Technical Data
PanelView Plus SpecificationsCatalog Numbers 2711P 2711PC
PanelView Plus Family PanelView Plus HMI terminals are used for applications with a need to monitor control and display information graphically allowing operators to quickly understand the status of their application All PanelView Plus applications are programmed with FactoryTalk View Studio for Machine Edition (ME) software and have FactoryTalk View ME Station runtime installed on each terminal
This family provides a broad range of rugged terminals offering these featuresbull Premier integration with the Integrated Architecture platformbull Scalable 4- to 15-inch displays with touch screen keypad or both for inputbull Common development softwarebull Real-time monitoring of a terminals displays via a web browser
Use this document along with the Visualization Solutions Selection Guide publication VIEW-SG001 to make decisions on the visualization solutions best suited for your system requirements
Topic Page
Environmental Specifications 2
Certifications 3
PanelView Plus 6 Terminals 4
PanelView Plus 400 and 600 Terminals 11
PanelView Plus Compact Terminals 15
External Power Supply 18
HMI Software 20
Communication Cables 23
Migration Hardware 27
Additional Resources 28
2 PanelView Plus Specifications
Environmental Specifications
The environmental certifications apply to all PanelView Plus terminalsbull PanelView Plus 6 terminals including logic communication modules
and 700 1000 1250 1500 display modulesbull PanelView Plus 400 and 600 terminalsbull PanelView Plus Compact 400 600 and 1000 terminals
Table 1 - Environmental Specifications - PanelView Plus Terminals
Attribute 2711P 2711PC
Temperature operating 0hellip55 degC (32hellip131 degF)
Temperature storage -25hellip70 degC (-13hellip158 degF)
Heat dissipation400 600700 1000 1250 1500
85 BTUhr240 BTU hr
Relative humidity 595 noncondensing
Vibration 0012 in peak-peak 10hellip57 Hz2 g at 57hellip500 Hz
Altitude operating 2000 m (6561 ft)
Shock operating 15 g at 11 ms
Shock nonoperating 30 g at 11 ms
Enclosure ratings NEMA Type 12 13 4X (indoor use only) IEC IP54 IP65
Airborne contaminants For PVPPVP-CE conformal-coated PCBA level productsANSIISA S7104 - 1985 Severity Level G3EN60654-4 1998 Class 3
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 3
Certifications The certifications apply to all PanelView Plus terminalsbull PanelView Plus 6 terminals including logic communication modules
and 700 1000 1250 1500 display modulesbull PanelView Plus 400 and 600 terminalsbull PanelView Plus Compact 400 600 and 1000 terminals
Table 2 - Certifications - PanelView Plus Terminals
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P 2711PC
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314
UL Listed Industrial Control Equipment for use inbull Class I Div 2 Groups A B C Dbull Class I Zone 2 Group IIC (2)
bull Class II Div 2 Groups F Gbull Class III Hazardous Locations
(2) Applies only to the 1250 high-bright display module
CE (EMC) European Union 2004108EC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61000-6-4 Industrial Emissions
CE (LVD) European Union 200695EC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS CISPR 11 Industrial Emissions
Marine(3)
(3) The 700 and 1000 display modules are marked as marine-certified
Products identified with the suffix M in the catalog number are certified to the requirements of one or more marine societies For additional marine-certified components refer to the Product Certification link below this table
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
4 PanelView Plus Specifications
PanelView Plus 6 Terminals The PanelView Plus 6 terminals use modular components allowing for flexible configuration installation and upgrades Factory-assembled terminals with a display module (700 1000 1250 1500) and logic module are available as a single catalog number or as separate components for field installation Optional communication modules can be ordered for additional network communication
The field-replaceable 65 104 121 and 151-in flat-panel color displays come with keypad touch screen or keypadtouch-screen input Other display options are available to meet more stringent environmental conditions
bull High-bright display module for outdoor applicationsbull Conformal-coated displaysbull Marine-certified displaysbull Displays with built-in antiglare overlays
The high-performance logic module runs the Windows CE 60 operating system allowing you to run HMI applications with the ability to also access the desktop For users with more complex application requirements the platform and logic module can be ordered with optional extended features and file viewers
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 3 - Logic Module Features
Features Description
High memory capacity 512 MB nonvolatile flash and 512 MB RAM
Power input AC or DC
Network interface For optional DH+ DH-485 or ControlNet communication module
Communication ports Ethernet RS-232 serial
USB ports bull 2 USB host ports for connecting a USB mouse keyboard printer and USB flash drives that are hot swappable
bull 1 USB device port for connecting a host personal computer
Secure Digital (SD) card slot Hot-swappable card slot supports 1784-CDx SD cards for transferring files upgrading firmware or logging data
Operating system All terminals run the Windows CE 60 operating system (OS) providing OS functionality needed for most users needsbull FTP serverbull VNC clientserverbull PDF readerbull Active X controlsbull Third-party device support
Additional functionality is available by ordering terminals with optional extended featuresbull Internet Explorer web browserbull Remote desktop connectionbull Media playerbull Microsoft file viewers for PowerPoint Excel and Wordbull WordPad text editorbull PDF reader
FactoryTalk View software bull FactoryTalk View Machine Edition software version 60 or later is preloaded and activated on each terminal
bull Single license support for FactoryTalk ViewPoint software version 12 or later gives remote users access to a terminalrsquos displays via standard web browser
bull HMI applications are developed with FactoryTalk View Studio for Machine Edition software which is purchased separately
Reset and Default Switches Provide easy access to diagnostic and repair operations
OptionalExtended Features
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 5
Technical Specifications - PanelView Plus 6 Terminals
Table 4 - Technical Specifications - PanelView Plus 6 Terminals
Attribute 700 Color(1)
2711P-K7C4Dx 2711P-T7C4Dx 2711P-B7C4Dx 2711P-K7C4Ax 2711P-T7C4Ax 2711P-B7C4Ax
1000 Color(1)
2711P-K10C4Dx 2711P-T10C4Dx 2711P-B10C4Dx 2711P-K10C4Ax 2711P-T10C4Ax 2711P-B10C4Ax
1250 Color(1)
2711P-K12C4Dx 2711P-T12C4Dx 2711P-B12C4Dx 2711P-K12C4Ax 2711P-T12C4Ax 2711P-B12C4Ax
1500 Color(1)
2711P-K15C4Dx 2711P-T15C4Dx 2711P-B15C4Dx 2711P-K15C4Ax 2711P-T15C4Ax 2711P-B15C4Ax
Operator input Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT
Display size 65 in 104 in 121 in 15 in
Display area (WxH) 132 x 99 mm (52 x 39 in) 211 x 158 mm (83 x 62 in) 246 x 184 mm (97 x 72 in) 304 x 228 mm (120 x 90 in)
Resolution 640 x 480 18-bit color graphics 800 x 600 18-bit color graphics 1024 x 768 18-bit color graphics
Luminance 300 cdm2 Nits 300 cdm2 Nits(2)
Backlight 50000 h life min field replaceableBacklight for 1250 high-bright display module is not replaceable
Touch screen 8-wire analog resistiveActuation 1 million presses operating force 10hellip110 g
Keypad description Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 22 function keys F1hellipF10 and K1hellipK12
32 function keys F1hellipF16 and K1hellipK16
40 function keys F1hellipF20 and K1hellipK20
40 function keys F1hellipF20 and K1hellipK20
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per monthBattery life 4 year min 25 degC (77 degF)Field-replaceable cat no 2711P-RY2032
Memory 512 MB nonvolatile flash and 512 MB RAM
External storage Secure Digital (SD) card cat no1784-SDx supported by hot-swappable SD card slotUSB flash drives supported by high-speed hot-swappable 20 USB host ports
Operating system Windows CE 60 operating system with or without extended featuresfile viewers
Software FactoryTalk View Machine Edition version 60 or laterFactoryTalk ViewPoint version 12 or later
Communication ports Ethernet (10100 Mbps Auto-MDIMDI-X) RS-232 (2) USB host (1) USB device Network interface for optional DH+DH-485 or ControlNet (scheduled or unscheduled) communication module
Input voltage DC 18hellip32V DC (24V DC nom)
Power consumption DC 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) power supply for 700 to 1500 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 160VA max
Weight approx(3) Keypad 18 kg (41 lb)Touch 17 kg (37 lb)
Keypad 28 kg (62 lb)Touch 25 kg (56 lb)
Keypad 34 kg (75 lb)Touch 32 kg (70 lb)
Keypad 45 kg (99 lb)Touch 42 kg (92 lb)
Dimensions (HxWxD) approx (3) Keypad 193 x 290 x 55 mm758 x 1140 x 218 in
Touch 179 x 246 x 55 mm704 x 968 x 218 in
Keypad 248 x 399 x 55 mm977 x 1572 x 218 in
Touch 248 x 329 x 55 mm 977 x 1297 x 218 in
Keypad 282 x 416 x 55 mm 1112 x 1636 x 218 inTouch 282 x 363 x 55 mm 1112 x 1430 x 218 in
Keypad 330 x 469 x 65 mm 1297 x 1846 x 255 inTouch 330 x 416 x 65 mm 1297 x 1637 x 255 in
Cutout dimensions (HxWxD) Keypad 167 x 264 mm657 x 1039 in
Touch 154 x 220 mm608 x 867 in
Keypad 224 x 375 mm88 x 1475 in
Touch 224 x 305 mm88 x 120 in
Keypad 257 x 390 mm1011 x 1535 in
Touch 257 x 338 mm1011 x 1329 in
Keypad 305 x 419 mm120 x 165 in
Touch 305 x 391 mm120 x 154 in
(1) Replace x in catalog number with an 8 or 9 For catalog numbers ending in 9 the Windows CE operating system includes extended features and file viewers catalog numbers ending in 8 do not support these features
(2) The 1250 high-bright display module cat no 2711P-RDT12H for outdoor operations has a luminance of 1000 cdm2 Nits The backlight is not replaceable(3) Weights and dimensions do not include communication module Add 95 g (021 lb) to the weight for a communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
6 PanelView Plus Specifications
Terminal Dimensions - PanelView Plus 6 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView Plus 6 terminals The 1000 keypad and touch terminal is shown for reference Other models look similar
b a
1000 Keypad
b a
1000 Touch
Table 5 - PanelView Plus 6 Terminal Dimensions
Terminal Type Width Height Depth a(1) Depth b(2) Cutout Width Cutout Height
700 Keypad or KeypadTouch 290 mm1140 in
193 mm758 in
55 mm218 in
83 mm327 in
264 mm1039 in
167 mm659 in
700 Touch 246 mm968 in
179 mm704 in
55 mm218 in
83 mm327 in
220 mm867 in
154 mm608 in
1000 Keypad or KeypadTouch 399 mm1572 in
248 mm977 in
55 mm218 in
83 mm327 in
375 mm1475 in
224 mm88 in
1000 Touch 329 mm1297 in
248 mm977 in
55 mm218 in
83 mm327 in
305 mm1200 in
224 mm88 in
1250 Keypad or KeypadTouch 416 mm1636 in
282 mm1112 in
55 mm218 in
83 mm327 in
390 mm1535 in
257 mm1011 in
1250 Touch 363 mm1430 in
282 mm1112 in
55 mm218 in
83 mm327 in
338 mm1329 in
257 mm1011 in
1250 High-bright Touch 363 mm1430 in
282 mm1112 in
74 mm29 in
101 mm399 in
338 mm1329 in
257 mm1011 in
1500 Keypad or KeypadTouch 469 mm1846 in
330 mm1297 in
65 mm255 in
93 mm365 in
419 mm1650 in
305 mm1200 in
1500 Touch 416 mm1637 in
330 mm1297 in
65 mm255 in
93 mm365 in
391 mm1540 in
305 mm1200 in
(1) Dimension is from display to logic module(2) Dimension is from display to communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 7
Accessories - PanelView Plus 6 Terminals
Tables 6hellip18 lists accessories for the PanelView Plus 6 platform
Table 6 - Display Modules
Cat No Input Type Display Marine Certified
ConformalCoated
Built-inAntiglare Overlay
700 Model
2711P-RDK7C Keypad 7-in color
2711P-RDK7CK Keypad bull
2711P-RDT7C Touch
2711P-RDT7CK Touch bull
2711P-RDT7CM Touch bull
2711P-RDB7C KeypadTouch
2711P-RDB7CK KeypadTouch bull
2711P-RDB7CM KeypadTouch bull
1000 Model
2711P-RDK10C Keypad 10-4 in color
2711P-RDT10C Touch
2711P-RDT10CM Touch bull
2711P-RDB10C KeypadTouch
2711P-RDB10CM KeypadTouch bull
1250 Model
2711P-RDK12C Keypad 121-in color
2711P-RDK12CK Keypad bull
2711P-RDT12C Touch
2711P-RDT12CK Touch bull
2711P-RDT12AG Touch bull
2711P-RDT12H(1)
(1) This catalog number is a high-bright display module indicated by the H at end of cat no that is designed for outdoor applications The high-bright display module can only be used with DC-powered logic modules
Touch
2711P-RDB12C KeypadTouch
2711P-RDB12CK KeypadTouch bull
1500 Model
2711P-RDK15C Keypad 15-in color
2711P-RDT15C Touch
2711P-RDT15AG Touch bull
2711P-RDB15C KeypadTouch
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
2 PanelView Plus Specifications
Environmental Specifications
The environmental certifications apply to all PanelView Plus terminalsbull PanelView Plus 6 terminals including logic communication modules
and 700 1000 1250 1500 display modulesbull PanelView Plus 400 and 600 terminalsbull PanelView Plus Compact 400 600 and 1000 terminals
Table 1 - Environmental Specifications - PanelView Plus Terminals
Attribute 2711P 2711PC
Temperature operating 0hellip55 degC (32hellip131 degF)
Temperature storage -25hellip70 degC (-13hellip158 degF)
Heat dissipation400 600700 1000 1250 1500
85 BTUhr240 BTU hr
Relative humidity 595 noncondensing
Vibration 0012 in peak-peak 10hellip57 Hz2 g at 57hellip500 Hz
Altitude operating 2000 m (6561 ft)
Shock operating 15 g at 11 ms
Shock nonoperating 30 g at 11 ms
Enclosure ratings NEMA Type 12 13 4X (indoor use only) IEC IP54 IP65
Airborne contaminants For PVPPVP-CE conformal-coated PCBA level productsANSIISA S7104 - 1985 Severity Level G3EN60654-4 1998 Class 3
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 3
