Ordinance No. G36-18 AN ORDINANCE ADOPTING THE INTERNATIONAL BUILDING CODE 2015 AS THE BUILDING CODE FOR THE CITY OF ELGIN WHEREAS, the City of Elgin is a home rule unit pursuant to the Constitution of the State of Illinois and, as a home rule unit, may exercise any power and perform any function pertaining to its government and affairs; and WHEREAS, the regulation of building and construction activities within the City relates to the public health, safety and welfare, and pertains to the government and affairs of the City. NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF ELGIN, ILLINOIS: Section 1. That Chapter 16.04 entitled Building Codeof the Elgin Municipal Code, 1976, as amended, be and is hereby repealed. Section 2. That Chapter 16.04 entitled Building Codebe and is hereby added to the Elgin Municipal Code, 1976, as amended, to read as follows: "Chapter 16.04 BUILDING CODE Sections: 16.04.010 Adopted-Exceptions. 16.04.020 Additions, Insertions, and Changes. 16.04.030 Sidewalks, Approaches and Driveways-When Required. 16.04.040 Fence Installation. 16.04.050 Assessors Receipt. 16.04.060 Street Numbers. 16.04.070 Construction Operations. 16.04.080 Conflicts With Other Provisions. 16.04.010 ADOPTED-EXCEPTIONS. That a certain document, one (1) copy of which is on file in the office of the City Clerk of the City of Elgin, being marked and designated as the International Building Code 2015, as published by the International Code Council, be and is hereby adopted as and shall be known as the Building Code of the City of Elgin for establishing minimum regulations governing the construction, alteration, addition, repair, removal, demolition, location, occupancy, and maintenance of all buildings and structures; and each and all of the regulations, provisions, penalties, conditions and terms of said International Building Code 2015 are hereby referred to, adopted, and made a part hereof, as if fully set out in this ordinance, with the additions, insertions, deletions and changes prescribed in this chapter.
Transcript
Page 1: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

Ordinance No. G36-18

AN ORDINANCE

ADOPTING THE INTERNATIONAL BUILDING CODE 2015

AS THE BUILDING CODE FOR THE CITY OF ELGIN

WHEREAS, the City of Elgin is a home rule unit pursuant to the Constitution of the State

of Illinois and, as a home rule unit, may exercise any power and perform any function pertaining

to its government and affairs; and

WHEREAS, the regulation of building and construction activities within the City relates

to the public health, safety and welfare, and pertains to the government and affairs of the City.

NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF

ELGIN, ILLINOIS:

Section 1. That Chapter 16.04 entitled “Building Code” of the Elgin Municipal Code,

1976, as amended, be and is hereby repealed.

Section 2. That Chapter 16.04 entitled “Building Code” be and is hereby added to the Elgin

Municipal Code, 1976, as amended, to read as follows:

"Chapter 16.04

BUILDING CODE

Sections:

16.04.010 Adopted-Exceptions.

16.04.020 Additions, Insertions, and Changes.

16.04.030 Sidewalks, Approaches and Driveways-When Required.

16.04.040 Fence Installation.

16.04.050 Assessor’s Receipt.

16.04.060 Street Numbers.

16.04.070 Construction Operations.

16.04.080 Conflicts With Other Provisions.

16.04.010 ADOPTED-EXCEPTIONS.

That a certain document, one (1) copy of which is on file in the office of the City Clerk of the City

of Elgin, being marked and designated as the International Building Code 2015, as published by

the International Code Council, be and is hereby adopted as and shall be known as the Building

Code of the City of Elgin for establishing minimum regulations governing the construction,

alteration, addition, repair, removal, demolition, location, occupancy, and maintenance of all

buildings and structures; and each and all of the regulations, provisions, penalties, conditions and

terms of said International Building Code 2015 are hereby referred to, adopted, and made a part

hereof, as if fully set out in this ordinance, with the additions, insertions, deletions and changes

prescribed in this chapter.

Page 2: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

2

16.04.020 ADDITIONS, INSERTIONS AND CHANGES.

The International Building Code 2015 is amended and revised in the following respects:

Section 101.1 Title, shall be amended to read as follows:

These regulations shall be known as the Building Code of the City of Elgin, hereinafter

referred to as “this chapter” or “this code.”

Section 101.4 Referenced codes, shall be amended to read as follows:

The other codes listed in Sections 101.4.1 through 101.4.8 and referenced elsewhere in this

code shall be considered part of the requirements of this code to the prescribed extent of

each such reference.

Section 101.4.1 Gas, shall be amended to read as follows:

The provisions of Chapter 16.20 and Chapter 16.32 of the Elgin Municipal Code, 1976, as

amended, shall apply to the installation of gas piping from the point of delivery, gas

appliances and related accessories as covered in this code. These requirements apply to

gas piping systems extending from the point of delivery to the inlet connections of

appliances and the installation and operation of residential and commercial gas appliances

and related accessories.

Section 101.4.2 Mechanical, shall be amended to read as follows:

The provisions of the International Mechanical Code 2015, as amended by Chapter 16.32

of the Elgin Municipal Code, 1976, as amended, shall apply to the installation, alterations,

repairs, and replacement of mechanical systems, including equipment, appliances, fixtures,

fittings and/or appurtenances, including ventilating, heating, cooling, air-conditioning and

refrigeration systems, incinerators, and other energy related systems.

Section 101.4.3 Plumbing, shall be amended to read as follows:

The provisions of State of Illinois Plumbing Code, as amended by Chapter 16.20 of the

Elgin Municipal Code, 1976, as amended, shall apply to the installation, alteration, repairs

and replacement of plumbing system, including equipment, appliances, fixtures, fittings

and appurtenances, and where connected to a water or sewage system. The provisions of

77 Illinois Administrative Code Chapter I: Department of Public Health Subchapter r: Part

905 et seq., as amended, shall apply to private sewage disposal systems.

Section 101.4.4 Property maintenance, shall be amended to read as follows:

The provisions of the International Property Maintenance Code 2012, as amended by

Chapter 16.12 of the Elgin Municipal Code, 1976, as amended, shall apply to existing

Page 3: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

3

structures and premises; equipment and facilities; light, ventilation, space heating,

sanitation, life and fire safety, hazards; responsibilities of owners, operators and occupants;

and occupancy of existing premises and structures.

Section 101.4.5 Fire prevention, shall be amended to read as follows:

The provisions of the International Fire Code 2015, as amended by Chapter 16.28 of the

Elgin Municipal Code, 1976, as amended, shall apply to matters affecting or relating to

structures, processes and premises from the hazard of fire and explosion arising from the

storage, handling or use of structures, materials or devices; from conditions hazardous to

life, property or public welfare in the occupancy of structures or premises; and from the

construction, extension, repair, alteration or removal of fire suppression, automatic

sprinkler systems and alarm systems or fire hazards in the structure or on the premises from

occupancy or operation.

Section 101.4.6 Energy, shall be amended to read as follows:

The provisions of the State of Illinois Energy Conservation Code, as amended, shall apply

to all matters governing the design and construction of buildings for energy efficiency.

Section 101.4.7, Existing Buildings, shall be created to read as follows:

The provisions of the International Existing Building Code 2015, as amended by Chapter

16.06 of the Elgin Municipal Code, 1976, as amended, shall apply to provide alternative

approaches to repair, alteration and additions to existing buildings, to make the alteration

process easier, while maintaining basic levels for fire prevention, structural and life safety

features of the rehabilitated building.

