Group
5Capacity
1200-29500 kW
Oil, Gas and Dual Fuel BurnersBurner series 400...2500 ME
Table of contents
General 1Howtochooseaburner 2
Technicaldataanddimensions 3-4
PIdiagrams 5-6
Scopeofdelivery 7
Gaselbow 8Gasvalveselectiontable 8
Combustionairfan 9Airdistributionbox 9
BoosterunitPKYK1...5forlightfueloil 10
BoosterunitPKYR1...8forheavyfueloil 11-12
Burnersforpreheatedcombustionair 12
Controlpanelsandsupplycabinets 13
WiseDrive 14Burnerpreheater 15Masonryfigure 15Flamedimensions 15
Oilsupplydiagramforheavyfueloil 16Gaspressurecontrolassembly 16
1
Oilonoil,gas,anddualfuelburnersarefullyautomatic,safe,andreliable.Thefundamentalsofthedesignandmanufacturingoftheburnersareeconomy,safety,serviceandenvironmentalfriendliness.OurgasburnerscomplywiththestandardEN676,oilburnerswiththestandardsEN230andEN267,anddualfuelburnerswithallofthesestandards.
Construction
Ahousingofweldedsteelsheetswithasurfacefinishwithdurable,high-glosspaint.Aremovablecoverlocatedontopoftheburnermakesiteasytocarryoutmaintenanceonthenozzleandignitionelectrodesasthisdoesnotrequireremovaloftheburner.Thecombustionheadanddiffuserdisc,whicharemadefromastainlesssteelalloy,withstandatemperatureofapprox.1,200°C.Theflowofairinthecombustionheadisautomaticallycontrolled(optimisationofthepressurelossatthecombustionhead)toachieveoptimumcombustionparametersthroughoutthecapacityrange.Theburnercontainsasightglassforflameobservation.Anairdamperassemblyonthesuctionsideofthefanautomaticallycontrols,togetherwiththeservo-motor,thefuelandairflowsaccordingtotherequiredoutput.
Suitable applications
Theburnersaresuitableforwarmandhotwaterboilers,steamboilers,hotairgeneratorsandvarioustypesofprocessheatingequipment.Theycanbemountedinhorizontal,verticalandupward-facing,orverticalanddownward-facingorientation.
Thestructure,materialsandenclosureclassoftheburnersrequireindoorsoperation.
Fuels
Differentfuelscanbeuseddependingontheburnermodel:KPmodels:
-lightfueloil,viscosity4-12mm2/s,+20°CRPmodels:
-heavyfueloil,viscositymax.250mm2/s,+50°C-heavyfueloil,viscositymax.450mm2/s,+50°C
heatingcartridgeforpumpandnozzle-heavyfueloil,viscositymax.650mm2/s,+50°C
heatingcartridgesasabove+traceheatingfortheoilpiping
GPmodels:-naturalgas,gasesof2ndfamily,groupsHandE
(equipmentcategoryI2R)GKPandGRPdualfuelburners:
-fuelpropertiesasabove,naturalgas/lightfueloil-fuelpropertiesasabove,naturalgas/heavyfueloil
Burnersusingotherfuelsareavailableonrequest.
Capacity regulation methods
Allburnersaremodulating.Theyareequippedwithanairdamperservomotorwithatransitiontimeof60s/90°.Theservomotorisconnectedtotheoilregulatorandcompoundregulatorviaanaxle.Theburneroperatesontheentirecapacityrangeaccordingtotheload.Theburn-ersarecontrolledaccordingtothefluegasanalysis.
Booster unit PKYK for light fuel oil
ThemodelsKPandGKPareequippedwithaseparateboosterunit,whichincludesanoilfilterandaboosterpumpwithcompletepiping.
Booster unit PKYR for heavy fuel oil
ThemodelsRPandGRPareequippedwithaseparatepreheaterandboosterunit,whichcomprisesanoilfilter,boosterpumpandanelectricmasspreheater.
Thepreheaterismadefromacastaluminiumalloy,andincludesembeddedoilpipingandelectricresistancecoils.Thecapacityofonepreheateris6kW.Thepreheateriscontrolledbysolid-staterelaysandbyanelectronicregulator,whichkeepstheoiltemperaturestable.Astableoiltemperaturehelpstoensurethattheoilmixesadequatelywiththecombustionair,helpingtoobtainoptimalcom-bustionparameters.Dependingonthemodel,thePKYRmayhavethreeormorepreheatingunits.
Intheheavyoilburners,theoilheatedduringthepre-purgephaseflowstothenozzlethroughthepreheatertoensurethattheoiltemperatureishighenoughinthenozzleduringtheignitionphase.
Gas equipment
Thegas-relatedcomponentsofthegasanddualfuelburnerscomplywiththestandardEN676:twoshut-offvalves,pres-sureswitches(min./max.)andanautomaticvalveleaktester.Otherpiping-relatedequipmentisavailableonrequest.
Oil piping
Theoilpipingisinstalledmainlyintheburner,andincludesthreesolenoidvalves.Theoilregulatorislocatedontheoillinereturningfromthenozzle.ThepipingbetweentheburnerandthePKYK/PKYRistobebuiltonsite.
Flame monitoring
Allmodelsareequippedwithautomaticflamemonitoring.InKPandRPmodels,flamemonitoringiscarriedoutbyaphotocell;inGP,GKP,andGRPmodels,itiscarriedoutbyanUVcell.
