+ All Categories
Home > Documents > PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... ·...

PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... ·...

Date post: 11-Sep-2021
Category:
Upload: others
View: 6 times
Download: 0 times
Share this document with a friend
118
VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03 0 CENTRE NATIONAL D'ETUDES SPATIALES Sous-Direction Développements Sol 18, Avenue Edouard-Belin 31401 TOULOUSE Cedex 4 Rond-point de l'Espace 91023 EVRY Cedex SDS/G BP 254 - 97377 KOUROU CEDEX CODE IDENTIFICATION PROJET VG-ST-2-C-0007-CNES EDITION : 1 REVISION : 0 Date édition ou dernière révision: 14/02/2003 REF. D'AUTEUR: SDS/PL/IR-2002/199 CLASSE : 1 CATEGORIE : 1 RESERVE A L'INDUSTRIEL PROJET : VEGA GROUND SEGMENT TITRE DU DOCUMENT : PARTICULAR SPECIFICATIONS ENERGY NOM & FONCTION DATE & SIGNATURE PREPARE PAR: François MARTY BETEM Philippe CUROT SDS/PL/IR POUR APPROBATION: P. GUILHEM Technical Officer POUR ACCEPTATION: APPLICATION AUTORISEE PAR: M. VALES Project Coordinator VEGA LISTE DE DIFFUSION Nb A I SDS/SG/MS/BT1 1 X Les signataires + 4 SDS/PL/OI 1 SDS/PL/SE 1 SDS/PL/SV 1 SDS/AP/SY 1 SDS/SM/CT ESA/LAU-V/IPT 1 A=Action I=Information
Transcript
Page 1: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

0

CENTRE NATIONAL D'ETUDES SPATIALES

Sous-Direction Développements Sol

18, Avenue Edouard-Belin 31401 TOULOUSE Cedex 4

Rond-point de l'Espace 91023 EVRY Cedex

SDS/G BP 254 - 97377 KOUROU CEDEX

CODE IDENTIFICATION PROJET

VG-ST-2-C-0007-CNESEDITION : 1 REVISION : 0

Date édition ou dernière révision: 14/02/2003

REF. D'AUTEUR: SDS/PL/IR-2002/199

CLASSE : 1 CATEGORIE : 1

RESERVE A L'INDUSTRIEL

PROJET : VEGA GROUND SEGMENT

TITRE DU DOCUMENT :

PARTICULAR SPECIFICATIONSENERGY

NOM & FONCTION DATE & SIGNATURE

PREPAREPAR:

François MARTYBETEM

Philippe CUROTSDS/PL/IR

POURAPPROBATION: P. GUILHEM

Technical Officer

POURACCEPTATION:

APPLICATIONAUTORISEE

PAR:

M. VALESProject Coordinator

VEGA

LISTE DE DIFFUSION Nb A I

SDS/SG/MS/BT1 1 X

Les signataires + 4

SDS/PL/OI 1

SDS/PL/SE 1

SDS/PL/SV 1

SDS/AP/SY 1

SDS/SM/CT

ESA/LAU-V/IPT 1

A=Action I=Information

Page 2: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Sous-Direction Développements Sol

18, Avenue Edouard-Belin 31401 TOULOUSE Cedex 4

Rond-point de l'Espace 91023 EVRY Cedex

SDS/G BP 254 - 97377 KOUROU CEDEX

LANGUE: Fr EDITION : 1 REVISION : 0

Date édition ou dernière révision: 14/02/2003

CODE IDENTIFICATION PROJET

VG-ST-2-C-0007-CNES

FICHESIGNALETIQUE

FICHIER INFORMATIQUE

C:\TEMP\VG ST 2 C 0007-10A_eng.doc

Nombre de pages totales (y/c annexeset pages de garde): 118

Nb de pagesannexes: 0

TITRE:

PARTICULAR SPECIFICATIONSENERGY

NOM (S) AUTEUR (S)François MARTY pour Henri BRUNET-LAVIGNESDS/PL/IR

TYPE DE DOCUMENT

SPECIFICATION TECHNIQUE

CLASSEMENT PHYSIQUE NO. MARCHE CLASSE: 1

CATEGORIE: 1

RESUME D'AUTEUR

The purpose of this document is to define the characteristics of the energy system as part of the VEGAproject.

MOTS CLES (mis par l'auteur) RESERVE AUX INDUSTRIELS

Page 3: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 3/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

EDITION REVISION DATE OBJET DE LA MODIFICATION

1 0 14/02/2003 Original issue.

Page 4: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 4/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

CONTENTS

1. PURPOSE ...................................................................................................................................................................... 7

2. REFERENCE DOCUMENTS...................................................................................................................................... 7

3. APPLICABLE DOCUMENTS..................................................................................................................................... 8

4. GLOSSARY ................................................................................................................................................................... 9

5. PROPOSAL ................................................................................................................................................................. 10

6. STUDIES, DRAWINGS AND DIAGRAMS ............................................................................................................. 10

7. CONSTRUCTION....................................................................................................................................................... 11

7.1. WORKS.................................................................................................................................................................. 117.2. COMMITMENTS...................................................................................................................................................... 127.3. INSPECTION: .......................................................................................................................................................... 12

8. VEGA LAUNCH COMPLEX.................................................................................................................................... 12

8.1. CLASSIFICATION OF ROOMS................................................................................................................................... 138.2. EARTH NETWORK .................................................................................................................................................. 13

8.2.1. Common units................................................................................................................................................... 138.2.2. Delivery substation ground ring earth circuit (1D60)...................................................................................... 138.2.3. BUNKER ground ring circuit ........................................................................................................................... 148.2.4. Delivery substation exposed metallic parts and equipotential frames (1D60) ................................................. 148.2.5. BUNKER and GANTRY exposed metallic parts and equipotential frames ...................................................... 148.2.6. BUNKER and GANTRY electron masses and measurement grounds .............................................................. 158.2.7. Launcher ground .............................................................................................................................................. 158.2.8. Mobile platform exposed conductive parts....................................................................................................... 158.2.9. Operator exposed conductive parts and exposed conductive parts of other units............................................ 158.2.10. Propellant room exposed conductive parts .................................................................................................. 168.2.11. Network interconnections............................................................................................................................. 16

8.3. LIGHTNING PROTECTION........................................................................................................................................ 168.3.1. External LPS ( IEPF ) ...................................................................................................................................... 178.3.2. Internal LPS ( IIPF ) ........................................................................................................................................ 22

8.4. ELECTROMAGNETIC COMPATIBILITY (CEM) PROTECTION .................................................................................... 238.4.1. Electrical equipment and miscellaneous equipment......................................................................................... 248.4.2. Sensitive equipment .......................................................................................................................................... 248.4.3. All systems ........................................................................................................................................................ 25

8.5. SUPPLY AND PRODUCTION OF ENERGY FOR THE VEGA LAUNCH COMPLEX........................................................... 268.5.1. Current distribution principle .......................................................................................................................... 268.5.2. Supply and production principle of categories I and II.................................................................................... 268.5.3. Category III production principle .................................................................................................................... 268.5.4. Category II power budget................................................................................................................................. 278.5.5. Category III A and B power budget, UPS power ............................................................................................. 298.5.6. DC power budget of rack TVC 270V 250A ...................................................................................................... 30

8.6. DELIVERY SUBSTATION TO CREATE: 1D60 ........................................................................................................... 308.6.1. Power supply of substation 1D60 in ZLV and resupply of substation 1D42 .................................................... 308.6.2. Equipment......................................................................................................................................................... 31

8.7. POWER SUPPLIES OF 20KV HV TRANSFORMERS OF THE ZLV................................................................................ 378.8. BURIED LINES ........................................................................................................................................................ 388.9. ZLV TRANSFORMER SUBSTATION FOR CAT. I AND II ENERGY............................................................................... 38

8.9.1. Transformer substation .................................................................................................................................... 388.9.2. 20KV/410V HV transformer power supply....................................................................................................... 388.9.3. ZLV transformers.............................................................................................................................................. 39

Page 5: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 5/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.10. CHARACTERISTICS COMMON TO HV/LV TRANSFORMERS ..................................................................................... 398.11. DRAWINGS AND DESIGN DOCUMENTS.................................................................................................................... 408.12. LOW-VOLTAGE (LV) DISTRIBUTION OF CATEGORIES I AND II ............................................................................... 40

8.12.1. Principle....................................................................................................................................................... 408.12.2. Neutral point treatment of category I and II low-voltage distribution......................................................... 418.12.3. Low-voltage main distribution panels (TGBT) ............................................................................................ 418.12.4. Sub-distribution panels (TD)........................................................................................................................ 44

8.13. CATEGORY III ENERGY PRODUCTION AND DISTRIBUTION...................................................................................... 498.13.1. Category III production ............................................................................................................................... 498.13.2. Category III A and III B distribution panels ................................................................................................ 588.13.3. Category III CU distribution panels ............................................................................................................ 618.13.4. Rack 270V 250A category III distribution ................................................................................................... 628.13.5. Category III information transfer ................................................................................................................ 638.13.6. Phase balancing........................................................................................................................................... 64

8.14. EMERGENCY CUTOFF............................................................................................................................................. 648.14.1. General emergency cutoff ............................................................................................................................ 648.14.2. Local emergency cutoff ................................................................................................................................ 658.14.3. Gantry emergency cutoff .............................................................................................................................. 658.14.4. Provisions common to local and gantry emergency cutoffs ......................................................................... 65

8.15. EQUIPMENT ........................................................................................................................................................... 658.15.1. Description................................................................................................................................................... 668.15.2. Room equipment........................................................................................................................................... 75

8.16. LAUNCHER LIGHTING ............................................................................................................................................ 858.16.1. Principle....................................................................................................................................................... 858.16.2. Earth network............................................................................................................................................... 858.16.3. Lightning protection..................................................................................................................................... 868.16.4. Calculation base .......................................................................................................................................... 878.16.5. Lighting apparatus....................................................................................................................................... 888.16.6. Power supplies ............................................................................................................................................. 888.16.7. Distribution panel ........................................................................................................................................ 898.16.8. Ballast cabinets ............................................................................................................................................ 89

9. CDL3............................................................................................................................................................................. 90

9.1. DEFINITION OF SYSTEMS........................................................................................................................................ 909.2. DEFINITION OF REQUIREMENTS ............................................................................................................................. 919.3. CATEGORY III A AND III B DISTRIBUTION ............................................................................................................ 91

9.3.1. Power supplies ................................................................................................................................................. 919.3.2. Distribution panels ........................................................................................................................................... 929.3.3. Category III information transfer..................................................................................................................... 939.3.4. Location of panels ............................................................................................................................................ 949.3.5. Electron mass and measurement ground collectors ......................................................................................... 949.3.6. Socket outlets.................................................................................................................................................... 94

9.4. ELECTROMAGNETIC COMPATIBILITY PROTECTION (CEM)..................................................................................... 94

10. ZEPHIRO PREPARATION CELL BUILDING ................................................................................................... 96

10.1. BUILDING CLASSIFICATION.................................................................................................................................... 9610.2. EARTH NETWORK .................................................................................................................................................. 9610.3. EXPOSED PYROTECHNICAL PARTS ......................................................................................................................... 9610.4. LIGHTNING PROTECTION........................................................................................................................................ 97

10.4.1. External Lightning Protection Systems ( IEPF ).......................................................................................... 9710.4.2. Internal Lightning Protection System ( IIPF ) ............................................................................................. 99

10.5. BUILDING ELECTRICAL POWER SUPPLY.................................................................................................................. 9910.6. SOLID BOOSTER STORAGE BOX .............................................................................................................................. 9910.7. DISTRIBUTION PANEL .......................................................................................................................................... 10010.8. EMERGENCY CUTOFF........................................................................................................................................... 10110.9. EQUIPMENT ......................................................................................................................................................... 101

10.9.1. Interior normal lighting ............................................................................................................................. 10110.9.2. Surrounding area external lighting............................................................................................................ 101

Page 6: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 6/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

10.9.3. Platform external lighting .......................................................................................................................... 10110.9.4. Common characteristics for lighting apparatus ........................................................................................ 102

10.10. SAFETY LIGHTING ........................................................................................................................................... 102

11. VEGA OFFICES: KEPLER AND BESSEL BUILDINGS ............................................................................... 103

11.1. FOREWORD.......................................................................................................................................................... 10311.2. EXISTING CONDITION........................................................................................................................................... 10311.3. NORMAL LIGHTING.............................................................................................................................................. 103

11.3.1. Characteristics ........................................................................................................................................... 10311.3.2. Lighting levels ............................................................................................................................................ 104

11.4. SAFETY LIGHTING................................................................................................................................................ 10411.5. CATEGORY I AND II SOCKET OUTLETS................................................................................................................. 10411.6. CATEGORY 1 AND 2 DISTRIBUTION PANEL........................................................................................................... 10511.7. CATEGORY 3 SYSTEMS ........................................................................................................................................ 106

11.7.1. Power supply of category 3 systems........................................................................................................... 10611.7.2. Existing low-voltage main distribution panel no. 193 04 30C................................................................... 10611.7.3. Ground floor distribution panels ............................................................................................................... 10711.7.4. Installation of socket outlets....................................................................................................................... 108

11.8. EMERGENCY CUTOFF........................................................................................................................................... 10811.8.1. Description................................................................................................................................................. 10811.8.2. Modifications in category 1 and 2 TDs...................................................................................................... 109

11.9. CONTROL OFFICE REPORT.................................................................................................................................... 10911.10. ELECTRIC DRAWINGS AND DIAGRAMS............................................................................................................. 110

12. INTERFACES AND MAINTENANCE.............................................................................................................. 111

12.1. INTERFACES......................................................................................................................................................... 11112.2. MAINTENANCE .................................................................................................................................................... 111

13. OPTION 1: LAUNCHER LIGHTNING PROTECTION................................................................................. 112

13.1. PROTECTION LEVEL ............................................................................................................................................. 11213.2. PRINCIPLE............................................................................................................................................................ 11213.3. DESCRIPTION OF THE SYSTEM.............................................................................................................................. 11313.4. DOWN CONDUCTORS ........................................................................................................................................... 11513.5. EARTH DISCHARGE DEVICES................................................................................................................................ 11513.6. LIGHTNING COUNTERS......................................................................................................................................... 11513.7. COMMON PROVISIONS.......................................................................................................................................... 116

14. OPTION 2: TVC RACK COMPLEMENTARY UPS ....................................................................................... 117

Page 7: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 7/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

1. PURPOSE

� The purpose of this document is to define the characteristics of the energy system as part of theVEGA project, i.e.:

� Vega Launch Complex:

� earth network,

� lightning protection,

� energy requirement,

� energy supply,

� low-voltage production and distribution in categories I, II and III,

� launcher lighting,

� CDL3: fitting-out:

� of operations room no. 167 and technical room no. 168 on 1st floor,

� of computer center room no.18 on ground floor.� KEPLER and BESSEL offices

� ground floor offices in the KEPLER building

� ground floor offices in the BESSEL building

� ZEPHIRO integration building

required for correct operation of systems.

2. REFERENCE DOCUMENTS

Reference documents are the requirements specifications,being:

� VEGA gantry,� VEGA launch table,� VEGA launch complex,� other SLV systems,� VEGA ground checkout equipment,� VEGA launch center,� safety technical specifications: VG-ST-2-C-003-CNES.

Page 8: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 8/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

3. APPLICABLE DOCUMENTS

All standards and decrees in force, as well as all technical specifications of the CNES, and in particular:

� decree dated 14/11/88 related to protection of operatives in buildings using electricalpower,

� standard NFC 13200 related to the distribution of high-voltage electrical power(U<=63kV),

� standard NFC 15100 related to the design, construction, and maintenance of low-voltage electrical systems,

� standard UTE C 15520 related to the construction of LV electrical systems – Practicalguide – electrical lines – laying methods – connections,

� standard NFC 17100 related to lightning protection,� standard CEI 61312.1 related to protection against electromagnetic impulse

generated by lightning,� standard CEI 61024-1-2 related to protection of structures against lightning – General

principles,� standard UTE C 91.005-1 related to electromagnetic compatibility: – Installation and

attenuation guide – General information,� standard UTE C 91-005-2 related to electromagnetic compatibility: – Installation and

attenuation guide – MALT and wiring,� standard UTE C 90-480-2 related to the implementation of systems and practical

methods inside buildings,� guide UIC GESIP DT 67 October 2000: recommendations for the protection of

systems classified as industrial against the effects of lightning,� NFC EN 50.174 Data transmission,� CNES technical specifications, in particular:

� DS IT IR 34 "Ground technical instruction - energy",

� DS IT AP 57 "Earth and ground network",

� DS IT IR 37 "Lightning protection",

� Application instructions DS-SM3 "Management specification applicable tocontractors",

� Vega launch zone lightning study: identification code VG-NT-21-C-0008-CNES,� Zéfiro preparation building lightning study: identification code VG-NT-214033-C-

0013-CNES,� Explosive atmosphere regulations: directive 94/9/CE and directive ATEX

1999/92/CE.

Page 9: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 9/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

4. GLOSSARY

� AC: Alternating current,� AD: To be defined,� ATEX: EXplosive ATmosphère,� AVUM: Attitude Vernier Upper Module,� BCV: Vega ground checkout equipment,� BT: Low voltage,� Cat I: Category I,� Cat II: Category II,� Cat III: Category III,� CC: Direct current,� CCS: Auxiliary system control command,� CDL: Launch center,� CEM: Electromagnetic compatibility,� CNES: Centre National d’Etudes Spatiales,� CSG: Guiana Space Center,� CU: Payload,� ELV: VEGA launch complex,� GE: Generator set,� HT: High voltage,� IEPF: External LPS,� IIPF: Internal LPS,� IP: Protection index,� IK: Impact index,� OF: Open, Closed,� RMO: Operational center and facilities,� SD: Fault signaling,� SDS: Ground subdivision,� TC: Current transformer,� TD: Sub-distribution panel,� TGBT: Low-voltage main distribution panel,� TN: Neutral point treatment of low-voltage systems: « T » Category neutral

connected to earth, « N » earth connected to neutral,

Page 10: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 10/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� TOR: Binary,� TQC: As built,� TCV: Thrust control,� VSO: Seen, no remarks,� ZL1: Launch zone no. 1 (future ZLV),� ZLV: Vega launch zone.

5. PROPOSAL

The proposal shall comprise the supply, installation, connection and all ancillary works related to workrequired and described in this CCTP.

The proposal shall be laid out in compliance with the chapters and sub-chapters of the CCTP and shallbe detailed with full information on quantities and unit prices. A reason for elimination of the proposal willbe the absence of this information.

Any suggestions or differences in relation to the CCTP shall be estimated as a variant and described inan appendix.

Information related to existing facilities and required for the estimate and/or the technical descriptionshall be obtained on the site from the interlocutors involved. A visit to the site is mandatory for theestimate in order to take into account all specific features related to existing systems.

The proposal shall include in-plant acceptance, drawings, diagrams and documents required before andafter works.

The proposal shall integrate the cost related to an adversarial inventory of condition of premises andproperty, with a bailiff, affected by the works.

Errors, omissions or inaccuracies in this document cannot be used as a reason to justify animplementation or supply error as the contractor was aware of the scope of works, the amount of worksand the type of works, and with his professional knowledge, has made up for any details that may bemissing from drawings, the CCTP or addenda.

6. STUDIES, DRAWINGS AND DIAGRAMS

The industrial contractor of the work package shall provide all studies, drawings and documents (non-exhaustive list: single-wire diagrams, HV and LV design document, installation of equipment,nomenclature of equipment, lightning design document, earth network, lightning protection, drawingswith provisions for future works, etc.) required for good completion of site works, for validation prior toworks by the technical department of the CNES (SDS/PL/IR) and the inspection office. Any provisionsomitted shall be the responsibility of the holder of this work package.

Studies shall include vertical selectivity of category II and III systems, in particular.

Page 11: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 11/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

At the end of works, the industrial contractor shall provide all TQC drawings and documents, includingoperational and maintenance documentation for validation by the technical department of the CNES(SDS/G/IN).

Drawings in files shall be produced using AUTOCAD, latest version.

Appended drawings and diagrams:

� Vega launch site (SLV):

� 1601 ED 1739 001 electrical schematic diagrams,

� 1601 ED 1739 002 ground floor power,

� 1601 ED 1739 003 basement power.

� 1606 ED 1739 001 substation 1D60,

� 1600 GD 1739 0004 roadways and miscellaneous networks

� 1602 VD 1739 00012 Gantry longitudinal cross-section

� 1602 VD 1739 00013 Gantry transversal cross-section

� 1602 ED 1739 0002 Gantry Level 18.40

� 1602 ED 1739 0003 Gantry Level 21.20

� 1602 ED 1739 0004 Gantry Level 24.00

� 1602 ED 1739 0005 Gantry Level 26.60

� 1602 ED 1739 0006 Gantry Level 29.20

� 1602 ED 1739 0007 Gantry Level 31.80

� 1602 ED 1739 0008 Gantry Level 34.40

� 1602 ED 1739 0009 Gantry Level 37.00� Offices:

� KEPLER building: 195 ED 1739 0540, 195 ED 1739 7000, 195 ED 17397001, 195 ED 2921 0001, 195 ED 2901 0004

� BESSEL building: 194 ED 1739 0543, 194 ED 1739 001, 194 KD 1739 005

� KEPLER / BESSEL buildings: 1604.BD.1739.0001

7. CONSTRUCTION

7.1. Works

Works shall comprise the supply, installation, connection, startup and validation tests, and allancillary works related to works required and described in this document.

Works may start with regard to the system(s) involved once the VSO is obtained on worksdocuments.

Page 12: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 12/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Plant inspection operations may take place for the equipment involved after the VSO is obtainedfor the following documents:

� purchasing,� acceptance, minimum 15 days beforehand.

7.2. Commitments

The hazards caused by works required are risk of electrocution and short-circuits that may causeburns and/or a fire. Consequently, the contractor of the work package shall implement theprocedures in publication UTE 18 510, for example, lockout/tagout of systems in compliance withsite procedures, certified personnel according to works to perform, etc.

Prior to any UPS battery assembly work, the industrial contractor shall forward the procedure toSDS/PL/IR for opinion. This procedure shall specify the certificate(s) of personnel accredited tocarry out work on batteries.

7.3. Inspection:

An inspection shall be carried out at the end of electrical system works:

� by the contractor of this work package that will provide inspection data sheetsconcerning equipment and systems,

� by an approved organization that will provide a verification report in compliance witharticle 53 of the decree dated 14/11/88 and the order dated 20/12/88 setting down therules and methods of the verification. This service is not the responsibility of thecontractor of this work package.

Additional inspection operations requested in this document and of a non-regulatory type are theresponsibility of the contractor of this work package.

8. VEGA LAUNCH COMPLEX

The VEGA launch complex requires, as part of the activities carried out:

� an earth network,� bunker and gantry lightning protection,� power supplies in categories I and II,� production and distribution of low-voltage power in categories I, II and III� launcher lighting.

Page 13: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 13/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.1. Classification of rooms

The rooms or zones of the bunker and of the gantry are classified as follows:

� Explosive Atmosphere (ATEX) zone or room of the gantry:

� closed vessel circulating in the gantry: entrance level 14200, lift, lift routes torooms, levels 29200 and 31800:� 3-meter volume around the walls of the vessel,

� AVUM and its fueling process:� propellant rooms at levels 29200 and 31800,� 15-meter volume around the outgassing vent, AD,� 5-meter volume around the AVUM fueling zone, level 31800 to level

37600, AD,� 3-meter volume around all other units, AD,� gantry mobile platforms,

� non-ATEX zones or rooms: all rooms or zones not indicated above.

The entire VEGA launch site is classified as a pyrotechnical room according to the safetyspecification document.

8.2. Earth network

The contractor of this work package shall provide photos covering 20% of the various phases ofthe non-visible construction part (buried) of the earth network, to be appended to the specific file« earth network, lightning protection and EMC ».

8.2.1. Common units

All networks shall be interconnected with the general earth network of the site by means of a95 mm² cross-section bare copper cable, routed with high-voltage outgoings and supplies.The network resistance shall be less than 1 ohm (measurement made before interconnectionwith equipotential bondings ).All connections shall be by silver solder brazing.

8.2.2. Delivery substation ground ring earth circuit (1D60)

An earth network laid on a ground ring shall be made with a bare copper conductor, minimumcross-section120 mm².The earth network shall be connected by silver soldering to the reinforcement network of thesubstation and to natural conducting items of the construction by a 95mm² cross-sectionconductor.