Section 101.4.8 Electrical, shall be created to read as follows:

The provisions of NFPA 70 National Electric Code 2014 Edition as amended by Chapter

16.24 of the Elgin Municipal Code, 1976, as amended, shall apply to the installation of

electrical systems, including alteration, repairs, replacement, equipment, appliances,

fixtures, fittings and appurtenances thereto.

Section 103.1 Creation of enforcement agency, shall be amended to read as follows:

The Community Development Department may be referred to as the Department of

Building Inspection for the purposes of this chapter and the Director of the Community

Development Department may be referred to as the code official for the purposes of this

chapter. Any reference to the terms code official, building code official or official in this

code shall also include the authorized designee of such code official, building code official

or official.

Section 103.2 Appointment, shall be deleted in its entirety.

Page 4: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

4

Section 103.3 Deputies, shall be deleted in its entirety.

Section 104.4 Inspections, shall be amended to read as follows:

The building official, or designee, shall make all of the required inspections. The building

official is authorized to engage such expert opinion as deemed necessary to report upon

unusual technical issues that arise.

Section 104.7 Department records, shall be deleted in its entirety.

Section 104.8 Liability, shall be deleted in its entirety.

Section 105.1 Required, shall be amended to read as follows:

Any owner or owner’s authorized agent who intends to construct, enlarge, alter, repair,

move, demolish, or change the occupancy of a building or structure, or to erect, install,

enlarge, alter, repair, remove, convert or replace any electrical, gas, mechanical or

plumbing system, the installation of which is regulated by this code or any other code

adopted by the City of Elgin or to cause any such work to be done, shall first make

application to the building official and obtain the required permit.

Section 105.1.1 Annual permit, shall be deleted in its entirety.

Section 105.1.2 Annual permit records, shall be deleted in its entirety.

Section 105.2 Work exempt from permit, subsection entitled Building, #1 shall be amended to read

as follows:

One-story detached accessory structures used as playhouses and similar uses, provided the

floor area does not exceed 120 square feet (11.15 m) and the floor is less than 4 feet above

grade.

Section 105.2 Work exempt from permit, subsection entitled Building, #2 shall be deleted in its

entirety.

Section 105.2 Work exempt from permit, subsection entitled Building, #4 shall be deleted in its

entirety.

Section 105.2 Work exempt from permit, subsection entitled Building, #6 shall be deleted in its

entirety.

Section 105.2 Work exempt from permit, subsection entitled Mechanical, #4 shall be amended to

read as follows:

Steam, hot or chilled water piping within any heating or cooling equipment, used for

production only.

Page 5: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

5

Section 105.3.1 Action on application, shall be amended to read as follows:

The building official, or designee, shall examine or cause to be examined applications for

permits and amendments thereto within a reasonable time after filing. If the application or

the construction documents do not conform to the requirements of pertinent laws, the

building official, or designee, shall reject such application in writing, stating the reasons

therefore. If the building official, or designee, is satisfied that the proposed work conforms

to the requirements of this code, or any other code adopted by the City of Elgin, and laws

and ordinances applicable thereto, the building official, or designee, shall issue a permit

therefore as soon as practicable.

Section 105.7 Placement of permit, shall be amended to read as follows:

A. A true copy of the building permit shall be kept on the site of operations, open to public

inspection during the entire time of prosecution of the work and until the completion

of the same.

B. A placard issued by the code official shall be posted at the site of operations, which

placard shall be posted at an exterior location not more than 100 feet from the lot line

of the subject property nearest to any street or other thoroughfare. Such placard shall

contain the following information:

1. Address of the property for which the permit was issued.

2. The number of the building permit, as provided by the Department of Code

Administration & Development Services.

3. A description of the permit type issued.

4. The date of the permit’s issuance.

5. The name(s) of the permit holder(s) and contractor(s) performing the work

authorized in the permit.

6. The signature of the code official.

Section 108.3 Temporary power, shall be amended to read as follows:

The building official, or designee, may authorize the temporary supply and use power in

part of an electric installation before such installation has been fully completed and a final

certificate of completion has been issued. The part of an electric installation covered by

the temporary certificate shall comply with the requirements specified for temporary

lighting, heat or power as set forth in Chapter 16.24 of the Elgin Municipal Code, 1976, as

amended.

Section 109.2 Schedule of permit fees shall be amended to read as follows:

Page 6: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

6

The fee for each plan examination, building permit and inspection shall be paid in

accordance with Chapter 16.48 of the Elgin Municipal Code, 1976, as amended.

Section 110.3.5 Lath or gypsum board inspection, shall be amended to read as follows:

Insulation inspection: After all rough inspections are completed and before drywall or

plaster lath is installed an insulation inspection is required.

Section 110.4 Inspection agencies, shall be deleted in its entirety.

Section 110.5 Inspection requests, shall be amended to read as follows:

It shall be the duty of the holder of the building permit or their duly authorized agent to

notify the building official when work is ready for inspection at least 24 hours prior to the

inspection request time. It shall be the duty of the permit holder to provide access to and

means for inspection of such work for any inspections that are required by the code.

Section 111.1 Use and occupancy, shall be amended to read as follows:

A building, structure or tenant space shall not be used or occupied, and a change in existing

use or occupancy classification of a building, structure or tenant space or portion thereof

shall not be made, until the building official has issued a certificate of occupancy thereof

as provided herein. The certificate of occupancy shall be posted in a visible area in the

building, structure or tenant space. Issuance of a certificate of occupancy shall not be

construed as an approval of a violation of the provisions of this code or of other ordinances

of the jurisdiction.

Exception: Certificate of occupancy are not required for work exempt from permits in

accordance with Section 105.2.

Section 111.1.1 entitled Certificate of Re-occupancy, shall be created to be located immediately

following section 111.1, and to read as follows:

Certificate of Re-occupancy. Any person seeking to establish an occupancy in an existing

building or any portion thereof shall be required to obtain a Certificate of Re-occupancy.

Every Certificate of Re-occupancy shall state that the new occupancy complies with all

applicable provisions of the Elgin Municipal Code, 1976, as amended, including the

Building Code, Existing Building Code, Plumbing Code, Heating, Ventilating and

Mechanical Code, Fire Prevention Code and zoning ordinance and that all building systems

are operational.

Section 111.3 Temporary occupancy, shall be amended to read as follows:

The building official may issue a temporary certificate of occupancy before the completion

of the entire work covered by the permit provided that the portion or portions of the

building or structure that are to be occupied meet all health and safety standards and

Page 7: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

7

requirements. The building official shall issue a letter stating the time period in which all

required work is to be completed and such letter shall be signed by the permit holder or his

or her authorized representative. The letter shall contain specific dates for the completion

of each outstanding item. The failure to complete each outstanding item by the specified

date shall result in the revocation of the certificate of occupancy and the vacation of the

building or structure within 24 hours.

Section 111.5 Partial occupancy, shall be created to read as follows:

The building official is authorized to issue a partial occupancy for the installation of

machines, equipment, furniture, or other items required before the commencement of

business. The portion of the building or structure that is to be occupied must meet all health

and safety standards and requirements.

Section 113.1 General shall be amended to read as follows:

In order to hear and decide appeals of orders, decisions or determination made by the

building official relative to the application and interpretation of this code, there shall be

and is hereby created a board of appeals. The board of appeals shall consist of the Building

Commission members and shall hold office at its pleasure. The board shall adopt rules of

procedure for conducting its business.

Section 113.3 Qualifications, shall be deleted in its entirety.

