TOTAL for POWER SYSTEMSPROTECTION
ASHIDA PROTECTION RELAYSASHIDA PROTECTION RELAYS
2 Time delay starting or closing relay
3 Trip circuits monitoring
21 Distance protection
25 Synchrocheck
27 Undervoltage function
27R Additional undervoltage function
37 Undercurrent detection
46 Unbalance negative sequence
current protection
47 Voltage unbalance protection
49 Thermal image
50 Phase instantaneous overcurrent
function
50C Transformers tank protection
50FA Instantaneous overcurrent with
harmonics restrain
50N Neutral / Ground Instantaneous
overcurrent function
50Ns Sensitive neutral instantaneous
overcurrent function
50N/50Ns Sensitive neutral instantaneous
overcurrent unit
50Nd/51Nd Neutral unbalance (WYE connection)
50d/51d Current unbalance in double WYE
Capacitor banks
50s+62 Circuit breaker failure protection
51 Phase overcurrent function
51N Neutral overcurrent function
50N/51Ns Neutral/Sensitive neutral time
overcurrent
51RB Protection against blocked rotor
59 Overvoltage function
59N Zero sequence overvoltage function
64 Ground faults protection
66 Excessive number of start ups
(motors)
67 Directional phase overcurrent
67N Directional neutral overcurrent
67NA Directional zero sequence
overcurrent (Isolated neutral
networks)
74TC Tric Circuit Supervision
79 Recloser
81 M/m Over/under frequency
87 Differential protection
95 Special neutral overcurrent function
95N Special neutral overcurrent function.
ANSI terminology Term Function
ASHIDA
ASHIDA Protection Relays for Power Systems:
ASHIDA ASCADA-SAS Substation Automation Systems:
Our Strength:
Some of our Achievements include:
35 years of technological service
is a pioneer in Protection Relays for Power Systems and
Substation Automation Systems that enable utility and industry customers
to improve performance economically.
We have complete
solutions for Industrial and commercial customers, with a broad range of
products, systems and services for power transmission & distribution.
Blends a
robust product and service portfolio with end-user expertise to deliver
solutions for control, monitoring , protection, and plant integration across
the full range of substation, process and utility industries.
With our strong R&D team and full-fledged production
plant, facility to design any emended & DSP base systems, application
knowledge and local expertise, we offer products, systems, solutions and
services that allow our customers to improve their operations.
Our people work together seamlessly to deliver benefits for our
customers.
Our way of doing business is values-based and performance-oriented.
>Complete Protection solutions, including distance protection for newly
converted 25kv traction of prestigious Mumbai suburbs railway
network.
>Specialised DC protection systems for Mumbai & Kolkata metro
railway.
>Various SCADA systems for upto 400KV sub-stations, integrated with
various numerical relays, GIS systems, etc for more than 3years.
Ashida Electronics Pvt. Ltd is started in 1970 by technocrat
Mr. Manohar P. Kulkarni. Soon we established our self as
reputed manufacturer of non-destructive testing
instrument for Geo-logical application. From 1985
onward we started manufacturing of Protection
Relays for Power Systems. In 1998 our company was
certified with ISO 9001and year 2000 we shifted in our
new full-fledged production plant of 25000 sq feet. stIn 2002 we were awarded 1 prize of very prestigious
Government of India - Nation Award for special
efforts in R&D.
Model ANSI Function
ACAG14 50N Single Pole REF Relay(Tuned to 50Hz)
ACAG34 3x50N 3 pole version of ACAGl4(Tuned to 50Hz)
ADAG3x 3x51+50 IDMT with 2 O/C + 50HZtuned Instant EF withchar. 1 & 2.
ADAG5x 2x51 IDMT with 2 O/C + 50Hz+51N tuned Instant EF + High+2x51 Fault with char. 1 & 2.
x = IDMT Characteristic (C1-C5)Model ANSI Function
ACDF31H 3x87 2 winding Tx diff relay with harmonic restrain
ACDT31H 3x87 2 winding Tx diff relay without harmonic restrain
Instantaneous High StabilityRestricted E/F Relay.