Page 14: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 14/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.2.3. BUNKER ground ring circuit

The existing ground ring earth circuit is kept and assumed to be in good condition. However,this network shall be completed or remade if necessary. As civil engineering work shall becarried out in the front zone, the earth network shall be built using bare copper cable, minimum120 mm² cross-section, interconnected with the existing ground ring network to make up aloop.The rebuilt earth network(s) shall be connected by silver soldering to the reinforcement of thebuilding and to natural conducting items of the construction by a 95mm² cross-sectionconductor.The platform which will be created for air conditioning unit heaters shall be provided with aground ring as described below and shall be connected to the bunker ground ring.

8.2.4. Delivery substation exposed metallic parts and equipotential frames (1D60)

Exposed metallic part and equipotential frame collectors shall be installed in the substation.Each collector, minimum size 32x5x400 mm, shall be silver soldered to the ground ring earthcircuit by a bare copper cable, 120 mm² cross-section, by means of a control bar.All exposed metallic parts and equipotential frames such as HV cells, LV panel, cable trays,metal piping, etc. shall be connected to the earth collectors, which will be created usingappropriate cross-section copper cables (minimum 29 mm²).Equipotential bondings shall be made between all exposed metallic parts not mechanicallyinterconnected.

8.2.5. BUNKER and GANTRY exposed metallic parts and equipotential frames

Exposed metallic part and equipotential frame collectors are installed in different rooms. Referto the paragraph on room equipment. In all cases, these collectors are to be installed at eachchangeover point of ZPF zones.Each collector, minimum size 32x5x400 mm, shall be connected by SILVER SOLDERING tothe ground ring earth circuit by a bare copper cable, 120 mm² cross-section, by means of acontrol bar.All exposed metallic parts and equipotential frames such as distribution panels, cable trays,metal piping, etc. shall be connected to earth collectors which will be created using appropriatecross-section copper cables (minimum 29 mm²).Equipotential bondings shall be made between all exposed metallic parts not mechanicallyinterconnected and in particular:

� door frames (not fixed to metal structures) and metal structures of the building by alink, as short as possible, made of 25 mm² (minimum) cross-section bare coppercable,

� doors and frames by clips made of flexible copper braids or conductors, 10 mm²(minimum) cross-section,

� etc.

Page 15: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 15/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

For cable trays, a 29 mm² cross-section earth cable will be routed with cable trays, and eachcable tray unit shall be connected to the cable by two BB terminals. All exposed conductiveparts such as those listed below shall be connected to this earth cable:

� piping routed nearby,� metal structures,� the gantry, at each level,� the mast, at each level,� etc.

8.2.6. BUNKER and GANTRY electron masses and measurement grounds

Electronic mass and measurement ground collectors shall be located in the different rooms.Refer to the paragraph on room equipment. The purpose of these collectors is to connect thevarious 0 V reference points of the low-level energy circuits.Each collector, minimum size 32x5x400 mm, shall be connected by SILVER SOLDERING tothe ground ring earth circuit by an R02V cable link, copper cross-section 1x50 mm², by meansof a control bar, identified with a special label.

8.2.7. Launcher ground

At level 14000, two ground braids of a sufficient length, flexible, minimum cross-section 50mm², with devices for connection to the launcher, shall be installed. These braids shall beconnected to table exposed conductive parts and to the equipotential network of the mast andgantry, then connected to the bunker ground ring .

8.2.8. Mobile platform exposed conductive parts

A 50 mm² cross-section flexible braid shall be routed with each supply line of the platforms.The origin of the braid shall be the platform cutoff switch by means of connection to the earthcable and the gantry structure for connection at the mobile platforms to a collector, minimumsize 32x5x400 mm.For each mobile platform, the contractor of the work package shall provide all the equipotentialbondings as follows, between the collector above and the platforms:

� by cable between the terminal block and the fixed units,� by flexible braids between the movable units and the fixed units,� by a flexible isolated braid, length 20 meters approx., cross-section 50mm², from the

terminal block for connection to the launcher. The connection principle to thelauncher by bolting or with a clip is not defined but must be included in the service.

8.2.9. Operator exposed conductive parts and exposed conductive parts of other units

To link operators and other units to the earth network, connection devices consisting of adrilled flat bar and round bar, with the following dimensions, shall be provided in each angle ofeach level, including for mobile platforms:

Page 16: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 16/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� flat bar: 32x5x400mm, minimum,� round bar: 20 mm diameter approx.

The connection devices above shall be connected directly to the earth conductors routedvertical to the building.

8.2.10. Propellant room exposed conductive parts

In the propellant room of the gantry level, an earth collector, minimum size 32x5x400 mm,shall be installed for connection of all exposed conductive parts in this room and especially thekarts. For the karts, conductors or flexible braids, minimum cross-section 35mm², shall beprovided. One end shall be connected directly to the collector indicated above and the otherend shall be provided with a manually operated connection system.The kart earthing devices shall be provided with supports with manually operated winders.

8.2.11. Network interconnections

The contractor of this work package shall provide interconnections for earth networks far fromthe bunker using bare copper cables, cross-section 95 mm², as included in the exhaustive listbelow:

� Substation 1D60,� Camera shelters,� Lighting masts,� Collector tank for flame chute water,� Collector tanks and N2O4 storage tanks,� Etc.

8.3. Lightning protectionThe bunker and the gantry shall be protected against direct and nearby lightning strikes. Theprotection level defined in the lightning study is I + additional measurements with anefficiency equal to 1.To take specific features of lightning into account, direct or nearby strikes, related to the site,the systems of the bunker shall also be protected against lightning according to the leveldefined in the lightning study. Furthermore, lightning protection systems shall satisfy therequirements for the lightning protection zones, level 2 (ZPF2).The contractor of this work package shall:

� provide from an organization (such as ONERA) with good knowledge on lightningprotection and electromagnetic fields in the space domain and space base installationdomain at KOUROU, the study related to the direct lightning strike protection systemof the launcher and modeling to confirm the value of the system interior field,

� at end of works, « MESA » type measurements (system developed by ONERA,APAVE, etc.),

Page 17: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 17/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� provide photographs covering 20% of the various phases of the non-visibleconstruction part (buried) of the earth network, to be appended to the specific file« earth network, lightning protection and EMC »,

� justify qualification and training levels in the high and low current fields.

8.3.1. External LPS ( IEPF )

The external LPS is intended to intercept direct lightning strikes, direct lightning currentbetween the impact point and the earth and disperse the current without causing anymechanic or thermal damage to the structure and no dangerous surge voltages for personneland equipment to protect.

8.3.1.1. Capture device

8.3.1.1.1. Delivery substation (1D60)

The lightning capture device shall be made up of a tinned flat copper ring, cross-section 30x2 mm, with a 50 cm minimum capture rod located at each angle of thebuilding, soldered or connected to the flat bar.

8.3.1.1.2. Bunker

The lightning capture device shall make up a 5x5 m size meshed cage.

The device shall be made of special conductors (30x2 mm cross-section tinned flatcopper bar) and shall be installed above the terrace sealing system and under theheavy-duty pavement.

On the terrace, the following items are connected to the capture device:

� metal units such as guard rails, rolling tracks, etc. every 5 meters,

� small metal units such as lighting columns, etc.

8.3.1.1.3. Gantry and launcher

The lightning capture device for the launcher shall be made using the gantry. Thisdevice shall be made of:

� a 5x5 m size meshed cage,

� natural components (framework) and capture rod(s), size depending on size ofunit(s) to protect, 50 cm minimum. The rod(s) shall be installed at element(s)to protect. The elements to protect, as described in this document, are theaircraft warning lights. The contractor of the work package shall present ageneral scope of work.

Page 18: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 18/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.3.1.1.4. Umbilical mast

The mast is located in the chamber of the launcher lightning capture device.Consequently, the mast is protected against lightning.

8.3.1.2. Down conductors

8.3.1.2.1. Items common to all down conductors

They shall be made of tinned flat copper bar, cross-section 30x2 mm, and shall beconnected to:

� reinforcement bars of the bunker at level 14000,

� capture device,

� earth evacuation devices,

� ground ring, existing for the building.

Mechanical protection shall be provided up to a 2-meter approx. height.

Down conductors must be located at least 1 meter from openings.

8.3.1.2.2. Delivery substation (1D60)

The capture device ring shall be connected to down conductors located at eachcorner of the substation.

8.3.1.2.3. Bunker

The capture devices shall be connected to down conductors located around thebuilding. The average distance between two down conductors shall 10 m.

At down conductors, as straight as possible, shall be connected:

� the rails of the transporter docking platform,

� fluid piping other than power, in front of each down conductor,

� cable trays of the electrical systems or other systems, in front of each downconductor. Cables on cable trays shall not exceed the flange edge,

� supports for high- and low-voltage cable chains.

Page 19: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 19/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.3.1.2.4. Gantry

Down conductors shall use the metal structure and, considering the size of thegantry, four down conductors shall be provided, one in each corner.

To take into account gantry movement operations, at the foot of the gantry, for eachdown conductor, an automatic clamping connection and disconnection device shallbe installed, working on the principle of the finger, length 0.5 meter, sliding in a 1-meter long fork, compressed with springs, plus a bolted connection with flexiblebraid and a 95 mm² cross-section flat bar, made of copper, as straight as possible.

The doubling, connection and disconnection devices, shall be installed at the gantrydown conductors and shall make links with the down conductors of the building,pending in the rear and front zone of the launcher. These down conductors shall becommon with those of the bunker.

8.3.1.2.5. Mast

The all-metal structure shall be connected at the four down conductors of the gantry,common with those of the bunker, with tinned copper flat bar, cross-section 30x2mm. Links shall be as straight and as short as possible.

8.3.1.3. Earth evacuation devices

Each lightning current evacuation down conductor shall be connected to an earthconnector made up of 30x2 tinned copper strips, laid in a radial pattern under theground, depth at least 50 cm, located 1 meter from the building, size:

� 3 m minimum per radial system for the bunker except for the radial systemat the gantry, at the launcher,

� 8 m minimum with stakes at the end of each strip for the 4 radial systemsat the gantry, at the launcher.

Each lightning arrestor earth connection of the bunker shall be connected to the SLVground ring by a tinned copper strip, cross-section 30x2 mm.

A disconnection device shall be located at each radial system, after interconnectionwith the ground ring.

The resistance of each lightning arrestor earth connector shall be less than 10 ohms(measurement made before interconnection to ground ring).

Page 20: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 20/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.3.1.4. Lightning counters

8.3.1.4.1. Delivery substation

A specific lightning counter shall be installed on a down conductor for the meshedcage down conductor, without signal transfer.

The characteristics of this lightning counter are as follows:

� detection of the lightning current on the meshed cage down conductors, inrelation to a preprogrammed threshold,

� 2.5 kA sensitivity threshold, approx.,

� impulse counter,

� sealed polycarbonate box (IP minimum 47),

� connection to down conductors with 30x2mm flat bar,

� with attachment flanges.

The contractor of this work package shall perform calibration and/or testing of thelightning counter, and provide a report delivered by an independent organization.

8.3.1.4.2. Bunker and launcher lightning protection

Two special lightning counters shall be installed at the bunker for the meshed cage,located diametrically opposite from each other (one in the front zone and one in therear zone).

The characteristics of these lightning counters are as follows:

� lightning counter detection on meshed cage down conductors, in relation to apreprogrammed threshold,

� 2.5 kA sensitivity threshold, approx.,

� impulse counter,

� optical transfer of impulses,

� sealed polycarbonate box (IP minimum 47),

� « ST » type optical connection,

� connection to down conductors with 30x2mm flat bar,

� with attachment flanges.

The optical fiber transfer shall be connected in the RMO room of the bunker forrouting to the CCS by the RMO optical fiber network. The contractor of this workpackage shall provide:

� with the approval of the contractor of the low-current work package, allconnections and equipment required for good operation of the system,

Page 21: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 21/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� the calibration and/or testing of the lightning counter and provide a reportdelivered by an independent organization.

8.3.1.5. Equipotential bonding of external exposed metallic parts

All exposed metallic parts shall be interconnected to the capture devices and downconductors, even if located more than 1 meter from the capture devices and downconductors.

Links shall be as short as possible and will be made of a conductor of same type asthat used to make down conductors or the capture device.

8.3.1.6. External links between buildings

To protect electrical systems from induced lightning currents, the high-currentexternal links shall be made with cables fitted with two steel strips, type MTS 220 orsimilar for HV cables and RGPFV or similar for LV cables.

At the entrance to the buildings involved, one or more special earth collectors shallbe installed in order to connect:

� the strips of high- and low-current cables, all types of current,

� lightning arrestors, where applicable,

� non-electric piping: water, air conditioning, etc. All metal piping.

Collectors are located on drawings for information purposes.

The connections at incoming piping are at 360°C and the sealing sheath will berebuilt.

The collector(s) shall be directly connected to the ground ring by a flat copperconductor, 30x2 mm, by the shortest possible route.

Other piping (low current, pipes, etc.) entering and leaving the building andconnected with the neighboring buildings shall be earthed when entering thebuilding by means of a collector connected to the ground ring. This requirementimposes that low-current lines are made of cables with reinforcing strips.

All systems involved entering the building shall be located at a single point ifpossible.

8.3.1.7. Common provisions

Special care shall be taken to prevent electrolytic couples and/or galvanic coupleswith different materials. Application of paint on galvanized steel shall be incompliance with SGS 436.

The 30x2 mm flat bar shall not be drilled. Connection devices or assembly devicesusing silver solder or special screw type couplings will be used.

Page 22: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 22/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

At all construction stages, to facilitate lightning current flow, the curve radii andangles made by the strip shall comply with the requirements in documents indicatedin this CCTP.

8.3.2. Internal LPS ( IIPF )

The internal LPS is provided to prevent the occurrence of potential differences thatmay entail the formation of dangerous sparks when lightning current flows in aconductor.

8.3.2.1. Equipotential bonding of internal exposed metallic parts

Internal exposed metallic parts located less than 1 m from capture devices anddown conductors shall be interconnected with the metal structure of the building bya link, as short as possible, made of bare copper cable, 16 mm² minimum.

8.3.2.2. Equipotential bonding of internal exposed metallic parts of gantry andmast

To decrease the electromagnetic radiation between the mast, the gantry and thelauncher, the following equipotential bondings will be made between:

� the mast and the gantry at levels 22600 and 47000 by means of fingertype devices sliding in a fork, compressed with springs. These devices shall besized appropriately to take into account the gantry movement operations.

� the launcher and the mast according to the principle described in the"Mobile platform exposed conductive parts" paragraph.

8.3.2.3. Lightning arrestor protection

Four-pole, low-voltage lightning arrestors (head protection) shall be installed at thesecondary terminal of each distribution transformer. The characteristics of lightningarrestors are as follows:

� maximum steady-state voltage Uc = 440 V,

� maximum discharge current Imax >= 65 kA wave 8/20,

� nominal discharge current In >= 20 kA wave 8/20,

� protection level Up <= 2.5 kV.

These lightning arrestors shall be connected as close as possible to the low-voltageoutputs of the transformers, in boxes integrating the lightning arrestor and itsprotection system, if any. The earth link shall be as short as possible and connecteddirectly to the ground circuit.

Four-pole, low-voltage lightning arrestors (sectioning protection) shall be installed forlinks between buildings. The characteristics of these lightning arrestors shall be asfollows:

� maximum steady-state voltage Uc = 440 V,

� maximum discharge current Imax >= 40 kA wave 8/20,

Page 23: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 23/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� nominal discharge current In> = 15 kA wave 8/20,

� protection level Up <= 1.5 kV.

These protection systems shall be located on links from the outside. Non-exhaustive list:

� the supply of the flame chute water collection tank.

Low-voltage lightning arrestors (terminal protection) shall be set up for links toexternal equipment (lighting, etc.):

� maximum steady-state voltage Uc = 275/440 V,

� maximum discharge current Imax >= 15 kA wave 8/20,

� nominal discharge current In >= 5 kA wave 8/20,

� protection level Up <= 1.5 kV.

These protection systems shall be located on the links. Non-exhaustive list:

� launcher lighting for all links,

� external lighting and power supplies for camera shelters, all systems,

� aircraft lights.

Lightning arrestors on external links shall be installed at the entry to the buildings inkey-locked boxes integrating the lightning arrestor and its protection system, if any.The most direct and shortest possible earth link (less than 50 cm) shall beconnected directly to the ground of the electric box. The box ground shall beconnected to the collectors of the lightning arrestors and exposed conductive partsby the shortest possible direct link. The collector shall be interconnected with theground ring, with a 120 mm² cross-section conductor.

8.4. Electromagnetic compatibility (CEM) protection

Systems are broken down into two groups for electrical compatibility protection:

� Electrical equipment and miscellaneous equipment,� Sensitive equipment.

The electromagnetic compatibility protection systems shall meet the requirements stipulated forlevel 2 lightning protection zones (ZPF2).

Page 24: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 24/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.4.1. Electrical equipment and miscellaneous equipment

Electrical equipment and miscellaneous equipment involved is installed in the following rooms:

� Transformer room,� Low-voltage main distribution panel (TGBT) room,� Air-conditioning room and in particular the control room,� UPS and battery rooms,� UPS room corridors,� Communication and safety means rooms,� Mast foot room,� Connection room.

For these rooms, the contractor of this work package shall:

� For the bunker: provide the reinforcement bar links in the ground, four points ifpossible, to the earth terminal block. To meet this requirement, this contractor shallforward the requirements concerning holes in order to correctly carry out site work tothe civil engineering work package contractor.

� For the gantry: provide the links between the earth terminal blocks and the metalstructure of the gantry. These links shall be as short as possible.

8.4.2. Sensitive equipment

Sensitive equipment concerns the racks. The racks shall be installed on technical floors, and therooms involved are:

� 002 bunker: TVC process room,� 013 bunker: VES process room (Vega Electrical System, ex MFEG),� 101 bunker: CU rack room,� 103 bunker: BCV rack room,� level 21200 gantry: RMO rack room,� level 24000 gantry: TCV rack room,� level 29200 gantry: TCV rack room,� level 31800 gantry: DVT rack room,� level 37000 gantry: BCV rack room.

To overcome any electromagnetic disturbance, a ground reference point will be made. Thisreference point under the technical floor shall be made up of 30x2 mm tinned copper flat bar typeconductors, as follows:

� one equipotentiality ring around rooms, at 20 cm from ground,� one 1.2x1.2 m ground grid, ends connected to the ring.

Page 25: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 25/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The ground reference point shall be connected to the equipotentiality bars (ground terminal blocks)of rooms and:

� reinforcement bars at the four corners, concerns the bunker,� at metal structures in four corners and metal walls every 2 meters, concerns the

gantry.

The purpose of this ground reference point is to connect up all equipotential frames and exposedmetallic parts of these rooms, i.e.:

� the metal frames of racks, boxes and consoles,� the cable trays under the floor,� the cylinders and metal structures of the technical floor, as follows:

� all ends to the ring,

� all cylinders to the grid,� all incoming non-electrical and electrical lines, including air conditioning sheaths.

Connections shall be made as follows:

� silver soldering for the ring and the grid,� 30x2 mm braids, maximum length 300 mm approx., for racks, connected to:

� the grid,

� the racks by 8 mm diameter fittings,

� by silver-soldered joints for items other than those indicated above. Conductors shallbe made of 30x2 mm flat bar or braids.

8.4.3. All systems

All incoming lines will enter the rooms at the same location. At the entering point, an earthcollector connected to the ground reference point shall be installed to connect all incoming lines.Connections to these lines shall be over 360°C, preferably through a copper plate for non-electricallines.

Page 26: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 26/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.5. Supply and production of energy for the VEGA launch complex

8.5.1. Current distribution principle

The Ariane 5 site systems in the VEGA launch zone are supplied with 20000V high-voltagepower in categories I and II by a branch line for each category, as follows:

� category I: substation 1D7 to substation 1D42,� category II: substation 1D30 to substation 1D42

These branch lines are located to the rear of "building P" in ZL1 (future ZLV).

8.5.2. Supply and production principle of categories I and II

The systems in the VEGA launch zone are supplied with electrical power in categories I and IIby the branch lines of the 20000V high-voltage (HV) network of the ARIANE 5 site by theinsertion of the high-voltage delivery substation called 1D60 in the lines at the rear of "buildingP" in ZL1 (future ZLV). This substation will supply the VEGA launch complex and substation1D42 according to the principle defined above.The HV links from the delivery substation 1D60 go to the VEGA building to a specific room,called the transformer substation (1D61) which includes the HV/LV transformers to drop downthe HV supply voltage (20kV) to the low-voltage (LV) 410V user voltage, as follows:

� cold production and air conditioning systems: by two transformers supplied from theHV network: one on category I and the other on category II,

� auxiliary systems: by two transformers supplied from the HV network: one oncategory I and the other on category II.

The low-voltage networks downline from the transformers, for each type of system, can becoupled to the category I or II networks automatically if one category is absent or following aCCS command.The transformer power is defined according to the power budget taking into account a growthpotential of:

� 30% for systems other than air conditioning,� 15% included in air conditioning equipment.

8.5.3. Category III production principle

The systems to be supplied in category III are classified in two families:� redundant systems: on two separate networks with two types: category III A and

category III B,� customer systems: with two types: category III CU B, bunker room, and category III

CU H, in the mast,� TVC rack system: on category III in bunker room.

Page 27: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 27/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The different production methods of category III are carried out using the low-voltage networksof categories I and II of the VEGA launch complex, as follows:

� categories III A and III B: by redundant UPSs per type installed in a special roomdistinct from batteries,

� category III CU: by a UPS per type B and H installed in a special room distinct frombatteries,

� category III TVC rack: by a UPS installed in a special room distinct from batteries.The UPS power is defined based on the power budget taking a 30% growth potential intoaccount.

8.5.4. Category II power budget

The power budget is defined using the information provided and the systems described in thisdocument, i.e. air conditioning + cold production, drive force, lighting, auxiliary system, etc.The industrial contractor shall provide the real budget.

Page 28: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 28/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Building/Level Room No. Equipment Characteristics P (kW) Cos phi P (kVA) SubtotalsBUNKER Foot of mast 001 Lighting 59 m2 at 300 lux 1.0 0.85 1.2 (kVA)basement Process 002+ Lighting 58 m2 at 300 lux 1.0 0.85 1.2

013, 015 TVC racks, cat III 250A, 270V DC 70.0 1 70.0 Lightingat 018 MFEG racks, cat III 5x1500w 7.0 1 7.0 11

Gallery + lobby 3+14+11 Lighting 153 m2 at 200 lux 2.0 0.85 2.4Means 004 Lighting 89 m2 at 3001ux 1.5 0.85 1.8Communications Communication racks, cat III 5x800W 4.0 0.85 4.7 FMMeans, safety 012 Lighting 40 m2 at 300 lux 1.0 0.85 1.2Lock 005 Lighting 20 m2 at 200 lux 0.5 0.85 0.6 96Technical room 006 Lighting 109 m2 at 200 lux 1.5 0.85 1.8Battery rooms 007 to Lighting 64 m2 at 200 lux 0.8 0.85 o.9 Lighting + FMCU 010 Racks, cat III Complex 10.0 0.85 11.8 108Complex Miscellaneous 2.5 0.85 2.9

BUNKER Front connection 100 Lighting 60 m2 at 300 lux 1.0 0.85 1.2ground floor CU racks 101 Lighting 50 m2 at 300 lux 1.0 0.85 1.2

Lock 102 Lighting 10 m2 at 200 lux 0.5 0.85 0.6 LightingBCV/CCS 103 Lighting 100 m2 at 300 lux 1.5 0.85 1.8 19

BCV racks, cat III 14 to 1500 VA 24.0 1 24.0BCV racks, cat III 4 to 2500 VA 10.0 1 10.0 FMRMO racks, cat III 2x1000W 2.0 0.85 2.4 635CCS racks, cat III 3 to 1000 VA 3.0 1 3.0

C02 104 Lighting 24 m2 at 300 lux 0.5 0.85 0.6Technical room 105 Lighting 54 m2 at 200 lux 1.0 0.85 1.2 Lighting + FMWithdrawal + lock 106+125 Lighting 87 m2 at 3001ux 1.0 0.85 1.2 654

Air conditioning Cat II 7.0 0.85 8.2C02 107 Lighting 40 m2 at 300 lux 1.0 0.85 1.2Fluid 108 Lighting 118 m2 at 300 lux 1.0 0.85 1.2

2 compressors redundant 18.0 0.85 21.2Lock 109 Lighting 20 m2 at 200 lux 0.5 0.85 0.6Electrical 111 to Lighting 128 m2 at 200 lux 1.5 0.85 1.8

117 Divers 2.5 0.85 2.9Air conditioning 118+ Lighting 200 m2 at 200 lux 2.0 0.85 2.4

126+ Cold production/air condition. 380.0 0.8 475.0127 Fire fighting pumps 10.0 0.85 11.8

Miscellaneous 5.0 0.85 5.9Sanitary facilities (men) 119 Lighting 0.5 0.85 0.6Sanitary facilities (women) 120 Lighting 0.5 0.85 0.6Booster plumbing 121 Lighting 90 m2 at 200 lux 1.5 0.85 1.8

Booster Power AD 20.0 0.85 23.5Storage 122 Lighting 28 m2 at 200 lux 0.5 0.85 0.6Flame chute water tank Pump 20.0 0.85 23.5Complex Miscellaneous 20.0 0.85 23.5

GANTRY Complex Lighting, lev. 14uuu 235m2 at 300 lux 4.0 0.85 4.7Lighting, lev. 15600 215 m2 at 300 lux 4.0 0.85 4.7Lighting, lev. 18400 215 m2 at 300 lux 4.0 0.85 4.7 LightingLighting, lev. 21200 215 m2 at 300 lux 4.0 0.85 4.7 46Lighting, lev. 24000 215 m2 at 300 lux 4.0 0.85 4.7 FMLighting, platforms 215 m2 at 300 lux 6.0 0.85 7.1 273Lighting, lev. 54000 at 200 lux 4.0 0.85 4.7 Lighting + FMStairs at 1501ux 9.0 0.85 10.6 319RMO racks, cat III 21200 4.0 0.85 4.73 racks, cat III lev. 24000 270V, 30A 25.0 1 25.03 racks, cat III lev. 29200 270V, 10A 8.0 1 8.0BCV racks, cat lll lev. 37000 800+1000W 1.8 0.85 2.1INTF racks,cat lll lev. 37000 3.0 0.85 3.54 pumps redundant 7.2 0.85 8.5Lift, lev. 52600 40.0 0.85 47.1Platform 4x12.5 50.0 0.85 58.8Doors, lev. 18400 5.0 0.85 5.9Crane, lev. 60000 57.0 0.85 67.1Air conditioning 26600 50.0 0.85 58.8Decontamination, lev. 55000 13.0 0.85 15.3Miscellaneous 10.0 0.85 11.8

OUTSIDE Building Lighting, surroundings 30 lux 10.0 0.85 11.8 NormalRoadways 30 20.0 0.85 23.5 lighting

Launcher Lighting 200 to 1000 lux 50.0 0.90 55.6 35General TOTAL 954 1 214 Light. 111

Growth coefficient, without cold production + air conditioning, room 118 0.6 443Growth coefficient, with cold production + air conditioning, room 118 0.8 380

TOTAL growth, without gantry movement (kVA) 823

The power required in categories I and II for VEGA site requirements is 823 Kva.