Certifications The certifications apply to all PanelView Plus terminalsbull PanelView Plus 6 terminals including logic communication modules
and 700 1000 1250 1500 display modulesbull PanelView Plus 400 and 600 terminalsbull PanelView Plus Compact 400 600 and 1000 terminals
Table 2 - Certifications - PanelView Plus Terminals
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P 2711PC
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314
UL Listed Industrial Control Equipment for use inbull Class I Div 2 Groups A B C Dbull Class I Zone 2 Group IIC (2)
bull Class II Div 2 Groups F Gbull Class III Hazardous Locations
(2) Applies only to the 1250 high-bright display module
CE (EMC) European Union 2004108EC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61000-6-4 Industrial Emissions
CE (LVD) European Union 200695EC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS CISPR 11 Industrial Emissions
Marine(3)
(3) The 700 and 1000 display modules are marked as marine-certified
Products identified with the suffix M in the catalog number are certified to the requirements of one or more marine societies For additional marine-certified components refer to the Product Certification link below this table
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
4 PanelView Plus Specifications
PanelView Plus 6 Terminals The PanelView Plus 6 terminals use modular components allowing for flexible configuration installation and upgrades Factory-assembled terminals with a display module (700 1000 1250 1500) and logic module are available as a single catalog number or as separate components for field installation Optional communication modules can be ordered for additional network communication
The field-replaceable 65 104 121 and 151-in flat-panel color displays come with keypad touch screen or keypadtouch-screen input Other display options are available to meet more stringent environmental conditions
bull High-bright display module for outdoor applicationsbull Conformal-coated displaysbull Marine-certified displaysbull Displays with built-in antiglare overlays
The high-performance logic module runs the Windows CE 60 operating system allowing you to run HMI applications with the ability to also access the desktop For users with more complex application requirements the platform and logic module can be ordered with optional extended features and file viewers
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 3 - Logic Module Features
Features Description
High memory capacity 512 MB nonvolatile flash and 512 MB RAM
Power input AC or DC
Network interface For optional DH+ DH-485 or ControlNet communication module
Communication ports Ethernet RS-232 serial
USB ports bull 2 USB host ports for connecting a USB mouse keyboard printer and USB flash drives that are hot swappable
bull 1 USB device port for connecting a host personal computer
Secure Digital (SD) card slot Hot-swappable card slot supports 1784-CDx SD cards for transferring files upgrading firmware or logging data
Operating system All terminals run the Windows CE 60 operating system (OS) providing OS functionality needed for most users needsbull FTP serverbull VNC clientserverbull PDF readerbull Active X controlsbull Third-party device support
Additional functionality is available by ordering terminals with optional extended featuresbull Internet Explorer web browserbull Remote desktop connectionbull Media playerbull Microsoft file viewers for PowerPoint Excel and Wordbull WordPad text editorbull PDF reader
FactoryTalk View software bull FactoryTalk View Machine Edition software version 60 or later is preloaded and activated on each terminal
bull Single license support for FactoryTalk ViewPoint software version 12 or later gives remote users access to a terminalrsquos displays via standard web browser
bull HMI applications are developed with FactoryTalk View Studio for Machine Edition software which is purchased separately
Reset and Default Switches Provide easy access to diagnostic and repair operations
OptionalExtended Features
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 5
Technical Specifications - PanelView Plus 6 Terminals
Table 4 - Technical Specifications - PanelView Plus 6 Terminals
Attribute 700 Color(1)
2711P-K7C4Dx 2711P-T7C4Dx 2711P-B7C4Dx 2711P-K7C4Ax 2711P-T7C4Ax 2711P-B7C4Ax
1000 Color(1)
2711P-K10C4Dx 2711P-T10C4Dx 2711P-B10C4Dx 2711P-K10C4Ax 2711P-T10C4Ax 2711P-B10C4Ax
1250 Color(1)
2711P-K12C4Dx 2711P-T12C4Dx 2711P-B12C4Dx 2711P-K12C4Ax 2711P-T12C4Ax 2711P-B12C4Ax
1500 Color(1)
2711P-K15C4Dx 2711P-T15C4Dx 2711P-B15C4Dx 2711P-K15C4Ax 2711P-T15C4Ax 2711P-B15C4Ax
Operator input Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT
Display size 65 in 104 in 121 in 15 in
Display area (WxH) 132 x 99 mm (52 x 39 in) 211 x 158 mm (83 x 62 in) 246 x 184 mm (97 x 72 in) 304 x 228 mm (120 x 90 in)
Resolution 640 x 480 18-bit color graphics 800 x 600 18-bit color graphics 1024 x 768 18-bit color graphics
Luminance 300 cdm2 Nits 300 cdm2 Nits(2)
Backlight 50000 h life min field replaceableBacklight for 1250 high-bright display module is not replaceable
Touch screen 8-wire analog resistiveActuation 1 million presses operating force 10hellip110 g
Keypad description Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 22 function keys F1hellipF10 and K1hellipK12
32 function keys F1hellipF16 and K1hellipK16
40 function keys F1hellipF20 and K1hellipK20
40 function keys F1hellipF20 and K1hellipK20
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per monthBattery life 4 year min 25 degC (77 degF)Field-replaceable cat no 2711P-RY2032
Memory 512 MB nonvolatile flash and 512 MB RAM
External storage Secure Digital (SD) card cat no1784-SDx supported by hot-swappable SD card slotUSB flash drives supported by high-speed hot-swappable 20 USB host ports
Operating system Windows CE 60 operating system with or without extended featuresfile viewers
Software FactoryTalk View Machine Edition version 60 or laterFactoryTalk ViewPoint version 12 or later
Communication ports Ethernet (10100 Mbps Auto-MDIMDI-X) RS-232 (2) USB host (1) USB device Network interface for optional DH+DH-485 or ControlNet (scheduled or unscheduled) communication module
Input voltage DC 18hellip32V DC (24V DC nom)
Power consumption DC 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) power supply for 700 to 1500 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 160VA max
Weight approx(3) Keypad 18 kg (41 lb)Touch 17 kg (37 lb)
Keypad 28 kg (62 lb)Touch 25 kg (56 lb)
Keypad 34 kg (75 lb)Touch 32 kg (70 lb)
Keypad 45 kg (99 lb)Touch 42 kg (92 lb)
Dimensions (HxWxD) approx (3) Keypad 193 x 290 x 55 mm758 x 1140 x 218 in
Touch 179 x 246 x 55 mm704 x 968 x 218 in
Keypad 248 x 399 x 55 mm977 x 1572 x 218 in
Touch 248 x 329 x 55 mm 977 x 1297 x 218 in
Keypad 282 x 416 x 55 mm 1112 x 1636 x 218 inTouch 282 x 363 x 55 mm 1112 x 1430 x 218 in
Keypad 330 x 469 x 65 mm 1297 x 1846 x 255 inTouch 330 x 416 x 65 mm 1297 x 1637 x 255 in
Cutout dimensions (HxWxD) Keypad 167 x 264 mm657 x 1039 in
Touch 154 x 220 mm608 x 867 in
Keypad 224 x 375 mm88 x 1475 in
Touch 224 x 305 mm88 x 120 in
Keypad 257 x 390 mm1011 x 1535 in
Touch 257 x 338 mm1011 x 1329 in
Keypad 305 x 419 mm120 x 165 in
Touch 305 x 391 mm120 x 154 in
(1) Replace x in catalog number with an 8 or 9 For catalog numbers ending in 9 the Windows CE operating system includes extended features and file viewers catalog numbers ending in 8 do not support these features
(2) The 1250 high-bright display module cat no 2711P-RDT12H for outdoor operations has a luminance of 1000 cdm2 Nits The backlight is not replaceable(3) Weights and dimensions do not include communication module Add 95 g (021 lb) to the weight for a communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
6 PanelView Plus Specifications
Terminal Dimensions - PanelView Plus 6 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView Plus 6 terminals The 1000 keypad and touch terminal is shown for reference Other models look similar
b a
1000 Keypad
b a
1000 Touch
Table 5 - PanelView Plus 6 Terminal Dimensions
Terminal Type Width Height Depth a(1) Depth b(2) Cutout Width Cutout Height
700 Keypad or KeypadTouch 290 mm1140 in
193 mm758 in
55 mm218 in
83 mm327 in
264 mm1039 in
167 mm659 in
700 Touch 246 mm968 in
179 mm704 in
55 mm218 in
83 mm327 in
220 mm867 in
154 mm608 in
1000 Keypad or KeypadTouch 399 mm1572 in
248 mm977 in
55 mm218 in
83 mm327 in
375 mm1475 in
224 mm88 in
1000 Touch 329 mm1297 in
248 mm977 in
55 mm218 in
83 mm327 in
305 mm1200 in
224 mm88 in
1250 Keypad or KeypadTouch 416 mm1636 in
282 mm1112 in
55 mm218 in
83 mm327 in
390 mm1535 in
257 mm1011 in
1250 Touch 363 mm1430 in
282 mm1112 in
55 mm218 in
83 mm327 in
338 mm1329 in
257 mm1011 in
1250 High-bright Touch 363 mm1430 in
282 mm1112 in
74 mm29 in
101 mm399 in
338 mm1329 in
257 mm1011 in
1500 Keypad or KeypadTouch 469 mm1846 in
330 mm1297 in
65 mm255 in
93 mm365 in
419 mm1650 in
305 mm1200 in
1500 Touch 416 mm1637 in
330 mm1297 in
65 mm255 in
93 mm365 in
391 mm1540 in
305 mm1200 in
(1) Dimension is from display to logic module(2) Dimension is from display to communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 7
Accessories - PanelView Plus 6 Terminals
Tables 6hellip18 lists accessories for the PanelView Plus 6 platform
Table 6 - Display Modules
Cat No Input Type Display Marine Certified
ConformalCoated
Built-inAntiglare Overlay
700 Model
2711P-RDK7C Keypad 7-in color
2711P-RDK7CK Keypad bull
2711P-RDT7C Touch
2711P-RDT7CK Touch bull
2711P-RDT7CM Touch bull
2711P-RDB7C KeypadTouch
2711P-RDB7CK KeypadTouch bull
2711P-RDB7CM KeypadTouch bull
1000 Model
2711P-RDK10C Keypad 10-4 in color
2711P-RDT10C Touch
2711P-RDT10CM Touch bull
2711P-RDB10C KeypadTouch
2711P-RDB10CM KeypadTouch bull
1250 Model
2711P-RDK12C Keypad 121-in color
2711P-RDK12CK Keypad bull
2711P-RDT12C Touch
2711P-RDT12CK Touch bull
2711P-RDT12AG Touch bull
2711P-RDT12H(1)
(1) This catalog number is a high-bright display module indicated by the H at end of cat no that is designed for outdoor applications The high-bright display module can only be used with DC-powered logic modules
Touch
2711P-RDB12C KeypadTouch
2711P-RDB12CK KeypadTouch bull
1500 Model
2711P-RDK15C Keypad 15-in color
2711P-RDT15C Touch
2711P-RDT15AG Touch bull
2711P-RDB15C KeypadTouch
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 3
Certifications The certifications apply to all PanelView Plus terminalsbull PanelView Plus 6 terminals including logic communication modules
and 700 1000 1250 1500 display modulesbull PanelView Plus 400 and 600 terminalsbull PanelView Plus Compact 400 600 and 1000 terminals
Table 2 - Certifications - PanelView Plus Terminals
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P 2711PC
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314
UL Listed Industrial Control Equipment for use inbull Class I Div 2 Groups A B C Dbull Class I Zone 2 Group IIC (2)
bull Class II Div 2 Groups F Gbull Class III Hazardous Locations
(2) Applies only to the 1250 high-bright display module
CE (EMC) European Union 2004108EC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61000-6-4 Industrial Emissions
CE (LVD) European Union 200695EC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS CISPR 11 Industrial Emissions
Marine(3)
(3) The 700 and 1000 display modules are marked as marine-certified
Products identified with the suffix M in the catalog number are certified to the requirements of one or more marine societies For additional marine-certified components refer to the Product Certification link below this table
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
4 PanelView Plus Specifications
PanelView Plus 6 Terminals The PanelView Plus 6 terminals use modular components allowing for flexible configuration installation and upgrades Factory-assembled terminals with a display module (700 1000 1250 1500) and logic module are available as a single catalog number or as separate components for field installation Optional communication modules can be ordered for additional network communication
The field-replaceable 65 104 121 and 151-in flat-panel color displays come with keypad touch screen or keypadtouch-screen input Other display options are available to meet more stringent environmental conditions
bull High-bright display module for outdoor applicationsbull Conformal-coated displaysbull Marine-certified displaysbull Displays with built-in antiglare overlays
The high-performance logic module runs the Windows CE 60 operating system allowing you to run HMI applications with the ability to also access the desktop For users with more complex application requirements the platform and logic module can be ordered with optional extended features and file viewers
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 3 - Logic Module Features
Features Description
High memory capacity 512 MB nonvolatile flash and 512 MB RAM
Power input AC or DC
Network interface For optional DH+ DH-485 or ControlNet communication module
Communication ports Ethernet RS-232 serial
USB ports bull 2 USB host ports for connecting a USB mouse keyboard printer and USB flash drives that are hot swappable
bull 1 USB device port for connecting a host personal computer
Secure Digital (SD) card slot Hot-swappable card slot supports 1784-CDx SD cards for transferring files upgrading firmware or logging data
Operating system All terminals run the Windows CE 60 operating system (OS) providing OS functionality needed for most users needsbull FTP serverbull VNC clientserverbull PDF readerbull Active X controlsbull Third-party device support
