SD16_P28_LV-Ver I_030416 Page 1 of 6 P7/8 24V Series Actuator Specifications P7 P8 Torque “lb/Nm 8900”lbs/1000Nm 13250”lbs/1500Nm Supply Voltage 24vac/vdc 24vac/vdc Max Inrush Current 7.8A 8.0A Running Current 6.8A 8.1A Motor DC Brush Type Runtime (90°@60Hz) 46 sec 46 sec Runtime (90 O @50Hz) 46 sec 46 sec Duty Cycle 75% Motor Starts 1200 per hour Weight 82lbs/37kg Mechanical Connections ISO5211 F12 8pt 36mm Electrical Entry (2) 3/4” NPT Electrical Terminations 12-16ga Environmental Rating NEMA 4/4X Manual Override 11.6” Handwheel Control On/Off-Jog, Proportional Actuator Case material Aluminum Alloy, Powder coated Motor Protection 230°F/110°C Thermal F* Class *Totally Enclosed Non-Ventilated Motors Ambient Temperature Operating Range -22°F to +125°F -30°C to +52°C Data Sheet P7/8 24V Series On/Off/Jog/Proportional ISO5211 F12 8P36 Also available in 120VAC or 230VAC or 3 phase supply. Separate spec sheets are available for these configurations. See www.promationei.com for more information or call ProMation Engineering. The 24V P series quarter turn actuators have been designed for dependable performance in rugged industrial applications such as mining, clean water and wastewater treatment, and damper control. ProMation Engineering has an extensive stock of electric actuators and can ship product very rapidly, worldwide. Several key features increase ProMation actuator reliability: Cool running DC brush motors deliver 75% duty cycle. Easy to see yellow/red raised position indicator. Clutchless Manual Override Anti-Condensation Heater protects components from moisture. Epicyclic geartrains eliminate the need for an unreliable brake. Product Notes: 1. The P Series LV models can be ordered as an on/off (two position) model that can also be used in bump/jog applications. Available in 24vac/vdc. 2. It can also be ordered with a premium internal proportional control card that accepts a wide range of control signals, generates multiple feedback signals, and has look-ahead fault prevention. Available in 24vac. 3. It can also be ordered with an internal proportional control card that accepts a wide range of control signals and 4-20mA feedback signal. Available in 24 vdc. On/Off/Jog / Proportional 50°F 10°C 75°F 24°C 100°F 38°C 125°F 52°C 25% 50% 75% 100% Ambient Temperature Duty cycle is defined as the ratio of total time vs. run time, and is a function of environmental conditions including ambient temperature, supply voltage and control signal stability Duty Cycle rating on all 24VAC/VDC actuators is 75%. Duty cycle graph
Transcript

SD

16_P28_LV-Ver I_030416

Page 1 of 6 P7/8 24V Series

P7/8 LV N4

MAX distance between Actuator and Supply (feet)

Actuator P7 P8Voltage 24VAC/VDC 24VAC/VDC

7.8A 8.0A

16 33 3214 54 5212 82 8010 140 1368 209 204

MAX distance between Actuator and Supply (feet)

Actuator P7 P8Voltage 24VAC/VDC 24VAC/VDC

7.8A 8.0A

16 33 3214 54 5212 82 8010 140 1368 209 204

WireGage

Amps

Wire Sizing Chart

Actuator Specifi cations P7 P8Torque “lb/Nm 8900”lbs/1000Nm 13250”lbs/1500NmSupply Voltage 24vac/vdc 24vac/vdcMax Inrush Current 7.8A 8.0ARunning Current 6.8A 8.1AMotor DC Brush TypeRuntime (90°@60Hz) 46 sec 46 secRuntime (90O@50Hz) 46 sec 46 secDuty Cycle 75%Motor Starts 1200 per hourWeight 82lbs/37kgMechanical Connections ISO5211 F12 8pt 36mmElectrical Entry (2) 3/4” NPTElectrical Terminations 12-16gaEnvironmental Rating NEMA 4/4XManual Override 11.6” HandwheelControl On/Off-Jog, ProportionalActuator Case material Aluminum Alloy, Powder coated

Motor Protection 230°F/110°C Thermal F* Class*Totally Enclosed Non-Ventilated Motors

Ambient Temperature Operating Range

-22°F to +125°F-30°C to +52°C

Data Sheet

P7/8 24V SeriesOn/Off/Jog/Proportional

ISO5211 F12 8P36

Also available in 120VAC or 230VAC or 3 phase supply. Separate spec sheets are available for these configurations.See www.promationei.com for more information or call ProMation Engineering.

