESTIONS

Concerning the installation of the Thicknet active tap, what is the purpose for the hex wrench included in the kit?

22

Page 41: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 QUESTIONSLAB 1 QUESTIONS

According to the instruction sheet for the installation of the Thicknet active tap, what are the two purposes for which the application tool is used?

33

Page 42: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 QUESTIONSLAB 1 QUESTIONS

What is the diameter of the RG8 coaxial cable around which the Thicknet active tap must clamp?

44

Page 43: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 QUESTIONSLAB 1 QUESTIONS

What was the impedance of the following cable types that you examined during this lab?

55

(a) CAT5 UTP cable(b) CAT5 STP cable(c) Type-1A STP cable(d) RG6 coaxial cable(e) RG58 coaxial cable(f) RG8 coaxial cable

Page 44: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 QUESTIONSLAB 1 QUESTIONS

What would you expect the color of the outer jacket for RG8 coaxial cable to be?

66

Page 45: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 1 QUESTIONSLAB 1 QUESTIONS

Which of the cable types from the samples you examined possessed the smallest diameter?

77

Page 46: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

If one wire run is damaged, it will not affect the other devices in that system.

Some advantages of the star topology include:

11

It is easy to locate a problem in the system.22

Additions and changes can be made very easily, without interfering with the rest of the system.

33

Page 47: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-19: Star Topology

Page 48: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The bus topology is passive (it does not actively move the data signal). Therefore, if one device fails, it does not affect the others.

The advantages of a bus topology are:

11

The system does not have to be shut down in order to add other devices.

22

Page 49: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-20: Bus Topology

Page 50: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

If a cut should occur in the wire, the entire network will be brought down. The connected devices will work in stand-alone mode, but will not be able to communicate with each other.

The disadvantages of a bus topology are:

11

Only one device can transmit at any one time. The more devices on a cable run, the slower the network.

22

Page 51: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

If any additions are to be made to the system, the system must be shut down.

Disadvantages of the ring topology are:

11

If a break occurs in the cable, the entire system shuts down.

22

Page 52: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-21: Combination of Star and Bus Topology

Page 53: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Never put a splice behind a wall or in an area where it cannot be accessed.

The following general tips for running network cable will help you become acquainted with basic data cabling concepts:

Always test the cable runs after the installation is complete.

If possible, avoid placing splices on cable runs altogether. If there is a real problem, pull a new cable.

Page 54: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Do not pull 4-pair cable with more than 25 pounds of pulling force.

The following general tips for running network cable will help you to become acquainted with basic data cabling concepts: (continued)

Do not run data cables in parallel with any type of electrical cables.

Page 55: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Maintain the following separation between tele-communications wiring and other types of wiring:

The following general tips for running network cable will help you to become acquainted with basic data cabling concepts: (continued)

Electrical bare light, or power of any voltage

5 feetElectrical open wiring under 300 volts 2 inchesElectrical wires in conduit, or in armored or nonmetallic sheath cable/power ground wires

none

Radio and television antenna lead and ground wires 2 inchesOpen signal/control wiring under 300 volts noneCommunity television systems coaxial cables, with grounded shield

none

Telephone service drop wire, aerial or buried 2 inchesNeon signs, and associated wiring from transformer 6 inchesFluorescent lighting 5 inchesLightning wire 6 feet

Page 56: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Minimum separations between residential and light commercial telecommunications wiring are specified in TIA/EIA 570. When in doubt, use the rule of sixes:

The following general tips for running network cable will help you to become acquainted with basic data cabling concepts: (continued)

Six feet of separation between telephone wiring and open high-voltage wiring, lightning grounding wire, or grounding rods

Six inches of separation from all other high-voltage wire, unless in conduit

Page 57: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Never bend the cable sharply, or cut the sheath intended to protect the conductors.

The following general tips for running network cable will help you to become acquainted with basic data cabling concepts: (continued)

Always maintain correct polarity.

