  • Weishaupt oil burners Sizes 30 to 70

    1/2003 GB

  • 2

    RegulationDependent on fuel, burner size andrequirements, the regulation of air andfuel is by:

    • Two and three stageOil burners have a nozzle assemblewith two or three nozzles. A change infiring rate is effected by opening andclosing of solenoid valves 2 and 3with the relevant air volume.

    • Sliding two stageFor sliding two stage control, partialand full load are set positions withinthe regulation range. The burner’sfiring rate slides between the two loadpoints, depending on the heatdemand. Thus there are no suddenlarge increases or decreases in theamount of fuel used.

    • ModulationModulating burners operate at anypoint within the regulation range,depending on the heat demand.

    Fuel / air ratioThe controlled mixing of fuel andcombustion air varies depending on thesize and type of burner:Size 30

    Burner types RL and RMS: Pressure side air regulation via acompound regulated control sleeve inthe mixing head.Burner types L and MS: Pressure side air regulation via anadjustable control sleeve in the mixinghead for capacity adjustment.

    Sizes 40 to 70Burner types RL and RMS: Pressure side air regulation via acompound regulated control sleeve inthe mixing head.Burner types L and MS: Diffuser disc matched to burnercapacity

    Increased safety via shut off assemblywith solenoid valveA type tested safety shut off assembly inthe nozzle of R... type burners (exceptRL30) shuts off the oil flow directly at thenozzle during pre-circulation and whenthe burner shuts down.

    Electromagnetic clutchElectromagnetic clutches are availableon request at extra cost for RL oil burnerswith post purge (see SpecialEquipment).

    Oil circulation on heavy oil burnersHeavy oil burners have oil warmed by theoil preheater circulated through the oillines. In this way at the point of ignitionthe oil in the nozzles is at the correcttemperature.

    Precise oil temperature regulationwith Weishaupt oil preheatersHeavy oil burners are fitted with oilpreheaters which by means of anelectronic thermostat keep thetemperature and thus the viscosity of theoil at the required, predetermined level.This results in uniform atomisation andcombustion quality.

    Digital combustion managementThe W-FM 100 and W-FM 200*combustion managers ensure the simpleand safe operation of combustion plant.

    All important functions, such as fuel andair feed or flame monitoring arecontrolled with digital precision. The aimis the optimisation of operationalfunctions, the maximisation of economy,and the minimisation of emissions.Thanks to digital combustionmanagement such an optimisation isavailable today at limited cost. The outlayfor installation and service is substantiallylower than with conventionaltechnologies.

    For example, a separate control panel forthe burner switchgear is no longernecessary. Furthermore, remoteoperation, diagnosis and monitoring ofthe plant can be realised. That makesthings safer and simpler for the operator.

    ApplicationsThe burners can be used with heatexchangers such as hot water boilers,steam boilers, air heaters, and for certainprocess applications. As the burners arecapable of overcoming high combustionchamber resistances, they are usedprimarily on modern high rated boilers.

    FuelsThe burners fire, in accordance with DIN 51 603, fuel oils:Light fuel oil (EL)Viscosity 6 mm2/s at 20°CMedium and heavy fuel oil (S)Viscosity up to 50 mm2/s at 100°C

    Installation sitesIn standard execution (materials,construction, protection), the burners aresuitable for use indoors at temperaturesbetween -15°C and +40°C and with amaximum relative humidity of 80%.

    CertificationThe burners have been independentlytested and comply with the followingEuropean standards and EC directives:

    • EN 267 • Machinery Directive 98/37/EC• Electromagnetic Compatibility

    Directive 89/336/EEC• Low Voltage Directive 73/23/EEC• Pressure Vessel Directive 97/23/EC

    Outstanding serviceWeishaupt maintains an extensive globalsales and service network. Customerservice is available every day around theclock. In-house training by Weishauptensures the high standard of their serviceengineers.

    *Available early 2004

    Description

    Weishaupt industrial burners, sizes 30 to 70, have been especially designed forindustrial capacity ranges. The monobloc burners are noteworthy for their largecapacity and operational ranges and numerous other interesting details:

    • Compliance with the most stringent directives and emission limits• Large capacity and operational ranges• Stable fan reference line - good combustion behaviour• Quiet operation• Burner housing can be hinged open• Easy to install, set and service• Automatic air shut off on burner shut down

  • 3

    Explanation of designation

    Z = Two stageT = Three Stage ZM = Sliding two stage or modulating

    Index for mixing head

    Number for capacity range

    Size

    Fuel: L = Light Oil, M = Medium Oil, S = Heavy Oil

    Regulating burner

    RL 40/1 – B, exec.. ZM

    Variants

    Standard

    Special execution

    Digital combustion management(W-FM 100)

    Electronic compound (RVW)with O2 trim

    Electronic compound (RVW)with speed control

    Electronic compound (RVW)with O2 trim and speed control

    Mechanical compound

    Digital combustion management(W-FM 100)

    with capacity regulation

    Digital combustion management(W-FM 100)

    with capacity regulationand speed control

    Digital combustion management(W-FM 200*)

    with capacity regulationO2 trim and speed control

    Capacity regulation

    Two stage (Z) G

    K

    Three stage (T) G

    ZW

    T

    Modulating (ZM) G

    K

    ZF = Full loadINT = Intermediate

    loadP = Partial loadI = Ignition load

    Sliding two stage(ZM) G

    K

    Z

    On Off

    On Off

    On Off

    On Off

    F

    P

    F

    P

    I

    F

    P

    I

    F

    INT

    P

  • 4

    The advantages of digital combustion management

    Digital combustion managementmeans optimal combustion figures,continually reproducible settingfigures, and ease of use.

    Weishaupt burners are equipped withelectronic compound and digitalcombustion management since moderncombustion technologies demand aprecise, continually reproducible dosingof fuel and combustion air. Only in thisway can optimal combustion figures beensured over extended periods.

    If required, the burners can also beequipped with O2 trim* and speedcontrol.

    Error free operation via a clear textdisplay.Setting and control of the burnerfunctions is achieved using a control anddisplay unit with a clear text display. TheCDU is linked to the combustionmanager via a safety bus system and canbe placed anywhere the user chooseswithin 100 m of the burner.

    Flexible communication possibilitiesThe inbuilt interface enables allnecessary information and functions tobe relayed to a BMS system. If required,a modem enables a telephoneconnection to be installed for remoteoperation (e.g. oil/gas change-over,adjustment of setting values) and remotediagnosis.

    Communication with external systemsvia Bus.If data has to be exchanged betweenburners and other heating systems withPLC devices, Weishaupt E-Gate acts asa gateway and translates the eBusprotocol into the standard Profibus DPprotocol.

    * Available early 2004 in conjunction with the W-FM 200 combustion manager

    Integration with building managementFor the control and management level,Weishaupt offers ProGraf NT - asoftware product that provides a realtime solution to meet all requirements.

    The price advantage of newtechnologyWith improved technology and ease ofuse, combustion plant is becoming evenmore economical.

    • No additional burner controls arerequired, since this effected by thecombustion manager. Contactors andburner motor fuses are the onlyadditional items required.

    • Less installation work means fewererrors: the burners are tested as acomplete unit at the factory.

    • If required, the W-FM 100 can befitted with a capacity regulator andspeed control module. No separateequipment is required. The capacityregulator and speed control moduleare included as standard with the W-FM 200.

