+ All Categories
Home > Documents > Patton AU PAC Air Cooled Condensers

Patton AU PAC Air Cooled Condensers

Date post: 18-Mar-2016
Category:
Upload: patton-ltd
View: 228 times
Download: 2 times
Share this document with a friend
Description:
Patton high efficiency air-cooled condensers.
4
Air Cooled Condensers PAC Air Cooled Condensers www.pattonau.com
Transcript
Page 1: Patton AU PAC Air Cooled Condensers

Air Cooled Condensers

PAC Air Cooled Condensers

www.pattonau.com

Page 2: Patton AU PAC Air Cooled Condensers

Air CooledCondensers

PAC60 240 2400 3600 237 2370 3450 58 45

PAC75 280 2800 4200 276 2760 4140 60 49

PAC100 390 3900 5850 385 3850 5775 62 51

PAC125 510 5100 7650 504 5040 7560 64 53

PAC150 570 5700 8550 564 5640 8460 65 55

dbA @ dbA @

1KTD 10KTD 15KTD 1KTD 10KTD 15KTD 3m 10m

R404A R134aSOUND LEVEL (1)

MODEL

PAC Low Line

PA

C

3.6 8.5 kW(15KTD)

n Highly efficient external rotor fan

motors give optimum performance

with low noise levels

n Multiple fans (on all except smallest

models) for flexibility of head

pressure control

n Condensers supplied with “Patton

Coat” fin and coil protective coating

www.pattonau.com

CAPACITY THR (Watts)

Page 3: Patton AU PAC Air Cooled Condensers

MODEL

FANS MOTORS (2) COIL

DIA(mm)

TOT. Air Vol

l/sec

Weight (dry) kg

TOT. AMPS

No.OFF

F.P.ITOT. Watts

ROWSCoil Vol.

(dm3)

Std. Connections mm F. Sw

OUTLETINLET

PAC60 1 300 490 0.40 80 9 3 1 x 9.52 1 x 9.52 1.00 8

PAC75 1 300 450 0.40 80 9 4 1 x 9.52 1 x 9.52 1.34 9

PAC100 2 300 1100 0.80 160 9 2 1 x 9.52 1 x 9.52 1.35 13

PAC125 2 300 1030 0.80 160 9 3 1 x 12.7 1 x 9.52 2.00 15

PAC150 2 300 950 0.80 160 9 4 1 x 12.7 1 x 9.52 2.70 17

NTS (mm)

NOTES:

1. Sound level data “free field” in accordance with ISO3741 to be used as a guide only

Add 15db to “Sound pressure levels” @ 3 mtrs listed to obtain approx “Sound power levels” in db above 10-12 watts

2. All motors 220-240/1/50

3. Refrigerant capacity correction factors relative to R404A Multiply capacities by the following: R22 R407C R410A R407F 1.01 0.95 1.02 0.95

4. Altitude correction factors Multiply capacities by the following: Altitude (m) 500 1000 1500 2000 2500 Factor 0.96 0.92 0.87 0.83 0.78

www.pattonau.com

The

com

pany

rese

rves

the

right

to m

ake

spec

ifica

tion

chan

ges

with

out n

otic

e. 1

8/03

/14

DIMENSIONS

TECHNICAL DATA

Page 4: Patton AU PAC Air Cooled Condensers

The company reserves the right to make specification changes without notice. 18/04/14

www.pattonau.com


Recommended