The 24V P series quarter turn actuators have been designed for dependable performance in rugged industrial applications such as mining, clean water and wastewater treatment, and damper control. ProMation Engineering has an extensive stock of electric actuators and can ship product very rapidly, worldwide.Several key features increase ProMation actuator reliability:

• Cool running DC brush motors deliver 75% duty cycle. • Easy to see yellow/red raised position indicator. • Clutchless Manual Override • Anti-Condensation Heater protects components from moisture.

• Epicyclic geartrains eliminate the need for an unreliable brake.

Product Notes:1. The P Series LV models can be ordered as

an on/off (two position) model that can also be used in bump/jog applications. Available in 24vac/vdc.

2. It can also be ordered with a premium internal proportional control card that accepts a wide range of control signals, generates multiple feedback signals, and has look-ahead fault prevention. Available in 24vac.

3. It can also be ordered with an internal proportional control card that accepts a wide range of control signals and 4-20mA feedback signal. Available in 24 vdc.

Duty Cycle Graph

CSA Certified Duty Cycle Graph Duty Cycle Graph

50°F10°C

75°F24°C

100°F38°C

125°F52°C

150°F65°C

25%

50%

75%

100%

On/Off/Jog

Ambient Temperature Ambient Temperature

CSA Certified Duty Cycle Graph

50°F10°C

75°F24°C

100°F38°C

125°F52°C

150°F65°C

25%

50%

75%

100%

On/Off/Jog

Duty Cycle Graph

50°F10°C

75°F24°C

100°F38°C

125°F52°C

150°F65°C

25%

50%

75%

100%

On/Off/Jog

Proportional

Ambient Temperature

50°F10°C

75°F24°C

100°F38°C

125°F52°C

150°F65°C

25%

50%

75%

100%

On/Off/Jog

Proportional

Ambient Temperature

CSA Certified Duty Cycle Graph

50°F10°C

75°F24°C

100°F38°C

125°F52°C

150°F65°C

On/Off/Jog / Proportional On/Off/Jog / Proportional

Ambient Temperature

50°F10°C

75°F24°C

100°F38°C

125°F52°C

25%

50%

75%

100%

Ambient Temperature

• Dutycycleisdefinedastheratiooftotaltimevs.runtime,andis a function of environmental conditions including ambient temperature, supply voltage and control signal stability

• Duty Cycle rating on all 24VAC/VDC actuators is 75%.

Duty cycle graph

SD

16_P

28_L

V-Ve

r I_0

3041

6

The Premium Proportional Controller offers a full array of features - such as various control and feedback signals, alphanumeric readout, several fault indicators for operational diagnostics, extensive data logging that provides full proportional control for all industrial applications. ModBus communications are also an option on this controller.

Control Signal Inputs(selectable using program menu):

• 0-10vdc• 1-5vdc• 2-10vdc • 4-20mA

Factory set with common isolated from ground. Ground reference is possible.

Signal Input Impedance Sensitivity

0-10vdc 140k ohms 50mV

1-5vdc 250k ohms 20mV

2-10vdc 140k ohms 40mV

4-20mA 250 ohms 80µA

Feedback Signal Output (Can be different than input):

• 0-10vdc• 1-5vdc• 2-10vdc• 4-20mA Max Load: 250 ohms

Full Proportional Control Featuring:

• Autocalibration• Programmable• High resolution• Alarm Outputs• Data logging• Simple User Interface• Field Selection Friendly• Thermal Management

Auxiliary Signal Output (programmable):Alarm Contacts al low for signaling of 5 different fault conditions. 2 Position ControlContacts and capability for 2 position (only) override of the actuator.

ProMation Premium Controller:

SAMPLE DIAGRAMRefer to the proper IOM for your actuator for the correct wiring diagram or visit www.promationei.com.