    • Commissioning and service worktakes less time. The initial pre-settingof the burner is carried out at thefactory. On site, only the site specificload points have to be determined.

    • To facilitate O2 trim, only an O2 probeand O2 module have to be installedand connected with the W-FM 200via the internal safety bus.

    Control and Display Unit

  • 5

    Mixing head

    Oil feed

    Air feed

    O2 probe

    O2 module

    Control and

    Display Unit

    BMSvisualisationProGraf NT

    Impulse sender

    Steppingmotors

    CAN-Bus

    CAN-Bus

    eBus

    W-FM 200 combustion manager

    Frequencyconvertor

    Example of O2 trim and speed control with W-FM 200

  • 6Weishaupt RL70/2-A oil burner with digital combustion manager

  • 7Weishaupt RMS50/2-A oil burner with digital combustion manager

  • 8

    Proven quality in detail

    Pressure side air regulationvia mixing head with compound regulated controlsleeve

    The forward and reverse movements ofthe regulating sleeve in the mixing headensure that that the air annulus is correctat every load point throughout thecapacity range. This results in optimumvelocities over the whole of the regulationrange. With this system, the mixingpressure is increased at partial load,improving the intermixture of fuel and air.This results in a reduction in excess airand improved combustion efficiency dueto the constant air/fuel ratio.

    Increased safety via shut off assembly with solenoid valve

    The electromagnetically actuated safetyshut off device isolates the oil supply andreturn on burner types RGL40 to 70 andRGMS30 to 70 when the burner shutsdown. Oil shut off directly at the nozzleensures a drip free burner shut down.(Burner type RGL30 uses a systemwithout nozzle shut off).

    Considerable noise reduction due to sound absorbing air inlet

    By fitting sound absorbing materials onthe fan suction side it has been possibleto reduce operational noise considerably.

    Example regulation ranges for different burner types

    Cut-away of the fan housing

    Cut-away of a nozzle shut of assembly

    Burner sizes 60 and 70 with pressure side compound regulation

    Control range up to 1:3

    Control range up to 1:5

    Burner without pressure side compound regulation

  • 9

    Oil burner selectionTypes L, RL, MS and RMS30

    1614

    12

    10

    8

    64

    2

    0

    -20 500 1000 1500 2000

    0 50 100 150

    [kW]

    [kg/h] EL

    2500

    200

    3000

    [ mbar ] Burner type L30Z/2-A und L30T/2-ACombustion head type M30/2 - 190kx65Rating kW 475 – 2440Rating kg/h, light oil EL 40 – 205

    1614

    12

    10

    8

    64

    2

    0

    -20 500 1000 1500 2000

    0 50 100 150

    [kW]

    [kg/h] EL

    2500

    200

    0 50 100 150 200[kg/h] S 250

    [ mbar ] Burner type RL30/2-A RMS30/2-ACombustion head type M30/2 - 190kx65 M30/2 - 190kx65Rating kW 475 – 2440 675 – 2440Rating kg/h, light oil EL 40 – 205 –

    heavy oil S – 60 – 217

    1614

    12

    10

    8

    64

    2

    0

    -20 500 1000 1500 2000[kW] 2500

    0 50 100 150 200[kg/h] S 250

    3000

    [ mbar ] Burner type MS30Z/2-ACombustion head type M30/2 - 190kx65Rating kW 675 – 2440Rating kg/h, heavy oil S 60 – 217

    Burner type Version Type test No. Order No.

    L30Z/2-A – 5G333/99 211 303 02

    L30T/2-A – 5G333/99 211 309 02

    MS30Z/2-A – – 212 303 02

    RL30/2-A ZM 5G332/99 211 305 02

    RMS30/2-A ZM – 212 305 02

    The capacity ranges shown correspond to maximal valuesmeasured on idealised test flame tubes in accordance withEN 267. All ratings given are based on an air temperature of20C and an installation altitude of 500 m.

    The stated oil throughputs refer to a calorific value of 11.91kWh/kg for light oil EL and 11.24 kWh/kg for medium/heavyoil S

    Voltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent 400 V, 3 ~, 50 Hz. Other voltages and frequenciesavailable on request at no extra cost.

    Standard burner motor:Isolation class BF, IP 54 protection.

    Ligh

    t oil

    EL

    Hea

    vy o

    ilS

  • 10

    Oil burner selectionTypes L, RL, MS and RMS40

    16

    14

    12

    10

    8

    6

    4

    2

    0

    -20 500 1000 1500 2000

    0 50 100 150

    [kW]

    [kg/h] EL

    2500 3000 3500 4000

    200 250 300

    [ mbar ] Burner type L40Z/1-B L40Z/1-BCombustion head type M30/2 - 200x50 M30/2 - 175x50Rating kW 655 – 2560 895 – 2980Rating kg/h, light oil EL 55 – 215 75 – 250

    16

    14

    12

    10

    8

    6

    4

    2

    0

    -20 500 1000 1500 2000[kW] 2500 3000 3500 4000

    0 50 100 150 200[kg/h] S 250 300

    [ mbar ] Burner type MS40Z/1-B MS40Z/1-BCombustion head type M30/2 - 200x50 M30/2 - 175x50Rating kW 1010 – 2560 1010 – 2980Rating kg/h, Residual oil M/S 90 – 228 90 – 265

    Burner type Type test No. Order No.

    L40Z/1-B – 5G787/02 211 402 00

    MS40Z/1-B – – 212 402 00

    L40T/1-B – 5G787/02 211 408 00

    RL40/1-B ZM 5G789/02 211 404 00

    RMS40/1-B ZM – 212 404 00

    RL40/2-A ZM 5G789/02 211 405 02

    RMS40/2-A ZM - 212 405 02

    181614121086420-2

    0 500 1000 1500 2000[kW] 2500 3000 3500 4000

    0 50 100 150[kg/h] EL 200 250 300

    [ mbar ] Burner type L40T/1-B L40T/1-BCombustion head type M30/2 - 200x50 M30/2 - 175x50Rating kW 655 – 2560 955 – 3215Rating kg/h, light oil EL 55 – 215 80 – 270

    181614121086420-2

    0 500 1000 1500 2000[kW] 2500 3000 3500 4000

    0

    0

    50 100 150

    50 100 150 200

    [kg/h] EL

    [kg/h] S

    200 250

    250

    300

    300

    [ mbar ] Burner type RL40/2-A RMS40/2-ACombustion head type M40/2 – 217k x 75 M40/2 – 217k x 75Rating kW 655 – 3690 1010 – 3690Rating kg/h, light oil EL 55 – 310 –

    Residual oil M/S – 90 – 328

    181614121086420-2

    0 500 1000 1500 2000[kW] 2500 3000 3500 4000

    0

    0

    50 100 150

    50 100 150 200

    [kg/h] EL

    [kg/h] S

    200 250

    250

    300

    300

    [ mbar ] Burner type RL40/1-B RMS40/1-BCombustion head type M30/2 - 190kx65 M30/2 - 190kx65Rating kW 475 – 2920 785 – 2920Rating kg/h, light oil EL 40 – 245 –

    Residual oil M/S – 70 – 260

    Ligh

    t oil

    EL

    Hea

    vy o

    il S

    Ligh

    t oil

    EL

    Hea

    vy o

    il S

  • 11

    Oil burner selectionTypes L, RL and RMS50

    20181614121086420-2

    0 500 1000 1500 2000[kW]

