+ All Categories
Home > Documents > Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these...

Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these...

Date post: 29-Sep-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
36
Supply water temperature (ºF) 70 110 150 190 Outdoor temperature (ºF) 70 60 50 40 30 20 10 0 170 130 90 60 heat source on heat source off 140 this portion of reset line not used target temperature 210 190 ºF Outdoor Reset Control Theory FULL versus PARTIAL reset Conventional boilers must be protected against sustained operation at low water temperatures. If not, they will be damaged by sustained flue gas condensation. The blue line shows partial reset control for a conventional, gas-fired boiler. The supply water temperature is not allowed to go below a target of 140 ºF, regardless of how warm it is outside.
Transcript
Page 1: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Supp

ly wa

ter t

empe

ratu

re (º

F)

70

110

150

190

Outdoor temperature (ºF)70 60 50 40 30 20 10 0

170

130

90

60

heat source on

heat source off

140

this portion of !reset line not used

target temperature

210

190 ºF

Outdoor Reset Control TheoryFULL versus PARTIAL reset

Conventional boilers must be protected against sustained operation at low water temperatures. If not, they will be damaged by sustained flue gas condensation.

The blue line shows partial reset control for a conventional, gas-fired boiler. The supply water temperature is not allowed to go below a target of 140 ºF, regardless of how warm it is outside.

Page 2: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Supp

ly wa

ter t

empe

ratu

re (º

F)

70

110

150

190

Outdoor temperature (ºF)70 60 50 40 30 20 10 0

170

130

90

60

140

target temperature!(boiler outlet)

210

190 ºF

105 ºF

target temperature!(mixing valve outlet)

VENT

combined boiler + mixing reset controller

boiler supply temperature!

sensor

boiler inlet temperature!

sensor

mixed supply temperature!

sensor3-way

motorized mixing valve

conventional boiler

Outdoor Reset Control TheoryFULL and PARTIAL reset in same system

Page 3: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Outdoor Reset Control TheoryCompensation for non-proportional heat loss/gain(parallel shifting)

Tbalance = Tindoor –

Qgain

UA building

70

80

90

100

110

120

70 60 50 40 30 20 10 0 -10

Wat

er s

uppl

y te

mpe

ratu

re (º

F)

Outdoor temperature (ºF)

60

80

60

starting point line

parallelshift

starting point (moves along starting point line)

Tstart =Tinside + R×Tbalance( )

1+ R( )outdoor reset controllers with indoor temperature sensors will automatically parallel shift the reset line based on internal gains or losses.

Page 4: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating
Page 5: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Instantaneous Domestic Water HeatingFrom Thermal Storage Tanks

Page 6: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Starting points:

• Most of these systems use water for thermal storage.

• Nearly all thermally-based renewable heat sources require significant heat storage.

• Solar thermal system• Geothermal heat pump systems• Wood- and pellet-fired boilers

• Even low storage tank temperatures are useful for preheating domestic hot water.

• Keeping all portions of the DHW system outside the thermal storage tank has several benefits.

• Hydronic based instantaneous domestic water heating has been used in thousands of European installations .

• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating.

• Modulating electric tankless water heaters have some distinct advantages in dealing with preheated water.

• Brazed plate stainless steel heat exchangers are readily available and have very fast response times.

Page 7: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

air vent!w/ shut off

valveso

lar co

llector

array

solar!circulation!

station

check!valve

DHW

CW

solar storage tank!(dual coil)

relay

mod

/con

boi

ler

make-up water

AB 3-way !diverter !valve (D1)

A B

(P1)closely spaced tees

outdoor!temperature!

sensor

(P2)

pressure- regulated circulator

space-heating circuits!(highly zoned)

heat source!circulator

!anti-scald!tempering !valve

relay (R1)

manifold valve actuator

thermostat!(1 per zone)

end

switc

h le

ads

3-way!motorized!

mixing!valve!(C2)

end switch leads from actuators

P&TP3

One way to make a solar combisystem...Drawbacks: • Top of thermal storage has to be maintained at suitably high temperature for domestic hot water delivery - reduces collector efficiency.

