+ All Categories
Home > Documents > Out of Step Protection Enhancements

Out of Step Protection Enhancements

Date post: 10-Feb-2018
Category:
Upload: yourou1000
View: 225 times
Download: 0 times
Share this document with a friend
6
7/22/2019 Out of Step Protection Enhancements http://slidepdf.com/reader/full/out-of-step-protection-enhancements 1/6 OUT-OF-STEP PROTECTION ENHANCEMENTS D Hou and D A Tziouvaras Schweitzer Engineering Laboratories, Inc., USA ABSTRACT Power systems are subjected to a wide range of small or larger disturbances during operating conditions and they are designed to survive disturbances caused by faults, loss of a large generator, or line switching. The power system typically adjusts to these disturbances and continues to operate satisfactorily and within the desired bounds of voltage and frequency. Multiple system disturbances, however, could cause loss of synchronism between interconnected power systems that lead to loss of generation and load, and sometimes to wide-area blackouts. To mitigate the effect of these disturbances, it is common practice to provide controls called special protection systems that aid in maintaining system stability. In addition, properly designed power systems include out-of-step (00s) rotection systems that detect loss of angular instability and perform controlled network islanding to preserve stability within smaller networks. In this paper, we describe the application philosophy of s protection systems in transmission systems and discuss recent enhancements in the design of out-of-step tripping (OST) and blocking protection functions that improve the security and reliability of the power system. INTRODUCTlON Power systems in the US ave experienced a number of large disturbances in the last ten years, including the largest blackout, which occurred on August 14, 2003 in the Midwest and Northeast U.S. and impacted millions of customers. The July 2, 1996 and August IO 1996 major system disturhances also impacted several million customers in the Western U.S. All of these disturbances caused considerable loss of generation and loads and had a tremendous impact on customers and the economy in general. Typically, these disturbances happen when the power systems are heavily loaded and a number of multiple outages occur within a short period of time, causing power oscillations between neighboring utility systems, low network voltages, and consequent voltage instability or angular nstability. It is very expensive to design a power system to completely prevent very rare multiple outages and withstand their consequences. To mitigate the effect of these disturbances, it is common practice to provide controls called special protection systems or remedial action schemes. These special protection systems are designed to avoid voltage or angular instability and minimize the effects of a disturbance. Special protection systems include underfrequency and undervoltage load- shedding schemes, direct load and generation tripping, and many other schemes (1). Certain power system disturbances may lead to loss of synchronism between interconnected power systems. If such a loss of synchronism occurs, it is imperative that the system areas operating asynchronously are separated immediately to avoid wide-area blackouts and equipment damage. An effective mitigating way to contain such a disturbance is through controlled islanding of the power system using 00s protection systems. Controlled system separation is achieved with an OST protection system at preselected network locations. OST systems must he complemented with out-of-step blocking (OSB) of distance relay elements, or other relay elements prone to operate during loss of synchronism or unstable power swings. OSB prevents system separation from occurring at any locations other than the preselected ones. This paper illustrates the philosophy and application of OST and OSB schemes. In addition, we discuss the performance requirements of distance relays when faults occur during an 00s condition. While there are many challenges presented to distance relay element5 in correctly detecting faults after issuing an OSB, we selectively present two of them: security against external unbalanced faults, and correct faulted phase selection of internal line faults to trip only the faulted phase instead of all three phases. s PROTECTlON PHILOSOPHY The power system's response to a disturbance depends on both the initial operating state of the system and the severity of the disturbance. A fault on a critical element of the power system, followed by its isolation by protective relays, will cause variations in power flows, network bus voltages, and machine rotor speeds. Depending on the severity of the disturbance and the actions of protective relays and other power system controls, the system may remain stable and return to a new equilibrium state, experiencing what is referred to as a stable power swing. On the other hand, if the system is transiently unstable, then it will cause large separation of generator rotor angles, large swings of power flows, large fluctuations of voltages and currents, and eventually lead to a loss of synchronism between groups of generators or between neighboring utility systems. 2004 Schweitzer Engineering Labs INC. USA. Reproduced with kind permission
Transcript
Page 1: Out of Step Protection Enhancements