Control devices
Theburnercontrolautomaticsareassembledinasepa-ratecontrolcabinet,whichcontainsacontrolunit,signallamps,thecapacitycontrollerandoperatingswitches.Thecontrolunitautomaticallycarriesoutallthefunctionphasesoftheburner.
Intheeventofaburnerfailure,thesystemautomaticallystopstheburner.Themodulatingburnersalsoincorporateapre-installedcapacitycontroller.Ifrequired,theburnercanalsobesuppliedwithelectronicfuel/airratiocontrolatanaddedcost.
Accessories
Eachofthefuelcontrolvalvesandtheairdampermaybeequippedwithaservomotor(electronicfuel/airratiocontrol).Anairdistributionboxshouldbeinstalledundertheburner,incaseofairductcannotbeinstalledvertically(lengthofstraightverticalpartshouldbeatleast1.5m)undertheburner.
Wereservetherighttomaketechnicalalterations.
Oil, gas and dual fuel burnersBurner series 400...2500 ME
2
A. Procedure1 Establishrelevantboilerandapplicationinformation
•boilercapacityandefficiency,orrequiredburnercapacity
•backpressureofthefurnace•fuel(s)tobeused•fuelinletpressuretotheburner•capacityregulationmethodoftheburner
2 Calculatetheburnercapacity.Burnercapacity=boilercapacity/efficiency.Example:boilercapacity=10,000kW,efficiency=90%→Burnercapacity=10,000kW/0.9=11,110kW.
3 Gasburners:Calculatetherequiredgasflow[m3n/h].Therequiredgasflow[m3n/h]=(burnercapacity[kW]x3.6)/thecalorificvalueofthegas[MJ/m3n].Example:therequiredburnercapacity=11,110kW→there-quiredgasflow=(11,110kWx3.6)/35.8MJ/m3n=1,117m3n/h,where35.8MJ/m3nisthecalorificvalueofnaturalgas.Oilburners:Calculatetherequiredoilflow[kg/h].Therequiredoilflow[kg/h]=(burnercapacity[kW]x3.6)/thecalorificvalueofoil[MJ/kg].Example:therequiredburnercapacity=11,110kW→therequiredoilflow=(11,110kWx3.6)/40.5MJ/kg=988kg/h,where40.5MJ/kgisthecalorificvalueofheavyfueloil.
4 Seethebrochureforaburnerwithasufficientrangeofcapacity.Example:Aburnerof11,110kWofcapacity,firingnaturalgasandheavyfueloilisneeded.Theappropri-ateburnerforthesespecificationsisGRP-1000ME.
5 Calculatetherequiredcombustionairflowandpres-sure.Example:therequiredburnercapacity=11,110kW,thepressurelossoftheboilerandchimneyatthisburnercapacityis15mbar.
Example:Thecombustionairflowrequiredwhenusingnaturalgaswithafluegasoxygenvalueof3%iscalcu-lated.Tocombust1m3nofnaturalgastoproducea3%oxygencontentinthefluegas,approximately11.3m3nofairisrequired(seediagram2,page9).Therequiredcombustionairflow=1,117m3n/hx11.3m3n/m3n=12,620m3n/h.Thecombustionairflowisalsotobecalculatedwhenusingheavyfueloil.Tocombust1kgofheavyfueloilproducingafluegasoxygencontentof3%,approximately12.4m3nofairisrequired(seediagram1,page9).Therequiredcombustionairflow=988kg/hx12.4m3n/kg=12,250m3n/h.Therequiredfanoutputiscalculatedbymultiplyingtherequiredcombustionairflowwiththesafetyfactor1.05.Thelargerfigureisselectedforthecombustionairflow,i.e.12,620m3n/h,andthefanoutputrequiredforthisflowisapproximately1.05x12,620m3n/h=13,250m3n/h.Therequiredfanpressureiscalculatedusingthemax.airflow.Therequiredflowpressurep[mbar]=(thepressurelossgeneratedbytheboilerandthechimney+thepressurelossoftheairducts+max.pressurelossintheburner,35mbar)xsafetyfactor1.05.Example:Thepressurelossgeneratedbytheboilerandthechimney=15mbar,thepressurelossoftheairducts=5mbar,max.pressurelossoftheburner=35mbar.Therequiredfanpressurep=(15mbar+5mbar+35mbar)x1.05=58mbar.Afanapplicableinthiscasehastoproduceaflowofapproximately13,250m3n/hatapressureof58mbar.
N.B:Theairducttobeconnectedwiththeburnershouldrundirectlyfrombelowtheburner,anditshouldbe
straightforadistanceofnolessthan1.5metresbeforetheburner.Iftheductcannotbeinstalledinthisway,anairdistributionboxshouldbeused.Forinformationonairdistributionboxes,seepage9.
6 Gasburners:Fromtheselectiontableforgasvalves,selectasufficientvalvesizeaccordingtotheburnercapacity.Notethatthevaluesintheselectiontableapplywhenthefurnacebackpressureis0mbar.Thereforeyoumustsubtractthefurnacebackpressurefromtheactualgasinletpressure,andselectthevalveaccordingtothevaluethusobtained.Theratingsshowninthetableapplytonaturalgas.
Example:Thegasinletpressureoftheburner=200mbar,theboilerbackpressure=18mbarandtherequiredburnercapacity=11,110kW.Theeffectivepressureistherefore200mbar-18mbar=182mbar.FortheburnerGRP-1000ME,forexample,avalvegeneratingacapacityofnolessthan11,110kWwithagasinletpressureof182mbarshouldbechosen.ThevalveDN80isselectedforthisburner.
