DEEP SEA ELECTRONICS PLC P123 DSE Load Share Lines Interface DESCRIPTION The advent of electronic load share controllers has in some cases meant that existing control systems require expensive updates if additional generating sets are added into the system. This is because many of the ‘newer’ controllers utilise proprietary communication links rather than the traditional analogue load share lines (often called Parallel Lines) used in existing systems. The DSE 5510 load sharing controller utilises the MultiSet Communications (M.S.C.) link to enable load sharing between other 5510 equipped generators as well as providing other advanced functionality not available with load share lines. The P123 Load Share Lines Interface is designed to allow the DSE 5510 load sharing controller to interface with analogue load share lines on existing systems without the need to replace the existing controls. The P123 monitors the load share lines and converts this into digital information. This data is then used by the onboard microprocessor to allow the P123 to drive its own load share lines and to communicate on the M.S.C. link with the host DSE 5510 controller. When DC power is applied to the module, the status LED will illuminate. If the P123 cannot communicate to the host 5510 controller using the M.S.C. link, the status LED begins flashing to indicate “Link Lost”. CONFIGURATION To allow connection to the load sharing lines of a wide variety of manufacturers, the P123 interface is selector switch configurable as detailed below. Ensure the P123 selector switches are correctly positioned before connecting to the load share lines. Table of switch positions for common types of load share lines Type P123 switch position kW share settings Var share settings A B C D E F Barber Colman 6 4 2 0 0 0 Deif* 0 1 8 0 1 8 Selco 2 2 8 0 0 0 Woodward 6 8 1 0 0 0 NOTE:- Switch locations shown opposite. NOTE:- * Deif includes VAr share lines. NOTE:- Operation of the P123 cannot be determined if switch combinations other than those listed above are chosen. NOTE:- When using analogue load sharing lines, some additional external equipment may be required to complete the synchronising and load sharing system. 053-004 Issue 1 AM 26/09/05 SPECIFICATION DC SUPPLY: 8V DC to 33V DC MAX. CURRENT (operating and standby): 150mA @ 12V DC, 80mA @ 24V DC. DIMENSIONS: 160.5mm x 77.5mm x 76mm (6.32” x 3.05” x 2.99”) DIN Rail mounted housing. OPERATING TEMPERATURE RANGE: -30 o C to +70 o C INDICATIONS: Status LED: LED lit steady - OK LED flashing - M.S.C. Link lost SWITCH LOCATION: A B C D E F In line with our policy of continual improvement, DSE reserve the right to change the specification without prior notice.
Transcript
Page 1: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

DEEP SEA ELECTRONICS PLC

P123DSE Load Share

L ines In te r faceDESCRIPT ION

The advent of electronic load share controllers has in some cases meant that existing control systems require expensive updates if additional generating sets are added into the system. This is because many of the ‘newer’ controllers utilise proprietary communication links rather than the traditional analogue load share lines (often called Parallel Lines) used in existing systems. The DSE 5510 load sharing controller utilises the MultiSet Communications (M.S.C.) link to enable load sharing between other 5510 equipped generators as well as providing other advanced functionality not available with load share lines. The P123 Load Share Lines Interface is designed to allow the DSE 5510 load sharing controller to interface with analogue load share lines on existing systems without the need to replace the existing controls. The P123 monitors the load share lines and converts this into digital information. This data is then used by the onboard microprocessor to allow the P123 to drive its own load share lines and to communicate on the M.S.C. link with the host DSE 5510 controller. When DC power is applied to the module, the status LED will illuminate. If the P123 cannot communicate to the host 5510 controller using the M.S.C. link, the status LED begins flashing to indicate “Link Lost”. CONFIGURATION

To allow connection to the load sharing lines of a wide variety of manufacturers, the P123 interface is selector switch configurable as detailed below. Ensure the P123 selector switches are correctly positioned before connecting to the load share lines. Table of switch positions for common types of load share lines Type P123 switch position kW share settings Var share settings A B C D E F Barber Colman 6 4 2 0 0 0 Deif* 0 1 8 0 1 8 Selco 2 2 8 0 0 0 Woodward 6 8 1 0 0 0

NOTE:- Switch locations shown opposite.