7/22/2019 Out of Step Protection Enhancements

http://slidepdf.com/reader/full/out-of-step-protection-enhancements 1/6

OUT-OF-STEP PROTECTION ENHANCEMENTS

D Hou and D A Tziouvaras

Schweitzer Engineering Laboratories, Inc., USA

ABSTRACT

Power systems are subjected to a wide range of small or

larger disturbances during operating conditions and they

are designed to survive disturbances caused by faults,

loss of a large generator, or line switching. The power

system typically adjusts to these disturbances and

continues to operate satisfactorily and within the desired

bounds of voltage and frequency. Multiple system

disturbances, howev er, could cause loss of synchronism

between interconnected power systems that lead to lossof generation and load, and sometimes to wide-area

blackouts. To mitigate the effect of these disturbances, it

is common practice to provide controls called special

protection systems that aid in maintaining system

stability. In addition, properly designed power systems

include out-of-step (00s) rotection systems that detectloss of angular instability and perform controlled

network islanding to preserve stability within smaller

networks. In this paper, we describe the application

philosophy of s protection systems in transmission

systems and discuss recent enhancements in the design

of out-of-step tripping (OST) and blocking protection

functions that improve the security and reliability of thepower system.

INTRODUCTlON

Power systems in the US ave experienced a number

of large disturbances in the last ten years, including the

largest blackout, which occurred on August 14, 2003 in

the Midwest and Northeast U.S. and impacted millions

of customers. The July 2, 1996 and August IO 1996

major system disturhances also impacted several million

customers in the W estern U.S. All of these disturbances

caused considerable loss of generation and loads and

had a tremendous impact on customers and the econom y

in general. Typically, these disturbances happen when

the power systems are heavily loaded and a number of

multiple outages occur within a short period of time,

causing power oscillations between neighboring utility

systems, low network voltages, and consequent voltageinstability or angular nstability.

It is very expensive to design a power system to

completely prevent very rare multiple outages and

withstand their consequences. To mitigate the effect of

these disturbances, it is common practice to provide

controls called special protection systems or remedialaction schemes. These special protection systems are

designed to avoid voltage or angular instability andminimize the effects of a disturbance. Special protection

systems include underfrequency an d u ndervoltage load-

shedding schemes, direct load and generation tripping,

and many other schemes (1).

Certain power system disturbances may lead to loss o f

synchronism between interconnected power systems. If

such a loss of synchronism occurs, it is imperative that

the system areas operating asynchronously are separated

immediately to avoid wide-area blackouts and

equipment damage. An effective mitigating way to

contain such a disturbance is through controlled

islanding of the power system using 00s protection

systems. Controlled system separation is achieved withan OST protection system at preselected network

locations. OST systems must he complemented with

out-of-step blocking (OSB) of distance relay elements,

or other relay elements prone to operate during loss of

synchronism or unstable power swings. OSB prevents

system separation from occurring at an y locations other

than the preselected o nes.

This paper illustrates the philosophy and application of

OST and OSB schemes. In addition, we discuss the

performance requirements of distance relays when faults

occur during a n 00s condition. While there are manychallenges presented to distance relay element5 in

correctly detecting faults after issuing an OSB, we

selectively present two of them: security against

external unbalanced faults, and correct faulted phase

selection of internal line faults to trip only the faulted

phase instead of all three phases.

s PROTECTlON PHILOSOPHY

The power system's response to a disturbance depends

on both the initial operating state of the system and the

severity of the disturbance. A fault on a critical elementof the power system, followed by its isolation by

protective relays, will cause variations in power flows,

network bus voltages, and m achine rotor speeds.

Depending on the severity of the disturbance and the

actions of protective relays and other power system

controls, the system may remain stable and return to anew equilibrium state, experiencing what is referred to

as a stable power swing. On the other hand, if the

system is transiently unstable, then it will cause large

separation of generator rotor angles, large swings ofpower flows, large fluctuations of voltages an d currents,

and eventually lead to a loss of synchronism between

groups of generators or between neighboring utilitysystems.