7 Oilburners:Selectanappropriateboosterunitaccord-ingtotheburnercapacity.ThelightfueloilburnersusethemodelPKYKandtheheavyfueloilburnersPKYR.Theboosterunitforlightfueloilisselectedusingthediagram3.Theboosterunitforheavyfueloilisselectedusingthediagram4.Forburnercapacityof988kg/h,forexample,therequiredtemperaturedifferenceintheboosterunitis45°C.ThediagramshowsthattheappropriateboosterunitisPKYR3.
8 Checkthattheexternaldimensionsoftheburner,particularlythelengthofthecombustionhead,aresuitablefortheapplication.Thecombustionheadlengthshouldbesuchthattheheadisflushwiththefurnacewallorapprox.10-20mminsidethefurnace(see‘Masonryfigure’).
9 Checkthedimensionsoftheflameintheflamedimensionsdiagram.Notethattheflamemustnottouchthefurnacewalls.
10 Donotforgettheaccessories:gaspressureregulator,oilpumpingandpreheatingunit,boilerthermostats/pressostats.
Oursalesdepartmentwillbehappytohelpyouwithanyquestionsrelatedtoburnerselectionandoperation.
B. Equations and rules of thumb1 Burnercapacity=boilercapacity/0.9(whenboiler
efficiencyis90%)2 Steamboilers:1ton/hsteam≈700kWboilercapacity3 Lightfueloil:1kg/h≈11.86kWburnercapacitywith
calorificvalue42.7MJ/kg4 Heavyfueloil:1kg/h≈11.22kWburnercapacity
withcalorificvalue40.5MJ/kg5 Naturalgas:1m3n/h≈10kWburnercapacitywith
calorificvalue35.84MJ/m3n6 Oilpumping,filtering,andpreheatingunit(OilonHot-
Box)isrequiredwhenfiringheavyfueloil.Whentheburnercapacityismorethan2MW,atransferpumpunit(OilonSPY)isalwaysneeded,evenwhenfiringlightfueloil.Therequiredminimumpumpoutput[kg/h]canbecalculatedasfollows:
Requiredminimumoutput[kg/h]=(oilflowtobeburned[kg/h]+150kg/h)x1.2.Theclauseinbracketsreferstothepreheatedoilflowtoeachburner.
How to choose a burner
3
Oil, gas and dual fuel burners
KP/RP/GP/GKP/GRP-1600...2000 ME
KP/RP/GP/GKP/GRP-400...600 ME KP/RP/GP/GKP/GRP-800...1200 ME
������
����
���
�������
�
������
���
������
��
���
���
��� ��
���
���
��
���
��
���
��
���� ��
��
����
���
�����
�
�
���
���
������
�����
���
���
������
���
�����
���
���
��� ��
������
��
���
��
���
���
������
����
���
�������
�
������
���
������
��
���
���
��� ��
���
���
��
���
��
���
��
���
���� ��
��
����
����
����
�
���
������
������
���
���
���
��� ��
��
������
���
���
����
��
��������
���
��
����
����
��
�
����
������
������
���
���
��� ��
���
��
����
��
���
�������
����
KP/RP/GP/GKP/GRP-2500 ME
BURNER L2 ØD1 ØD4
400 ME 325 370 430
600 ME 335 395 455
800 ME 360 422 482
1000 ME 390 496 556
1200 ME 400 520 580
BURNER L2 ØD1 ØD4
1600 ME 450 594 654
2000 ME 450 650 710
2500 ME 570 740 800
InstallationoftheburnertoaboilerVIEWEDFROMDIRECTIONAAirductinstallationflange
VIEWEDFROMDIRECTIONAAirductinstallationflange
Installationoftheburnertoaboiler
*Onlyingasanddualfuelburners
InstallationoftheburnertoaboilerVIEWEDFROMDIRECTIONAAirductinstallationflange
VIEWEDFROMDIRECTIONAAirductinstallationflange
Installationoftheburnertoaboiler
*Onlyingasanddualfuelburners
4
Lightfueloil: 1kg/h≅11,86kW 1kW≅860kcal/hHeavyfueloil: 1kg/h≅11,22kW 1kW≅860kcal/hNaturalgas: caloricvalueHμ=9,5kWh/m3n(34,3MJ/m3n) densityp=0,723kg/m3n
Regulatingrange:Lightfueloil: 1:3(100-33%)Heavyfueloil: 1:2,5(100-40%)Gas: 1:5(100-20%,1:4/400/600)
BURNER KP-400 ME KP-600 ME KP-800 ME KP-1000 ME KP-1200 ME KP-1600 ME KP-2000 ME KP-2500 ME
Capacity MW kg/h Connections
1,2 - 5,0100 - 4202 x Ø 22
1,7 - 6,8143 - 5732 x Ø 22
2,4 - 9,5200 - 8002 x Ø 22
3,0 - 12,0 250 - 10002 x Ø 22
3,5 - 14,0300 - 12002 x Ø 22
4,2 - 16,5350 - 14002 x Ø 22
5,6 - 22,5470 - 19002 x Ø 22
7,4-29,5621 – 2490
Ø 22/28