Always maintain the line number with respect to the pair number.

Always use plastic, nonmetallic staples.

Always leave a pull cord in the conduit for future cable pulls.

Page 58: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Never run voltage and telecommunication cables in the same conduit.

The following general tips for running network cable will help you to become acquainted with basic data cabling concepts: (continued)

If possible, avoid running telecommunication cables under carpeting to avoid damage, or slow degradation, to the cable.

Try to run cabling through the inner walls rather than the outer walls if possible.

Page 59: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Do not run Telco wiring parallel to electrical wiring. Instead, always cross electrical wiring at 90-degree angles. Also, never share bore holes with any electrical wiring.

The following general tips for running network cable will help you to become acquainted with basic data cabling concepts: (continued)

Avoid running wire near known sources of heat.

Always conceal wire runs. Do not leave wire runs exposed.

Always leave a one- to three-foot service loop of wire slack at outlets, or termination points, for later additions, changes, or repairs.

Page 60: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Never share bore holes with any type of electrical wiring.

The following are general tips for the installation of telecommunication outlets:

All data cabling outlets should be set up to handle either two 100-ohm UTP cables, or one 100-ohm UTP cable and one cable of the following:

2-pair, 150-ohm STP

2-strand, 62.5/125-micron optical fiber

Page 61: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Place Telco outlets at the same wall height as electrical outlets, but no closer than 12 inches, keeping in mind that they should not share the same stud space.

The following are general tips for the installation of telecommunication outlets: (continued)

Always consider the current layout of the furniture, and how it could be rearranged when you are installing telecommunication outlets.

Page 62: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 2 OBJECTIVELAB 2 OBJECTIVECable Examinations

To examine the construction and To examine the construction and makeup of the various cable types makeup of the various cable types provided with this courseprovided with this course

Page 63: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Try not to damage any of the inside wires as you make the slit.

TIPTIP

Page 64: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-22: Examining the Contents of CAT5 UTP

Page 65: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Recall your reading about twisted-pair cable, and the purpose for the twisting.

TIPTIP

Page 66: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

You will want to use the 24-gauge marking position on the wire stripper.

TIPTIP

Page 67: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Try to depict the twist, as well as the color markings, for each of the pairs. Identify the tip and ring, and don’t worry if your drawing doesn’t win any art awards.

TIPTIP

Page 68: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Try not to damage any of the inside wires as you make the slit.

TIPTIP

Page 69: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-23: Examining the Contents of CAT5 STP

Page 70: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-24: Examining the Contents of Type-1A STP

Page 71: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

See if you can do this without putting any nicks in the center conductor. The wire stripper will help to remove the insulation once the cut has been made.

TIPTIP

Page 72: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-25: Examining the Contents of RG6

Page 73: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Although the center conductor for RG6 is obviously solid, some types of coaxial cable use stranded conductor. These coaxial types are generally more flexible than those with solid center conductors.

TIPTIP

Page 74: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-26: Examining the Contents of RG58

Page 75: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-27: Examining the Contents of RG8

Page 76: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 2 QUESTIONSLAB 2 QUESTIONS

What is the significance of any differences in the number of twists per inch between the pairs in UTP/STP cable?

11

Page 77: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 2 QUESTIONSLAB 2 QUESTIONS

In 4-pair UTP/STP which wire, tip or ring, is mostly white?

22

Page 78: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 2 QUESTIONSLAB 2 QUESTIONS

When comparing RG6, RG58, and RG8, which type of coaxial cable contains the most shielding?

33

Page 79: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 1-28: Binding Post Termination

Page 80: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Never nick the conductors when removing the sheath.

The general tips on binding post connections are as follows:

Conductors always wind clockwise, between the two washers.

Ensure that the insulation does not get caught under the screw terminals.

Always trim off the excess bare wire to avoid shorting out the connection.

Page 81: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Always leave additional slack wire in case future repairs are required.