NOTE:- * Deif includes VAr share lines.

NOTE:- Operation of the P123 cannot be determined if switch combinations other than those listed above are chosen.

NOTE:- When using analogue load sharing lines, some additional external equipment may be required to complete the synchronising and load sharing system.

053-004 Issue 1

AM 26/09/05

SPECIF ICATION DC SUPPLY: 8V DC to 33V DC MAX. CURRENT (operating and standby): 150mA @ 12V DC, 80mA @ 24V DC. DIMENSIONS: 160.5mm x 77.5mm x 76mm (6.32” x 3.05” x 2.99”) DIN Rail mounted housing. OPERATING TEMPERATURE RANGE: -30oC to +70oC INDICATIONS: Status LED: LED lit steady - OK LED flashing - M.S.C. Link lost

SWITCH LOCATION:

A

B

C

D

E

F

In line with our policy of continual improvement, DSE reserve the right to change the specification without prior notice.

Page 2: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

CASE D IMENSIONS

Deep Sea Electronics Plc. Highfield House, Hunmanby Industrial Estate, North

Yorkshire. YO14 0PH. ENGLAND Tel +44 (0)1723 890099.

Fax +44 (0)1723 893303. LoCALL (uk only) Tel 0845 260 8900 LoCALL (uk only) Fax 0845 260 8901

Email: [email protected] Web: www.deepseaplc.com

Deep Sea Electronics Inc. 3230 Williams Avenue

Rockford, IL 61101-2668. U.S.A. Tel +1 (815) 316-8706 Fax +1 (815) 316-8708

TOLL FREE (USA only) Tel.1 866 636 9703

Email: [email protected] Web: www.deepseausa.com

TYPICAL WIRI NG D IAGRAM

Page 3: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC

DSE123 Load Share Lines Interface

Page 4: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

2 057-003 P123 load share lines interface manual ADM 25/07/07 ISSUE 1.1

Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail: [email protected] Website: www.deepseaplc.com

DSE123 Load Share Lines Interface © Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

Page 5: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

057-003 P123 load share lines interface manual TM 25/07/07 ISSUE 1.1 3

TABLE OF CONTENTS

1� INTRODUCTION .............................................................................................. 4�2� CONNECTION DESCRIPTION ........................................................................ 5�3� SETTINGS ........................................................................................................ 6�INDICATIONS ......................................................................................................... 7�

3.1� TYPICAL WIRING DIAGRAM ............................................................................................. 8�

4� CASE DIMENSIONS ........................................................................................ 9�5� SPECIFICATION ............................................................................................ 10�

Page 6: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

4 057-003 P123 load share lines interface manual ADM 25/07/07 ISSUE 1.1

1 INTRODUCTION The advent of electronic load share controllers has in some cases meant that existing control systems require expensive updates if additional generating sets are added into the system. This is because many of the ‘newer’ controllers utilise proprietary communication links rather than the traditional analogue load share lines (often called Parallel Lines) used in existing systems. The DSE 5510 load sharing controller utilises it’s MultiSet Communications (M.S.C.) link to enable load sharing between other 5510 equipped generators as well as providing other advanced functionality not available with load share lines. The P123 Load Share Lines Interface is designed to allow the DSE 5510 load sharing controller to interface with analogue load share lines on existing systems without the need to replace the existing controls. As the MSC datalink is not used in applications of this type, enhanced features provided by this link are not available. The P123 monitors the load share lines and converts this into digital information. This data is then used by the onboard microprocessor to allow the P123 to drive it’s own load share lines and to communicate on the M.S.C. link with it’s host DSE 5510 controller. When DC power is applied to the module, the status LED will illuminate. If the P123 cannot communicate to the host 5510 controller using the M.S.C. link, the status LED begins flashing to indicate “Link Lost”.