Page 29: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 29/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Depending on the power budget, the growth potential to take into account and the usecoefficient of the transformer, the standard power level of transformers for each type ofsystem, i.e.:

� cold production and air conditioning systems, room 118,� auxiliary systems,

is indicated in the following table.

System Requirement(kVA)

Growthpotential

Usetransformer

at Pn

Power (kVA)standard

transformer, cat I

Power (kVA)standard

transformer, cat II

- cold production and air conditioningsystem, room 118

380 15%included inrequirement

80% 630 630

- auxiliary systems and gantry airconditioning systems

443 30% 80% 800 800

Pn: transformer nominal power

Note: This document takes into account that the required power is available on the site and is definedabove in category I and II networks to meet the power requirements of the VEGA systems.

8.5.5. Category III A and B power budget, UPS power

Building Room Racks Qty UP(Kw)

Cos(phi)

TP(Kva) Qty UP

(Kw)Cos(phi)

TP(Kva)

004communications RMO 4 1 0.85 4.00 4 1 0.85 4.00

013 process MFEG 3 1.5 0.85 4.50 2 1.5 0.85 3.00103 BVC BVC 7 1.5 0.85 10.50 7 1.5 0.85 10.50

BVC 1 2.5 0.85 2.50 2 25 085 5.00CCS 5 1.5 0.85 7.50 5 1.5 0.85 7.50

115 TGBT TGBT 1 1 0.85 1.00

bunker

126 Air cond Air cond 1.5 1 0.85 1.5021200 RMO 2 1 1.00 2.00 2 1 1.00 2.0024000 270V 30A 2 8.1 1.00 16.20 1 8.1 1.00. 8.1029200 270V 10A 1 2.7 1.00 2.70 2 2.7 1.00 5.4037000 BVC 2 1.5 0.85 3.00 1 1.5 0.85 1.50

RMO 2 1.5 0.85 3.00 2 1.5 0.85 3.00

gantry

RMO 2 1.5 0.85 3.00 2 1.5 0.85 3.00Total 58.9 55.5

Growth 0.7 Requirement 41 0.7 Requirement 39UPS Growth potential Use at Pn Category IIIA (kVA) Category IIIB (kVA)power 25% 80% 80 80

Page 30: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 30/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.5.6. DC power budget of rack TVC 270V 250A

A TVC rack shall be installed (another one optional), powered from a special UPS. The 250 Avalue announced is a peak value. It is necessary to take into account a 150 A current, todefine the requirement per rack, which results in: 270x150= 41 Kva. The current drain isaround the maximum current value announced.For operating reasons, the rack power source must be of the uninterruptible type.Consequently, the power source must be from accumulator batteries with a 10-minute batterytime after 3 years.

8.6. Delivery substation to create: 1D60An HV delivery substation (1D60) will be created in ZLV at the location of the building marked"P" in ZL1, future ZLV. This substation will supply the systems of Launch zone no. 3 and ofZLV.

8.6.1. Power supply of substation 1D60 in ZLV and resupply of substation 1D42

The insertion of substation 1D60 in the 20 000V HV branch lines of categories I and II, as perfollowing principle:

� category I: between substations 1D7 and 1D42,� category II: between substations 1D30 and 1D42,

will make it possible to power ZLV systems which will resupply substation 1D42.Connections and links, with junction boxes, to existing cables shall be by interrupting the linesat the rear of "building P" of ZL1 (future ZLV) as follows:

� to supply substation 1D60: from the lines from 1D7 and 1D30, by extending thecables,

� to resupply substation 1D42: from 1D60 reusing the existing lines, by extending thecables.

The characteristics of the cables shall be as follows:� voltage: 12/20 KV,� insulation: PR,� cross-section: 25 mm² to remain homogeneous with the existing link (standardized

cross-section 35mm²),� reinforcement: 2 steel strips,� sealing: lead sheath� external sheath: black PCV,� specifications: MTS 220, three-pole

Page 31: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 31/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.6.2. Equipment

The HV delivery substation shall be equipped with:� incoming switch cells from 20 kV branch lines, i.e. 1 for category I from 1D7 and 1

other for category II from 1D30,� voltage transformer cells, i.e. 1 for each category (I and II),� protection and cutoff circuit breaker cells for outgoings to substation 1D42 of Launch

zone no. 3, i.e. 1 for each category (I and II),� protection and cutoff circuit breaker cells for power supplies of SLV transformers, i.e.

2 for each category (I and II),� protection and cutoff cell for the auxiliary equipment transformer,� 20 kV voltage drop-down transformer to 410 volts for auxiliary equipment,� HV cell control and command,� a space between network cells of categories I and II for « coupling », if applicable, of

category I and II network incomings,� one set of spare HV fuses for the auxiliary equipment transformer, fuses available on

the platform,� regulatory posters and safety instructions,� safety equipment (stool, gloves, sticks, etc.),� operating data sheets,� auxiliary equipment TGBT,� normal lighting based on 200 lux minimum, controlled by pushbuttons located at each

entrance,� exterior lighting above each entrance provided through windows fitted with low-

consumption lamps, controlled by clock + ON, OFF and automatic switch,� safety lighting with autonomous units secured to each exit, portable,� socket outlets 2P+T 10/16A installed at each entry,� a socket outlet 4P+T 20 A installed at one entry,� earth collectors.

8.6.2.1. 20 KV HV branch line incoming switch cells

The HV cable of each incoming of the 2 branch lines (1D7 and 1D30) is fed to the deliverysubstation1D60, and shall be connected to an incoming switch cell.

8.6.2.1.1. Characteristics

The characteristics of the incoming switch cells are as follows:� 400 A three-pole set of busbars,� one 400 A section switch, cut off in SF6, CIT type control,

Page 32: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 32/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� 3 current transformers, ratio 100 – 200/5A, class 5P10 - 0.5,� one earth isolator,� operating devices,� power on indicators,� connection lands for cables,� locking systems with keys, compatible with the existing branch line cells, and in

compliance with the description in ZLV and VEGA offices,� auxiliary position contacts on terminal boards,� incoming cells: an LV compartment comprising:

� the programmable operating system, type SEPAM, tropicalized for thefunctions described in paragraph below,

� voltage and current test boxes,� 50-watt resistor with a thermostat,� closed bottom.

8.6.2.1.2. Locking

Key locks between switch cells and existing equipment shall be compatible. Key locking shallbe as follows:

� for category I:

� at substation 1D42, keys and locks of cell IM (incoming from substation 1D7before work, incoming from substation 1D60 after work) shall be recoveredand installed at substation 1D60 on the IMC cell from substation 1D7,

� at substation 1D42, new locks shall be installed on cell IM (incoming fromsubstation 1D7 before work, incoming from substation 1D60 after work) toensure servo-control between the cells of substation 1D60 and of substation1D42,

� for category II:

� at substation 1D42, locks and keys of cell IM (incoming from substation 1D30before work, incoming from substation 1D60 after work) shall be recoveredand installed at substation 1D60 on the incoming cell of substation 1D30,

� at substation 1D42, new locks shall be installed on cell IM (incoming fromsubstation 1D30 before work, incoming from substation 1D60 after work) toensure servo-control between the cells of substation 1D60 and of substation1D42,

8.6.2.2. Voltage transformer cells

Each power supply category (I and II) shall be provided with a voltage transformer cell with thefollowing characteristics:

� one 400 A three-pole set of busbars,� one isolator, manual control,

Page 33: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 33/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� one short-circuiting and earthing isolator,� HV protection with 6.3A fuses,� 3 dry-isolation voltage transformers, with phase/ground connection, with the following

characteristics:

� transformer ratio: 20000V√3/100V√3,

� precision class: 0,5 – 1,

� precision power: 30VA,� an isolator and a secondary circuit protection device for voltage transformers,� auxiliary position contacts on terminal boards,� blowing fuse indicator,� an LV compartment fitted with a power supply deck, specific to sepam of the category

involved (existing on SIMPLEX type site), in compliance with the followingcharacteristics:

� 230 V power supply voltage,

� 48 V DC use voltage,

� 1 A min. permanent current,

� 4 Ah min. battery capacity,

� backup power 160 W/1 hour min.

� 50-watt resistor with thermostat,� closed bottom.

8.6.2.3. Transformer circuit breaker cells for ZLV and 20 KV HV branch lines to1D42

A circuit breaker cell shall be installed on:� each set, HV power supply and ZLV transformer, shall be protected by the same

circuit breaker,� each branch line supplying substation of 1D42.

Circuit breaker cells shall have the following characteristics:� one 400 A three-pole set of busbars,� one upline isolator,� one 400 A circuit breaker, cut off in SF6, RI type control, fitted with a motor and a

trigger, type MITOP,� one upline and downline earth isolator,� operating devices,� power on indicators,� connection lands for cables,

Page 34: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 34/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� key locking (between LV general circuit breaker, HV earth isolator, and transformerplug-in terminals),

� auxiliary position contacts on terminal boards,� 3 current transformers with 2 secondary windings, with the following characteristics:

� transformer ratio: 20-40A/5A,

� precision class: 5P15 - 0.5,

� precision power: 7.5VA,� STATIMAX type protection with static relay RAH 411 E (existing on site) or similar,

associated with MITOP trigger,� polarized current test boxes,� 50-watt resistor with thermostat,� closed bottom.

8.6.2.4. Protection cutoff cell for 20 KV HV transformer of auxiliary equipment

The protection and cutoff cell of the HV/LV transformer of auxiliary equipment, supplied incategory II, shall have the following characteristics:

� one 400 A three-pole set of busbars,� one 400 A isolating switch, cut off in SF6, CI2 type control, with trigger,� one earth isolator,� operating devices,� HV protection by striker fuses,� power on indicators,� connection lands for cables,� key locking (between LV general circuit breaker, HV earth isolator, and transformer

plug-in terminals),� auxiliary position contacts on terminal boards,� 50-watt resistor with thermostat,� closed bottom.

8.6.2.5. Transformer of auxiliary equipment

8.6.2.5.1. Supply of the 20KV/410V HV transformer of auxiliary equipment

The characteristics of the link between the protection and cutoff cell and the HV/LV transformerof auxiliary equipment are as follows:

� single-pole cables MTS 223, copper core,� voltage: 12/20 kV,

Page 35: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 35/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� isolation: PR,� screen: aluminum tape,� external sheath: black PCV,� cross-section: 50 mm²,� connection on transformer side: 200A plug-in connectors,� installation method: in sleeve or channel between HV cells and transformers and

reinstalled on cable tray for connection to transformers. Appropriate cross-sectionearth cables will be routed with HV cables.

8.6.2.5.2. Characteristics of auxiliary equipment transformer

The transformer of auxiliary equipment supplied with category II at 20000V voltage will dropthis voltage to the 410V service voltage. The neutral point treatment shall be TN type (neutralconnected to earth and exposed conductive parts connected to neutral) as per paragraph onneutral point treatment of the low-voltage distribution network of categories I and II below.Depending on requirements, the power of the transformer shall be at least 160 kVA.The following shall be connected to the equipotential frame collector:

� the neutral with a 50 mm² minimum cross-section conductor,� the transformer ground by a 50 mm² minimum cross-section conductor,

justified by a design document.The other technical characteristics are defined in the paragraph common to the transformers.

8.6.2.5.3. Servo-control

Servo-control between the transformer and the LV general circuit breaker is scheduled: the2nd HV/LV transformer temperature threshold and absence of voltage at the converter willinitiate opening of the general circuit breaker.

8.6.2.6. HV control-command

All delivery substations of the Ariane 5 site are fitted with a SEPAM 15 control-command,make MG, linked with a TSX 47 programmable controller at CDL3. So that site systemsremain homogeneous, it is recommended to choose MG/SCHNEIDER equipment withcharacteristics compatible with existing equipment (for example, the « SEPAM » is anintermediary in commands. Decisions are taken by the programmable controller).Management of the delivery substation HV and LV control-command functions shall beperformed for each category (I and II) by a multifunctional digital unit, type SEPAM 1000+ forexample, with characteristics to be defined according to the functions managed, compatiblewith existing equipment in order to integrate the functions to manage. Equipment shall bedelilvered with a console for operation.The functions shall be defined after existing equipment is examined. Functions shall take intoaccount, non-exhaustive list:

� the positions of HV switches,� the positions of HV isolators,

Page 36: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 36/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� the positions of HV circuit breakers,� the auxiliary transformer faults, 1st threshold and 2nd threshold,� the faults of the LV circuit breakers of the auxiliary equipment TGBT, fitted with OF

and SD,� the presence of converter voltage of the transformer PTC probe,� the presence of voltage at power supply boards,� measurement of: U, I, W, Wh, Varh, Cos phi, frequency,� etc.

Communication compatibility with the programmable controller TSX47 at CCS of CDL3 and itsconnections (currently MODBUS protocol, 300 bits/s) is part of the services of the Auxiliarysystem control-command work package contractor. However, the contractor of this workpackage must check that adaptation and dialog is possible with selected equipment and links.SEPAM power supplies shall be with 48V via the boards provided above the voltagetransformer HV cells.The interface point is the junction box, to be provided by the contractor of this work package,at 1D60.IMPORTANT: All tests shall be recorded in an acceptance report.

8.6.2.7. HV fault localization

To facilitate troubleshooting on substation 1D60 cable sections to substation 1D42, a Bardin orsimilar type fault indicating device shall be installed on each section.Indicating devices shall be powered from the SEPAM power supply board of the networkinvolved or via a built-in independent power supply.Fault indicating lights shall be located outside substation 1D60.

8.6.2.8. Low-voltage main distribution panel (TGBT) of delivery substation 1D60

A low-voltage main distribution panel shall be installed in substation 1D60 and powered fromthe auxiliary equipment transformer with a 95 mm² minimum cross-section RO2V cable,justified by a design document.This panel, sized according to the equipment to install, with a useful spare space of 30%, willbe at least 1800 mm high, 1600 mm wide and 400 mm deep, installed on a 200 mm base.The panel shall be fitted with key-locked doors and shall house:

� a general circuit breaker, display front type or plug-in type with OF+SD,� a circuit breaker, all poles protected, for the PTC probe converter circuit of the

auxiliary equipment transformer, supply tapped upline from the general cutoff, orangecolored wiring and identification with general voltage supply on, with OF+SD,

� PTC probe converter,� one set of busbars, minimum current 400 amps,� three ammeters and current transformers 250A/5A,� one circuit breaker, all poles protected, for the voltmeter circuit,

Page 37: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 37/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� circuit breakers, all poles protected, for circuits:

� power on indicator,

� safety lighting remote control box,

� roadway lighting: separate for pedestrian ways and traffic roads,

� lighting control outside building 1D60, roadway and barrier by 24-hourprogrammable switch with crystal and 3-position switch (automatic, manualand off),

� lighting outside the substation,

� lighting inside the substation,

� plugs including differentials,

� power supply of HV cell auxiliary equipment, at least one per category,

� resistors,� contactors controlled by programmable switch and 3-position switch,� natural ventilation, resistor on the thermostat,� etc.

All control, indicating, and control-command circuits shall be wired to separate terminal boardsfor each type of circuit and identified with engraved screwed labels. Terminals powered afteropening of the general cutoff shall be orange and identified when general power on.Panel and circuit breaker identification shall be with engraved labels riveted on supports,according to CNES technical specification(s). All conductors, switchgear and control gear, etc.inside the panel shall be identified according to CNES technical specification(s).Cables shall be identified with cable holders, marked with letters and numbers, attached tocables as per CNES technical specification(s).For information: the neutral point treatment is TN according to the paragraph below, neutralpoint treatment of LV distribution for categories I and II.

8.7. Power supplies of 20Kv HV transformers of the ZLVThe characteristics of the links between the circuit breaker cells of substation 1D60 and theHV/LV transformers of ZLV will be as follows:

� voltage: 12/20 KV,� isolation: PR,� cross-section: 35 mm² (standardized cross-section),� armor: 2 steel strips,� sealing: lead sheath� external sheath: black PCV,

Page 38: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 38/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� specifications: MTS 220, three-poleLinks shall be made by burying cables according to the common characteristic paragraph.

8.8. Buried linesTrenches shall be excavated in compliance with good works practice (depth 1.1 m for HV,sand bed, mesh tracer, sleeves under road crossings, etc.).A 95 mm² cross-section bare copper earth cable will be routed with HV cables to make thelinks between the ground rings.At channel inlet and exit, HV, LV, etc. cable strips shall be connected to the earth collectorlocated in the channels with 360°C connections on the cables.Terminals in compliance with the CSG specification will indicate on the ground:

� the cable path, every 50 m,� each change in direction,� junction boxes,

and shall be marked on the topographic plan, in the same manner as cables.One or several indicating sign posts will be installed at the cable entry into the building.Distances between networks shall be observed.

8.9. ZLV transformer substation for cat. I and II energy

8.9.1. Transformer substation

The HV to LV transformer substation located in room 116 of the bunker shall be fitted with:� 20 kV to 410V voltage step-down transformers,� energy metering system,� regulatory posters and safety instructions,� safety equipment (stool, gloves, sticks etc.),� transformer HV terminal unlocking plugs.

Lighting equipment and plugs shall be described in the ZLV room equipment paragraph.

8.9.2. 20KV/410V HV transformer power supply

Links from 1D60 shall be laid, in the room, in channels or sleeves and routed to transformerson cable trays. Earth cables of appropriate cross-section shall be routed with HV cables.At the channel entry, HV cable strips shall be connected to the earth collector located in thechannel, with 360°C connections on cables.

Page 39: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 39/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.9.3. ZLV transformers

For each category I and II, the 20000V voltage shall be dropped to the 410V service voltageby transformers with neutral point connected to earth and exposed conductive parts connectedto neutral (TN).

8.9.3.1. Description

The power ratings of transformers shall be as follows:� for categories I and II of air conditioning and cold production systems: 630 kVA

minimum for the 2 transformers,� for categories I and II of auxiliary systems: 800 kVA minimum for the 2 transformers.

The following will be connected to the equipotential frame collector:� the neutral of transformers by a 300 mm² copper cross-section (minimum) conductor,� the ground of transformers by a 300 mm² copper cross-section (minimum) conductor,

justified by a design document.The other technical characteristics are defined in the common paragraph of HV/LV transformercharacteristics.

8.9.3.2. Servo-control

Servo-control between the transformers and the LV general circuit breakers is scheduled: the2nd HV/LV transformer temperature threshold and absence of voltage at the converters willinitiate opening of the general circuit breaker involved.

8.10. Characteristics common to HV/LV transformersThe common characteristics of transformers are as follows:

� IP31 dry type, aluminum windings,� 23 Kv isolation voltage,� primary voltage: 20 kV with triangle coupling, with plug ± 2.5%,� secondary voltage: 410 V with star coupling (n 11), with neutral disconnected,� plug-in HV terminals, type 200 A, with lock,� LV terminals protected by sealed cover,� thermal device comprising:

� 2 PTC probes located in windings and connected to terminal board with plug-in type connector,

� 1 2-level electronic converter (alarm and triggering), to incorporate in theTGBT.

� maximum environmental temperature 46°C� average daily environmental temperature 36°C.

Page 40: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 40/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.11. Drawings and design documentsThe holder of this work package shall:

� update the existing HV/LV single-wire diagrams (ref. 300 ED 2921 6080 Rev. « K »,CNES 810 ED 2921 6550 Rev. F, Electrical networks - General information: 520 ED1739 5002, etc.), using the same principle.

� short circuit current design documents, earth fault and selectivity related to the partyinvolved, following extension of sections 1D7 – 1D42 et 1D30 – 1D42, based onexisting design documents (810 EC CYSI C002, 810 EC CYSI C013, etc.).

� adaptation of protection systems on the general HV network, if necessary.

8.12. Low-voltage (LV) distribution of categories I and II

8.12.1. Principle

High-voltage/Low-voltage transformers will provide by electrical lines the two low-voltage maindistribution panels located in a special room at no. 115 as follows:

� one TGBT for air conditioning systems, powered by a category I transformer and acategory II transformer,

� one TGBT for auxiliary systems, powered by a category I transformer and a categoryII transformer.

The operating principle of each TGBT shall be as follows:� operational phase: on category II network,� non-operational phase: on category I network

with switchover between networks as follows:� automatically in case of loss of a category,� from CCS for category I or II.

TGBTs shall be backed up by a 670 kVA power mobile generator set. To be confirmed by thesite authority before work.The following equipment shall be powered from the TGBTs:

� high power: by a separate link,� low power: by creation of TDs.

Page 41: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 41/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.12.2. Neutral point treatment of category I and II low-voltage distribution

The neutral point treatment most suited to systems is the neutral point treatment linked to theearth and distribution exposed conductive parts linked to the neutral point (TN) as follows:

� for main distribution, the neutral and earth are the same: TNC,� for terminal circuit distribution, UPS networks 2, the category II rack networks, and

according to the request specified in this document, the neutral and earth shall beseparated: TNS,

in compliance with the following rules:� no TNC distribution downline from a TNS distribution,� TNS type distribution for all active conductors with a cross-section less than:

� 10mm² copper,

� 16mm² aluminum.

Consequently, at the transformers, the neutral shall be:� connected to the earth terminal block by a conductor of an appropriate cross-section,� distributed to main distribution panels by conductor(s) of an appropriate cross-section

and joined to active conductors.With the TNC type diagram, separation of the earth and neutral conductor (PEN) is madeupline from the general cutoff of the cabinet involved if downline distribution is of the TNSdiagram type. This is in order to facilitate troubleshooting of isolation faults.

8.12.3. Low-voltage main distribution panels (TGBT)

8.12.3.1. Power supplies

The low-voltage links between the transformers and each TGBT shall be made of RO2V typecables (copper mandatory) or similar, and of an appropriate cross-section. Implementationshall take into account the following for links made up of cables:

� maximum 4, in parallel,� same cross-section, minimum 240 mm²,� identical length,� symmetrical type laying (stack or layer) on cable tray.

Links between exposed metallic parts of transformers and TGBTs shall be made with 300 mm²minimum copper cross-section conductor(s).

8.12.3.2. Description

Each low-voltage main distribution panel shall be of the size defined according to equipmentinstalled with at least 30% minimum useful spare space and shall be available in columns:

� with metal envelope,� with plug-in type racks,� with rear connection,

Page 42: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 42/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� OKKEN type from SCHNEIDER or similar,� with a minimum number of columns:

� 6 for TGBT called auxiliary systems,

� 3 for TGBT, air conditioning.