Pilot burner- fuel
- connection
-
-
-
-
light fuel oil (LPG)
(Ø 22)
light fuel oil (LPG) (Ø 22)
light fuel oil (LPG) (Ø 22)
light fuel oil (LPG) (Ø 22)
light fuel oil (LPG) (Ø 22)
light fuel oil (LPG) (Ø 22)
BURNER RP-400 ME RP-600 ME RP-800 ME RP-1000 ME RP-1200 ME RP-1600 ME RP-2000 ME RP-2500 ME
Capacity MW kg/h Connections
1,2 - 4,7106 - 4172 x Ø 22
1,7 - 6,8150 - 6002 x Ø 22
2,2 - 9,0 200 - 800 2 x Ø 22
2,8 - 11,0 250 - 1000 2 x Ø 22
3,4 - 13,0 300 - 1200
2 x Ø 22
3,9 - 15,5 350 - 1400
2 x Ø 22
5,3 - 21,0470 - 19002 x Ø 22
8,0 – 28,0710 – 2530
Ø 22/28
Pilot burner - fuel
- connection
-
-
liquid gas
Ø 18
LPG(light fuel
oil)Ø 22 (Ø 8)
LPG(light fuel
oil) Ø 22 (Ø 8)
LPG(light fuel
oil)Ø 22 (Ø 8)
LPG(light fuel
oil)Ø 22 (Ø 8)
LPG(light fuel
oil)Ø 22 (Ø 8)
LPG(light fuel
oil)Ø 22 (Ø 8)
BURNER GP-400 ME GP-600 ME GP-800 ME GP-1000 ME GP-1200 ME GP-1600 ME GP-2000 ME GP-2500 ME
Capacity MW - connection
1,2 - 5,0DN50 - 100
1,7 - 6,8DN50 - 100
1,9 - 9,5DN65 - 125
2,0 - 12,0DN65 - 125
2,8 - 14,0DN80 - 125
3,3 - 16,5 DN100 - 125
4,5 - 22,5DN100 - 125
5,9 – 29,5DN125
Pilot burner- connection Ø 18 Ø 18 Ø 22
Ø 22
Ø 22 Ø 22 Ø 22 Ø 22
BURNER GKP-400 ME GKP-600 ME GKP-800 ME GKP-1000 ME GKP-1200 ME GKP-1600 ME GKP-2000 ME GKP-2500 ME
Capacity - gas MW - oil MW kg/h Connections- gas - oil
1,2 - 5,01,2 - 5,0100 - 420
DN50 - 1002 x Ø 22
1,7 - 6,81,7 - 6,8143 - 573
DN50 -1002 x Ø 22
1,9 - 9,5 2,4 - 9,5200 - 800
DN65 - 1252 x Ø 22
2,0 - 12,03,0 - 12,0
250 - 1000
DN65 - 1252 x Ø 22
2,8 - 14,03,5 - 14,0
300 - 1200
DN80 - 1252 x Ø 22
3,3 - 16,5 4,2 - 16,5
350 - 1400
DN100 - 125 2 x Ø 22
4,5 - 22,5 5,6 - 22,5 470 - 1900
DN100 - 125 2 x Ø 22
5,9 – 29,57,4 – 29,5
621 – 2490
DN125Ø 22/28
Pilot burner- fuel
- connection
natural gas
Ø 18
natural gas
Ø 18
natural gas/ light fuel oil
(LPG) (Ø 22)
natural gas/ light fuel oil
(LPG) (Ø 22)
natural gas/light fuel oil
(LPG) (Ø 22)
natural gas/light fuel oil
(LPG) (Ø 22)
natural gas/light fuel oil
(LPG)(Ø 22)
natural gas/light fuel oil
(LPG)(Ø 22)
BURNER GRP-400 ME GRP-600 ME GRP-800 ME GRP-1000 ME GRP-1200 ME GRP-1600 ME GRP-2000 ME GRP-2500 ME
Capacity - gas MW - oil MW kg/h Connections- gas - oil
1,2 - 5,01,2 - 4,7106 - 417
DN50 - 1002 x Ø 22
1,7 - 6,81,7 - 6,8150 - 600
DN50 -1002 x Ø 22
1,9 - 9,5 2,2 - 9,0 200 - 800
DN65 - 125 2 x Ø 22
2,0 - 12,0 2,8 - 11,0
250 - 1000
DN65 - 125 2 x Ø 22
2,8 - 14,0 3,4 - 13,0
300 - 1200
DN80 - 125 2 x Ø 22
3,3 - 16,5 3,9 - 15,5
350 - 1400
DN100 - 125 2 x Ø 22
4,5 - 22,5 5,3 - 21,0
470 - 1900
DN100 - 1252 x Ø 22
5,9 – 29,5 8,0 – 28,0
710 – 2530
DN125Ø 22/28
Pilot burner- fuel
- connection
natural/liquid gas
Ø 18
natural/liquid gas
Ø 18
light fuel oil (LPG)
Ø 22 (Ø 8)
light fuel oil(LPG)
Ø 22 (Ø 8)
light fuel oil(LPG)
Ø 22 (Ø 8)
light fuel oil(LPG)
Ø 22 (Ø 8)
light fuel oil(LPG)
Ø 22 (Ø 8)
light fuel oil(LPG)
Ø 22 (Ø 8)
Technical data
KP/RP/GP/GKP/GRP-400...-2500 ME
5
������
��
�
���
� � �
�
� ����
�
�
��
�
����
�
�
��
��
��
������
��
�
���
�
��
�
� ����
�
�
�
����
�
�
��
��
���
�
�
��
�� ��
�
��
�
�
�
� ������
��
�
��
��
�
�
�
�
�
1.Ballvalve,blow-off2.Pressureswitch,min.3.Doublesolenoidvalve,NC4.Valveleaktester5.Gasbutterflyvalve6.Pressureswitch,max.7.Solenoidvalve,ignitiongas,NC8.Controllerunit9.Airdamperassembly
10.Airpressureswitch11.SeparatecombustionairfanCGas,inletEAirtotheburner
Gas burners GP-400...2500 ME
1.Temperatureregulator2.Pressuregauge3.Solenoidvalve,NC4.Solenoidvalve,NC5.Solenoidvalve,NO6.Pressuregauge7.Oilregulator8.Non-returnvalve9.Oilpressureswitch,max.