The general tips on binding post connections are as follows: (continued)

Do not overtighten the screw terminals, or the wire could break off. In addition, the threads will strip out.

Page 82: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-29: Impact or Punch-down Tool

Page 83: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-30: Standard and CAT5 Pair Spacing

Page 84: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-31: Impact or Punch-down Tool with Blades

Page 85: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-32: Electricians’ Scissors

Page 86: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-33: Diagonal Cutting Pliers

Page 87: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-34: Slotted-head Screwdriver

Page 88: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-35: Phillips-head Screwdriver

Page 89: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-36: Wire Stripper

Page 90: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-37: RG8 Wire Stripper

Page 91: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-38: Tone Generator and Signal Probe

Page 92: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-39: MODAPT® Test Adapter

Page 93: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-40: Modular Crimpers

Page 94: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 3 OBJECTIVELAB 3 OBJECTIVETool Identification

To properly identify common tools To properly identify common tools used for CAT5 and coaxial cable used for CAT5 and coaxial cable installationsinstallations

Page 95: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations

Cable Stripper, RG58/RG6

Wire Stripper, CAT5 Punch-down Tool, Steel

Cable Stripper, RG8/CAT5

Page 96: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations (continued)

Punch-down Tool, Plastic

Electrical Tape Twine

Punch-down Blades, 110/66

Page 97: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations (continued)

Electricians’ Scissors

Pliers, Diagonal Cutting Screwdriver, Slotted-Head

Utility Knife

Page 98: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations (continued)

Screwdriver, Phillips-Head

Pliers, Needle-nose Pliers, Groove-joint

Insertion/Extraction Tool

Wrench, Adjustable Dental Pick

Page 99: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations (continued)

Crimping Tool, RJ45

Crimping Tool, Pin Nippers, End-Cutting

Crimping Tool, RG58/RG6

Page 100: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations (continued)

Fish Tape, Steel

Hex Wrench Pencils, Colored (set)

Thicknet Application Tool

Page 101: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations (continued)

Tension Scale/Tape Measure

Cable Tester, Continuity-type Multimeter, Digital

Label Markers

Page 102: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-41: Common Tools for Cable Installations (continued)

Level II Testers

Page 103: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 3 QUESTIONSLAB 3 QUESTIONS

How many different types of cable or wire strippers are included in the tool list?

11

Page 104: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 3 QUESTIONSLAB 3 QUESTIONS

What are the two types of punch-down blades provided with this course?

22

Page 105: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 3 QUESTIONSLAB 3 QUESTIONS

Identify a tool reviewed in the text that is not supplied for this course.

33

Page 106: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 3 QUESTIONSLAB 3 QUESTIONS

How many different types of crimpers are included in the tool list?

44

Page 107: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

6-position plugs with 6-position jacks

Some FCC USOC test requirements address the mating of:

4-position plugs with 6-position jacks

8-position plugs with 8-position jacks

6-position plugs with 8-position jacks

Page 108: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-42: RJ11 Jack (a) and Plug (b)

Page 109: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-43: USOC RJ11

Page 110: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-44: USOC RJ14

Page 111: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-45: Telco 8P8C

Page 112: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-46: RJ45 Jack (a) and Plug (b)

Page 113: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-47: TIA/EIA T568A Plug

Page 114: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Pin 1 = T3

The tip and ring assignments for TIA/EIA T568A are:

Pin 2 = R3

Pin 3 = T2

Pin 4 = R1

Pin 5 = T1

Pin 6 = R2

Pin 7 = T4

Pin 8 = R4

Page 115: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-48: TIA/EIA T568B Plug

Page 116: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Pin 1 = T2

The tip and ring assignments for TIA/EIA T568B are:

Pin 2 = R2

Pin 3 = T3

Pin 4 = R1

Pin 5 = T1

Pin 6 = R3

Pin 7 = T4

Pin 8 = R4

Page 117: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-49: Telco Outlet

Page 118: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

At least two station cable pairs must be connected at every installed outlet.