Additional functionality is available by ordering terminals with optional extended featuresbull Internet Explorer web browserbull Remote desktop connectionbull Media playerbull Microsoft file viewers for PowerPoint Excel and Wordbull WordPad text editorbull PDF reader
FactoryTalk View software bull FactoryTalk View Machine Edition software version 60 or later is preloaded and activated on each terminal
bull Single license support for FactoryTalk ViewPoint software version 12 or later gives remote users access to a terminalrsquos displays via standard web browser
bull HMI applications are developed with FactoryTalk View Studio for Machine Edition software which is purchased separately
Reset and Default Switches Provide easy access to diagnostic and repair operations
OptionalExtended Features
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 5
Technical Specifications - PanelView Plus 6 Terminals
Table 4 - Technical Specifications - PanelView Plus 6 Terminals
Attribute 700 Color(1)
2711P-K7C4Dx 2711P-T7C4Dx 2711P-B7C4Dx 2711P-K7C4Ax 2711P-T7C4Ax 2711P-B7C4Ax
1000 Color(1)
2711P-K10C4Dx 2711P-T10C4Dx 2711P-B10C4Dx 2711P-K10C4Ax 2711P-T10C4Ax 2711P-B10C4Ax
1250 Color(1)
2711P-K12C4Dx 2711P-T12C4Dx 2711P-B12C4Dx 2711P-K12C4Ax 2711P-T12C4Ax 2711P-B12C4Ax
1500 Color(1)
2711P-K15C4Dx 2711P-T15C4Dx 2711P-B15C4Dx 2711P-K15C4Ax 2711P-T15C4Ax 2711P-B15C4Ax
Operator input Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT
Display size 65 in 104 in 121 in 15 in
Display area (WxH) 132 x 99 mm (52 x 39 in) 211 x 158 mm (83 x 62 in) 246 x 184 mm (97 x 72 in) 304 x 228 mm (120 x 90 in)
Resolution 640 x 480 18-bit color graphics 800 x 600 18-bit color graphics 1024 x 768 18-bit color graphics
Luminance 300 cdm2 Nits 300 cdm2 Nits(2)
Backlight 50000 h life min field replaceableBacklight for 1250 high-bright display module is not replaceable
Touch screen 8-wire analog resistiveActuation 1 million presses operating force 10hellip110 g
Keypad description Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 22 function keys F1hellipF10 and K1hellipK12
32 function keys F1hellipF16 and K1hellipK16
40 function keys F1hellipF20 and K1hellipK20
40 function keys F1hellipF20 and K1hellipK20
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per monthBattery life 4 year min 25 degC (77 degF)Field-replaceable cat no 2711P-RY2032
Memory 512 MB nonvolatile flash and 512 MB RAM
External storage Secure Digital (SD) card cat no1784-SDx supported by hot-swappable SD card slotUSB flash drives supported by high-speed hot-swappable 20 USB host ports
Operating system Windows CE 60 operating system with or without extended featuresfile viewers
Software FactoryTalk View Machine Edition version 60 or laterFactoryTalk ViewPoint version 12 or later
Communication ports Ethernet (10100 Mbps Auto-MDIMDI-X) RS-232 (2) USB host (1) USB device Network interface for optional DH+DH-485 or ControlNet (scheduled or unscheduled) communication module
Input voltage DC 18hellip32V DC (24V DC nom)
Power consumption DC 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) power supply for 700 to 1500 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 160VA max
Weight approx(3) Keypad 18 kg (41 lb)Touch 17 kg (37 lb)
Keypad 28 kg (62 lb)Touch 25 kg (56 lb)
Keypad 34 kg (75 lb)Touch 32 kg (70 lb)
Keypad 45 kg (99 lb)Touch 42 kg (92 lb)
Dimensions (HxWxD) approx (3) Keypad 193 x 290 x 55 mm758 x 1140 x 218 in
Touch 179 x 246 x 55 mm704 x 968 x 218 in
Keypad 248 x 399 x 55 mm977 x 1572 x 218 in
Touch 248 x 329 x 55 mm 977 x 1297 x 218 in
Keypad 282 x 416 x 55 mm 1112 x 1636 x 218 inTouch 282 x 363 x 55 mm 1112 x 1430 x 218 in
Keypad 330 x 469 x 65 mm 1297 x 1846 x 255 inTouch 330 x 416 x 65 mm 1297 x 1637 x 255 in
Cutout dimensions (HxWxD) Keypad 167 x 264 mm657 x 1039 in
Touch 154 x 220 mm608 x 867 in
Keypad 224 x 375 mm88 x 1475 in
Touch 224 x 305 mm88 x 120 in
Keypad 257 x 390 mm1011 x 1535 in
Touch 257 x 338 mm1011 x 1329 in
Keypad 305 x 419 mm120 x 165 in
Touch 305 x 391 mm120 x 154 in
(1) Replace x in catalog number with an 8 or 9 For catalog numbers ending in 9 the Windows CE operating system includes extended features and file viewers catalog numbers ending in 8 do not support these features
(2) The 1250 high-bright display module cat no 2711P-RDT12H for outdoor operations has a luminance of 1000 cdm2 Nits The backlight is not replaceable(3) Weights and dimensions do not include communication module Add 95 g (021 lb) to the weight for a communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
6 PanelView Plus Specifications
Terminal Dimensions - PanelView Plus 6 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView Plus 6 terminals The 1000 keypad and touch terminal is shown for reference Other models look similar
b a
1000 Keypad
b a
1000 Touch
Table 5 - PanelView Plus 6 Terminal Dimensions
Terminal Type Width Height Depth a(1) Depth b(2) Cutout Width Cutout Height
700 Keypad or KeypadTouch 290 mm1140 in
193 mm758 in
55 mm218 in
83 mm327 in
264 mm1039 in
167 mm659 in
700 Touch 246 mm968 in
179 mm704 in
55 mm218 in
83 mm327 in
220 mm867 in
154 mm608 in
1000 Keypad or KeypadTouch 399 mm1572 in
248 mm977 in
55 mm218 in
83 mm327 in
375 mm1475 in
224 mm88 in
1000 Touch 329 mm1297 in
248 mm977 in
55 mm218 in
83 mm327 in
305 mm1200 in
224 mm88 in
1250 Keypad or KeypadTouch 416 mm1636 in
282 mm1112 in
55 mm218 in
83 mm327 in
390 mm1535 in
257 mm1011 in
1250 Touch 363 mm1430 in
282 mm1112 in
55 mm218 in
83 mm327 in
338 mm1329 in
257 mm1011 in
1250 High-bright Touch 363 mm1430 in
282 mm1112 in
74 mm29 in
101 mm399 in
338 mm1329 in
257 mm1011 in
1500 Keypad or KeypadTouch 469 mm1846 in
330 mm1297 in
65 mm255 in
93 mm365 in
419 mm1650 in
305 mm1200 in
1500 Touch 416 mm1637 in
330 mm1297 in
65 mm255 in
93 mm365 in
391 mm1540 in
305 mm1200 in
(1) Dimension is from display to logic module(2) Dimension is from display to communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 7
Accessories - PanelView Plus 6 Terminals
Tables 6hellip18 lists accessories for the PanelView Plus 6 platform
Table 6 - Display Modules
Cat No Input Type Display Marine Certified
ConformalCoated
Built-inAntiglare Overlay
700 Model
2711P-RDK7C Keypad 7-in color
2711P-RDK7CK Keypad bull
2711P-RDT7C Touch
2711P-RDT7CK Touch bull
2711P-RDT7CM Touch bull
2711P-RDB7C KeypadTouch
2711P-RDB7CK KeypadTouch bull
2711P-RDB7CM KeypadTouch bull
1000 Model
2711P-RDK10C Keypad 10-4 in color
2711P-RDT10C Touch
2711P-RDT10CM Touch bull
2711P-RDB10C KeypadTouch
2711P-RDB10CM KeypadTouch bull
1250 Model
2711P-RDK12C Keypad 121-in color
2711P-RDK12CK Keypad bull
2711P-RDT12C Touch
2711P-RDT12CK Touch bull
2711P-RDT12AG Touch bull
2711P-RDT12H(1)
(1) This catalog number is a high-bright display module indicated by the H at end of cat no that is designed for outdoor applications The high-bright display module can only be used with DC-powered logic modules
Touch
2711P-RDB12C KeypadTouch
2711P-RDB12CK KeypadTouch bull
1500 Model
2711P-RDK15C Keypad 15-in color
2711P-RDT15C Touch
2711P-RDT15AG Touch bull
2711P-RDB15C KeypadTouch
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
4 PanelView Plus Specifications
PanelView Plus 6 Terminals The PanelView Plus 6 terminals use modular components allowing for flexible configuration installation and upgrades Factory-assembled terminals with a display module (700 1000 1250 1500) and logic module are available as a single catalog number or as separate components for field installation Optional communication modules can be ordered for additional network communication
The field-replaceable 65 104 121 and 151-in flat-panel color displays come with keypad touch screen or keypadtouch-screen input Other display options are available to meet more stringent environmental conditions
bull High-bright display module for outdoor applicationsbull Conformal-coated displaysbull Marine-certified displaysbull Displays with built-in antiglare overlays
The high-performance logic module runs the Windows CE 60 operating system allowing you to run HMI applications with the ability to also access the desktop For users with more complex application requirements the platform and logic module can be ordered with optional extended features and file viewers
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 3 - Logic Module Features
Features Description
High memory capacity 512 MB nonvolatile flash and 512 MB RAM
Power input AC or DC
Network interface For optional DH+ DH-485 or ControlNet communication module
Communication ports Ethernet RS-232 serial
USB ports bull 2 USB host ports for connecting a USB mouse keyboard printer and USB flash drives that are hot swappable
bull 1 USB device port for connecting a host personal computer
Secure Digital (SD) card slot Hot-swappable card slot supports 1784-CDx SD cards for transferring files upgrading firmware or logging data
Operating system All terminals run the Windows CE 60 operating system (OS) providing OS functionality needed for most users needsbull FTP serverbull VNC clientserverbull PDF readerbull Active X controlsbull Third-party device support
Additional functionality is available by ordering terminals with optional extended featuresbull Internet Explorer web browserbull Remote desktop connectionbull Media playerbull Microsoft file viewers for PowerPoint Excel and Wordbull WordPad text editorbull PDF reader
FactoryTalk View software bull FactoryTalk View Machine Edition software version 60 or later is preloaded and activated on each terminal
bull Single license support for FactoryTalk ViewPoint software version 12 or later gives remote users access to a terminalrsquos displays via standard web browser
bull HMI applications are developed with FactoryTalk View Studio for Machine Edition software which is purchased separately
Reset and Default Switches Provide easy access to diagnostic and repair operations
OptionalExtended Features
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 5
Technical Specifications - PanelView Plus 6 Terminals
Table 4 - Technical Specifications - PanelView Plus 6 Terminals
Attribute 700 Color(1)
2711P-K7C4Dx 2711P-T7C4Dx 2711P-B7C4Dx 2711P-K7C4Ax 2711P-T7C4Ax 2711P-B7C4Ax
1000 Color(1)
2711P-K10C4Dx 2711P-T10C4Dx 2711P-B10C4Dx 2711P-K10C4Ax 2711P-T10C4Ax 2711P-B10C4Ax
1250 Color(1)
2711P-K12C4Dx 2711P-T12C4Dx 2711P-B12C4Dx 2711P-K12C4Ax 2711P-T12C4Ax 2711P-B12C4Ax
1500 Color(1)
2711P-K15C4Dx 2711P-T15C4Dx 2711P-B15C4Dx 2711P-K15C4Ax 2711P-T15C4Ax 2711P-B15C4Ax
Operator input Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT
Display size 65 in 104 in 121 in 15 in
Display area (WxH) 132 x 99 mm (52 x 39 in) 211 x 158 mm (83 x 62 in) 246 x 184 mm (97 x 72 in) 304 x 228 mm (120 x 90 in)
Resolution 640 x 480 18-bit color graphics 800 x 600 18-bit color graphics 1024 x 768 18-bit color graphics
Luminance 300 cdm2 Nits 300 cdm2 Nits(2)
Backlight 50000 h life min field replaceableBacklight for 1250 high-bright display module is not replaceable
Touch screen 8-wire analog resistiveActuation 1 million presses operating force 10hellip110 g
Keypad description Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 22 function keys F1hellipF10 and K1hellipK12
32 function keys F1hellipF16 and K1hellipK16
40 function keys F1hellipF20 and K1hellipK20
40 function keys F1hellipF20 and K1hellipK20
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per monthBattery life 4 year min 25 degC (77 degF)Field-replaceable cat no 2711P-RY2032
Memory 512 MB nonvolatile flash and 512 MB RAM
External storage Secure Digital (SD) card cat no1784-SDx supported by hot-swappable SD card slotUSB flash drives supported by high-speed hot-swappable 20 USB host ports
Operating system Windows CE 60 operating system with or without extended featuresfile viewers
Software FactoryTalk View Machine Edition version 60 or laterFactoryTalk ViewPoint version 12 or later
Communication ports Ethernet (10100 Mbps Auto-MDIMDI-X) RS-232 (2) USB host (1) USB device Network interface for optional DH+DH-485 or ControlNet (scheduled or unscheduled) communication module
Input voltage DC 18hellip32V DC (24V DC nom)
Power consumption DC 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) power supply for 700 to 1500 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 160VA max
Weight approx(3) Keypad 18 kg (41 lb)Touch 17 kg (37 lb)
Keypad 28 kg (62 lb)Touch 25 kg (56 lb)
Keypad 34 kg (75 lb)Touch 32 kg (70 lb)
Keypad 45 kg (99 lb)Touch 42 kg (92 lb)
Dimensions (HxWxD) approx (3) Keypad 193 x 290 x 55 mm758 x 1140 x 218 in
Touch 179 x 246 x 55 mm704 x 968 x 218 in
Keypad 248 x 399 x 55 mm977 x 1572 x 218 in
Touch 248 x 329 x 55 mm 977 x 1297 x 218 in
Keypad 282 x 416 x 55 mm 1112 x 1636 x 218 inTouch 282 x 363 x 55 mm 1112 x 1430 x 218 in
Keypad 330 x 469 x 65 mm 1297 x 1846 x 255 inTouch 330 x 416 x 65 mm 1297 x 1637 x 255 in
Cutout dimensions (HxWxD) Keypad 167 x 264 mm657 x 1039 in
Touch 154 x 220 mm608 x 867 in
Keypad 224 x 375 mm88 x 1475 in
Touch 224 x 305 mm88 x 120 in
Keypad 257 x 390 mm1011 x 1535 in
Touch 257 x 338 mm1011 x 1329 in
Keypad 305 x 419 mm120 x 165 in
Touch 305 x 391 mm120 x 154 in
(1) Replace x in catalog number with an 8 or 9 For catalog numbers ending in 9 the Windows CE operating system includes extended features and file viewers catalog numbers ending in 8 do not support these features
(2) The 1250 high-bright display module cat no 2711P-RDT12H for outdoor operations has a luminance of 1000 cdm2 Nits The backlight is not replaceable(3) Weights and dimensions do not include communication module Add 95 g (021 lb) to the weight for a communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
6 PanelView Plus Specifications
Terminal Dimensions - PanelView Plus 6 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView Plus 6 terminals The 1000 keypad and touch terminal is shown for reference Other models look similar