Section 114.4 Violation penalties, shall be amended to read as follows:

Any person who violates a provision of this code or fails to comply with any of the

requirements thereof or who erects, constructs, alters or repairs a building or structure in

violation of the approved construction documents or directive of the building official, or of

a permit or certificate issued under the provisions or the code, shall be subject to penalties

as prescribed by Chapter 1.20 of the Elgin Municipal Code, 1976, as amended.

Section 115.2 Issuance, shall be amended to read as follows:

The stop work order shall be in writing and shall be posted on the property where the

violation exists. All persons working in the building or structure at that time of the posting

of the stop work order shall be notified that the stop work order was posted. Upon issuance

of a stop work order, the cited work shall immediately cease. The stop work order shall

state the reasons for the issuance of the order.

Section 310.5 Residential Group R-3, shall be amended to read as follows:

Residential Group R-3 shall include all buildings arranged for occupancy as one or two

family dwelling units and multiple single family dwellings where each unit has an

independent means of egress and is separated by an approved two-hour rated fire

separation assembly. Residential Group R-3 shall further include residential occupancies

Page 8: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

8

where the occupants are primarily permanent in nature and not classified as group R-1, R-

2, R-4 or I, including: Buildings that do not contain more than two dwelling units;

Boarding houses (nontransient) with 16 or fewer occupants;

Boarding houses (transient) with 10 or fewer occupants;

Care facilities that provide accommodations for five or fewer persons receiving

care;

Congregate living facilities (nontransient) with 16 or fewer occupants;

Congregate living facilities (transient) with 10 or fewer occupants.

Section 406.3.1 Classification, shall be amended to read as follows:

Private garages and carports shall be classified as Group U occupancies. Each private

garage shall not be greater than 1,000 square feet (93 m2) in area. Multiple private garages

are permitted in a building where each private garage is separated from the other private

garages by 1-hour fire barriers in accordance with Section 707, or 1-hour horizontal

assemblies in accordance with Section 711, or both. In a multi-family building, if the

building is not fire-sprinklered, a heat detection system shall be installed in the garage

areas.

Section 406.3.4.1 Dwelling unit separation, shall be amended to read as follows:

The private garage shall be separated from the residence and its attic as follows:

The wall(s) separating the garage from habitable areas of the house shall have one layer

of 5/8” fire code type gypsum board on both sides of the wall(s) or equivalent. Where

a gable type connection is used, the same construction shall be utilized as that

separating the garage from the adjacent habitable space. When the garage ceiling is to

be finished to separate the garage from the attic space, two (2) layers of 5/8” fire code

type gypsum board or equivalent shall be installed. The second layer of gypsum board

shall be positioned perpendicular to the first layer. All joints shall be taped and

spackled. Where habitable rooms are constructed over the garage, all walls shall have

one layer of 5/8” fire code type gypsum board or equivalent applied and the ceiling will

have two layers 5/8” fire code type gypsum board or equivalent. The door opening

between the garage and the residence shall have a minimum fire rating of 20 minutes

and be equipped with a closer.

Section 406.3.4.3 Ducts, shall be amended as follows:

Ducts in a private garage and ducts penetrating the walls or ceiling/floors separating

the dwelling unit from the garage shall be constructed of a minimum no.26 gage sheet

Page 9: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

9

steel and have no openings into the garage. Ducts in the garage shall be enclosed with

5/8” fire code type gypsum board or equivalent.

Section 407.2.6 Nursing home cooking facilities, subparagraphs 7 and 8, shall be amended to read

as follows:

7. A commercial cooking hood installed and constructed in accordance with Section 506

of the International Mechanical Code 2015, as amended by Chapter 16.32 of the Elgin

Municipal Code, as amended, is provided over the cooktop or range.

8. The commercial cooking hood provided over the cooktop or range shall be equipped

with an automatic fire-extinguishing system of a type recognized for protection of

commercial cooking equipment. Pre-engineered automatic extinguishing systems shall

be tested in accordance with UL300A and listed and labelled for the intended

application. The system shall be installed in accordance with this code, its listing and

the manufacturer’s instruction.

Section 501.2 Address identification, shall be amended to read as follows:

New and existing buildings shall be provided with approved Arabic address numbers or

letters. Each character shall be not less than 5 inches (127.5 mm) in height and not less than

0.5 inch (12.7 mm) in width. They shall be installed on a contrasting background and be

plainly visible from the street or road fronting the property. When required by the code

official, address numbers shall be provided in additional approved locations to facilitate

emergency response. Where access is by means of a private road and the building address

cannot be viewed from the public way, a monument, pole or other approved sign or means

shall be used to identify the structure. Address numbers shall be maintained.

Table 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE, shall be

amended such that a reference to footnote “d” shall be added to all “OCCUPANCY

CLASSIFICATIONS” in the NS (non-sprinklered rows) of each occupancy classification entry.

In addition, a reference to new footnote “i” shall be added to all “OCCUPANCY

CLASSIFICATIONS” in the NS (non-sprinklered rows) of each occupancy classification entry.

Table 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE, shall be

amended to add a new Footnote “i,” which shall read as follows:

i. Refer to amended sections 903.2.01 through 903.2.9.1 for fire sprinkler requirements.

Table 506.2 ALLOWABLE AREA FACTOR IN SQUARE FEET, shall be amended such that a

reference footnote “d” shall be added to all “OCCUPANCY CLASSIFICATIONS” in the NS

(non-sprinklered rows) of each occupancy classification entry. In addition, a reference to new

footnote “i” shall be added to all “OCCUPANCY CLASSIFICATIONS” in the NS (non-

sprinklered rows) of each occupancy classification entry.

Page 10: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

10

Table 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE, shall be

amended to add a new Footnote “i,” which shall read as follows:

i. Refer to amended Sections 903.2.01 through 903.2.9.1 for fire sprinkler requirements.

Section 506.2.3 Single-occupancy, multi-story buildings, Paragraph Sa shall be amended to read

as follows:

Sa = Actual number of building stories above grade plane, not to exceed three. For

buildings equipped throughout with an automatic sprinkler system installed in accordance

with Section 903.3.1.1, use the actual number of stories above grade plane, not to exceed

four.

Section 506.2.4 Mixed-occupancy, multi-story buildings, Exception shall be amended to read as

follows:

For buildings designed as separated occupancies under Section 508.4 and equipped

throughout with an automatic sprinkler system installed in accordance with Section

903.3.1.1, the total building area shall be such that the aggregate sum of the ratios of the

actual areas of each story divided by the allowable area of such stories determined in

accordance with Equation 5-3 based on the applicable provisions of Section 508.1, shall

not exceed four.

Section 507.3 Non-sprinklered, one-story buildings, shall be amended to read as follows:

The area of a Group F-2 or S-2 building no more than one story in height shall be limited

to 7,500 square feet per Sections 903.2.4 and 903.2.10 amended.

Section 507.14 Subdivision of existing unlimited area building, shall be created to read as follows:

Subdivision of Existing Unlimited Area Buildings. Lawfully existing unlimited area

buildings divided by new lot lines are not required to comply with the setback regulations

set forth in this section provided each of the following requirements is met:

1. A fire separation rating at the lot line dividing the building shall have a minimum fire-

resistance rating of 3 hours.

2. The existing building complied with all requirements for unlimited area building

regulations prior to the subdivision.

3. Building areas being subdivided must be of the same use group.

4. Any addition or alteration of any portion of a building shall comply with all

requirements for an unlimited area building.

Page 11: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

11

Table 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS

(HOURS), shall be amended to add a reference to new footnote g to TYPE IIA, TYPE IIIA and

TYPE VA construction types.