Telecommunications outlets should meet the following criteria:

The minimum number usable termination points at the wiring closet is 3 per user.

Outlets may be recessed, flush-mounted, or surface-mounted.

When installed on building exteriors, outlets must be weather resistant.

Page 119: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Always use the minimum number of connections possible. Each additional connection to the system will degrade its overall performance.

For quality installations, keep the following suggestions in mind:

During installations, always install additional modular jacks, as well as service loops, to prepare the system for future upgrades, changes, moves, and repairs.

Page 120: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

All installations must be performed in a neat and orderly fashion. Documentation should include information as to where all outlets and cable runs are located, and should use a clearly understandable method of labeling the cable runs.

For quality installations, keep the following suggestions in mind: (continued)

Always install cables that are rated at the highest data speeds currently available, and never connect cables to any equipment or connector that is rated lower than that specified for the category of wire being used by the system.

Page 121: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Once all of the telecommunications components have been installed, the entire system (cabling runs and associated equipment) must be tested for proper performance.

For quality installations, keep the following suggestions in mind: (continued)

Page 122: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 4 OBJECTIVELAB 4 OBJECTIVETerminating CAT5 with RJ45/T568A Jacks

To properly terminate CAT5 UTP To properly terminate CAT5 UTP cable onto CAT5-compliant RJ45 cable onto CAT5-compliant RJ45 termination jacks using the T568A termination jacks using the T568A configurationconfiguration

Page 123: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-50: Untwisting the Cable Pairs

Page 124: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Keep the individual pairs grouped together for ease of identification, because some tip wires may not have any visible trace of color and may appear to be solid white.

TIPTIP

Page 125: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Look on the jack cap first for a manufacturer’s color code. If you find one, use it, because some jacks are manufactured with internal cross connections. For stop-end jacks, make sure that the conductors are inserted so that the cable jacket resides inside of the jack cap, with the tips of the wires inserted to the very end of the cap.

TIPTIP

Page 126: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

zzzzzzzzzzzzz

Figure 2-51: Inserting Wires in a Straight-through Jack Cap

Page 127: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

For stop-end jacks, insert the jack cap/housing combination into the crimping tool, apply pressure to the cable to make sure that the conductors remain inserted to the very ends of the jack, and apply firm, even pressure to the crimping tool to attach the jack.

TIPTIP

Page 128: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Snap jacks can be pried apart, using a slotted-head screwdriver, and reused for practice. Stop-end jacks must be clipped off, thrown away, and replaced in order to practice on the same piece of cable. If you must clip the cable ends to remove stop-end jacks for practice purposes, under no circumstances allow the cable to become shorter than four feet (48 inches) long. This cable will be used for later labs. If necessary, practice using pieces of scrap cable.

TIPTIP

Page 129: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The tension scale/tape measure is exactly one meter long. Measure the cable to the 3-foot marker, place the start of the measure at that point, and measure at least 12 more inches beyond it. If the total length of the cable is less than four feet, you will have to discard it (or add it to the practice cable scrap pile) and try again using a new piece of cable. You may reuse the jacks if they are the snap type.

TIPTIP

Page 130: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 4 QUESTIONSLAB 4 QUESTIONS

What is the purpose of twisting the cable pairs in CAT5 cable?

11

Page 131: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 4 QUESTIONSLAB 4 QUESTIONS

List the pin/pair configuration for the TIA/EIA T568A standard.

22

Page 132: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 4 QUESTIONSLAB 4 QUESTIONS

What is the minimum length required for the completed T568A terminated CAT5 cable in this lab?