10.Solenoidvalve,NC11.Solenoidvalve,NC12.Airdamperassembly13.Airpressureswitch14.SeparatecombustionairfanAOil,inletBOil,returnCLPG,inletEAirtotheburner
Heavy oil burners RP-400...2500 ME
1.Pressuregauge 2.Solenoidvalve,NC 3.Solenoidvalve,NC 4.Solenoidvalve,NC 5.Solenoidvalve,NC 6.Pressuregauge 7.Oilregulator 8.Non-returnvalve 9.Oilpresssureswitch, max.10.Solenoidvalve,NC*11.Solenoidvalve,NC*12.Airdamperassembly
13.Airpressureswitch14.Separatecombustionairfan AOil,inlet BOil,return CLPG,inlet* EAirtotheburner *)Alternativeforlightfueloilignition (optional).
Light oil burners KP-400...2500 ME
PI diagrams
6
�� ��
��
����
��
������
��
�
�
��
��
��
�
�
��
��
���
�
�
�
�
��
��
�
�
��
�
��
�� ��
��
��
��
��
������
��
�
�
��
��
��
�
�
��
����
��
�
��
��
�
�
��
�
���
�
����
�
�
��
Dual fuel burners, heavy fuel oil/gas GRP-400...2500 ME
1.Temperatureregulator 2.Pressuregauge 3.Solenoidvalve,NC 4.Solenoidvalve,NC 5.Solenoidvalve,NO 6.Pressuregauge 7.Oilregulator 8.Non-returnvalve 9.Oilpressureswitch,max.10.Solenoidvalve,NC11.Solenoidvalve,NC12.Ballvalve,blow-off13.Pressureswitch,min.14.Doublesolenoidvalve,NC15.Valveleaktester16.Gasbutterflyvalve
1.Pressuregauge 2.Solenoidvalve,NC 3.Solenoidvalve,NC 4.Solenoidvalve,NC 5.Solenoidvalve,NC 6.Pressuregauge 7.Oilregulator 8.Non-returnvalve 9.Oilpressureswitch,max.10.Ballvalve,blow-off11.Pressureswitch,min.12.Doublesolenoidvalve,NC13.Valveleaktester14.Gasbutterflyvalve15.Pressureswitch,max.16.Solenoidvalve,NC,ignitiongas17.Airdamperassembly18.Airpressureswitch19.Separatecombustionairfan AOil,inlet BOil,return CGas,inlet EAirtotheburner
Dual fuel burners, light fuel oil/gas GKP-400...2500 ME
PI diagrams
17.Pressureswitch,max.18.Solenoidvalve,NC,ignitiongas19.Airdamperassembly20.Airpressureswitch21.Separatecombustionairfan AOil,inlet BOil,return CGas,inlet DLPG,inlet(ignitionwhenusingoil) EAirtotheburner
7
KP/RP/GP/GKP/GRP-400...-2500 MEScope of deliveryBurners include following equipment:
KP-... ME RP-... ME GP-... ME GKP-... ME GRP-... ME
Burner flange gasket • • • • •
Oil nozzle • • • •
Heating cartridge for oil nozzle o o
Solenoid valves for oil • • • •
Heating cartridge for solenoid valves • •
Non-return valve • • • •
2 pressure gauges for oil • • • •
Thermometer • •
Pressure switch for return oil • • • •
Electric tracing cables for burner oil pipes o o o o
Controller unit for regulating the air/oil ratio, incl.:- oil regulator- servomotor
• •
Controller unit for regulating the air/gas ratio, incl.:- gas butterfly valve- servomotor
•
Controller unit for regulating the air/oil/gas ratio, incl.:- oil regulator- gas butterfly valve - servomotor
• •
WiseDrive (electronic ratio control)for regulating the air/oil ratio, incl.: - oil regulator- servomotor for oil regulator- servomotor for air dampers- servomotor for combustion head regulation
o o
WiseDrive (electronic ratio control)for regulating the air/gas ratio, incl.: - gas butterfly valve- servomotor for gas butterfly valve- servomotor for air dampers - servomotor for combustion head regulation
o
WiseDrive (electronic ratio control)for regulating the air/oil/gas ratio, incl.:- oil regulator- gas butterfly valve- servomotors for oil regulator and gas butterfly valve- servomotor for air dampers- servomotor for combustion head regulation
o o
Potentiometer fitted in servomotor o o o o o
Gas nozzle • • •
Pressure gauge for measuring the pressure in gas nozzle o o o
Gas pressure switch, max. • • •
Air pressure switch • • • • •
Ignition transformer • • • • •
Ignition cables and electrodes • • • • •
Flame sensor • • • • •
Air dampers • • • • •
Pressure gauge for fan pressure o o o o o
Elbow 90° • • •
Double solenoid valve for gas incl.:- gas pressure switch, min.- 2 gas valves- automatic valve leak tester- ball valve, blow-off (loose)