AC Proportional Control

• Auxiliary switches are rated 10A @ 250vac MAX. • Terminals 7-12 are dry type Form C. • Terminals accept 16-22ga solid/stranded wire.

Page 2 of 6 P7/8 24V Series

Wiring Diagrams for P7/8 Series

ALL SWITCHESSHOWN WITHACTUATOR IN

FULL OPENPOSITION

Actuator ships in fully closed position!

Pro

po

rtion

al C

on

trol F

UL

L M

OD

24

VA

C S

up

ply

24

VA

C NEU

HOT

GND p/n 430-10100

FEEDBACK OUT

SIGNAL IN

COMMON

ALARMCONTACT

0.5A 125VACMAX

STATUS ALARM

OUT

IN

COM

COM

DIR

PWR

NC

NO

COM

AL

AR

MP

WR

FA

ILA

NA

LO

G

NOT OPEN*

OPEN COM*

OPEN*

NOT CLOSED*

CLOSED COM*

CLOSED*

12

11

10

9

8

7

6

5

4

3

2

1

SW3

SW4

AUX

CO

NN

EC

TIO

NS

OP

TIO

NA

L

GNDScrew

Close

POSITIONFEEDBACK

1K ohmJ6

J4

FACTORYCONNECTOR

6.3A250V3AGSLO

OPTIONPOWER

J7

F3

HEATER

SW1

SW2

J2

E1E2

1

12

43

Red - Close

Grn-Open

1

TB1

MRED BLK

p/n 408-00052

p/n 408-00030

AUX

+ on RedDrive CW

+ on BlkDrive CCW

P7/8-24PN4-AC

C

Items within dotted line located inside actuator housing

Use For:

FIELD WIRING (BY OTHERS)

INTERNAL WIRING (FACTORY)

WD

-85

0-4

32

01

GRYREDBLUYEL

1 2

3 4

1.0

K .5

W 5

%1

.0K

.5W

5%

RED

BLU

WHT

12VAC

NEU

HOT

GND

Field WiringActuator Wiring

SD

16_P28_LV-Ver I_030416

The Premium controller offers features such as various control and feedback signals, indicators for operational diagnostics, and non-interactive zero and span trimmers for precise actuator performance.

• Auxiliary switches are rated 10A @ 250vac MAX. • Terminals 7-12 are dry type Form C. • Terminals accept 16-22ga solid/stranded wire.

Control Signal Inputs(selectable using dip switches):• 0-5vdc• 0-10vdc• 1-5vdc• 2-10vdc• 4-20mA

Signal Input Impedance Sensitivity

0-5vdc 13k ohms 20mV

0-10vdc 13k ohms 50mV

1-5vdc 13k ohms 20mV

2-10vdc 13k ohms 40mV

4-20mA 250 ohms 80µA

Feedback Signal Output 4-20mA

Max Load: 250 ohms

Full Proportional Control Featuring:• Potentiometric feedback• Selectable Loss of Signal

functions• Drive / Fault Indicators• Zero and Span Trimmers

Drive / Fault Indicators Drive / Fault indicators allow for signaling of 8 different conditions.

Zero and Span Trimmers Can be set to any position within the usable range of the feedback potentiometer. This allows the unit to be calibrated for direct or reverse acting without rewiring.

ProMation DC Proportional Controller:

SAMPLE DIAGRAMRefer to the proper IOM for your actuator for the correct wiring diagram or visit www.promationei.com.

DC Proportional Control

Page 3 of 6 P7/8 24V Series

Wiring Diagrams for P7/8 Series

GND Screw

HEATER

SW1

SW2

SW3

SW4

AUXILIARYSWITCH

(STANDARD)

ALL SWITCHESSHOWN WITHACTUATOR IN

FULL OPENPOSITION

AUXILIARYSWITCH

(STANDARD)

J2

E1E2

1

21

43

Items within dotted line indicates internal components

DC

M

24V

3 TerminalMTA Plug

6

5

2

1

+5v

4

3

J-1

J-2

7

8

+

-

6

5

4

3

8

7

TB-1

2

1

9

10

12

11

DM

C-1

02

W

5K

4-20mA IN +

Mounted inside Actuator Housing

-24VDC

Sig IN+

+5VOUT

BLK16

GRY16

TB-1

YEL16

BLU16

0V

GRY

ORG

BLU

p/n 430-11212p/n 430-10100

BLK

RED

Red - Close

Grn-Open

Red - Close

Grn-Open

W

+

-

4-20

XM

A-1

05

Span

Zero

p/n 430-10134

4-20mA Out +

24VDCPowerSupply

Sig Common

GND

ZS

J2

1

WIRING DIAGRAM FOR DIRECT ACTING

DRAIN

Field Wiring Actuator Wiring

Connect at source ONLY!