b a
1000 Keypad
b a
1000 Touch
Table 5 - PanelView Plus 6 Terminal Dimensions
Terminal Type Width Height Depth a(1) Depth b(2) Cutout Width Cutout Height
700 Keypad or KeypadTouch 290 mm1140 in
193 mm758 in
55 mm218 in
83 mm327 in
264 mm1039 in
167 mm659 in
700 Touch 246 mm968 in
179 mm704 in
55 mm218 in
83 mm327 in
220 mm867 in
154 mm608 in
1000 Keypad or KeypadTouch 399 mm1572 in
248 mm977 in
55 mm218 in
83 mm327 in
375 mm1475 in
224 mm88 in
1000 Touch 329 mm1297 in
248 mm977 in
55 mm218 in
83 mm327 in
305 mm1200 in
224 mm88 in
1250 Keypad or KeypadTouch 416 mm1636 in
282 mm1112 in
55 mm218 in
83 mm327 in
390 mm1535 in
257 mm1011 in
1250 Touch 363 mm1430 in
282 mm1112 in
55 mm218 in
83 mm327 in
338 mm1329 in
257 mm1011 in
1250 High-bright Touch 363 mm1430 in
282 mm1112 in
74 mm29 in
101 mm399 in
338 mm1329 in
257 mm1011 in
1500 Keypad or KeypadTouch 469 mm1846 in
330 mm1297 in
65 mm255 in
93 mm365 in
419 mm1650 in
305 mm1200 in
1500 Touch 416 mm1637 in
330 mm1297 in
65 mm255 in
93 mm365 in
391 mm1540 in
305 mm1200 in
(1) Dimension is from display to logic module(2) Dimension is from display to communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 7
Accessories - PanelView Plus 6 Terminals
Tables 6hellip18 lists accessories for the PanelView Plus 6 platform
Table 6 - Display Modules
Cat No Input Type Display Marine Certified
ConformalCoated
Built-inAntiglare Overlay
700 Model
2711P-RDK7C Keypad 7-in color
2711P-RDK7CK Keypad bull
2711P-RDT7C Touch
2711P-RDT7CK Touch bull
2711P-RDT7CM Touch bull
2711P-RDB7C KeypadTouch
2711P-RDB7CK KeypadTouch bull
2711P-RDB7CM KeypadTouch bull
1000 Model
2711P-RDK10C Keypad 10-4 in color
2711P-RDT10C Touch
2711P-RDT10CM Touch bull
2711P-RDB10C KeypadTouch
2711P-RDB10CM KeypadTouch bull
1250 Model
2711P-RDK12C Keypad 121-in color
2711P-RDK12CK Keypad bull
2711P-RDT12C Touch
2711P-RDT12CK Touch bull
2711P-RDT12AG Touch bull
2711P-RDT12H(1)
(1) This catalog number is a high-bright display module indicated by the H at end of cat no that is designed for outdoor applications The high-bright display module can only be used with DC-powered logic modules
Touch
2711P-RDB12C KeypadTouch
2711P-RDB12CK KeypadTouch bull
1500 Model
2711P-RDK15C Keypad 15-in color
2711P-RDT15C Touch
2711P-RDT15AG Touch bull
2711P-RDB15C KeypadTouch
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 5
Technical Specifications - PanelView Plus 6 Terminals
Table 4 - Technical Specifications - PanelView Plus 6 Terminals
Attribute 700 Color(1)
2711P-K7C4Dx 2711P-T7C4Dx 2711P-B7C4Dx 2711P-K7C4Ax 2711P-T7C4Ax 2711P-B7C4Ax
1000 Color(1)
2711P-K10C4Dx 2711P-T10C4Dx 2711P-B10C4Dx 2711P-K10C4Ax 2711P-T10C4Ax 2711P-B10C4Ax
1250 Color(1)
2711P-K12C4Dx 2711P-T12C4Dx 2711P-B12C4Dx 2711P-K12C4Ax 2711P-T12C4Ax 2711P-B12C4Ax
1500 Color(1)
2711P-K15C4Dx 2711P-T15C4Dx 2711P-B15C4Dx 2711P-K15C4Ax 2711P-T15C4Ax 2711P-B15C4Ax
Operator input Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT Color active-matrix TFT
Display size 65 in 104 in 121 in 15 in
Display area (WxH) 132 x 99 mm (52 x 39 in) 211 x 158 mm (83 x 62 in) 246 x 184 mm (97 x 72 in) 304 x 228 mm (120 x 90 in)
Resolution 640 x 480 18-bit color graphics 800 x 600 18-bit color graphics 1024 x 768 18-bit color graphics
Luminance 300 cdm2 Nits 300 cdm2 Nits(2)
Backlight 50000 h life min field replaceableBacklight for 1250 high-bright display module is not replaceable
Touch screen 8-wire analog resistiveActuation 1 million presses operating force 10hellip110 g
Keypad description Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 22 function keys F1hellipF10 and K1hellipK12
32 function keys F1hellipF16 and K1hellipK16
40 function keys F1hellipF20 and K1hellipK20
40 function keys F1hellipF20 and K1hellipK20
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per monthBattery life 4 year min 25 degC (77 degF)Field-replaceable cat no 2711P-RY2032
Memory 512 MB nonvolatile flash and 512 MB RAM
External storage Secure Digital (SD) card cat no1784-SDx supported by hot-swappable SD card slotUSB flash drives supported by high-speed hot-swappable 20 USB host ports
Operating system Windows CE 60 operating system with or without extended featuresfile viewers
Software FactoryTalk View Machine Edition version 60 or laterFactoryTalk ViewPoint version 12 or later
Communication ports Ethernet (10100 Mbps Auto-MDIMDI-X) RS-232 (2) USB host (1) USB device Network interface for optional DH+DH-485 or ControlNet (scheduled or unscheduled) communication module
Input voltage DC 18hellip32V DC (24V DC nom)
Power consumption DC 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) power supply for 700 to 1500 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 160VA max
Weight approx(3) Keypad 18 kg (41 lb)Touch 17 kg (37 lb)
Keypad 28 kg (62 lb)Touch 25 kg (56 lb)
Keypad 34 kg (75 lb)Touch 32 kg (70 lb)
Keypad 45 kg (99 lb)Touch 42 kg (92 lb)
Dimensions (HxWxD) approx (3) Keypad 193 x 290 x 55 mm758 x 1140 x 218 in
Touch 179 x 246 x 55 mm704 x 968 x 218 in
Keypad 248 x 399 x 55 mm977 x 1572 x 218 in
Touch 248 x 329 x 55 mm 977 x 1297 x 218 in
Keypad 282 x 416 x 55 mm 1112 x 1636 x 218 inTouch 282 x 363 x 55 mm 1112 x 1430 x 218 in
Keypad 330 x 469 x 65 mm 1297 x 1846 x 255 inTouch 330 x 416 x 65 mm 1297 x 1637 x 255 in
Cutout dimensions (HxWxD) Keypad 167 x 264 mm657 x 1039 in
Touch 154 x 220 mm608 x 867 in
Keypad 224 x 375 mm88 x 1475 in
Touch 224 x 305 mm88 x 120 in
Keypad 257 x 390 mm1011 x 1535 in
Touch 257 x 338 mm1011 x 1329 in
Keypad 305 x 419 mm120 x 165 in
Touch 305 x 391 mm120 x 154 in
(1) Replace x in catalog number with an 8 or 9 For catalog numbers ending in 9 the Windows CE operating system includes extended features and file viewers catalog numbers ending in 8 do not support these features
(2) The 1250 high-bright display module cat no 2711P-RDT12H for outdoor operations has a luminance of 1000 cdm2 Nits The backlight is not replaceable(3) Weights and dimensions do not include communication module Add 95 g (021 lb) to the weight for a communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
6 PanelView Plus Specifications
Terminal Dimensions - PanelView Plus 6 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView Plus 6 terminals The 1000 keypad and touch terminal is shown for reference Other models look similar
b a
1000 Keypad
b a
1000 Touch
Table 5 - PanelView Plus 6 Terminal Dimensions
Terminal Type Width Height Depth a(1) Depth b(2) Cutout Width Cutout Height
700 Keypad or KeypadTouch 290 mm1140 in
193 mm758 in
55 mm218 in
83 mm327 in
264 mm1039 in
167 mm659 in
700 Touch 246 mm968 in
179 mm704 in
55 mm218 in
83 mm327 in
220 mm867 in
154 mm608 in
1000 Keypad or KeypadTouch 399 mm1572 in
248 mm977 in
55 mm218 in
83 mm327 in
375 mm1475 in
224 mm88 in
1000 Touch 329 mm1297 in
248 mm977 in
55 mm218 in
83 mm327 in
305 mm1200 in
224 mm88 in
1250 Keypad or KeypadTouch 416 mm1636 in
282 mm1112 in
55 mm218 in
83 mm327 in
390 mm1535 in
257 mm1011 in
1250 Touch 363 mm1430 in
282 mm1112 in
55 mm218 in
83 mm327 in
338 mm1329 in
257 mm1011 in
1250 High-bright Touch 363 mm1430 in
282 mm1112 in
74 mm29 in
101 mm399 in
338 mm1329 in
257 mm1011 in
1500 Keypad or KeypadTouch 469 mm1846 in
330 mm1297 in
65 mm255 in
93 mm365 in
419 mm1650 in
305 mm1200 in
1500 Touch 416 mm1637 in
330 mm1297 in
65 mm255 in
93 mm365 in
391 mm1540 in
305 mm1200 in
(1) Dimension is from display to logic module(2) Dimension is from display to communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 7
Accessories - PanelView Plus 6 Terminals
Tables 6hellip18 lists accessories for the PanelView Plus 6 platform
Table 6 - Display Modules
Cat No Input Type Display Marine Certified
ConformalCoated
Built-inAntiglare Overlay
700 Model
2711P-RDK7C Keypad 7-in color
2711P-RDK7CK Keypad bull
2711P-RDT7C Touch
2711P-RDT7CK Touch bull
2711P-RDT7CM Touch bull
2711P-RDB7C KeypadTouch
2711P-RDB7CK KeypadTouch bull
2711P-RDB7CM KeypadTouch bull
1000 Model
2711P-RDK10C Keypad 10-4 in color
2711P-RDT10C Touch
2711P-RDT10CM Touch bull
2711P-RDB10C KeypadTouch
2711P-RDB10CM KeypadTouch bull
1250 Model
2711P-RDK12C Keypad 121-in color
2711P-RDK12CK Keypad bull
2711P-RDT12C Touch
2711P-RDT12CK Touch bull
2711P-RDT12AG Touch bull
2711P-RDT12H(1)
(1) This catalog number is a high-bright display module indicated by the H at end of cat no that is designed for outdoor applications The high-bright display module can only be used with DC-powered logic modules
Touch
2711P-RDB12C KeypadTouch
2711P-RDB12CK KeypadTouch bull
1500 Model
2711P-RDK15C Keypad 15-in color
2711P-RDT15C Touch
2711P-RDT15AG Touch bull
2711P-RDB15C KeypadTouch
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
6 PanelView Plus Specifications
Terminal Dimensions - PanelView Plus 6 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView Plus 6 terminals The 1000 keypad and touch terminal is shown for reference Other models look similar
b a
1000 Keypad
b a
1000 Touch
Table 5 - PanelView Plus 6 Terminal Dimensions
Terminal Type Width Height Depth a(1) Depth b(2) Cutout Width Cutout Height
700 Keypad or KeypadTouch 290 mm1140 in
193 mm758 in
55 mm218 in
83 mm327 in
264 mm1039 in
167 mm659 in
700 Touch 246 mm968 in
179 mm704 in
55 mm218 in
83 mm327 in
220 mm867 in
154 mm608 in
1000 Keypad or KeypadTouch 399 mm1572 in
248 mm977 in
55 mm218 in
83 mm327 in
375 mm1475 in
224 mm88 in
1000 Touch 329 mm1297 in
248 mm977 in
55 mm218 in
83 mm327 in
305 mm1200 in
224 mm88 in
1250 Keypad or KeypadTouch 416 mm1636 in
282 mm1112 in
55 mm218 in
83 mm327 in
390 mm1535 in
257 mm1011 in
1250 Touch 363 mm1430 in
282 mm1112 in
55 mm218 in
83 mm327 in
338 mm1329 in
257 mm1011 in
1250 High-bright Touch 363 mm1430 in
282 mm1112 in
74 mm29 in
101 mm399 in
338 mm1329 in
257 mm1011 in
1500 Keypad or KeypadTouch 469 mm1846 in
330 mm1297 in
65 mm255 in
93 mm365 in
419 mm1650 in
305 mm1200 in
1500 Touch 416 mm1637 in
330 mm1297 in
65 mm255 in
93 mm365 in
391 mm1540 in
305 mm1200 in
(1) Dimension is from display to logic module(2) Dimension is from display to communication module
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 7
Accessories - PanelView Plus 6 Terminals
Tables 6hellip18 lists accessories for the PanelView Plus 6 platform
Table 6 - Display Modules
Cat No Input Type Display Marine Certified
ConformalCoated
Built-inAntiglare Overlay
700 Model
2711P-RDK7C Keypad 7-in color
2711P-RDK7CK Keypad bull
2711P-RDT7C Touch
2711P-RDT7CK Touch bull
2711P-RDT7CM Touch bull
2711P-RDB7C KeypadTouch
2711P-RDB7CK KeypadTouch bull
2711P-RDB7CM KeypadTouch bull
1000 Model
2711P-RDK10C Keypad 10-4 in color
2711P-RDT10C Touch
2711P-RDT10CM Touch bull
2711P-RDB10C KeypadTouch
2711P-RDB10CM KeypadTouch bull
1250 Model
2711P-RDK12C Keypad 121-in color
2711P-RDK12CK Keypad bull
2711P-RDT12C Touch
2711P-RDT12CK Touch bull
2711P-RDT12AG Touch bull
2711P-RDT12H(1)
(1) This catalog number is a high-bright display module indicated by the H at end of cat no that is designed for outdoor applications The high-bright display module can only be used with DC-powered logic modules
Touch
2711P-RDB12C KeypadTouch
2711P-RDB12CK KeypadTouch bull
1500 Model
2711P-RDK15C Keypad 15-in color
2711P-RDT15C Touch
2711P-RDT15AG Touch bull
2711P-RDB15C KeypadTouch
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 7
Accessories - PanelView Plus 6 Terminals
Tables 6hellip18 lists accessories for the PanelView Plus 6 platform
Table 6 - Display Modules
Cat No Input Type Display Marine Certified
ConformalCoated
Built-inAntiglare Overlay
700 Model
2711P-RDK7C Keypad 7-in color
2711P-RDK7CK Keypad bull
2711P-RDT7C Touch
2711P-RDT7CK Touch bull
2711P-RDT7CM Touch bull
2711P-RDB7C KeypadTouch
2711P-RDB7CK KeypadTouch bull
2711P-RDB7CM KeypadTouch bull
1000 Model
2711P-RDK10C Keypad 10-4 in color
2711P-RDT10C Touch
2711P-RDT10CM Touch bull
2711P-RDB10C KeypadTouch
2711P-RDB10CM KeypadTouch bull
1250 Model
2711P-RDK12C Keypad 121-in color
2711P-RDK12CK Keypad bull
2711P-RDT12C Touch
2711P-RDT12CK Touch bull
2711P-RDT12AG Touch bull
2711P-RDT12H(1)
(1) This catalog number is a high-bright display module indicated by the H at end of cat no that is designed for outdoor applications The high-bright display module can only be used with DC-powered logic modules
Touch
2711P-RDB12C KeypadTouch
2711P-RDB12CK KeypadTouch bull
1500 Model
2711P-RDK15C Keypad 15-in color
2711P-RDT15C Touch
2711P-RDT15AG Touch bull
2711P-RDB15C KeypadTouch
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
8 PanelView Plus Specifications
Table 7 - Logic Modules
Cat No Power Input
Nonvolatile Flash RAM Memory Communication Conformal
Coated Included Software
Without Extended Features
2711P-RP8A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface for
communication module
bull Windows CE 60 operating system without extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP8D DC 512 MB512 MB
2711P-RP8DK DC 512 MB512 MB bull
With Extended Features
2711P-RP9A AC 512 MB512 MB bull Ethernetbull RS-232bull Network interface
communication module
bull Windows CE 60 operating system with extended featuresfile viewers
bull FactoryTalk View Machine Edition runtime version 60 or later
bull FactoryTalk ViewPoint version 12 or later
2711P-RP9D DC 512 MB512 MB
2711P-RP9DK DC 512 MB512 MB bull
Table 8 - Communication Modules
Cat NoCommunication Conformal
CoatedMarine CertifiedDH+ DH-485 ControlNet (1)
(1) Scheduled and unscheduled communication
2711P-RN6 bull bull
2711P-RN6K bull bull bull
2711P-RN15S bull bull
2711P-RN15SK bull bull
Table 9 - Secure Digital (SD) Cards
Cat No Description
1784-SD1 1 GB Secure Digital (SD) card
1784-SD2 2 GB Secure Digital (SD) card
2711C-RCSD USB to SD adapter for secure Digital card (SD)