Table 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS

(HOURS), shall be amended to add a new footnote “g,” which shall read as follows:

g. An approved automatic sprinkler system in accordance with Section 903.3.1.1 shall be

allowed to be substituted for 1-hour fire-resistance-rated construction, provided such

system is not otherwise required by other provisions of the code or used for an allowable

area increase in accordance with Table 506.2 or an allowable height increase in accordance

with Tables 504.3 and 504.4. The 1-hour substitution for the fire resistance of exterior walls

shall not be permitted.

Section 603.1 Allowable materials, subparagraph 1.4 shall be created to read as follows:

Such applications as approved by the Building Official and the Fire Code Official.

Section 603.1.2 Piping, shall be amended to read as follows:

The use of combustible piping materials shall be permitted when installed in accordance

with the limitations of the International Mechanical Code 2015 as amended by Chapter

16.32 of the Elgin Municipal Code, 1976, as amended, and the state of Illinois Plumbing

Code as amended by Chapter 16.20 of the Elgin Municipal Code, 1976, as amended.

Section 603.1.3 Electrical, shall be amended to read as follows:

The use of electrical wiring methods with combustible insulation, tubing, raceways, and

related components shall be permitted when installed in accordance with the limitations of

the NFPA 70 National Electrical Code 2014 Edition as amended by Chapter 16.24 of the

Elgin Municipal Code, 1976, as amended.

Section 703.7 Marking and identification, shall be amended to read as follows:

Fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other

wall required to have protected openings or penetrations shall be effectively and

permanently identified with signs or stenciling. Such identification shall:

1. Be located in accessible concealed floors, floor-ceiling or attic spaces;

2. Be repeated at intervals not exceeding 30 feet (914 mm) measured horizontally along

the wall or partition, and

3. Including lettering not less than 2 inches (50.8 mm) in height, incorporating the

suggested wording: “FIRE AND/OR SMOKE BARRIER–PROTECT ALL

OPENINGS,” or other wording.

Page 12: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

12

Exception: Walls in Group R-2 occupancies that do not have a removable decorative

ceiling allowing access to the concealed space.

Section 704.9 Impact protection, shall be amended to read as follows:

Where the fire protective covering of a structural member is subject to impact damage from

moving vehicles, the handling of merchandise or other activity, the fire protective covering

shall be protected by corner guards or by a substantial jacket of metal or other

noncombustible material to a height of 8 feet (2438 mm) from the finished floor, or to the

ceiling, whichever is lower. Exception: Corner protection is not required on concrete columns in open or enclosed parking garages.

Section 708.1 General, shall be amended to read as follows:

The following wall assemblies shall comply with this section:

1. Separation walls as required by Section 420.2 for Groups I-1, R-1, R-2, R-3 and R-4.

2. Walls separating sleeping units in occupancies in Group R-1 hotel occupancies, R-2

and I-1.

3. Walls separating tenant spaces and as required by Section 402.4.2.1

4. Corridor walls as required by Section 1012.1.

5. Elevator lobby separation as required by Section 3006.2.

6. Egress balconies as required by Section 1019.2.

Section 716.5.01 Hold open devices, shall be created to be located immediately following section

7.16.5, and to read as follows:

Combination heat and smoke actuated hold open devices, when used, shall be installed on

both sides of the wall, interconnected so that the operation of any single device will permit

the door to close. Combination smoke and heat detectors shall be installed at the door

opening and at the ceiling in conformance with NFPA 80, as listed in Appendix A unless

otherwise approved by the building official.

Section 901.8 Pump and riser room size, shall be amended to read as follows:

Fire pump and automatic sprinkler system riser rooms shall be designed with adequate

space for all equipment necessary for the installation, as defined by the manufacturer, with

sufficient working room around stationary equipment. Clearances around equipment to

elements of permanent construction, including other installed equipment and appliances,

Page 13: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

13

shall be sufficient to allow inspection, service, repair or replacement without removing

such elements of permanent construction or disabling the function of a required fire-

resistance-rated assembly. Fire pump and automatic sprinkler system riser rooms shall be

provided with an exterior door large enough to allow removal of the largest piece of

equipment.

Section 901.8.1 Pump and riser room separation, shall be created to be located immediately

following section 901.8, and to read as follows:

A minimum 1-hour fire-rated separation shall be provided for all fire pump and sprinkler

riser rooms.

Section 903.2.01 Automatic sprinkler system, shall be created to be located immediately following

section 903.2, and to read as follows:

An approved automatic sprinkler system shall be installed in every building more than four

(4) stories in height, or where the floor of the upper most story is fifty (50) feet or more

above the lowest level of fire department vehicle access. For the purposes of this section,

basements shall be included as stories. An approved automatic sprinkler system shall be

installed in buildings less than five (5) stories in height as provided in this chapter.

Section 903.2.1.1 Group A-1, shall be amended to read as follows:

1. Use Group A-1. An approved automatic fire suppression system shall be provided

throughout the entire building in all buildings with Use Group A-1 occupancies.

Section 903.2.1.2 Group A-2, shall be amended to read as follows:

Where a Use Group A-2 fire area comprises more than 3000 square feet in area, or is

located either above or below the level of exit discharge of exits that serve the Use Group

A-2 fire area, an approved automatic fire suppression system shall be provided as follows:

1. Throughout the entire story or floor level where the A-2 use Group is located;

2. Throughout all stories and floor levels below the A-2 Use Group; and

3. Throughout all intervening stories and floor levels between the A-2 Use Group and the

level of exit discharge of exits that serve the Use Group A-2 fire area, including the

level of exit discharge.

Section 903.2.1.3 Group A-3, shall be amended to read as follows:

Where a Use Group area exceeds 5000 square feet in area, or is located either above or

below the level of exit discharge of exits that serve the Use Group A-3 fire area, an

approved automatic fire suppression system shall be provided as follows:

Page 14: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

14

1. Throughout the entire story or floor level where the A-3 Use Group is located;

2. Throughout all stories and floor levels below the A-3 Use Group; and

3. Throughout all intervening stories and floor levels below the A-3 Use Group and the

level of exit discharge of exits that serve the Use Group A-3 fire area, including the

level of exit discharge.

Section 903.2.1.4 Group A-4, shall be amended to read as follows:

Where a Use GroupA-4 fire area exceeds 5000 square feet in area or is located either above

or below the level of exit discharge of exits that serve the Use Group A-4 fire area, an

approved automatic fire suppression system shall be required as follows:

1. Throughout the entire story or floor level where the A-4 Use Group is located;

2. Throughout all stories and floor levels below the A-4 Use Group; and

3. Throughout all intervening stories and floor levels below the A-4 Use Group and the

level of exit discharge of exits that serve the Use Group A-4 fire area, including the

level of exit discharge.

Section 903.2.2.1 Group B, shall be created to be located immediately following section 903.2.2,

and to read as follows:

In all buildings with a Use Group B fire area, an approved automatic fire suppression

system shall be provided as follows:

1. Throughout all buildings with a Use Group B fire area having more than 7500 square

feet in area; or

2. In buildings with two (2) stories when the combined total area of the two (2) floors

exceeds 10,000 square feet; or

3. In buildings of three (3) or more stories regardless of the square footage of each floor.

Section 903.2.3 Group E, shall be amended to read as follows:

Where a Use Group E fire area exceeds 5000 square feet in area, or is located either above

or below the level of exit discharge of exits that serve the Use Group E fire area, an

approved automatic fire suppression system shall be provided as follows:

1. Throughout the entire story or floor level where the E Use Group is located;

2. Throughout all stories and floor levels below the E Use Group; and

Page 15: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

15

3. Throughout all intervening stories and floor levels below the E Use Group and the level

of exit discharge of exits that serve the Use Group E fire area, including the level of

exit discharge.