• • •
Solenoid valve for ignition gas • • •
Solenoid valves for ignition gas (LPG) o • •
Solenoid valves for light fuel oil ignition • •
Manual • • • • •
•standarddelivery ooption
8
Gas elbow
Gas valve selection table
NOTE! Themax.capacitiesshowninthetableareachievedwhentheboilerbackpressureis0. Naturalgas1m3n/h≅10kW*) orcorrespondingtype**) Gasinletpressure(Pmax)atburner -max.500mbarwhenusingDMV-(D)valve
�
�
GAS ELBOW DIMENSIONS WITH DIFFERENT VALVES
DN50 DN65 DN80 DN100 DN125
H L L L L L
GP/GKP/GRP-400/600 ME 535 635 690 710 750 -
GP/GKP/GRP-800 ME 663 - 805 730 772 825
GP/GKP/GRP-1000…1200 ME 620 - 805 730 772 825
GP/GKP/GRP-1600...2000 ME 700 - - - 772 825
GP/GKP/GRP-2500 ME 738 - - - - 895
Otherdimensionsavailableonspecialrequest
BURNER GAS VALVE
SIZE TYPE **)
DN
BURNER MAX. CAPACITY kW*)
GAS INLET PRESSURE mbar
100 150 200 250
GP/GKP/GRP-400 ME 50 DMV-D5050/11 3200 3920 4700 4700
65 DMV-5065/11 4700 4700 4700 4700
GP/GKP/GRP-600 ME 65 DMV-5065/11 4850 5940 6800 6800
80 DMV-5080/11 6750 6800 6800 6800
GP/GKP/GRP-800 ME 80 DMV-5080/11 7500 9200 9500 9500
100 DMV-5100/11 9500 9500 9500 9500
GP/GKP/GRP-1000 ME 100 DMV-5100/11 7500 10000 12000 12000
125 DMV-5125/11 12000 12000 12000 12000
GP/GKP/GRP-1200 ME 100 DMV-5100/11 8000 10500 14000 14000
125 DMV-5125/11 12000 14000 14000 14000
GP/GKP/GRP-1600 ME 100 DMV-5100/11 8000 10500 14000 16500
125 DMV-5125/11 12000 15500 16500 16500
GP/GKP/GRP-2000 ME 125 DMV-5125/11 12000 16000 20000 22500
GP/GKP/GRP-400 ME 2” DMV-D 525/12 4700 4700 4700 4700
65 DMV-D5065/12 4700 4700 4700 4700
GP/GKP/GRP-600 ME 2” DMV-D 525/12 4850 5940 6800 6800
65 DMV-D5065/12 6750 6800 6800 6800
80 DMV-D5080/12 6750 6800 6800 6800
GP/GKP/GRP-800 ME 65 DMV-D5065/12 5500 7900 9500 9500
80 DMV-D5080/12 8500 9500 9500 9500
GP/GKP/GRP-1000 ME 65 DMV-D5065/12 6000 8000 10000 12000
80 DMV-D5080/12 8500 10000 12000 12000
100 DMV-D5100/12 12000 12000 12000 12000
GP/GKP/GRP-1200 ME 80 DMV-D5080/12 9000 10000 14000 14000
100 DMV-D5100/12 13000 14000 14000 14000
125 DMV-D5125/12 14000 14000 14000 14000
GP/GKP/GRP-1600 ME 100 DMV-D5100/12 13000 16000 16500 16500
125 DMV-D5125/12 16500 16500 16500 16500
GP/GKP/GRP-2000 ME 100 DMV-D5100/12 13400 17000 19000 22500125 DMV-D5125/12 16000 22500 22500 22500
GP/GKP/GRP-2500 ME 125 DMV-D5125/12 16000 22500 29500 29500
9
������������������������
�� �������������������
���������
������������������ ����������� ������������
��
���
���
���
���
��
� � � �
�������������� ���������
�������
���
���
������������������������
���������
������������������ ����������� ����� ����
� �
�� �
�� �
� �
�� �
� � � �
�������������� ����������
�������
����
� �
��
��
�
�
�
�
� �
�
�
�
��
Combustion air fan
TheburnerseriesMErequiresaseparatecombustionairfan.
Scopeofthefandelivery:•electricmotor•platform•flexibleconnector,pressurisedside•2connectorflanges•vibrationdampers•surfacefinish•suctionnoisesilencer(optional)•silencerfortheentirefan(optional)•PT-100temperaturesensorsforthemotorphases(optional)
Required combustion air flowDiagrams1and2indicatetherequiredcombustionairflowforeachkilogramofoilorcubicmeterofnaturalgas.Fordetailedcalculationinstructions,seepage2.
The dimensions H1 and L4 are recommended minimum values.
1.Burner2.Fan3.Airduct4.Bellows(notnecessary
atbothends)5.Airdistributionbox6.Maintenancehatch7.Vibrationdamper
A. To be dimensioned according to the air duct of the burner. B. To be dimensioned as ordered.
Air distribution box for the ME series burnersTheairducttobeconnectedwiththeburnershouldrundirectlyfrombelowtheburner,anditshouldbestraightforadistanceofnolessthan1.5metresbeforetheburner.Iftheductcannotbeinstalledasinstructedabove,anairdistributionboxshouldbeused.