Table 10 - Function Key Legend Inserts
Cat NoPanelView Plus 6 Terminal Model(1)
(1) Applies to keypad and keypadtouch-screen terminals
Includes
2711P-RFK7 700 keypad
Blank legend inserts and software
2711P-RFK10 1000 keypad
2711P-RFK12 1250 keypad
22711P-RFK15 1500 keypad
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 9
Table 11 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RGK7700
bull bull
2711P-RGT7 bull
2711P-RGK101000
bull bull
2711P-RGT10 bull
2711P-RGK121250
bull bull
2711P-RGT12 bull
2711P-RGK151500
bull bull
2711P-RGT15 bull
Table 12 - Solar Visor
Cat No Description
2711P-RVT12 Solar visor for 1250 high-bright display module cat no 2711P-RDT12H
Table 13 - Mounting Hardware
Cat No Description Quantity
2711P-RTMC Mounting clips 8
Table 14 - Battery Replacement
Cat No Description Quantity
2711P-RY2032 Replacement battery 1
Table 15 - Power Supply and Power Terminal Blocks
Cat No Description Quantity
2711P-RSACDIN DIN-rail power supply AC-to-DC 85hellip265V AC 47hellip63 Hz 1
2711P-RTBAC3 AC power terminal block 10
2711P-RTBDC2 2-pin DC power terminal block 10
Table 16 - Programming Cable
Cat No Description Length
2711C-CBL-UU02 USB host to USB device programming cable 2 m (65 ft)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
10 PanelView Plus Specifications
Table 17 - Backlight Replacements
Cat No PanelView Plus 6 Display Module Size Series Number of
Backlights
2711P-RL7C 700 A and B 1
2711P-RL7C2 C and D 1
2711P-RL10C 1000 A 1
2711P-RL10C2 B and C 1
2711P-RL12C 1250 A and B 2
2711P-RL12C2 C 1
2711P-RL15C 1500 B 2
Table 18 - Bezel Replacements
Cat No PanelView Plus 6 Terminal Model
Operator Input
Keypad Touch KeyTouch
2711P-RBK7
700
bull
2711P-RBT7 bull
2711P-RBB7 bull
2711P-RBK10
1000
bull
2711P-RBT10 bull
2711P-RBB10 bull
2711P-RBK12
1250
bull
2711P-RBT12 bull
2711P-RBT12H(1)
(1) Applies to the cat no 2711P-RDT12H 1250 high-bright display module
bull
2711P-RBB12 bull
2711P-RBK15
1500
bull
2711P-RBT15 bull
2711P-RBB15 bull
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 11
PanelView Plus 400 and 600 Terminals
The PanelView Plus 400 and 600 terminals combine a 35 or 55-in display logic module memory and power (AC or DC) in the base unit The terminals offer a range of display and input options
bull PanelView Plus 400 grayscale graphic displays with keypad inputbull PanelView Plus 400 color graphic displays with keypad or combination
keypadtouch-screen inputbull PanelView Plus 600 color or grayscale graphic displays with keypad touch
screen or combination keypadtouch-screen input
Two base units are available
Other features include the followingbull Unique mounting mechanism requiring a single die-cut and no special
tools for installationbull Replaceable bezel ID labels for terminal or system identificationbull Function key legend kit and software for customizing the function key
legends of PanelView Plus 600 keypad terminalsbull Same panel cutouts as the PanelView Standard 550 terminals
Each terminal is preloaded with FactoryTalk View Machine Edition that does not require activation Applications are created using FactoryTalk View Studio for Machine Edition software
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Table 19 - Base-configured Terminals
Base Unit Contains
RS-232 unit This base unit contains the followingbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingFor applications with limited budgets that require only PLC communication the RS-232 port of this unit supports DF1 DH-485 and other multivendor PLC protocols
Ethernet and RS-232 unit This base unit contains the followingbull Ethernet portbull RS-232 communication portbull USB port connects to mouse keyboard printer bar code
scanner and other devicesbull CompactFlash slot for file transfers and data loggingbull Network interface for optional communication modules
including DH-485 DH+ ControlNet and isolated RS-232For distributed and complex applications requiring PLC communication this unit can provide simultaneous communication with multiple networks
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
12 PanelView Plus Specifications
Technical Specifications - PanelView Plus 400 and 600 Terminals
Table 20 - Technical Specifications - PanelView Plus 400 and 600 Terminals
Attribute 400 Grayscale
2711P-K4M400 Color
2711P-K4C -B4C600 Grayscale
2711P-K6M -T6M -B6M600 Color
2711P-K6C -T6C -B6C
Operator input Keypad Keypad or KeypadTouch Keypad Touch or KeyTouch Keypad Touch or KeyTouch
Display type Grayscale passive-matrix FSTN
Color active-matrix TFT Grayscale passive-matrix FSTN
Color active-matrix TFT
Display size 38 in 35 in 55 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in)
Resolution 320 x 240 32-level gray 320 x 24018-bit color graphics
320 x 240 32-level gray 320 x 24018-bit color graphics
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life min not replaceable
Touch screen mdash Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Analog resistiveActuation 1 million pressesOperating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) 10 function keys (F1hellipF10)
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery Not replaceable - Battery life 5 year min 25 degC (77 degF)
Memory 64 MB nonvolatile flash64 MB RAM for bitmaps or recording data (not expandable) 20 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition or Enterprise Series
Communication ports RS-232 and 1 USB or Ethernet RS-232 and 1 USB plus optional DH-485 DH+ ControlNet(1) or Isolated RS-232 communication module
Input voltage DC 18hellip30V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for non-isolated 400 and 600 DC powered terminals 85hellip264V AC 120VA max
Input voltage AC 85hellip264V AC 47hellip63 Hz
Power consumption AC 60VA max
Weight approx Keypad 562 g (124 lb)Touch mdash
Keypad 562 g (124 lb)Touch mdash
Keypad 930 g (205 lb)Touch 789 g (174 lb)
Dimensions (HxWxD) approx Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch mdash
Keypad 152 x 185 x 90 mm60 x 728 x 354 in
Touch 152 x 185 x 90 mm60 x 728 x 354 in
Keypad 167 x 266 x 98 mm658 x 1047 x 386 in
Touch 152 x 185 x 98 mm60 x 728 x 386 in
Cutout dimensions (HxWxD) Keypad 123 x 156 mm486 x 615 in
Touch mdash
Keypad 123 x 156 mm486 x 615 in
Touch 123 x 156 mm486 x 615 in
Keypad 142 x 241 mm561 x 950 in
Touch 123 x 156 mm486 x 615 in
(1) ControlNet network requires FactoryTalk View Machine Edition software version 40 or later
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 13
Terminal Dimensions - PanelView Plus 400 and 600 Terminals
The table provides overall dimensions and cutout dimensions for the PanelView 400 and 600 terminals The 600 touch and keypad and touch terminal are shown for reference
+
ba
600 Keypad Shown
ab
600 Touch Shown
Table 21 - PanelView Plus 400 and 600 Terminal Dimensions
Terminal Type Width Height Depth a Depth b Cutout Width Cutout Height
400 Keypad 185 mm728 in
152 mm600 in
60 mm235 in
90 mm354 in
156 mm615 in
123 mm486 in
600 Keypad and Touch 266 mm1057 in
167 mm658 in
68 mm268 in
98 mm386 in
241 mm950 in
142 mm561 in
600 Touch 185 mm728 in
152 mm600 in
68 mm268 in
98 mm386 in
156 mm615 in
123 mm486 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
14 PanelView Plus Specifications
Accessories - PanelView Plus 400 and 600 Terminals
Tables 22hellip27 lists accessories for the PanelView Plus 400 and 600 terminals
Table 22 - Communication Modules
Cat NoCommunication
DH+ DH-485 ControlNet(1)
(1) Scheduled and unscheduled communication
RS-232 Isolated
2711P-RN3 bull
2711P-RN8 bull
2711P-RN15C bull
2711P-RN22C bull
Table 23 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelInput Type
Keypad Touch KeyTouch
2711P-RGK4 400 Grayscale bull
2711P-RGB4 400 Color bull bull
2711P-RGK6600 Grayscale or Color
bull bull
2711P-RGT6 bull
Table 24 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA adapter
Table 25 - Power Terminal Blocks
Cat No Description Quantity
2711P-RVAC AC power terminal block 10
2711-TBDC DC power terminal block 10
Table 26 - Mounting Hardware
Cat No Description Quantity
2711P-RTFC Mounting levers 8
Table 27 - Function Key Legend Inserts
Cat No Terminal Model Includes
2711P-RFK6 600 keypad and keypadtouch Blank legend inserts and software
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 15
PanelView Plus Compact Terminals
The PanelView Plus Compact 400 600 and 1000 terminals provide a solution for midsize applications requiring fewer displays and alarms in a FactoryTalk View ME application These terminals are a subset of the PanelView Plus family with selective hardware and software functionality They are the preferred HMI solution for many of the CompactLogix controllers
These are the major features of the PanelView Plus Compact terminalsbull Preferred HMI for CompactLogix controllersbull RS-232 serial port Ethernet port USB port (two on 1000 model) DC
power input and CompactFlash Type 1 slotbull Serial and Ethernet communication onlybull Connection to a single controller by using either RSLinx Enterprise
software version 520 or later or KEPServer softwarebull 25 displays and 200 alarm messages supported in the FactoryTalk View
Compact Machine Edition application and runtime softwarebull Fixed hardware configurations without the addition or replacement of
modular components
For a complete listing of catalog number selections refer to the Visualization Solutions Selection Guide publication VIEW-SG001
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
16 PanelView Plus Specifications
Technical Specifications - PanelView Plus Compact Terminals
Table 28 - Technical Specifications - PanelView Plus Compact Terminals
Attribute 400 Grayscale
2711PC-K4M20D400 Color
2711PC-B4C20D600 Grayscale
2711PC-T6M20D600 Color
2711PC-T6C20D1000 Color
2711PC-T10C4D1
Operator input Keypad KeypadTouch Touch Touch Touch
Display type Passive-matrix FSTN Active-matrix TFT Passive-matrix FSTN Active-matrix TFT Active-matrix TFT
Display size 38 in 35 in 55 in 104 in
Display area (WxH) 78 x 59 mm (307 x 232 in) 71 x 53 mm (28 x 21 in) 111 x 84 mm (437 x 330 in) 211 x 158 mm (83 x 62 in)
Resolution 320 x 240 32-level gray 320 x 240 18-bit color 320 x 240 32-level gray 320 x 240 18-bit color 640 x 480 18-bit color
Luminance 120 cdm2 Nits 200 cdm2 Nits 300 cdm2 Nits 300 cdm2 Nits
Backlight LED CCFL 50000 h life minNot replaceable
CCFL 50000 h life min field replaceable
Touch screen mdash Analog resistive actuation 1 million presses operating force 10hellip110 g
Keypad description Poly-domed membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Stainless-steel membraneNumeric navigation and function keysActuation 1 million presses operating force 340 g
Keypad function keys 8 function keys (F1hellipF8) mdash mdash mdash
Real-time clock Battery-backed clock timestamps critical data plusmn2 minutes per month
Battery 5 year min 25 degC (77 degF)Not replaceable
4 year min 25 degC (77 degF)Replacement 2711P-RY2032
Memory 64 MB nonvolatile flash64 MB RAM non-expandable20 MB for application storage
64 MB nonvolatile flash64 MB RAM non-expandable25 MB for application storage
External storage 256 MB (cat no 2711P-RC3) or 512 MB (cat no 2711P-RC4) CompactFlash card
Software FactoryTalk View Studio for Machine Edition version 51
Communication ports RS-232 Ethernet 1 USB no communication interface RS-232 Ethernet 2 USB no communication interface
Input voltage DC 18hellip30V DC (24V DC nom) 18hellip32V DC (24V DC nom)
Power consumption DC 25 W max (10 A at 24V DC) 70 W max (29 A at 24V DC)
External power supply Cat no 2711P-RSACDIN Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply for DC powered terminals 85hellip264V AC 120VA max
Weight approx 562 g (124 lb) 562 g (124 lb) 789 g (174 lb) 26 kg (57 lb)
Dimensions (HxWxD) approx
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 90 mm60 x 728 x 354 in
152 x 185 x 98 mm60 x 728 x 386 in
248 x 329 x 55 mm977 x 1297 x 218 in
Cutout dimensions (HxWxD)
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
123 x 156 mm486 x 615 in
224 x 305 mm88 x 120 in
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 17
Accessories - PanelView Plus Compact Terminals
Tables 29hellip34 lists accessories for the PanelView Plus Compact terminals
Table 29 - Antiglare Overlays
Cat No(1)
(1) Three overlays are shipped with each catalog number
Terminal ModelOperator Input
Keypad Touch KeyTouch
2711P-RGK4 400 grayscale bull
2711P-RGB4 400 color bull bull
2711P-RGT6 600 color grayscale bull
2711P-RGT10 1000 color bull
Table 30 - CompactFlash Cards
Cat No Description
2711P-RC3 256 MB blank CompactFlash card
2711P-RC4 512 MB blank CompactFlash card
2711P-RCH CompactFlash to PCMCIA Adapter
Table 31 - Backlight Replacement
Cat No Description
2711P-RL10C2 Color backlight replacement for the 1000 series B and C displays
Table 32 - Bezel Replacements
Cat No Description
2711P-RBT10 Replacement bezel for the 1000 touch terminal
Table 33 - Mounting Hardware
Cat No Terminal Model Description Quantity
2711P-RTFC 400 and 600 Mounting levers 8
2711P-RTMC 1000 Mounting clips 8
Table 34 - Power Terminal Blocks
Cat No Terminal Model Description Quantity
2711-TBDC 400 and 600 DC power terminal block 10
2711P-RTBDC2 700 to 1500 series E or later
2-pin DC power terminal block 10
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
18 PanelView Plus Specifications
External Power Supply This SELV or PELV 24V DC power supply can be used to power any of the
PanelView Plus terminals with a DC power input This power supply provides
protection so that under normal and single fault conditions the voltage
between conductors and earth ground does not exceed a safe value