Section 903.2.4 Group F-1, shall be amended to read as follows:

In all buildings with a Use Group F-1 and F-2 fire areas, an approved automatic fire

suppression system shall be provided as follows:

1. Throughout all buildings with a Use Group F-1 or F-2 fire area having more than 7500

square feet in area;

2. In buildings with two (2) stories if the combined total area of two (2) floors exceed

10,000 square feet;

3. In buildings with three (3) or more stories regardless of the square footage of each floor;

or

4. In buildings with a Group F-1 occupancy used for the manufacture of upholstered

furniture or mattresses which exceeds 2,500 square feet.

Section 903.2.6 Group I, shall be amended to delete Exception #3.

Section 903.2.7 Groups M, shall be amended to read as follows:

In all buildings with a Use Group M fire area, an approved automatic fire suppression

system shall be provided as follows:

1. Throughout all buildings with a Use Group M fire area having more than 7500 square

feet in area;

2. In buildings with two (2) stories if the combined total area of two (2) floors exceed

10,000 square feet;

3. In buildings with three (3) or more stories regardless of the square footage of each floor;

or

4. In buildings with a Group M occupancy used for the display and sale of upholstered

furniture or mattresses which exceeds 5,000 square feet.

Section 903.2.8.1 Group R-3, shall be amended to read as follows:

Where a one- and two-family dwelling and/or a townhouse is to be located upon land that

was located within the City of Elgin as of the adoption date of this ordinance, such one-

and two-family dwelling shall include fire sprinkler protection in the basement area only.

Page 16: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

16

This fire sprinkler system can be part of the domestic water system, without backflow

prevention, as long as the system is a looped system with no dead-ends in excess of 2 feet.

Exceptions:

1. When wood I-joists or open web trusses are used and protected with a ½-inch gypsum

wallboard membrane, 5/8-inch wood structural membrane, or equivalent on the

underside of the floor framing member.

2. Wood floor assemblies using dimensional lumber or structural composite lumber equal

to or greater than 2-inch by 10-inch nominal dimension, or other approved floor

assemblies demonstrating equivalent fire protection.

3. An automatic residential fire sprinkler system shall not be required when additions or

alterations are made to existing one- and two-family dwellings that do not have an

automatic residential fire sprinkler system installed.

4. Factory applied “Flac Jacket” to the wood I-joist is an approved alternate as required

by #1 or #2 above with the following notation:

(If the wood I-joist with Flak Jacket protection has been exposed to temperatures

sufficient to activate the coating, the product should no longer be used as the structural

capacity and fire endurance may have been compromised. In such a case, an evaluation

report from a licensed architect or structural engineer will be required to determine

appropriate repairs).

In all such instances above, the general contractor shall be responsible for ensuring that the

homeowner is advised of the availability and benefits of a full automatic fire sprinkler

system (NFPA 13D compliant). Such notification shall be on a form provided by the City

of Elgin and include the printed name and signature of the homeowner.

Where a one- and two-family dwelling is to be located upon land annexed to the City of

Elgin after the adoption date of this ordinance, a full fire sprinkler system shall be required,

installed in accordance with NFPA 13D. This system shall include backflow protection by

use of a double check valve.

Section 903.2.9, Group S-1, shall be amended to read as follows:

In all buildings with a Use Group S-1 fire area, an approved automatic fire suppression

system shall be provided as follows:

1. Throughout all buildings with a Use Group S-1 fire area having more than 7500 square

feet in area;

2. In buildings with two (2) stories if the combined total area of two (2) floors exceed

10,000 square feet;

Page 17: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

17

3. In buildings with three (3) or more stories regardless of the square footage of each floor;

or

4. In buildings with a Group S-1 occupancy used for the storage of upholstered furniture

or mattresses which exceeds 2,500 square feet.

Section 903.2.9.1 Repair garages, subparagraph no. 2 shall be amended to read as follows:

One-story buildings with a fire area containing a repair garage exceeding 7500 square feet.

Section 903.2.10, Group S-2, shall be amended to read as follows:

In all buildings with a Use Group S-2 fire area, an approved automatic fire suppression

system shall be provided as follows:

1. Throughout all buildings with a Use Group S-2 fire area having more than 7,500 square

feet in area;

2. In buildings with two (2) stories if the combined total area of two (2) floors exceed

10,000 square feet; or

3. In buildings with three (3) or more stories regardless of square footage of each floor.

An automatic sprinkler system shall be provided throughout buildings classified as

enclosed parking garages in accordance with Section 406.4 or where located beneath other

groups.

Exception: Enclosed parking garages located beneath Group R-3 occupancies as applicable

in Section 101.2.

Section 903.3.5 Water supplies, shall be amended to read as follows:

Water supplies for automatic sprinkler systems shall comply with this section and the

standards referenced in Section 903.3.1. The potable water supply shall be protected

against backflow in accordance with the requirements of this section and the State of

Illinois Plumbing Code, as amended by Chapter 16.20 of the Elgin Municipal Code, 1976,

as amended. Hydrant water flow data used for the design of any sprinkler system shall be

no more than 1 year old. A minimum 10% safety factor shall be provided in the fire

protection system hydraulic calculations. On each design drawing, provide a copy of the

hydraulic nameplate for each hydraulically calculated area.

Section 903.3.5.1 Domestic services, shall be amended to read as follows:

A domestic service shall not provide the water supply for the automatic sprinkler system.

Page 18: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

18

Exception: Single water supply and combination systems may be utilized in conjunction

with a residential fire sprinkler system as part of a looped system where such a system is

permitted under applicable provisions of Chapter 16.36 of the Elgin Municipal Code, 1976,

as amended.

Section 903.3.8.1 Number of sprinklers, shall be amended to read as follows:

Limited area sprinkler systems shall not exceed twenty sprinklers in any single fire area.

Section 903.4.2 Alarms, shall be amended to read as follows:

An approved audible device, located on the exterior of the building in an approved location,

shall be connected to each automatic sprinkler system. In addition, alarm indicating

appliance audio/visual devices shall be seen and heard within all areas of the building. Such

sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow

of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm

system is installed, actuation of the automatic sprinkler system shall activate the building

fire alarm system. Where automatic fire sprinklers provide protection to an area with an

approved flow switch interconnected to the fire alarm system, a white strobe shall be

installed at each multi- sprinkler riser.

Section 903.4.2.1 Test Valves, shall be created to be located immediately following section

903.4.2, and to read as follows:

Fire sprinkler system inspector’s test valves shall be accessible at all times and located no

more than 6 feet above finished floor. On multiple riser systems, test valves shall be marked

as to which riser and area it tests.

Section 903.4.3 Floor control valves, shall be amended to read as follows:

Approved supervised indicating control valves shall be provided at the point of connection

to the riser on each floor of all multiple story buildings.

Section 904.13 Domestic cooking systems in Group I-2 Condition 1, shall be amended to read as

follows:

In Group I-2 Condition 1, occupancies where cooking facilities are installed in accordance

with Section 407.2.6 of this code, the commercial cooking hood provided over the cooktop

or range shall be equipped with an automatic fire-extinguishing system of the type

recognized for protection of the domestic cooking equipment. Preengineered automatic

extinguishing systems shall be tested in accordance with UL 300A and listed and labelled

for the intended application. The system shall be installed in accordance with this code, its

listing and the manufacturer’s instructions.