    22

    2500 3000 3500 4000 4500 5000 5500

    0 50[kg/h] EL 100 150 200 250 300 350 400 450

    6000

    500

    6500

    [ mbar ] Burner type L50T/2-ACombustion head type M50/1 - 185x50Rating kW 1010 – 4765Rating kg/h, light oil EL 85 – 400

    20181614121086420-2

    0 500 1000 1500 2000[kW]

    22

    2500 3000 3500 4000 4500 5000 5500

    0

    0 50

    50[kg/h] EL

    [kg/h] S

    100 150 200 250 300 350 400 450

    100 150 200 250 300 350 400 450 500

    6000

    550

    500 550

    6500

    [ mbar ] Burner type RL50/2-A RMS50/2-ACombustion head type M50/2 - 290x185 M50/2 - 290x185Rating kW 1130 – 6170 1460 – 6170Rating kg/h, light oil EL 95 – 518 –

    Residual oil M/S – 130 – 549

    20181614121086420-2

    0 500 1000 1500 2000[kW]

    22

    2500 3000 3500 4000 4500 5000 5500

    0

    0 50

    50[kg/h] EL

    [kg/h] S

    100 150 200 250 300 350 400 450

    100 150 200 250 300 350 400 450 500

    6000

    550

    500

    6500

    [ mbar ] Burner type RL50/1-B RMS50/1-BCombustion head type M40/2 - 217kx75 M40/2 - 217kx75Rating kW 715 – 3810 1125 – 3810Rating kg/h, light oil EL 60 – 320 –

    Residual oil M/S – 100 – 339

    Ligh

    t oil

    EL

    Hea

    vy o

    il S

    Ligh

    t oil

    EL

    Hea

    vy o

    il S

    Burner type Type test No. Order No.

    L50T/2-A - 5G607/2001 211 509 02

    RL50/1-B ZM 5G790/02 211 504 00

    RMS50/1-B ZM – 212 504 00

    RL50/2-A ZM 5G790/02 211 505 02

    RMS50/2-A ZM – 212 505 02

    The capacity ranges shown correspond to maximal valuesmeasured on idealised test flame tubes in accordance withEN 267. All ratings given are based on an air temperature of20C and an installation altitude of 500 m.

    The stated oil throughputs refer to a calorific value of 11.91kWh/kg for light oil EL and 11.24 kWh/kg for medium/heavyoil S

    Voltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent 400 V, 3 ~, 50 Hz. Other voltages and frequenciesavailable on request at no extra cost.

    Standard burner motor:Isolation class BF, IP 54 protection.

  • 12

    Oil burner selectionTypes RL and RMS60 and 70

    20181614121086420-2

    0 1000 2000[kW]

    22

    3000 4000 5000

    0[kg/h] EL 300

    6000 7000

    100 200 400 500 600

    100 200 400 500 600[kg/h] S 300

    [ mbar ] Burner type RL60/2-A RMS60/2-ACombustion head type M60/2-345-230 M60/2-345-230Rating kW 1310– 7265 1800 – 7265Rating kg/h light oil EL 110– 610 –

    Residual oil S – 160 – 646

    20181614121086420-2

    0 2000[kW]

    22

    4000

    0[kg/h] EL

    6000 8000

    200 400 800600

    200 400 800600[kg/h] S

    10000

    [ mbar ] Burner type RL70/2-A RMS70/2-ACombustion head type M70/1a-425-290 M70/1a-425-290Rating kW 1905 – 10900 2025 – 10900Rating kg/h light oil EL 160 – 915 –

    Residual oil S – 180 – 970

    20181614121086420-2

    0 2000[kW]

    22

    4000

    0[kg/h] EL

    6000 8000

    200 400 800600

    200 400 800600[kg/h] S

    10000

    [ mbar ] Burner type RL70/1-A RMS70/1-ACombustion head type M70/1a-425-290 M70/1a-425-290Rating kW 1905 – 8750 2025 – 8750Rating kg/h light oil EL 160 – 735 –

    Residual oil S – 180 – 778

    Ligh

    t oil

    EL

    Hea

    vy o

    il S

    Ligh

    t oil

    EL

    Hea

    vy o

    il S

    Ligh

    t oil

    EL

    Hea

    vy o

    il S

    Burner type Version Type test No. Order No.

    RL60/2-A ZM 5G587/2000 211 605 02

    RMS60/2-A ZM – 212 605 02

    RL70/1-A ZM 5G588/2000 211 704 02

    RMS70/1-A ZM – 212 704 02

    RL70/2-A ZM 5G589/2000 211 705 02

    RMS70/2-A ZM – 212 705 02

    The capacity ranges shown correspond to maximal valuesmeasured on idealised test flame tubes in accordance withEN 267. All ratings given are based on an air temperature of20C and an installation altitude of 500 m.

    The stated oil throughputs refer to a calorific value of 11.91kWh/kg for light oil EL and 11.24 kWh/kg for medium/heavyoil S

    Voltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent 400 V, 3 ~, 50 Hz. Other voltages and frequenciesavailable on request at no extra cost.

    Standard burner motor:Isolation class BF, IP 54 protection.

  • 13

    Scope of delivery

    Description L30 MS30 RL30 RMS30 L40 MS40 RL40 RMS40 RL60 RMS60L50 RL50 RMS50 RL70 RMS70

    Burner housing, hinged flange, housing cover, Weishaupt burner motor, air regulation housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes, nozzle assembly with oil nozzle(s), combustion manager with control unit, flame sensor, flange gasket, limit switch on hinged flange, fixing screws ● ● ● ● ● ● ● ● ● ●

    W-FM 100 combustion manager ● ● ● ● ● ● ● ● ● ●

    Air pressure switch ●

    Oil pressure switch in return ● ● ● ● ● ● ● ●

    Servomotor for direct control of the air damper ● ● ● ● ● ● ● ● ● ●

    Adjustable regulating sleeve in the mixing head ● ●

    Compound regulated sleeve in the mixing head ● ● ● ● ● ●

    Integral oil pump ● ● ● ● ● ● ● ● ● ● ➀

    Integral oil preheater ● ● ● ● ● ➀

    Oil hoses ● ● ● ● ● ● ● ● ● ●

    2 oil solenoid valves, 1 safety valve, two stage nozzle assembly without shut off ● ➁ ● ➁

    3 oil solenoid valves, 1 safety valve, three stage nozzle assembly without shut off ● ➂ ● ➂

    2 oil solenoid valves in flow and return, nozzle assembly without shut off ●

    1 solenoid valve in flow and return, nozzle assembly with shut off (solenoid on RL & RMS, hydraulically controlled ball valve on MS) ● ● ● ● ● ●

    1 solenoid valve in flow and return, bypass solenoid valve, nozzle assembly with solenoid shut off ●

    ➀ RMS type burners require separate pump and preheater stations (see pages 20-23)➁ Types L30Z and L40Z only➂ Types L30T, L40T and L50T only

    Burner execution complies with TRD 606, 24 h/72 h see technical brochure, Print No. 863.