Table 35 - Environmental Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Temperature operatingIEC 60068-2-1 (Test Ad Operating Cold)IEC 60068-2-2 (Test Bd Operating Dry Heat)IEC 60068-2-14 (Test Nb Operating Thermal Shock)
0hellip55 degC (32hellip131 degF)
Temperature storageIEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold)IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat)IEC 60068-2-14 (Test Nb Unpackaged Nonoperating Thermal Shock)
-40hellip85 degC (-40hellip185 degF)
Relative humidityIEC 60068-2-30 (Test Db Unpackaged Nonoperating Damp Heat)
595 noncondensing
VibrationIEC 60068-2-6 (Test Fc Operating)
5 g at 10hellip500 Hz
Shock operatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
15 g
Shock nonoperatingIEC 60068-2-27 (Test Ea Unpackaged Shock)
30 g
ESD immunityIEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunityIEC 61000-4-3
10Vm with 1 kHz sine-wave 80 AM from 30hellip1000 MHz
EFTB immunityIEC 61000-4-4
plusmn2 kV at 5 kHz on power ports
Surge transient immunityIEC 61000-4-5
plusmn1 kV line-line (DM) and plusmn2 kV line-earth (CM) on AC power ports
Conducted RF immunityIEC 61000-4-6
10V rms with 1kHz sine wave 80 AM from 150 kHzhellip80 MHz
Enclosure type rating None (open-style)
Power conductorsWire Size
Category
12 gauge (4 mm2 ) max solid or stranded copper wire rated at 75 degC (167 degF) or greater12 mm ((364 in) insulation max1 (1)
(1) Use this conductor capacity information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Table 36 - Certifications - 2711P-RSACDIN Power Supply
Certification(1)
(1) When marked See the Product Certification link at httpwwwabcom for Declarations of Conformity Certificates and other certification details
2711P-RSACDIN
c-UL-us UL Listed Industrial Control Equipment certified for US and Canada See UL File E10314UL Listed for Class Division 2 Groups A B C and D for US and Canada
CE European Union 89336EEC EMC Directive compliant withbull EN 61000-6-2 Industrial Immunitybull EN 61326 MeasControlLab Industrial Requirementsbull EN 61000-6-4 Industrial EmissionsEuropean Union 73235EEC Low Voltage Directive compliant withbull EN 61131-2 Programmable Controllers
C-Tick Australian Radiocommunications Act compliant withASNZS 2064 Industrial Emissions
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 19
Table 37 - Technical Specifications - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Input Specifications
Supply voltage nom 120V AC 47hellip63 Hz 17 A max230V AC 47hellip63 Hz 11 A max
Voltage range 85hellip265V AC
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Interruption Output voltage will stay within specification when input drops out for 12 cycle at 47 Hz 85V AC with max load
Output Specifications
Output voltage nom +24V DC SELV
Voltage range 204hellip276V DC includes noise and 5 AC ripple
Inrush current 40 A typical 1 AC cycle at Vin 265V AC 55 degC (131 degF)
Minimum load 50 mA
Overvoltage protection Output internally limited to 35V DC Cycle power to re-energize
Overcurrent protection Current limit 32 A min (107 min)
Leakage current 05 mA rms max at rated input and output
Isolation voltage 2830V DC for 1 second
Table 38 - Dimensions - 2711P-RSACDIN Power Supply
Attribute 2711P-RSACDIN
Mounting Horizontal on a DIN railWall or panel mount with cat no 1794-NM1 panel mounting kit
Terminal screw torque 05hellip06 Nbullm (5hellip7 lbbullin)
Dimensions (HxWxD) approx 87 x 68 x 69 mm (34 x 27 x 27 in)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
20 PanelView Plus Specifications
HMI Software All PanelView Plus terminals are configured with FactoryTalk View Studio software and have an integrated runtime system called FactoryTalk View Machine Edition Station
Machine Edition Station runs projects developed with FactoryTalk View Studio Two versions of FactoryTalk View Studio support application development for PanelView Plus terminals
You can import PanelView StandardPanelBuilder32 and PanelView e applications into FactoryTalk View Studio as Machine Edition applications using the Machine Edition Import Wizard The Import Wizard steps you through a few options such as scaling to a new screen resolution size and then converts objects text tags and communication configurations to ones that are available in Machine Edition
FactoryTalk ViewPoint software an add-on to FactoryTalk View Studio software allows plant managers production supervisors system integrators and other key stakeholders to view real-time plant floor operations remotely from a web browser FactoryTalk ViewPoint enabled displays are fully scalable and animated in the browser The remote user can also view displays that are not the active display of the terminal
Each PanelView Plus 6 terminal contains one license supporting a single client connection to the terminal No additional software is required
For a complete list of available HMI software visit httpwwwrockwellautomationcomrockwellsoftware
Table 39 - HMI Software for PanelView Plus Terminals
Cat No Description
9701-VWSTMENE FactoryTalk View Studio for Machine Edition - Configuration software for developing and testing machine level human machine interface (HMI) applications
9701-VWSTENE FactoryTalk View Studio - Configuration software for developing and testing machine level and supervisory level human machine interface (HMI) applications
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 21
Software ComparisonTECHNOLOGY Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Operating systems (32-bit) bull Windows XPbull Windows Server 2003bull Windows Vista Businessbull Windows Server 2008
bull Windows XPbull Windows 7 Professionalbull Windows CEbull Windows Vista Home BasicVista Businessbull Windows Server 20032008
bull Windows XP2000NT9xbull Windows Server 2003
Embedded platforms
Windows domain security
OPCActiveX
FactoryTalk enabled
Server-side VBA
Client-side VBA
ARCHITECTURE Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Primary application Supervisory level single-station or multiple-server multiple-client
Machine level single-station Supervisory level single station or single server multiple client
Tag-based HMI bull Windows XP2000NT9xbull Windows Server 2003
Direct referencing
Network (Distributed) Local
Max number of serversclients 1050 120
FactoryTalk ViewPoint (1)
RSView32 web server
Thin clients (terminal services)
Multi-user development
Remote configuration at runtime
Redundancy - data server
Redundancy - HMI server Active display
(1) Supported only on PanelView Plus terminals
FEATURES Customer Requirements FactoryTalk View Site Edition FactoryTalk View Machine Edition RSView32
Animation - visibility color fill horizontal and vertical position width height rotation horizontal and vertical slider and more
And touch And touch And touch
Alarms bull Tag-based and device-based bull Digital and analogbull Definable alarm severitiesbull Alarm log
bull State-based (from controller)bull Alarm log
bull Tag-basedbull Digital and analogbull Definable alarm severitiesbull Alarm log
Data logging bull 20 data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
bull 1 data log model per projectbull With up to 100 tagsbull 300K records maxbull Export to dbf
bull 20 plus data log models per projectbull Each with up to 10000 tagsbull Log to ODBC or proprietary database
Trending TrendX 40 TrendX 40 subset TrendX 31 and native
Security bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
bull Display-basedbull Local or Windows security
bull Security assigned to tags graphic displays macros commands OLE objects
bull Local or Windows security
Other features bull Test run macrosbull Derived tags bull Event detector
bull Test run macrosbull Derived tags
bull Test run macrosbull Derived tags bull Event detector
Pricing model bull Display-based pricing bull Multiple levels
bull Included with PanelView Plus or display-based pricing
bull Multiple levels for FactoryTalk View ME Station
bull Tag-based pricingbull Multiple levels
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
22 PanelView Plus Specifications
Software Selection
FactoryTalk View Studio for Machine Edition software is configuration
software for developing and testing machine level HMI applications It
includes RSLinx Enterprise and KEPServer Enterprise
FactoryTalk View Machine Edition Station is the runtime environment used to run FactoryTalk View ME projects created with FactoryTalk View Studio software on any computer with the Windows 7 Professional XPVista Home BasicVista BusinessWindows Server 20032008 operating system including the industrial computers FactoryTalk View ME Station is included with all PanelView Plus terminals
FactoryTalk ViewPoint software is an add-on to FactoryTalk View Studio
software allowing casual users to view real-time plant floor operations
remotely from a web browser FactoryTalk ViewPoint server and a single client
access license is included with the purchase of a PanelView Plus terminal No
other catalog numbers are required to use FactoryTalk ViewPoint software
with PanelView Plus terminals
Table 40 - FactoryTalk View Machine Edition (ME) Software
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWSTMENE FactoryTalk View Studio Machine Edition
Table 41 - FactoryTalk View Machine Edition (ME) Station Runtime
Cat No(1)
(1) Order localized versions of the software by replacing EN in the catalog number with DE for German FR for French JP for Japanese or ZH for Chinese
Description
9701-VWMR015AENE FactoryTalk View ME Station runtime 15 displays
9701-VWMR030AENE FactoryTalk View ME Station runtime 30 displays
9701-VWMR075AENE FactoryTalk View ME Station runtime 75 displays
9701-VWMR250AENE FactoryTalk View ME Station runtime 250 displays RS-232 operating cable 9-pin D Shell to 8-pin Mini DIN
Table 42 - FactoryTalk ViewPoint Software
Cat No(1)
(1) Order any of these catalog numbers to use FactoryTalk ViewPoint software with FactoryTalk View SE network or local applications
Description
9552-VWP01RENE FactoryTalk ViewPoint 1 client system (read only)
9552-VWP03RENE FactoryTalk ViewPoint 3 client system (read only)
9552-VWP05RENE FactoryTalk ViewPoint 5 client system (read only)
9552-VWP10RENE FactoryTalk ViewPoint 10 client system (read only)
9552-VWP25RENE FactoryTalk ViewPoint 25 client system (read only)
9552-VWP50RENE FactoryTalk ViewPoint 50 client system (read only)
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 23
Communication Cables The table provides a general list of cables used by the PanelView Plus terminals All PanelView Plus terminals use a standard Ethernet cable for application transfers between a computer and the terminal
PanelView Plus Runtime CablesTables 44hellip47 list required runtime cables for PanelView Plus 400600 and PanelView Plus 6 (700 1000 1250 1500) terminals
Table 43 - Cables
Cat No Description Length
2711C-CBL-UU02(1)
(1) This cable is used only by PanelView Plus 6 terminals
USB host to USB device programming cable 2 m (65 ft)
2711-NC13 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 5 m (164 ft)
2711-NC14 RS-232 operatingprogram cable 9-pin D-shell to 9-pin D-shell 10 m (327 ft)
2711-NC17 Remote RS-232 cable assembly 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC21 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 5 m (164 ft)
2711-NC22 RS-232 operating cable 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
1761-CBL-AS03DH-485 network cable 6-pin Phoenix to RJ45
3 m (10 ft)
1761-CBL-AS09 9 m (30 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable 43 m (14 ft)
Table 44 - Runtime Communication Cables PanelView Plus Terminals to SLC Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
SLC 500 501 502CH1 RJ45 (DH-485)
SLC 503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)(DH-485)
SLC 504CH1 (DH+)
SLC 505CH1 (ENET)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
mdash mdash mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ Module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 3
1747-C10 (2 m6 ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
Use AIC+ module(1761-NET-AIC)
to connect to Port 3
1761-CBL-AS03 (3 m10 ft)
1761-CBL-AS09 (9 m30 ft)
mdash mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 700 to 1500Requires 2711P-RN15S -RN15SK
mdash mdash mdash mdash mdash
EtherNetIP EtherNetIP portPanelView Plus 400 to 1500
mdash Use 1761-NET-ENI modulewith Ethernet cable
mdash mdash1585J-M type cable or
2711P-CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashmdash
shieldedtwinaxial
cable (1770-CD)
mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) EtherNetIP direct connection from the terminal to an SLC 505 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
24 PanelView Plus Specifications
Table 45 - Runtime Communication Cables PanelView Plus Terminals to PLC-5 and MicroLogix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
PLC-5 PLC-5C PLC-5ECH0 (25-pin RS-232)
(DF1)
MicroLogix 1400 1500LRPCH1CH2 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1100 1200 1400 1500LSP
CH0 (8-pin Mini DIN)(DF1 or DH-485)
MicroLogix 1100 1400 Ethernet
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) (3)
mdash
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
mdash mdashUse AIC+ module(1761-NET-AIC)
to connect to Port 3mdash
ControlNet
ControlNet portPanelView Plus 400 and 600Requires 2711P-RN15CPanelView Plus 400 to 1500Requires 2711P-RN15S -RN15SK
To PLC-5C with ControlNet cable
mdash mdash mdash
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
To PLC-5E with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft) (2)
Use 1761-NET-ENI modulewith Ethernet cable
1585J-M type cable or 2711P- CBL-EX04 (4 m14 ft) (2)
DH+ DH+ portPanelView Plus 400 and 600Requires 2711P-RN8PanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