1. Input C.T : 1/5 AMP.2. Setting : ACAG 14 : 5%-80%
ACAG 34 : 5%-80%ADAG 3x : 50 % -200 % for Phase
5 % - 80 % for EFADAG 5x : 50% - 200% for Phase
5% - 80% for E/F INST - 20N for HF
3. Pick Up : 1.1 times of Setting4. Reset time : 200mS - 500mS after Removal
of Fault5. Operating time : less than 50mS6. Accuracy : Better than Class 5 as Per IS 32317. C.T Burden : Less than 02VA8. Aux. DC Supply : 24. 30V, 110 or 220V9. Burden of Aux. Supply
: Less than 10VA10. Insulation : 2.0 KV as per IS 323111. Impulse : 5.0 KV as per IS 868612. Thermal withstand
: Continuous 4 times of ratedFor 3 sec 40 times of rated
13. Output : 2 No trip duty contact
Model ANSI Function
ACTU 12 50N+2 Definite Time Earth Relay
ACTUM 15 50NS Sensitive E/F Relay with timer
ACTU 32P 3x51+3x2 3 O/C Relay
Definite Time Overcurrent Relay
1. Input C.T. : 1/5 Amp
2. Setting : ACTU 12 : 5% - 80 o far Current
Inst - 10 sec for timer
ACTU32P : 50 %-200 a for Current
Inst - 25 sec for timer
ACTUM15: 5mA-550mA
for Current
Inst - 10 sec for timer
3. Pick up : 1.1 times of setting
4. Reset time : 200 mS after removal of fault
current
5. Accuracy : Better than Class 5 as per IS 3231
6. C.T Burden : 0.2 VA max
7. Output : 2 No trip duty contact
8. Insulation : 2.0 Kv as per IS 3231
9. Impulse : 5.0 Kv as per IS 8686
10. Aux. Supply : 18-52 / 77-250V
11. Thermal : Continuous 4 times of rated 3 sec
withstand 40 times of rated
1. Input C.T : 1/5 AMP
2. Setting : Bias setting -15%, 30%&45%
HF setting -2N -20N
3. Pickup : 20% of rated
4 Reset time : 100mS
5. Operating time : 25mS
6. C.T Burden : 0.2 VA max
7. Output : 2No Trip duty contact
8. Insulation : 2.0kv as per IS 3231
9. Impulse : 5 0 kv as per IS 8686
10. Thermal withstand
: Continuous d times of rated
For 3 sec 40 Times of rated
11. Aux. supply : 18 - 52V and 77 - 250V
12. Burden on Aux. Supply : Less than 10VA
High speed Biaseddifferential relay.
IDMT characteristics C5 Long time Inverse of 10 Times 13.3 sec.
1000.00
800.00700.00600.00500.00
400.00
300.00
200.00
X 1.0X 0.9X 0.8X 0.7X 0.6X 0.5X 0.4
X 0.3
X 0.2
X 0.1
X 0.05
1.0 2 3 4 5 6 7 8 9 10 15 20N
N = CURRENT (MULTIPLE OF SETTING)
TIM
E (
IN S
EC
ON
DS
)
TIM
E (
TIM
E M
ULT
IPL
IER
SE
TT
ING
) F
OR
ID
MT
IDM
T C
UR
VE
S
100.00
80.0070.0060.0050.00
40.00
30.00
20.00
10.00
8.007.006.005.00
4.00
3.00
2.00
1.00
0.800.700.600.50
0.40
0.30
0.20
IDMT characteristics C4A - Extremely Inverse(Matching to Electro mechanical Relay)
of 10 Times 0.6 sec.
X 1.0X 0.9X 0.8X 0.7X 0.6X 0.5X 0.4
X 0.3
X 0.2
X 0.1
X 0.05
1.0 2 3 4 5 6 7 8 9 10 15 20N
N = CURRENT (MULTIPLE OF SETTING)
TIM
E (
IN S
EC
ON
DS
)
TIM
E (
TIM
E M
ULT
IPL
IER
SE
TT
ING
) F
OR
ID
MT
IDM
T C
UR
VE
S
10.00
8.007.006.005.00
4.00
3.00
2.00
1.00
0.800.700.600.50
0.40
0.30
0.20
100.00
80.0070.0060.0050.00
40.00
30.00
20.00
0.10
0. 800. 700. 600. 50
0. 40
0. 30
0. 20
0.01
IDMT characteristics C4Extremely Inverse of 10 Times 0.8 sec.