• Space heating from storage may be significantly limited by capacity of upper internal coil in storage.

Page 8: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Another way to make a solar combisystem...

DHW coil

PRV

All solar circuit piping sloped minimum

1/4" per ft.

sight!glass

static water level

lift

head

AB

3-way!diverter!valve

A B

heat source!circulator!w/ check

storage / drainback tank

air space

air return!tube

differential!temperature!

controller

3-way mixing valve

closely spaced tees

solar!collector!

array

collector!circulator

auxiliary boiler

space heating!distribution!

system

air return tube

cold water

hot water

3-way mixing valve

outside temperature

sensor

Pressurized drainback system w/ internal coil for domestic water heating.

• Passive domestic water preheating• Boiler maintains temperature at top of storage.• Thermal mass of tank buffers space heating load.• Single tank simplicity

• Sourcing the tank may be an issue• Internal coil may be difficult or impossible to service

Page 9: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

!loading!

unitpressurized thermal storage tank

wood-fired boiler

bypa

ss

air vent

temperature sensor well

Wood gasification boiler with heat storage.

Large thermal storage is often used with wood gasification boilers.

Page 10: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

VENT

buffer tank

temperature!sensor

to / from other heating

zones

variable-speed!pressure-regulated!

circulator

outdoor!reset!

controller

low temperature distribution system

water-to-water!heat pump(heating only)

Comp.

cond

ense

r

evap

orat

or

compressor

TXV

geothermal manifolds

earth loop circuits

purging!valves

Geothermal heat pump space heatingwith heat storage.

Page 11: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

make up water

buffer tank

OUTS

IDE

INSI

DE

air to water heat pumpflow switch

pressure regulated!variable speed

circulator

manifold valve

actuators

zoned radiant ceiling panels

outdoor!temperature!

sensor

outdoor!reset controller

antifreeze!protected!

circuit

Air-to-water heat pump with heat storage.

Page 12: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

gas or propane supply

hot water

cold water

premix gas burner

outlet!temperature !

sensor flow sensor

heat exchanger

controller

ASSE 1070 mixing valve

inlet!temperature !

sensor

isolation &!flushing valves

Gas-fired tankless water heaters and preheated water• Many gas-fired tankless water heaters have limited modulation ability.• Most require an inlet temperature at least 20ºF lower than their setpoint as a condition to fire their combustion system.

IF Qthermal ≤ QHTmin THEN burner doesnʼt fire

Where:Qthermal = current thermal load on heater (Btu/hr)f = flow rate through heater (gpm)Tseptoint = desired water outlet temperature leaving heater (ºF)Tin = water inlet temperature to heater (ºF)QHTmin = minimum rate of heat transfer to water (Btu/hr)Qgas = minimum gas input rate to burner (Btu/hr)n = combustion efficiency of burner / heat exchanger (decimal %)

Thermal load on heater:

Minimum heat transfer rate of heater:

Page 13: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Because Qthermal ≤ QHTmin THEN burner doesnʼt fire

Thermal load on heater:

Minimum heat transfer rate of heater:

gas or propane supply

hot water

cold water

premix gas burner

outlet!temperature !

sensor flow sensor

heat exchanger

controller

ASSE 1070 mixing valve

inlet!temperature !

sensor

isolation &!flushing valves

Assume the minimum gas input to a tankless heater is 10,000 Btu/hr, and the combustion efficiency is 90%. Solar preheated water enters the unit at 110 ºF and 0.8 gpm. The setpoint of the heater is 120 ºF. If the controller in the unit operates as described on previous slide, will the burner fire under the stated conditions?

Page 14: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

This works - BUT...

It also lowers the “net” preheating effect supplied by the solar subsystem.