  • Special equipmentSizes 30 and 40

    14

    Description L30Z L30T MS30Z RL30 RMS30L40Z L40T MS40Z RL40 RMS40

    Vertically firing burner version standard standard standard standard standard

    Air intake flange for connection of an air duct Size 30 280 003 47 280 003 47 280 003 47 280 003 47 280 003 47

    Size 40 280 001 68 280 001 68 280 001 68 280 001 68 280 001 68

    Ölzähler VZO20 angebaut Size 30 280 002 91 280 002 91 – – –Size 40 280 002 92 280 002 92 – – –

    Pump J7 in lieu of J6 280 007 60 280 007 60 – – –TA2 in lieu of J6 Size 40 – 280 002 74 – – –E6 in lieu of J6 (for ring main pressure >2.0 bar) 280 007 61 280 007 61 – – –E7 in lieu of J7 (for ring main pressure >2.0 bar) 280 007 62 280 007 62 – – –

    Oil hoses DN13 / 1300 mm in lieu of 1000 mm 280 002 50 280 002 50 – 280 002 35 –Heated stainless steel – – 280 001 69 – 280 001 69

    Pressure gauge with ball valve 0 – 25 bar 280 001 90 280 001 90 – – –

    0 – 40 bar – – 280 004 08 280 000 02 280 000 02

    Vacuum gaugewith ball valve -1 – 9 bar 280 004 07 280 004 07 280 004 07 280 000 03 280 000 03

    Electromagnetic clutch Size 30 – – – 280 003 56 280 003 57Size 40 – – – 280 001 70 280 001 70

    Combustion head extension 150 mm Size 30/2 280 003 86 280 003 88 280 003 90 280 003 09 280 003 58Size 40/1 280 003 66 280 003 68 280 001 99 280 002 54 280 002 56Size 40/2 – – – 280 001 72 280 001 73

    300 mm Size 30/2 280 003 87 280 003 89 280 003 91 280 003 10 280 003 59Size 40/1 280 003 67 280 003 69 280 002 00 280 002 55 280 002 57Size 40/2 – – – 280 001 50 280 001 51

    Capacity regulator for W-FM 100 Size 30 280 007 57 280 007 57 280 007 57 280 007 57 280 007 57

    Oil preheaterWEV2 in lieu of EV2D Size 40 – – – – 280 001 71WEV3 in lieu of EV2D Size 40 – – – – 280 002 06

    MV9C oil preheater (medium)in addition to standard Size 30 – – 280 003 55 – 280 003 60integral electric oil preheater Size 40 – – 280 002 33 – 280 002 34

    Fittings medium preheater station in conjunction with electric preheaterscrewed for warm water up to 110°C – – 120 001 70 – 120 001 70flanged for warm water up to 110°C – – 120 001 78 – 120 001 78flanged for hot water from 110°C up to 180°C – – 120 001 79 – 120 001 79

    screwed for low pressure steam up to 0.5 bar – – 280 001 18 – 280 001 18screwed for high pressure steam up to 1.5 bar – – 280 001 18 – 280 001 18flanged for high pressure steam from 1.5 bar up to 15 bar – – 280 001 19 – 280 001 19

    flanged for high pressure steam from 12 bar up to 20 bar – – 280 001 21 – 280 001 21flanged for high pressure steam from 20 bar up to 25 bar 280 001 22 – 280 001 22

    flanged for thermal fluid up to 250°C – – 120 001 75 – 120 001 75flanged for thermal fluid up to 300°C – – 120 001 77 – 120 001 77

  • 15

    Special equipmentSize 50

    Description L50T RL50 RMS50

    Vertically firing burner version standard standard standard

    Air intake flange for connection of an air duct 280 000 92 280 000 92 280 000 92

    Oil hoses Heated stainless steel – – 280 001 05

    Pressure gauge with ball valve 0 – 40 bar 280 000 02 280 000 02 280 000 02

    Vacuum gauge with ball valve -1 – 9 bar 280 000 03 280 000 03 280 000 03

    Combustion head extension 150 mm Size 50/1 – 280 003 70 280 003 71Size 50/2 280 002 75 280 002 76 280 002 77

    300 mm Size 50/1 – 280 003 72 280 003 73Size 50/2 280 001 06 280 000 90 280 000 91

    Capacity regulator for W-FM 100 280 007 57 280 007 57 280 007 57

    Oil preheater WEV3 in lieu of WEV2 Size 50/1 – – 280 002 68

    MV9C oil preheater (medium) in addition to standard Size 30 – – 280 002 98integral electric oil preheater Size 40 – – 280 001 17

    Fittings medium preheater station in conjunction with electric preheater screwed for warm water up to 110°C – – 120 001 70flanged for warm water up to 110°C – – 120 001 78 flanged for hot water from 110°C up to 180°C – – 120 001 79

    screwed for low pressure steam up to 0.5 bar – – 280 001 18screwed for high pressure steam up to 1.5 bar – – 280 001 18flanged for high pressure steam from 1.5 bar up to 15 bar – – 280 001 19

    flanged for high pressure steam from 12 bar up to 20 bar – – 280 001 21flanged for high pressure steam from 20 bar up to 25 bar 280 001 22

    flanged for thermal fluid up to 250°C – – 120 001 75flanged for thermal fluid up to 300°C – – 120 001 77

  • 16

    Special equipmentSizes 60 and 70

    Description RL60 RMS60 RL70 RMS70

    Vertically firing burner version standard standard standard standard

    Air intake flange for connection of an air duct 280 000 38 280 000 38 280 000 13 280 000 13

    Oil hoses Heated stainless steel – 280 000 60 – 280 000 18

    Pressure gauge with ball valve 0 – 40 bar 280 000 02 – 280 000 02 –

    Vacuum gauge with ball valve -1 – 9 bar 280 000 03 – 280 000 03 –

    Electromagnetic clutch 280 000 40 – 280 000 14 –

    Combustion head extension 150 mm 280 002 78 280 002 79 280 002 80 280 002 81300 mm 280 000 36 280 000 37 280 000 11 280 000 31

    Capacity regulator for W-FM 100 280 007 57 280 007 57 280 007 57 280 007 57

  • 17

    Pump and preheater stationsDescription

    Scope of delivery - pump stationsPump unit (screw spindle pump withmotor), pressure gauge, vacuum gauge,pressure regulating valve, ball valves,suction flange, pressure flange includingcounter flanges, screws and washers,suction-side filter. All parts fullyassembled on an oil drip tray.

    The pump station is built as one of twodifferent versions - either as a singlestation unit with one pump, or as a twinstation unit with two pumps, one pumpbeing in reserve. Should the one pumpfail, it is possible to quickly switch over tothe other.

    Only tried and tested makes of pump areused. The pumps are carefully matchedto the capacity of the burner.

    Scope of delivery - preheater stationsPreheater stations are supplied fullyassembled on an oil drip tray. Thepreheater ensures the constantregulation of the preheat temperatureand thus the viscosity of the fuel oil.

    There are two basic versions of thepreheater station available:

    1. Electric preheating2. Medium preheating

    WEV.. and MV.. type preheaters areused.

    MV.. medium oil preheaterMedium preheaters are high capacity,forced circulation heat exchangers. Highcapacity is achieved with a compact,space saving construction. Hot water,steam or thermo fluid can be used asheating media. The oil preheatersguarantee substantially stable oiltemperatures and thus good combustionfigures. The oil temperature achieveddepends on the heating medium used.

    When selecting and sizing, please referto the oil temperature diagrams inchapter 5.3 of the technical brochure“Weishaupt electric and medium oilpreheaters”, print No. 18. Weishauptmedium oil preheaters can be useduniversally. It is possible to change themedium at any time. The preheaters areused either alone or in conjunction withan electric oil preheater.

    If operating steam at more than 7.5 bar orhot water between 180C and 200C iscontinuously available, then an electricpreheater is not required. This is alsopossible if plant with the above minimumpressures or temperatures can beoperated with distillate oil EL or gas.