Section 905.3.1 Height, shall be amended to read as follows:

Page 19: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

19

Class III standpipe systems shall be installed throughout buildings where the floor level of

the highest story is more than 2 stories and/or 26 feet above the lowest level of fire

department vehicle ground access, or where the floor level of the lowest story is more than

2 stories and/or 26 feet below the highest level of fire department vehicle ground access.

Section 905.3.9 Storage warehouses, shall be created to read as follows:

In all warehouse storage areas exceeding 50,000 square feet or where storage exceeds 12

feet high, interior 2 ½” fire hose valves with a 1 ½” reducer to a 1 ½” hose connection shall

be provided. Valves shall be located at each exterior door to the warehouse and/or storage

area. The location of all obstructions and/or rack storage shall be shown on any plans.

Where the system pressure exceeds 100 psi, a “Potter” reduced pressure adjustable type

valve shall be provided.

Section 907.1.4 Control/annunciator panels, shall be created to read as follows:

All fire alarm control panels or full function annunciator panels shall be installed within 10

feet of the building main entrance, sprinkler room, or in a location approved by the fire

code official.

Section 907.2.01, entitled Fire Alarm Application, shall be created to be located immediately

following section 907.2, and to read as follows:

Notwithstanding other provisions within this Section 907.2, fire alarm systems shall be

installed in all buildings or tenant spaces of 2,500 square feet or more where automatic fire

sprinkler systems are not installed.

Section 907.2.7 Group M, shall be amended to read as follows:

A manual fire alarm system that activates the occupant notification system in accordance

with Section 907.5 shall be installed in Group M occupancies where one of the following

conditions exists:

1. The combined Group M occupant load of all floors is 500 or more persons.

2. The Group M occupant load is more than 100 persons above or below the lowest

level of exit discharge.

Multi-tenant Use Group M buildings will be “ring/alert by tenant,” activated by the fire

pull station/automatic fire detection, and shall include a weatherproof clear outside strobe

over the entrance to each tenant space as directed by the fire code official. All outside

strobes to be a minimum 75 candela.

Exceptions:

1. A manual fire alarm system is not required in covered or open mall buildings

Page 20: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

20

complying with Section 402.

2. A manual fire alarm box shall be required in all buildings when equipped with a fire

alarms system and automatic fire sprinkler system.

Section 907.3.1 Duct smoke detectors, shall be amended to read as follows:

Duct smoke detectors shall be connected to the building’s fire alarm control panel when a

fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible

and audible supervisory signal at a constantly attended location. Duct smoke detectors

shall not be used as a substitute for required open-area detection. Duct smoke detectors

shall be located as provided in Sections 606.2.1, 606.2.2, 606.2.3 and 606.3 of the

International Mechanical Code 2012 as amended by Chapter 16.32 of the Elgin Municipal

Code, 1976, as amended.

The Exceptions to section 907.3.1 shall remain without amendment.

Section 912.1.1 Connection type, shall be created to be located immediately following section

912.1, and to read as follows:

All fire department connections shall be a NST 4” Storz connection with a 30 degree

downturn (Storz type only).

Section 913.1.1 Test outlet valves, shall be created to be located immediately following section

913.1, and to read as follows:

An OS & Y control valve shall be provided on all fire pump test headers.

Section 1015.2 Where required, shall read as follows:

Guards shall be located along open-sided walking surfaces, including mezzanines,

equipment platforms, stairways, ramps and landings which are located more than 30 inches

(762mm) measured vertically to the floor or grade below at any point within 36 inches (914

mm) horizontally to the edge of the open side. Guards shall be adequate in strength and

attachment in accordance with Section 1607.8. Guards shall be located along glazed sides

of stairways, ramps and landings that are located more than 30 inches (762 mm) above the

floor or grade below where the glazing provided does not meet the strength and attachment

requirements in Section 1607.8.

Where retaining walls with differences in grade level on either side of the wall in excess of

30 inches (762mm) are located closer than 2 feet (610mm) to walk, path, parking lot or

driveway on the high side, such retaining walls shall be provided with guards that are

constructed in accordance with this section.

Exception: Guards are not required for the following locations:

Page 21: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

21

1. On the loading side of loading docks or piers.

2. On the audience side of stages and raised platforms, including steps leading up to

the stage and raised platforms.

3. On raised stage and platform floor areas such as runways, ramps and side stages

used for entertainment or presentations.

4. At vertical openings in the performance area of stages and platforms.

5. At elevated walking surfaces appurtenant to stages and platforms for access to

utilization of special lighting or equipment.

6. Along vehicle service pits not accessible to the public.

7. In assembly seating where guards in accordance with Section 1028.14 are permitted

and provided.

Section 1015.8 Windows openings, shall be amended to read as follows:

In Occupancy Groups R-2 and R-3 and multiple-family dwellings, where the opening of

the sill portion of an operable window is located more than 72 inches above the finished

grade or other surfaces below, the lowest part of the clear opening of the window shall be

at a height not less than 36 inches above the finished floor surface of the room in which the

window is located. Operable sections of windows shall not permit openings that allow the

passage of a 4-inch-diameter sphere where such openings are located with 36 inches of the

finished floor.

Exceptions:

1. Operable windows where the sill portion of the opening is located more than 75 feet

above the finished grade or other surface below and that are provided with window fall

prevention devices that comply with ASTM F 2006.

2. Windows whose openings will not allow a 4-inch-diameter sphere to pass through the

opening when the window is in its largest opened position.

3. Openings that are provided with window fall prevention devices that comply with

ASTM F 2090.

4. Windows that are provided with window opening control devices that comply with

Section 1013.8.1.

Section 1030.2.1 Minimum dimensions, shall be amended to add the following exceptions:

Page 22: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

22

Exceptions: The minimum net clear opening height of windows below grade shall be 36

inches (914mm). The minimum net clear opening width of windows below grade shall be

24 inches (610mm).

Chapter 11 Accessibility, shall be deleted in its entirety.

Section 1206.3.3 Court drainage, shall be amended to read as follows:

The bottom of every court shall be properly graded and drained to a public storm sewer or

other approved disposal system.

Section 1209.2 Attic spaces, shall be amended to read as follows:

An opening not less than 22 inches by 30 inches (559mm by 762 mm) shall be provided to

any attic area having a clear height of over 30 inches (762 mm). A minimum 30-inch (762

mm) clear headroom in the attic space shall be provided at or above the access opening.

Attic access doors and hatches shall have a mechanical latching device such that the door

will not open unless the latch is physically or manually released. Such doors and hatches

shall be operable from occupant side and achieve a fire-resistance-rating not less than the

assembly being penetrated. The access shall be in a readily accessible location. When

mechanical equipment is located in attics the requirements of Chapter 16.32 of this title

shall apply.

Exception: Doors and hatches that are hinged shall have latches operable from occupant

and non-occupant sides.

Chapter 13 Energy Efficiency, shall be deleted in its entirety.

Section 1404.2 Water-resistive barrier, shall be amended to read as follows:

Asphalt saturated felt free from holes and breaks, weighing not less than 15 pounds per 100

square feet and complying with ASTM D 226 or other approved weather resistant material

shall be applied over studs or sheathing of all exterior walls, with flashing as described in

Section 1405.4, as required. Such felt or material shall be applied horizontally, with the

upper layer lapped over the lower layer not less than two (2) inches. Where vertical joints

occur, material shall overlap not less than six (6) inches.

Exception: Such felt or material is permitted to be omitted in the following situations:

1. In detached accessory buildings unless aluminum or vinyl exterior siding is used.

2. Under paper-backed stucco lath.

Section 1507.2 Asphalt shingles, shall be amended to read as follows:

Page 23: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

23

The installation of asphalt shingles shall comply with the provisions of this section. The

use of staples for attachment of asphalt shingles is prohibited.

