F L 3 6 CP G - 120
Page 1 of 4Catalog Numbering System for MCCBs Based on PLS001 REV. 47 8/12/2013
Frame Size
(Amps)
SqD/FPL/FP/ (MG)
MG only
Breaker Platform
100 G E C3
100 F - - EF
125 E - - EX
150 H - - M1
225 (240V)
Q -- Q2R
250 C F C1
250 K - - QK
250 J TBD M2
250 T - - C1 (DC)
600 D J C2
600 L - - C2
600 U - - C2 (DC)
800 M -- C4R
1600 P -- C4
1600 V - - C4 (DC)
3200 R -- C5
Position 2
Breaker FrameCharacter
Char Meaning
B Bolt onC Drawout (Simplified)D Drawout (Universal)F No Lugs (Buss Connections)G* Bus on ON end; PDC on OFF endH* Lugs on ON end; PDC OFF endJ Strap ConnectorsL LUG-LUGM Lugs On End OnlyN Plug-in BaseP Lugs Off End OnlyS Rear Connecting StudsT* Bus on OFF end; PDC on ON endU* Lugs on OFF end; PDC ON end
A StandardE Bolt onK Shroud OFF EndR Drawout
* See Lug Options (L) for type of PDC.
Position 4
TerminationsNON I LINE BREAKERS
I LINE BREAKERS
Character Maximum Voltage (V AC unless noted)2 240, 208Y/1204 415Y/240, 480Y/277, 480 or 4405 5006 600Y/347 or 600 or 690 or 600 VDC7 500VDC1 1000 VDC
Position 7
Voltage
Character
Rating Trip Unit
- 80% FixedC** 100% FixedT* 80% Field Interchangeable
R* 100% Field Interchangeable
W 80% Mission CriticalG 80%/Ground Factory installedJ 80%/Unground Factory installedK 100%/Ground Factory installedL 100%/Unground Factory installed
RatingPosition 11
* Required if Trip Unit interchange may expose live parts per UL489 section 6.1.5.13**For 100% rated H/J Frame, breakers may only be unit mount construction AND only copper lugs can be used.
English French SpanishNo
characterX X* X* UL / CSA /
NOM*/soft IEC*E X IEC
C X X UL/CSA/IEC
M X NOM / IEC
Shaded area removed from options to avoid conflicting order designations (this area is not to be deleted from PLS001 for record purposes).
Position 5
Language and CertificationLanguageCharacter Certification
* Spanish and French to be added as part of MCCB labels program. NOM will also be added. IEC is not always part of the UL/CSA/NOM offer.
Character
12345
100 150 160125 250150 250250 400400 600 630
3
4 with Over-sized Neutral (OSN)
IEC (A)Neutral Protection Values for OSN (5)
Phase Rating (A)
UL (A)
4
2
Number of Poles
Position 6
Number of Poles
1
Pos. < 1000 > 1000
8 100s of Amps 1000s of Amps
9 10s of Amps 100s of Amps
10 Amps 10s of Amps
Ampacity
Frame Ampacity (Amps)
000_Snn = Automatic Sw itch (See Trip Systems) 000_Znn = Non-Automatic Sw itch 000_Fnn = Frame Only
SqD/FP/MG MG 1 240 480 600 600 DC 1000 DCB 10 - - - - 3 3C 65 14 - - - - 5D 25 18 14 7.5 7.5G N 65 35 18 10 - -J H 100 65 25 - - - -
K 2 2 2 - - - -
L L 1253 100 50 - - - -
I4 -- 200 200 100 - - - -R -- 200 200 100 - - - -
CharacterDENHLR IEC LB Equivalent
*Values vary. See Compact NS Price Guide for specific values.