Page 7: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

057-003 P123 load share lines interface manual TM 25/07/07 ISSUE 1.1 5

2 CONNECTION DESCRIPTION Terminal Recommended

cable size Description

1 1.0mm² Battery negative connection 2 1.0mm² Battery positive connection (8V-35V DC) 3 Twisted pair 120:

screened communications cable

For connection to the MSC link terminal L of the host 55xx series controller

4 Twisted pair 120: screened communications cable

For connection to the MSC link terminal H of the host 55xx series controller

5 For connection to the MSC link screen of the host 55xx series controller

6 Screen KW load share line Screen 7 1.0mm² KW load share line negative (-ve) 8 1.0mm² KW load share line positive (+ve) 9 - Not connected 10 Screen VAr share line Screen 11 1.0mm² VAr share line negative (-ve) 12 1.0mm² VAr share line positive (+ve)

Page 8: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

6 057-003 P123 load share lines interface manual ADM 25/07/07 ISSUE 1.1

3 SETTINGS To allow connection to the load sharing lines of a wide variety of manufacturers, the P123 interface is selector switch configurable as detailed below. Ensure the P123 selector switches are correctly positioned before connecting to the load share lines.

NOTE:- * Deif includes VAr share lines.

NOTE:- If you do not intend to connect to the VAr share lines, the setting of D,E and F is not important. A suggestion is to set them all to position 1.

NOTE:- Operation of the P123 cannot be determined if switch combinations other than those listed above are chosen.

NOTE:- When using analogue load sharing lines, some additional external equipment may be required to complete the synchronising and load sharing system.

NOTE : Setting D E F to zero will disable the VAr share output. Do not set them to zero if you connect to the VAr share lines.

NOTE : If you have the DSE 5510 connected to the AVR for voltage matching, but don’t intend to connect VAr share lines to the P123 device, ensure D=1, E=1, F=1.

Table of switch positions for common types of load share lines

Type P123 switch positions kW settings VAr settings A B C D E F

Barber Colman 6 4 2 x x x Deif* 0 1 8 0 1 8 Selco 2 2 8 x x x

Woodward 6 8 1 x x x

A

B

C

D

E

F

Page 9: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

057-003 P123 load share lines interface manual TM 25/07/07 ISSUE 1.1 7

INDICATIONS A single LED is provided to indicate the status of the P123 module. Led operation Description Lit Operation is normal. Flashing The module is powered up but no activity is

detected on the MSC Link Unlit The module is not powered up.

Status LED

Page 10: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

8 057-003 P123 load share lines interface manual ADM 25/07/07 ISSUE 1.1

3.1 TYPICAL WIRING DIAGRAM

Page 11: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

057-003 P123 load share lines interface manual TM 25/07/07 ISSUE 1.1 9

4 CASE DIMENSIONS 160.5mm x 77.5mm x 76mm (6.32” x 3.05” x 2.99”)

Page 12: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

P123 Load Share Lines Interface

10 057-003 P123 load share lines interface manual ADM 25/07/07 ISSUE 1.1

5 SPECIFICATION DC Supply 8V - 35 DC continuous Cranking dropouts Able to survive 0 V for 50mS, providing supply was

at least 10 V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries.

Max. current (operating and standby)

150mA @ 12V DC, 80mA @ 24V DC.

Dimensions 160.5mm x 77.5mm x 76mm (6.32” x 3.05” x 2.99”)

Mounting DIN Rail mounted housing. Electromagnetic compatibility BS EN 50081-2 EMC Generic Emission Standard

(Industrial) BS EN 50082-2 EMC Generic Immunity Standard (Industrial)

Electrical safety BS EN 60950 Safety of I.T. equipment, including electrical business equipment.

Cold temperature BS EN 60068-2-1 to -30 oC Hot temperature BS EN 60068-2-2 to +70oC Humidity BS2011-2-1 to 93% RH @ 40qC for 48 Hours Vibration BS EN60068-2-6

10 sweeps at 1 octave/minute in each of 3 major axes. 5Hz to 8Hz @ +/-7.5mm constant displacement 8Hz to 500Hz @ 2gn constant acceleration

Shock BS EN 60068-2-27 3 Half sine shocks in each of 3 major axes 15gn amplitude, 11mS duration

Page 13: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

DSE123ANALOGUE LOAD SHARE LINES INTERFACE

DSEGenset

®

SPECIFICATION

DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous

CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropoutand supply recovers to 5 V. This isachieved without the need for internalbatteries. LEDs and backlight will not bemaintained during cranking.