2004 S chw ei t ze r E ng i nee r ing Labs INC. USA. Rep rod uce d with kind permiss ion

Page 2: Out of Step Protection Enhancements

7/22/2019 Out of Step Protection Enhancements

http://slidepdf.com/reader/full/out-of-step-protection-enhancements 2/6

6

The philosophy of 00s relaying is simple and

straightforward avoid tripping of any power system

elements during stable swings and protect the power

system during unstable or 00s conditions. When twoareas of a power system or two interconnected systems

lose synchronism, the systems must be separated from

each other quickly and automatically in order to avoidequipment damage and shutdown of major portions of

the power system. Uncontrolled tripping of circuit

breakers during an 00s condition could cause

equipment damage and pose a safety concern for utility

personnel. Therefore, a controlled tripping of certain

power system elements is necessary in order to prevent

equipment damage and widespread power outages, andminimize the e ffects of the disturbance.

Effect of s Condit ion on Transmiss ion Line

Relays an d Relay Systems

The loss of synchronism between power systems, or

between a generator and the power system, affects

transmission line relays and systems in various ways.Some relay systems, such a s segregated line differentialrelays, do not respond to an 00s condition. Directional

and nondirectional instantaneous overcurrent and

distance relays may operate during stable or unstable

power swings. Operation of these relays during a power

swing will cause undesired tripping of transmission

lines or other power system elements, thereby

weakening the system and possibly leading to cascading

outages and the shutdown of major portions of the

power system.

Instantaneous -pha se overcurrent relays will operate

during 00s conditions if the line current during the

swing exceeds the minimum pickup setting of the relay.

Likewise, directional instantaneous overcurrent relaysmay operate if the swing current exceeds the minimumpickup setting of the relay and the polarizing and

operating signals have the proper phase relationship

during the swing. Voltage-restrained or voltage-

controlled current relays used for backup protection of

generators are also prone to operate during power

swings or 00s conditions. Time-overcurrent relays

may o r may not operate, depending on the swing current

magnitude and the time delay settings of the relay.

Phase distance relays measure the positive-sequence

impedance for three-phase and two-phase faults. The

impedance measured by distance relays at a line

terminal during an 00s condition varies as a function

of the phase angle separation 6 between the twoequivalent system source voltages 2) . Distance relay

elements will operate during a power swing, stable or

unstable, if the swing locus enters the distance relay

characteristic. Zone distance relay elemen ts with no

intentional time delay are' most pron e to operate during

a power swing. Zone 2 distance relay elements used in

pilot relaying systems, such as blocking or permissive

type relay systems, are also prone to operate during,

power swings. Backup zone step distance relay elements

may or may not operate during a power swing,

.

depending on their time-delay setting and the time ittakes for the swing imped ance locus to traverse through

the relay characteristic.

It is important to recognize that the relationship between

the distance relay polarizing memory and the measured

voltages and currents plays a critical role in whether adistance relay will operate during a power swing.

Another important factor in modem distance relays is

whether the distance relay has a frequency-tracking

algorithm to track system frequency. Relays without

frequency tracking will experience voltage polarization

memory rotation with respect to the measured voltages

and currents. Furthermore, the relative magnitude of the

protected line and the equivalent system source

impedances is another important factor in the

performance of distance relays during power swings. If

the line positive-sequence impedance is large when

compared with the system impedances, the distance

relay elements may not only operate during unstahle

swings but may also operate during swings from which

the power system may recover and remain stable.

s Detect ion Method s and Types of Schemes

A short circuit is an electromagnetic transient process

with a short time constant. The apparent impedance

moves from the prefault value to a fault value in a very

short time (a few milliseconds). On the other hand, a

power swing is an electromechanical transient process

with a time constant much longer than that of a fault.

The rate of change of the positive-sequence impedance

is much slower during a power swing or 00s condition

than during a fault, and it depends on the slip frequency

of the 00s.The fundamental method for discriminating

between faults and power swings is to track the rate of

change of measured apparent impedance, because theimpedance measurement by itself cannot be used to

distinguish an 00s condition from a phase fault.

The difference in the rate of change of the impedance

has been traditionally us+d to detect an 00s condition

and then block the operation of distance protection

elements before the impedance enters the protective

relay operating characteristics. Actual implementation

of measuring the impedance rate of change is normally

performed though the use of two impedance

measurement elements together with a timing device. If

the measured impedance stays between the two

impedance measurement elements for a predetermined

time, then an 00s is declared and an OSB signal is

issued to block the distance relay element operation.