Section 1510.6.01 Screening of mechanical equipment, shall be created to be located immediately

following section 1510.6, and to read as follows:

All rooftop mechanical equipment, on buildings 30 feet (9.15 m) or less in height,

extending more than 36" (913 mm) above the roof, including but not limited to heating, air

conditioning, ventilating or other mechanical equipment, shall be screened or enclosed in

a manner which masks the equipment from view at a distance twice the height of the

building at finished grade elevation.

Construction of the screening or enclosure shall comply with the provisions of the building

code, and shall be of the same character and design as the building.

A building permit shall not be issued for any building unless the screening or enclosure is

included on plans submitted with the building permit application.

Section 1603.1.1.1 Live loads posted, shall be created to be located immediately following section

1603.1.1, and to read as follows:

Where the live loads for which each floor or portion thereof of a commercial or industrial

building is designed to exceed 50 pounds per square foot (2.40 kN/m2), such design live

loads shall be conspicuously posted by the owner at all entrances to all applicable portions

of each story. Signs used for such posting shall be made durable by laminating, framing

or engraving in plastic. The print on such signs shall consist of uppercase letters, be in a

contrasting color and have a font size of at least size 20 points. The code official shall

approve each sign before it is installed. It shall be unlawful to remove or deface such

notices.

Section 1607.12.5 Photovoltaic panel systems, shall be amended to read as follows:

Roof structures that provide support for photovoltaic panel systems shall be designed in

accordance with Sections 1607.12.5.1 through 1607.12.5.4, as applicable. In addition, the

photovoltaic panel system layout shall be designed to allow for a minimum 36” access aisle

to all roof mounted equipment and skylights/vents as well as a 36” access clearance around

the equipment and skylights/vents.

Section 1807.1.4 Permanent wood foundation systems, shall be deleted in its entirety.

Section 1808.10 Horizontal reinforcement, shall be created to read as follows:

Concrete walls shall be reinforced by four (4) number five rods. Two (2) of the number

five rods shall be located twelve (12) inches from the bottom of the wall and the remaining

two (2) number five rods shall be located twelve (12) inches below the top of the wall.

Page 24: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

24

TABLE 2304.8(3) shall be amended to read as follows:

ALLOWABLE SPANS AND LOADS FOR WOOD STRUCTURAL PANEL

SHEATHING AND SINGLE-FLOOR GRADES CONTINUOUS OVER TWO OR MORE

SPANS WITH STRENGTH AXIS PERPENDICULAR TO SUPPORTS

(Plywood Structural panels are to be marked as a 4/5 rating)a, b

SHEATHING GRADES ROOFc FLOORd

Panel span

rating

roof/floor span

Panel

thickness

(inches)

Maximum span

(inches)

Loade (psf)

Maximum

span (inches)

With edge supportf

Without edge

supportf

Total load

Live load

16\0 5/8 16 16 50 40 0

20\0 5/8 20 20 50 40 0

24\0 5/8 24 20g 50 40 16

24\16 5/8 24 24 50 40 16

32\16 5/8 24 24 50 40 16h

40\20 5/8, 3/4, 7/8 40 32 40 30 24h,i

48\24 21/32, 3/4, 7/8 48 36 45 35 32

54\32 7/8, 1 54 40 45 35 32

60\32 1,1 1/8 60 48 45 35 32

SINGLE FLOOR GRADES ROOFc

FLOORd

Panel span

rating

Panel

thickness (inches)

Maximum span

(inches)

Loade (psf)

Maximum

span (inches)

With edge supportf

Without edge

supportf

Total load

Live load

16 oc 5/8 24 24 50 40 16h

20 oc 5/8, 3/4 24 24 50 40 20h,i

24 oc 23/32, 3/4 48 36 35 25 24

Page 25: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

25

32 oc 7/8, 1 48 40 50 40 32

48 oc 1 3/32, 1 1/8 60 48 50 40 48

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m2.

a. Applies to panels 24 inches or wider.

b. Floor and roof sheathing conforming with this table shall be deemed to meet the design

criteria of Section 2304.7.

c. Uniform load deflection limitations 1/180 of span under live load plus dead load, 1/240

under live load only.

d. Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking unless 1/4 inch minimum thickness underlayment or 1 1/2 inches of approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/4 inch wood strip. Allowable uniform load based on deflection of 1/360 of span is 100 pounds per square floor (psf) except the span rating of 48 inches on center is based on a total load of 65 psf.

e. Allowable load at maximum span.

f. Tongue-and-groove edges, panel edge clips (one midway between each support, except

two equally spaced between supports 48 inches on center), lumber blocking, or other. Only lumber blocking shall satisfy blocked diaphragms requirements.

g. For ½ inch panel, maximum span shall be 24 inches.

h. Span is permitted to be 24 inches on center where ¾ inch wood strip flooring is installed

at right angles to joist.

i. Is permitted to be 24 inches on center for floors where 1½ inches of cellular or lightweight

concrete is applied over the panels.

Table 2304.8(5) shall be amended to read as follows:

ALLOWABLE LOAD (PSF) FOR STRUCTURAL PANEL ROOF

SHEATHING CONTINUOUS OVER TWO OR MORE SPANS

AND STRENGTH AXIS PARALLEL TO SUPPORTS

(Plywood structural panels are five-ply, five-layer unless otherwise noted)a, b

PANEL GRADE THICKNESS

(INCH)

MAXIMUM

SPAN (inches)d

LOAD AT MAXIMUM SPAN (psf)

Structural I Sheathing

Live

Total

5/8 24 70 80

23/32, 3/4 24 90 100

Page 26: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

26

Sheathing, other grades covered in DOC PS 1or DOC

PS 2

5/8 16 45c 55c

5/8 24 45c 55c

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479kN/m2.

a. Roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.

b. Uniform load deflection limitations: 1/180 of span under live load plus dead load 1/240

under live load only. Edges shall be blocked with lumber of other approved type of edge supports.

c. For composite and four-ply plywood structural panel, load shall be reduced by 15 pounds

per square foot.

d. On spans 16” or greater panel edge clips (one midway between each support, except two equally spaced between supports 48 inches on center), lumber blocking, or other. Only lumber blocking shall satisfy blocked diaphragms requirements.

Chapter 27 Electrical, shall be deleted in its entirety. The provisions of NFPA 70 National Electric

Code 2014 Edition as amended by Chapter 16.24 of the Elgin Municipal Code, 1976 as amended,

shall apply to the installation of electrical systems, including alteration, repairs, replacement,

equipment, appliances, fixtures, fittings and appurtenances thereto.

Chapter 28 Mechanical Systems, shall be deleted in its entirety. The provisions of the International

Mechanical Code 2015, as amended by Chapter 16.32 of the Elgin Municipal Code, 1976, as

amended, shall apply to the installation, alterations, repairs, and replacement of mechanical

systems, including equipment, appliances, fixtures, fittings and/or appurtenances, including

ventilating, heating, cooling, air-conditioning and refrigeration systems, incinerators, and other

energy related systems.

Chapter 29 Plumbing Systems, shall be deleted in its entirety. The provisions of the Illinois State

Plumbing Code as amended by Chapter 16.20 of the Elgin Municipal Code, 1976, as amended,

shall apply to the installation, alteration, repairs and replacement to the plumbing system, including

equipment, appliances, fixtures, fittings and appurtenances, and where connected to a water or

sewage system. The provisions of the 77 Illinois Administrative Code Chapter I: Department of

Public Health Subchapter Part 905 et seq., as amended shall apply to private sewage disposal

systems.