BURNER H1 L4
400/600 280 800
800 280 900
1000 440 900
1200 440 900
1600 550 1130
2000 550 1130
2500 650 1300
10
���
����
���
���
�������
���
�
�
� �
��
�
� �
�
�
�
�
�
�
�
�
�����
����
����
����
����
����
����
����
����
���
���
���
����������������������������� ���������������������������
����
�����
�����
����
Booster unit PKYK 1...5 for light fuel oil
Theboosterunitlendsitselfforpumpinglightfueloilwithviscosityof4...12mm2/s,+20°C.Theoilcomingtotheboosterunitmustbefiltered,max.filtrationdegree=400µm.
1. Oilfilter2. Pressuregauge3. Oilpump4. Electricmotor5. Pressureregulatingvalve6. DrilledballvalveA. InlettotheboosterunitDN25,
1...5bar4...12mm2/sB. ReturnfromtheboosterunitR1/2”C. InlettotheburnerØ22D. ReturnfromtheburnerØ22
Booster unit Motor400 V/50 Hz
kW r/min
Oil pump
Type
Pump output 12 mm2/s 25 bar
kg/h
PKYK 1 4 3000 T3 C 1420
PKYK 2 4 3000 T4 C 1980
PKYK 3 4 3000 T5 C 2900
PKYK 4 5,5 3000 AFI40R46 4230
PKYK 5 5,5 3000 AFI40R54 5500
Theoutputhasbeencalculatedusingadensityof850kg/m3forthelightfueloil.
PKYK booster units may be selected using the diagram 3.
11
����
���������
�����
���������
��
��
�
����
���������
�
��
��
����
���������
�
�
���
����
���
����
����
����
����
����
����
����
����
���
���
���
����������
����������������������������
� ����������������������������������������������������
����
������
������
����
Booster unit PKYR 1...8 for heavy fuel oil
Theboosterunitlendsitselfforpumpingandheatingheavyfueloilwithamaximumviscosityof650mm2/s,+50°C.Theoilcomingtotheboosterunitmustbefiltered,max.filtrationdegree=400µm.
��
�
� �
� ��
��
��
�
��� ��� ��� ���
�
�
�
�
�
�
�
�
1. Oilfilter2. Pressuregauge3. Oilpump4. Electricmotor5. Pressureregulating
valve6. Drilledballvalve7. Preheater8. Limitthermostat9. Temperatureregulator
andlowerlimit thermostat
10.TemperaturesensorA. Inlettotheboosterunit
DN25,3...5bar4...70mm2/sB. Returnfromthebooster
unitR1/2”C. InlettotheburnerØ22D.ReturnfromtheburnerØ22
Booster unit L1 L2 B1 B2
PKYR 1 840 880 815 855
PKYR 2 840 880 815 855
PKYR 3 840 880 815 855
PKYR 4 900 940 1250 1290
PKYR 5 900 940 1250 1290
PKYR 6 900 940 1540 1580
PKYR 7 890 940 1700 1750
PKYR 8 890 940 1700 1750
PKYR 1...6
PKYR 7...8
12
Booster unit PKYR 1...8 for heavy fuel oil
Scope of delivery Boosterunitsincludefollowingequipment:
PKYK PKYR
Oil filter • •
Pressure gauge • •
Oil pump • •
Electric motor • •
Pressure regulating valve • •
Drilled ball valve • •
Preheater •
Limiter thermostats •
Temperature regulatorand lower limit thermostat
•
Temperature sensor •
Trace heating of the piping o
Pressure gauge for monitoringoil inlet pressure
o o
Pressure switch o o
Operating and maintenance manual • •
•standarddeliveryooptional
Burners for preheated combustion airByusingpreheatedcombustionair,theoverallefficiencyrateoftheplantimprovesremarkably.
Preheatedcombustionaircanbeuseduptothetemperatureof+250°CinMEseriesburners(optional).Whenaburner
isbuilttousepreheatedcombustionair,itselectricandme-chanicalpartsaretobeprotectedfromheat.Theburnersmayusecombustionairofupto+50°Cwithoutmodification.
Schematic drawing of the principle of a plant using preheated combustion air.
�����
�����
�����
�����
�����
�����
�����
�����
�����
�����
����
����
����
������ �� �� ��
����
���
���
��� ��
����
�������������������������������� ��������������������������
��������������������������
����������������������������
���
����
������
��
�
�������
�������
�������
�������
������
������
������
�������
���
Booster unit Heat exchanger400 V/50 Hz
kW
Motor 400 V/50 Hz
kW r/min
Oil pump
Type
Pump output 12 mm2/s 25 bar
kg/h
PKYR 1 18 3 3000 AFI20R46 2030 PKYR 2 24 4 3000 AFI20R56 2880 PKYR 3 30 4 3000 AFI20R56 2880 PKYR 4 36 5,5 3000 AFI40R38 3280 PKYR 5 48 5,5 3000 AFI40R46 4430PKYR 6 60 5,5 3000 AFI40R46 4430PKYR 7 72 7,5 3000 AFI40R54 5500 PKYR 8 84 7,5 3000 AFI40R54 5500
Theoutputhasbeencalculatedusingadensityof980kg/m3fortheheavyfueloil.
PKYR booster units may be selected using the diagram 4.
����
����
����
����
����
����
����
����
����
����
����
��������������������������������� �������������������
��� �������������������
�� �����������������������
�����
����
���
����
����
��
�
���������������������������������������������������������������������������������������������������������
13
Control panels and supply cabinetsThisburnerseriesincorporatesseparatecontrolpanelsandpowersupplycabinets.Thestandardpanelsandcabinetsaredesignedforvoltages3~400V50Hz,controlvoltage1~230V50Hz.EnclosureclassIP40.Outerdimensionsare600x600x210mm.
