Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley, CA 93065 (805) 522-2733 AmeriSpec Inspection Services This is a Confidential Report, any use by unauthorized persons is prohibited. (c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated Inspection No: 201404-0115 Inspector: Joe Nernberg Inspection Date: 4/4/2013 Dwelling: 1234 Easy Street Camarillo, CA 93010 Client: Judy Punch Client's Agent: Jack Daniels We attempt to give the client a comprehensive, clear cut, unbiased view of the home. This inspection is performed to www.creia.org standards of practice. The purpose of the inspection is to perform a basic operation of the systems and components which can be reached without difficulty, moving obstructions, or requiring any action which may result in damage or personal injury. Mostly, we attempt to identify "MAJOR" concerns associated with the property, although minor items may also be mentioned. Areas which may be of concern to us may be a lesser concern to the client and some items which may be of concern to the client may be considered minor to us, therefore, it is advisable to read the entire report. Where repairs or replacements are suggested, we recommend qualified licensed professionals in that field be called upon to make those repairs. We typically do not perform verification of repairs. Parties are advised to obtain documents from these professionals concerning the work performed and maintain all paperwork on repairs for future reference. GENERAL CONDITIONS 0001 Structure Type The property is a single family dwelling. 0002 Levels 1 story structure. 0003 Lot Type Flat lot. 0004 Estimated Age The estimated age of the property is 56 years. 0005 Weather Conditions Partly cloudy; Warm. 0006 Schedule Time The inspection was scheduled at 1:00 P.M.
Transcript
Page 1: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 1

AmeriSpec Inspection Services

1464 Madera Road, PMB 266

Simi Valley, CA 93065

(805) 522-2733

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Inspection No: 201404-0115 Inspector: Joe Nernberg

Inspection Date: 4/4/2013

Dwelling: 1234 Easy Street

Camarillo, CA 93010

Client: Judy Punch Client's Agent: Jack Daniels

We attempt to give the client a comprehensive, clear cut, unbiased view of the home. This inspection is performed to

www.creia.org standards of practice. The purpose of the inspection is to perform a basic operation of the systems and

components which can be reached without difficulty, moving obstructions, or requiring any action which may result in damage

or personal injury. Mostly, we attempt to identify "MAJOR" concerns associated with the property, although minor items may

also be mentioned. Areas which may be of concern to us may be a lesser concern to the client and some items which may be of

concern to the client may be considered minor to us, therefore, it is advisable to read the entire report. Where repairs or

replacements are suggested, we recommend qualified licensed professionals in that field be called upon to make those repairs.

We typically do not perform verification of repairs. Parties are advised to obtain documents from these professionals

concerning the work performed and maintain all paperwork on repairs for future reference.

GENERAL CONDITIONS

0001

Structure Type

The property is a single family dwelling.

0002

Levels

1 story structure.

0003

Lot Type

Flat lot.

0004

Estimated Age

The estimated age of the property is 56 years.

0005

Weather

Conditions

Partly cloudy; Warm.

0006

Schedule Time

The inspection was scheduled at 1:00 P.M.

Page 2: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 2

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Exterior

Our exterior evaluation is visual only. Our review does not take into consideration normal wear, cosmetic issues or

code/manufacturer's specifications.

Step # Component

Comments

1101

Driveway

Concrete. Cracks noted.

1102

Walkways

Concrete. Cracks noted.

1103

Fences/Gates

Wood; Block wall. Gate hardware is damaged. Evidence of insect

infestation noted. These areas are generally not inspected by the termite

company. Suggest repairs/replacement as needed.

1104

Siding

Stucco; Wood. Cracks, blisters and damage noted. Evidence of patching

noted. Unable to determine the effectiveness of these repairs.

1105

Trim

Wood. Paint peeling at multiple locations. Recommend addressing

lead-base paint issues, if any. Possible health concern. Suggest

reviewing the latest pest control report for a more detailed evaluation

regarding wood destroying organisms.

1106

Windows &

Frames

Aluminum. Double glazed insulated windows noted. The inspector

was unable to determine if all double glazed insulated windows in this

property are completely intact and without broken seals. Conditions

such as temperature, humidity and lighting limit the ability of the

inspector to review these windows for broken seals.

1107

Electrical

Components

Serviceable.

Page 3: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 3

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1108

Gutters &

Downspouts

Metal. Debris/rust noted. Gutters are leaking at multiple locations.

Suggest repairs/replacement as needed.

1110

Bell/Chime

Doorbell/chime inoperable. Suggest repair.