Columns shall be fitted with:� a set of power busbars, minimum 3200 amps, for IP 31 and a 35 degree Celsius

environmental temperature, rms short circuit current intensity at least 50KA.� two general circuit breakers, plug-in type, for categories I and II, adapted to the power

of transformers and each one fitted with:

� a standalone control unit with measurement of: voltage, current, power factor,frequency, active and reactive powers, available for RS 485 type link,

� a tamper-proof plate,

� a 230 V / 50 Hz motor controlled by the programmable controller from theCCS for acknowledgement of the following information: coupling on category Ior II automatically if no category is specified or from command to CCS,

� a 230 V/ 50 Hz closing solenoid valve,

� a 230 V/ 50 Hz transmission voltage trigger,

� 4 OF contacts,

� one ready-to-close contact PF,

� 4 pinned contacts CE,

� one supplementary terminal board BS,

� pinned position locking,

� mechanical locking of 2 category I and II inlets,� a manual source reverser between the two category I and II source circuit breakers

and the source from the generator set with current circuit breaker, minimum 1000 A,fitted with:

� a 230 V/ 50 Hz transmission voltage trigger,

� position contacts,

� mechanical locking or key locking between LV circuit breakers of transformers,

� unpinned position locking,� power on relays, upline from general circuit breakers of categories I and II (orange

wiring set) and a set of busbars (common),� power on indicator lights upline from circuit breakers of categories I and II and a set of

busbars,

Page 43: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 43/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� circuit breakers, all poles protected, appropriate thermal and magnetic; eachprotection system shall be provided with OF + SD contacts + unpinning,

� two PTC probe converters for transformers, powered with category III, wiring andterminals in orange with pictogram and signal processing,

� pre-wiring of signals above to recover and convey, in communication in bus mode byCIC board(s) or similar for integration in a programmable controller and transfer toCDL3 control substation by busbar,

Important: In the auxiliary system TGBT, an office automation type UPS will be installed topower the emergency cutoff described later in the document.This UPS shall be powered by the category III network of the TGBT and its characteristicsshall be as follows:

� power according to equipment to supply, minimum 250 VA,� range 10 minutes,� internal protection against surge currents,� general fault summary, to insert in the fault chain involved of category III,� All command, signaling, control-command circuits shall be wired to separate terminal

boards for each type of circuit and identified with engraved screwed labels.� All command circuits powered after cutoff of LV general circuit breakers shall be wired

with orange cables and the switchgear and control gear of these circuits shall beidentified with general voltage open.

� The panel and circuit breakers shall be identified with engraved labels riveted tosupports as per CNES technical specification(s). All conductors, switchgear andcontrol gear, etc. inside the panel shall be identified as per CNES technicalspecification(s).

� Cables shall be identified with label holders, marked in letters and numbers, attachedto cables as per CNES technical specification(s).

8.12.3.3. LV control-command

All TGBTs of Ariane 5 site shall be equipped with a programmable controller TSX 47 totransfer the following information, non-exhaustive list, to CDL3:

� the positions of LV general circuit breakers,� power on indicator lights upline from LV general circuit breakers and sets of busbars,� 1st threshold and 2nd threshold transformer faults,� power on for PTC probe converters of transformers,� LV circuit breaker faults of TGBT,� voltage, current, power, frequency, energy, etc.

Communication compatibility with programmable controller TSX47 at CCS of CDL3 and itsconnections (currently MODBUS protocol at 300 bits/s) is the responsibility of the contractor of

Page 44: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 44/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

the auxiliary system control-command work package. However, the contractor of this workpackage shall ensure that adaptations and dialog are open.Control-command and indicating power supply shall be with 230V, from category III, by settingup a protection for:

� the programmable controller,� pre-wiring.

These protection devices shall be fitted with OF+SD contacts, series wired, connected todisconnectable terminals in TBGTs cat I and II, and inserted as follows:

� programmable controller: in the category III chain involved,� pre-wiring: in the power on control chain upline from general circuit breakers

Category III links shall be over RVFV cables with earthing of strips at both ends, and shall beconnected.The interface point is the junction box, responsibility of the contractor of this work package, inroom 116 of the bunker.IMPORTANT: All tests shall be recorded in an acceptance report.

8.12.3.4. Power supply by mobile generator set

Each TGBT shall be backed up by a mobile generator set, power 670 kVA. For this purpose, itis necessary to schedule for each TGBT:

� outside the building, installation of a connection box with busbars, current 1000Aminimum,

� outside the building, a socket outlet to power the mobile generator set preheatingsystem,

� a power line between the TGBT and the external box, RO2V cable, cross-sectionadapted to the power of the generator set.

8.12.3.5. Energy counting

To count ZLV site power, a counter shall be installed. This counter shall:� take into account the tariff applicable in Guiana,� record the active and reactive energies of the transformers,� be of the triple tariff type,� be readable at distance using a software identical to the one existing on the site

(CEVATEC) and with supply of the service.The interface point is the counter, responsibility of the contractor of this work package, withconnection in room 116.

8.12.4. Sub-distribution panels (TD)

8.12.4.1. Principle

8.12.4.1.1. Bunker

Page 45: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 45/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Sub-distribution panels for the bunker, powered directly from the TGBT, except for the TD ofroom 102 which will be powered by a derivation from the TD of room 103, will be provided forauxiliary systems: lighting, socket outlets, special low power supplies.These panels shall be installed in rooms to power systems, as follows:

� auxiliary system TD, category II:

� room 103: for lighting networks, single-phase and three-phase sockets,special low power supplies for rooms 001, 002, 013, 014 100, 103 and 104 ofthe bunker,

� room 102: for lighting networks, single-phase and three-phase sockets,special low power supplies for rooms 007 to 010, 101 and 102 of the bunker,mast rooms (normal lighting and safety lighting by sockets),

� room 108: for compressors, lighting, socket outlets and special powersupplies,

� room 109: for lighting networks, single-phase and three-phase sockets,special low power supplies for rooms 004 to 006, 012, 105 to 107, 109, 110and 125 of the bunker,

� room 115: for lighting networks, single-phase and three-phase sockets,special low power supplies for rooms 111 to 118, 126 and 127 of the bunker,

� room 117: for lighting outside the building, parking areas and camerashelters,

� room 117: for launcher lighting,

� room 121: for lighting networks, single-phase and three-phase sockets,special low power supplies for rooms 119 to 122 of the bunker.

8.12.4.1.2. Gantry

A sub-distribution panel capable of supplying a power level of at least 200 kW shall beinstalled at level 18400 of the gantry. This panel shall be powered directly from the TGBT bycables supported by cable chains; the cable chain is supplied by the mechanical workpackage. This panel will supply all category II systems, i.e.:

� gantry motorization with dual power supply (redundant),

� interior lighting of all levels,

� external lighting of north and east side (docking), and interior docking lighting,

� aircraft lighting,

� socket outlet systems,

� goods lift,

� the 4 TDs of the platforms for:� platform motorization,� platform lighting,

Page 46: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 46/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� doors,

� crane,

� air conditioning,

� decontamination,

� pumps,

� miscellaneous outgoings.

8.12.4.2. Description, excluding mobile platform TDs of the gantry

8.12.4.2.1. Principle

Panels shall be of a modular type, protection index IP 55 and IK 07, with front panels + keylocked door, size according to equipment to install in it and with 30% useful spare space.The drive power and lighting TD shall comprise columns and sheaths with at least one300 mm width sheath per column. The sheath will be used to route and connect cables. Theunit shall be installed on a base. Columns shall be provided for the drive power circuits andsocket outlets, separate from lighting.Panels and circuit breakers shall be identified with engraved labels riveted to supports as perCNES technical specification(s). All conductors, switchgear and control gear, etc. inside thepanel shall be identified as per CNES technical specification(s).Cables shall be identified with label holders, marked in letters and numbers, attached to cablesas per CNES technical specification(s).All cable inlets shall be through packing glands of appropriate size.

8.12.4.2.2. Auxiliary system panels

Auxiliary system panels shall comprise:� connection lands or similar, depending on wiring + screen for connection of power

supply cable,� general cutoff fitted with OF contact, transmission coil and a control on side face,� a circuit breaker, all poles protected, for the emergency cutoff circuit and power off

indicator lights and power on indicator lights at emergency cutoff level, power supplyupline from general cutoff and orange wiring, identification of general open poweredequipment,

� one terminal block upline from the general cutoff, nominal current adapted to headprotection,

� circuit breakers, all poles protected, for power lines of equipment, for example lift, airconditioning, etc. (circuit breaker rating to be confirmed by contractors of workpackages),

� for T4 type boxes of 63A circuit breakers for circuits servicing these boxes,

Page 47: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 47/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� for TD servicing the external pod: one circuit breaker + 30mA differential for socketoutlet circuit,

� circuit breakers, all poles protected, protecting lighting power lines, with at least:

� for the gantry:

� 1 circuit breaker at least per level,� 1 circuit breaker at least per stairway well,

� for bunker and gantry external lighting:� front: 2 circuit breakers at least,� parking: 2 circuit breakers at least,� single-pole control devices of lighting circuits,

� for control of external lighting including gantry:

� 1 switch, programmable 24 hours/ day and with crystal,� 1 3-position switch: manual, automatic, off,� contactors controlled by programmable switch and 3-position switch,

� 1 remote control box for safety lighting.

� circuit connection terminal boards, identified.

8.12.4.2.3. Compressor panel

The compressor panel shall include:� connection lands or similar, depending on wiring + screen for connection of power

supply cable,� one general cutoff fitted with control on side face,� one terminal block downline from general cutoff, nominal current adapted to head

protection,� 4 circuit breakers, all poles protected, for compressor power lines (circuit breaker

rating to be defined by the contractors of work packages),� circuit connection terminal boards, identified.

TD links to compressors are the responsibility of the contractor of this work package.

8.12.4.3. Mobile platform TDs

Each mobile platform TD consists of two half platforms each with a TD, i.e. 4 TDs for the 2platforms.

8.12.4.3.1. Platform TD power supply:

Each mobile platform TD will be powered as follows:� from TD at level 15600 by RO2V cable to cutoff switch located at level 39600. The

switch will be latched in open position,

Page 48: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 48/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� by self-supporting daisy chain, cable chain type, between the previous switch and theplatform TD involved, with necessary slack for routing in the column. Cables shall becompatible for cable chains (cable type HO7RNF not accepted),

� by an arm to bring the daisy chain to the platform TD.The column and the arm are the responsibility of the gantry structure work package. However,the contractor of this work package shall ensure that the design of the column enables routingand operation of the self-supporting daisy chain.The daisy chain shall meet the criteria defined for ATEX zones or rooms.

8.12.4.3.2. Description

As platforms run in the ATEX zone, the sub-distribution panel of each platform shall have thefollowing characteristics:

� Protection index: IP55 minimum,� Impact index: IK07 minimum,� Gas group: IIB,� Temperature class: T4 .

Sub-distribution panels shall be sized according to the equipment to be installed in them andshall allow for a 30% useful spare space.The lighting part shall be separate from the drive power and socket outlet part.Panels and circuit breakers shall be identified with labels engraved on supports as per CNEStechnical specification(s). All conductors, switchgear and control gear, etc. inside the panelshall be identified as per CNES technical specification(s).Cables shall be identified with label holders, marked in letters and numbers, attached to cablesas per CNES technical specification(s).Each panel shall comprise:

� connection lands or similar, depending on wiring + screen for connection of powersupply cable,

� a general cutoff fitted with an OF contact, a transmission coil and a command on theside face,

Page 49: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 49/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� a circuit breaker, all poles protected, for the emergency cutoff circuit and power offindicator lights and power on indicator lights at emergency cutoff level, power supplyupline from general cutoff and orange wiring, identification of general open poweredequipment,

� a terminal block downline from the general cutoff, nominal current adapted to headprotection,

� circuit breakers for motorization power lines (circuit breaker rating to be confirmedby contractors of work packages),

� protection circuit breakers for safety and normal lighting power lines, with 2 circuitbreakers at least per platform,

� protection circuit breakers for the 24V socket outlet safety transformer,� single-pole control devices for lighting circuits,� remote control box for safety lighting.

8.13. Category III energy production and distribution

8.13.1. Category III production

8.13.1.1. Definition of requirements

To meet site system requirements, the following categories are produced:� III A,� III B,� III CU,� III rack 270V, 250A,

The characteristics of each category will be as follows depending on the power budget:� Category III A: 80 kVA power, service voltage 230/410 volts, frequency 50 hertz,

TNS neutral point treatment,� Category III B: 80 kVA power, service voltage 230/410 volts, frequency 50 hertz,

TNS neutral point treatment,� Category III CU: 20 kVA power, service voltage 230/410 volts at frequency of 50

hertz and 120/208 volts at frequency 60 hertz, TNS neutral point treatment,� Category III rack 270V, 250A: 100 kVA power, service voltage 230/410 volts,

frequency 50 hertz, TNS neutral point treatment.Category III production shall be obtained as follows:

� III A and III B: by two redundant UPSs for each category, to separate power supplynetwork 1 and common power supply network 2,

Page 50: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 50/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� III CU: by one UPS for each sub-category B and H:

� to separate power supply network 1,

� to power supply network 2 provided for:� the 50 hertz by category II of the site for each UPS,� the 60 hertz by a static converter for power 40 kVA, common to UPSs,

each fitted on the service network with invertors to select the 230/410-volt networkat 50 hertz frequency or the 120/208-volt network at 60 hertz frequency by meansof a voltage adaptation rack,

� III rack 270V, 250A: by a UPS to separate power supply networks 1 and 2.Note: Sub-categories III CU B and H are not redundant, as well as category III rack 270 V,250 A.Charger boxes for battery operating tests shall be installed. Also, power supplies for mobileUPS shall be installed.

8.13.1.2. Description of UPSs

The characteristics of UPSs shall be as follows:� nominal use power at cos phi 0.8,

� network 1 and 2 voltage: 410 V � 10%, 50 Hz, three-phase (TNC) in network 1,three-phase + neutral (TNS) in network 2,

� output voltage: 410V � 1.5% three-phase + neutral (TNS),� output frequency:

� 50 Hz for category III A and III B UPSs,

� 50 or 60 Hz for category III CU UPSs, may be configured according to aprocedure,

� gradual power rise at power-up or power return,� voltage harmonic distortion rate (THDU) less than or equal to 5% between phases

and 3% between phases and neutral, i.e. class 1 (sensitive systems and equipment)according to standard EN 50160 -3. This rate means a non-linear charge accordingto standard EN 50091-3 related to ASI performance,

� global distorsion rate for reinjection of current harmonics (THDI) less than or equal to5%,

� an automatic by-pass, no cutoff,� isolation devices on networks shall be made as follows:

� on power supplies 1 and 2: with switches,

� on the service:

� for category III A and III B: with switch at output of each UPS and withswitch for each set of parallel and redundant UPSs downline from staticcontactor. The isolation switches of service networks shall be fitted withOF contacts by insertion in the general fault chain of UPS(s),

Page 51: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 51/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� for category III CU: by switch for each UPS upline of the static contactorand by circuit breaker for each UPS downline from static contactor.Isolation devices for service networks shall be fitted with OF contacts forinsertion in the general fault chain of UPS(s),

� for category III of rack 270 V, 250 A: by switch at output of the UPSdowline from the static contactor. The isolation switch of the servicenetwork shall be fitted with OF contacts to be inserted in the general faultchain of UPS(s).

� a manual maintenance by-pass integrated in category III A and III B UPSs. Themanual by-pass will shunt the isolation function of the UPS and of the static contactor,and shall be fitted with an OF contact,

� a switch for the power line of the charger box. This switch and the service networkisolation switch may be of the reverser type with locking:

� mechanical between the service position and the charger,

� with key so that only one inverter is in position on the charger. Refer to theparagraph on charger boxes,

� in the parallel and redundant UPS configuration, the automatic and manual by-passesshall be integrated in UPSs and regulation between UPSs shall be by an internalcurrent loop link, common to UPSs,

� a rectifier sized to simultaneously power the UPS at nominal power level and hold thebattery charge level or recharge the battery after discharge,

� equipped with RS485 serial links converted into RS232 serial link by TESF to takeinto account, non-exhaustive list:

� charger fault,

� UPS fault,

� by-pass fault,

� charger off,

� charger on,

� UPS off,

� UPS on,

� by-pass closed

� by-pass open

� stand-alone operation,

Page 52: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 52/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� TOR information, no common and potential free, returned to terminal boards and inparticular:

� end of stand-alone operation,

� general fault,

� manual by-pass position.� with emergency stop function with TOR information for cutoff on general emergency

stop.Operating procedures between UPSs, charger boxes, the converter and the mobile UPS arepart of the services provided by the contractor of this work package.Note: The manufacturer shall guarantee correct operation of ASIs for a period of 5 years.Any errors found during operation and questioning the initial software shall be taken intoaccount by the manufacturer and the software upgraded to a higher index without anypayment by CNES (in this case, “ system ” changes are not taken into account).

8.13.1.3. UPS links

UPS links shall be made as follows:� power supply networks I and II: RVFV cables,� service network: RVFV cables.

Cables shall be of a correctly sized cross-section.Strips are connected to the earth network at both ends and before entry in the to and fromrooms with 360°C connections. The sealing sheath shall be rebuilt.

8.13.1.4. Batteries

8.13.1.4.1. Description

The characteristics of the accumulator batteries provided shall be as follows:� battery life of 10 minutes at full charge after 3 years,� sealed lead,� type 12 volts RG,� 3+3-year guarantee,� installation on 2-level wood site.

8.13.1.4.2. Installation

Batteries shall be installed as follows:� with RO2V cables of appropriate cross-section for the link between the batteries and

the UPSs,� by installing a battery protection circuit breaker in the battery room and a switch close

to the corresponding UPS,

Page 53: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 53/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� the battery circuit breaker shall be provided with an MX coil for cutoff followingemergency shutdown controlled by the UPS. The whole command shall be poweredwith DC downline from the battery protection circuit breaker and shall be protected bya two-pole circuit breaker for the DC current, fitted with an OF contact.

� the circuit breaker and the switch shall be correctly rated, installed in class II boxeswith key locking (RONIS 3113A) and external latchable operating lever type.

� OF and/or SD contact(s) of the circuit breaker and the switch shall be inserted in theUPS fault chain, including that of the MX coil circuit breaker.

8.13.1.4.3. Transport

To maintain battery performance, the transport phase shall be in air-conditioned type containerand with air conditioned storage. A traceability document for the different transport andstorage phase conditions shall be handed over by the contractor of this work package. Thisdocument will trace battery life from the origin (manufacturing) up to comissioning.

8.13.1.5. 50/60 hertz converter

8.13.1.5.1. Description

The characteristics of the 50/60 hertz static type frequency converter are as follows:� power 40 kVA,

� output voltage: 400 V ± 1.5%,� output frequency: 60 Hz,� neutral terminal output connected to earth,� fitted with RS485 serial links for GTB and TOR information, no common and potential

free, connected to terminal boards and in particular:

� converter fault,

� converter off,

� converter on.

8.13.1.5.2. Installation

The converter shall be shared by the two CU category UPSs and shall be installed in a rack.Installation shall be as follows:

� switch on 410 volt 50 hertz power supply, fitted with OF position contacts,� circuit breaker on use for 410 volts 60 hertz, fitted with OF position contacts,� a manual inverter upline from network 2 of each UPS to select 50 Hz network (site

category II) or 60 Hz network (converter), with mechanical locking and OF positioncontacts,

� by RO2V cable of appropriate cross-section for link between the converter rack andthe UPS.

Page 54: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 54/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

OF position contacts shall be returned for converter TOR information to terminal boards.The operating procedures between UPSs and converters are part of the service of thecontractor of this work package.

8.13.1.6. 208 volt 60 hertz voltage adaptation rack

8.13.1.6.1. Installation

A voltage rack shall be installed on the service network of each UPS of category III CU.Installation shall be as follows:

� transformers and inverters integrated in racks,� by RO2V cable of cross-section adapted to the link between the transformer rack and

the UPS,� manual inverters fitted with OF position contacts and installed:

� upline from transformers: by switches on UPS use and transformer powersupply networks, with mechanical locking,

� downline from transformers: by circuit breaker on the service network of thetransformer (to protect the transformer) and by switch on the UPS usenetwork, with mechanical locking,

� to select the voltage:

� 410 volts at frequency 50 Hz,

� 208 volts at frequency 60 hertz

� transformer secondary neutral connected to earth,� by cables of appropriate cross-section, minimum 16 mm², for links between

transformers and distribution panels of category III CU as follows:

� RVFV for the panel in room 101 (CU B),

� HO7RNF for the panel in the mast, on the cable tray alone up to entry in mast(CU H).

Operating procedures are part of the services of the contractor of this work package.

8.13.1.6.2. Measurement sockets

ENTRELEC type measurement sockets shall be installed on the fronts of voltage racks. Theymake it possible to measure:

� the output voltage from each voltage rack, with a 4x6A +SD circuit breaker on thecircuit,

� the current output from each voltage rack, with corresponding TIs.Measurement sockets shall be correctly identified.

Page 55: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 55/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.13.1.6.3. Description of transformers

The characteristics of transformers shall be as follows:� power 20 kVA,� current drain and low power-up (5 In),� primary voltage 400 V,� secondary voltage 208 V,� operating frequency 60 Hz.

8.13.1.7. Charger boxes

8.13.1.7.1. Principle

To avoid multiplying the number of boxes outside buildings, the following shall be installed:� a single box for the charger for category III A and III B production, close to the entry of

room 117,� a charger box for category III CU production, close to entry of room 102,� a charger box for category III rack 270V 250A production, close to entry of room 103.

Selection for each production corresponding to:� category III A or III B,� category III CU B or CU H,� categories III rack 270V 250A, with 2-rack option

shall be between the use involved and the charger box by an inverter (or 2 switches withmechanical locking) positioned in each UPS and completed with key-operated servo-controllocking in open position, on charger side, the inverters and thus leaving the key free. The keybecomes captive from an inverter closed on charger side and consequently operation of allother inverters is not possible.The inverter UPS use position shall be provided with OF position contacts.The charger position of each inverter is connected by cable of an appropriate section andjustified by design documents, from inverter to inverter for each type of production.

� categories III A and III B,� categories III CU B and CU H,� categories III rack 270V 250A

The operating procedures between UPSs and charger boxes are part of the service of thecontractor of this work package.

Page 56: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 56/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.13.1.7.2. Installation

For each box, the RVFV cable link from the last inverter wired according to description aboveand integrated in the UPS rack shall be of a correct cross-section, justified by designdocuments. The strip shall be connected to the earth network by a 360° connection at bothends and before entering the to or from room.Each box made of a very strong corrosion resistant material, protection index IP55 and impactindex IK08, shall be fitted with:

� a key-operated door (RONIS 3113A),� an isolator switch, latchable in open position and of a current adapted to

requirements,� busbar tails for connection of the 100 kVA power charger cables, to be confirmed by

the site authority before studies.

8.13.1.8. Description of the mobile UPS power supply

A power supply and a use network for the 120 kVA approx. power mobile UPS, to beconfirmed by the site authority before studies, shall be set up for production of:

� categories III A and III B,� categories III CU B and H,� categories III rack 270V 250A.

8.13.1.8.1. Principle

The mobile UPS shall be designed for connection to the various systems involved withoutcutting off the systems, by using power supply network 2 of the different local productions.To avoid multiplying the number of sockets outside the buildings, the following will be set up:

� a set of 3 socket outlets for category III A and III B production, close to the entry toroom 117,

� a set of 3 socket outlets for category III CU production, close to the entry to room 102,� a set of 3 socket outlets for category III production, required at racks in room 002,

close to the entry to room 103,The use network of the mobile UPS shall be connected as follows:

� for categories III A and III B: at TGBTs of category III, downline from the generalcutoff switch,

� for categories III CU B and CU H: at voltage adaptation racks, upline from theinverter located on the voltage transformer power supply,

� for category III of TCV rack: downline from the general production cutoff switch.

Page 57: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 57/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The selection of the mobile UPS use network shall be by means of servo-control devices asfollows:

� categories III A and III B: for each local production, by keys and locks prohibiting thestartup of the mobile UPS use network if the switches downline from UPSs, excludingstatic contactors, of the local production selected are not in open position. The 2 localproductions may be chosen at the same time depending on the mobile UPS power,

� categories III CU B and CU H: for each local production, by keys and locksprohibiting startup of the mobile UPS use network if:

� the switch upline from the static contactor of each local production is not inopen position,

� the switch of the frequency converter use network of each local production isnot in open position,

the 2 local productions may be selected at the same time depending on the powerof the mobile UPS.

� category III of TVC rack: for local production, by keys and locks prohibiting startup ofthe mobile UPS use network if the switch downline from the UPS, excluding staticcontactors, of the local production chosen is not in open position.

The operating procedures between the local UPSs and the mobile UPS are part of theservices of the contractor of this work package.