MAXIMUM OPERATING CURRENT150 mA at 12 V, 80 mA at 24 V

MAXIMUM STANDBY CURRENT150 mA at 12 V, 80 mA at 24 V

DIMENSIONSOVERALL161 mm x 78 mm x 76 mm6.3” x 3.1” x 3.0”

MOUNTINGDIN Rail

OPERATING TEMPERATURE RANGE-30°C to +70°C

STORAGE TEMPERATURE RANGE-40°C to +80°C

RELATED MATERIALSTITLE PART NO’SDSE5510 Data Sheet 055-039DSE5510 Operators Manual 057-015DSE7510 Data Sheet 055-065DSE7510 Operators Manual 057-088DSE8610 Data Sheet 055-083DSE8610 Operators Manual 057-115

DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com

DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com

055-044/02/13 (4)Registered in England & Wales No.01319649VAT No.316923457

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.

KEY FEATURES• Power On/Status LED• Plug & socked connection for

quick and easy set-up• Simple configuration via multiple

position switches• Converts a single DSE5510,

DSE7510 or DSE8610’s MSClink to analogue load sharelines.

• Compatible with Barber Colman,Deif, Delco and Woodwardproducts that support analogueload share lines.

KEY BENEFITS• Expand existing systems with

DSE modules without replacingexisting control

• kW & kV Ar loadsharing betweenDSE & other manufacturersproducts.

Page 14: P123 - Setecomsetecom.com/wp-content/uploads/2015/09/DSE123-Data-Sheet-.pdf · Deif* 0 1 8 0 1 8 ... P123 interface is selector switch configurable as detailed below. ... If you have

DSE123ANALOGUE LOAD SHARE LINES INTERFACE

DSEGenset®

ENVIRONMENTAL TESTING STANDARDS

ELECTRO MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Emission Standard for theIndustrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for theIndustrial Environment

ELECTRICAL SAFETYBS EN 60950Safety of Information TechnologyEquipment, including Electrical BusinessEquipment

TEMPERATUREBS EN 60068-2-2Test Ab to +70oC 60067-2-2 HotTest Ab to -30oC 60068-2-1 Cold

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @2gn

HUMIDITYBS 2011 part 2.1 60068-2-30Test Cb Ob Cyclic93% RH @ 40oC for 48 hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15gn in 11mS

The DSE123 converts the digitalloadshare link between DSEproducts to the univeral analogueload share lines. This processallows synchronising of controlmodules of a diferent manufacturerto share kW and kV Ar with theDSE5510, DSE7510 or DSE 8610.

By interfacing with manufacturersproducts, esxpanding an existingsystem can be acomplished withease when utilising DSEsynchronising and loadsharingproducts.

When DC power is applied to theDSE123, a status LED willilluminate. If the DSE123 cannotcommunicate with the DSE5510,DSE7510 or DSE8610, the LED willflash to indicate a communicationmalfunction.

MSC LINK DC POWER SUPPLY 8-35V

7

OTHER

DSE123

kW LOADSHARE LINE

SINGLE DSExx10 MODULE

kV Ar LOADSHARE LINE*

COMPATIBLE WITH DSE5510, DSE7510 & DSE8610

BARBER COLMANDEIF*SELCOWOODWARD

ISSUE 1

COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS

kW SHARE SETTINGS V Ar SHARE SETTINGS

TYPE

BA C

BARBER COLMAN

DEIF*

SELCO

WOODWARD

6

6

4 2

2 2

0

0

0

0

0 8 8

8

8

1

1

1

1 1

1

1

1

1

D FE

DSE123 SWITCH POSITIONCONFIGURATIONThe table shows how theDSE123 interface needs to beconfigured depending on theexisting load share system.

kW kV Ar

*DEIF INCUDES kV Ar LOADSHARE LINES WHERE AS THE OTHERS DO NOT


Recommended