P7/8-24PN4-DC (4-20mA)

C

Actuator ships in fully closed position!Use For:

Use

s DM

C-1

02

WD

-85

0-4

23

01

6

5

2

1

3

4

Sig IN-

Earth

+24VDC

7.5V

RED22

BLU22

ORG22

RED16

ON 1 2 3 4 5

4-20mA Out -

Field Wiring Actuator Wiring

SD

16_P

28_L

V-Ve

r I_0

3041

6

Wire sizing data is provided to assist in the selection of the proper wire size for ProMation P Series actuators using various wire sizes over distance.

Please make sure to reference the correct voltage and do not exceed the indicated length of the wire run for each model.

On/Off/Jog Control Featuring:• Simple Installation• Drive Indicators• Switched Pilot Outputs• Dry Contact Auxiliary

Switches• Optional Connections

for position indication• Upgradeable with a number

of factory installed options

ProMation On/Off/Jog Controller:

On/Off/Jog Control

• Field Control Device may be relay contact, Switch or Triac type.

• Pilot device 10A MAX. • Auxiliary switches are rated 10A @ 250vac MAX. • Terminals 7-12 are dry type Form C. • Terminals accept 16-22ga solid/stranded wire.

SAMPLE DIAGRAMRefer to the proper IOM for your actuator for the correct wiring diagram or visit www.promationei.com.

Page 4 of 6 P7/8 24V Series

P7/8 LV N4

MAX distance between Actuator and Supply (feet)

Actuator P7 P8Voltage 24VAC/VDC 24VAC/VDC

7.8A 8.0A

16 33 3214 54 5212 82 8010 140 1368 209 204

MAX distance between Actuator and Supply (feet)

Actuator P7 P8Voltage 24VAC/VDC 24VAC/VDC

7.8A 8.0A

16 33 3214 54 5212 82 8010 140 1368 209 204

WireGage

Amps

Wire Sizing Chart

Actuator Specifi cations P7 P8Torque “lb/Nm 8900”lbs/1000Nm 13250”lbs/1500NmSupply Voltage 24vac/vdc 24vac/vdcMax Inrush Current 7.8A 8.0ARunning Current 6.8A 8.1AMotor DC Brush TypeRuntime (90°@60Hz) 46 sec 46 secRuntime (90O@50Hz) 46 sec 46 secDuty Cycle 75%Motor Starts 1200 per hourWeight 82lbs/37kgMechanical Connections ISO5211 F12 8pt 36mmElectrical Entry (2) 3/4” NPTElectrical Terminations 12-16gaEnvironmental Rating NEMA 4/4XManual Override 11.6” HandwheelControl On/Off-Jog, ProportionalActuator Case material Aluminum Alloy, Powder coated

Motor Protection 230°F/110°C Thermal F* Class*Totally Enclosed Non-Ventilated Motors

Ambient Temperature Operating Range

-22°F to +125°F-30°C to +52°C

Wiring Diagrams for P7/8 Series

The heart of the On/Off/Jog actuator is a robust general purpose relay controlled 24vac or 24vdc controller which drives a 75% duty cycle DC motor. It is suitable for bump/jog operation.

P7/8-24N4+ACDC

AActuator ships in fully closed position!