8.13.1.8.2. Outside connections to category II and III networks

Connections to categories II and III shall be as follows:� installation of wall-mounted socket outlets, connected according to the TNS neutral

point treatment, network 2 and use side, and type Maréchal DS2 in order to remainhomogeneous with existing systems:

� 3P+T 200 A female on network 1 of UPS,

� 4P+T 200 A female on network 2 of UPS,

� 4P+T 115 A male on use network of UPS,� by RO2V cables of a cross-section adapted to power supply networks 1 and 2,� by RVFV cables of a cross-section adapted to the use network. Cable strips shall be

connected to the earth network at both ends and before entering the rooms, UPSside.

These sockets shall be installed as follows:� for category III A and III B production: close to the entry to room 117,� for category III CU production: close to the entry to room 102,� for category III rack 270V 250A production: close to the entry to room 103.

The two networks of category II (power supplies) of the mobile UPS shall be individuallyprotected against surge currents taking the mobile UPS power into account.

Page 58: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 58/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Protection systems of the two mobile UPS networks for category III A, III B, CU and rack 270V,250A production shall be common and supply the sockets defined above.

8.13.1.8.3. Category III local production connections

Use network selection devices described in the previous explanatory paragraph will comprisecircuit breakers located in boxes in UPS rooms or:

� for categories III A and III B: in main distribution panels, category III,� for categories III CU: in voltage adaptation racks,� for category III rack 270V, 250A: in the main distribution panel, category III.

Links between these devices and TGBTs, categories III A and III B, of the voltage adaptationrack for categories III CU B and H, and the TGBT, category III of rack 270V, 250A, shall bewith RO2V cables of an appropriate cross-section, justified by design documents.

8.13.2. Category III A and III B distribution panels

8.13.2.1. Low-voltage main distribution panels, categories III A and III B (TGBTcat III A and cat III B)

A low-voltage main distribution panel for each category III A and III B (TGBT cat III A andTGBT cat III B) shall be installed in the UPS room.These panels shall be sized according to the equipment to install, with a 30% useful sparespace, minimum height 1800mm, width 800 mm and depth 400 mm, and shall be installed ona 200-mm high base.Each panel shall be fitted with a RONIS (3113A) key locked door and a magnetic contactinserted in the surge current protection and cutoff device OF chain.Panels shall be powered from UPSs of each category III A and III B by RVFV cables of anappropriate cross-section, 5G35 mm² minimum.Each panel shall comprise:

� a general lever-operated outside switch, minimum current 160A, fitted with OFcontacts,

� a selection circuit breaker of the mobile or fixed UPS use network, fitted with SDcontacts,

� a set of busbars, minimum current 160 amps, downline from the switch,� a circuit breaker, all poles protected, 2X10A, with curve and breaking capacity

adapted for the power on indicator light circuit,� circuit breakers, all poles protected, at appropriate breaking capacity, fitted with relay

4x63A or 4x32A+OF+SD for RVFV cables, minimum cross-section 5G16mm² or5G10mm², of the bunker TDs defined in the following table,

� 1 circuit breaker, all poles protected, appropriate breaking capacity, fitted with relay4x63A +OF+SD for the link to the main distribution panel of level 18400 of the gantry,according to the category IIIA and IIIB power supply paragraph of the gantry,

Page 59: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 59/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The panels will integrate the category III auxiliary power supplies as follows:� TGBT of category III B:

� air conditioning in room 118: the circuit shall be protected by a circuit breakerwith appropriate breaking capacity, fitted with relay 4x32A +OF+SD for RVFVcable, minimum cross-section 5G10mm², routed in the air conditioning andcold production TD,

� programmable controller + HV cells + TGBT(s) in room 115: the circuit shallbe protected by a circuit breaker, appropriate breaking capacity, fitted withrelay 2x32A +OF+SD for RVFV cable, minimum cross-section 3G10mm²,routed to the auxiliary system TGBT, protection of sub-distribution circuits willbe in the TGBT by circuit breakers fitted with OF+SD, with power circuitindications and grouping of these protection devices.

Outgoings shall be directly connected to circuit breaker terminals. The neutral conductor andthe earth conductor shall be separate, TNS diagram.SD and OF contacts shall be wired in series in two separate chains and returned todisconnectable terminals for wiring as per the information transfer paragraph.

8.13.2.2. Category III A and IIIB gantry power supply

The gantry shall be directly powered from the TGBT with category III A and III B by a cable,minimum cross-section 5G35 mm², for each category. The installation method shall be:

� on cable trays inside the bunker,� on cable chain outside the bunker. Cables shall be compatible for cable chains

(HO7RNF type cable not accepted),� on support arm attached to the gantry (mechanical work package; however, the

contractor of the work package shall provide all information defining the arm),� on cable trays in the gantry.

Cables shall end in the main distribution panels, of level 18400.

8.13.2.3. Category III A and IIIB main panel of gantry

This panel is located at level 18400 of the gantry and consists of two compartments, with aphysical separation: one for category III A and the other for category III B.This panel, sized according to the equipment to install in it and taking into account a 30%spare space, protection index IP 55 and impact index IK 07 minimum, shall be of a modulartype with front panels and transparent door fitted a key lock (RONIS 3113A), a magnetic typecontact inserted in the OF chain and a lead sealing device.The panel shall comprise for each category III A and IIIB:

� connection lands or similar, depending on wiring + screen for connection of powersupply cable,

� 1 general switch 4X100A fitted with an OF contact,� 1 terminal block, multiclip type, 100A minimum,� 1 terminal block power white indicator light, protected by circuit breaker with

appropriate breaking capacity, rated 2x6A,

Page 60: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 60/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� circuit breakers, all poles protected, with appropriate 4-pole breaking capacity +SD+OF contacts for RVFV cables, minimum cross-section 5G16 mm² or 5G10 mm² ingantry TDs, defined in table below.

� in TD III A, 1 circuit breaker, appropriate breaking capacity and rating 2x32A+OF+SDfor RVFV cable, minimum cross-section 3G10 mm², to air conditioning category II TDinstalled at level 26600.

8.13.2.4. Category III A and III B distribution panels

8.13.2.4.1. Distribution panels

Distribution panels intended to supply racks, powered from:� Category III A and III B TGBTs for the bunker,� Category III A and IIIB main panel of the gantry,

shall be created according to table below.These panels, minimum dimensions 600 x 600 x 275 mm, protection index IP 55 and impactindex IK 07 minimum, shall be of a modular type with front panels and transparent door, fittedwith key lock (RONIS 3113A), a magnetic type contact inserted in the OF chain and a leadsealing device.Each panel shall comprise:

� connection lands or similar, depending on wiring + screen for connection of powersupply cable,

� 1 general switch 4X63A, fitted with an OF contact,� 1 terminal block, multiclip type, 100A minimum,� 1 terminal block voltage white indicator light, protected by circuit breaker with

appropriate breaking capacity, rated 2x6A,� 9 circuit breakers, all poles protected, with appropriate breaking capacity, 2 poles, +

SD+OF contacts, for cables of racks connected to identified terminals. Thecorresponding number and rating of circuit breakers are defined below.

Page 61: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 61/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room Qty ofpanels

Racks LocationQty per panelC/B 2x10A/C

Qty per panelC/B 2x16A/C

Qty per panelC/B + rating

Bunker013

Cat IIIA: 1Cat IIIB: 1 5 VES Process 9

9Bunker004

Cat IIIA: 2Cat IIIB: 2 Comm Communication

means 9

Bunker103

Cat IIIA: 1Cat IIIB: 1Cat IIIA: 1

Cat IIIB: 1

Cat IIIA: 2Cat IIIB: 2

6 BCV1.56 BCV1.51 BCV1.51 BCV2.51 BCV1.52 BCV2.5RMORMO

BCV roomRMO

773

3

99

222

24: 2x20A/C

4: 2x20A/C

Bunker126 Cat IIIB: 1 Control 9

Gantry21200

Cat IIIA: 1Cat IIIB: 1 RMO+DVT RMO 9

Gantry24000

Cat IIIA:1Cat IIIB: 1

2: 270Vx30A1: 270Vx30A

TCV rackroom 3 3: 4x20/C

3: 4x20/CGantry29200

Cat IIIA:1Cat IIIB: 1

1: 270Vx10A2: 270Vx10A Rack room 3 2 4: 2x20A/C

Gantry37000

Cat IIIA: 1

Cat IIIB: 1

2 BCV1.5INTF1 BCV1.5INTF

Level 37000

5

5

4

4

SD and OF contacts are wired in series in two separate chains and shall be returned todisconnectable terminals for insertion in the chain, according to the information transferparagraph. All cable inlets shall be through packing glands, appropriate size. Cables are not part of the service of the contractor of this work package.

8.13.3. Category III CU distribution panels

8.13.3.1. Category III CU distribution panels

For each category III CU B and CU H, a distribution panel will be created, powered directly fromcategory III CU voltage adaptation racks, intended to supply customer racks in room 101 of thebunker for category III CU B and mast level 34400 for category III CU H.

Page 62: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 62/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

These panels, sized according to the equipment to install, taking into account a 30% sparespace, minimum dimensions 600 x 600 x 275 mm, shall have a protection index IP 55 andimpact index IK 07 minimum. They shall be of a modular type with transparent door fitted withkey lock (RONIS 3113A), a magnetic type contact inserted in the OF chain and a lead sealingdevice. Each panel shall comprise:

� connection lands or similar, depending on wiring + screen for connection of powersupply cable,

� 1 general switch 4X63A, fitted with an OF contact,� 1 terminal block, multiclip type, 100A minimum,� 1 terminal block voltage white indicator light, protected by circuit breaker with

appropriate breaking capacity and rated 2x6A,� 9 circuit breakers, all poles protected, with appropriate breaking capacity, 2 poles, +

SD+OF contacts, for rack cables connected to identified terminals. The rating ofcircuit breakers and the corresponding number are defined below.

Room Qty of panels Racks Location Per panel qtyC/B 10A/C

101 Cat III CU: 1 CU Room 101 9

Mast 34400 Cat III CU: 1 CU Level 34400 9

SD and OF contacts shall be wired in series in two separate chains and routed back todisconnectable terminals for insertion in the chain, as per the information transfer paragraph. All cable inlets shall be through packing glands, appropriate size. Rack cables are not part of the service of the contractor of this work package. Important: The mast distribution panel shall be installed on dampers. Dampers are not part ofthis work package. However, the contractor of this work package shall provide allcharacteristics related to the attachment of the TD.

8.13.4. Rack 270V 250A category III distribution

8.13.4.1. Distribution panel

A low-voltage main distribution panel shall be installed in the UPS room.This panel, size defined according to the equipment to install and taking into account a 30%spare space, minimum height 1800 mm, width 1600 mm and depth 400 mm, will be installedon a 200 mm high base. The protection index will be IP 55 and the impact index IK 07 atleast. The panel shall be of a modular type with front panels and transparent door fitted with:

� a key lock fitted with a RONIS key closing device (3113A),

Page 63: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 63/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� a magnetic contact inserted in the OF chain of surge current protection and cutoffdevices,

� a lead sealing device.The panel shall be powered from the rack 270V 250A UPS by RVFV cables, appropriatecross-section, minimum 5G35 mm².

This panel shall comprise:� a selection circuit breaker of the mobile or fixed UPS use network, fitted with OF+SD

contacts, used for protection of link to the rack of RVFV cable, minimum cross-section5G35mm²

� a circuit breaker, all poles protected, 2X10A, with curve and breaking capacityadapted to the power on indicator light circuit,

Outgoings shall be directly connected to the circuit breaker terminals. The neutral conductorand the earth conductor shall be separate, TNS diagram.The rack cable is part of the service of the contractor of this work package. The cable shall beRVFV type, appropriate cross-section, minimum 5G35 mm². All cable inlets shall be through packing glands, appropriate size.SD and OF contacts shall be wired in series in two separate chains and shall be returned todisconnectable terminals for wiring as per the information transfer paragraph.

8.13.5. Category III information transfer

Information transfer in communication with CCS is not part of the service of the contractor ofthis work package, but is the responsibility of the contractor of the auxiliary system control-command (CCS) work package. However, the contractor of this work package shall provide allinformation required to ensure successful completion of site work. Transferred information is described in the various paragraphs related to production (UPSs +batteries + charger + converter + voltage racks, etc.) and distribution (distribution panels, etc.).Interface points shall be located:

� category III A+B production: UPSs + batteries + charger + etc.: in junction box inroom 113,

� category III CU production: UPSs + converter + voltage racks + batteries + charger +etc.: in junction box in room 007,

� category III production of rack 270V 250A: UPS + batteries + charger + etc.: injunction box in room 018,

� TGBT and TD of category III A + III B: disconnectable terminals in panels:

� TGBT cat III A + B: in room 113,

� TD: defined in paragraph of category IIIA + IIIB distribution panels,� TD of category III CU: disconnectable terminals in panels defined in paragraph of

category III CU distribution panels,� TGBT of category III of rack 270V 250A: disconnectable terminals in panel in room

018.

Page 64: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 64/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Important: The category III A + B fault chain shall integrate the office automation UPS faultsummary system of the category II auxiliary system TGBT.

8.13.6. Phase balancing

The contractor of the work package shall balance phases on category IIIA and IIIB UPS usenetworks according to systems installed, as part of the contract.

8.14. Emergency cutoff Two types of easy-to-access emergency cutoffs shall be provided for systems:

� general cutoff:

� one in the bunker,

� one in the gantry,� local cutoff:

� in the bunker rooms,

� at each level of the gantry.

General emergency cutoffs are separate from local cutoffs.

8.14.1. General emergency cutoff

General emergency cutoffs are located:� one on the outside, close to the entry of bunker room 117,� the other at the entry to the gantry, level 14200.

The link between the gantry and the bunker shall be by cable in the cable chain. Cutoffs shall work on the entire low-voltage system of the VEGA site as follows:

� categories I and II, including the generator set source by activating the transmissiontriggers installed in the general circuit breakers,

� categories III by activating UPSs. UPSs control the MX transmission coils of batterycircuit breakers.

Cutoffs are powered with 230V voltage, category III, produced by the UPS installed in the TGBT(refer to paragraph TGBT) with dual signaling at actuator.

� green color: powered: position of one or more closed devices, device positioncontacts parallel,

� red color: down-powered: position of all open devices, device position contacts inseries.

To limit the power in emergency cutoff links, a 0.1 to 5 second adjustable time-out shall beinserted in the chain to down-power the UPS following emergency cutoff action. Fault signalingfor this time-out shall be taken into account in the TGBT programmable controller according tothe principle used.

Page 65: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 65/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Wiring in TGBT shall be orange. Buttons and indicator lights shall be put under red color glass panel boxes, correctly identified.

8.14.2. Local emergency cutoff

Local emergency cutoffs acting on the general device of category II by MX transmission coilshall be installed in the following rooms:

� 001 which acts on TD in room 103,� 014 which acts on TD in room 103,� 005 which acts on TD in room 109,� 010 which acts on TD in room 102,� 102 which acts on TD in room 102,� 103 which acts on TD in room 103,� 108 which acts on TD in room 108,� 109 which acts on TD in room 109,� 117 which acts on TD in room 115,� 118 which acts on the general circuit breaker of the air conditioning TGBT,� 121 outside, which acts on TD in room 121.

8.14.3. Gantry emergency cutoff

These cutoffs shall down-power category II systems by MX transmission coil acting on thegeneral cutoff device of the power supply. These cutoffs shall be installed at levels:

� 14200 at entrance,� then at each level: on the pillar, chute side, and on the diametrically opposite pillar,

i.e. two per level.

8.14.4. Provisions common to local and gantry emergency cutoffs

Emergency cutoffs shall be fitted with a mechanical locking actuator protected against untimelyaction to prevent unwanted triggering and indicator lights of the following colors:

� green color: power on indicator light, supplied by the closing contact of the generalcutoff involved

� red color: power off indicator light, supplied by the opening contact of the generalcutoff involved.

Emergency cutoffs shall be correctly identified and wired as above, according to descriptiongiven in the category I and II TD paragraphs. Pushbuttons and indicator lights shall be installed in red color glass panel boxes.

8.15. Equipment

Page 66: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 66/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.15.1. Description

8.15.1.1. Switchgear and control gear

Depending on the classification of rooms or zones in the room classification chapter, thecharacteristics of the switchgear and control gear shall be as follows:

� Explosive Atmosphere zones or rooms (ATEX) of the gantry:

� Protection index: IP55 minimum,

� Impact index: IK07 minimum,

� Gas group: IIB,� Temperature class: T4 .

� non-ATEX zones or rooms:

� Protection index: IP55 minimum,

� Impact index: IK07 minimum.

All equipment shall satisfy European Directives. Within the scope of switchgear and control gear implementation, special care shall be taken inall rooms to:

� make all cable entries in switchgear and control gear from the bottom (switches,socket outlets, boxes, junction boxes, lighting equipment, etc.). For damp rooms, thewater retainer shall be installed at the cable inlet in the switchgear and control gear,

� seal cable inlet with packing glands, one packing gland per cable, adapted to the typeof switchgear and control gear, appropriately sized and efficient with fine dust,

� do not use silicone or similar (prohibited).

8.15.1.2. Power lines

Distribution power lines shall be made with cables of the following type:� RO2V for installation in cable trays for categories I and II, inside the bunker and

gantry,� RGPFV for buried cables, all categories,� RVFV for installation in cable trays for category III production power supply and

category III distribution inside the bunker and gantry,� HO7RNF for installation in cable trays used in the mast,� Special class 6 for cable chain, for gantry supply.

All cable trays shall be sized for installation of cables in a single layer, with a 30% useful sparespace.

Page 67: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 67/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Special care shall be paid to the cable installation method on cable trays, especially byseparating cat I and II from cat III on the same high current cable tray. Cable armor or strips for category III production and panel power supplies shall be connected tothe earth network with 360°C connections at both ends before the cable enters the to and fromrooms, using a collar compatible with copper and the strip or armor. The collar shall be coveredwith a sealing sheath to prevent any corrosion. Non-armored cables on building fronts shall be installed in stainless steel ducting with stainlesssteel attachments. Ducting shall be earthed with a 16 mm² copper cross-section conductor,taking into account the couple the copper and stainless steel connection may cause. Power lines shall be of a correctly defined cross-section justified by design documents. Buried power lines of terminals complying with CSG specification shall indicate on the ground:

� the cable path every 50 m,� each change to direction,� junction boxes,

and shall be indicated on the topographic drawing in the same manner as cables. One or more indicating posts shall be installed at the entry of cables in the building. High and low current power lines shall be separated by at least 20 centimeters. For ATEX rooms or zones, refer to the paragraph on switchgear and control gear above. Powerlines not required for these rooms shall not be accepted.

8.15.1.3. Gantry power supply

The gantry power supply shall be of the PRC type, or similar, made of 2 cables in parallel,minimum cross-section each 70 mm². For parallel power lines, implementation shall complywith requirements and in particular, length of cables identical and connections correctly madetaking into account the tightening torque. The emergency cutoff cable shall be PRC type, or similar, with multiple conductors, minimum19. Daisy chains shall be installed on cable chains under the overhang of the bunker platform, level14000, East side. Crossings towards the outside shall be in MCT frame, part of the civil engineering work packagesupply. However, the contractor of this work package shall provide all information required tocorrectly carry out works.

Page 68: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 68/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.15.1.4. Cable trays

To supply systems, a terminal distribution and general distribution network will be installed incable trays:

� in technical rooms,� in energy rooms, categories I, II and III to rooms: BCV racks, payload racks,� in rooms 119 to 122,� in the gantry; for ATEX zones and rooms, only cable trays specific to these rooms are

accepted. Cable trays shall be of the perforated sheet tray type:

� hot galvanized in rooms,� stainless steel outside,

correctly sized for installation of cables in a single layer with a 30% spare space, flange height48mm, with 29mm² cable (copper inside and stainless steel outside, taking connections intoaccount) on the flange edge for earthing of cable trays and exposed metallic parts. High-current and low-current cable trays shall be physically separated one from the other by atleast 20 centimeters. Cable trays installed in false floors in technical rooms which house sensitive equipment(electronic – computer, racks, etc.) shall be connected in several locations to the groundreference of the room by the shortest possible links. All crossings shall be blanked.

8.15.1.5. Lighting

Lighting shall be provided by lighting equipment and associated lamps taking into account:� the service life,� the efficiency,� the best light flow/consumption ratio.

Fluorescent type lighting equipment shall be fitted with 20 or 40 watt tubes or low-consumptionfluo-compact lamp with electronic starter. Rooms lit by the equipment without instantaneous relight or light shall be equipped withminimum lighting provided by instantaneous lighting equipment. Halogen type lighting equipment shall not be accepted. The room equipment table below defines the lighting principle and lighting levels. However,with regard to the gantry, refer to the paragraph discussing the volume that can accommodatethe stairway wells and launcher of the chapter below. After completion of works, lighting measurements will be made 1 m from the ground by thecontractor of this work package, in the presence of a CNES representative.

Page 69: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 69/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.15.1.5.1. Normal lighting inside bunker and gantry, excluding platforms,docking and lift shaft

This lighting concerns:� all rooms of bunker,� the platforms of levels 14000, 15600, 18400, 21200, 24000 of the gantry,� levels 54000 and 55000 of the gantry,� rooms and circulations of the gantry,

In the gantry, for the volume that can accommodate the launcher and for stairwells, lighting shallbe controlled by pushbuttons located at each level as follows:

� at entries (level 14000),� close to the lift exit and landings of stairways.

Lighting of the gantry, docking platforms and the lift well shall be the subject of specificparagraphs below. Normal interior lighting shall be provided by equipment:

� metallic iodide type lamp or similar,� fluo-compact lamp or fluorescent type.

Lighting equipment in sanitary facilities shall be low-consumption fluo-compact lamps, power9 W.

8.15.1.5.2. Platform lighting

Platform lighting shall be installed on platforms. As the platforms move in ATEX zone, allequipment shall meet the characteristics given for the switchgear and control gear above. As platforms are made of two half platforms, each half platform shall be fitted with normal andsafety lighting. Lighting shall be controlled by a device located at each access to half platforms.

8.15.1.5.3. Lighting under gantry platform

Lighting on legs supplied by socket outlets shall be scheduled to light under the floor at gantrylevel 14000. These four socket outlets shall be installed in corners of level 14000 and identifiedas follows "reserved for leg lighting equipment".

Control of socket outlets intended for leg lighting equipment shall be by means of a all-poleswitch turning socket outlets on and off and shall be installed at level 14000, close to theunderfloor access.

Page 70: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 70/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.15.1.5.4. Gantry lift shaft lighting

The contractor of the work package shall include, in his services, lighting for the lift shaft bywindows, with the necessary slack needed for connection by the contractor of the lift workpackage in his panel. The lighting level shall be 50 lux.

8.15.1.5.5. Bunker and gantry safety lighting

Safety lighting shall provide:� indicating of exits of all rooms including electrical, air conditioning rooms, etc., and

vertical circulation landings,� circulation in rooms and horizontal and vertical circulation,� routing on the floor under the gantry.

Lighting shall be provided by independent units, in compliance with standards 71800, 71820and EN 60598, non-permanent type C, range 1 hour, remote controlled from boxes installed asfollows:

� in TDs of the different rooms,� in the TD of each platform.

The independent units shall incorporate the following complementary characteristics:� for rooms and circulation ways in the bunker and the gantry: 45-lumen units.� for the floor under the gantry, routing: spot light type unit(s) installed so as to take the

entire floor level into account.� for each half platform: one 300-lumen unit (approx.) ATEX II B T4, installed to take

access stairway into account. In electrical rooms:

� HV room of the bunker: 116,� TGBT room of the bunker: 115,� electrical room of the gantry, level 18400,

portable light equipment shall be installed. Connections shall be to socket outlets and light shallbe of the halogen lamp type. Indicating shall be provided by labels with white writing on green background except for spotlight units, ATEX and portable units.

8.15.1.5.6. Launcher docking external lighting from the gantry

Launcher docking external lighting shall be provided from the gantry. Lighting equipment shallbe installed:

� on the north side on either side of the doors to light the closed doors,� in the gantry, at doors to light the exterior docking zone, no matter what door(s)

is(are) open.

Page 71: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 71/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Lighting shall be provided by light equipment with metallic iodide or similar, controlled fromdevices located at level 14000. For lighting equipment outside the gantry, the control shall bealso connected to a clock to prohibit startup by day, and an operating indicator shall beconnected at the control. The light equipment shall provide a lighting level of:

� 300 lux at the foot of the gantry,� 120 lux in a 20m-radius zone.