X 1.0X 0.9X 0.8X 0.7X 0.6X 0.5X 0.4
X 0.3
X 0.2
X 0.1
X 0.05
1.0 2 3 4 5 6 7 8 9 10 15 20N
N = CURRENT (MULTIPLE OF SETTING)
TIM
E (
IN S
EC
ON
DS
)
TIM
E (
TIM
E M
ULT
IPL
IER
SE
TT
ING
) F
OR
ID
MT
IDM
T C
UR
VE
S
10.00
8.007.006.005.00
4.00
3.00
2.00
1.00
0.800.700.600.50
0.40
0.30
0.20
100.00
80.0070.0060.0050.00
40.00
30.00
20.00
0.10
0. 800. 700. 600. 50
0. 40
0. 30
0. 20
0.01
Specification
MODEL CASE CUT-OUT
ACAG14 CSB - 150 92 x 92 mm.
ACAG34 CSA - 150 138 x 138 mm.
ADAG3x /5x CSA - 150 138 x 138 mm.
Specification
MODEL CASE CUT-OUT
ACTU 12 CSB - 150 92 x 92 mm
ACTU 32P CSA - 150 138 x 138 mm.
ACTUM 15 CSB - 150 92 x 92 mm
Specification
MODEL CASE CUT-OUT
ACDF31H CSD - 120 - V 138 x 280 mm
ACDT31H CSD - 120 - V 138 x 280 mm
1. Input C.T : 1/5 AMP
2. Setting : ACAG 17 : 100% -800 a
ACAG 12 : 5% -80 0
APR4H : 0.5Amp-15.5Amp
for phase & E/F
3. Operating time : less than 50 mS
4. Accuracy class : Better than Class 5
as per IS 3231
5. Pick Up : 1.1 times of Setting
6. Reset time : 200mS - 500m5 after Removal of
Fault Current
7. C.T Burden : Less than 0.1 VA
8. Aux. Supply : 24, 30V, 110 or 220V
9. Output : 2 No trip duty contact
10. Insulation : 2.0 KV as per IS 3231
11. Impulse : 5 0 KV as per IS 8686
12 Thermal withstand : Continuous 4 times of
rated For 3sec 40 times of rated
Model ANSI Function
ACAG17 50 Single Pole O/C Relay
ACAG12 50N Single Pole E/F Relay
APR4H 3x50+50N 3 O/C + EF Relay
Instantaneous Over Current /Earth Fault Relay
1. Input voltage : 110VAC
2. Setting : AVDG 11 : 110-170%
AVDG 13 : 30 - 90 %
AVDG 14 : 5.4 - 20V
3. Pick Up : 1.1N of setting
4. Resetting Voltage : +/-10 of set value
5. Operating Time
: AVDG 11 : At 1.5 lime = 7.0 sec
AVDG 13 : At OV = 5.0 sec
AVDG 14 : At 5 times = 10.5 sec
6. Accuracy : Class of 7.5
7. Burden on PT : 1 VA
8. Output : 2 No trip duty contact
9. Insulation : 2.0 kv as per IS 3231
10. Impulse : 5.0 kv as per IS 8686
11. Aux. Supply : 18 - 52V and 77 - 250V
12. Burden on Aux. Supply : Less than 10VA
Inverse timeVoltage Operated Relay
Model ANSI Function
AVDG 11 59 Inverse Time Over VoltageRelay
AVDG 13 27 Inverse Time Under VoltageRelay
AVDG 14 50N Inverse Time NeutralDisplacement Relay
Model ANSI Function
ASUV 27 Definite time under voltagewith adjustable time setting
ASUVF 27 Definite time under voltage fix time setting
ASOV 59 Definite time over voltagewith adjustable time setting
ASOVF 59 Definite time over voltagewith fix time setting
AOUV 27+59 Definite time under / overvoltage relay with adjustable time
AUV 3P 27 3 Phase under voltage Relay with adjustable timer
AOV 3P 59 3 Phase over voltage Relay with adjustable timer
Definite TimeUnder/Over Voltage Relay.