Section 3002.4 Elevator car to accommodate ambulance stretcher, shall be amended to read as

follows:

In buildings three or more stories in height, at least one elevator shall be provided for fire

department emergency access to all floors. Such elevator car shall be of such a size and

arrangement to accommodate a 24-inch by 84-inch (610 mm by 2134 mm) ambulance

stretcher in the horizontal, open position and shall be identified by the international symbol

for emergency medical services (star of life). The symbol shall not be less than 3 inches

Page 27: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

27

(76 mm) high and shall be placed inside on both sides of the hoistway door frame.

Section 3103.1 General, shall be amended to read as follows:

The provisions of this section shall apply to tents, membrane structures and other structures

erected for a period of less than 30 days or as herein described. Those erected for a longer

period of time shall comply with Section 3102 of this chapter or with all applicable sections

of this chapter where Section 3102 is not applicable. The code official may issue a permit

for temporary construction. Such permit shall be limited as to time of service, but such

temporary construction shall not be permitted for more than 6 months. Tents, air supported

structures and other temporary structures may be erected for a period not exceeding thirty

(30) days for educational, recreational, or similar purposes. Temporary tents may be

erected for a period not exceeding fifteen (15) days for other purposes upon written

application to the building official. Said application shall be made not later than thirty (30)

days prior to the commencement of use of said tent.

Exception: Open-sided tents shall be exempt from the provisions of this section.

Section 3303.4 Vacant lot, shall be amended to read as follows:

Where a structure has been demolished or removed the vacant lot shall be filled with clean

fill to within four (4) inches of finished grade and maintained to the existing grade with

black dirt. Existing grade will match the adjacent lots with provisions for proper drainage.

Section 3303.6 Utility connections, shall be amended to read as follows:

All utilities, including sewer and water, shall be terminated in accordance with the City of

Elgin Utility Disconnection/Termination Policy and at the main, unless otherwise approved

by the Public Works Director in writing.

Section 3303.8, Maintenance of lot, shall be created to read as follows:

Property which will remain vacant for a period of more than six months shall be seeded or

planted with ground cover and the resulting growth maintained.

Section 3303.9 Demolition, shall be created to read as follows:

Where a building, structure or portion thereof has been demolished and a building permit

for any building reconstruction has not been applied for or approved, the demolition shall

include the removal of all below grade walls, vaults, footings, slabs and foundation walls.

Section 3307.1 Protection required, shall be amended to read as follows:

Adjoining public and private property shall be protected from damage during construction,

remodeling and demolition work. Protection must be provided for footings, foundations,

party walls, chimneys, skylights and roofs. Provisions shall be made to control water runoff

Page 28: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

28

and erosion during construction or demolition activities in accordance with Title 21 of the

Elgin Municipal Code. Erosion control measures shall remain in place until such time that

the associated grounds are stabilized. The person making or causing an excavation to be

made shall provide written notice to the owners of adjoining buildings advising them that

the excavation is to be made and that the adjoining buildings should be protected. Said

notification shall be delivered not less than 10 days prior to the scheduled starting date of

the excavation. Directional signage shall be provided in number, size, location, and content

approved by the building official when deemed necessary by the building official to protect

the general public from construction, remodeling, or demolition work or to provide

advance notification to the general public of changes to pedestrian or vehicular traffic

patterns required to provide same protection.

Appendix A, Employee Qualifications, shall be deleted in its entirety.

Appendix B, Board of Appeals, shall be deleted in its entirety.

Appendix C, Group U-Agricultural Buildings, shall be adopted in its entirety.

Appendix D, Fire Districts, shall be deleted in its entirety.

Appendix E, Supplementary Accessibility Requirements, shall be deleted in its entirety.

Appendix F, Rodent proofing, shall be adopted in its entirety.

Appendix G, Flood-Resistant Construction, shall be adopted in its entirety.

Appendix H, Signs, shall be deleted in its entirety.

Appendix I, Patio Covers, shall be deleted in its entirety.

Appendix J, Grading, shall be deleted in its entirety.

Appendix K, Administrative Provisions, shall be deleted in its entirety.

Appendix L, Earthquake Recording Instrumentation, shall be deleted in its entirety.

Appendix M, Tsunami – Generated Flood Hazard, shall be deleted in its entirety.

16.04.030 SIDEWALKS, APPROACHES AND DRIVEWAYS-WHEN REQUIRED.

A concrete sidewalk and driveway approach, conforming with the specifications established in

Chapter 13.04 of the Elgin Municipal Code, 1976, as amended, shall be required prior to the

issuance of an occupancy permit for any new building or structure that is situated on a lot or plot

of ground which abuts upon any street in the city unless said sidewalk is specifically exempted.

Driveways located on private property must be paved with concrete, masonry pavers or asphalt

prior to the issuance of a permanent occupancy permit.

Page 29: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

29

16.04.040 FENCE INSTALLATION.

A building permit is required prior to the construction or installation of any fence within the city.

Fences shall be constructed or installed according to the regulations established in Title 19 of the

Elgin Municipal Code, 1976, as amended.

16.04.050 ASSESSOR’S RECEIPT.

No certificate of use and occupancy shall be issued until and unless a non-executed certificate of

use and occupancy has been filed with the township assessor or the county assessor of the county

in which the property is located. The owner of such property shall obtain from the assessor, in the

form prescribed by such official, a receipt showing that the non-executed certificate of use and

occupancy has been filed and that the property is subject to increased assessment from the date of

the issuance of the certificate on a proportionate basis for the year in which the improvement was

completed. The owner of the property shall file such receipt with the building official, and a

certified copy of the certificate, when issued, shall be filed with the assessor.

16.04.060 STREET NUMBERS.

A. Required. All lots, buildings and structures within the corporate limits of the city shall be

assigned a street number in accordance with the numbering system established by the

Department of Code Administration and Development Services.

B. Size and Type. Street numbers shall be displayed in a position easily observed and readable

from the public right-of-way. All numbers shall be in Arabic numerals at least 5 inches high.

(3 inch numbers are acceptable on existing buildings if they are easily visible from the

adjoining street or parking lot.)

C. Location.

1. Prior to the start of construction of any structure on vacant land, the assigned street

number shall be posted in a prominent location, visible from the adjoining street.

2. No structure shall be occupied unless the assigned street number is mounted on the

structure next to the front entrance in a prominent location and visible from the

adjoining street. If that location is not readily visible from the adjoining street, the

number shall be placed elsewhere in close proximity to the front entrance where it is

not obstructed.

3. The street number of multiple tenant buildings with common entrances shall be placed

in a prominent location visible from the adjoining street or parking area. Each tenant

space shall have the numbers or letters assigned to that unit posted on the door of that

unit.

Page 30: Ordinance No. G36-18 AN ORDINANCE ADOPTING THE ...

30

16.04.070 CONSTRUCTION OPERATIONS.

Construction or alteration operations shall not be carried on prior to sunrise or after sunset unless

approved in writing by the building official. On Sundays the permitted hours for construction or

alteration shall be from 9 a.m. to 6 p.m.

16.04.080 CONFLICTS WITH OTHER PROVISIONS.

When a provision of this chapter conflicts with any other provision of the Elgin Municipal Code

regulating the same subject matter, either as presently adopted or to be adopted or amended in the

future, the more stringent or restrictive provision shall apply."

Section 3. That all ordinances or parts of ordinances in conflict with the provisions of this

ordinance be and are hereby repealed.

Section 4. That this ordinance shall be in full force and effect immediately after its passage

in the manner provided by law.