8.15.1.5.7. Mast lighting: normal and safety

Each room shall be provided with normal 200 lux lighting by an IP55 and IK 07 window,minimum requirement (identical to those installed in the table: make LEGRAND, to be checked)and shall be equipped with polycarbonate type diffusers and low-consumption type lampsproviding a good lighting level (for example, fluorescent lamp(s)). The weight of the lampincluded shall be as low as possible. Control shall be at each mast level by means of apushbutton. Normal lighting shall be completed by safety lighting provided by a portable unit connected tothe special socket outlet. Units shall be installed at the entry. Normal lighting and socket outlets shall be powered from the distribution panel of room 102 ofthe bunker via an H07RNF cable, minimum cross-section 3G2,5mm². The equipment fitting shall be carefully attached to take vibrations into account. All connections shall be crimped. Screw type terminals are prohibited.

8.15.1.5.8. External lighting

External lighting concerns lighting of the areas around the building, the covered area, theplatform of the bunker, the parking lot, the roadway and the barrier.

8.15.1.5.8.1. Area around the building, platform of the bunker The selected lighting level is 50 lux around the building and the platform. Additional lighting fordocking is defined in the paragraph above. Lighting shall be by means of the following equipment:

� for surrounding areas: low-consumption fluo-compact lamp installed above eachexternal exit,

� for the platform: metallic iodide spot lights or similar, according to design documents,installed on either side and at the top of the access ramp of the platform of the bunkerbuilding and offset to enable circulation in the gantry. Complementary lighting shallbe by means of external lighting of north and south sides of the gantry in forward andrear position,

� for the access ramp: lighting columns. These lights may also light the surroundingarea,

� for the covered area: fluorescent type. The power supply shall be from the external lighting TD of room 117, controlled in compliancewith the description given for this TD.

Page 72: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 72/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Lighting equipment shall be installed as follows:� with cables, type R02V, appropriate cross-section, justified by design documents for

all equipment on fronts and in covered area,� with cables, type RVFV, appropriate cross-section, justified by design documents for

lighting columns,� with a 29 mm² cross-section cable which joints the cable, for lighting columns, and

connected to equipment,� by earthing of cable shielding and especially in the entry to the bunker building, the

sealing sheath will be remade at each connection.8.15.1.5.8.2. Roadway, parking lot

The selected lighting level is 25 lux approx. for the parking area and the roadway. The personnel circulation roadway shall be protected by devices separate from those of thematerial transport roadway. The lighting of the parking lot and the roadway shall be by means of lighting column typeequipment. Power supplies shall be provided from:

� TGBT substation 1D60 for the roadway,� external lighting TD of room 117 for the parking,

and controls shall be in compliance with the description given for these TDs. Lighting equipment shall be installed as follows:

� with RGPFV type cables, appropriate cross-section and justified by designdocuments,

� by installing a 29 mm² cross-section cable which joints the cable, for lighting columns,and connected to equipment,

� by earthing of cable shielding of each cable section and especially in the entry to thebunker building, the sealing sheath will be remade at each connection,

� by installing a trace net in the trench,� by integration of bunkers for the attachment of lighting columns.

8.15.1.5.8.3. Lighting column type lighting equipment Lighting column type lighting equipment shall be made of hot-galvanized steel, height 8 m with1.50-m bracket, PETIT JEAN diffusion type to remain homogeneous with the existing lighting, orsimilar, with light fixture ECLATEC ref. LEM 101L MULTITEC and 250 W mixed MMF lamp, toremain homogeneous with the existing lamps, or similar. The distance between lightingcolumns is estimated to be 22 meters on the roadway, to be confirmed by the lighting study.

8.15.1.5.9. Shelter power supplies

Power supplies for 4 or 5 shelters are scheduled. Power supplies shall be made individuallyfrom the category TD for external lighting in room 117.

Page 73: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 73/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Power supplies shall be made as follows:� with RGPFV type cables, appropriate cross-section and justified by design

documents,� by installing a 29 mm² cross-section cable which joints the cable, for lighting columns,

and connected to equipment,� by earthing of cable shielding of each cable section and especially in the entry to the

bunker building, the sealing sheath will be remade at each connection,� by installing a trace net in the trench,� with necessary slack at each shelter.

To protect cameras against lightning, a radial type earth connection shall be made for eachshelter. This earth connection shall be interconnected with the earth network of the shelter andto the 29 mm² cable. The length of each radial of the radial system shall be 8 m. The lightning arrestor earth connection shall be 1 meter at least from the shelter opening. A special lightning counter shall be installed for each shelter for the lightning arrestor downconductor. The characteristics of this lightning counter will be as follows:

� lightning current detection of lightning arrestor down conductors in relation to apreprogrammed threshold,

� sensitivity threshold, 2.5 kA approx.,� impulse counter,� optical fiber transfer of impulses,� sealed polycarbonate box (IP minimum 47),� « ST » type optical connection,� connection to 30x2mm flat down conductors,� with attachment flanges.

The optical fiber transfer shall be connected to room BCV CCS of the bunker for routing to theCCS by optical fiber network the BCV CCSs. The contractor of this work package shall providefor:

� with the approval of the contractor of the low-current work package, all connectionsand equipment required for correct operation of the system,

� the calibration or testing of the lightning counter with a report supplied by anindependent organization.

8.15.1.5.10. High-speed evacuation system lighting

The high-speed evacuation system shall be provided with indicating lighting, normal lighting andsafety lighting at the entrance, and braking lighting. This lighting shall be set up as follows:

� - at each level:

� indication: by permanent type 300-lumen independent unit, marked "high-speed evacuation",

Page 74: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 74/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� normal lighting at sheath entry: by a light fixture fitted with two lamps,

� safety lighting of sheath entry: by a non-permanent 60-lumen independentunit.

� - braking lighting by three windows located at 120 degrees, height 6.35 meter fromground, unit power 500W.

Lighting of the entire high-speed evacuation system shall be following release of the "chute".The command shall be identified by a special label.

8.15.1.5.11. Gantry aircraft lighting

The gantry aircraft lighting shall be powered by the TD of level 18400. Aircraft beaconing shall be by means of lights installed at each corner of the gantry. Theselights shall be installed in masts attached to the peripheral gangway to make them accessiblefor maintenance. For protection against lightning, external links shall be made either with RVFV cable, or R02Vcable in metal ducting. Earthing of cable strips or metal ducting shall be before the entry to thebuilding by a 360-degree connection. The sealing sheath shall be remade if RVFV cables areused. Lightning arrestors shall be installed at the cable entry and top part of the gantry. Lightningarrestors will comply with the characteristics defined in the Internal LPS chapter (IIPF),according to the lightning arrestor protection paragraph. Lightning arrestor boxes shall be of easy access from the top-level platform.

8.15.1.6. Socket outlets

Socket outlets shall be of a standardized type, and the installation method and compositionshall be adapted to the rooms where used. Several types of fixed socket outlets are scheduled:

� 230V 2P+E 10/16A,� 400V 3P+N+E 20 and 32A depending on requirement,� 24V 2P + connector:

� on mobile platforms,

� under floor level 14000: with built-in safety transformer 250VA powerprotected by circuit breaker at secondary, or safety unit,

� in T4 type box installed at each level close to high-speed evacuation chute, including:

� socket outlet differential circuit breakers,

� socket outlet 3P+ N +E 32A,

� two socket outlets 2P +E 16A.

Page 75: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 75/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The pod outlet shall be installed at roof access point close to the door and on the inside.The outlet shall be of a type identical to what exists. The contractor of this work package shall provide power supplies, each protected by a 0.03Adifferential device for category II socket outlets 2P+E 10/16A at bottom of racks.

8.15.1.7. Specific category II power supplies

The various technical work packages involved shall specify the characteristics of equipment tosupply, to the energy work package, to enable correct sizing of protection systems and links.The specific power supplies are listed in the table below. The interface limit is fixed:

� for category II: at ends with sufficient slack for connection, responsibility of thecontractor of the work package involved, with installation of nearby cutoff powerdevices for power supplies,

� for category III: the terminals downline from protection systems in distribution panels.

A power supply provision shall be provided per row of racks with the necessary slack forsupply to socket outlets at bottom of racks. This power supply shall be provided with a30 mA differential protection device.

8.15.1.8. Collector tank, flange chute, pump power supply

Installation of a pump in the collector tank is scheduled to recover flange chute water. Thecontractor of this work package shall:

� In the TGBT, install a rack to protect the pump power supply line (power 20 kW),� Install a lightning arrestor box at the entry to the building (chapter 8.3.2.3),� Supply and install an RGPFV type cable to power the pump (20 kW),� Install a nearby cutoff at the collector tank.

8.15.2. Room equipment

The following table describes the equipment scheduled per room. The meanings of thecolumns are:

� room: drawing number,� IP/IK, ATEX: Protection index, impact index, and possible ADF information,

Page 76: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 76/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� lighting: with lighting of type of equipment including:

� Fluo: fluorescent tube equipment.

� Fluo BL: fluorescent tube equipment, low luminance.

� Sealed: fluorescent tube equipment, sealed type.

� B C: low-consumption bulb light fixtures.

� Ens: volume that can accommodate the launcher and its associated stairwaywells; the lighting control shall be by means of pushbuttons installed at eachlevel as follows: entrances (level 14000), close to a lift exit and landings bystairway wells; the control shall be divided into two subassemblies: Ens 1 andEns 2 according to the tables below,

� IO: metallic iodide equipment,

� CAN: lighting column,� BA: number of fixed safety lighting independent units, with P meaning for portable

units.� Control: number of control spots, with: TL for remote switch, BP for pushbutton, CT

for contactor, SA for simple lighting, VV for two-way and Inter for switch, with otherpossible information concerning the rooms involved.

� PC: number of socket outlets, with:

� M2: socket outlet 10/16A / 2P+E / Cat2 50Hz.

� T2: socket outlet 20A / 3P+N+E / Cat2 50Hz.

� BS: 24-volt socket outlet with safety transformer unit.

� P24: 24-volt socket outlet.

� T4: T4 type box.� Miscellaneous: main equipment in room and power supply (Alim) provision with slack

required for work package involved other than energy:� Ground: number of ground points, with:

� M: for exposed metallic parts and equipotential frames,

� m: for measurement grounds,

� e: for electron masses,

� PF for lightning,

� Emergency stop:

� L: local,

� G: general, except HV,

� P: gantry.

Page 77: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 77/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

BUNKER

001 Mast base

55/07 300 lux. 2 1 SA 1 M2 1 M AU:L

002 TCV process

55/07 300 lux.Fluo 1 1 SA 4 M2

1 M 1 m

1 pwr sup, Cat III, TCV rack (high power), 1 pwr sup, cat II, protectedby 30 mA for rack bottomPCs EMC reference

013 VES process

55/07 300 luxFluo 1 1 SA 4 M2

1 M 1 m

1 TD, cat IIIA, 1 TD, cat IIIB, 1 pwr sup, cat II, protectedby 30 mA for rack bottomPCs EMC reference

014 Lobby

55/07 200 luxFluo 2

TL 3 BP

4 M2 1M AU:L

015 Batteries

55/07200 lux Fluo 1 1 SA

016 Batteries

55/07200 lux Fluo 1 1 SA

TVC batteries (option), Battery circuit breaker box

017 Batteries

55/07200 lux Fluo 1 1 SA

TVC batteries, Battery circuit breaker box

018 UPSs

55/07200 lux. Fluo 1 1 SA 1 M2

1 M 1 m

1 UPS, 1 battery switch, 1 TGBT, cat III

003 Gallery

55/07 150 luxFluo 3 2 M2

011 Lock

55/07 150 luxFluo 1

TL 2 BP

004 Communication

55/07300 lux. Fluo 1

TL 2 BP

4 M2 1 T2

1M 1m

1TD cat III B

Page 78: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 78/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

005 Lock + stairs

55/07200 lux. Fluo 1

TL 2 BP

1 M2 AU:L

012 Safety

55/07300 lux. Fluo 1 1 SA

2 M2 1 T2

1 M 1 m

1 TD, cat II, racks

006 Technical room

55/07 200 luxFluo 1 CT on 1

Inter 1 M2 1PF

007 Cat III CU

55/07 200 luxFluo 1 1 SA 1 M2

1 M 1 m

2 UPSs, 4 battery switches, 1 converter, 2 voltage adaptation racks

008 Batteries CU H

55/07200 lux Fluo 1 1 SA

Batteries CU H, Battery circuit breaker box

009 Batteries CU B

55/07200 lux Fluo 1 1 SA

Batteries CU B, Battery circuit breaker box

010 Stairs

55/07200 lux Fluo 1

TL 3 BP

1 M2 AU:L

100 Connection

55/07 300 lux. 2 1 SA 1 M2 1 M

101 Racks

55/07 300 lux.Fluo 1 1 SA 1 M2

1 M 1 m

1 TD, cat III CU B, EMC reference

102 Lock

55/07 200 luxFluo 1

TL 3 BP

1 M2 1M

1 TD, cat II, auxiliarysystem, AU:L External: - 3 mobile UPS PCs,-1 charger box,

Page 79: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 79/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

103 BCV/CCS

55/07 300 lux.Fluo 2

TL 2 BP

4 M2 1 T2

3 M 3 m

1 TD, cat II 4 TDs, cat III A 4 TDs, cat III B 4 pwr sup, cat II, protectedby 30 mA for rack bottomPCs EMC reference AU:L External for room 002 - 3 mobile UPS PCs, -1 charger box

104 CO2

55/07 200 luxFluo 1 1 SA 1 M2

105 Technical room

55/07 150 luxFluo 2 1 SA 1 M2

106 Withdrawal

55/07 300 lux.Fluo 3 4 M2

(lighting on 2 circuits) 1 air cond pwr sup withnearby cutoff switch, AU:L

125 Lock

55/07 300 lux.Fluo 1

2 SA +1 withlock

107 CO2

55/07200 lux. Fluo 1 1 SA

1 M2 1 T2

1 M

108 Fluid

55/07300 lux. Fluo 2

TL 2 BP

3 M2 1 T2

2 M 1TD compressor40kW+links, 1 AUL

109 Lobby

55/07200 lux. Fluo 2

TL 1 BP

2 M2 1 TD, cat II, auxiliarysystem, AU:L

111 Batteries

55/07200 lux. Fluo 1 1 SA

Batteries III A and III B 2 battery circuit breakers

112 Batteries

55/07200 lux. Fluo 1 1 SA

Batteries III A and III B 2 battery circuit breakers

Page 80: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 80/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

113 UPSs

55/07200 lux. Fluo

1 1 SA 1 M2 1 M 1 m

4 UPSs, 4 battery switches 1 TGBT, cat III A, 1 TGBT, cat III B,

114 Transformer airconditioning

55/07200 lux.Fluo

1 1SA 1M2 1M

115 TGBT

55/07200 lux. Fluo

1+ 1P

1 SA 2 M2 1 T2

2 M

1 pwr sup, cat III B 2 TGBTs, cat II, 1 TD, cat II, auxiliarysystem

116 HV substation

55/07200 lux. Fluo

1+ 1P

1 SA 2 M2 1 T2

1 M 1 PF

4 transformers 1 general counter

117 Lobby

55/07200 lux. Fluo

2 TL 4 BP

2 M2 1 T2

2 M 2 PF

1 TD, cat II, externallighting, TDs, launcher lighting, AU:L External: - 2 mobile GE boxes, - 1 GE preheating PCs, - 3 mobile UPS PCs, - 1 charger box - AU:G

118 Air conditioning

55/07200 lux. Fluo 1 CT on 1

Inter 4 M2 1 T2

3 M 2PF

3 pwr sup, cat II: total 400kw, AU:L

126 Air conditioningauxiliarysystems

55/07 300 Lux

Fluo 1 SA 1M2

1M 1m

1 pwr sup, cat II, 40 kW, 1 TD, cat III B

127 Fresh air

55/07 200 Lux

Fluo 1 SA 1M2

119 Sanitaryfacilities, men

55/07 150 lux

BC 1 1 SA 1 M2 Equipotential bondings

Page 81: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 81/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

120 Sanitaryfacilities,women

55/07 150 lux

BC 1 1 SA 1 M2

Pwr sup for water heater 4kW approx.,routed in all-pole switch andon slack time tariff withManu and Auto operation inTD CMV power supply Equipotential bondings

121 Plumbing +overpressure

55/07 200 lux

Fluo 1 1 SA

2 M2 1T2

2 M 1PF

1 TD, cat II AU:L external

122 Storage

55/07 200 lux

Fluo 1 1 SA 1 M2

123 Tool storage

55/07 200 lux

Fluo 1 1 SA 1 M2

Surroundings 55/07 30 luxapprox.

BC

See rooms

Clock+auto/manu/off

Platform 55/07 50

lux

Clock+auto/manu/off

Lighting addition fromgantry

Outside

4 or 5 shelter powersupplies, gantry power supplies, airchute pump power supply

Roadways 55/07 25 lux

approx.

CAN

Clock+auto/manu/off

Parking lot 55/07 25 lux

environ

CAN

Clock+auto/manu/off

GANTRY

Ens: For the volume that can accommodate the launcher and its associated stairwells, the lightingshall be controlled by pushbuttons installed at each level as follows: at entries (level 14000), close tothe lift exit and landings by stairwells.

Page 82: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 82/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

Level 14000 circulation

55/07+ ATEX

ofzones

200 lux Fluo

Lightunit Ens1

4 M2 4 BS

1 M 2AU:P, 1AU: G: entrance, 2 motorization pwr supplies

Level 15600 entry

ATEX Fluo Yes Ens1 1 M2

Level 14200/ 16400

55/07 200 lux Fluo

Yes Ens1 2T4

Level 18400 Energy 101

55/07 200 lux Fluo

1+P 1 SA 1 M2 1 M TD, cat II, supply by cablechain TD, cat III A and B

Level 18400 Air cond 102

55/07 200 lux Fluo

1 1 SA 1 M2 1M

Level 18400 Platform

55/07 300 lux Fluo

Yes Ens1 1 T4 2 AU:P

Level 21200 RMO 201

55/07 300 lux Yes 1SA 2M2 1M 1m

TD, cat IIIA TD, cat III B 1 pwr sup, cat II, protectedby 30 mA for rack bottomPCs

Level 21200 Air cond 202

55/07 200 lux Fluo

Yes 1SA 1M2

Level 21200 Platform

55/07 300 lux Fluo

Yes Ens1 1 T4 2 AU:P

Level 24000 Racks TCV 301

55/07 300 lux Fluo

1 1 SA 2 M2 1M 1m

1 TD, cat III A 1 TD, cat III B 1 pwr sup, cat II, protectedby 30 mA for rack bottomPCs

Level 24000 Platform

55/07 300 lux Fluo

Yes Ens1 1 T4 2AU:P

Level 26600 Air cond 401

55/07 200 lux Fluo

Yes 1SA 2M2 1M 1 pwr sup, cat II, 65 kVA 1 pwr sup, cat III

Level 26600 Platform

55/07 300 lux Fluo

Yes Ens2 1 T4 2AU:P

Page 83: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 83/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

Level 29200 Racks TCV 501

55/07 300 lux Fluo

1 1 SA 2 M2 1M 1m

1 TD, cat III A 1 TD, cat III B 1 pwr sup, cat II, protectedby 30 mA for rack bottomPCs

Level 29200 Fluids 502

55/07 300 lux Fluo

Yes 1SA 1M2 1M

Level 29200 Circulationbetween lift andpropellant room

55/07 ATEX

300 lux Fluo

Yes Ens2

Level 29200 Platform

55/07 300 lux Fluo

Yes Ens2 1 T4 2AU:P

Level 31800 Propellant 601

55/07 ATEX

300 lux Fluo

2 1SA 1M2 1M

Level 31800 Racks DVT 602

55/07 300 lux Fluo

1 1 SA 2 M2 1M 1m

1 TD, cat IIIA 1TD, cat IIIB

Level 31800 Circulationbetween lift andpropellant room

55/07 ATEX

300 lux Fluo

Yes Ens2

Level 31800 Platform

55/07 300 lux Fluo

Yes Ens2 1 T4 2AU:P

Level 34400 UDMH

55/07 ATEX

300 lux Fluo

2 1 SA 1 M

Level 34400 Circulationbetween andUDMH room

55/07 ATEX

300 lux Fluo

Yes Ens2 Management lights to beinstalled outside the ATEXzone

Level 34400 Fluid room 702

55/07 300 lux Fluo

1 1 SA

Level 34400 Platform

55/07 300 lux Fluo

Yes Ens2 1 T4 2AU:P

Page 84: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 84/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

Level 37000 Racks BVC

55/07 300 lux Fluo

1 1 SA 2 M2 2M 2m

1 TD, cat IIIA, 1TD, cat IIIB, 2 pwr sup, cat II, protectedby 30 mA for rack bottomPCs

Level 37000 to47400 55/07

300 lux Fluo

Yes Ens2 1 T4

Level 39600: 4 platformpwr supplies with lockableswitches 2AU P per level

Level 50000 to60000 55/07 200 lux Yes Ens2 1 T4

Level 60 000 crane pwr supby lockable switch Pod PC

All levels Vertical andhorizontalcirculations

55/07

200 lux

Yes

Ens 1+ Ens2

Lift shaft 55/07 60 lux 1 SA

Per ½ halfmobile platform

55/07 ATEX

300 lux Yes 1 SA 1 P24 1M 1 flexible braid

Evacuationsystem 55/07

Windowswith 2lamps

3 500Wunits ofequipment

Yes 1 SA

Docking -from insidedoor level -from outside

55/07

300 lux at base 120 lux radius 20m IO

As perdescription

Ditto +Clock+auto/manu/off

Aircraft 55/07 Permanent

Page 85: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 85/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room IP/IK ATEX

Lighting BA Control PC Mass/Ground Miscellaneous

MAST

Level 34400 1 M 1 m

1 TD, cat III CU H, ondampers (not included inwork package)

All levels 55/07 200 lux windows

P onoutlet

By BPat eachlevel

1 M2at eachlevel

8.16. Launcher lighting

8.16.1. Principle

The launcher is lit with floodlight type lights designed to illuminate great heights. These lightsare secured to the top of masts and pylons provided by the civil engineering work package,height to be defined by the lighting design documents. A platform will enable adjustment and maintenance once installed. The masts and bunkers are part of the civil engineering work package. However, thecontractors of the various work packages have to coordinate work to take into account allpossible constraints related to each work package.

8.16.2. Earth network

A ground ring earth network will be created at each mast or pylon anchoring spot. The networkwill be made of 120 mm2 minimum cross-section bare copper conductors and will be connectedby 50 mm² minimum cross-section conductors to all metal structures of anchoring systems,bunker reinforcement, etc. Each earth network shall be interconnected:

� to the general earth network of the site by 95 mm² cross-section bare copper cables,which will be routed with the lighting system power supplies

� to each earth conductor of the launcher lighting power supplies. All connection points between the copper conductors and the steel reinforcement will be madeby CADWEL type welding. The resistance of each earth network must be less than 1 ohm (measurement made beforeinterconnection with equipotential bondings ). The contractor of this work package shall provide photos covering 20% of the various phases ofthe non-visible construction part (buried) of the earth network, to be appended to the specific file« earth network, lightning protection and EMC ».

Page 86: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 86/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.16.3. Lightning protection

8.16.3.1. External system

The lightning capture device shall be made up of a 100 cm minimum capture rod located at thetop of each mast or pylon. The capture rod shall be installed so as to protect the lightingapparatus from lightning. Each capture rod shall be welded or joined with 30x2 mm cross-section tinned flat copper bar tothe mast or pylon which will make up the down conductor. Each down conductor shall be connected to a lightning earth connection made up of 30x2tinned copper strips laid in a radial system, minimum overall dimensions 8 m, buried at least50 cm deep and installed at 1 meter from the base of the mast or pylon. Each lightning arrestor earth connection shall be connected to the ground ring of the mast orpylon base involved by means of a 30x2 mm cross-section tinned copper strip. A disconnection device shall be located in an inspection hole after interconnection with theground ring. The resistance of each lightning earth connection shall be less than 10 ohms (measurementmade before interconnection with the ground ring). All exposed metal parts of lighting apparatus shall be interconnected to capture devices or downconductors by means of flexible conductors, preferably flat. These bonds shall be as short aspossible. The contractor of this work package shall provide photos covering 20% of the various phases ofthe non-visible construction part (buried) of the earth network, to be appended to the specific file« earth network, lightning protection and EMC ».

8.16.3.2. Lightning counter

A specific lightning counter designed for lightning arrestor down conductor shall be installed oneach down conductor of each pylon or mast. The characteristics of these lightning countersshall be as follows:

� detection of lightning current on lightning arrestor down conductors and in relation toa preprogrammed threshold,

� sensitivity threshold 2.5 kA approx.,� impulse counter,� impulse optical fiber transfer,� sealed polycarbonate box (IP minimum 47),� "ST" type optical connection,� connection to down conductors with 30x2mm flat bar,� with attachment flanges.