IEC I-Line (Swindon)
Standard interrupting*
Character
Current limiting*
IEC-only TableInterrupting
Low interrupting*
High interrupting*
1 Shaded area used on MG NSE/NSJ/NSF breakers only.2 K ratings at 240/480/600 V are as follows: P-Frame (C4) breaker: 65/50/50 kA R-Frame (C5) breaker: 65/65/65 kA3 L rating is 150kA @240V in the MG NSJ, CK, CM breakers4 Irating iwll be obsolete with FI,KIand LI breakers5 P-frame is 25kA at 600V for L
Position 3
Interrupting LevelUL/CSA/NOM Table
Voltage Class
NOTE: This graphic representation of PLS001 is a summary of the detailed Product Line Standard 001 document prepared by the Circuit Breaker Product Line Management Team in Cedar Rapids. It does not include all information found in that document. For details, and for revision history, please refer to that document.
U63
Page 2 of 4
Family Family
1 100 16 -- 15 400 150 D2 25 -- 25 250 D3 30 -- 40 400 D3 32 -- 40 250 400 NS4 40 -- 60 400 600 NS5 50 -- 63 400 630 NS6 60 -- 25 600 250 U6 63 -- 30 300 U8 80 -- 40 400 D,U10 100 NS 50 500 U3 150 30 -- 60 600 D,P10 100 150 -- 63 630 630 D,P12 125 -- 80 800 800 P15 150 H 80 1200 800 P15 100 150 NS 10 1000 P,R16 100 160 NS 12 1200 P,R25 125 250 NS 12 1250 1250 P25 150 250 NS 16 1600 1600 P12 160 125 -- 06 1600 600 V16 160 NS 08 1600 800 V10 250 100 T 10 1600 1000 V15 250 150 NS,T 12 2000 1200 R16 160 NS 16 1600 R17 175 J 20 2000 R20 250 200 T 20 2500 2000 R22 225 NS 25 2500 R
25 250 J 30 3000 3000 R32 3200 3200 R
Continuous Current Rating
Positions 13 and 14, with the Automatic Switch (S) option, Non-Automatic Switch (Z) option, Frame-only (F) and 4-Pole with protected neutral (N). Two digits define the continuous current rating of the device.
Frame Size
Amps
Phase Amp
Rating
Oversized Neutral Rating
Frame Size
Amps
* For Switch ratings with oversized neutral, use Phase amperage for the character. Example: NFHF56000S15 is a 150 A Switch with 250 A oversized neutral.Note: Shaded cells are IEC only products
Char.*
Char.*
Phase Amp
Rating
Oversized Neutral Rating
Char. Trip Range (Amperes)
Char. Trip Range (Amperes)
Char. Trip Range (Amperes)
1 9 - 33 31 1125 - 2250 61 75 - 1752 21 - 77 32 1250 - 2500 62 150 - 3503 45 - 165 33 1500 - 3000 63 300 - 7004 90 - 330 34 1500 - 6500 64 600 - 14005 150 - 550 35 1750 - 3500 65 Undefined6 225 - 825 36 2000 - 4000 66 Undefined7 450 - 1650 37 2000 - 6000 67 900 - 100008 600 - 2200 38 2000 - 8000 68 1200 - 100009 750 - 2750 39 Undefined 69 1500 - 10000
10 750 - 1600 40 2500 - 5000 70 1800 - 1000011 8 - 28 41 2500 - 7500 71 4 - 1712 18 - 70 42 3000 - 6000 72 1 - 913 50 - 180 43 3000 - 8000 73 5 - 4514 75 - 260 44 3500 - 7000 74 40 - 12515 100 - 350 45 4000 - 8000 75 110 - 20016 150 - 580 46 4500 - 9000 76 1500 for 24ms
17 250 - 750 47 5000 - 10000 77 1750 for 24ms
18 300 - 1100 48 6000 - 10000 78 2000 for 24ms
19 300 - 1000 49 6000 - 12000 79 2250 for 24ms
20 300 - 800DC 50 8000 - 14000 80 2500 for 24ms
21 400 - 800 51 800 - 1300 81 300 - 600
22 500 - 1000 52 1200 - 1950 82 500 - 850
23 500 - 1200DC 53 1760 - 2860 83 400 - 850
24 450 - 1100 54 24 - 64DC 84 800 - 1450
25 625 - 1250 55 3150 - 6250 85 900 - 1700
26 750 - 1500 56 6327 750 - 1500DC 57 80
28 750 - 1600 58 125
29 875 - 1750 59 15 - 3530 1000 - 2000 60 38 - 88
NOTE: For Powerpact H/J/L with Micrologic Trip Units:
M37=1.3M L-FRAME MCP
M38 = 2.2M H/J-FRAME STANDARD MCP / 2.3M L-FRAME MCP
M58=6.2E-M H/J-FRAME ENERGY MCP/6.3E-M L-FRAME ENERGY MCP
Magnetic Trip Range
Character Option Character Option1 D - type (LI) 0 no options2 S - type (LSI) 1 Option T: Residual type ground fault3 G - type (LSI) 2 Option R: Load monitoring4 M - type (LSI) 3 Option F: LED fault indicators5 U - type (LSI) 4 Options T+F (see above)
5 Options R+F (see above)6 Options T+R (see above)7 Options T+R+F (see above)8 Options F (see above) + I (ammeter)9 Options F+T+I (see above)
Trip Unit Type (1st Digit) Protective Functions (2nd Digit)Electronic Trip Unit (STR)
Positions 13 and 14 following "E" prefix. The first digit defines the trip unit type and the second digit defines the protective function.