Whennecessary,panelsandcabinetscanbebuiltaccordingtothecustomer’sneeds.
Typemarkingofthecontrolpanels:OK100Typemarkingofthesupplycabinets:RK100
Fuel-specifictypemarkingsofthecontrolpanels:Controlpanelforlightfueloilburner OK100-KPME0Controlpanelforheavyfueloilburner OK100-RPME0Controlpanelforgasburner OK100-GPME1Controlpanelfordualfuelburnerlightfueloil/gas OK100-GKPME1Controlpanelfordualfuelburnerheavyfueloil/gas OK100-GRPME1
Control panel OK100Scope of deliveryControlpanelsincludethefollowingitems:
OK100-KPME0
OK100-RPME0
OK100-GPME1
OK100-GKPME1
OK100-GRPME1
Control unit LAL • •Control unit LFL • • •Capacity controller RWF-40 • • • • •Capacity controller, other o o o o oAuxiliary relays • • • • •Burner control switch • • • • •Run hour counter for oil • • • •Run hour counter for gas • • •Failure reset button • • • • •Signal lamps • • • • •Preheater temperature controller CALPreheater operating switch • •Remote start/stop o o o o oCapacity information for remote use(potentiometer with servomotor)
o o o o o
Potential-free alarms o o o o oSteam/water boiler automaticsintegrated into the control panel
o o o o o
O2 display/alarm o o o o oElevated IP class o o o o oOther voltage o o o o oBuilt according to the requirements of classification societies o oPLC control and/or electronic fuel/air ratio control o o o o oFlue gas damper control o o o o oOil leakage alarm o o o o
Supply cabinet RK100Scope of deliverySupplycabinetsincludethefollowingitems:
RK100Main switch •Automatic circuit breakers •Contactor outputs •Thermal relays •Star-delta starter oSoft starter oBoiler automation power-current outputs o
All-inclusive burner automatics: oxygen (O2)/pressure difference/ cascade control Supply cabinet RK100
Control panel OK100
•standarddeliveryooptional
14
WiseDrive
WiseDrive (WD), an electronic regulator for controlling the fuel/air ratio – an energy-efficient and environmentally friendly solution
Electronicfuel/airratiocontroloftheburner(optional)bringsthebenefitsoflowerfluegasemissions,decreasedconsumptionofenergyandimprovedtechnicalcharacter-isticsoftheburner,suchasmoreaccurateregulation.
Examples of the WiseDrive’s functions:
•Controlsequencesoftheburner,conventionalcontrolunitdeleted
•Fuel/airratiocontrolwithdedicatedservomotors,whichcanbesetaccuratelyforeachcontroldevice
•Outputregulator(PID)asstandard,outputregulationalsobyanexternal4...20mAsignal
•Whencombustinggas,leaktestingofthemaingasvalvescarriedoutbytheWiseDrive
•O2andfanmotorRPMregulationaccordingtotheoutput•Readingoftheconsumptionsignalsfromfuelgauges•Canbeconnectedwithexternalplantautomation viaaModBuss•4operatinglevels•Inputofparametersviaacharacterdisplaypaneland
anoperatingpanel.Alsocomeswithagraphicaltouchscreenatextracost.
Combustionmanager
Airflowcontrol Combustionheadoptimizer
O2sensor
Indicationandoperatingunit
Frequencyconverter
Impulsegenerator
Oilflowcontrol
ExampleWiseDrive 200 + frequency converter
Control sequences, fuel/air ratio and output regulation and much more in a single package.
������������
�
�
�
�
�
�
�
�
� � �� �� �� �� �� �� �� �� �� � �� �� �� ���
���������
���
����
��
�
���� �� �� �� �� �� � ��
�����������
���������������
��������������
������������������
15
��������������������������������
��������������������������������������
Burner preheater
Accurate temperature control guarantees good combustionInburningheavyfueloil,therightatomisingviscosityoftheoilisessentialforgoodcombustionandlowcombustiongasemissions.Aprerequisiteforstableatomisingviscosityisthattheoiltemperaturestaysstablethroughoutthefiringrate.
OilonMLmasspreheaterkeepstheoiltemperaturestableeveniftheincomingtemperaturefluctuates.Onaccountoftheconstructionandtheelectronicregulator,thetemperatureoftheoilflowingtothenozzleremainsstable.Theburnermay,dependingonthecapacityandmodel,haveoneormore6-kWheatersequippedwithasafetydevicetoguardagainstoverheating.Theelectronicregulatorhasanintegratedminimumtemperaturelimiteraswell;thispreventstheburnerfromstartingiftheoilistoocold.
Masonry figure Flame dimensions
1 Gasket2 Mounting panel3 Ceramic wool or equivalent4 MasonryØ D1, Ø D4, L2 See burner dimension diagram
Lower diagrams for light fuel oil and gas, upper diagrams for heavy fuel oil.
ØD1
ØD4
L2
60...90°
1
2
4
3
����
�����
��
��
��������
����
���
������������������
��
Oil supply diagram for heavy fuel oil
Example
Gas pressure control assembly
Example
16
�������������
Oilon invests in product development and research. A modern product development centre meeting all European standards enables us to carry out a wide range of burning tests and accurate oil and gas measurements.
We supply burners for ships according to the requirements of classification societies such as ABS, BV, CCS, DNV, GL, KR, LR, NKK, RINA and RS.