The optical fiber transfer shall be routed to the BCV CCS room of the bunker for connection tothe CCS by the optical fiber network of the BCV CCS. The contractor of this work package shallprovide:

Page 87: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 87/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� conjointly with the contractor of the low-current work package, all connections andequipment required for correct operation of the system,

� calibration and/or testing of the lightning counter, including a report provided by anindependent organization.

8.16.3.3. Internal system

The internal LPS is designed to prevent, when lightning current flows in a conductor, theoccurrence of difference in potential that may cause the formation of dangerous sparks. For this purpose, low-voltage lightning arrestors (terminal protection) shall be installed for alllinks to lighting apparatus:

� - maximum steady-state voltage Uc = 275/440 V,� - maximum discharge current Imax >= 15 kA wave 8/20,� - nominal discharge current In> = 5 kA wave 8/20,� - protection level Up <= 1.5 kV.

These lightning arrestors shall be installed upline from the distribution panel (TD) of thelauncher lighting system and on the power supply, in a key-locked box integrating the lightningarrestor and protection system, if applicable. The earth links shall be as short as possible anddirectly connected to the ground of the electrical box, interconnected with the general earthnetwork.

8.16.4. Calculation base

The system shall take into account the ground pressure at lift-off. Lighting shall be over the entire surface (360°) and at a height of:

� during the phase prior to lift-off: 35 meters, from level 14000,� after lift-off over a distance: 80 meters i.e.: 35+80=115 meters from level 14000

The launcher is assimilated to a 3-meter approx. diameter cylinder, height 35 meters approx. inits optimum version. Lighting shall make it possible to:

� observe umbilical links, launcher side, by video cameras and camera systems,� prestige or general information type photos taken by 35 mm cameras or 6x6 and

24x36 photo cameras The required average lighting level is as follows:

� 200 lux at the base,� 600 lux over the entire surface of the launcher,� 1000 lux at the umbilical links.

Lighting measurements shall be made in a vertical plane parallel to the centerline of thelauncher.

Page 88: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 88/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.16.5. Lighting apparatus

The lighting apparatus used on the Ariane 5 launcher complex are made by Philips, typeARENA VISION MFV 406, with the following characteristics:

� 1 and 4 category optics,� bulbs, type MHD 1800W, powered with 400 volts.

In order to remain homogeneous with the existing systems, the apparatus of the VEGA launchercomplex shall be the same mark and preferably with the same technical characteristics:

� preferably category 1 and 4 optics according to the design documents. However, theoptic shall be chosen from a range of seven different types of optics making itpossible to adjust the light flow according to the distance between the point ofinstallation of the apparatus and the zone to illuminate,

� bulbs, type MHD or MHN 1800W minimum, under 230 or 400 volts, in compliancewith the design documents. Preference shall be given to the apparatus with thelowest priming current.

Apparatus attachment shall take into account:� a relative wide elevation and bearing adjustment,� turning over of lights on their centerline during lift-off. For this purpose, an adjustable

linkage system enabling a vertical adjustment shall be installed,� damping of vibrations due to lift-off to ensure the mechanical strength of apparatus

and bulbs. For this purpose, apparatus shall be secured to the cross-member fixed tothe mast by means of two hot-galvanized steel plates installed on vibration mounts.This system will integrate horizontal adjustment by rotation of a plate,

� maintenance.

8.16.6. Power supplies

Lighting apparatus shall be individually and directly powered from the distribution panel (TD)and two separate ballast cabinets. The TD and the cabinets shall be located in the lobby 117 ofthe electrical rooms. The link between the TD and the ballast cabinets shall be made with RO2V cables. The linksbetween the ballast cabinets and the lighting apparatus shall be made with RGPFV cables, laidas follows:

� on cable trays (hot-galvanized) in the building,� in sleeves buried between the building and the base of masts or pylons,� in masts or pylons.

Cable armoring shall be connected to the earth network with 360 °C connections at 2 ends, atthe entrance to the room for the building with a collar compatible with copper and armor. Thecollar shall be covered with a glued sheath to rebuild the cable sheath and thus prevent anycorrosion, especially on masts or pylons.

Page 89: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 89/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

8.16.7. Distribution panel

A distribution panel shall be installed in lobby 117 of the electrical rooms. The size of the panel shall be defined according to the equipment to be installed with a 30%useful spare space, modular type with front panels and door fitted with a lock. It shall include:

� connection lands or similar, depending on wiring + screen for connection of powersupply cable,

� a general cutoff fitted with a front-mounted command,� a 2x6A circuit breaker with a breaking capacity adapted to the power on indicator light

circuit,� a terminal block downline from the general cutoff, minimum nominal current adapted

to head protection,� contactor circuit breakers with a breaking capacity adapted to the power lines of each

lighting apparatus with the ballast downline in two separate cabinets,� four circuit breakers with a breaking capacity adapted to lighting apparatus control

circuits (one per mast or pylon),� two circuit breakers with a breaking capacity adapted to the ballast cabinet ventilation

circuits,� the 48 V relays for individual control of contactors powered by the CCS front-end.

The relay control links are the responsibility of the CCS,� the connection terminal boards of the power, command circuits, separate for each

type of circuits, grouped and identified with engraved and screwed labels. The panel and the circuit breakers shall be identified by engraved labels riveted to supportsaccording to the CNES technical specification(s). All conductors, switchgear and control gearinside the panel shall be identified according to the CNES technical specification(s). Cables shall be identified with label holders, marked in letters and numbers, attached to cablesas per CNES technical specification(s).

8.16.8. Ballast cabinets

Ballast cabinets shall be installed in lobby 117 of electrical rooms. Cabinets shall include:

� ballast and accessories needed for correct operation of systems,� connections for cables to terminal boards, identified with engraved and screwed

labels,� appropriate ventilation.

Cables shall be identified with label holders, marked in letters and numbers, attached to cablesas per CNES technical specification(s).

Page 90: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 90/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

9. CDL3

9.1. Definition of systems The systems required for the VEGA project are limited to:

� installation of category III A and IIIB distribution panels and earth terminal blocks atpanels:

� in operations room no.167 and technical room no.168 of the first floor,

� in the calculation center room no. 18 of the ground floor,� setting up of a ground reference (EMC) in room no. 168 and no. 167,� installation of socket outlets in rooms no. 167, 168

Lighting systems, auxiliary system sockets and other devices are considered as being availableand satisfactory.

Page 91: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 91/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

9.2. Definition of requirements Definition of category III A and III B requirements.

Category III A C ategorie III BBuild ing/ Room N° Equipment Nb Pu C os Pt Nb Pu C os Ptlevel (kW ) ph i (kVA) (kW ) phi (kVA)CDL3 operations room 167 console 4 1.5 1 6 4 1.5 1 61st floor

d isp lay m onitor 2 0.1 1 0.2 2 0.1 1 0 .2 technical room 168 rack 5 2.5 1 12.5 5 2.5 1 12.5

CCS 4 1 1 4 4 1 1 4Ground floo Calculation center 18 machine 1 2.5 1 2.5

workstation 3 0.5 1 1.5 3 0.5 1 1 .5Tota l 10 10

Growth 0.5 Requirem en 13 0.5 Requiremen 12

The energy required for VEG A requirem ents at CDL3 is 13 kVA forcategory III A and 12 kVA for category IIIB .

9.3. Category III A and III B distribution

9.3.1. Power supplies

Power supplies for requirements:� in operations room no. 167,� in technical room no. 168,� in calculation room no. 18,

will be satisfied from the existing category III TGBTs by equipment, of the same make, to remainhomogeneous with the existing systems, as follows:

� category III A: from TGBT no. 841 06A 31 by the installation of a circuit breakerNS100 fitted with a relay 4x63A +OF+SD on each power supply of the TDs of roomslisted in the table below,

� category III B: from TGBT no. 841 06A 32 by the installation of a circuit breakerNS100 fitted with a relay 4x63A +OF+SD SD on each power supply of the TDs ofrooms listed in the table below.

Outgoing shall be directly connected to circuit breaker terminals. The neutral conductor and theearth conductor are separate, TNS diagram. SD and OF contacts shall be wired in series in existing chains corresponding to the TGBTinvolved.

Page 92: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 92/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The links between the TGBTs and the TDs to be created shall be made with RVFV cable,minimum cross-section 5G16mm² as defined in the design documents. Laying mode:

� in existing cable trays or cable trays to be created, in technical rooms or suspendedceilings,

� in existing channels or channels to be created in rooms crossed. Cable trays and channels created shall be included in the proposal. Cable armor shall be connected to the earth network with 360 °C connections at 2 ends, beforeentering the room, using a collar compatible with copper and armor. The collar shall be coveredwith a glued sheath to prevent any corrosion.

9.3.2. Distribution panels

To supply the systems, the following shall be created for each category III A and III B:� in operations room no. 167: a distribution board; these boards, size approximately

600 x 600 x 275 mm, shall be of the modular type with front panels and shall beinstalled in a low office cabinet supplied as part of the furniture. This cabinet willbe provided with two doors, each fitted with a key lock ( RONIS 3113A), a leadsealing device and a magnetic type contact.

� in technical room no. 168 and in calculation center: distribution cabinet, modular typewith front panels and transparent door(s), each fitted with a key lock ( RONIS 3113A),a lead sealing device and a magnetic type contact.

Each board and cabinet shall comprise, according to the following table:� connection lands or similar, depending on wiring + screen for connection of power

supply cable,� 1 general switch 4X63A, fitted with an OF contact,� 1 terminal block, multiclip type, 100A minimum,� 1 terminal block voltage white indicator light, protected by circuit breaker with

appropriate breaking capacity and rated2x6A,� 9 circuit breakers, all poles protected, with appropriate breaking capacity, 2 poles, +

SD+OF contacts, for rack cables connected to identified terminals. The rating ofcircuit breakers and the corresponding number are defined below.

Page 93: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 93/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Room

Qty of panels

Racks

Location

Per panel Qty C/B 10A/C

Per panel Qty C/B 16A/C

Operations No. 167

Cat III A: 2 Cat III B: 2

consoles consoles

Operationsroom

5 5

4 4

Technical No. 168

Cat III A: 1 Cat III B: 1

racks racks

Technical room 5 5

4 4

Calculation center No. 18

Cat III A: 1

Cat III B: 1

Machine 2.5Kva

3 workstations 3 workstations

MEX room

8

9

1 C/B 2x20A

SD and OF contacts shall be wired in series in two separate chains and shall be routed back todisconnectable terminals for wiring according to the information transfer paragraph. Packing glands shall be provided at cable crossings. Rack cables are not included in the services of the contractor of this work package. The contractor of the work package:

� shall balance phases on service points,� shall not provide cables for racks in rooms no. 167 and 168,� shall provide for calculation center rooms the links between panels and boxes, make

Legrand (as existing system), dimensions 190x150mm with terminals, sealable box inlocking system.� Distribution between panels and boxes shall be in channels.

9.3.3. Category III information transfer

Transfer of information dialoging with the CCS is not included in the services of the contractor ofthis work package but the responsibility of the control-command-auxiliary system (CCS) workpackage contractor. However, the contractor of this work package must give all informationnecessary to ensure good completion of site work. Information to transfer is described in the previous paragraph. The interface points are locatedat:

� TD of category III A + B: the disconnectable terminals in the tables defined in theprevious paragraph,

Page 94: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 94/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

9.3.4. Location of panels

The distribution panels are located as follows:� Operations room no. 167: on the wall in the entrance,� Technical room no. 168: close to the existing category III panels,� Calculation center room: in the room of panels 841 18 30A and 841 18 30B, on the

wall section at 90°.

9.3.5. Electron mass and measurement ground collectors

An exposed metallic part and equipotential frame collector and a measurement collector shallbe installed close to each panel above created. These collectors, minimum size 32x5x400 mm, shall be joined by silver soldering to the groundring earth circuit by a link:

� made of a 120 mm² cross-section bare copper cable, with a control connection stripfor exposed metallic part and equipotential frame collectors,

� made of 1x50 mm² cross-section copper R02V cable, by means of a controlconnecting strip, identified by a special label for measurement collectors.

However, to obtain general equipotentiality, the various earth collectors shall be interconnectedtogether for linking with the ground ring.

9.3.6. Socket outlets

The contractor of this work package shall provide:� two socket outlets, standardized type 230V 2P+T 10/16A, category II on each console

in room no. 167 (number of consoles: 4),� a power supply per row of racks, protected by a 0.03A differential device for socket

outlets 2P+T 10/16A of category II at the bottom of racks in rooms no. 167 in 168,� 6 socket outlets 2P+T 10/16A and 2 power supplies, protected by a 0.03A differential

device, either on connectors or by cables provisions for printers in the calculationcenter.

9.4. Electromagnetic compatibility protection (CEM) In technical rooms no. 168 and no. 167, the equipment is installed on a technical floor. To prevent electromagnetic interference, a ground reference will be made. This referencelocated under the technical floor shall consist of 30x2 mm tinned copper flat conductors locatedas follows:

� an equipotential ring around rooms, and at 20 cm from ground,� a grid on ground, 1.2x1.2 m, with the ends connected to the ring.

Page 95: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 95/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The ground reference shall be connected to the equipotentiality bars of the room and:� the ground ring,� the metal structures.

The purpose of this ground is to connect all exposed metal parts and equipotential frames ofthis room, i.e.:

� metal frames of racks, boxes and consoles� cable trays under floor,� cylinders and metal structures of technical floor as follows:

� all ends to the ring,

� all cylinders to grid,� all incoming non-electrical and electrical lines, including air-conditioning sheathes,

Connections shall be made as follows:� by silver soldering for the ring and grid,� by 30x2 mm braids, maximum length 300 mm approx., for racks and connected to:

� the grid,

� the racks with 8-mm diameter lugs,� by silver solder connections for items other than those indicated above. Conductors

shall be 30x2 mm flat bars or braids. Incoming lines will enter the rooms at the same location. An earth collector at the point ofpenetration shall be connected to the ground reference to make all connections. Theconnections on these lines shall be on 360°C preferably by means of a copper plate for non-electric lines.

Page 96: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 96/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

10. ZEPHIRO PREPARATION CELL BUILDING

10.1. Building classification According to NFC 15103, the building is classified as follows:

� AE: 4 ; AD: 5 ; AG: 2 , Considering the pyrotechnical activity carried out, the building is subject to the regulationsconcerning classified systems.

10.2. Earth network An ground ring earth network will be made of a bare copper conductor, minimum cross-section120 mm². The earth network will be silver soldered to the reinforcement bars of the building ateach down conductor of the framework and to natural conducting items of the construction by a95 mm² cross-section conductor. The building earth network shall be interconnected with the general earth network of the site bymeans of a 95 mm2 cross-section bare copper cable routed with the electrical power supply. Two collectors, minimum size 32x5x400 mm, for exposed metal parts and equipotential framesshall be installed in the building: one under the distribution panel and the other at the end of thebuilding. Each collector shall be joined by silver soldering to the ground ring earth circuit by a120 mm2 cross-section bare copper cable by means of a connecting control strip. All exposed metal parts and equipotential frames such as distribution panels, cable trays, metalpower lines, etc., shall be connected to the earth collector, which will be created using anappropriate cross-section bare copper cable (minimum 29 mm²). Equipotential bondings are made between all exposed metal parts not interconnectedmechanically by means of bondings as short as possible:

� with a bare copper cable, minimum cross-section 25 mm², for fixed items,� with flexible copper braids or conductors, minimum cross-section 10 mm², for mobile

items. On cable trays, a 29 mm² cross-section earth cable shall be routed with the cable trays andeach cable tray section shall be connected to the earth cable by means of two terminals BB. Allexposed conductive parts such as those listed below shall be connected to this earth cable:

� power lines routed nearby,� metal structures.

10.3. Exposed pyrotechnical parts To earth exposed pyrotechnical parts, earth braids shall be installed, quantity 3: one for thetrailer and the container and the two others for the removable items. Each braid shall beconnected at one end to the earth collector and at the other end to an adapted device toconnect the item to earth.

Page 97: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 97/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

10.4. Lightning protection The building shall be protected against lightning. The protection level defined in the study is I with a 0.98 efficiency. The contractor of this work package shall provide photos covering 20% of the various phases ofthe non-visible construction part (buried) of the earth network, to be appended to the specific file« earth network, lightning protection and EMC ».

10.4.1. External Lightning Protection Systems ( IEPF )

The external lightning protection system (LPS) is designed to intercept the direct lightningflashes, conduct the lightning current from the impact point to the earth and to disperse itwithout any thermal or mechanical damage for the structure and no dangerous voltage surgesfor personnel and equipment to be protected.

10.4.1.1. Capture device

The roof capture device of the building will make up a 5x5 m size meshed cage, made up ofnatural components (framework). If necessary, capture rods will be provided, dimensionsaccording to the items to protect of at least 50 cm, shall be installed vertically to the vulnerablepoints of the building. The distance between two rods shall not exceed 15 m.

10.4.1.2. Down conductors

Capture devices shall be connected to down conductors installed around the building. Downconductors will use the metal structure and the average distance between two down conductorsshall be 10 meters. This value has been selected to better protect the building against"lightning" risks: for a 17x6 meter building, 6 down conductors are required, one at each cornerand one in the middle of the 17-meter side.

10.4.1.3. Earth discharge devices

Each down conductor shall be connected to an earth connection made of 30x2 tinned copperstrips laid in a radial pattern. The size shall be:

� 3 m minimum per radial if the number of radials is greater than 3,� 8 m minimum per radial if the number of radials is less or equal to 3,

buried at a depth of at least 50 cm at 1 meter from the building. They shall be connected to the ground ring by a 30x2 mm cross-section tinned copper strip. A device for disconnection shall be installed after interconnection with the ground ring. The resistance of each lightning arrestor earth connection shall be less than 10 ohms( measurement made before interconnection with ground ring).

Page 98: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 98/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

10.4.1.4. Lightning counters

A lightning counter with the following characteristics shall be installed, specific for the meshedcage:

� detection of lightning current on meshed cage down conductors and in relation to apreprogrammed threshold,

� sensitivity threshold 2.5 kA approx.� impulse counter,� sealed polycarbonate box (IP minimum 47),� connection to 30x2mm flat bar down conductors,� with attachment flanges.

The contractor of this work package shall calibrate or test the lightning counter and provide areport established by an independent organization.

10.4.1.5. External exposed part equipotentiality

All exposed metal parts located less than 1 m from down conductors shall be interconnected tothe down conductors. Bondings shall be as short as possible and shall be made with a conductor of the same type asthose used to make down conductors.

10.4.1.6. External bondings between buildings

To protect the electrical systems from induced lightning currents, the external bondings for highcurrents shall be made with cables reinforced with 2 steel strips, of the RGPFV type or similarfor LV cables. At the entry to the building involved, the following items will be connected to the exposed metalpart and equipotential frame earth collector:

� The strips or armor of high and low current cables, all current,� Lightning arrestors, where applicable,� Non-electrical pipes: water, air-conditioning, and any metal pipe.

Connections to incoming pipes are made over 360°C and the sealing sheath shall be rebuilt. All systems involved entering the building shall, if possible, be located at a single point.

10.4.1.7. General provisions

Special care shall be taken to avoid creating electrolytic or galvanic couples with the variousmaterials. Paint, if applied to galvanized steel, shall be according to SGS 436. The 30x2 mm flat bar shall not be drilled. Connection or assembly devices by silver solderingshall be used or specific coupling devices of the screw type.

Page 99: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 99/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

At all construction levels, to facilitate discharge of lightning current, the angles and radiuses ofcurves made by the flat bar must comply with the provisions of the documents mentioned in thisCCTP.

10.4.2. Internal Lightning Protection System ( IIPF )

The internal LPS is designed to prevent, during conduction of lightning current in a conductor,the occurrence of a potential difference which could result in the formation of dangerous sparks.

10.4.2.1. Internal exposed part equipotentiality

Internal exposed metal parts located at less than 1 m from capture devices and downconductors shall be interconnected with the metal structure of the building by bonds as short aspossible, made of a 16 mm2 minimum bare copper cable.

10.4.2.2. Protection by lightning arrestor

Four-pole low voltage lightning arrestors shall be installed for the building power supply link.The lightning arrestor characteristics shall be as follows:

� maximum steady-state voltage Uc = 440 V,� maximum discharge current Imax >= 40 kA wave 8/20,� nominal discharge current In> = 15 kA wave 8/20,� protection level Up <= 1.5 kV.

These lightning arrestors shall be installed at the cable point of entry in the buildings in key-locked boxes integrating the lightning arrestor and protection system, if applicable. The earthlinks shall be as short as possible and directly connected to the earth of the electrical boxes,interconnected with the ground ring.

10.5. Building electrical power supply The estimated energy budget is 30kW to supply auxiliary systems: lighting, socket outlets,special low power supply, etc. To meet this requirement, the power supply shall be providedfrom the solid booster storage box (no. 198.05.01 - drawing no. 198.ED.1739.7000) and will beconnected to a distribution panel, passing by the lightning arrestors. The power supply shall be with RGPFV copper cable or similar, minimum cross-section 25 mm²,laid buried between the two buildings.

10.6. Solid booster storage box A protection system, all poles protected, minimum rating 63A and appropriate EMC,substantiated by design documents shall be installed in this box. The contractor of this work package shall update the drawings corresponding to this box.

Page 100: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 100/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

10.7. Distribution panel The distribution panel installed in this building shall be of a modular type, protection index IP 55and impact index IK 07, with front panels and door fitted with key locks, size defined accordingto the equipment to install in the panel, and taking into account a 30% useful spare space. Panels and circuit breakers shall be identified with engraved labels riveted to front panels, incompliance with CNES technical specification(s). All conductors, switchgear and control gear,etc. inside the panel shall be identified according to CNES technical specification(s). Cables shall be identified with label holders, marked in letters and numbers, attached to cablesas per CNES technical specification(s).

The panel shall comprise:� connection lands or similar, according to wiring + screen for connection of the power

supply cable.� a circuit breaker, all poles protected, for the emergency cutoff circuit and power off

indicator lights and power on indicator lights at emergency cutoff level, power supplyupline from general cutoff and orange wiring, identification of general open poweredequipment,

� one general cutoff fitted with OF contact and transmission coil,� one terminal block downline from the general cutoff, nominal current adapted to head

protection,� one protection circuit breaker for the winch power supply,� the circuit breakers, all poles protected, for protection of lighting power lines, principle

as follows:

� for the building: 2 circuit breakers at least with downline start-up devicescontrolled by switches,

� for building external lighting: 1 circuit breaker at least and another circuitbreaker for control, with downline:� 1 24-hour programmable switch and quartz clock,� 1 3-position switch: manual, automatic and stop,� contactors controlled by the programmable switch and 3-position switch,

� for platform lighting: 1 circuit breaker distributing lighting fittings to severalphases with the start-up device downline controlled by a switch.

� the safety lighting remote control box,� the 2x16A 0.03A differential circuit breaker for 2P+T 10/16A power socket circuit

protection,� the 4x20A 0.03A differential circuit breaker for 4P+T 20A power socket circuit

protection,� lighting controls on the side of the cabinet,� the socket outlet 2P+T and the socket outlet 4P+T on the side of the cabinet,

Page 101: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 101/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� the circuit connection terminal boards, identified. The contractor of this work package shall provide design documents to justify the characteristicsof the protection devices.

10.8. Emergency cutoff Two emergency cutoff devices, easily accessed for the entire system of the building, shall beinstalled:

� one at the distribution panel,� one at the back of the building.

These devices shall be powered with 230 V tapped upline from the general cutoff and shall befitted with power on indicator lights (green) and power off indicator lights (red). These colorsshall operate by voltage transmission on general cutout of the distribution panel above. Links between the distribution panel and the emergency cutoff devices shall be made of 7G1.5channel. Buttons and indicators shall be installed in glass panel boxes, color red, appropriately identified,with protection index IP 55 and impact index IK 07 at least.

10.9. Equipment

10.9.1. Interior normal lighting

Normal lighting shall be provided by sealed fluorescent fittings, protection index IP 55 andimpact index IK 07, fitted with 40 or 60 watt bulbs. The selected lighting level is:

� 300 lux at the back of building, over a 6-meter long area from the back,� 200 lux elsewhere.

Control is in compliance with the description given for the distribution panel.

10.9.2. Surrounding area external lighting

The external lighting shall be provided by low-consumption (9 watts) fluo-compact bulbapparatus, sealed type, protection index IP 55 and impact index IK 07. A light fitting shall be installed on each side of the building entrance. The light on thedistribution panel side shall give access to the lighting controls. Control is in compliance with the description given for the distribution panel.

10.9.3. Platform external lighting

Around the edge of the building roof, spotlights shall be installed, minimum 2, metal iodide lampor similar to light the platform. The selected lighting level is 120 lux over a 20 m radius from the building entrance. Control is in compliance with the description given for the distribution panel.