shielded twinaxial cable(1770-CD)
mdash mdash mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and the controller use the 2711P-CBL-EX04 crossover cable(3) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply
Table 46 - Runtime Communication Cables PanelView Plus Terminals to Logix Controllers
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485
RS-232 (DH-485) port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600 only)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)2706-NC13 (3 m10 ft)
DH-485 portPanelView Plus 400 and 600 requires 2711P-RN3(1)
PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6Kmdash
Use AIC+ module(1761-NET-AIC)
to connect to port 3
ControlNetControlNet portPanelView Plus 400 and 600 requires 2711P-RN15CPanelView Plus 700 to 1500 requires 2711P-RN15S -RN15SK
Use 1756-CNB module with ControlNet cable1769-L35CR 1769-L32C 1768-CNB or 1768-CNBR
with ControlNet cable
EtherNetIPEtherNetIP portPanelView Plus 400 to 1500
Use 1756-EN2T or 1756-ENBT module with1585J-M type cable or
2711P- CBL-EX04 (4 m14 ft)(2)
To 1769-L35E 1769-L23E 1769-L32E or 1768-ENBT module with 1585J-M type cable
or 2711P- CBL-EX04 (4 m14 ft)(2)
DH+ DH+ portPanelView Plus 400 and 600 requires 2711P-RN8PanelView Plus 700 to 1500 requires 2711P-RN6 -RN6K
Use 1756-DHRIO module withshielded twinaxial cable (1770-CD) mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 25
PanelView Plus Compact Runtime Cables
Tables 48hellip51 list cables required to connect PanelView Plus Compact terminals to controllers and interface modules for runtime operations
Table 47 - Runtime Communication Cables PanelView Plus Terminals to Interface Modules
Protocol PanelView Plus Comm Port400 600 700 1000 1250 1500 1747-AIC
1761-NET-AIC 1771-NET-ENI
Port 1 (9-pin) Port 2(8-pin Mini DIN)
Port 3(DH-485)
Port 2(8-pin Mini DIN)
DF1 RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
1761-CBL-AP00 (5 m)1761-CBL-PM02 (2 m)2711-CBL-PM05 (5 m)
2711-CBL-PM10 (10 m)
DH-485
RS-232 port (9-pin)PanelView Plus 400 to 15002711P-RN22C (for 400 and 600)
mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
Null modem requiredmdash
DH-485 portPanelView Plus 400 and 600Requires 2711P-RN3(1)
1747-C10 (2 m6ft) 1747-C11 (03 m1 ft)1747-C20 (6 m20 ft)
mdash mdash 1761-CBL-AS03 (3 m10 ft)1761-CBL-AS09 (9 m30 ft)
to single AIC+
mdash
DH-485 portPanelView Plus 700 to 1500Requires 2711P-RN6 -RN6K
Direct connection to single AIC with
Belden 9842 cable(2)mdash mdash
Direct connection to single AIC+ with
Belden 9842 cable(2)mdash
(1) For CE compliance use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft)(2) Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution
Table 48 - Runtime Communication Cables PanelView Plus Compact Terminals to SLC Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
SLC-500 501 502CH1 RJ45 (DH-485)
SLC-503 504 505CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 503CH1 (RJ45)
(DH-485)SLC 504
CH1 (DH+)SLC 505
CH1 (ENET)
DF1 RS-232 (DF1) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft) mdash
mdash mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2
2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
Use AIC+ module(1761-NET-AIC)
to connect to port 1 or 2mdash mdash
EtherNetIP EtherNetIP Comm port mdash Use 1761-NET-ENI modulewith Ethernet cable mdash mdash 2711P- CBL-EX04 Ethernet
crossover cable (1)
(1) An EtherNetIP direction connection between a PanelView Plus Compact terminal and an SLC 505 requires hub or crossover cable listed
Table 49 - Runtime Communication Cables PanelView Plus Compact Terminals to MicroLogix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
MicroLogix 1500LRPCH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000 1200 1500LSPCH0 (8-pin Mini DIN)
(DF1 or DH-485)MicroLogix 1100 1400
Ethernet Port
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
DH-485 RS-232 (DH-485) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)2711-NC21 (5 m16 ft)
2711-NC22 (15 m49 ft) (1) mdash
EtherNetIP EtherNetIP Comm portUse 1761-NET-ENI module
with Ethernet cable1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(2)
(1) AIC+ Module recommended for isolation when PanelView and controller are not using same power supply(2) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
26 PanelView Plus Specifications
Table 50 - Runtime Communication Cables PanelView Plus Compact to Logix Controllers
Protocol PanelView Plus Compact400 600 1000 Comm Port
ControlLogixCH0 (9-pin RS-232)
(DF1)
CompactLogixCH0 (9-pin RS-232)
(DF1 or DH-485)
DF1 RS-232 (DF1) Comm port (9-pin)2711-NC13 (5 m16 ft)
2711-NC14 (10 m32 ft)
DH-485 RS-232 (DH-485) Comm port (9-pin) mdash 2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
EtherNetIP EtherNetIP Comm portUse 1756-EN2T or 1756-ENBT module
with 1585J-M type cable or 2711P-CBL-EX04 cable (4 m14 ft)(1)
To 1769-L35E L23E L32E with1585J-M type cable or
2711P-CBL-EX04 cable (4 m14 ft)(1)
(1) For a direct connection between the terminal and controller use the 2711P-CBL-EX04 crossover cable
Table 51 - Runtime Communication Cables PanelView Plus Compact to Network Modules
Protocol PanelView Plus Compact400 600 1000 Comm Port
1761-NET-AIC
Port 1 (9-pin) Port 28-pin Mini DIN
Port 3(DH-485)
DF1 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft)
mdash
DH-485 RS-232 Comm port (9-pin)2711-NC13 (5 m16 ft)2711-NC14 (10 m32 ft)
2711-NC21 (5 m16 ft)2711-NC22 (15 m49 ft) mdash
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
PanelView Plus Specifications 27
Migration Hardware The PanelView Plus platforms provide a clear migration path for replacing older terminals When migrating to a new platform consider both the display size and the unit size PanelView Plus terminals uses the same panel cutouts as existing PanelView products yet offer a larger display For instance a PanelView Plus 6 1250 terminal with a 121-inch display fits into the same cutout as a PanelView 1000 or 1000e with a 104-inch display When choosing a terminal with the same display size adapter plates are used to adapt the cutout of the new terminal
Table 52 - PanelView Plus Replacement Terminals
PanelView Standard Terminal PanelView Plus Replacement Terminal Adapter Plate Required
Adapter Plate Cat No
PanelView Standard 300 or 300 Micro None available(1) mdash mdash
PanelView 550 or 600 touch PanelView Plus or PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus or PanelView Plus Compact 600 touch No mdash
PanelView 550 keypadPanelView 550 keypadtouch
PanelView Plus 600 keypad or keypadtouch No mdash
PanelView Plus PanelView Plus Compact 400 keypad or keypadtouchPanelView Plus PanelView Plus Compact 600 touch Yes 2711P-RAK4
PanelView 600 keypadPanelView 600 keypadtouch
PanelView Plus 600 keypad or keypadtouch Yes 2711P-RAK6
PanelView Plus 6 700 keypad or keypadtouch No mdash
PanelView 900 keypadPanelView Plus 6 700 keypad or keypadtouch Yes 2711P-RAK7
PanelView Plus 6 1000 keypad or keypadtouch No mdash
PanelView 900 touchPanelView Plus 6 700 touch Yes 2711P-RAT7
PanelView Plus 6 or PanelView Plus Compact 1000 touch No mdash
PanelView 1000 keypadPanelView Plus 6 1000 keypad or keypadtouch Yes 2711P-RAK10
PanelView Plus 6 1250 keypad or keypadtouch No mdash
PanelView 1000 touchPanelView Plus 6 or PanelView Plus Compact 1000 touch Yes 2711P-RAT10
PanelView Plus 6 1250 touch No mdash
PanelView 1400 keypadPanelView Plus 6 1250 keypad or keypadtouch Yes 2711P-RAK12S
PanelView Plus 6 1500 keypad or keypadtouch No mdash
PanelView1400e keypadPanelView Plus 6 1500 keypad or keypadtouch(2) Yes 2711P-RAK15
None available mdash mdash
PanelView 1400 touch PanelView Plus 6 1250 touch Yes 2711P-RAT12S
PanelView Plus 6 1500 touch No mdash
PanelView 1400e touchPanelView Plus 61500 touch(2) Yes 2711P-RAT15
None available mdash mdash
PanelView 1200 1200e1400e Keypad PanelView Plus 61250 keypad(2) Yes RAK12E
None available mdash mdash
PanelView 1200 1200e Touch PanelView Plus 61250 touch(3) Yes RAT12E
None available mdash mdash
PanelView 12001200E touch PanelView Plus 61250 touch(3) Yes 2711P-RAT12E2
None available mdash mdash
(1) Replace the PanelView Standard 300 or 300 Micro with a PanelView Plus 400 keypad terminal by increasing the size of the current panel cutout(2) Adapter plate required for stud-mounted terminals(3) Requires modification of panel cutout
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
28 PanelView Plus Specifications
Additional Resources These documents contain additional information concerning related Rockwell Automation products
You can view or download publications at httpwwwrockwellautomationcomliterature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative
Resource Description
Visualization Solutions Selection Guide publication VIEW-SG001
Provides an overview of the visualization products including catalog number selections offered by Rockwell Automation
PanelView 6 Terminals User Manual publication 2711P-UM006
Provides information on how to install configure operate and troubleshoot the PanelView Plus 6 (700 to 1500) terminals
PanelView Plus 6 Terminals Installation Instructions publication 2711P-IN029
Provides information on how to install the PanelView Plus 6 (700 to 1500) terminals in a panel
PanelView Plus Compact Terminals User Manual publication 2711PC-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus Compact terminals
PanelView Plus Terminals User Manual publication 2711P-UM001
Provides information on how to install configure operate and troubleshoot the PanelView Plus 400 and 600 terminals
Industrial Automation Wiring and Grounding Guidelines publication 1770-41
Provides general guidelines for installing a Rockwell Automation industrial system
Product Certifications website httpwwwabcom
Provides declarations of conformity certificates and other certification details
Rockwell Automation Publication 2711P-TD005A-EN-P - November 2010
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
Important User Information
Publication 2711P-TD005A-EN-P - November 2010 Copyright copy 2010 Rockwell Automation Inc All rights reserved Printed in the USA
Solid-state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwrockwellautomationcomliterature) describes some important differences between solid-state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid-state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable
In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment
The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams
No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual
Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited
Documentation Feedback
Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA-DU002 available at httpwwwrockwellautomationcomliterature
Allen-Bradley CompactLogix ControlLogix DH+ PanelView Plus PanelView Component FactoryTalk View Studio FactoryTalk FactoryTalk View ME FactoryTalk ViewPoint
Integrated Architecture MicroLogix PLC-5 SLC RSLinx Enterprise RSView32 Rockwell Software Rockwell Automation are trademarks of Rockwell Automation Inc
Trademarks not belonging to Rockwell Automation are property of their respective companies
Rockwell Otomasyon Ticaret AŞ Kar Plaza İş Merkezi E Blok Kat6 34752 İccedilerenkoumly İstanbul Tel +90 (216) 5698400
JIT Printing Specifications | RA-QR005G-EN-P - 3292010 | ||||||||||||||||||||||||||||||||
Printing Specification | YOUR DATA HERE | Instructions | NO | ||||||||||||||||||||||||||||||
(required) Category | D5 | Select Print Category ABC or D from category list on Introduction_Catagory Types tab | 11rdquo x 17rdquo | LOOSE -Loose Leaf | YES | Pre-sale Marketing | TOP | ||||||||||||||||||||||||||
(required) Finished Trim Size Width | 85rdquo x 11rdquo | 85rdquo x 11rdquo | PERFECT - Perfect Bound | A1 | LEFT | ||||||||||||||||||||||||||||
(required) Publication Number | 2711P-TD005A-EN-P | Sample 2030-SP001B-EN-P | 3rdquo x 5rdquo | SADDLE - Saddle Stitch | A2 | RIGHT | CORNER | ||||||||||||||||||||||||||
Use Legacy Number | YES or NO | 18rdquo x 24rdquo Poster | PLASTCOIL - Plastic Coil (Coil Bound) | A4 | BOTTOM | SIDE | |||||||||||||||||||||||||||
Legacy Number if applicable | Sample Legacy Number 0160-533 | 24rdquo x 36rdquo Poster | STAPLED1 -1 position | A3 | |||||||||||||||||||||||||||||
Publication Title | PanelView Plus Specifications Technical Data | Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title | 36rdquo x 24rdquo Poster | STAPLED1B - bottom 1 position | A5 | ||||||||||||||||||||||||||||
(required) Business Group | Marketing Commercial | As entered in DocMan | 4rdquo x 6rdquo | STAPLED2 - 2 positions | A6 | ||||||||||||||||||||||||||||
(required) Cost Center | 19021 | As entered in DocMan - enter number only no description Example - 19021 | CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 | 475rdquo x 7rdquo (slightly smaller half-size) | THERMAL - Thermal bound (Tape bound) | A7 | |||||||||||||||||||||||||||
BindingStitching | SADDLE - Saddle Stitch | Review key on right | Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch - no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastcoil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) | 475rdquo x 775rdquo | THERMALO - Thermal Bound (Tape bound - offline) | A8 | |||||||||||||||||||||||||||
(required) Page Count of Publication | 30 | Total page count including cover | 55rdquo x 85rdquo (half-size) | A9 | |||||||||||||||||||||||||||||
Paper Stock Color | White is assumed For color options contact your vendor | 6rdquo x 4rdquo | Post Sale Technical Communication | ||||||||||||||||||||||||||||||
Number of Tabs Needed | 5 tab in stock at RR Donnelley | 7385rdquo x 9rdquo (RSI Std) | B1 | ||||||||||||||||||||||||||||||