    If the medium temperature is notsufficient to adequately preheat the fueloil, then the electric oil preheater inputsthe additional heat required. The electricoil preheater heats the oil for the start upof the plant. If the required mediumtemperature is available then the stationswitches over to the medium oilpreheater thus saving on expensiveelectrical energy.

    Suitable connection fittings for mediumoil preheaters can be selected,depending on the medium available. Ifmedium oil preheaters are providedwithout electric oil preheaters, amechanical temperature regulator mustbe used with the medium connectionfittings. The given prices do not includemedium connection fittings.

    Air / gas separators or oil circulationtanksPatented air / gas separators orcirculation tanks are always required andmust be offered.

    By using an air / gas separator orcirculation tank, it is possible for thepreheated oil from the burner return tobe mixed in with that of the burner supply.This results in an energy saving, as it isonly necessary to partially heat the fueloil.

    Where one burner is operating ondistillate oil , it is possible to use a twopipe system so long as the suctionvacuum does not exceed 0.5 mbar. Ifseveral burners with air / gas separatorsor oil circulation tanks are being suppliedby a ring main, then it is a good idea toprovide a manually actuated double shutoff device with limit switch immediatelyafter the air / gas separator or circulationtank. The air / gas separator or circulationtank must be selected according to thering main pump rating and the burnersize. When choosing ring main pumpunits, please ensure that the capacity isaround 1.5 - 2 times the nozzle rating.

    General instructionsWhen starting a boiler from a coldcondition with residual oil, an electric oilpreheater capacity must be provided forat least 30% of the boiler rating. On hotwater boilers up to 130C operatingtemperature, the electric oil preheatersmust be able to produce the full boileroutput without medium preheaters. Useof a medium preheater is not suitable formedium temperatures below 100C. Thenumber of media oil preheaters to beselected depends on the oil throughputand can be taken from the capacitycharts (see the technical brochure“Weishaupt electric and media oilpreheaters”).

    Planning and installation instructionsAir / Gas separator, circulation tank,pump station and oil preheater stationmust be installed close to the burner.

    On RGMS type burners, sizes 60 and70, the time required for oil circulationduring start up depends on the length ofthe pipework between the burner and theair gas separator or circulation tank.

    The shorter the pipeline, the shorter theperiod between heat being called for andoil release / burner start after a controlledshutdown.

  • 18

    Pump and preheater stationsTypes and fittings

    Pump stations - 50 Hz frequency Burner Technical data - pump Version with 1 pump Version with 2 pumpscapacity Supply at Speed Motor at Pump type Order No. Pump type Order No.kg/h 150 mm2/s l/h rpm 450 mm2/s kW230 – 350 860 2900 1.5 SPF 10-38 170 002 81 SPZ 10-38 170 002 85350 – 650 1700 2900 2.2 SPF 20-38 170 002 82 SPZ 20-38 170 002 86650 – 940 2310 2900 4.0 SPF 20-46 170 002 83 SPZ 20-46 170 002 87940 – 1480 3630 2900 5.5 SPF 40-38 170 004 87 SPZ 40-38 170 004 88

    Pump stations - 60 Hz frequency 270 – 415 1020 3400 2.2 SPF 10-38 170 003 09 SPZ 10-38 170 003 11415 – 780 2050 3400 2.6 SPF 20-38 170 003 10 SPZ 20-38 170 003 12780 – 965 2720 3400 4.0 SPF 20-46 170 003 13 SPZ 20-46 170 003 14

    Preheater stations Type Number Medium Electric preheater (EV) Order No.

    preheater kg/h kg/h at ∆t = 75°CWEV3.1/01 1 – 375 170 003 55WEV3.1/01 2 – 750 170 003 52WEV3/01 1 – 500 170 002 23WEV3/01 2 – 1000 170 002 24MV9C with temperature controller 1 500 – 170 001 03MV9C without temperature controller 1 500 – 170 001 04MV10A with temperature controller 1 1000 – 170 000 94MV10A without temperature controller 1 1000 – 170 002 30

    Connection fittings for preheater stations with 1 oil preheater Description Order No.Fittings for MV9C medium preheater station (with electric preheater stations) – screwed for warm water up to 110°C 120 001 70– screwed for high pressure steam up to 1.5 bar 170 003 59– screwed for high pressure steam from 1.5 bar up to 15 bar 170 003 60– flanged for warm water up to 110°C 120 001 78– flanged for hot water from 110°C up to 180°C 120 001 79– flanged for high pressure steam up to 1.5 bar 170 003 61– flanged for high pressure steam from 6 bar up to 20 bar 170 003 62– flanged for high pressure steam from 20 bar up to 25 bar 170 003 67– flanged for thermal fluid up to 250°C 120 001 75– flanged for thermal fluid up to 300°C 120 001 77Fittings for MV9C medium preheater station (with thermostat valve, without electric preheater) – flanged for hot water from 180°C up to 200°C 120 001 81– flanged for high pressure steam from 7.5 bar up to 13 bar 170 003 63– flanged for high pressure steam from 13 bar up to 20 bar 170 003 64– flanged for high pressure steam from 20 bar up to 25 bar 170 003 65– flanged for thermal fluid from 200°C up to 250°C 120 001 84– flanged for thermal fluid from 250°C up to 300°C 120 001 85Fittings for MV10A medium preheater station (with electric preheater stations) – screwed for warm water up to 110°C 170 001 35– screwed for high pressure steam up to 1.5 bar 170 001 47– screwed for high pressure steam from 1.5 bar up to 15 bar 170 001 53– geflanscht für Warmwasser up to 110°C 170 001 38– flanged for hot water from 110°C up to 180°C 170 001 44– flanged for high pressure steam up to 1.5 bar 170 001 50– flanged for high pressure steam from 6 bar up to 20 bar 170 001 56– flanged for high pressure steam from 20 bar up to 25 bar 170 002 00– flanged for thermal fluid up to 250°C 170 001 59– flanged for thermal fluid up to 300°C 170 001 62Fittings for MV10A medium preheater station (with thermostat valve, without electric preheater)– flanged for hot water from 180°C up to 200°C 170 001 68– flanged for high pressure steam from 7.5 bar up to 13 bar 170 001 71– flanged for high pressure steam from 13 bar up to 20 bar 170 001 74– flanged for high pressure steam from 20 bar up to 25 bar 170 001 85– flanged for thermal fluid from 200°C up to 250°C 170 001 77– flanged for thermal fluid from 250°C up to 300°C 170 001 80

  • 19

    Brenner-Anschluß

    Pump station (with 2 pumps) Medium preheater station Electric preheater station

    Examples of medium connection fittings

    Hot water

    HW outlet

    HW inlet

    Hot water and thermo fluid

    HW outlet Thermo fluid outlet

    HW inletThermo fluid inlet

    Low / high pressure steam up to 1.5 bar

    Condensate outlet

    Steam inlet

    High pressure steam up to 15 bar

    Condensate outlet

    HPS inlet

    DescriptionThe connection fittings are chosendepending on the medium type andthe number of preheaters.