Page 102: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 102/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

10.9.4. Common characteristics for lighting apparatus

All fluo-compact bulbs and fluorescent apparatus shall have an electronic starter and shall takeinto account:

� the service life,� the efficiency,� the best light flow/consumption ratio.

Halogen type lights are not accepted.

10.10. Safety lighting Safety lighting shall be provided by a floodlight unit, 1200 lumens minimum, installed at theentrance to the building and centered to the rear of the cladding. The light shall comply withstandards 71800, 71820 and EN 60598, non-permanent type, range 1 hour and remote controlfrom box installed in the sub-distribution panel.

Page 103: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 103/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

11. VEGA OFFICES: KEPLER AND BESSEL BUILDINGS

11.1. ForewordVEGA offices are installed in the Bessel and Kepler buildings, currently occupied byARIANESPACE personnel ( Ariane 4 ).The offices shall be located on the ground floor of the 2 buildings and works concern the followingrooms:

� Bessel: room 03 to room 27, except for 09, 12 and 13,� Kepler: room 01 to room 23,

11.2. Existing condition The various existing electrical networks are as follows: category 1, category 2, category 3 (thelast category partially in offices). The existing systems comprise:

� the normal lighting network,� the safety lighting network,� the high power network,� the category 2 power socket network.

However, to ensure durability of the system, it is necessary to update the following systems:� normal lighting: replacement of light fittings,� safety lighting: replacement of independent units,� socket outlets: installation of differential protection systems,

Works required are described in the paragraphs below.

11.3. Normal lighting Generally speaking, lighting units installed are in poor condition and are obsolete. They shall bereplaced in rooms listed in the foreword paragraph, except in rooms 02 and 03.

11.3.1. Characteristics

Lighting fittings to be installed and to replace the existing fittings shall incorporate the followingcharacteristics:

� offices: built-in fluorescent type, low luminance,� corridors: built-in fluorescent type or mosaic reflector type,� meeting rooms: built-in fluorescent type or mosaic reflector type,� technical rooms: sealed fluorescent lights, protection index IP 55 and impact index IK

07,

Page 104: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 104/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� sanitary facilities: fluo-compact bulbs, low-consumption. Lighting apparatus and related bulbs shall take into account:

� the service life,� the efficiency,� the best light flow/consumption ratio.

Fluorescent type fittings shall be fitted with 20 or 40 watt tubes. All fluo-compact bulbs and fluorescent fittings shall be fitted with electronic starters. Halogen-type lights are not accepted.

11.3.2. Lighting levels

The selected lighting level is:� 300 lux minimum for offices,� 120 lux minimum for sanitary facilities and circulations� 200 lux minimum for technical rooms

11.4. Safety lighting Generally speaking, independent units and portable safety lighting units do not operate. Theyshall be replaced by apparatus installed instead of the existing apparatus in the rooms listed inthe foreword. 45 lumen independent units shall comply with standards 71800, 71820 and EN 60598, nonpermanent type C, range 1 hour and remote control from box located in each sub-distributionpanel of the 2 buildings. Portable units shall be of the halogen type. Connection shall be to existing socket outlets. Also, remote control units in distribution panel shall be replaced. Quantity approximately 3 or 4,to verify on the site.

11.5. Category I and II socket outlets Category I and 2 socket outlets are assumed sufficient and it is not scheduled to installadditional sockets. As part of office reallocation requirements, differential devices shall be installed on the existingsocket outlet network. These devices shall be installed in the category 1 and 2 distributionpanel according to the paragraph below.

Page 105: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 105/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

11.6. Category 1 and 2 distribution panel The distribution panels concerned by the installation of differential devices are as follows:

� Bessel: category 2 no. 194-16-20 ( Drawing no. 194.ED.1739.0543 ).� Kepler: category 2 no. 195-13-20 (Drawing no. 195.ED.1739.0540 ),

In these panels, on the socket outlet circuits, the existing protection devices (single-phase+neutral fuse or three-phase+neutral fuse) shall be replaced by 30 mA differential circuitbreakers, all poles protected, with the following characteristics:

� 2x16 A for each 2P+T 10/16A socket outlet circuit,� 4x20 A for each 4P+T 20A socket outlet circuit,� 4x16 A for each electric sheath circuit supplying sockets in offices,with appropriate breaking capacity and electromagnetic compatibility and substantiatedby design documents.

As there is no space in existing distribution panels to accommodate the differential circuitbreakers, another panel of a size similar to the existing panel will be installed closeby, i.e. forthe building:

� Bessel: 2100x750x450 mm on base, to verify on site.� Kepler: 1200x800x300 mm, to verify on site,

Panels shall be installed so as to return the cables of circuits involved to the new distributionpanels for connection to terminal boards. If circuits cannot be returned to the new panels, asheath will be installed between the existing panel and the new panel to route the links,downline from circuits breakers, to the terminal boards in the existing panel. Added distribution panels shall be of the modular type, protection index IP 55 and IK 07, withfront panels + door fitted with key locks, minimum size defined according to data above, takinginto account the equipment to be installed and a 30% useful spare space. Identification of panels, same as existing equipment, and circuit breakers, shall be by means ofengraved labels riveted to supports according to CNES technical specification(s). Allconductors, switch gear and control gear, etc. inside the panel, shall be identified according toCNES technical specification(s). Wires and cables shall be identified with label holders marked in letters and numbers, attachedto cables according to CNES technical specification(s). Each new panel shall include:

� a set of busbars, nominal minimum current 250A, adapted to head protection, directlypowered from a set of busbars, downline from the general switch of the existingpanel,

� the differential circuit breakers of the circuits involved and listed above,� the connection terminal boards of the circuits involved and identified.

All cable inlets shall be by means of packing glands, size adapted to cables.

Page 106: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 106/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

In existing panels, the following is necessary:� elimination of the protection devices of socket outlet circuits involved,� blanking of unused packing glands,� incorporation of modifications required as part of the extension to these panels

defined above (may not be exhaustive). The contractor of this work package shall update existing drawings and mark any added panels.

11.7. Category 3 systems In Bessel and Kepler buildings, the category 3 socket outlet network does not exist, except inroom 03 of the Kepler building. Consequently, for the ground floor of each building, the following will be created:

� a socket outlet distribution network for office category 3,� a distribution panel to supply the socket outlet network.

The existing system in room 03 of the Kepler building shall be removed.

11.7.1. Power supply of category 3 systems

The category 3 socket outlet distribution panels of the ground floor in Bessel and Képlerbuildings shall be supplied from the category IIIC TGBT no. 193 04 30C by creating a supply foreach panel. Power supplies shall be made with RO2V cables, minimum cross-section 5G16mm², laid on existing cable trays, with attachment of 29mm² minimum cross-section cable to theflange edge. All holes needed shall be part of the services of the contractor of this workpackage.

11.7.2. Existing low-voltage main distribution panel no. 193 04 30C

For each TD in the existing TGBT, a circuit breaker, minimum rating 4x40A, with appropriateEMC and breaking capacity, justified by design documents, shall be installed. These circuitbreakers shall be fitted with OF and SD contacts, which will be wired in series in two separatechains and returned to disconnectable terminal boards. Transfer to the centralization box onthe operational UPS room (basement of CDL2) shall be by a 5G1.5 cross-section linking cable.The contractor of the work package shall meet with the department involved (Design Office orother) for connection to the centralization unit and for any adaptation required between the boxand the rack. Allocations or impacts to CCS are not the responsibility of the contractor of thiswork package.

As selectivity on existing category 3 distribution is not incorporated, it is not requested for theseworks. However, if the operator requires selectivity, it can only be made on ground floorsystems and will only be very partial.

Page 107: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 107/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

11.7.3. Ground floor distribution panels

A distribution panel shall be created to supply the category III socket outlets of the offices on theground floor of each building. They shall be powered individually from the category IIIC TGBTaccording to the category 3 system power supply chapter. They shall be installed in thefollowing electric rooms:

� Bessel: room no.16,� Kepler: room no. 13.

These panels, sized according to the equipment to be installed, with a 30% useful spare space,protection index IP 55 and impact index IK 07 minimum, shall be of the modular type with frontpanels and transparent door fitted with a key lock ( RONIS 3113A), a magnetic type contactinserted in the existing OF chain as well as a lead sealing device. The emergency cutoff will operate on the general cutoff of each TD via the transmission device. Each panel shall include:

� connection lands or similar depending on wiring, + screen for connection of powersupply cable,

� a circuit breaker, all poles protected, for the emergency cutoff circuit and power offindicator lights and power on indicator lights at emergency cutoff level, power supplyupline from the general cutoff and orange wiring, identification of general openpowered equipment,

� 1 general switch 4X63A fitted with an OF contact and a transmission coil,� 1 multiclip type terminal block, 100A minimum,� 1 terminal block power on white indicator light, protected by a circuit breaker with

appropriate breaking capacity and rated 2x6A,� circuit breakers with SD, all poles protected, protection of socket outlet power lines,

with as principle:

� 1 30 mA differential circuit breaker for a dual office,

� 1 30 mA differential circuit breaker for 2 single offices,

� 1 30 mA differential circuit breaker for each conference room,

� circuit connection terminal boards, identified. SD contacts shall be wired in series and returned to disconnectable terminals. Transfer to thecentralization box in the operational UPS rooms (basement of CDL2) shall be by a 5G1.5 cross-section linking cable. The contractor of the work package shall meet with the departmentinvolved (Design Office or other) for connection to the centralization unit and for any adaptationrequired between the box and the rack. Allocations or impacts to CCS are not the responsibilityof the contractor of this work package. Packing glands shall be scheduled at cable crossings. Panels shall be connected to earth terminal blocks in electrical rooms.

Page 108: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 108/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

11.7.4. Installation of socket outlets

Socket outlets are of the standardized type and adapted to the rooms where installed by theirmethod of installation and composition. 230V 2P+T 10/16A socket outlets shall be provided with foolproof devices. These socketoutlets shall be installed on channels and supplied via the channels. Channels shall be installed very carefully:

� cut carefully,� use of all joining accessories,� attachment by gluing and screwing,� etc.

Socket outlets shall be installed as below:� Single office: 2 PC 2P+E 10/16 A with foolproof device, category 3, on channel� Double office: 4 PC 2P+E 10/16 A with foolproof device, category 3, on channel� Conference room: 4 PC 2P+E 10/16 A with foolproof device, category 3, on channel

11.8. Emergency cutoff Existing electrical systems on the ground floor of Bessel and Kepler buildings are not fitted withemergency cutoff devices. As part of upgrading of electrical systems, these emergency cutoffdevices shall be installed in all electrical systems (categories 1, 2 and 3) of the ground floor ofeach building.

11.8.1. Description

These cutoff devices shall be of the transmission type and will actuate opening of the generalswitch of the distribution panels:

� Bessel: no. 195 13 20 for categories 1 and 2+ category 3,� Kepler: no. 194 16 20 for categories 1 and 2+ category 3.

An emergency cutoff shall be installed in the corridor of each building close to the entry to theelectrical room. For information purposes, the distribution panel for category 3 no. 195 03 30C shall beremoved. This action shall be performed by a 2-contact emergency stop pushbutton: one for category IIvoltage and the other for category III voltage, fitted with power on and power off indicator lightsfor both categories Emergency cutoff indicator lights on boxes shall be of the following color:

� green: power on indicator light, powered by the closing contact of the general cutoffinvolved

� red: power off indicator light, powered by the opening contact of the general cutoffinvolved.

Page 109: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 109/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

In emergency stop boxes, the various power supplies shall be correctly identified andinformation shall be available to indicate the presence of the two sources. Emergency cutoff shall be fitted with a mechanical locking button protected against untimelyaction to prevent any unwanted triggering. Buttons and indicator lights shall be located in boxes with glass panels, color red, and correctlyidentified. Emergency stop pushbuttons shall be correctly wired as indicated above and according to thedescription given in paragraphs on TDs, categories I, II and III.

11.8.2. Modifications in category 1 and 2 TDs

The distribution panels (TD) involved in modifications to make the emergency cutoff for category1 and 2 systems are:

� Bessel: no. 195 13 20,� Kepler: no. 194 16 20.

Modifications concern the general switch, the control of this switch by the emergency cutoff andthe updating of drawings. General switch of panels listed above: The current general switch cannot be used for emergency cutoff by transmission. It will bereplaced by an appropriate rated device, minimum 250 amperes, fitted with:

� a transmission coil,� OF contact,� control operating lever, outside the casing.

TD general switch control The emergency cutoff will act on the general cutoff of each TD by means of a transmissiondevice. In each existing panel, it is necessary to add:

� a circuit breaker, all poles protected, for the emergency cutoff circuit and power offindicator lights and power on indicator lights at emergency cutoff level, power supplyupline from general cutoff and orange wiring, identification of general open poweredequipment,

� terminal boards for connection of emergency cutoff circuits, identified. Drawings The contractor of this work package shall update existing drawings.

11.9. Control office report

Regulatory upgrading shall be made on the ground floor of the two buildings. For this purpose,works shall be carried out according to the remarks made by the APAVE control office, whichcarries out routine inspections of the electrical systems in these two buildings.

Page 110: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 110/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The remarks of the control office are to be taken into account:

BESSEL:

� Updating of drawings and diagrams,

� Panel 194.16.20: installation of a packing gland for routing of the earth cable

� Box 194.07.20 ( room 07 ): replacement of a packing gland, broken / Installation of anemergency shutdown device.

� Room 10: Replacement of workbench sockets which are damaged / Attachment of socketoutlets

� Room 11: on the air-conditioning fan, it is necessary to ensure the sealing of the cableentry / Identification of cables supplying the motors

KEPLER

� Ground floor cabinet 195-13-20: replacement of packing glands which are broken

� TD 195.03.01-Cafeteria: correct insulation which is insufficient in some circuits /replacement of differential switches QM1 and QM2 / Replacement of QF11 protectionwhich is overrated / Replacement of outgoing fuses FU9

� Cafeteria suction hood box: wiring of the hood according to good works practice

� Cafeteria: connect the ice cube machine to the protection circuit / Blank opening in front ofCAPIC oven / Blank opening in front of refrigerated cabinet ZANUSSI / Replace flexiblelines of heating plate MATIC

� Office 10: correctly attach a socket

� Room 17B: Connect some socket outlets of the room power supply to the protection circuit

11.10. Electric drawings and diagrams

All electric drawings and diagrams existing for KEPLER and BESSEL buildings shall be recordedunder a reproducible computer medium (Autocad, electric diagram software). A complete updateshall be made.

Page 111: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 111/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

12. INTERFACES AND MAINTENANCE

12.1. Interfaces Interfaces with site units (CSG, ….) shall be identified on the site, estimated and included in thecall for tender file.

12.2. Maintenance The contractor of this work package shall provide the following in his services:

� maintenance of systems up to final acceptance of systems,� prepare and estimate the list of spare parts recommended and essential.

Furthermore, between the "IAR" and the "GSORR", the contractor of this work package shallmaintain systems he implements. During this period of time, the contractor shall also provide a24 hour maintenance service for this site and the rear base.

Page 112: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 112/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

13. OPTION 1: LAUNCHER LIGHTNING PROTECTION

Depending on the launcher lightning protection data and the induced or electromagnetic fields,which will be established by launcher development, the launcher lightning protection systemmay be reviewed and provided by a device other than the gantry. Currently, the protection system developed by ONERA on the ARIANE 5 base site comprises 4pylons with a wire stretched over the top and remote discharge of lightning current. Consequently, this system is an option and shall be designed and estimated as part of thisdescription. As part of this option 1, an additional option 1’ is requested.

13.1. Protection level As there is no permissible "lightning current" data for the launcher and for the induced orelectromagnetic field, the permissible " lightning current " of 5kA shall be taken into account forthe launcher. This "lightning current" value protects the launcher against lightning strikes of anintensity greater than 5 kA in 95% of cases according to worldwide statistics. The upper limit ofthe intensity of lightning strikes for which the launcher is protected is 200 kA (i.e. 1% of casesaccording to statistics). For an intensity greater than or equal to 5 kA, the striking distance defined according to theformula in NFC 17100: D=10x(I�2/3) is 29 meters, which is also the radius of the artificialsphere.

13.2. Principle To obtain the protection level defined above, the protection system associates two principles:

� the principle of the artificial sphere consisting in protecting the structure by aconducting cage of which the grid depends on the minimum intensity of the lightningto avoid, i.e. 58 m. This principle does not provide protection against nearby effects,

� the principle consists in discharging the lightning current to the ground by asymmetrical system.

The system based on the two principles provides a device:� for capture by stretched wires and rods installed on pylons,� discharging lightning strikes symmetrically to decrease induced or electromagnetic

fields at the launcher,� providing protection against direct high-intensity strikes, greater than 5 kA, without an

electromagnetic field induced in the system,� capable of collecting low intensity lightning currents, greater than 5kA, by pylons,� option 1’: capture by stretched wires and rods installed on isolating masts to obtain

remote discharge of lightning current. The entire set-up is supported by pylons.

Page 113: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 113/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

13.3. Description of the system Pylons are not part of the supply provided by the contractor of this work package. Forinformation, they shall be made of metal, height 80.5 meters approx. according to the study.However, the contractor of this work package shall provide the lightning current discharge earthconnection for pylons according to the description "earth discharge devices". The system comprises:

� the capture rods, height 5.7 meters, Franklin type,� the capture device by stretched wire(s), Almélec type, section 228 mm², covering the

4 sides (several wires if confirmed by the study),� anchoring of the four down conductors outside the bunker,� the radial system for pylons and discharges,� lightning counters with signal transfer on two diametrically opposite down conductors

according to the lightning counter description below,� posting of instructions close to the lightning protection system,� option 1’: isolating tube masts made of reinforced resin, height 12.5 meters,

diameter 0.9 m, with ladder (free clearance 0.65 m) to take into account theinstallation of discharge cables, capture rods, maintenance, etc.

� option 1’: symmetrical discharge of 4 down conductors separated by 100 metersfrom Almélec type pylon, section 228 mm².

Study and estimate for option 1’ shall be separate from option 1.

Technical specifications:� ST1: normal wind, speed 24 meters/second according to wind and snow rules,� ST2: maximum wind for launching: 23 meters/second, independent from height,� ST3: related to direct blast on the mast: launcher at 370 (AC) meters height: dynamic

pressure of blast assimilated to a 80 m/s wind (AC) according to direction inclined by° in relation to vertical, section involved, entire mast,

� ST4: related to direct blast on cable: ditto ST3 except for section involved, to take intoaccount: 20 meters horizontal projection with two cables covering the mast involved.

Possible at the same time:S1 = ST2 + ST3,S2 = ST2 + ST4,S3 = ST2 + ST3 + ST4.

Page 114: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 114/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

� acoustic environment: this environment is described for launcher in document AD,the contractor shall take into account a propagation of the sound in free field to thestructures; the contractor shall take into account a frequency excitation of Hz due tothe launcher; structure fatigue shall concern the following duration 10 seconds x 5launchings per year x 20 years = 1000 seconds.

� chemical environment created by launchings: characteristics of gases are given indocument AD.

� total absence of metal guys participating in pylon resistance,� rupture of one or more capture wires shall not affect the resistance of supports

(dielectric and metal parts) and the dielectric characteristics of the isolating part,� service life of the structure 20 years with as a principle no maintenance required

during the first 4 years. Electric specifications: The basic principle of the protection system is based on total electrical separation between theprotection system and the structure. Consequently, the installation of equipment such asfollows on pylons: aircraft beacon, air speed indicator, branch lines, lighting floodlights,cameras, etc…. is prohibited. Option 1’: dielectric specifications The particular specifications of isolating masts are as follows:

� total insensitivity to UV radiation, chemical and thermal aggression (10 yearguarantee),

� total absence of water retention on surface and formation of mold,� high dielectric strength, greater than 5.10-13 ohm/cm².cm,� force by rung 600 daN,� perpendicular tolerance in relation to centerline: angle of 0.043°C.

Isolating masts may be coated with Polytetrafluoroethylene (PTFE) but no painting or primercoats. To increase the UV resistance, the masts shall be tinted during manufacture ifnecessary. Personnel safety specification: For the entire structure consisting of the lightning protection device according to NFC17100, thepassageway for personnel to the protection device shall be controlled and posted informationshall inform the personnel. In all cases, the system must only be approached when there is noforecast lightning. Lightning arrestor earth connection specifications: Refer to paragraph dealing with the earth discharge devices.

Page 115: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 115/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

Study complementary specification: Studies related to protection system against direct lightning strikes shall be modeled to

� confirm the location and effective geometry of the protection system to make:

� real height of metal pylons, insulating masts, capture rods for lightning current,

� distance between pylons,

� angular position of down cables, distance between pylons and earthconnections,

� calculate the value of the field within the system.These studies shall be validated or performed by an organization (such as ONERA), withgood knowledge on the problems related to lightning protection and to electromagnetic fieldsin space domain and space base systems at KOUROU.

Control complementary specification: On completion of works, the verification shall be completed with « MESA » type measurements(system developed by ONERA and APAVE).

13.4. Down conductors Pylons are all-metal structures and shall be used as down conductors and side capture devices.

13.5. Earth discharge devices Each electric current discharge down conductor shall be connected to an earth connectionconsisting in 30x2 tinned copper strips laid in a radial pattern, buried at 50 cm depth minimum,size 8 m minimum per radial for the launcher lightning protection system, located 1 meter fromthe base of pylons and remote down conductor anchoring systems, Each lightning arrestor earth connection of the pylons and remote anchoring system shall beconnected to:

� the ground ring for bunkers by a 30x2 mm cross-section tinned copper strip,� one in relation to the other by making up a ground ring type network made of 120

mm² minimum cross-section bare copper conductors. These earth networks shall beinterconnected to the bunker ground ring and to all conductors in the perimeter ofthese networks (fluid piping, all categories, etc.).

A disconnection device shall be located at each radial and downline from the interconnectionwith the ground ring. The resistance of each lightning arrestor earth connection shall be less than 10 ohms( measurement made before interconnection with the ground ring ).

13.6. Lightning counters Lightning counters scheduled for the system defined in the base description shall be installed ontwo diametrically opposite down conductors.

Page 116: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 116/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

13.7. Common provisions Special care shall be paid to prevent electrolytic couples and/or galvanic couples with differentmaterials. If necessary, paint shall be applied to galvanized steel as per SGS 436. The 30x2 mm flat bar shall not be drilled. Connection devices or assembly devices by means ofsilver soldering shall be used or special couplings of the screwed type. At all construction levels, to facilitate discharge of lightning current, the angles and radiuses ofcurves made by the flat bar must comply with the provisions of the documents mentioned in thisCCTP.

Page 117: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 117/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

14. OPTION 2: TVC RACK COMPLEMENTARY UPS

As an option, the power supply of a new TVC rack shall be estimated. For this new rack,category III production shall be provided by a new UPS complying with the followingcharacteristics:

� Category III rack 270V, 250A: power 100 kVA, service voltage 230/410 volts,frequency 50 hertz, neutral point treatment TNS.

Category III production shall be obtained:� by an UPS at separate power supply networks 1 and 2.

Description of the UPS

The characteristics of the UPS are defined in the base description (UPS descriptionparagraph).However, the reverser type switch for the charger unit shall be key-locked so that there is onlyone reverser set on the charger. Refer to paragraph on charger boxes in the basicdescription.

UPS links

As per the basic description.

Batteries

Description

As per the basic description

Installation

As per the basic description

Transport

As per the basic description

Electric protection in the panel

In the TGBT panel for the category III rack 270 V 250A of the basic description, the followingdescription devices shall be added:

� fixed or mobile UPS use selection circuit breaker, fitted with OF+SD contacts, used toprovide protection for the link to the rack with RVFV cable, minimum cross-section5G35mm²

� a circuit breaker, all poles protected, 2X10A with curve and breaking capacityadapted for the power on indicator light circuit,

Page 118: PARTICULAR SPECIFICATIONS ENERGYemits.sso.esa.int/emits-doc/ESRIN/AO4401En-VGST2C0007-10... · standard NFC 15100 related to the design, construction, and maintenance of low-voltage

VG ST 2 C 0007-10A_eng.doc Version validée SDS Imprimé le 16 / 04 / 03

CENTRE NATIONAL D'ETUDES SPATIALES

Titre du document:PARTICULAR SPECIFICATIONS

ENERGY

Sous-direction Développements Sol

VG-ST-2-C-0007-CNES

Page: 118/118 Ed.: 1 Rév.: 0 Date: 14/02/2003

The outgoing shall be directly connected to the circuit breaker terminals, the neutral conductorand the earth conductor shall be separate, TNS diagram.The link between the UPS, the TGBT and the rack shall be with RVFV cable, appropriatecross-section and at least 5G35 mm².

All cable inlets shall be by means of packing glands of an appropriate size. SD and OF contacts shall be wired in series in two distinct chains and shall be routed back todisconnectable terminals, for wiring according to the signal transfer paragraph.


Recommended