1. Input : AC or DC 24,30,110 & 220V
2. Setting : For ASUV & ASUVF 45-95%
For ASOV & ASOVF 105 - 155 %
3. Plck-up : 1.1N of setting-OV / 0.95N-UV
4. Reset voltage : 5 % of rated
5. Aux. Supply : 24,30,110 & 220V
6. Burden on Aux. Supply : Less then 5.0VA
7. Burden on monitor supply : Less then 2.0VA
8. Thermal with stand : 2 times of normal voltage
continuous
9. Output : Annunciation Duty / Trip Duty, to be
specified
10. Insulation : 2.0 KV as per IS 3231
11. Impulse : 5.0 KV as per IS 8686
18.0
16.0
14.0
12.0
10.0
8.00
6.00
4.00
2.00
0.000 1.0 2.0 3.0
Multiple Of Plug Setting
Time / Voltage Characteristic of Over Voltage Relay AVDG 11 IDMT 7 Sec At 1.5 Times
Op
era
tin
g T
ime
In
Se
co
nd
s
45.0
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.00
0.00
0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 00.0
Percentage of Closing Voltage
Op
era
tin
g T
ime
in
Se
co
nd
s
Time / Voltage Characteristic of Under VoltageRelay AVDG 13 IDMT 5 Sec At 0.0 Voltage
50.0
40.0
30.0
20.0
10.09.08.07.06.05.0
4.0
3.0
2.0
1.00.90.80.70.60.5
0.4
0.3
0.2
x 1.0x 0.9x 0.8x 0.7x 0.6x 0.5
x 0.4
x 0.3
x 0.2
x 0.1
2 3 4 5 6 7 8 9 10Multiple of Plug Setting
Op
era
tin
g T
ime
In
Se
co
nd
s
IDMT Characteristic of 10.5 sec At 5 TimeNetral Displacement Voltage Relay Type
Specification
MODEL CASE CUT-OUT
ACAG17 / 12 CSB - 150 92 x 92 mm.
APR 4H CSA - 150 138 x 138 mm.
Specification
MODEL CASE CUT-OUT
AVDG xx CSA - 150 138 x 138 mm.
Specification
MODEL CASE CUT-OUT
ASUV CSB - 150 92 x 92 mm.
ASUVF CSB - 150 92 x 92 mm.
ASOV CSB - 150 92 x 92 mm.
ASUVF CSB - 150 92 x 92 mm.
AOUV CSB - 150 92 x 92 mm.
AUV 3P CSA - 150 138 x 138 mm.
AOV 3P CSA - 150 138 x 138 mm.
5
Model ANSI Function
ATSR31A 74TC Trip circuit monitor
Model ANSI Function
AEAR1 79 Single shot auto-recloser
AEARM/2S 2x79 2 shot Auto-recloser
APAR4xS2 2x51+51N IDMT 20/c+EF+High Fault+2x50 +2 shot auto recloser
+50N+2x79
Auto Recloser Relay.
1. Input : 1/5 AMP
2. Setting
APAR4xS2 : 50 %-200 % (or phase
5 %-80 % for Earth Fault
INST-20N and Bypass for
high fault
Reclaim time 50-300sec
Reclose 1 : 30-60sec
Reclose 2 : 60sec Fixed
AEARM/2S Reclose 1 : 10-60sec
Reclose 2 : 30-180sec
Reclose 3 : 200-300sec
3. Pickup : 1.1 N of setting
4. Reset Time : 200mS after removal of fault
current
5. Accuracy : Within class 2.5 as per IS 3231
6. C.T. Burden : Less than 0.2 VA
7. Aux DC Supply : 18-52VDC or 77-250VDC
8. Burden on Aux Supply : Less then 10VA
9. Insulation : 2.0 KV as per IS 3231
10. Impulse : 5.0 KV as per IS 8686
11. Thermal with Stand
: Continuous 4 times of rated
for 3 sec 40 times of rated
12. Output : 2 NO trip duty contact
Model ANSI Function
AVAJH 13 High Speed Master TripRelay (1 Element )
AVAJH 23 High Speed Master TripRelay (2 Element )
AVAJH 33 High Speed Master TripRelay (3 Element )
AVAJHM 23 High Speed Tripping Relay(2 Element In Series)
AVAJHM 33 High Speed Tripping Relay(3 Element In Series)
AVA 11 Voltage Operated AuxiliaryRelay (1 Element )
AVA 21 Voltage Operated AuxiliaryRelay (2 Element )
AVA 33 Voltage Operated AuxiliaryRelay (3 Element )
AVA 21D DC Failure Alarm Relay
Note : For other models Please refer detail technical catalogues
Auxiliary Relay
1. Operationmits : 50 to 120% of rating for AVAJH
20 to 50% for AVA 2. Operational Time : 10 - 15 mS at normal rated voltage
for AVAJH, 20 - 25 mS for AVA 3. Coil Rating : 24V / 30V / 110V / 220V or AC 4. Burden : @ 30VDC / 24VDC: 8 watts @ 110 VDC: 8 watts
@ 220 VDC: 18 watts 5. Operational Indicator
: Mechanical Flag (Red for Alarm, white for Normal)
6. Contacts : 4 pair of Hand Reset 7. Relay Conforms : IS:3231 fully for all requirement
9. Contact Rating Make & Carry Make & Carry
Break Continuous For 3.0 ssc.