1111

Front Door

Wood. Dead bolts that require a key from the inside are considered a

potential safety hazard when this door becomes an emergency exit.

Recommend replacing with one operated with a thumb latch.

1112

Chimney

Not Present.

1113

Lot/Grade

Drainage

Flat lot. Re-grading where needed is recommended to assure all water

drains away from the foundation. Typically, the grade should fall a

minimum of 6 inches within the first 10 feet.

1114

Gas Meter

Located at left side.

1115

Crawl Space/Sub

Area

Access located at the master bedroom closet. Ventilation appears to be

adequate. Suggest adding insulation to improve comfort and efficiency.

Page 4: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 4

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1116

Foundation

Raised concrete construction. Foundation cracks. Recommend a

structural engineer and/or a licensed contractor to repair as needed.

The house is bolted to the foundation.

1126

Orientation

Right and left is oriented by looking at the house from the street.

Patio/Porch

We suggest periodically checking concrete/wood and other materials for signs of deterioration. Suggest periodically treating

all wood and monitoring drainage around concrete slabs to help prevent deterioration.

Step # Component

Comments

1151

Cover

Not Present.

1152

Electrical

Serviceable.

1153

Deck/Slab

Concrete. Cracks noted.

1154

Steps

Concrete. Uneven risers. Tallest and shortest riser should not exceed

3/8-inches. Suggest repairs to ensure safety.

1155

Railing

Not Present.

Page 5: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 5

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Roof

Our evaluation of the roof is to determine if portions are missing and/or deteriorating. Portions of underlayment and decking

are hidden from view and cannot be evaluated by our visual inspection. Leaks are not always visible to the inspector, nor can

the inspector determine the water tight integrity of a roof by visual inspection. If such a review is desired, client should contact

a qualified licensed roofing contractor.

Step # Component

Comments

1201

Roofing Type and

Materials

Observed from the roof; Sloped construction.

1202

Flashings

Improperly re-roofed. If the old flashing was in good condition, the

lower part of the flange must be exposed and new shingles installed

beneath same flange.

Page 6: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 6

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1203

Conditions

Composition shingles over wood shingles. Roofing materials are

deteriorating and/or missing from several areas. Improper lapping.

Evidence of patching. Unable to determine the effectiveness of these

repairs. Recommend a licensed roofing contractor to repair and evaluate

the entire roof system.

Attic

Step # Component

Comments

1251

Access

Attic access is located in the hall.

1252

Framing

Serviceable.

1253

Sheathing

Spaced 1" x 6". Moisture stains noted. Cannot determine if stains are

active or passive.

1254

Insulation

Blown in. Insulation is approximately 6-inches thick.

1255

Ventilation

Eave vents; Hooded roof vents.

Page 7: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 7

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Garage

Step # Component

Comments

1301

Location

Attached.

1302

Exterior

Garage is attached. See EXTERIOR section for more information.

1303

Roof

Garage is attached. See ROOF section for more information.

1304

Floor/Slab

Concrete. Expansive cracks noted.

1305

Garage Door

Metal; Roll up/sectional panels. Damaged gasket/sweep.

1306

Garage Door

Hardware

Serviceable. Rollers.

1307

Garage Door

Opener

This garage door is equipped with a safety reverse device which operated

when tested at the time of inspection. The U.S. Product Safety

Commission recommends that these devices be checked monthly for

proper operation and safety.

1309

Fire Door

Not Present.

1310

Access/Exterior

Door

Wood. Damage noted.

1311

Fire Wall/Ceiling

Compromised due to holes/damage/gaps and a microwave oven. The

garage must be separated from the residence and its attic area by not less

than 1/2-inch gypsum board applied to the garage side (and not less than

5/8-inche type X gypsum board beneath habitable rooms). Recommend

repairs by a licensed contractor to resist the free passage of flame and

products of combustion.

1313

Walls and Ceiling

Open framed; Drywall. Damage noted. Recommend unblocking the

vents.

Page 8: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 8

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1314

Garage Electrical

Extension cord improperly used at the garage door opener. Extension

cords should not be used for permanent wiring due to safety concerns.

Multiple open electrical splices noted.

Whenever electrical wires are cut and reconnected, the 'splice' should be

encased in a covered 'junction box' to ensure safety and protect the wires.

The non-metallic sheathed wiring (also referred to as Romex) is exposed.