Impedance measurement elements with different shapes

have been used traditionally for the detection of OOS,including double blinders, concentric polygons, and

concentric circles.

To guarantee that there is enough time to cany out

blocking of the distance elements after an 00s is

detected, the inner impedance measurement element of

the 00s detection logic must he placed outside the

largest distance protection region that is to b e blocked.

The outer impedance measurement element for the 00s

Page 3: Out of Step Protection Enhancements

7/22/2019 Out of Step Protection Enhancements

http://slidepdf.com/reader/full/out-of-step-protection-enhancements 3/6

detection has t t b e placed away from the load region to

prevent inadvertent OSB logic operation caused by

heavy loads.

s Tripping a nd Blocking Funct ions

There are basically two functions related to 00sdetection. The first function is the OSB protection

function that discriminates faults from stable or unstable

power swings. The OSB function blocks relay elements

prone to operate during stable and/or unstable power

swings to prevent system separation in an indiscriminate

manner. In addition, the OSB function must unblock

and allow relay elements to operate for internal faults

that occur during an 00s condition.

The second function, the OST protection function,

discriminates between stable and unstable swings and

initiates network sectionalizing or islanding during lossof synchronism. OST schemes are designed to protect

the power system during unstable conditions, isolating

unstable generators or larger power system areas fromeach other with the formation of system islands, in order

to maintain stability within each island by balancing the

generation resources with the area load.

To accomplish this, OST systems must he applied at

preselected network locations, typically near the

network electrical center, and network separation must

take place at such points to preserve a close halance

between load and generation. Where a load-generation

balance cannot be achieved, some means of shedding

nonessential load or generation will have to take place

to avoid a complete shutdown of the area.

As we discussed earlier, many relay systems are prone

to operate at different locations in the power system

during an 00s condition and cause undesired tripping.Therefore, OST systems must he complemented with

OSB functions to prevent undesired relay system

operations, to prevent equipment dam age and shutdown

of major portions of the power system, and to achieve a

controlled system separation.

Typically, the location of OST relay systems determines

the location where system islanding takes place during

loss of synchronism. However, it may be necessary in

some systems to separate the network at a location other

than the one where OST is installed. This is

accomplished with the application of a transfer trippingtype of scheme.

Uncontrolled tripping during 00s conditions can cause

damage to power system breakers due to transientovervoltages that appear across the breaker contacts

when switching a line that contains the electrical center

of a transmission system. The maximum transient

recovery voltage occurs when the relative phase angleof the two systems is 180 during the 00s condition.

To adequately protect the circuit breakers and ensurepersonnel safety, most utilities do not allow

uncontrolled tripping during 00s conditions and

restrict the operation of OST relays when the relative

voltage angle between the two systems is between -90and 90 degrees.

Application of OST and O S B F unc ti ons

While the 00s relaying philosophy is simple, it is often

difficult to implement in a large power system becauseof the complexity o f the system and the different

operating conditions that must he studied. The selection

of network locations for placement of OST systems can

hest he obtained through transient stability studies

covering many possible operating conditions. Themaximum rate of slip is typically estimated from

angular chang e versus time plots from stability studies.

With the above information at hand, reasonable settings

can be calculated for well-designed OST relaying

schemes.

The recommended approach for 00s relaying

application is summarized below:

Perform system transient stability studies to identify

system stability constraints based on many operatingconditions and stressed-system operating scenarios.

The stability studies will help identify the parts ofthe power system that impose limits to angular

stability, generators that are prone to go 00s during

system disturbances, and those that remain stable.

The results of stability studies are also used to

identify the optimal location of OST and OSB

protection relay systems.

Determine the locations of the swing loci during

various system conditions and identify the optimal

locations to implement the OS T protection function.The optimal location for the detection of the 00scondition is near the electrical center of the power

system. However, we must determine that thebehavior of the impedance locus near the electrical

center would facilitate the successful detection o f

00s.

Determine the optimal location for system

separation during an 00s condition. This will

typically depend on the impedance between islands,

the potential to attain a good loadgeneration

balance, and the ability to establish stable operating

areas after separation. High impedance paths

between system areas typically represent appropriate

locations for network separation.