AC 1250 VA with 7500 VA with 1250 VA with maxima of maxima of maxima of 5 A & 660 V. 30 A & 660 V. 5 A & 660V.
DC 1250 VA with 7500 VA with 100W Resistive maxima of maxima of 50W Inductive 5 A & 660 V. 30 A & 660V.
Trip CIRCUIT Supervisory Relay
1. Control Supply : 24 / 30 / 110 / 220 VDC
Specify while ordering
2. Aux. annunciation supply
: 24 / 30 / 110 / 220 VDC.
Specify while ordering
3. Trip coll DC resistance
: To be less then 500 Ohms
5. Operating Time : 10 sec
6. Control and auxiliary supply
: can be made parallel If required
7. Supervision : Pre Closing & Post Closing
Specification
MODEL CASE CUT-OUT
AEAR1 CSB - 150 92 x 92 mm.
AEARM2S CSC - 150 - H 92 x 192 mm.
APAR42 S2 CSD - 150 - V 138 x 280 mm.
Specification
MODEL CASE CUT-OUT
AVAJH13 CSB - 80 92 X 92 mm.
AVA11 /33 CSB - 80 92 X 92 mm.
AVA21 /21D CSB - 80 92 X 92 mm.
AVAJH23 / 33 CSC - 80 - H 92 X 186 mm.
AVAJHM23 /33 CSC - 80 - H 92 X 186 mm.
Specification
MODEL CASE CUT-OUT
ATSR31 CSB - 150 92 x 92 mm.
Model ANSI Function
APR1xP 51 Single Pole O/C Relaywith char. 1 or 2.
APR1xPH 51+50 APR1xP withInstantaneous High Fault.
APR1xE 51 N Single Pole Earth FaultRelay with char. 1 or 2.
APR1xEH 51N+50N APR1xE withInstantaneous High Fault.
APR3x 2x51+51N 2 O/C+1 E/F IDMT Relaywith char. 1 or 2.
APR3xHP 2x50+ APR3x with Instantaneous51Nx50 High Fault for phase.
APR3xHS 2x51+51N APR3x+Separate High+2x50 Fault Setting tor phase+50N & Earth.
APR3xH 2x51+51N APR3x Relay with High+50+50N Fault Setting common
to phase and Earth Fault.
APR3xP 3x51 3 Pole IDMT over current Relay.
APR3xPH 3x51+3x50 APR3xP withInstantaneous High Fault.
APR4x 3x51+51N 3 O/C + EF IDMT Relay.with char. 1 or 2
APR4xHP 3x51+51N APR4x Relay with High+3x50 Fault for phase
APR4xHS 3x51+51N APR4x Relay with+3x50 separate High Fault for
phase & Earth.
APR4xH 3x51+51N APR4x Relay with Hi+3x50 Fault Setting common to+50N phase & Earth.
Note: Draw-out Cabinet Optional
IDMT characteristics C1 Normal Inverse 10 time 3.0 sec.
10
987
6
5
4
3
2
1.00
X 1.0X 0.9X 0.8X 0.7
X 0.6
X 0.5
X 0.4
X 0.3
X 0.2
X 0.1
X 0.05
0.900.800.70
0.60
0.50
0.40
0.30
0.20
0.100.090.080.07
1.0 1.3 2 3 4 5 6 7 8 9 10 15 20n
N = CURRENT (MULTIPLE OF SETTING)
TIM
E (
IN S
EC
ON
DS
)
TIM
E (
TIM
E M
ULT
IPL
IER
SE
TT
ING
) F
OR
ID
MT
IDM
T C
UR
VE
S
IDMT characteristics C3 Very Inverse 10 Times 1.5 sec.
