Condition Monitoring Of High Voltage
Machines
By The Analysis of
Electrical Partial Discharges
22 April 04
Dino KouadriaPhD MSc BEng CEng MIEE MIEEE
DOWDING & MILLS
CONTENT
What is Partial Discharge (PD) Analysis.
Stator winding Common Faults.
Basics Of Why & How To Measure PD.
Case Studies.
Open Discussions.
DOWDING & MILLS
It is an electrical condition monitoring
technique.
Used to assess the condition of hv
insulation
Wider applications
static items i.E. Switchgear, cables
transformers, etc.
Dynamic items i.E. Electrical machines
What is Partial Discharges Analysis
DOWDING & MILLS
Apply to HV motors & generators (>5kv)
Online & off line tests.
Predominantly on-line tests - no shut
down & tests under
normal stress condition.
PDs Analysis On HV Windings
DOWDING & MILLS
Assess the current & development in
condition of the
windings
Maintenance planning based on machines’
health.
Elimination of unwanted/unexpected
shutdowns.
Assistance in targeting maintenance effort
effectively.
Leave Maintain
Replace
PDs Analysis On HV Windings
DOWDING & MILLS
Why Do HV Stators Fail?
Failures due to windings’ insulation failure caused
by the combined
electrical, thermal, environmental and mechanical
stress factors.
Most common causes in modern insulation are
mechanically induced defects i.E. Loose wedges,
erosion due to bar vibration etc. - Short time
degradation process.
Discharge between phases due to cracks / low
spacing
Contamination of end windings.
Others: internal voids, insulation ageing,
delamination.
Electrical partial discharges
DOWDING & MILLS
Regardless of the type of defects, they
all result in the generation of
Electrical partial discharges.
So what are partial discharges?
DOWDING & MILLS
What is a partial dischargeLocal breakdown that short circuits part of the Insulation.
Formation of corrosive ions, acids, nitrogen oxides, ozone.
Detected using of chemical sensors for detection.
Emission of light, sound & electromagnetic waves.
Detected using ultrasonic devices, antennae, cameras..
Injection of high frequency current pulses.
Detected using electrical partial discharges measurement
(pd).
Vs = Applied voltage
CavityVs
DOWDING & MILLS
-
+ +
Patterns & location of pulses within AC cycleIs the key in defects identification
Partial Discharges Basic Theory
DOWDING & MILLS
Importance Of Monitoring PDs
Different defects produce different PD patterns.
Complex PD patterns are produced when multiple defects
are present.
Failures are due to localized defects.
PD pattern development over time represents developing
degradation processes.
Provide an early warning of potential problems
DOWDING & MILLS
Discharge levels
Time
3 – 6 months ?? Years
Curing Process Fabrication Defects
Contamination
Mechanical failure
Partial discharge monitoring over a machine life cycle
Repair/action required
DOWDING & MILLS
PD Detection
Two main type of permanently installed sensors.
Capacitive couplers first developed in north
america. Main users power industry.
Rogowski coils first developed for the north sea
oil industry.
North sea oil industry – mainly Rogowski coils
Ease of installation: no disconnection of supply
cables, less installation time.
Atex certified
DOWDING & MILLS
Rogowski Coils: Typical Installation
DOWDING & MILLS
Partial Discharge Analysis/Display: Typical Cycle
DOWDING & MILLS
Partial Discharge Analysis/Display: Total Discharge Activity
DOWDING & MILLS
Partial Discharge Analysis/Display: Pulse Height Analysis
DOWDING & MILLS
CASE STUDIES
DOWDING & MILLS
Case studies
1 Contamination on old pump motor 11KV-3MW
2 New motor manufacturing problem 13.8KV-12MW
3 Coil Movement old motor 6.6KV-9MW
4 Plastics plant old motor high PD 11KV-2.5MW
DOWDING & MILLS
Total Discharge Activity
3MW Pump Motor
DOWDING & MILLS
White power deposits clear signs of discharge activity
Typical Detected Faults Damage due to movement and contamination3MW Pump Motor
DOWDING & MILLS
13.8 kV 12.7 MW Gas Compressor
DOWDING & MILLS
13.8 kV 12.7 MW Gas Compressor
0ver 70% of wedges loose or missing
DOWDING & MILLS
Typical Detected Faults Damage due to wedge movement
13.8 kV 12.7 MW Gas Compressor
DOWDING & MILLS
Banded Discharge is modulated which is due to coil movement .....
9MW Gas Compression Motor
DOWDING & MILLS
9MW Gas Compression Motor
DOWDING & MILLS
Good Coil
Air Duct Impressions
9MW Gas Compression Motor
DOWDING & MILLS
Damaged Coil
Lamination groves due to movement
Air Ducts (no abrasion)
9MW Gas Compression Motor
DOWDING & MILLS
Heavily Damaged Coil Due to impacting on slot bottom
9MW Gas Compression Motor
DOWDING & MILLS
2420KW 11kV ASEA synchronous compressor motor
DOWDING & MILLS
Detect any potential insulation problems.
The contribution of the different problems.
Location of problems within the winding.
Development in windings condition (through regular
monitoring)
Early detection allows scheduling of remedial
work/repairs.
“Provide the maintenance engineer with the
information to make
The most cost effective decisions on planned
maintenance”
Outcome of A PD Analysis Survey
DOWDING & MILLS
Partial Discharge Analysis
Not an exact Science.
Does not predict when plant is likely to
fail.
BUT will highlight which machines are
most likely to fail.
Does not detect Inter-turn Faults
More room for improvement in defect
recognition.
Future development in insulation/motor
designs.
DOWDING & MILLS
Condition Monitoring Of High Voltage
Machines
By The Analysis of
Electrical Partial Discharges
22 April 04
Dino KouadriaPhD MSc BEng CEng MIEE MIEEE