    Diagram - separate pump and preheater stations

    Preheater (not included in delivery)

    Included with pump station

    Ball valve

    Included with preheater

    Regulator

    Accessories

    Condensate sight glass

    Steam trap

    Filter

    Pressure gaugeLines shown in black to be provided on site

    Mediumpreheater

    Electricpreheater

    Mechanically connected shut offassembly with limit switch and

    safety valveMechanicallyconnectedshut offassemblywith limitswitch andsafety valve

    Air/gas separator

  • 20

    Technical dataSize 30

    Technical data L30Z/2-A L30T/2-A MS30Z/2-ABurner motor 400 V, 3 ~, 50 Hz Type D112/110-2 D112/110-2 D112/110-2Nominal capacity kW 4.5 4.5 4.5Nominal load at 400 V A 9.5 9.5 9.5Motor prefuse (�∆ start) A 20 20 20Speed (50 Hz) rpm 2900 2900 2900Fan wheel colour / ø blue / 268 x 100 blue / 268 x 100 blue / 268 x 100Combustion manager Type W-FM100 W-FM100 W-FM100Ignition unit V W-ZG02/2 W-ZG02/2 W-ZG02/2Servomotor Air Type SQM 45 SQM 45 SQM 45

    Fuel Type – – –Mixing head Type – – –

    Integral pump Type J6/J7 ➀ J6/J7 ➀ E7Oil preheater Type – – EV2D

    Oil throughput kg/h – – 270Heating capacity kW – – 13.2

    Oil solenoid valve 230V 1/8” 9 W Type 7121ZBG1KRTO (2 off) 7121ZBG1KRTO (3 off) –230V 1/8” 19 W Type 121 K 2423 121 K 2423 121 K 2423230V 1/8” 19 W Type – – 122 K 9321115V 3/8” (flow) 20 W Type – – 321 H 2322115V 3/8” (return) 20 W Type – – 121 G 2320

    Oil pressure 1 – 10 bar (light oil return - 5 bar) Type – – –switch 1 – 10 bar (heavy oil return - 7 bar) Type – – DSA 46 F001Oil hoses DN / Length 13/1000 (2 off) 13/1000 (2 off) 20/1000(High pressure metal hoses for MS, RMS and RGMS) – – 20/1300Burner weight kg (approx.) 90 92 135

    Technical data RL30/2-A RMS30/2-ABurner motor 400 V, 3 ~, 50 Hz Type D112/110-2 D112/110-2Nominal capacity kW 4.5 4.5Nominal load at 400 V A 9.5 9.5Motor prefuse (�∆ start) A 20 20Speed (50 Hz) rpm 2900 2900Fan wheel colour / ø blue / 268 x 100 blue / 268 x 100Combustion manager Type W-FM100 W-FM100Ignition unit V W-ZG02/2 W-ZG02/2Servomotor Air Type SQM 45 SQM 45

    Fuel Type SQM 45 SQM 45Mixing head Type SQM 45 SQM 45

    Integral pump Type TA3 TA3Oil preheater Type – EV2D

    Oil throughput kg/h – 270Heating capacity kW – 13.2

    Oil solenoid valve 115V 1/8” (flow and return) 19 W Type 121K2423 (2 off) –115V 1/4” (flow and return) 20 W Type 121K6220 (2 off) –115V 3/8” (flow) 20 W Type – 321 H 2322115V 3/8” (return) 20 W Type – 121 G 2320

    Oil pressure 1 – 10 bar (light oil return EL - 5 bar) Type DSA 46 F001 –switch 1 – 10 bar (heavy oil return S - 7 bar) Type – DSA 46 F001Oil hoses DN / Length 20/1000 (2 off) 20/1000(High pressure metal hoses for MS, RMS and RGMS) – 20/1300Burner weight kg (approx.) 100 140

  • 21

    Technical dataSize 40

    Technical data L40Z/1-B L40T/1-B MS40Z/1-BBurner motor 400 V, 3 ~, 50 Hz Type D112/140-2a D112/140-2a D112/140-2aNominal capacity kW 5.5 5.5 5.5Nominal load at 400 V A 11 11 11Motor prefuse (�∆ start) A 25 25 25Speed (50 Hz) rpm 2900 2900 2900Fan wheel colour / ø blue / 295 x 100 blue / 295 x 100 blue / 295 x 100Combustion manager ➀ Type W-FM100 W-FM100 W-FM100Ignition unit V W-ZG02/2 W-ZG02/2 W-ZG02/2Servomotor Air Type SQM 45 SQM 45 SQM 45

    Fuel Type – – –Mixing head Type – – –

    Integral pump Type J6/J7 ➀ J6/J7/TA2 ➀➁ E7Oil preheater Type – – EV2D

    Oil throughput kg/h – – 270Heating capacity kW – – 13.2

    Oil solenoid valve 230V 1/8” 19 W Type 121 K 2423 (2 off) 121 K 2423 (3 off) 121 K 2423230V 1/4” ( safety valve) 20 W Type 121 K 6220 121 K 6220 –230V 1/8” 19 W Type – – 122K9321115V 1/8” (flow) 20 W Type – – 321 H 2322115V 1/8” (return) 20 W Type – – 121 G 2320

    Oil pressure 1 – 10 bar (light oil return - 5 bar) Type – – –switch 1 – 10 bar (heavy oil return - 7 bar) Type – – DSA 46 F001Oil hoses DN / Length 13/1000 (2 off) 13/1000 (2 off) 20/1000( High pressure metal hoses for MS, RMS and RGMS) – – 20/1300Burner weight kg (approx.) 135 135 159

    Technical data RL40/1-B RMS40/1-BRL40/2-A ➄ RMS40/2-A ➄

    Burner motor 400 V, 3 ~, 50 Hz Type D112/140-2a ➄ D112/140-2a ➄Nominal capacity kW 5.5 5.5Nominal load at 400 V A 11 11Motor prefuse (�∆ start) A 25 25Speed (50 Hz) rpm 2900 2900Fan wheel colour / ø blue / 295 x 100 blue / 295 x 100Combustion manager Type W-FM100 W-FM100Ignition unit V W-ZG02/2 W-ZG02/2Servomotor Air Type SQM 45 SQM 45

    Fuel Type SQM 45 SQM 45Mixing head Type SQM 45 SQM 45

    Integral pump Type TA3 TA3Oil preheater Type – EV2D ➂➃

    Oil throughput kg/h – 270Heating capacity kW – 13.2

    Oil solenoid valve 115V 1/8” (flow) 20 W Type 321 H 2322 321 H 2322115V 1/8” (return) 20 W Type 121 G 2320 121 G 2320

    Oil pressure 1 – 10 bar (light oil return - 5 bar) Type DSA 46 F001 –switch 1 – 10 bar (heavy oil return - 7 bar) Type – DSA 46 F001Oil hoses DN / Length 20/1000 (2 off) 20/1000( High pressure metal hoses for MS, RMS and RGMS) – 20/1300Burner weight kg (approx.) 142 166

    ➀ Burners > 200 kg/h: oil pump J7 in lieu of J6 (see Special Equipment for extra cost)

    ➁ Burners > 250 kg/h: oil pump TA2 in lieu of J6 (see Special Equipment for extra cost)

    ➂ Burners > 270 kg/h: oil preheater WEV2.2 in lieu of EV2D (see Special Equipment for extra cost)

    ➃ Burners > 300 kg/h: oil preheater WEV3 in lieu of WEV2.2 (see Special Equipment for extra cost)

    ➄ Burner types .../2-A with 112/140-2 burner motors, Nominal capacity7 kW, nominal load 13.4 A, motor prefuse 25 A.