X 1.0X 0.9X 0.8X 0.7X 0.6X 0.5X 0.4
X 0.3
X 0.2
X 0.1
X 0.05
1.0 2 3 4 5 6 7 8 9 10 15 20N
N = CURRENT (MULTIPLE OF SETTING)
TIM
E (
IN S
EC
ON
DS
)
TIM
E (
TIM
E M
ULT
IPL
IER
SE
TT
ING
) F
OR
ID
MT
IDM
T C
UR
VE
S
10.00
8.007.006.005.00
4.00
3.00
2.00
1.00
0.800.700.600.50
0.40
0.30
0.20
100.00
80.0070.0060.0050.00
40.00
30.00
20.00
0.10
0. 800. 700. 600. 50
0. 40
0. 30
0. 20
10
987
6
5
4
3
2
1.00 X 1.0X 0.9X 0.8X 0.7
X 0.6
X 0.5
X 0.4
X 0.3
X 0.2
X 0.1
X 0.07
0.900.800.70
0.60
0.50
0.40
0.30
0.20
0.100.090.080.070.06
0.05
0.04
0.03
0.02
0.011.0 1.3 2 3 4 5 6 7 8 9 10 15 20N
N = CURRENT (MULTIPLE OF SETTING)
TIM
E (
IN S
EC
ON
DS
)
TIM
E (
TIM
E M
ULT
IPL
IER
SE
TT
ING
) F
OR
ID
MT
IDM
T C
UR
VE
S
IDMT characteristics C2 Normal Inverse 10 time 1.3 sec.
Model ANSI Function
ACDR1xHP 67+50 Single Pole ACDR Relayfor phase and nondirectional High Fault withchar. 1 or 2.
ACDR1xHPD Single Pole ACDR Relay67+50 for phase and directional
High Fault with Char.1 or2.
ACDR1x HE 67N+50N Single Pole ACDR forEarth Fault and nondirectional High Fault withChar. 1 or 2.
ACDR1xHED 67N+50N ACDR 1 x HE withdirectional High Fault withchar 1 or 2
ACOR4xH 3x67+67N 4Pole directional O/C &+3x50+50N E/F relay with non
directional HF with char.1 or 2.
ACDR4xHD 3x67+67N 4 Pole directional O/C &+3x50+50N E/F relay with directional
HF with char 1 & 2
Current DirectionalCurrent Operated IDMT Relay
Specification
Model CASE CUT-OUT
APRxxx CSA - 150 138 x 138 mm
ACDR1xx CSA - 150 138 x 138 mm
ACDR4xx CSD - 120 - V 138 x 282 mm
3
1. Input C.T : 1/5 AMP.
2. Setting Phase : 50 % - 200 %
E/F: 5%-80%
Phase HF : 200 % - 2900% - ¥
Earth HF : 100 % - 1200 % - ¥
Comm. HF : INST - 20N - ¥
Directional setting :
Phase : 30degree, 45 deg, or
60 deg lead
Earth : 14deg, 30deg, 45 deg, or
60 deg Lag
3. Pick Up : 1.1 times of Setting
4. Reset time : 200mS after Removal of Fault
current
5. Operating time
: As per IDMT Characteristic l
X = IDMT type
1-5 = C1-C5
6. Accuracy : Class 2.5
7. C.T Burden : 0.2 VA max
8. Output 2 No trip duty contact
9. Aux. Supply : 18VDC - 52VDC OR
77VDC - 250 VDC/AC
10. Burden of Aux. Supply
: Less than 10 VA
11. Insulation : 2.0 KV as per IS 3231
12. Impulse : 5.0 KV as per IS 8686
13. Thermal with stand
: Continuous 4 limes of rated
For 3sec 40 times of rated
Current Operated IDMT Relay
ASHIDA SCADA Software coupled with ASHIDA s
FCCM series of modules forms a scalable & flexible
ASCADA-SAS System This system can be employed to
make a satellite sub-station completely un-manned,
controlled from a central location Such a scheme can
serve as an Important tool in Energy Management &
Audits and also completely encompass the functions of
Event Sequence Recording.