Establish the maximum rate of slip between systems

for 00s timer setting requirements, as well as the

minimum forward and reverse reach settingsrequired for success%l detection of s conditions.

The swing frequency of a particular power system

area or group of generators relative to another power

system area or group of generators does not remain

constant. The dynamic response of generator control

systems, such as automatic voltage regulators, and

the dynamic behavior of loads or other power

system devices, such .as SVCs and FACTS, can

influence the rate of change of the impedance

measured by 00s protection devices.

Page 4: Out of Step Protection Enhancements

7/22/2019 Out of Step Protection Enhancements

http://slidepdf.com/reader/full/out-of-step-protection-enhancements 4/6

For OSB schemes, the 00s logic uses two

concentric polygons: an outer zone and an innerzone. Two factors affect the 00s outer and inner

zones impedance settings: the outermost

overreaching zone of phase distance element you

want to block, and the load impedance the relaymeasures during the maximum anticipated load. The

inner zone must be set to encompass the outermost

overreaching zone of phase distance element you

have selected for OSB. Set the outermost zone suchthat the minimum anticipated load impedance locus

is outside the outermost zone. The 00s block timedelay is set based on the settings of the inner and

outer resistance blinders and the fastest stable swing

frequency.

For OST schemes, the OST inner zone is set at a

point along the 00s swing trajectory beyond which

the power system cannot regain stability. The OSTouter zone is set such that the minimum anticipated

load impedance locus is outside the outermost zone.

The OST time delay is set based on the settings of

the inner and outer zone resistance blinders and the

fastest 0 0 s swing frequency expected or

determined from transient stability studies.

Earlier OST schemes were designed to operate when

the two system angles were greater than 270 degrees

and were moving closer to one another. This trippingis referred to as trip-on-the-way-out (TO WO ).

TOW O has a softer impact on the breakers involved

because the transient recovery voltage that results

from tripping at a smaller angle between the two

systems is more favorable. stability studies in someinterconnected power systems could point out that

waiting to trip until the relative phase ang le .o f the

two systems reaches 270' or more may causeinstability of other areas within each subsystem.

Therefore, if the TOWO technique is deemed to he

too slow, then tripping before the systems reached arelative phase angle of 90°-120 may he desirable.

This is referred to as trip-on-the-way-in (TOW I).

The TOWI technique can prevent severe voltagedips in the power system and potential loss of loads.

TOW1 is also reserved for very large systems whose

angular movement with respect to one another isvery slow and where there is a real danger that

transmission line thermal damage may occur if

tripping is delayed until a more favorable angle

between the two systems is reached. Care should he

exercised in such an application, because the

tripping command to the circuit breakers is issuedwhen the relative phase angles of the two systems is

close to 180 and poses higher circuit breaker OST

duty.

dependability, selectivity, sensitivity, security, and

speed. However, due to the nature of the 00s and the

response of distance relay elements during system OOS,

it is almost impossible to demand and achieve distanceelement performance similar to that under normal

system fault conditions.Many utilities do not have clear performance

requirements for distance relays during system 00sconditions because of the rare occurrence of these

events. We hope that the following discussion will

promote the awareness of distance relay element

response during system 00s and how to use modem

relays to satisfy some of the requirements.

Faul ted Phase Selection

Single-pole tripping is an important method to minimize

the impacts to the power system after it is disturbed by

single-line-to-ground SLG) faults. To ensure that the

power system can he separated in a controlled manner

and that balanced subsystem operations can be achievedduring system OOS, it is extremely important that the

distance relays retain the single-pole tripping capabilityduring system 00s.However, as we shall see below, it

is quite difficult for the distance elements to discern the

faulted phase during system 00s.