For example: Assume the setpoint of the tankless heater is 120 ºF. Solar preheated water arriving at the tankless heater at 110ºF would have to be mixed down to 100 ºF before entering the heater. Assuming a desired delivery temperature of 120ºF and a cold water temperature of 50 ºF, this 10 ºF mix down decreases the solar supplied portion of the water heating load from 86% to 71%.

One “work around” is to mix down the inlet temperature using a second thermostatic valve.

hot water

cold water

thermostatic MIX DOWN valve!(set 20 ºF lower than setpoint of heater)

preheated

water

Page 15: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

One “work around” is to mix down the inlet temperature using a second thermostatic valve

European product by

Caleffi

Page 16: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Another option is to divert water around the tankless heater if temperature is above a specified setting.

hot water

cold water

electric diverter valve

solar preheated

water

PRV

Page 17: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Thermostatically controlled electric tankless water heaters

Typical “point of use”ETWH 3-6 KW

Typical “whole house”ETWH 10-40 KW

20KW unit

maximum possible water temperature rise always depends on flow rate

Page 18: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

contactor

relay coil contacts

flow switch

electronics (PCB)

overtemp switch

element enclosure

240VAC input

setpoint adjustment

12KW unit, 50Amp / 240VAC

COLD

in

HOT

out

ETWH

hot water

cold water

isolation &!flushing valves

inlet!temperature !

sensor

heating!element

outlet!temperature !

sensor

flow !sensor

controls

240 VAC !electrical supply

PRV

Thermostatically controlled electric tankless water heaters

Page 19: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Amps = KW0.24

Thermostatically controlled electric tankless water heatersElectric tankless water heaters are HIGH AMPERAGE devices.

Minimum 200 Amp breaker panel recommended.

23 KW Requires TWO, 50 amp /240VAC breakers

3.5 KW Requires 15 amp / 240VAC breaker

May be an issue in some older retrofits.

Page 20: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Thermostatically controlled electric tankless water heaters

ETWH

hot water

cold water

isolation &!flushing valves

inlet!temperature !

sensor

heating!element

outlet!temperature !

sensor

flow !sensor

controls

240 VAC !electrical supply

PRV

Thermostatically controlled electric tankless water heaters use a TRIAC to vary the wattage to their heating elements from 0 to 100%.

They can therefor handle situations where preheated water needs a small temperature “boost” without short cycling.

gates for TRIACS

Page 21: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

from heat!

source

to heat!

source

space heating!supply

space heating!return

air vent

temperature!sensor(s)

small circulator

with check valve

flow switch

space heating!supply

ASSE 1017 !anti scald !

mixing valve

hot water

cold water

stainless steel heat exchanger

from storage

return to storage

electric tankless!water heater

space heating!return

HX flushing!valves

Instantaneous DHW subassembly

Page 22: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

flow switch

ASSE 1017 !anti scald !

mixing valve

hot water

cold water

electric tankless!water heater

buffer tank

pressure-regulated!variable speed

circulator

1/2" PEX or PEX-AL-PEX tubing

TRV

flow switch

ASSE 1017 !anti scald !

mixing valve

hot water

cold water

electric tankless!water heater

Instantaneous DHW subassembly• Leverages the thermal mass for stabilizing DHW delivery.

• Brazed plate heat exchanger provides very fast response (1-2 seconds)

• Fully serviceable heat exchanger (unlike an internal coil heat exchanger) Can be cleaned or replaced if necessary.

• Predictable heat exchanger performance

• Very little heated domestic water is stored (reducing potential for Legionella growth).

• Very low wattage circulator needed on primary side of heat exchanger

Page 23: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Instantaneous DHW subassembly

Brazed plate stainless steel heat exchangers are widely available.They have very high ratio of surface area to volume.