Char. Option Char. Option3 Micrologic Type Basic 1 LI (UL)4 Micrologic Type A (Ammeter) 2 LSO (IEC)5 Micrologic Type E (Energy) 3 LSI (UL/IEC)6 Micrologic Type P (Power) 4 LSIG (UL/IEC)
7 Micrologic Type H (Harmonics) 5 LSIV (IEC)
6 LIV (UL/IEC)7 Im Magnetic Only (UL)8 Im and OL Protection (UL)
Positions 13 and 14, following "U." The first character defines the trip type and the second defines the protection type.
For Micrologic Trip Unit (Unn)Control Unit Type (1st Digit) Protection Types (2nd Digit)
A E11
V
Q
Character Option
Q Special CT Calibration (CT characterization)
CT Characterization
Position 19, w hen Position 12 = “U” and Position 13 = “6” or “7”
Catalog Numbering System for MCCBs Based on PLS001 REV. 47 8/12/2013
2nd Char. Option 2nd Char. Option
A 1 - Form C E 1 - Form C (Gold Flashed)
B 2 - Form C F 2 - Form C (Gold Flashed)
C 3 - Form C G 3 - Form C (Gold Flashed)
D 4 - Form C H 4 - Form C (Golf Flashed)
J 8 - Form C K 12 - Form C
Aux Switch (A) Info
For the Aux Sw itch (A) option, the second character gives configuration information:
S
Page 3 of 4
1st Char. Option
E Communications
W or V Programmable Contacts
Q Calibration
# I-Line Phasing
G POWERLINK introducer
A Auxiliary Sw itch
B Alarm / Overcurrent Trip Sw itch
S Shunt Trip
U UVR, no intentional time delay
F Adjustable Time Delay UVR
K Non-adj. Time Delay UVR
V VIGI Module
M Motor Operator
N Com Motor Operator
R Rotary Handle
T Special Terminations
H Plug-in & Draw out Options
D Disconnecting Blocks
L Lug Option
J Key interlock
C Special Ambient
P Add-on Ammeter
Y Special Option
See Sequence Rules on page 4 for order.