33

Page 133: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 5 OBJECTIVELAB 5 OBJECTIVETerminating CAT5 with RJ45/T568B Jacks

To properly terminate CAT5 UTP To properly terminate CAT5 UTP cable onto CAT5-compliant RJ45 cable onto CAT5-compliant RJ45 termination jacks using the T568B termination jacks using the T568B configurationconfiguration

Page 134: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Keep the individual pairs grouped together for ease of identification, because some tip wires may not have any visible trace of color and may appear to be solid white.

TIPTIP

Page 135: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Look on the jack cap first for a manufacturer’s color code. If you find one, use it, because some jacks are manufactured with internal cross connections. For stop-end jacks, insert the conductors so that the cable jacket resides inside of the jack cap, and the tips of the wires reach to the very end of the cap.

TIPTIP

Page 136: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-52: Trimming Excess Cable

Page 137: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-53: Crimping the Jack Housing

Page 138: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

For stop-end jacks, insert the jack cap/housing combination into the crimping tool, apply pressure to the cable to keep the conductors inserted to the very ends of the jack, and apply firm, even pressure to the crimping tool to attach the jack.

TIPTIP

Page 139: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-54: Using the Crimping Tool

Page 140: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Snap jacks can be pried apart, using a slotted-head screwdriver, and reused for practice. Stop-end jacks must be clipped off, and thrown away, and replaced in order to practice on the same piece of cable. If you must clip the cable ends to remove stop-end jacks for practice purposes, under no circumstances allow the cable to become shorter than four feet (48 inches) long. This cable will be used for later labs. If necessary, practice using pieces of scrap cable.

TIPTIP

Page 141: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The tension scale/tape measure is exactly one meter long. Measure the cable to the 3-foot marker, place the start of the measure at that point, and measure at least 12 more inches beyond it. If the total length of the cable is less than four feet, you will have to discard it (or add it to the practice cable scrap pile) and try again using a new piece of cable. You may reuse the jacks if they are the snap type.

TIPTIP

Page 142: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 5 QUESTIONSLAB 5 QUESTIONS

List the advantages/disadvantages of straight-through versus stop-end termination jacks.

11

Page 143: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 5 QUESTIONSLAB 5 QUESTIONS

List the pin/pair configuration for the TIA/EIA T568B standard.

22

Page 144: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 6 OBJECTIVELAB 6 OBJECTIVETerminating CAT5 with RJ45/T568A Plugs

To properly terminate CAT5 UTP To properly terminate CAT5 UTP cable with two RJ45 modular plugs, cable with two RJ45 modular plugs, using the T568A configurationusing the T568A configuration

Page 145: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Keep the individual pairs grouped together for ease of identification, because some tip wires may not have any visible trace of color and may appear to be solid white.

TIPTIP

Page 146: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-55: Trimming the CAT5 Conductors

Page 147: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-56: Inserting the CAT5 Conductors

Page 148: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-57: Trimming the CAT5 Conductors

Page 149: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-58: Resting the Cable Sheath

Page 150: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-59: Testing CAT5 Plug and Jack Cables for T568A

Page 151: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

In order to practice on the same piece of cable, a crimped RJ45 modular plug or jack must be clipped off, thrown away, and replaced. If you must clip the cable ends to remove RJ45 plugs or jacks for practice purposes, under no circumstances allow the cable to become shorter than four feet (48 inches) long. This cable will be used for later labs. If necessary, practice making terminations using pieces of scrap cable.

TIPTIP

Page 152: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The tension scale/tape measure is exactly one meter long. Measure the cable to the 3-foot marker, place the start of the measure at that point, and measure at least 12 more inches beyond it. If the total length of any cable is less than four feet, you will have to discard it (or add it to the practice cable scrap pile) and try again using a new piece of cable. You must discard the used RJ45 modular jacks or plugs, if they have been crimped.

TIPTIP

Page 153: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 6 QUESTIONSLAB 6 QUESTIONS

When arranging the cable colors for the TIA/EIA T568A configuration, what happens to pairs 1, 3, and 4?