This Intuitive GUI based system is built on
internationally standard components. Any available
communication medium (ea. PLCC, VHF, dial-up,
Dedicated cables, etc.) can be used to link the Sub-
station equipment to the central software using
appropriate communication interfaces The modular
approach gives a benefit of add-on simplicity with
maximum economic benefit.
'
ASHIDA ASCADA-SAS System.
ASHIDA RELAY TESTING UNIT VARIABLE FREQUENCY (ARTUVF)
Variable AC current: - 0-200Amp with 250VA.
Variable AC voltage : - 0-300 VAC.
Variable DC voltage : - 0-360 VDC.
In-built auxiliary power supply: - 30 / 110 / 220VDC.
Fix AC voltage : for direction/power relay testing - 63.5 V / 110 V AC.
Time measuring : Micro-controller based unit with 1ms resolution.
Special provision : Relays ON Delay / OFF delay time measurement.
The ARTUVF/S unit is specially designed to suit relay
testing designed of power station testing engineers. The
ARTUVF/S is a cabinet, which has all the necessary
functions for relay testing viz. Auxiliary source, Time
Interval Meter up to 1ms resolution etc. After adding
optional phase shifter and phase angle meter, the
ARTUVF/S become a complete relay-testing unit for
testing of all available Static / Electromechanical TSS
r e l a y s , l i k e I D M T O v e r C u r r e n t ( O C R -
1/2/3)/REF/Under-over Voltage/ Power- Directional /
Distance Protection (DPR, WPC)/ Delta-I Protection/
Auxiliary Relays etc.
A 2R D 1 B 4
NO
SN IA
05
N50
55 10,
5 50 1N N,
79
4T7 C
E I C
I>>
IE>>
I>t, Ip
EE>t, II P
E N I R T N UC OIT T NP O F C O
S OVE R C ENTIN AN U
T AN U R S T EO R
AULIN AN HT AN US T EO S F TEARTT C EN PHT SE)U A
I R ME VER R (O
O EN AC E RTI U TMR R HER (
T V R ) O RECAU L SERT O
R U PERI CP IT VIT IR SI N O .C SU RC LON OTBREAKER
r P laFe r ee ot yde ction Re
sr es e i
3S 2R 2
PKP
TLFAU
LCSP/R
PITR
ASHIDA Numerical Protection Relay
s e r i e s
>RS232 and RS485 Communication port for Local /
Remote SCADA System
>Load parameter on LCD Display
>Latching of fault parameter
>Programming Via local keys as well as remote
programming Via communication port .
>Back-lit LCD display for settings & parameter
display
>Pass-word protection
>Communication with IEC-870 protocol
>Disturbance recording
>Tested as per IEC 60255 standard
ADITYA Numerical Relay having Common User
Interface & Communication Interface. Various
protection such as OC / EF (IDMT / Definite time) /
Transformer differential / Directional / Reverse power /
UV / OV can be available.
1. Power Supply
2. Measurement Range
: 1 mS to 99999 Sec. Auto ranging.
3. Measurement Mode
: NO / NC Start.
NO / NC Stop.
4. Accuracy : 0.1 %
5. Display : 5 Digits bright 7 segment LEDs.
7. Cabinet : Table Top 110 x 200 x 120 mm.
: 250 VAC
ASHIDA RELAY TESTINGTIMER UNIT (ARTU)
ARTU: Micro-Controller based auto ranging timer / counter unit of operating / dropout time of time operating relay.
Specification
Specification
Specification
>Accurate Frequency monitoring with Crystal
Controlled references.
>Trip Frequency Point can be selected with 0.01 Hz
Resolution.
>Self-Calibration and check ON-Site facility inbuilt.
>Instrument tested to withstand as per IS:3231,
IS:8686-1977 Specification.
>Two Independent set points programmable as Under
or Over Frequency.
>RS232 & RS485 Communication Port for remote
SCADA.
>AC Input from 230 / 110 / 63 V AC PT for Frequency
Sensing.
>Frequency setting Range : 49.99 Hz to 40.00 Hz in
steps of 0.01 Hz for Under Frequency and 50.01 Hz
to 60.00 Hz in steps of 0,01 Hz for Over Frequency.
