Date post: | 23-May-2017 |
Category: |
Documents |
Upload: | mohamed-wahid |
View: | 254 times |
Download: | 7 times |
OMICRON TEST METHOD FOR DTP
1. From relay software Press measure & counter
2. This screen will appeared
1 /17
3. For pickup value (sensitivity) Double click on omicron icon
2 /17
4. This screen will appear OMICRON MAIN SCREEN click QUICKCMC
3 /17
5. There are two methods to test sensitivity 5/1 by applying value in ph R =0.2 A if no trip stop the test and increase the value to 0.3 Ato get the min pickup value
4 /17
5/2 by applying value in ph R =0.2 A and make auto test by adjust the increasing value and take stop contact from the diff. relay to stop test at the pickup value So adjust step like as fellow:Triple = CMC156-EPI size = 0.01 AQuantity = I1 time = 0.5 SAnd select auto step and select stop contact then press test
5 /17
6. For test harmonic in the main screen press testing tools then press harmonic
6 /17
7. This screen will appearput Ia = 5 A time = 1 S select Ia from here and harmonic value = 22 % then file - export
7 /17
8. this screen will appear enter the name of your harmonic (any name) for ex. 2 hr 22
8 /17
9. this screen will appear then press OK then file - Exit or press here
9 /17
10. this screen will appear then press NO
10 /17
11. The main screen will appear againPress testing tools then transplay
11 /17
12. This screen will appear press add to list
12 /17
13. This screen will appear then select your test name and press open
13 /17
14. This screen will appear then press ok
14 /17
15. This screen will appear then press play (means the tester start to inject if you want to change the harmonic value repeat again from point 7 and adjust according your requirements
15 /17
16. For RESTRAIN testOpen screen QUICKCMCThen inject ph R = 2.5 A angle 0 and connect it to ph R HV side, Inject ph S = 1.443 A angle 180, ph T= 1.443 A angle 0 and connect it to ph R ,ph T LV side consequently Then start test and read the measurements from TDP software and take Id , It
16 /17
17. Instantaneous function 87B
Disable the harmonic & diff. functions Enable Instantaneous function 87B
Then open QUICKCMC and make auto test for this function to bring the tripping value Like as point Start from 9 A and size 0.1 ALike this screen
Eng. Mohammed Deraz
ThyssenKrupp Co.
17 /17