11

Page 154: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 6 QUESTIONSLAB 6 QUESTIONS

When inserting CAT5 conductors into a RJ45 plug, is the tab facing up or down?

22

Page 155: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 6 QUESTIONSLAB 6 QUESTIONS

What differences exist in the cable color arrangements between a T568A plug configuration and a T568A jack configuration?

33

Page 156: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 6 QUESTIONSLAB 6 QUESTIONS

What use can be made of a CAT5 cable terminated with a T568A plug at one end and a T568A jack at the other?

44

Page 157: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 7 OBJECTIVELAB 7 OBJECTIVETerminating CAT5 with RJ45/T568B Plugs

To properly terminate CAT5 UTP To properly terminate CAT5 UTP cable with two RJ45 modular plugs, cable with two RJ45 modular plugs, using the T568B configurationusing the T568B configuration

Page 158: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Keep the individual pairs grouped together for identification. Some tip wires may not have any visible trace of color, and may appear to be solid white.

TIPTIP

Page 159: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-60: Grouping Individual Pairs

Page 160: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-61: Resting the Cable Sheath

Page 161: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

Figure 2-62: Testing CAT5 Plug and Jack Cables for T568B

Page 162: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

In order to practice on the same piece of cable, a crimped RJ45 modular plug or jack must be clipped off, thrown away, and replaced. If you must clip the cable ends to remove RJ45 plugs or jacks for practice purposes, under no circumstances allow the cable to become shorter than four feet (48 inches) long. This cable will be used for later labs. If necessary, practice making terminations using pieces of scrap cable.

TIPTIP

Page 163: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

The tension scale/tape measure is exactly one meter long. Measure the cable to the 3-foot marker, place the start of the measure at that point, and measure at least 12 more inches beyond it. If the total length of any cable is less than four feet, you will have to discard it (or add it to the practice cable scrap pile) and try again using a new piece of cable. You must discard the used RJ45 modular jacks or plugs, if they have been crimped.

TIPTIP

Page 164: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 7 QUESTIONSLAB 7 QUESTIONS

When arranging the cable colors for the TIA/EIA T568B configuration, are there any instances of white wires without any visible alternate color?

11

Page 165: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 7 QUESTIONSLAB 7 QUESTIONS

Why is it necessary to apply pressure to the cable before attaching the RJ45 modular plug with the crimping tool?

22

Page 166: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 7 QUESTIONSLAB 7 QUESTIONS

How can you visually identify which RJ45 wiring scheme (TIA/EIA T568A or T568B) a given cable is using?

33

Page 167: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 7 QUESTIONSLAB 7 QUESTIONS

What is the biggest difference between snap-type and crimp-type RJ45 jack or plug connectors?

44

Page 168: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

LAB 7 QUESTIONSLAB 7 QUESTIONS

Which cable would be less likely to have a problem, a single CAT5 cable that is long enough to reach from a computer to a wall jack, or a composite cable made up of several shorter sections connected through CAT5 plugs or jacks?

55

Page 169: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

State two benefits of standardization.11

Page 170: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

What is the analog voice bandwidth of a telephone line?

22

Page 171: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

Describe two methods of implementing color coding.

33

Page 172: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

What is the maximum pulling force recommended for pulling a 4-wire cable through a conduit?

44

Page 173: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

How far should a telecommunication cable be located away from a fluorescent light

55

Page 174: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

What type of topology is employed for residential telecommunication wiring?

66

Page 175: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

Should cabling be run under carpeting? Explain.

77

Page 176: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

How are type-66 IDC blocks for CAT4 and CAT5 different?

88

Page 177: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

When using a binding post connection, in which direction should the wire be oriented?

99

Page 178: OBJECTIVES 1. State the advantages that come from establishing industrial cabling standards. 2. Identify the standards that specifically apply to cable.

REVIEW QUESTIONSREVIEW QUESTIONS

What action should be taken after all of the communication components have been installed?

1010