Installed Options
The positions follow ing ampacity, or trip unit, or rating plug designate installed options
2nd Char. Option3 Powerlink Gen 3 system
For the POWERLINK option (G), the second character options are:
POWERLINK (G)
Char. w/ Black Handle and Black Bezel Char. w/ Red Handle and Yellow BezelD10 Direct Mounted D20 Direct Mounted D11 Direct Mounted w/ 1 Form C(early make) D21 Direct Mounted w/ 1 Form C(early make)
D12 Direct Mounted w/ 1 Form C(early break) D22 Direct Mounted w/ 1 Form C(early break)
D13 Direct Mounted w/ 2 Form C(early make) D23 Direct Mounted w/ 2 Form C(early make)
D14 Direct Mounted w/ 2 Form C(early break) D24 Direct Mounted w/ 2 Form C(early break)
D15 Direct Mounted w/ 1 EB + 1 EM D25 Direct Mounted w/ 1 EB + 1 EMD16 Direct Mounted w/ 2 EB + 2 EM D26 Direct Mounted w/ 2 EB + 2 EMD17 Direct Mounted w/ 2 EB + 1 EM D27 Direct Mounted w/ 2 EB + 1 EMD18 Direct Mounted w/ 1 EB + 2 EM D28 Direct Mounted w/ 1 EB + 2 EME10 Extended E20 ExtendedE11 Extended w/ 1 Form C(early make) E21 Extended w/ 1 Form C(early make)E12 Extended w/ 1 Form C(early break) E22 Extended w/ 1 Form C(early break)E13 Extended w/ 2 Form C(early make) E23 Extended w/ 2 Form C(early make)E14 Extended w/ 2 Form C(early break) E24 Extended w/ 2 Form C(early break)E15 Extended w/ 1 EB + 1 EM E25 Extended w/ 1 EB + 1 EME16 Extended w/ 2 EB + 2 EM E26 Extended w/ 2 EB + 2 EME17 Extended w/ 2 EB + 1 EM E27 Extended w/ 2 EB + 1 EME18 Extended w/ 1 EB + 2 EM E28 Extended w/ 1 EB + 2 EMT10 Telescopic shaft T20 Telescopic shaftT11 Tele. Shaft w/ 1 Form C(early make) T21 Tele. Shaft w/ 1 Form C(early make)T12 Tele. Shaft w/ 1 Form C(early break) T22 Tele. Shaft w/ 1 Form C(early break)T13 Tele. Shaft w/ 2 Form C(early make) T23 Tele. Shaft w/ 2 Form C(early make)T14 Tele. Shaft w/ 2 Form C(early break) T24 Tele. Shaft w/ 2 Form C(early break)T15 Tele. Shaft w/ 1 EB + 1 EM T25 Tele. Shaft w/ 1 EB + 1 EMT16 Tele. Shaft w/ 2 EB + 2 EM T26 Tele. Shaft w/ 2 EB + 2 EMT17 Tele. Shaft w/ 2 EB + 1 EM T27 Tele. Shaft w/ 2 EB + 1 EMT18 Tele. Shaft w/ 1 EB + 2 EM T28 Tele. Shaft w/ 1 EB + 2 EM
2nd Char. “ON” end “OFF” endA I-LIne Shroud and Jaws (Line Side) English Terminal Nut Inserts for Bus or
Crimp Lug (Default for H/J, D and M/P. Tapped hold for R) (Load Side)
B I-Line Shroud and Jaws (Load Side) Metric Terminal Nut Insert for Bus or Crimp Lug (option for H/J) (Load Side)
C Vertical Terminals Vertical TerminalsD Vertical Terminals Horizontal TerminalsE Vertical Terminals Front Connection TerminalsF Horizontal Terminals Horizontal TerminalsG Horizontal Terminals Vertical TerminalsH Horizontal Terminals Front Connection TerminalsJ Front Connection Terminals Front Connection TerminalsK Front Connection Terminals Vertical TerminalsL Front Connection Terminals Horizontal TerminalsM Studs with Nuts/Washers Installed Lugs Off EndN Lugs On End Studs Off End, No Nuts/WashersP Studs without Nuts/Washers Installed Lugs Off EndQ Lugs On End Lug Right Pole, Stud Left Pole, no
nut/washerR Special Plug-in Jaws Lugs Off EndS Studs On End, No Nuts/Washers Studs Off End, No Nuts/WashersV Plug-in/Drawout w/ front connect lugs Plug-in/Drawout w/ front connect lugs
W * For -F-, Metric terminal nuts both ends (Default for Powerpact L)
For -F-, Metric terminal nuts both ends(Default for Powerpact L)
X * For -M-, lugs on ON endFor -P-, metric terminal nuts on ON end