Stitching Location | SIDE | Blank Corner or Side | 825rdquo x 10875rdquo | B2 | |||||||||||||||||||||||||||||
Drill Hole YESNO | YES | All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border | 825rdquo x 11rdquo (RA product profile std) | B3 | None | ||||||||||||||||||||||||||||
Glue Location on Pad | Glue location on pads | 8375rdquo x 10875 | B4 | Half or V or Single Fold | |||||||||||||||||||||||||||||
Number of Pages per Pad | Average sheets of paper 25 50 75100 Max | 9rdquo x 12rdquo (Folder) | B5 | C or Tri-Fold | |||||||||||||||||||||||||||||
Ink Color | One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip | A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) | Catalogs | DbleParll | |||||||||||||||||||||||||||||
Used in Manufacturing | A5 (583rdquo x 826rdquo) (148 x 210 mm) | C1 | Sample | ||||||||||||||||||||||||||||||
Fold | Review key on right | Short (must specify dimensions between folds in Comments) | |||||||||||||||||||||||||||||||
Comments | This is an electronic only document Print specs are attached just for future use if needed | C2 | Z or Accordian Fold | ||||||||||||||||||||||||||||||
Part Number | JIT POD | Microfold or French Fold - designate no of folds in Comments - intended for single sheet only to be put in box for manufacturing | |||||||||||||||||||||||||||||||
D1 | Double Gate | ||||||||||||||||||||||||||||||||
D2 | |||||||||||||||||||||||||||||||||
FoldsHalf V Single C or TriDble ParllZ or Accordian Microfold or FrenchDouble Gate Short Fold | D3 | ||||||||||||||||||||||||||||||||
D4 | |||||||||||||||||||||||||||||||||
D5 | |||||||||||||||||||||||||||||||||
D6 | |||||||||||||||||||||||||||||||||
D7 | |||||||||||||||||||||||||||||||||
D8 | |||||||||||||||||||||||||||||||||
D9 |
This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan | |||||||||||||
Publication Type and Print Category | |||||||||||||
Publication Type | Off Set Print Category Spec (See table below) | JIT Spec (See table below) | Description | Order Min | Order Max | Life Cycle Usage Release Option | |||||||
AD | NA - Puttman | NA | Advertisement Reprint Colour | NA | NA | Presale Internal | |||||||
AP | A3 | D2 | Application Solution or Customer Success Story | 5 | 100 | Presale External | |||||||
AR | NA | NA | ArticleEditorialByline | NA | NA | Presale Internal | |||||||
(press releases should not be checked into DocMan or printed) | |||||||||||||
AT | B3 B4 | D5 | Application techniques | 5 | 100 | Presale External | |||||||
BR | A2 Primary A1 | NA | Brochures | 5 | 100 | Presale External | |||||||
CA | C2 Primary C1 | NA | Catalogue | 1 | 50 | Presale External | |||||||
CG | NA | NA | Catalogue Guide | 1 | 50 | Presale External | |||||||
CL | NA | NA | Collection | 5 | 50 | Presale External | |||||||
CO | A5 A6 A9 | D5 | Company Confidential Information | NA | NA | NA Confidential | |||||||
CP | E-only | E-only D5 | Competitive Information | 5 | 50 | NA Confidential | |||||||
DC | E-only | E-only | Discount Schedules | NA | NA | Presale Internal | |||||||
DI | A1 A3 | NA | Direct Mail | 5 | 100 | Presale Internal | |||||||
DM | NA | NA | Product Demo | 5 | 50 | Presale Internal | |||||||
DS | B3 | D5 | Dimensions Sheet | 1 | 5 | Post External | |||||||
DU | B3 | D5 | Document Update | 1 | 5 | Post External | |||||||
GR | B2 | D6 | Getting Results | 1 | 5 | Post External | |||||||
IN | B3 Primary B2 | D5 D6 | Installation instructions | 1 | 5 | Post External | |||||||
LM | NA | NA | Launch Materials | 5 | 50 | Presale Internal | |||||||
PC | B3 | D5 | Packaging Contents | ||||||||||
PL | E-only primary B3 | E-only | Price List | 5 | 50 | Presale Internal | |||||||
PM | B2 | D6 | Programming Manual | 1 | 5 | Post External | |||||||
PP | A3 | D1 | Profile (Single Product or Service) NOTE Application Solutions are to be assigned the AP pub type | 5 | 100 | Presale External | |||||||
QR | B2 primary B3 B5 | D5 D6 | Quick Reference | 1 | 5 | Post External | |||||||
QS | B2 primary B3 B5 | D5 D6 | Quick Start | 1 | 5 | Post External | |||||||
RM | B2 | D5 D6 | Reference Manual | 1 | 5 | Post External | |||||||
RN | B3 | D5 | Release Notes | 1 | 5 | Post External | |||||||
SG | B1 Primary B4 | D5 D6 | Selection Guide Colour | 5 | 50 | Presale External | |||||||
SG | B2 | D5 D6 | Selection Guide BW | 5 | 50 | Presale External | |||||||
SP | A1 A2 A3 A4 | NA | Sales Promotion NOTE Service profiles are to be assigned the PP pub type | 5 | 100 | Presale Internal | |||||||
SR | B2 B3 | D5 D6 | Specification Rating Sheet | 5 | 100 | Presale External | |||||||
TD | B2 Primary B3 B4 B5 | D5 D6 | Technical Data | 5 | 50 | Presale External | |||||||
TG | B2 B3 | D6 | Troubleshooting Guide | 1 | 5 | Post External | |||||||
UM | B2 Primary B4 | D6 | User Manual BW | 1 | 5 | Post External | |||||||
WD | B3 | D5 | Wiring Diagrams Dwgs | 1 | 5 | Post Internal | |||||||
WP | B3 Primary B5 | D5 | White Paper | 5 | 50 | Presale External | |||||||
Minimum order quantities on all JIT items are based on the publication length | |||||||||||||
Publication length | Minimum Order Quantity | ||||||||||||
77 or more pages | 1 (no shrink wrap required) | ||||||||||||
33 to 76 pages | 25 | ||||||||||||
3 to 32 pages | 50 | ||||||||||||
1 or 2 pages | 100 | ||||||||||||
Pre-sale Marketing | All paper in this category is White Brightness 90 or better Opacity 90 or better | ||||||||||||
Category | Color Options | AP EMEA Paper Requirements | Canada LA US Paper Requirements | ||||||||||
A1 | 4 color | 170 gsm 2pp | 100 gloss cover 100 gloss text | ||||||||||
A2 | 4 color | 170 gsm folded 4pp | 100 gloss cover 80 gloss text | ||||||||||
A3 | 4 color | Cover 170 gsm with Body 120 gsm gt 4pp | 80 gloss cover 80 gloss text | ||||||||||
A4 | 2 color | 170gsm Silk ndash 120gsm Silk | 80 gloss cover 80 gloss text | ||||||||||
A5 | 2 color | 170gsm Silk ndash 120gsm Silk | 80 gloss cover 80 matt sheet text | ||||||||||
A6 | 1 color | 170gsm Silk ndash 120gsm Silk | 80 gloss cover 80 matt sheet text | ||||||||||
A7 | 4 color cover2 color textSelection Guide | Category being deleted | 10 Point Cover C2S50 matte sheet text | ||||||||||
A8 | 4 color cover | Category being deleted | 50 matte sheet text self cover | ||||||||||
2 color text | |||||||||||||
Selection Guide | |||||||||||||
A9 | 2 color | 100gsm bond | 50 matte sheet text self cover | ||||||||||
Selection Guide | |||||||||||||
Gray shading indicates Obsolete Print Catagories | |||||||||||||
Post Sale Technical Communication | |||||||||||||
Category | Color Options | AP EMEA Paper Requirements | Canada LA US Paper Requirements | ||||||||||
B1 | 4 color cover | 270gsm Gloss 100gsm bond | 10 Point Cover C2S | ||||||||||
2 color text | 50 matte sheet text | ||||||||||||
B2 | 1 color | 160gsm Colortech amp 100gsm Bond | 90 Cover50 matte sheet text | ||||||||||
B3 | 1 color | 100gsm bond | 50 matte sheet text self cover | ||||||||||
B4 | 2 color | 160gsm Colortech amp 100gsm Bond | 90 Cover50 matte sheet text | ||||||||||
B5 | 2 color | 100gsm bond | 50 matte sheet text self cover | ||||||||||
Catalogs | |||||||||||||
Category | Color Options | AP EMEA Paper Requirements | Canada LA US Paper Requirements | ||||||||||
C1 | 4 color cover | 270gsm Gloss 90gsm silk | 10 Point Cover C2S | ||||||||||
4 color text | 45 Coated Sheet | ||||||||||||
C2 | 4 color cover | 270gsm Gloss 80gsm silk | 10 Point Cover C2S | ||||||||||
2 color text | 32-33 Coated Sheet | ||||||||||||
JIT POD | All paper in this category is White Brightness 82 or better Opacity 88 or better | ||||||||||||
Category | Color Options | AP EMEA Paper Requirements | Canada LA US Paper Requirements | ||||||||||
D1 | 4 color | 170gsm white silk | 80 gloss cover coated 2 sides | ||||||||||
D2 | 4 color | 120gsm white silk | 80 gloss text coated 2 sides self cover | ||||||||||
D3 | 4 color | Cover 170gsm with Body 120gsm | 80 gloss cover 80 gloss text coated 2 sides | ||||||||||
D4 | 1 color | 160gsm tab | 90 index | ||||||||||
D5 | 1 color | 80gsm bond | 20 bond self cover | ||||||||||
D6 | 1 color | Cover 160gsm tab with Body 80gsm bond | 90 index 20 bond | ||||||||||
D7 | 2 color | 160gsm tab | 90 index | ||||||||||
D8 | 2 color | 80gsm bond | 20 bond self cover | ||||||||||
D9 | 2 color | Cover 160gsm tab with Body 80gsm bond | 90 index 20 bond | ||||||||||
D10 | Combination 4 color cover with 2 color body | Cover 160gsm with Body 80gsm | 90 index 20 bond | ||||||||||
Gray shading indicates Obsolete Print Catagories | |||||||||||||
Just In Time (JIT) or Off Set (OS) | |||||||||||||
Use these guidelines to determine if your publication should be JIT (just in timeprint on demand) or if it would be more economical to print OS (offseton a press) OS print jobs require an RFQ (Request For Quote) in US If your job fits into the ldquoEitherrdquo category an RFQ is recommended but not required In the US RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category Guidelines differ for black amp white and color printing so be sure to check the correct tables | |||||||||||||
Black amp White Printing | |||||||||||||
Color Printing | |||||||||||||
Color Printing |
JIT Printing Specifications | RA-QR005G-EN-P - 3292010 | ||||||||||||||||||||||||||||||||
Printing Specification | YOUR DATA HERE | Instructions | NO | ||||||||||||||||||||||||||||||
(required) Category | D5 | Select Print Category ABC or D from category list on Introduction_Catagory Types tab | 11rdquo x 17rdquo | LOOSE -Loose Leaf | YES | Pre-sale Marketing | TOP | ||||||||||||||||||||||||||
(required) Finished Trim Size Width | 85rdquo x 11rdquo | 85rdquo x 11rdquo | PERFECT - Perfect Bound | A1 | LEFT | ||||||||||||||||||||||||||||
(required) Publication Number | 2711P-TD005A-EN-P | Sample 2030-SP001B-EN-P | 3rdquo x 5rdquo | SADDLE - Saddle Stitch | A2 | RIGHT | CORNER | ||||||||||||||||||||||||||
Use Legacy Number | YES or NO | 18rdquo x 24rdquo Poster | PLASTCOIL - Plastic Coil (Coil Bound) | A4 | BOTTOM | SIDE | |||||||||||||||||||||||||||
Legacy Number if applicable | Sample Legacy Number 0160-533 | 24rdquo x 36rdquo Poster | STAPLED1 -1 position | A3 | |||||||||||||||||||||||||||||
Publication Title | PanelView Plus Specifications Technical Data | Sample ElectroGuard Selling Brief80 character limit - must match DocMan Title | 36rdquo x 24rdquo Poster | STAPLED1B - bottom 1 position | A5 | ||||||||||||||||||||||||||||
(required) Business Group | Marketing Commercial | As entered in DocMan | 4rdquo x 6rdquo | STAPLED2 - 2 positions | A6 | ||||||||||||||||||||||||||||
(required) Cost Center | 19021 | As entered in DocMan - enter number only no description Example - 19021 | CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 | 475rdquo x 7rdquo (slightly smaller half-size) | THERMAL - Thermal bound (Tape bound) | A7 | |||||||||||||||||||||||||||
BindingStitching | SADDLE - Saddle Stitch | Review key on right | Saddle-Stitch Items All page quantities must be divisible by 4Note Stitching is implied for Saddle-Stitch - no need to specify in Stitching Location80 pgs max on 20 (text and cover)76 pgs max on 20 (text) and 24 (cover)72 pgs max on 24 (text and cover)Perfect Bound Items940 pgs max wcover (90 index unless indicated otherwise)70 pgs min for spine without words200 pgs min for spine with words Plastcoil Bound Items530 pgs max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise)Tape Bound Items250 pgs max on 20 no cover240 pgs max wcover (90 index unless indicated otherwise) | 475rdquo x 775rdquo | THERMALO - Thermal Bound (Tape bound - offline) | A8 | |||||||||||||||||||||||||||
(required) Page Count of Publication | 30 | Total page count including cover | 55rdquo x 85rdquo (half-size) | A9 | |||||||||||||||||||||||||||||
Paper Stock Color | White is assumed For color options contact your vendor | 6rdquo x 4rdquo | Post Sale Technical Communication | ||||||||||||||||||||||||||||||
Number of Tabs Needed | 5 tab in stock at RR Donnelley | 7385rdquo x 9rdquo (RSI Std) | B1 | ||||||||||||||||||||||||||||||
Stitching Location | SIDE | Blank Corner or Side | 825rdquo x 10875rdquo | B2 | |||||||||||||||||||||||||||||
Drill Hole YESNO | YES | All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border | 825rdquo x 11rdquo (RA product profile std) | B3 | None | ||||||||||||||||||||||||||||
Glue Location on Pad | Glue location on pads | 8375rdquo x 10875 | B4 | Half or V or Single Fold | |||||||||||||||||||||||||||||
Number of Pages per Pad | Average sheets of paper 25 50 75100 Max | 9rdquo x 12rdquo (Folder) | B5 | C or Tri-Fold | |||||||||||||||||||||||||||||
Ink Color | One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip | A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) | Catalogs | DbleParll | |||||||||||||||||||||||||||||
Used in Manufacturing | A5 (583rdquo x 826rdquo) (148 x 210 mm) | C1 | Sample | ||||||||||||||||||||||||||||||
Fold | Review key on right | Short (must specify dimensions between folds in Comments) | |||||||||||||||||||||||||||||||
Comments | This is an electronic only document Print specs are attached just for future use if needed | C2 | Z or Accordian Fold | ||||||||||||||||||||||||||||||
Part Number | JIT POD | Microfold or French Fold - designate no of folds in Comments - intended for single sheet only to be put in box for manufacturing | |||||||||||||||||||||||||||||||
D1 | Double Gate | ||||||||||||||||||||||||||||||||
D2 | |||||||||||||||||||||||||||||||||
FoldsHalf V Single C or TriDble ParllZ or Accordian Microfold or FrenchDouble Gate Short Fold | D3 | ||||||||||||||||||||||||||||||||
D4 | |||||||||||||||||||||||||||||||||
D5 | |||||||||||||||||||||||||||||||||
D6 | |||||||||||||||||||||||||||||||||
D7 | |||||||||||||||||||||||||||||||||
D8 | |||||||||||||||||||||||||||||||||
D9 |