These conductors are normally used inside walls where they are not

subject to damage. Recommend a licensed electrician to correct for

safety. The water and gas piping is not bonded at the water heater. This

is a safety concern. Bonding is defined as "the permanent joining of

metallic parts to form an electrically conductive path that will assure

electrical continuity and the capacity to conduct safely any current likely

to be imposed." Recommend a licensed electrician to repair with a solid

copper conductor not less than #8 awg.

Page 9: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 9

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Laundry Area

Step # Component

Comments

1351

Floor

Serviceable. Concrete.

1352

Walls & Ceiling

Drywall; Unfinished.

1356

Laundry Sink

Loosely mounted sink. Drain fittings are for gas, water and oil. Suggest

repairs.

1357

Electrical

Ungrounded receptacle. A qualified licensed electrician should repair to

ensure safety. See also 1314 comments.

1359

Washer Hook-ups

Water valves leaking and unprofessionally installed. Suggest repairs.

1360

Clothes Dryer

Connections

Gas and 220-volt electric. Clothes dryer pilot/ignition should be at least

18" above the garage floor. Recommend building a stand/correcting for

safety.

Page 10: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 10

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Heating & Cooling

Step # Component

Comments

1401

Heating

Gas; Forced air. Unit is located at the entry.

1402

Conditions

Carbon Monoxide concern. Discoloration at supply registers. Due to the

presence of rust, scale and the age of this appliance, a thorough service

review a qualified licensed HVAC contractor is advised to ensure safe

and proper operation of this unit. Inspection for holes and/or cracks in

heat exchangers is not within the scope of this inspection and should be

performed prior to closing to ensure the safe operation of the system.

The flexible gas connector is attached inside the furnace compartment.

Recommend that this connection occur 2-inches outside of the furnace

for safety.

1403

Exhaust Venting

Serviceable.

1404

Thermostat

Serviceable. Thermostat is located at the hall.

Page 11: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 11

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1405

Ducting

Damaged asbestos covered ducts at the attic. Intact or sealed (painted or

taped over) asbestos is not harmful unless it becomes friable. Friable

means the material can be easily crushed or pulverized to a powder by

hand pressure. Friable materials have a higher potential to release fibers.

This is a possible health and safety concern. Suggest further

review/repairs/replacement by a qualified licensed asbestos abatement

contractor prior to closing.

1406

Air Conditioning

System

Not Present.

Page 12: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 12

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Plumbing

Step # Component

Comments

1501

Plumbing Water

Supply System

Pressure was within normal range of 40 to 80 psi. Shut off location is at

the front. Property has public water supply.

1502

Plumbing Sewer

System

Recommend a video inspection of this home's underground sewer line.

Buildings older than 30 years may have root infestation, leaking

connections due to earth movement, age and/or defective material.

1503

Water Piping

Copper; Galvanized. Rust and corrosion were observed on galvanized

water supply lines. Galvanized water lines rust from the inside out and

can become restricted over time. Low water flow noted at plumbing

fixtures. Also, there may be undiscovered leaks in walls. Suggest a

qualified licensed plumbing contractor to re-pipe as needed.

Page 13: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 13

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1504

Waste/Drain Pipes

Galvanized; Cast iron; Plastic. Rust/corrosion noted on waste pipes.

Waste lines are leaking at multiple locations. Suggest

repairs/replacement as needed.

Page 14: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 14

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1506

Water Heater

40 Gallon; Gas. The bracing on this tank is too loose to meet the

minimum compliance. Recommend the installer properly block the

space between the wall(s) and the water heater. A discharge pipe is

missing on the temperature pressure relief valve. Suggest installing the

required 3/4-inch metal discharge pipe on the TPR valve to the exterior of

the building to ensure safety. Water heater is located at the garage.

1507

Exhaust Venting

System

Recommend adding a 3" x 4" fitting where the water heater vent pipe

changes sizes. This water heater vent is improperly attached. Each

fitting must be connected by three screws/rivets. This is a safety

concern requiring repairs by licensed heating/plumbing contractor.

1508

Gas Piping

Cap and remove add-on gas line. Left side of house. Safety concern.

Page 15: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 15

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Electrical System

Step # Component

Comments

1601

Electrical Main

Box/Panel

Recommend replacing this electrical panel. No main disconnect

provided at this equipment as is required when there are 6

switches/circuit breakers or more. Expansion of this system is contrary

to the manufacturer installation instructions. The main panel is located at

the rear. Service entrance is overhead. This house is equipped with a

two wire non-grounded system which was standard at the time of

construction. Receptacles near water sources and at exterior locations

ideally should be grounded. Because of the age or configuration of this

system, we are unable to determine if grounding is in place or can occur.