For -M-, metric terminal nuts OFF endFor -P-, lugs on OFF end
Shaded fields apply to QB/QD/QG/QJ only* W, X apply metric terminal nuts to H/J Frame when termination character (4th) is F, M, P
OptionSpecial Terminations (T)
For the Special Terminations (T) option, the second character options are:
G A S, F/K/U, M/NB
2nd Char. Option
A NO
B NC
C 1 - Form C (SD)
D 1 - Form C (SDE)
E SD + SDE
F NO (Gold Flashed)
G NC (Gold Flashed)
H 1 - Form C (SD) (Gold Flashed)
J 1 - form C (SDE) (Golld Flashed
K SD + SDE (Gold Flashed)
L 1 form C long time trip
N 1 form C instantaneous tripS 1 form C short time trip
For the Alarm Sw itch (B) option, the follow ing character describes contact configuration:
Alarm Switch (B) Info
Char. OptionA ME – 200/440VacB MH - 200/440VacC MH - 440/550VacD MB - 200/440VacE MB - 440/550VacF Insulation monitorG Factory-installed GFM150HDH Factory-installed GFM250JDL Factory-installed ELM150HDM Factory-installed ELM250JD
For the Vigi (V) ground fault protection option, the second characters are:
Vigi (V) Option
V
R T
Catalog Numbering System for MCCBs Based on PLS001 REV. 47 8/12/2013
Char. Option Char. Option
A 120 Volts AC M 6 Volts DC
B 208 Volts AC N 12 Volts DC
C 240 Volts AC O 24 Volts DC
D 277 Volts AC P 48 Volts DC
E 380 Volts AC Q 72 Volts DC
F 415 Volts AC R 125 Volts DC
G 440 Volts AC S 250 Volts DC
H 480 Volts AC T 525 Volts AC
I 347 Volts AC U 30 Volts DC
J 600 Volts AC V 60 Volts DC
K 24 Volts AC W 42 Volts AC
L 48 Volts AC
For the Shunt Trip (S or E), UVR (F, K, or U) & Motor Operator (M or N) options, the second character provides voltage information.
Shunt (S), UVR (U, F, K) and Motor Operator (M or N)
To more installed options (Page 4)
Page 4 of 4
Provision only (vertical mount) C4R/C4 A A -- --Provision only (horizontal mount) C4R/C4/C5/C4E K R B DProvision + one lock (vertical mount) C4R/C4 G H -- --Provision + one lock (horizontal mount) C4R/C4/C5/C4E L S C FProvision + two locks keyed alike (vertical) C4R/C4 N V -- --Provision + two locks keyed alike (horizontal) C5 N V -- --Provision + two locks keyed differently (vertical) C4R/C4 P W -- --
Provision + two locks keyed differently (horizontal) C5 P W -- --
Provision only (vertical mount) includes padlock attachment - Not available on I-line
C4/C5 E E -- --
Char. Option Char. Option Char. OptionA No locks or interlocks 0 No Switches 0 No shuttersB Door interlock 1 Connected 1 ShuttersC Racking interlock 2 DisconnectedD Cylinder lock 3 Conn. + Disc..E Door & Racking interlocksF Door interlock + Cyl. lockG Racking interlock + Cyl. lock
H Door & Racking + CylinderJ No Stationary Part
For the Plug-in and Drawout (H) option, the second, third & fourth character options are:
2nd Char (Interlocks and Locks) 3rd Char (Position switches)
4th Char (Shutters)Plug-in and Drawout (H) options
Char. OptionA Standard Configuration
Disconnect Block (D)
The Disconnect Block (D) option will be followed by one character giving the appropriate number of secondary connections. Note: Disconnect block is already included on all H, J and L frame plug-in or drawout breakers, “DA” suffix is not required for H,J,L frame. DA suffix is for Compact.
2nd Char. OptionA 50 CelsiusB Special Low Temperature Grease
The Special Ambient (C) option will be followed by one character giving the calibration temperature, in Celsius.
