RB - -001
Last Inst. Cal. Date
Contact P/AOlympus MX2 PA 32/128600427 / 100843Mar-12
Figure 1 - PAUT Scan Plan
NA NAK0249 44°-70° 5MHz
Type
6+
Page 1 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-201
Ultrasonic Inspection Report
Reference
Cable Type, Length
Couplant UsedAcceptance Criteria
WaterClient Information
Integral PAUT2nd Cable Type & Length Integral PAUT
Surface Temperature Ambient
Scan (-) Transfer Value (+)
dB SettingsTransducerManufacturer
Scope
note, the weld profile has been built according to available data from the U1-A form. Actual bevel angle may be different. The scan plan shall be built to employ sectorial PAUT to observe the inner 1/3rd of the weld in order to quantify any signs of ID cracking. ToMaple Glen Gas Plant (16-36-036-16W4). A0151944 and A0151945. This is an in-service client information inspection only. We were asked to perform Phased Array inspection of 100% of the welds on the following two Condensate Storage Bullets located at the
* See continuation report for further scope and results.
Material Type and Thickness SA 612Method and Reference Documentation
Olympus 1.5mm SDH1.5mm SDH
NANA
Method / TypeInstrument UsedInstrument S.N.
A105L16 6+ NA NASerial No.
J4220Angle
44°-70°Frequency Size
5MHzOlympus A105L16
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
Technician NameCGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk Stinis
120817Client Devon Canada Report NumberW.O. Number
Equipment ID Condensate Storage Bullets
Facility Maple Glen Gas PlantAttention
Job Description and DetailsSurface Condition Painted, Acceptable
Cam Busby20015628
P.O. Number NA
Calibration Data Additional EquipmentCalibration /
Reference Block(s) Serial No. Distance Reading(s)
IIW 110411 NA
Serial No.Equipment TypeIndication Amplitude(s)
Reference Reflector(s)
Last Cal. Date
1.5mm SDH08-13-2012 80%
RB - -001
Henk StinisTechnician Name
Page 2 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Scope - Continued
Cam Busby20015628
P.O. Number
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
When discontinuities are encountered that may be indicative of ID connected cracking, they shall be imaged with TOFD to determineextent and only whether the indication is crack like or not. Due to the original joint efficiency requirements, this inspection shall not be utilizedto determine acceptability of the weld in accordance to code of construction. The Bullet on the North side of the plant is called tank north, the Bullet on the South side is called tank south. The ‘direction of flow’ of thetanks is assumed to be from west to east, naming the outer most circular weld on the west side number 1. All circular welds are scanned in
interpreted as crack like. As a cautionary note the other 17 indications may pose a risk to develop into cracks in the future. A monitoringprotocol may be wise until such time that a visual internal can be completed. Refer to Figures A and B for crack like indication detail.
four sections, 12 to 3 o-clock, 3 to 6 o-clock, 9 to 6 o-clock and 12 to 9 o-clock. The longitudinal welds on the heads are scanned clockwise, naming the 12 o-clock position ‘zero’.
Summary Report 146 data sets were captured, giving 100% coverage of all welds for each vessel. 19 relevant indications were detected, 2 of which are
Detail Report - PAUT Data sets and description.
RB - -001
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
Page 3 of 4
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Detail Report - PAUT Data sets and description - Continued.
Cam Busby20015628
RB - -001
Figure A - Indication number 10
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
Page 4 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Detail Report - Discontinuity Identification
Cam Busby20015628
RB - -001
the next internal inspection by visual or magnetic particle methods.
Images of Relevant Indications The following pages contain the images of both the PAUT and TOFD for the 19 relevant indications detected during the inspection.
Comments on Figures A and B (Indications 10 and 12) Indication 10 measures Length: 46mm (1129 to 1175) Height: 3mm (17 to 20). Indication 12 measures Length: 103mm (100 to 203) Height: 1.5mm (18.5 to 20). While these indications certainly appear to be ID connected, without full knowledge of the weld bevel and internal weld profile (caps ground flush?) these has to be some caution in analysis. These indications may turn out to be undercut or small
Figure B - Indication number 12
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
areas of cold lap. Future monitoring to look for signs of growth would be prudent, however these indications may be easily classified with
Page 5 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Detail Report - Discontinuity Identification
Cam Busby20015628
RB - -001
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
Page 6 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Images of Relavant Indications - Continued
Cam Busby20015628
RB - -001
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
Page 7 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Images of Relavant Indications - Continued
Cam Busby20015628
RB - -001
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
Page 8 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Images of Relavant Indications - Continued
Cam Busby20015628
RB - -001
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
Page 9 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Images of Relavant Indications - Continued
Cam Busby20015628
RB - -001
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
Henk StinisTechnician Name
Page 10 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Images of Relavant Indications - Continued
Cam Busby20015628
RB - -001
Henk StinisTechnician Name
Page 11 of 11
Date of InspectionTime of InspectionNDE Procedure UT-0001
17:0008/13/2012 - 08/17-2012
Ultrasonic Inspection Report
120817
Attention
Images of Relavant Indications - Continued
Cam Busby20015628
Report is an interpretation of test results, not a guarantee. The client representative's signature indicates acceptance of results and applicable charges.
This form property of Ultratest NDT Services • 5925 91St Edmonton, Alberta T6E 6A7 • www.ultratest.ca
CGSB Level & Cert. Number
Signature
UT III 13457 Client Representative Cam Busby
Signature
P.O. Number NA
Client Devon Canada Report NumberW.O. NumberFacility Maple Glen Gas Plant