Suggest review by a qualified licensed electrician to determine the

feasibility of GFCI receptacles in lieu of grounding for wet locations to

ensure safety. Conductors are copper, preferred for safety. Breakers

present to provide overload protection. Recommend legible identifying

each circuit as to purpose or use on the face or inside the electrical panel

door.

1625

Electrical System

Comments

Today's standards require that receptacles that serve counters in the

kitchen, bathrooms, the garage, outdoors to be ground fault circuit

interrupter (GFCI) protected. The client may wish to have them

installed, where needed, as a safety upgrade. This GFCI device detects

leaking electrical current flowing to ground. When the sensor detects

4-6 milliamps of leakage, it automatically turns off power fast enough to

prevent serious injury.

Page 16: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 16

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1630

Smoke & CO

Alarms

Recommend smoke alarms in each sleeping room and at a point centrally

located in the corridor/hall giving access to each separate sleeping area

(bedroom).

Kitchen

The kitchen inspection is a combination of visual and operational testing. Appliances are operated (if power is supplied) using

normal operating controls. Calibrations to cooking systems or their efficiencies are not evaluated nor are life expectancies

given. NOTE: Dishwashers can fail at any time due to their complexity. Our review is to determine if the system is free of

leaks and excessive corrosion.

Step # Component

Comments

1701

Floor

Serviceable. Vinyl.

1702

Walls

Drywall. Damaged under the sink. Suggest patching.

1703

Ceiling

Drywall. Cracks noted.

1704

Doors

Wood. The glass is tempered. Dead bolts that require a key from the

inside are considered a potential safety hazard when this door becomes an

emergency exit. Recommend replacing with one operated with a thumb

latch.

1705

Windows/Screens

Serviceable.

1706

Cabinets

Serviceable. Wood.

1707

Counter Tops

Serviceable. Laminate.

Page 17: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 17

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1708

Electrical

Exposed electrical splices found (to the cook top). All Splices should be

inside a junction box for safety.

Ungrounded outlets. The non-metallic sheathed wiring is exposed in

cabinets. These conductors are normally used inside walls where they

are not subject to damage.

Recommend a licensed electrician to correct for safety.

1709

Sinks

Serviceable. Stainless steel.

1710

Faucets

Serviceable.

1711

Traps/Drain

System

Serviceable.

1712

Waste Disposer

Serviceable. In-Sink-Erator.

1713

Dishwasher

Not Present.

1714

Stove/Cook Top

Serviceable. Gas; Tappan.

Page 18: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 18

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

1715

Oven

Gas; Tappan. The oven is not secured to the cabinet. Suggest repairing

for safety.

1716

Exhaust Hood/Fan

Serviceable.

1717

Microwave Oven

Not Inspected.

Entry

Step # Component

Comments

1801

Floor

Wood. Floor damage noted.

1802

Walls

Serviceable. Drywall.

1803

Ceiling

Serviceable. Drywall.

1804

Doors

Serviceable. Wood.

1806

Electrical

Serviceable.

Page 19: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 19

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Living Room

Step # Component

Comments

2001

Floor

Serviceable. Wood.

2002

Walls

Drywall. Cracks noted. Infrared camera (thermal image) shows a larger

door was removed when French doors were installed.

2003

Ceiling

Drywall. Cracks noted.

2004

Doors

French. Weathered. The glass is tempered. Dead bolts that require a key

from the inside are considered a potential safety hazard when this door

becomes an emergency exit. Recommend replacing with one operated

with a thumb latch.

2005

Windows/Screens

Serviceable.

2006

Electrical

Ungrounded three slot receptacles here and at every room. It is

recommended that these outlets be grounded, replaced with two slot

outlets, or protected on a GFCI circuit as applicable. Suggest repairs by a

qualified licensed electrical contractor to ensure safety.

2007

Heat Source

Forced air register observed.

Hall

Step # Component

Comments

2202

Floor

Serviceable. Wood.

2203

Walls

Serviceable. Drywall.

2204

Ceiling

Drywall. Cracks noted.

2207

Electrical

Serviceable.

Page 20: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 20

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Master/Front Bathroom

Our focus in bathrooms is directed at identifying visible water damage and/or visible plumbing problems. We may not always

mention common faults such as stuck stoppers or dripping faucets. If considered important, you should check these items

independently. Minor cosmetic issues such as common rust, corrosion and stains may not always be reported.

Step # Component

Comments

2302

Floor

Serviceable. Vinyl.

2303

Walls

Drywall. Patching noted.