Special Ambient (C)
Char OptionA 100AB 150A or160AC 250AD 400AE 600A or 630AF 100A CT onlyG 150A or 160A CT onlyH 250A CT onlyJ 400A CT onlyK 600A or 630A CT onlyL 100A CT w/I max
M 150A or 160A CT w/I max
N 250A CT w/I max
P 400A CT w/I max
Q 600A or 630A CT w/I max
Ammeter (P) Option
For the Ammeter (P) option, the second character options are:
Char. Option Char. OptionA * 3-wire PDC; Factory-installed P * 6-wire PDC; Factory-installedB * 4-wire PDC; Factory-installed Q * 12-wire PDC; Factory-installedC Copper Lugs R High Amp Cu Lugs with Control Wire Tapped
on ON End of ProductD High Amp Copper Lugs S High Amp Cu Lugs with Control Wire Tapped
on OFF End of ProductE High Amp Al Lugs with Control Wire
Tapped on ON End of ProductT High Amp Cu Lugs with Control Wire Tapped
on Both Ends of ProductF High Amp Al Lugs with Control Wire
Tapped on OFF End of ProductU Al lugs with Control Wire Tapped on ON End
of ProductG High Amp Al Lugs with Control Wire
Tapped on Both Ends of ProductV Al lugs with Control Wire Tapped on OFF End
of ProductH High Amp Standard (Al) Lugs W Al lugs with Control Wire Tapped on Both
Ends of ProductK Cu lugs with Control Wire Tapped on
ON End of ProductX * 5-wire PDC; factory-installed
L Cu lugs with Control Wire Tapped on OFF End of Product
Y Low Amp lug on high amp breaker
M Cu lugs with Control Wire Tapped on Both Ends of Product
Z Al lugs with Control Wire Tapped on Left and Center Poles of OFF end of product
Jº Mid range lug on high amp breaker Nº Mid range lug on high amp breaker with control tap
D1^ Stepped Copper Lugs D2^̂ FWBS Copper LugsH1^ Stepped Alum Lugs H2^̂ FWBS Alum Lugs
Y1 Low amp lug on high amp breaker with control tap
Lugs Option (L)The character following the Special Options (L) defines the lug configuration.
* Used with G, H, T, U, or A in position 4. º For M & P-Frame, the "LJ" lug is the 48010-119-52 lug without a control wire tap. This lug is currently only available in the AL800P7K lug kit. For P frame, this lug is only applied to load end. º For M & P-Frame, the "LN" lug is the 48010-119-53 lug with a control wire tap. This lug is currently only available in the AL800P7TK lug kit. For P frame, this lug is only applied to load end.** For 100% rated H/J, only copper lugs can be used. Therefore, the only lug options are K,L,M for 100% rated H/J frame breakers. ̂L-frame option, not for use on I-Line, ^^L-frame option, not for use on 4 Pole
H D
C
Y
P
L
J
More Installed Options
2nd Char. Option 2nd Char. Option
A Marine SA rating, w ith Cu lugs only and marine rating label
P Handle Padlock Attachment, ON or OFF Positions
B Padlockable Push Button Cover (Electrically-operated P-Frame Only)
Q Handle Padlock Attachment, OFF Position Only
C Cable Interlocks R Rod Interlocks
D Test Report S Ship w ithout terminal pad kit
E Longer Handle Extension G Mechanical Operations Counter
F Fungus Treat V External voltage sensing**
J Special Requirements (Japan) W Walking Beam (or equivalent)
K Ship breaker in closed position H Wiring Harness (per installed options)
H1 Wiring Harness for all installed non-communication accessories except external NCT and ZSI
H2 Wiring Harness for all installed non-communication accessories PLUS external NCT
H3 Wiring Harness for all installed non-communication accessories PLUS ZSI
H4 Wiring Harness for all installed non-communication accessories PLUS external NCT and ZSI
M Remote Reset - 110Vac (C4E only) N Remote Reset - 230Vac (C4E only
L Removed Handle Extension A1 Naval SB rating, w ith Cu lugs only and Navalrating label
* • Character “Y” follow ed by a 3-digit number (e.g. Y123) is used to define “customer special”. If the catalog number exceeds 25 characters, some features/ options w ill be combined into this Yxxx (in variable positions) so that the number of characters is 25 or less. • Packing Characters such as RP and Z shall remain part of the catalog number and not be placed into the Yxxx variable positions. ** Valid only for Pow erpact P/R
Special Options (Y):
Catalog Numbering System for MCCBs Based on PLS001 REV. 47 8/12/2013