WD

-85

0-4

A1

01

Use For:

RUN OPEN

RUN CLOSED

2

1

12

11

10

9

8

7

6

5

4

3

2

124 VAC/VDC

GND Screw

HEATER

SW1

SW2

SW3

SW4

AUXILIARYSWITCH

(STANDARD) ALL SWITCHESSHOWN WITHACTUATOR IN

FULL OPENPOSITIONAUXILIARY

SWITCH(STANDARD)

J2

J1

E1E2

J3 M

HOT/POS

NEU/NEG

24VDC

Pin Headeron PCB

3 TerminalMTA Plug

1

12

43

Items within dotted line indicates internal components

J1

1

J2

3

4 TerminalMTA PlugPin Header

on PCB

1

2

3

4

5

6

7

GRY

YEL

RED

BLK

RED

408-30116(Blue PCB)430-10100

Closed*

Closed COM*

Not Closed*

Open*

Open COM*

Not Open*

Open Pilot*

Closed Pilot*

FIELDCONTROL

DEVICE

*Connections Optional

~

~

+

-

AC +BLK

RED

WHTBLU

GND

YEL

RED

BLU

Anti-CondensationHeater

Field Wiring Actuator Wiring

SD

16_P28_LV-Ver I_030416

P Series Exploded View

Easily distinguishable yellow/red position

indicator

Worm Drive

Heavy Duty Drive Motor

Easily accessible switch &

cam stacks

Modular ControlCards

Clutchless OverrideHandwheel

Aluminum Casting4X Protection

Mechanical Stop Screws (2)

Epicyclic Gearing

Aluminum Casting4X Protection

NEMA 4Cover Seal

(Typical)

Application Notes:1. These actuators are to be mounted ONLY between a horizontal and upright position.2. When installing conduit, use proper techniques for entry into the actuator. Use drip loops to prevent

conduit condensate from entering the actuator. 3. Both NPT conduit ports MUST use proper equipment to protect the NEMA 4X integrity of the housing. 4. The anti-condensate heater is to be used in ALL applications. 5. Do not install or store the actuator outdoors or in humid environments without power to the heater.6. Use proper wire size to prevent actuator failure (see wire sizing chart). 7. Mechanical travel stops exist to prevent over-rotation for manual override only. They are not intended

to stop motor driven rotation.8. Do not parallel wire multiple actuators together without utilizing isolation relays! If this is your

intention, please contact ProMation Engineering for a multiple actuator parallel wiring diagram.

Switch Logic Map and Switch/Cam Arrangement

Term

inal

ID#

12

11

10

9

8

7

-5° 0°CW CCW

85°5° 90° 95°

SW3 CCW AUX(Factory Set - Adj)

SW4 CW AUX(Factory Set - Adj)}

}Closed Common

Open Common

}Used by Controller

Open

Not Closed

Closed

Not Open

Switch sequencing data is provided in the table below to show the change-of-state points during the rotation of the actuator from OPEN to CLOSED and back again. The red bar indicates when that terminal makes with it’s respective common.

SW1 and SW2 are set at the factory and should NOT be changed. The INCLUDED auxiliary switches SW3 & SW4 are forterminals7thru12andthosesetpointsmaybemodifiedifneed be. When so optioned, SW5 & SW6 auxiliary switches are initially set to function the same as auxiliary switches SW3 & SW4.

On/Off Switch/Cam arrangement shownPage 5 of 6 P7/8 24V Series

P7/8 Series Dimensional Data

1

1

2

2

A A

B B

Drawn By

Finish

Promation Engineering Inc.16138 Flight Path Drive

Brooksville, Fl 34604Phone: 352-544-8436Fax: 352-544-8439

This Document is the property of ProMation Engineering,Inc. Distribution of this document without the written

consent of the owner is Strictly forbidden. Failure to comply will incur a liability for Damages.

Checked By4/8/2015

P7~P8 Dim Data Rev.

E

NO SCALE Sheet Number: 1

Material

ProMation Engineering, Inc.KHL

KHL

5/2/2013

P7_8 F12 8P36 DimData.idw

Created:

Last Checked:

Part No.