    Note: If the flow pressure exceeds 2.0 bar then pump types E6 andE7 must be used in lieu of J6 and J7 respectively

  • Technical dataSize 50

    22

    Technical data L50T/2-A RL50/1-B RL50/2-ABurner motor 400 V, 3 ~, 50 Hz Type D132/170-2 D132/120-2 D132/170-2Nominal capacity kW 13.5 9 13.5Nominal load at 400 V A 25 18 25Motor prefuse (�∆ start) A 50 35 50Speed (50 Hz) rpm 2900 2850 2900Fan wheel colour / ø blue / 345 x 100 blue / 345 x 100 blue / 345 x 100Combustion manager Type W-FM100 W-FM100 W-FM100Ignition unit V W-ZG02/2 W-ZG02/2 W-ZG02/2Servomotor Air Type SQM 45 SQM 45 SQM 45

    Fuel Type – SQM 45 SQM 45Mixing head Type – SQM 45 SQM 45

    Integral pump Type TA2C TA4C T2COil preheater Type – – –

    Heating capacity kg/h – – –Heating capacity kW – – –

    Oil solenoid valve 230V 1/8” 19 W Type 121 K 2423 (3 off) – –230V 1/4” ( safety valve) 20 W Type 121 K 6220 – –115V 3/8” (flow) 20 W Type – 321 H 2322 321 H 2322115V 3/8” ( return) 20 W Type – 121 G 2320 121 G 2320

    Oil pressure 1 – 10 bar (light oil return - 5 bar) Type – DSA 46 F001 DSA 46 F001switch 1 – 10 bar (heavy oil return - 7 bar) Type – – –Oil hoses DN / Length 20/1300 (2 off) 25/1300 (2 off) 25/1300 (2 off)( High pressure metal hoses for MS, RMS and RGMS) – – –Burner weight kg (approx.) 200 208 210

    Technical data RMS50/1-B RMS50/2-A Burner motor 400 V, 3 ~, 50 Hz Type D132/120-2 D132/170-2Nominal capacity kW 9 13.5Nominal load at 400 V A 18 25Motor prefuse (�∆ start) A 35 50Speed (50 Hz) rpm 2850 2900Fan wheel colour / ø blue / 345 x 100 blue / 345 x 100Combustion manager Type W-FM100 W-FM100Ignition unit V W-ZG02/2 W-ZG02/2Servomotor Air Type SQM 45 SQM 45

    Fuel Type SQM 45 SQM 45Mixing head Type SQM 45 SQM 45

    Integral pump Type TA4C T2COil preheater Type WEV2.2/01 ➀ WEV3/01

    Oil throughput kg/h 300 500Heating capacity kW 13.8 22.2

    Oil solenoid valve 115V 3/8” (flow) 20 W Type 321 H 2322 321 H 2322115V 3/8” ( return) 20 W Type 121 G 2320 121 G 2320

    Oil pressure 1 – 10 bar (light oil return - 5 bar) Type – –switch 1 – 10 bar (heavy oil return - 7 bar) Type DSA 46 F001 DSA 46 F001Oil hoses DN / Length 25/1150 25/1150( High pressure metal hoses for MS, RMS and RGMS) 25/1500 25/1500Burner weight kg (approx.) 248 250

    ➀ Burners > 300 kg/h: oil preheater WEV3 in lieu of WEV2.2 (see Special Equipment for extra cost)

  • 23

    Technical dataSizes 60 and 70

    Technical data RL60/2-A RMS60/2-ABurner motor 400 V, 3 ~, 50 Hz Type D132/170-2 D132/170-2Nominal capacity kW 13.5 13.5 Nominal load at 400 V A 25 25 Motor prefuse (�∆ start) A 50 50Speed (50 Hz) rpm 2900 2900Fan wheel colour / ø blue / 515 x 120 blue / 515 x 120Combustion manager Type W-FM100 W-FM100Ignition unit V W-ZG02/2 W-ZG02/2Servomotor Air Type SQM 45 SQM 45

    Fuel Type SQM 45 SQM 45Mixing head Type SQM 45 SQM 45

    Integral pump Type T2C –Oil solenoid valve 115V 3/8” (flow) 20 W Type 321 H 2322 321 H 2322

    115V 3/8” ( return) 20 W Type 121 G 2320 121 G 2320230V 3/8” (bypass) 19 W Type – 322 H 7306

    Oil pressure 3 – 25 bar (flow - bar) Type – DSA 58 F 001switch 1 – 10 bar ( light oil return - 5 bar) Type DSA 46 F 001 –

    1 – 10 bar (heavy oil return - bar) Type – DSA 46 F 001Oil hoses DN / Length 25/1300 (2 off) 16/1150( High pressure metal hoses for MS, RMS and RGMS) – 16/1500Burner weight kg (approx.) 250 210* * Weight excluding pump station and preheater station

    Technical data RL70/1-A RL70/2-A RMS70/1-A RMS70/2-ABurner motor 400 V, 3 ~, 50 Hz Type D160/150-2 D160/215-2 D160/150-2 D160/215-2Nominal capacity kW 14 21 14 21 Nominal load at 400 V A 27 39 27 39 Motor prefuse (�∆ start) A 50 63 50 63 Speed (50 Hz) rpm 2900 2900 2900 2900Fan wheel colour / ø blue / 530 x 120 blue / 590 x 160 blue / 530 x 120 blue / 590 x 160Combustion manager Type W-FM100 W-FM100 W-FM100 W-FM100 Ignition unit V W-ZG02/2 W-ZG02/2 W-ZG02/2 W-ZG02/2 Servomotor Air Type SQM 45 SQM 45 SQM 45 SQM 45

    Fuel Type SQM 45 SQM 45 SQM 45 SQM 45Mixing head Type SQM 45 SQM 45 SQM 45 SQM 45

    Integral pump Type T2C (< 600 kg/h) T2C (< 600 kg/h) – –Type T3C (> 600 kg/h) T3C (> 600 kg/h) – –

    Oil solenoid valve 115V 1/2” (flow) 20 W Type 321 H 2522 321 H 2522 321 H 2522 321 H 2522115V 1/2” ( return) 20 W Type 121 G 2520 121 G 2520 121 G 2520 121 G 2520230V 3/8” (bypass) 19 W Type – – 322 H 7306 322 H 7306

    Oil pressure 3 – 25 bar (flow - 18 bar) Type – – DSA 58 F 001 DSA 58 F 001switch 1 – 10 bar ( light oil return - 5 bar) Type DSA 46 F 001 DSA 46 F 001 – –

    1 – 10 bar (heavy oil return - 7 bar) Type – – DSA 46 F 001 DSA 46 F 001Oil hoses DN / Length 25/1300 (2 off) 25/1300 (2 off) 20/1150 20/1150( High pressure metal hoses for MS, RMS and RGMS) – – 20/1500 20/1500Burner weight kg (approx.) 350 350 310* 310* * Weight excluding pump station and preheater station

  • d5

    d4

    d6

    l3

    l6

    l2

    d3

    r1

    r2

    l1

    l5

    b6

    b15 b2

    b3

    b4

    b8

    b7

    d2l8

    l7

    l l9 10

    h6 d1

    h3h1

    h5

    h2

    b

    24

    Dimensions Sizes 30 and 40

    Size Dimensions in mm l1 l2 l3 l5 l6 l7 l8 l9 l10 b1 ➀ b2 b3 b4 b5

    L to RMS30/2-A 892 244 303 8 354 133 57 130 198 787 697 371 208 418

    L to 130 198RMS40/1-A 937 269 303 8 414 130 57 147 ➀ 254 ➁ 849 759 401 242 462

    RL / 130 198RMS40/2-A 937 269 361 8 414 130 52 147 ➀ 254 ➀ 849 759 401 242 462

    117 ➁ 314 ➁

    b6 b7 b8 h1 h2 h3 h5 h6 d1 d2 d3 d4 d5 d6 r1 r2L to RMS30/2-A 195 430 � 330 572 207 407 264 � 330 280 250 218 M12 360 285 950 890

