+ All Categories
Home > Documents > Ozone Treatment of Cooling Tower Water

Ozone Treatment of Cooling Tower Water

Date post: 02-Jun-2018
Category:
Upload: lh-koo
View: 221 times
Download: 0 times
Share this document with a friend

of 26

Transcript
  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    1/26

    OZONE TREATMENT

    OF

    COOLING TOWER WATER

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    2/26

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    3/26

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    4/26

    Cooling Tower Stats

    45MW Two Stage Oxygen Compressor

    325m3/hr Circulation Rate

    102m3

    Basin Volume

    2 Heat Exchangers in Parallel

    Cooling Oxygen from 125C to below 30C

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    5/26

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    6/26

    Cooling Tower Trial Objectives

    Reduce water consumption

    Improve Heat transfer efficiency

    Stop Chemical Treatment

    Improve quality of Blow Down Water

    Ultimately save on power and operating

    costs

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    7/26

    |

    Flow diagramm of a typical cooling water

    treatment system with ozone

    Basin

    Power Supply

    Unit incl. PLC

    Cooling TowerOzone-

    Generator

    Feedgas Options:

    Liquid Oxygen, Dry Air

    VSA Oxygen

    O3

    Blow Down

    : Optional dosing points

    Make-upWater

    Ozone Monitoring

    Circulation Pump

    Heat ExchangerO3

    O3

    O3

    Side stream

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    8/26

    Cooling Tower Problems

    Biological counts and fouling

    Corrosion

    Scale formation/Increased powerconsumption

    Chemical handling Water consumption

    Blowdown water disposal

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    9/26

    Water Quality before ozone treatmentMake Up Basin Make Up Basin

    31-Mar 31-Mar 10-Jul 10-Jul

    Conductivity

    (mS/m @25'c) 240 86 16 44

    pH 7.8 8.1 7.8 8.2

    TSS

    (mg/l @105'C)

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    10/26

    Heat Exchanger Efficiency

    Hot

    gas

    Cooled

    gas

    Cold

    Water

    Heated

    WaterMonitor

    Difference

    H E h Effi i

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    11/26

    Heat Exchanger Efficiency

    0

    2

    4

    6

    8

    10

    12

    14

    16

    7/1

    015

    7/1

    113

    7/1

    117

    7/1

    211

    7/1

    215

    7/1

    311

    7/1

    315

    7/1

    411

    7/1

    415

    7/1

    511

    7/1

    515

    7/1

    611

    7/1

    615

    Date

    DeltaTem

    p

    17/07/2006 B f O

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    12/26

    17/07/2006 Before Ozone

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    13/26

    20/07/2006 After Ozone

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    14/26

    17/07/2006

    Before Ozone

    20/07/2006

    After Ozone

    H t E h Effi i

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    15/26

    Heat Exchanger Efficiency

    0

    2

    4

    6

    8

    10

    12

    14

    16

    7/10

    15

    7/11

    17

    7/12

    15

    7/13

    15

    7/14

    15

    7/15

    15

    7/16

    15

    7/17

    11

    7/18

    11

    7/19

    11

    7/20

    11

    7/21

    13

    7/22

    11

    7/23

    11

    7/24

    11

    7/25

    11

    7/26

    11

    7/27

    11

    7/28

    10

    Date

    DeltaTemp

    Water Quality after ozone treatment

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    16/26

    Water Quality after ozone treatmentMake Up Basin Make Up Basin

    14-Aug 14-Aug 15-Aug 15-Aug

    Conductivity

    (mS/m @25'c) 244 651 242 615

    pH 7.4 8.2 9.7 8.7

    TSS

    (mg/l @105'C) 18 46 26 10

    TDS

    (mg/l @180'c) 144 4106 1420 4018

    Total Alkalinity(CaCO3) 132 211 255 278

    Total Hardness

    (CaCO3) 202 636 84 507

    Ca Hardness

    (mg/l) 141 444 34 150

    Mg Hardness

    (mg/l) 61 192 50 157

    Cl (mg/l) 278 950 199 780

    Na (mg/l) 351 1084 435 1233

    Fe (mg/l) 0.39

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    17/26

    Water Quality after ozone treatment

    0

    2

    4

    6

    8

    10

    12

    Hours

    pH

    0

    2000

    4000

    6000

    8000

    10000

    12000

    14000

    C

    onductivity

    (uS/cm

    )