Response time to quasi steady state = 1 to 2 seconds

3”x5”

5”x12”

10”x20”

Response time of this subassembly is likely under 5 seconds.(assuming short, insulated piping b/w HX and storage tank)

Page 24: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

<= 10 ºF

domestic water

maximum suggested!approach temperature!

difference

from!storage!

tank

http://flatplateselect.com

Sizing the brazed plate heat exchangerSuggest a maximum approach temperature difference of 10 ºF under max. anticipated water demand, and minimum preheat inlet temperature.

FG5x12-305” wide x12” long -30 plates

Page 25: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

from heat!

source

to heat!

source

space heating!supply

space heating!return

air vent

temperature!sensor(s)

small circulator

with check valve

flow switch

space heating!supply

ASSE 1017 !anti scald !

mixing valve

hot water

cold water

stainless steel heat exchanger

from storage

return to storage

electric tankless!water heater

space heating!return

HX flushing!valves

Instantaneous DHW subassembly

B&G Vario circulator operating at 33 watts yields10 gpm as required to raise 4 gpm of water from 60 to 110 ºF through FG5x12-30 heat exchanger supplied by 120ºF water from thermal storage.

To deliver 60 gallons per day at average draw rate of 2 gpm, this circulator would operate for 30 minutes, and consume 0.0165 KWHR. Operating cost of this circulator would be $0.78 per YEAR.

Page 26: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

hot water

cold water

to / from!space!

heating

internal!circulator

motorized!diverter!valve

stainless steel!brazed plate!

heat exchanger

anti-scald!valve

flow!switch

combi-boiler

Other tankless water heater options

Response time from cold start to near steady state at delivery temperature (20-30 seconds)

combi-boilergas-fired tankless

All gas fired equipment needs gas supply, venting,and electrical connections

Page 27: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

flow switch

stainless steel !heat exchanger

to / from!other loads

HX flushing valves storage tank!(with varying temperature)

hot water

cold water

!mixing valve

electric tankless!water heater

to /

from

hea

t so

urce

(s)

swing check valve

circulator with check valve

circulator with check valve

Instantaneous DHW subassembly piping

NOTE: Check valve required on tank-to-HX circuit to prevent reverse flow during space heating

Page 28: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

thermostatically!controlled ETWH

240 VAC !electrical supply

relay!240 VAC coil!

in junction box

17

4

28

5

39

6

AB

120 VAC

N

storage to!HX circulator

PRV

Contactor inside Eemax EX012240Textra terminal on coil circuit of contactor

Using extra terminal on ETWH contactor to operate circulator

This eliminates the need for the flow switch.

Page 29: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

flow switch

from storage

return to storage

thermostatically controlled!tankless electric!water heater

set for 130 ºF

DHW

cold water

insulated piping

set for max 120 ºF

Add 2nd thermostatic valve if the high limit switch canʼt be set higher than 140 ºF.

Page 30: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Why not just use internal heat exchanger coils?These are all examples of European multi-coil thermal storage tanks.

Page 31: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Why not just use internal heat exchanger coils?• These tanks cost over $4000

• What happens when a pinhole leak develops anywhere inside the tank?

•Internal coils are limited by natural convection heat transfer.

•No one offers tanks like this in North America

• Many European tanks - even if available in North America, may not meet codes (ASME).

Page 32: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

This concept is already being used...

Thermal energy substations in European flats

Page 33: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Parting thoughts... 1. Keep it neat...

Page 34: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Parting thoughts... 2. Recognize opportunity...

Page 35: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Parting thoughts... 3. Donʼt get hung up...

Page 36: Outdoor Reset Control Theory FULL versus PARTIAL reset• It almost always makes sense to use these heat sources to provide domestic hot water, as well as space heating. • Modulating

Thank you for attending today’s session...

www.hydronicpros.com

Please visit our website for more information (publications & software) on hydronic systems:

Thanks also to the planning committee, and the sponsors of this session.

"Best Practices in Modern Hydronic Heating - THE DETAILS


Recommended