IB 6 6 m e4 si

m  n i C i S l

FIGURE I Distance Calcu lations for a BG Fault DuringSystem 00s

The upper plot of FIGURE 1 shows the distance

calculations for A-phase, B-phase, and C-phase

elements for a B-phase-to-ground fault at the end of a

line. The B-phase distance element calculation provides

the correct fault impedance. The distance calculations of

the unfaulted phases move into protection Zone 2 and

Zone 1 regions as the machine 6 approaches 180 . The

lower plot of FIGURE 1 shows the distance calculationsDISTANCE PROTECTION CHALLENGES of the phase elements. All phase distance calculations

DURING SYSTEM s EVENTS move into protection regions as the machine S

amroaches 180 during svstem 00s.. _Ideally, the performance requirements o f protective

relays under system 00s conditions should be identical One microprocessor-based relay the angle

to those under normal system operations in of difference of negative- and zero-sequence currents in its

Page 5: Out of Step Protection Enhancements

7/22/2019 Out of Step Protection Enhancements

http://slidepdf.com/reader/full/out-of-step-protection-enhancements 5/6

faulted-phase selection. For example, when the phase-

angle difference of negative- and zero-seque nce currents

falls into the -60 to 60 region, the fault-type selection

logic asserts FSA, indicating a selection of A-phase.

However, when FSA asserts, it could mean either an

A-phase ground fault or a BC double-phase ground

fault. The distance relay calculates both the A-phase

ground distance and BC-phase distance elements. F0r.a

normal fault without a system OOS, only one of the

distance elements gives an output and allows the relay

to trip correctly. However, as we saw in the previous

B-phase ground fault example during system OOS, even

if the relay correctly selects FSB, it will assert both

B-phase ground and CA-phase distance elements and

issue three-pole permissive and local trip for a SLG

fault.

F IGURE2 shows a patent-pending logic used to

correctly select the faulted phase under the difficult

situation of faults that occur d uring system 00s. t thetime that the relay asserts a phase selection output

during the OSB, the relay latches in correspondingground and phase distance calculations. The relay then

starts to integrate the differences between following

distance calculations and its latched value for both

ground and phase distance elements. If the ground

distance difference integration is less than the difference

integration of the phase distance with a margin, the

relay will declare the fault type as an SLG fault and

allow the ground distance element to generate a single-

pole trip output. Otherwise, the relay will declare a

multiphase fault type and initiate three-pole permissive

and local trips.

FIGURE 2 Fault Phase Selection Logic during Systems

Security Against External Faults

Distance relay element security during 00s for external

faults is traditionally achieved using 3 negative-

sequence overcurrent eleme nt with a coordinating delay

pickup timer to reset the OSB bit. This delay timer

provides sufficient time for the external fault to he

cleared by other responsible relays. FIGURE 3 showsthe logic diagram of a traditional OSB reset scheme.

The logic allows a phase distance element MPP tooperate for forward unbalanced faults detected by a

directional negative-sequence overcurrent (32QF, SOQ)

element after a time delay equal to UBD. The OSBrelay bit comes from the power swing detection logic,

indicating that the distance relay has already detected a

swing condition and blocked the distance elementsund er user-specified conditions.

FIGURE 3 Distance Elements With 00s Block and TimeDelayed S Q Reset

However, the UBD concept may he difficult to apply

when the system swing center moves as a function of

the source voltage magnitudes and the relative line and

source impedances during an .OOS, as FIGURE 4 

shows.

X

FIGURE 4 The Location of 00s Center Is a Function of

Source Voltage M agnitudes

When the system 00s center falls within the line

section between stations R and S, the distance relays onthe line R-S would need a longer UBD than the relayson the line S-T so that they do not overreach for

external faults on the line S-T. However, if the swing

center moves to the line section S-T, then the UBD time

for the relays on this line should he longer than the

relays on the line R-S to achieve the same security for

faults on the line R-S. Therefore, it is difficult to apply

the UBD coordination time when swing center location

changes.

On parallel-line systems shown in FIGURE 5 it is

impossible to use the UBD time to coordinate with

external faults, because a fault internal to one pair of

relays on LI is external to the pair ofr elay s on L2.

67QF: Zone 2 67QR

6 7 QF Zone 27QF one 2

FIGURE Use POTT Scheme to Gain Protection SecurityDuring System 00s

To achieve security for external faults during system

OOS, one possible solution is to not reset the OSB hitfor the Zone 1 distance elements due to potential

Page 6: Out of Step Protection Enhancements

7/22/2019 Out of Step Protection Enhancements

http://slidepdf.com/reader/full/out-of-step-protection-enhancements 6/6

overreach. Instead, we can rely on the Zone 2 elements,

together with a Permissive Overreaching Transfer Trip

(POTT) scheme to gain the security.