>Accuracy Setting : +/- 0.01 Hz Repeat Accuracy
better then 0.05 Hz.
>Delay Time Adjustment : 0 to 99.9 sec Accuracy +/-
5% or +/- 0.02s whichever is Higher.
>Programmable Hysterisis.
>This Relay is also available with 2 Stage df/dt and 2
Stage Under/Over Frequency Features.
>Cutout : 186 x 92 mm.
Numerical Under/Over Frequency Monitoring Relay- AUOFMR2
Specification
7
Range of numerical / static protection relays & 01-25 kv AC traction application.
ADDR/1: Complete Feeder Protection relay for 25 kv / AC system including Distance / WRC / PT Fuse Fault location ETC. elements.
AIDI/1C: Delta-I type high resistive fault selective relay. (vectorial)
APFO/1: Digital Pento flash over relay.
ADTR/1: High Resistance fault detection relay for 1.5kdc / 750vdc protection systems.
(Refer detail Catalogue)
ASHIDA Digital Traction Protection Relays for Railways
‘ASHIDA HOUSE’, A-308. Road No.21, Wagle Industrial Estate, Thane-400604. INDIA
Tel: 91-22-2582 7524 / 25 / 26, 6577 1076 / 77 / 78Fax: 91-22-2580 4262 Email: [email protected]
www.ashidaelectronics.com
ASHIDA ELECTRONICS PVT. LTD.
FRONT
CAP
1
2
3
4
5
6
7
8
9 19
10 20
11 21
12 22
13 23
14 24
15 25
16 26
17 27
18 28
BACK
SIDE
203 92
75
75
110
‘D’
30
36
186
184
MINIMUM GAPFOR VER.MOUNTING.
MINIMUM GAP FOR HOR.MOUNTING.
CABINET STYLE ‘C’ - H
PANEL CUTOUT
ALL DIMENSION ARE IN MM.
FRONT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
BACK
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
BACK
160
138
75
75
302
CAP
SIDE
137
‘D’
30
36
282
MINIMUM GAPFOR VER.MOUNTING.
MINIMUM GAP FOR HOR. MOUNTING.
CABINET STYLE ‘D’ - VPANEL CUTOUT
FRONT
CAP
SIDE
137
160
138
138
75
75
160
‘D’
30
36
‘D’ CAB. STYLE
CSA- 80
CSA - 120
CSA - 150
CSA -150D
CSA - 200
80
120
150
150
200
MINIMUM GAPFOR VER.MOUNTING.
MINIMUM GAP FOR HOR.MOUNTING.
CABINET STYLE ‘A’
PANEL CUTOUT
ALL DIMENSION ARE IN MM.
2 4 6 8 10 12 14 16 18
BACK
1 3 5 7 9 11 13 15 17 A1 3 5 7 9 A11 13 15 17 19 A21
A2 4 6 8 10 A12 14 16 18 20 A22
C1 C2 C3 C4 C5 C6 C7 C8 C9
TERMINAL TYPE1 TERMINAL TYPE2
FRONT203
110
‘D’ CAB. STYLE
CSC - V - 120
CSC - V - 200
CSC - V - 80
CSC - V - 150120
200
80
150
CABINET STYLE ‘C - V’
PANEL CUTOUT
ALL DIMENSION ARE IN MM.
CAP
SIDE
91
‘D’
30
36
FRONT
CAP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
BACK
SIDE
91
110
92
92
75
75
110
‘D’
30
36
‘D’
120
CAB. STYLE
CSB - 80
CSB - 120
CSB - 150
80
150
MINIMUM GAPFOR VER.MOUNTING.
MINIMUM GAP FOR HOR.MOUNTING.
CABINET STYLE ‘B’
PANEL CUTOUT
ALL DIMENSION ARE IN MM.
CSB - 200200
75
MINIMUM GAPFOR VER.MOUNTING.
MINIMUM GAP FOR HOR.MOUNTING.
92
186
75
1 2
3 4
5 6
7 8
919
102
0
112
1
12
22
13
23
142
4
15
25
16
26
17
27
1828
BA
CK
‘D’ CAB. STYLE
CSC - H - 120
CSC - H - 200
CSC - H - 80
CSC - H - 150120