2304

Ceiling

Serviceable. Drywall.

2305

Doors

Serviceable. Wood.

2306

Windows/Screens

Serviceable.

2307

Electrical

Ungrounded receptacle. See also 2006 comments.

2308

Exhaust Fan

Not Present.

2309

Heat Source

Electric wall unit. Heating unit inoperable. Suggest repair.

2313

Shower/Surround

Serviceable. Tile.

2314

Shower Door

Not Present.

2315

Shower Faucet

Serviceable.

2316

Sink

Serviceable.

2317

Sink Faucet

Serviceable.

2318

Drain Piping &

Water Supply

Shower drains slowly. Suggest repair.

2319

Toilet

Serviceable.

2320

Counter/Cabinets

Wood; Solid surface. Counter/cabinet loose. Suggest repair.

Page 21: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 21

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Hall/Rear Bathroom

Step # Component

Comments

2302.2

Floor

Vinyl. Damaged.

2303.2

Walls

Drywall. Damage/deterioration noted at the tub area.

Infrared camera (thermal image) shows no active water damage.

Recommend repairs as needed.

2304.2

Ceiling

Drywall. Cracks noted.

2305.2

Doors

Serviceable. Wood.

2306.2

Windows/Screens

Serviceable.

2307.2

Electrical

Ungrounded receptacle. See also 2006 comments.

2308.2

Exhaust Fan

Not Present.

2309.2

Heat Source

Electric wall unit. Heating unit inoperable. Suggest repair.

Page 22: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 22

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

2310.2

Tub/Surround

Porcelain; Fiberglass. Chipped.

2312.2

Tub Faucet

Serviceable.

2314.2

Shower Door

Not Present.

2315.2

Shower Faucet

Serviceable.

2316.2

Sink

Serviceable.

2317.2

Sink Faucet

Serviceable.

2318.2

Drain Piping &

Water Supply

Tub drains slowly. Suggest repair.

2319.2

Toilet

Serviceable.

2320.2

Counter/Cabinets

Wood; Solid surface. Counter/cabinet loose. Suggest repair.

Master/Front Bedroom

Step # Component

Comments

2402

Floor

Serviceable. Wood.

2403

Walls

Drywall. Cracks noted.

2404

Ceiling

Drywall. Cracks noted.

2405

Doors

Serviceable. Wood.

2406

Windows/Screens

See 2406.3 comments.

2407

Electrical

Ungrounded receptacles. See also 2006 comments.

2408

Closets/Wardrobe

Serviceable. Mirrored.

2409

Heat Source

Forced air register observed.

Page 23: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 23

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Left Bedroom

Step # Component

Comments

2402.2

Floor

Wood. Stained.

2403.2

Walls

Drywall. Cracks noted.

2404.2

Ceiling

Drywall. Cracks noted.

2405.2

Doors

Serviceable. Wood.

2406.2

Windows/Screens

See 2406.3 comments.

2407.2

Electrical

Ungrounded receptacles. See also 2006 comments.

2408.2

Closets/Wardrobe

Serviceable.

2409.2

Heat Source

Forced air register observed.

Page 24: Page 1 AmeriSpec Inspection Services 1464 Madera Road, PMB ...s3.amazonaws.com/AmeriSpecPhotos/nernberg.pdf · AmeriSpec Inspection Services 1464 Madera Road, PMB 266 Simi Valley,

Page 24

AmeriSpec

AmeriSpec Inspection Services

This is a Confidential Report, any use by unauthorized persons is prohibited.

(c) 2013, AmeriSpec Inspection Services. Each Company Independently Owned and Operated

Right Bedroom

Step # Component

Comments

2402.3

Floor

Serviceable. Wood.

2403.3

Walls

Serviceable. Drywall.

2404.3

Ceiling

Drywall. Cracks noted.

2405.3

Doors

Serviceable. Wood.

2406.3

Windows/Screens

This newer window does not meet the minimum net opening for

emergency egress. The minimum opening must be 20 inches wide, and

24 inches in height. The finished sill height must be 44 inches from the

floor. Recommended a licensed contractor to repair/replace for safety.

Condensation noted in this double glazed insulated window pane. This

indicates a broken seal which can reduce visibility and the insulating

capability of the window. To restore visibility and regain the insulating

capability, replacement of this window/pane is required.

2407.3

Electrical

Ungrounded receptacles. See also 2006 comments.

2408.3

Closets/Wardrobe

Serviceable.

2409.3

Heat Source

Forced air register observed.


Recommended