    Make-up Water pH Basin pH

    Make-up Water Conductivity Basin Conductivity

    Water Quality after ozone treatment

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    18/26

    Water Quality after ozone treatment

    Difference Between Wet Bulb and Basin water Temperatures

    0

    2

    4

    6

    8

    10

    12

    14

    1 3 5 7 9

    1

    1

    1

    3

    1

    5

    1

    7

    1

    9

    2

    1

    2

    3

    2

    5

    2

    7

    2

    9

    3

    1

    3

    3

    3

    5

    3

    7

    3

    9

    4

    1

    4

    3

    4

    5

    4

    7

    4

    9

    5

    1

    5

    3

    5

    5

    5

    7

    5

    9

    6

    1

    6

    3

    6

    5

    6

    7

    6

    9

    7

    1

    7

    3

    7

    5

    7

    7

    7

    9

    8

    1

    8

    3

    8

    5

    Hours

    w et dif f Linear (w et dif f)

    Saturation Index

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    19/26

    Saturation Index

    1) P1 = log 10 (calcium * 2.5 * total alkalinity)

    2) P2 = (max. system water temp,F * 0.00912) + P1

    3) P3 = ((log 10 (conductivity * 0.8) * 0.1) + 12.27

    4) pH saturation = P3 P2

    5) SI = pH of cycled water - pH saturation

    Inserting values from latest analysis gives a value of 2.18

    POSI Number

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    20/26

    POSI Number

    Maximumum conductivity :

    = 10 (1/(log(CaxMg)/(Na+Cl)]xlog(Alk/10) x cond(mu)

    (Practical Ozone Scaling Index)

    Using this formula = 3.74 cycles of concentration

    Current cycles of concentration = 4.82

    Cycles of concentration

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    21/26

    Cycles of concentration

    0.00

    1.00

    2.00

    3.00

    4.00

    5.00

    6.00

    31-Mar 10-Jul 19-Jul 25-Jul 8-Aug 14-Aug 15-Aug 22-Aug

    Cl Na Ca Cond

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    22/26

    Ozone Consumption

    inCooling Towers

    0.3 to 0.6 g O3/ m3 in the total recirculation flow

    For average cooling tower of 1500m3

    recirculation flow= 216kg Oxygen consumption per day per tower

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    23/26

    Expected Results per Ave. Tower

    Current Expected Savings

    Tower Volume (m3) 650.00 650.00 0.00

    Recirculation Rate (m3/hr) 1,500.00 1,500.00 0.00

    Evaporation Loss (m3/hr) 9.90 9.90 0.00

    Drift Loss (m3/hr) 1.50 1.50 0.00

    Blow Down Rate (m3/hr) 4.38 0.60 3.78

    Make Up Water (m3/hr) 15.78 12.00 3.78

    Concentration Ratio 4.38 20.00

    Cost of Make up water (R/month) 23,859.53 18,114.00 5,745.53

    Cost of Treatment (R/month) 7,385.00 9,536.00 -2,151.00

    Total Costs (R/Month) 31,244.53 27,650.00 3,594.53

    TOTAL Savings (R/month) 3,594.53

    Advantages of ozone

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    24/26

    Advantages of ozone

    treatment Excellent cooling water quality, e.g. very good

    visibili ty depths

    Long term protection against bio-fouling Reduction of colony forming units

    Effective control of Bacteria Legionella

    Improved heat transfer

    Reduced waste water costs because COD and AOX are

    clearly under the discharge limits Corrosion rates < 0.1 mm/y (carbon steel)

    Improved industrial safety due to no storage, and

    handling of hazardous chemicals

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    25/26

    Thank youThank you

  • 8/10/2019 Ozone Treatment of Cooling Tower Water

    26/26

    tell me moretell me morewww.airproducts.com