    L to 195 430 264RMS40/1-B 337 ➀ 630 ➀ � 370 607 211 422 191 ➀ � 370 280 250 218 M12 360 285 1100 970

    RL / 195 430 264RMS40/2-A 337 ➀ 630 ➀ � 370 607 211 422 191 ➀ � 370 320 290 218 M12 400 325 1100 970

    394 ➁ 744 ➁ 205 ➁

    ➀ Dimension valid for medium and heavy oil burners in conjunction withWEV2.2 oil preheater (see Special Equipment for additional cost)

    ➁ Dimension valid for medium and heavy oil burners in conjunction withWEV3 oil preheater (see Special Equipment for additional cost)

    Size 30 and 40 burners on twin flue boilersIt should be taken into account at the planning stage that the burnersmust be at least 900 mm apart from each other. This ensures a minimumgap of 40 mm between the burners when the largest pump and motortypes are fitted.

    All measurements are approximate. Weishaupt reserve the right tomake alterations in light of future developments.

  • 25

    Dimensions Size 50

    Size Dimensions in mm l1 l2 l3 l5 l6 l7 l8 l9 l10 b1➀ b2 b3 b4 b5 b6 b7 b8

    L50T/2-A 990 315 357 8 422 153 67 – – 961 858 463 277 550 – – � 430147 254 337 630R..50/1-B 985 315 361 8 422 148 52 132➀ 314➀ 946 835 440 277 550 394➀ 744➀ � 430

    R..50/2-A 990 315 386 8 422 153 67 137 314 962 858 463 277 550 394 744 � 430

    h1 h2 h3 h5 h6 d1 d2 d3 d4 d5 d6 r1 r2L50T/2-A 728 263 513 - � 430 380 280 258 M16 480 390 1100 1025

    191R..50/1-B 728 263 513 205➀ � 430 320 290 258 M12 400 330 1100 1000

    R..50/2-A 728 263 513 205 � 430 380 350 258 M16 480 390 1100 1025

    ➀ Dimension valid for medium and heavy oil burners in conjunction withWEV3 oil preheater (see Special Equipment for additional cost)

    Size 50 burners on twin flue boilersIt should be taken into account at the planning stage that the burnersmust be at least 1020 mm apart from each other. This ensures a minimumgap of 40 mm between the burners when the largest pump and motortypes are fitted.

    All measurements are approximate. Weishaupt reserve the right tomake alterations in light of future developments.

    l8

    l7

    l l9 10

    d5

    d4

    d6

    l3

    l6

    l2

    d3

    r1

    r2

    l1

    l5

    h6 d1

    h3

    b6

    b1b5 b2

    b3

    b4

    b8

    b7

    d2h1

    h5

    h2

  • d5d6

    h4 1

    h3h1

    h2

    l7

    l8

    l

    ld

    r

    3

    2

    1

    r2

    l1

    b1

    b2

    b3

    b4

    6

    b5 d2b8

    l5l3

    l12

    d

    d4

    30° 30°

    26

    Dimensions Sizes 60 and 70

    Size- Dimensions in mm l1 l2 l3 l5 l6 l7 l8 b1 b2 b3 b4 b5 b8

    RL60/2-ARMS60/2-A 1189 405 407 8 520 180 62 1070 966 487 280 670 520

    RL70RMS70 1368 483 417 8 614 222 64 1275 1166 602 340 760 590

    h1 h2 h3 h4 d1 d2 d3 d4 d5 d6 r1➀ r2RL60/2-ARMS60/2-A 930 360 670 520 429 400 258 M16 470 435 1260 1140

    RL70RMS70 1075 420 775 600 470 480 310 M16 550 500 1500 1310

    ➀ With electromagnetic clutch Dimensions b1, b2 and b3 are reduced by 45 mm for burner size70/1.

    Size 60 and 70 burners on twin flue boilersIt should be taken into account at the planning stage that the burnersmust be at least 1130 mm (RL60) or 1325 mm (RL70) apart from eachother. This ensures a minimum gap of 40 mm between the burners whenthe largest pump and motor types are fitted.

    All measurements are approximate. Weishaupt reserve the right tomake alterations in light of future developments.

  • 27

    Burner fuel systems

    13a

    13a1310 16b

    Types L30Z/L40Z

    P

    10 16a17

    13b 13c14a12a

    1211

    115V115V

    Types MS30Z/MS40Z

    P M

    10 1612

    1514a12a

    11

    115V

    115V

    Types RL60/RL70

    P M

    ϑ P

    ϑ

    17 1811 1210 16

    1514a12a

    115V

    14

    12b

    115V

    18

    Types RMS60/RMS70With separate pump and preheater stations

    P M

    10 16b12

    15 12a14a12a

    12

    115V 115V

    115V 115V

    Types RL30

    P M

    ϑ

    10 1612

    1514a12a

    11

    115V

    115V

    17 18a

    Types RMS30 to RMS50 Integral pump and preheater

    13a

    13a1310 16b

    13a

    Types L30T / L40T / L50T

    P M

    10 1612

    1514a12a

    11

    115V

    115V

    Types RL40/RL50

    Legend

    10 Oil pump11 Oil filter12 Normally closed oil solenoid valve (115 V,

    electrically connected in series with 15a)12a Normally closed oil solenoid valve (115 V,

    electrically connected in series with 15,fitted against the direction of flow)

    12b Normally open bypass oil solenoid valve13 Normally closed oil solenoid valve13a Normally closed oil solenoid valve for

    stages 1, 2 and 313b Normally open oil solenoid valve

    (stage 1)13c Normally closed oil solenoid valve

    (stage 2)14 Oil pressure switch in flow14a Oil pressure switch in return15 Oil regulator16 Nozzle assembly with shut off device

    (solenoid valve)16a Nozzle assembly with shut off device16a Nozzle assembly without shut off device17 Oil preheater18 PT100 temperature sensor (to monitor

    minimum oil temperature)18a Thermostat

  • Max Weishaupt GmbH, D - 88475 SchwendiTel: +49(0)7353 830, Fax +49(0)7353 83358 Print No. 83201102, August 2003Printed in Germany. All rights reserved.

    Weishaupt (U.K.) Ltd.Neachells Lane, Willenhall, WV13 3RGTel: (01902) 609841, Fax: (01902) 633343

    63 Carlton Place, Glasgow, G5 9TWTel: (0141) 420 2030, Fax: (0141) 420 2088

    Product and customer service -the complete Weishaupt range

    Regular maintenance reduces heatingcosts and environmental pollution. Only aproperly adjusted burner can saveenergy and be environmentally friendly.Behind each Weishaupt burner standsthe whole Weishaupt customer serviceorganisation. The outstanding effortsmade in maintenance and service justifythe enormous trust placed inWeishaupt’s burners, for at Weishauptproduct and customer service belongtogether.

    Weishaupt customer service is there foryou all year round. Whenever you needhelp, be it the supply of spare parts,technical advice or a site visit. We arethere when you need us.


Recommended