Dwg. Name

Dimensional Data for P7~P8 Actuators

Engineering Change NoticeChange Date Description Name

05.01.13 Transferred file into Inventor format KHL

04.15.2014 Added tolerance on drive coupling data KHL

10.07.2014 Pushed square dimension to three decimal places KHL

04.08.2015 Added Isometric view of Drive Coupling and "Depth' tag for clarity KHL

REVA

B

C

D

E

F

Dimensional Tolerances (Unless Otherwise Noted):X ± 2.5mm [X.X ± .1]

X.X ± .3mm [X.XX ± .01"]X.XX ± .13mm [X.XXX ± .005"]

ALL TOLERANCE FEATURES IN mm

Drive Coupling Fabrication Data

337 mm13.2 in

227 mm8.9 in

346 mm13.6 in

180 mm7.1 in

220 mm8.7 in

295 mm11.6 in

404 mm15.9 in

Add 254mm

[10"] to allowfor coverremoval

101 mm4.0 in

236 mm9.3 in

(2) 3/4" NPTEMT Entry

36.00 mm1.417 inSquare

(4) M12x1.75

25mm1.0"

36.00 - .13.00+ mm

1.417 - 0.0050.000+ in

36.00 - .13.00+ mm

1.417 - 0.0050.000+ in

45.00 mm1.772 inDepth

125 mm4.9 inBHC

F12 ISO Flange

49.00 mm1.929 in

P7/8 Series Views(Typical)

Use your smart phone barcode scanner app here.

16138 Flight Path Drive Brooksville, FL 34604

Phone (352) 544-8436 Fax (352) 544-8439email: [email protected]

ProMation Engineering follows a policy of continual product updates and enhancements. Our website is the best place to obtain the latest product documentation, including the wiring diagrams for these controllers. Visit us at www.promationei.com or use the QR code below to link to the site.

ProMation Product Line

PL SeriesLinear Drive

Up to 4400lbs down/up force.

P SeriesNon-Spring Return

55”lbs through 40,000”lbs.

PA~PD Series Spring Return

445”lbs through 2300”lbs.

PBU Battery Back-Up Systems

Provides battery power to drive open

• Premium Proportional Controller Option. Converts 2 position to proportional control.

• Single Wire Control Relay (Internal) Units operate NORMALLY CLOSED - ENERGIZE TO OPEN.

• Single Wire Control Relay (Internal) Units operate NORMALLY OPEN- ENERGIZE TO CLOSED.

• Mechanical Torque Switch Assembly. P2~P8 except P2/3 24PN4-AC series.

• IP68 Protection, tested to 0.7kgf/cm2 for 72 hours. P2~P8 only.• 0-45-90 degree rotation option. • 0-90-180 degree rotation option. P2~P8 only.• 0-180 degree rotation option. No Mid-point position is offered.

(On/Off only). P2~P8 only.• 1k ohm position feedback potentiometer.• 5k ohm position feedback potentiometer.• 10k ohm position feedback potentiometer.• 4-20mA feedback generator for On/Off/Jog actuators.• Auxiliary Switch set. Provides 3rd and 4th auxiliary switches

(Form C x 2).• Adjustable Timer, Dual Set Point Timer (Duration and

Frequency) (Contact factory for application assistance).

• Proportional Control Signal override capability (OPEN OR CLOSED). LV P2~P8 Series only.

• Integral Thermostat for Heater Control - turns on at 32°F, turns off at 50°F.

• Timer function which slows actuator rotation (cycle time) using an internally mounted octal timer. (Contact factory for application assistance). LV P2~P8 series only.

• Chain wheel override for applications where an actuator ismountedsomedistancefromthefloor.(UsewithLCS).

• Local Control Stations (LCS) ProMation LCSs are designed to be remotely located or directly mounted to the actuator. Proportional actuators will have different options than On/Off. Available in steel, stainless, or fiberglassenclosures.(See catalog for additional Local Control Selections).

• 3 Phase models with or without Motor Control Center.

• Optional SCADA and Modbus compatability.

• Epoxy coating for increased environmental protection.

• Nylon coating for increased environmental protection.

• Stainless Steel enclosure. P1~P6 Only.

SD

16_P

28_L

V-Ve

r I_0

3041

6

AVAILABLE OPTIONS (Factory Installed)

Page 6 of 6 P7/8 24V Series

Note: Not all combinations are possible. Please consult factory.

On/Off

P

8900”lbs / 1000Nm

13250”lbs / 1500Nm

Non-SpringReturn24

7

8N

NEMA4X

424VAC+10%

P 7 - 24 N 4Product Family Control Options Special DesignationsVoltage Options

RO Relay Open (2 pos)

RC Relay Close (2 pos)

TS

68

Torque Switch

IP68

PremiumProportional

24VDC+10%


Recommended