For such a POTT scheme implementation, the distance

relays ’ must have two directional negative-sequence

overcurrent elements to reset the OSB for Zone I and

Zone 2 distance elements separately. The directional

negative-sequence overcurrent element that is used to

reset OSB for the Zone I element must have torque

control capability to allow users to disable resetting the

OSB bit for the Zone 1 elements as their application

requires.

Some utilities relax the security requirements for

external faults, recognizing the difficulties in achieving

the same performance achieved during system faults

without 00s. Typical security requirements of a major

utility regarding external faults are:

Distance elements must be secure to external

faults during system OOS, except for externalthree-phase faults

Distance elemen ts may trip on any external faults

if an OOS condition dev elops during a single-

pole open cond ition

Dependabil i ty

Distance elements must trip all internal faults during

system 00s. This requirement tests the relay sensitivity

to detect the negative-sequence current caused by

unbalanced faults during 00s. Sometimes it may be

difficult for the negative-sequence overcurrent element

to pick up and reset the OSB when the fault occurs at

the voltage peak in an 00s cycle. It is also required that

distance relays have an impedance rate-of-change

element to detect possible evolving three-phase faultsduring system OOS because three-phase faults in a

balanced network d o not produce any negative-sequence

currents.

In single-pole tripping applications, the power system

may become unstable after a successful clearing of a

SLG fault and during the pole-open period. In fact, the

lack of security requirements for faults under such

situations dictates that the distance relay reliably detect

the 0 0 s condition during the pole-open state, being

able to discern a fault occurrence, and then reset the

OSB bit dependably to allow the remaining distance

elements to operate.

SpeedTraditionally, negative-sequence overcurrent elements

are used with some time delay to reset the OSB

condition. This time delay is necessary to coordinate

with other protective devices in the event that the fault

is external to th e protected line section. For this reason,

some utilities relax the speed requirement and allow

distance elements to trip with a time delay for faults that

occur during system 00s However, as we discussed

earlier, a coordinating time delay is not necessary with

the proposed POTT scheme.

Selectivity

We showed earlier that all distance fault measurement

loops overreach protection zones simultaneously when

the 00s center falls on the protected line and a

subsequent fault occurs at a large machine 6 angle.

Therefore, it is not always possible for a distance relay

to perform single-pole tripping for SLG faults during

system 00s For this reason, some utilities relax the

security requirement and permit distance elements to

trip three-pole for internal SLG faults during system

00s

CONCLUSIONS ’ r

00s relaying systems prevent uncontrolled tripping of

transmission lines, minimize the extent of the

disturbance, and protect equipment from being

damaged, thus ensuring personnel safety and faster

service restoration.

OST systems should be applied at proper networklocations to separate the network during an OOS event

and create system islands, with balanced generation and

load deman d, that will remain in synchronism.

OST systems must be supplemented with OSB systems

to block relay elements prone to op erate during stable or

unstable power swings.

To preserve the protection security against external

faults during system OOS, block distance Zone 1

elements, use a negative-sequence overcurrent element

to only reset OSB for Zone 2 distance elements, and

rely on a POTT hipping scheme to guarantee thatdistance relays do not ove rreach for external faults.

The faulted phase selection logic ensures that distancerelays correctly identify if a fault is a single-phase or a

multiphase fault, and therefore keep their much-desired

single-pole tripping capability d uring system 00s.

REFERENCES

1. “Wide Area Protection and Emergency Controls”,

IEEE Power System Relaying Committee, 2002

Report, available at http:llwww.pes-psrc.org/  

Kimbark, E. W., Sc.D, Power System Stability,

John Wiley and Sons, Inc., New York, 1950,

Vol 11.

Hou, D., Chen, S., and Turner, S . SEL Application

Guide AG97-13, “SEL-321-5 Relay Out-Of-StepLogic.”

4. Tziouvaras, D. and Hou, D. “Out-of-Step

Protection Fundamentals and Advancements,”

Proceedings of the 30th Annual Western Protective

Relay Conference, Spoka ne, Washington, October

21-23,2003,

2.

3.

Copyight E L 2 3

All rights reserved)

Printed in U SA

2 3 I2 6


Recommended